Technical specification

advertisement
Technical specification
Control panel FCE type L, 50 Hz
Panel series 9350.010
Package 902
FCE, type L
Standard functions
Hand – 0 – Auto selector switch with run indication.
One ammeter for each pump.
One running hour meter for each pump.
Voltmeter with selector switch.
High-level alarm.
Failure indication with reset of overtemperature / leakage.
Reset overload inside panel.
Options
The control panel function can be completed by adding optional
functions:
•
FCE, type L
•
Outdoor enclosure (700)
Non-standard panels
When no product number is available the panel has to be specified by
the panel code.
40-9350.010-400/5-1D006-A-902.700.723
0,5 – 12,5 kW (rated power at 400 V)
400
5
1
D
006
A
902
770
723
0,63-25 A
3P+PE; 230 V, 380-400 V, 415 V
Frequency
50 Hz
Direct on Line start or Y/D start
Thermal/magnetic overload protection
Terminal inputs for level regulators
Control circuits
Monitoring
Delayed start of second pump (723)
For example, you want to order panel 40-9350.010.0021 + power on
lamp (770) + delayed start of second pump (723), the panel code will
be as follows:
Current range
Level control
•
All standard panels are identified with product no.,
i.e. 40-9350.010.0021 which should be used when ordering.
General
Short circuit protection
Duty stand by (722)
Standard panels
Technical data
Starting method
Power on lamp (770)
•
How to order
Three-phase control panel , for automatic duty or manual operation of
one or two pumps with Flygt level regulator ENM-10. The control panel
includes a main supply switch and motor protection switches for each
pump. All panels are prepared for supervision with MiniCas II or
MicroCAS. For all options see table below.
Voltage
•
Note: Control panels with options are only made at order and have not
any reserved product number.
Product
Power range
APF Cleaner, controller for automatic pumps sump cleaning
(option code 720)
24 VAC, separately fused
None
or only thermal contacts (TC) with MicroCAS
or TC+FLS and/or CLS with MiniCAS II
Material
1,2 mm steel plate
Colour
Grey (RAL 8032)
Degree of protection
IP43
Documentation
English (other languages on request)
Approval
CE-marked according to EN 60204-1
Size
Configuration
H x W x D (mm)
Weight(kg)
1 pump, D-start
500 x 300 x 210
15
2 pump, D-start
500 x 400 x 210
19
1 pump, Y/D-start
500 x 400 x 210
17
2 pump, Y/D-start
600 x 500 x 210
22
2
=
=
=
=
=
=
=
=
=
Voltage system (380-400 V)
Frequency (50 Hz)
Number of pumps (1 pump)
Start method (D-O-L)
Current range code (0.4-0.62 A, see table)
Monitoring code (see table)
Package code (always 902 for this panel series)
Code for Power on lamp
Code for Delayed start of second pump
Panel series 9350.010
Package 902
FCE, type L
Basic panel product range
Standard configuration with short delivery time
•
380-400 V, 50 Hz
•
1- 2 pumps
•
D-O-L start
Basic control panel without supervision (code A), D-start
Current range
Current
code
Control panel number
1-pump
2-pump
0.63 - 1.1 A
010
40-9350.010.0021 40-9350.010.0051
1 - 1.6 A
016
40-9350.010.0022 40-9350.010.0052
1.6 - 2.5 A
025
40-9350.010.0023 40-9350.010.0053
2.5 - 4 A
040
40-9350.010.0024 40-9350.010.0054
4 - 6.3 A
063
40-9350.010.0025 40-9350.010.0055
6.3 - 9 A
090
40-9350.010.0026 40-9350.010.0056
9 - 12.5 A
125
40-9350.010.0027 40-9350.010.0057
12.5 - 16 A
160
40-9350.010.0028 40-9350.010.0058
16 - 20 A
200
40-9350.010.0029 40-9350.010.0059
20 - 25 A
250
40-9350.010.0030 40-9350.010.0060
Basic control panel with MicroCAS (code B), D-start
Current range
Current
code
Control panel number
1-pump
2-pump
0.63 - 1.1 A
010
40-9350.010.0081 40-9350.010.0111
1 - 1.6 A
016
40-9350.010.0082 40-9350.010.0112
1.6 - 2.5 A
025
40-9350.010.0083 40-9350.010.0113
2.5 - 4 A
040
40-9350.010.0084 40-9350.010.0114
4 - 6.3 A
063
40-9350.010.0085 40-9350.010.0115
6.3 - 9 A
090
40-9350.010.0086 40-9350.010.0116
9 - 12.5 A
125
40-9350.010.0087 40-9350.010.0117
12.5 - 16 A
160
40-9350.010.0088 40-9350.010.0118
16 - 20 A
200
40-9350.010.0089 40-9350.010.0119
20 - 25 A
250
40-9350.010.0090 40-9350.010.0120
Basic control panel with MiniCAS (code H), D-start
Current range
Current
code
Control panel number
1-pump
2-pump
0.63 - 1.1 A
010
40-9350.010.0233 40-9350.010.0243
1 - 1.6 A
016
40-9350.010.0234 40-9350.010.0244
1.6 - 2.5 A
025
40-9350.010.0235 40-9350.010.0245
2.5 - 4 A
040
40-9350.010.0236 40-9350.010.0246
4 - 6.3 A
063
40-9350.010.0237 40-9350.010.0247
6.3 - 9 A
090
40-9350.010.0238 40-9350.010.0248
9 - 12.5 A
125
40-9350.010.0239 40-9350.010.0249
12.5 - 16 A
160
40-9350.010.0240 40-9350.010.0250
16 - 20 A
200
40-9350.010.0241 40-9350.010.0251
20 - 25 A
250
40-9350.010.0242 40-9350.010.0252
3
FCE type L.50Hz.04.EN_FIN.03.05 © ITT Flygt AB
www.flygt.com
895470
Download