INSTALLATION INSTRUCTIONS
Installation should be performed by a qualified
electrician in accordance with the National Electrical Code
and relevant local codes.
M9700C SERIES
Hydrel's M9700 Series of modular in-grade lights are an assembly of the following
components. Each component is shipped and installed separately.
Components (in order of installation):
Rough-In Section – MRIS rough-in housing is installed first during
the electrical installation. This houses the remainder of the M9700
Series components.
MRISC97RC -round
Power Module – MHSL power (ballast/transformer) module or is
installed within the MRIS rough-in housing. The sealed power
module operates the M9700 Series MACL lamp module via the
attached cord and plug.
MHSLC97
Finishing Section – MFS finishing section includes the door trim
and rotolock ring for the single lensed M9710 & M9730. The MFS
includes the door, lens assembly and aimset ring for the double
lensed M9720 and M9740.
MFSC97R - round single lens
LED Module – MACLC LED module is installed within the MFS
support/tilt ring. The sealed module is connected to the MHSL
power module for operation via the waterproof cord and plug.
MACLC
ROUGH-INSECTION
MRISC97SC - square
MFSC97S - square single lens
MFSC97RD - round double lens
MFSC97SD - square double lens
M9710C
M9720C
M9730C
M9740C
Round Single Lens
Round Double Lens
Square Single Lens
Square Double Lens
FINISHING
SECTION
LED
MODULE
POWER (DRIVER)
MODULE
©2005 Hydrel
Rev. 6/14/04
REV 0
NOTE: HYDREL RESERVES THE RIGHT TO MODIFY SPECIFICATION WITHOUT
NOTICE. Any dimension on this sheet is to be assumed as a reference
dimension: "Used for information purposes only. It does not govern
manufacturing or inspection requirements." (ANSI Y14.5-1973)
9144 Deering Ave., 2nd Floor
Chatsworth, CA 91311
Phone: 866.533.9901
Fax: 866.533.5291
www.hydrel.com
M9700C Housing
INSTALLATION INSTRUCTIONS
Installation should be performed by a qualified
electrician in accordance with the National Electrical Code and relevant local
codes.
TO INSTALL
1.
Dig hole to appropriate depth allowing for 6”
minimum of pea gravel at bottom of rough-insection for drainage.
ROUGH-IN SECTION
(MRISC)
SUITABLE FOR WET LOCATIONS - IP68
INSTALLATION DIAGRAM
Note: More pea gravel or additional drainage may
be required in locations that have poor soil
drainage and/or subject to freezing.
2.
Install the rough-in-section flush with finish
grade of earth or concrete only. No specific
orientation for the rough-in is required.
CAUTION: WHEN INSTALLING IN ORGANIC MULCH,
SURROUND ROUGH-IN-SECTION WITH APPROX. SIX
INCHES (15cm) OF SAND OR OTHER NON-ORGANIC
SUBSTANCE.
CAUTION: TEMPORARY COVER MUST REMAIN IN
HOUSING DURING INSTALLATION.
3.
Connect conduit to junction box. Use suitable
thread sealing compound. Duct sealant may be
added to the conduit to prevent water from
traveling from fixture to fixture in the even the
conduit is breached.
TO PULL ELECTRICAL CONDUCTORS
1.
Remove temporary cover with fastener wrench
provided.
2.
Remove junction box cover and gasket. Pull
conductors.
3.
Seal conduit entry with suitable compound to
prevent moisture penetration from conduit system.
4.
Re-install junction box cover and gasket with
fasteners provided. CAUTION: DO NOT OVER
TIGHTEN (20 in-lbs or 2 N-m).
5.
Re-install temporary cover with supplied fasten-ers.
CAUTION: DO NOT OVER TIGHTEN (20 in-lbs or 2 Nm).
INSTALLATION DIAGRAM
CAUTION: LEAVE TEMPORARY COVER IN PLACE
UNTIL READY TO INSTALL FINISHING SECTIONS.
©2014 Hydrel
8/20/15
M9700C Housing Installation
NOTE: HYDREL RESERVES THE RIGHT TO MODIFY SPECIFICATION WITHOUT NOTICE.
Any dimension on this sheet is to be assumed as a reference dimension: “Used
for information purposes only. It does not govern manufacturing or inspection
requirements.” (ANSI Y14.5-1973)
9144 Deering Ave., 2nd Floor
Chatsworth, CA 91311
Phone: 866.533.9901
Fax: 866.533.5291
www.hydrel.com
M9700C DRIVER INSTALLATION
INSTALLATION INSTRUCTIONS
Installation should be performed by a qualified
electrician in accordance with the National Electrical Code
and relevant local codes.
NOTICE: DO NOT CONNECT LED MODULE WHILE SYSTEM IS ENERGIZED. TURN OFF POWER PRIOR TO LAMPING.
CAUTION: TEMPORARY COVER MUST
REMAIN IN HOUSING UNTIL READY TO
INSTALL INTERNAL COMPONENTS
1.
Remove temporary cover from rough-in-section.
2.
Remove junction box cover & gasket.
3.
Loosen junction box cord seal nut. Run pig
tailed supply cord from power module through
cord seal and junction box cover (provide
enough cord for proper splicing within junction
box).
4.
Tighten junction box seal nut around power cord.
5.
Place power module in bottom of
rough-in-section.
6.
Make electrical connections.
INSTALLATION DIAGRAM
WIRING THE DRIVER
Temporary Cover
Power
Module
Note: Use silicone-filled wire nuts or fill junction box
with re-enterable potting compound (PC21) prior to
replacing lid and gasket. If using potting compound
be sure to seal the conduit with plumbers putty before
pouring the potting compound to prevent it leaking
into the conduit.
7.
Re-install junction box cover and gasket.
Driver Module
Tighten to ensure proper sealing.
CAUTION: DO NOT OVER TIGHTEN (20 inlbs or 2 N-m).
1. STANDARD 3 WIRE ELECTRICAL - SINGLE CORD TO SINGLE CORD
SPLICE
POWER FROM FIXTURE
2.
SUPPLY POWER
LDIM (0-10 volt) 5 WIRE - SINGLE CORD TO DOUBLE CORD
SUPPLY POWER - LINE VOLTAGE
POWER FROM FIXTURE
-
+
©2014 Hydrel
8/20/15
M9700C LED MODULE
INSTALLATION
0-10 LOW VOLTAGE DIMMING LINE
NOTE: HYDREL RESERVES THE RIGHT TO MODIFY SPECIFICATION WITHOUT
NOTICE. Any dimension on this sheet is to be assumed as a reference dimension:
“Used for information purposes only. It does not govern manufacturing or inspection
requirements.” (ANSI Y14.5-1973)
9144 Deering Ave., 2nd Floor
Chatsworth, CA 91311
Phone: 866.533.9901
Fax: 866.533.5291
www.hydrel.com
M9700C LED INSTALLATION
INSTALLATION DIAGRAM FINISHING SECTION INSTALLATION
Door
Door
Top Lens
LED Module
Tilt Ring
Rotolock Ring
LED Module
Rough-In Housing
Aim Lock Ring
Rough-In Housing
Single lens fixture assemblies
(M9710/M9730)
Double lens fixture assemblies
(M9720/M9740)
1.
Install rotolock ring or aimlock ring into top of rough-in
housing. Do not secure ring to housing.
2.
For single lensed luminaires skip to step 3.
For double lensed luminaires secure the tilt adjustment ring to
lamp module while assembly is outside of the housing. Position
the module into the tile ring by aligning the module pin with the
tilt ring slot and then tighten the three set screws around the
rim.
3.
Plug driver module into base of lamp module assembly.
4.
Place LED module assembly into the rotolock or aimlock ring.
PUSH CORD DIRECTLY INTO LAMP MODULE - DO NOT TWIST!
©2014 Hydrel
8/20/15
M9700C LED MODULE
INSTALLATION
NOTE: HYDREL RESERVES THE RIGHT TO MODIFY SPECIFICATION WITHOUT
NOTICE. Any dimension on this sheet is to be assumed as a reference dimension:
“Used for information purposes only. It does not govern manufacturing or inspection
requirements.” (ANSI Y14.5-1973)
9144 Deering Ave., 2nd Floor
Chatsworth, CA 91311
Phone: 866.533.9901
Fax: 866.533.5291
www.hydrel.com
M9700C LED INSTALLATION
AIMING INSTRUCTIONS
CAUTION: AVOID LOOKING DIRECTLY INTO
LIGHT SOURCE DURING AIMING. FIXTURE
LENS MAY BECOME HOT. AVOID CONTACT
WITH BARE SKIN.
5.
Energize the fixture, allowing it to fully reach operating temperature and light output.
6.
Rotate the LED module and its support ring (rotolock or aimlock) until desired position is achieved.
7.
Once the desired aiming position is determined, secure the support ring into the housing with the attached
fasteners. CAUTION: DO NOT OVER TIGHTEN (20 in-lbs or 2 N-m).
8.
For the double lensed luminaires adjust the lamp module tilt by turning the single phillips head screw at
the top of the module tilt ring.
9.
Install the finish door assembly with the fasteners provided. CAUTION: DO NOT OVER TIGHTEN (20 in-lbs or
2 N-m).
20°
10°
FLC10
FLC20
Single lensed fixture can be aimed using 10°and 20° tilt lenses only.
Lenses are made of prismatic glass that bend the beam of light. Tile lenses
have an arrow molded into the top showing the direction the beam of
light will be aimed. The entire lamp module and roto-lock ring can be
spun 360°to aim. Once aiming has been set, lock the roto-lock ring down
to maintain the aiming.
Double lens fixtures can be mechanically and optically aimed. The LED
module can be mechanically aimed up to 15° by adjusting the tilt ring.
FLC10 and FLC20 tilt lenses may also be used to optically aim the beam of
light. The entire lamp module and aim set ring can be spun 360° to aim.
Once aiming has been set, lock the aimset ring into the housing to
maintain aiming. The tilt ring is keyed into the aimset ring to ensure that
fixture aiming is never compromised.
©2014 Hydrel
8/20/15
M9700C LED MODULE
INSTALLATION
NOTE: HYDREL RESERVES THE RIGHT TO MODIFY SPECIFICATION WITHOUT
NOTICE. Any dimension on this sheet is to be assumed as a reference
dimension: "Used for information purposes only. It does not govern
manufacturing or inspection requirements." (ANSI Y14.5-1973)