NEMA Pump Controls - Viking Electric Supply

www.usa.siemens.com/controls
NEMA Pump Controls
Class 82 slim line NEMA pump controller for the agricultural industry
Answers for industry.
Class 82 Slim Line
NEMA Pump Controller
Typical applications include:
•Crop irrigation
•Sprinklers, misters and soakers
•Watering for livestock and other dairy applications
•Ground dewatering for excavation and construction sites
Siemens introduces its new Class 82 slim line NEMA Pump
Panel. This newest addition to the already extensive line of
Siemens pump panels was designed specifically for the
agricultural market. It is well suited for irrigation and similar
pumping applications and is built to withstand the harsh
elements of the outdoors.
Why you should use the Class 82 Pump Panel
• Simplicity and its compact lightweight design makes this an attractive solution to your budgeting challenges.
• The contactor is NEMA rated to provide reliable motor
control and protection expected in the most demanding applications.
• The ESP200 solid-state overload relay has a protective
coating on the circuit board which gives it superior
protection against high humidity, condensation and
corrosive environments.
• Its size and weight is about half that of the Class 87 which increases the ease of installation.
Product Selection
Max Hp
Rating
Motor
Voltage
Catalog Number
Overload
Relay
Amp
Range
Disc.
Amp
Rating
Fuse Clip
Amp/Volts
HOA Only
HOA & Start
Push Button
230
460
NEMA
Size
—
1
1
0.75–3.4
30
30A/600V
82ADB4FBH
82ADB6FBH
—
5
1
3–12
30
30A/600V
82ADC4FBH
82ADC6FBH
—
10
1
5.5–22
30
30A/600V
82ADD4FBH
82ADD6FBH
2
—
1
3–12
30
30A/250V
82ADC4FAG
82ADC6FAG
3
—
1
5.5–22
30
30A/250V
82ADD4FAG
82ADD6FAG
7 1/2
—
1
10–40
30
30A/250V
82ADE4FAG
82ADE6FAG
Accessories
Image
Description
3/4" Type 3R Conduit Hub
Part Number
ECHS075
1" Type 3R Conduit Hub
ECHS100
1 1/4" Type 3R Conduit Hub
ECHS125
1 1/2" Type 3R Conduit Hub
ECHS150
Disconnect Switch Auxiliary Contacts 2 NO/2 NC
DPDT (NEMA A600)
HA261234
Fuse Puller Kit For 30A Switch (1 kit required per
switch)
HP61
30A, 240V Class R Fuse Clip Kits
HR21
30A, 600V Class R Fuse Clip Kits
HR612
Contactor Auxiliary Contacts, Side Mounted 1 NO/NC
3RH29111DA11
(NEMA A300/Q300)
2
ESP200 Tamper Resistance Cover
49ASTC1
Start Push Button With Contact Block
52PA8A1K
Start Legend Plate
52NL03
Features and Benefits
D
C
A Compact and light-weight NEMA type 3/3R enclosure for ease of installation. Fabricated with galvanized steel
versus conventional cold rolled steel for superior corrosion resistance.
B Two lockable latches to tightly seal door.
C Drip shield to help prevent water entry.
D Pole straps at top and bottom of enclosure for easy
E
mounting on poles or flat surfaces using keyhole slots.
E Rugged metal handle with lock-out provision for durability.
A
B
9.5”
Class 87
22”
24”
-60%
20”
3
Features and Benefits
H
G
F Metal 30 mm H-O-A switch and Start push button are water and dust tight.
G Full gasketed door to ensure a dust tight and water tight seal.
J
H Pre-punched opening with cover plate for convenient field installation of a conduit hub should top entry be required.
I Multiple conduit knockouts for convenient field installation of conduit should bottom entry be required.
K
J Heavy-duty disconnect switch with line-side shield and visible blades for safety and double break switch action to reduce arcing and increase lifetime.
L
K NEMA rated contactor to provide reliable motor control and protection expected in the most demanding applications.
L ESP200 solid-state overload relay with
protective coating on circuit board which gives it superior protection against high humidity, condensation and corrosive environments.
F
M
N
M 3-point terminal strips, as standard, for convenient field connections
N 3-point ground lug.
4
I
Nomenclature
82
A
D
C
4
F
B
H
Series
Starter Size
D=1
OLR Current Range
B = 0.75 - 3.4A
C = 3 - 12A
D = 5.5 - 22A
E = 10 - 40A
Cover Control
4 = HOA selector switch only
6 = HOA selector switch with Start push button
Disconnect Type
F = Fusible Disconnect
Disconnect & Fuse Clip Rating
A = 30A/250V
B = 30A/600V
Coil Voltage
G = 220VAC 50Hz / 240VAC 60Hz
H = 480VAC 60Hz
5
Technical Data
General Technical Data:
Weight
Height x Width x Depth
Maximum altitude
Ambient (outside enclosure) storage temperature
Ambient (outside enclosure) operating temperature
Country of origin
23 lb.
26 x 12 x 5 in.
6560 ft.
(-30 to 65)°C / (-22 to 149)°F
(-20 to 40)°C / (-4 to 104)°F
USA
Horsepower Rating:
82ADB*FBH 1Hp@460VAC (NEMA size 1)
82ADC*FBH 5Hp@460VAC (NEMA size 1)
82ADD*FBH 10Hp@460VAC (NEMA size 1)
82ADC*FAG 2Hp@230VAC (NEMA size 1)
82ADD*FAG 3Hp@230VAC (NEMA size 1)
82ADE*FAG 7 1/2Hp@230VAC (NEMA size 1)
Contactor:
Number of NO main contacts
Amp rating
Mechanical operating cycles
3
32A
10,000,000
Internal / Standard Auxiliary Contact
Number of NC / NO auxiliary contacts
NEMA contact rating designation
Optional auxiliary contacts available
1NC / 1NO
A600 AC / Q600 DC
Yes
Coil:
Voltage
Apparent pull-in / holding power
Normal coil operating limits (% of rated voltage)
Pick-up time / Drop-out time
220/230 V 50/60 Hz or 460 V 60Hz
81 VA / 10.5 VA
80% - 110% at 60Hz
8-40 / 4-16 msec
Overload Relay:
Current range
Trip Class
Trip detection
Phase failure sensitivity
Repeat accuracy
Reset options
External reset
Test function
Conformal coating on printed circuit board
Number of NC / NO auxiliary contacts
Rating of auxiliary contacts
Single contact isolation
Dual contact isolation
0.75 - 3.4 or 3 - 12 or 5.5 - 22 or 10 - 40 Amps
Class 5 / 10 / 20 (factory set) / 10
Overload, phase failure, phase unbalance, ground fault
Trip time after phase loss: < 3 sec
Within 1%
Manual, automatic and remote
Yes
Electronics and manual actuation
Yes
1NC /1NO
B600 AC / R300 DC
600 V
300 V differing polarity / 600 V common polarity
Disconnect Switch:
Rating
Fuse type accepted
30 A with 30A/600 or 30A/250 V Class H fuse clips
Class H, J or R
Enclosure:
Type
Rating
NEMA Type 3/3R enclosure
Weather proof for outdoor use
Standard Control Devices:
Hand-Off-Auto selector switch (both 4 & 6 cover control)
Start push button (6 cover control only)
30mm metal housing with chrome finish
30mm metal housing with chrome finish
Mounting / Wiring:
Mounting orientation
Mounting type
Disconnect line side connection type / torque
Disconnect line side solid and stranded conductors
Power terminal block connection type / torque
Power terminal block solid and stranded conductors
Control terminal block connection type / torque
Control terminal block solid and stranded conductors
Coil connection type / torque
Coil solid and standed conductors
Main auxiliary contact connection type / torque
Main auxiliary contact solid and stranded conductors
OLR auxiliary contact connection type / torque
OLR auxiliary contact solid and starnded conductors
Vertical
Pole and surface
Box lug / 35 lb in (14 - 10); 40 lb in (8); 45 lb in (6 - 4) AWG
1x(14 - 2 AWG) 60/75°C AL or CU
Screw / 24 - 32 lb - in
1x(18 - 2 AWG) 75°C CU
Screw / 12 - 18 lb - in
1x(22 - 8 AWG) 75°C CU
Screw / 7 - 10 lb in
2x(16 - 12 AWG) CU 60/75°C
Screw / 7 - 10 lb in
2x(20 - 16), 2x(18 - 14) 75°C CU
Screw / 7 - 10 lb in
2x(20 - 14 AWG) CU 60/75°C
Short Circuit Current Rating:
Fuses
10kA@600V (Class H or K); 100kA@600V (Class R or J)
Certificates / Approvals:
cULus
UL rated Service Entrance Equipment
6
UL (file no. E185287)
ISO 9001 certification
2.75
.25
2.88
3.50
5.57
3.50
2.88
3.50
3.50
1/4-20 x1/2"
SCREW
10.93
1.68
1.81
26.13
24.27
25.00
3.06
2.13
∅2.85 O.D. FLANGED
CONDUIT OPENING
.37
MOUNTING HOLES FOR
5/16" HARDWARE
∅1.375, ∅1.700, ∅2.000, ∅2.500
ECCENTRIC KNOCKOUT
5.02
∅1.125, ∅1.385, ∅1.750, ∅2.000
ECCENTRIC KNOCKOUT
(2 PLACES)
5.08
ALL DIMENSIONS IN INCHES
OPTIONAL START BUTTON
HAND-OFF-AUTO SELECTOR SWITCH
TO SUPPLY
LEGEND
- FIELD WIRING
L1 L2 L3
- TERMINAL ON COMPONENT
- LOAD\CONTROL TERMINAL BLOCK POINT
DISCONNECT
LINE
FUSES
M
OLR
T1
1L1
2L1
1L2
2L2
T2
1L3
2L3
T3
AUXILIARY
CONTACTS
M
MOTOR
(13)
(14)
M
CONTROL OPTION A
(21)
HAND
OFF
AUTO
OLR
A1
4
AUTO
RUN
5
AUTO
STOP
6
SS
M
OLR
A2
(95)
(96)
HAND
AUTO
OLR
A1
PB
4
SS
AUTO
RUN
M
M
M
A2
(95)
(96)
(13)
5
(98)
AUXILIARY
CONTACTS
START
(14)
(97)
REMOVE JUMPER FOR AUTO - STOP
CONTROL OPTION B
OFF
(22)
(21)
(22)
OLR
AUTO
STOP
(97)
6
(98)
REMOVE JUMPER FOR AUTO - STOP
7
The information provided in this brochure
contains merely general descriptions or
characteristics of performance which in case
of actual use do not always apply as
described or which may change as a result
of further development of the products. An
obligation to provide the respective
characteristics shall only exist if expressly
agreed in the terms of contract.
All product designations may be trademarks
or product names of Siemens AG or supplier
companies whose use by third parties for
their own purposes could violate the rights
of the owners.
Siemens Industry, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
info.us@siemens.com
Subject to change without prior notice
Order No. CPBR-CLS82-1114
Printed in USA
All rights reserved
© 2014, Siemens Industry, Inc.
For additional information about
our currently stocked products or
to place an order, please contact
your local Viking Electric Supply
sales representative.
www.usa.siemens.com/controls