ELECTRICAL ADDENDUM
To:
Date:
Hoa Ha, P.Eng.
Firm:
Project Number:
RF Binnie & Associates Ltd.
101 – 19232 Enterprise Way
Surrey, BC V3S 6J9
DMD & Associates
Ltd.
#12-17358 104A
Avenue
Surrey, BC V4N 5M3
604/589-9010
Fax 604/589-9012
Re:
2011-02-08
3215-10
From:
Jason Furness, P.Eng.
Tamanawis Park – Field Hockey Field #2
Surrey, BC
Comments:
The following changes/additions are required to the electrical design drawings 3215-10-01 to -03 of
-03 (all changes indicated via revision 1 on the attached revised sheets 1 and 2):
Sheet 1:
1.
2.
3.
Scoreboard power circuit added.
Receptacle cabinet added to the referee area c/w power circuit back to service kiosk.
Communication cabinet added to the referee area c/w comm. duct, boxes and cable
to the scoreboard.
1.
2.
3.
7-1800VA fixtures per pole, not 8-1800VA fixtures per pole.
20A-1P (half size circuit breaker) added for receptacle circuit in referee area.
15A-1P (half size circuit breaker) added for scoreboard power circuit.
Sheet 2:
Sheet 3:
No changes required.
Pacific Northwest Office:
1770 Front Street, PMB # 267
Lynden WA 98264
Toll Free: 877/249-8080
www.dmdeng.com
The following changes are required to the electrical specifications:
1. The following change is made to SPECIFICATIONS – Sports Lighting, Item 2.01
Manufacturers: Item A, which shall now read:
Available Products: Subject to compliance with requirements, products that
may be incorporated in the work include:
1. Musco Lighting “Green Lighting System” (CONTROL
LINK AND SERVICE PLAN WILL NOT BE
REQUIRED)
2. Engineer Approved Alternate (refer to 1.02 above).
2. The following change is made to SPECIFICATIONS – Sports Lighting, Item 3.04
Independent Testing and Observations: Item A, which shall now read:
The owners engineer will field measure and document the on-field illumination
levels and uniformities in accordance with IESNA LM-5. Off-site spill light
levels will also be measured along the residential boundary line. Levels will be
measured at approximately 100 hours of lamp operation. Initial levels (at
between 50 and 100 hours) shall be within 10 percent (10 %) of those shown on
the Suppliers design. If the lighting fails to meet the required levels additional
cost for the engineer to re-measure and retest the field lighting ($1,000.00 per
test) shall be paid for by the lighting supplier. Supplier measurement of the
lighting levels will not be acceptable.
1-50mm RPVC
4 No.10 RW90 POLE F1
4 No. 8 RW90 POLE F2
3 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
EXIST. 1-50mm RPVC
8 No. 6 RW90 SPORTS LIGHTING
1 No. 8 RW90 BOND
LEGEND:
1-50mm RPVC
2 No. 8 RW90 RECEPTACLE (F1)
2 No. 4 RW90 RECEPTACLE (F2)
2 No. 4 RW90 SCOREBOARE PWR.
2 No.10 RW90 GATE LOCKS
1 No. 8 RW90 BOND
EXIST. 1-50mm RPVC
2 No. 10 RW90 SECURITY LTG
2 No. 1 RW90 RECEPT. PWR.
1 No. 12 RW90 BOND
1-30mm RPVC/RMC
2 No.10 RW90 GATE LOCKS
1 No.12 RW90 BOND
(FROM JB TO GATE LOCK)
TO EXIST. IRRIGATION
BOOSTER PUMP AND
IRRIGATION PLC
EXIST. 1-75mm RPVC
2 No. 10 RW90 SECURITY LTG
2 No. 12 RW90 GATE LOCKS
2 No. 1 RW90 RECEPT. PWR.
1 No. 12 RW90 BOND
1 No.12 RW90 BOND
2 No. 8 RW90 RECEPTACLE (F1)
2 No. 4 RW90 RECEPTACLE (F2)
2 No. 4 RW90 RECEPTACLE (F3)
2 No. 8 RW90 RECEPTACLE (F4)
2 No. 4 RW90 SCOREBOARE PWR.
2 No. 6 RW90 RECEPTACLE (REF. AREA)
2 No.10 RW90 GATE LOCKS
1 No. 6 RW90 BOND
EXIST. 1-75mm RPVC (EMPTY)
4 No.10 RW90 POLE F1
4 No. 8 RW90 POLE F2
4 No. 8 RW90 POLE F3
4 No.10 RW90 POLE F4
4 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
1
1-50mm RPVC
2 No. 4 RW90 RECEPTACLE (F2)
2 No. 4 RW90 SCOREBOARE PWR.
2 No.10 RW90 GATE LOCKS
1 No. 8 RW90 BOND
PROPOSED UNDERGROUND RPVC CONDUIT AND CONDUCTORS
1-25mm RPVC / RMC
2 No. 4 RW90 RECEPTACLE (F2)
1 No. 8 RW90 BOND
(FROM JB TO RECEPTACLE ENCLOSURE)
1
EXISTING UNDERGROUND RPVC CONDUIT AND CONDUCTORS
R
1-50mm RPVC (EMPTY)
(FROM JB TO POLE)
1-50mm RPVC
(EMPTY)
1-50mm RPVC (EMPTY)
(FROM JB TO POLE)
1-30mm RPVC/RMC
2 No.10 RW90 GATE LOCKS
1 No.12 RW90 BOND
(FROM JB TO GATE LOCK)
EXIST. IRRIGATION KIOSK
PROPOSED LARGE ROUND PLASTIC PULL BOX (MoTI SPEC.) C/W SECURITY LOCKABLE LID (LABELED 'COMM')
C
PROPOSED GFCI 120V RECEPTACLE ENCLOSURE
1-25mm RPVC / RMC
2 No. 8 RW90 RECEPTACLE (F1)
1 No.10 RW90 BOND
(FROM JB TO RECEPTACLE ENCLOSURE)
EXIST. 1-75mm RPVC
16 No. 6 RW90 SPORTS LIGHTING
1 No. 8 RW90 BOND
EXIST. 1-75mm RPVC
3 No. 6 RW90 IRRIGATION BOOSTER PUMP
2 No. 10 RW90 IRRIGATION PLC PWR
2 No. 10 RW90 WASHROOM BLD. FEEDER
1 No. 8 RW90 BOND
PROPOSED LARGE ROUND PLASTIC PULL BOX (MoTI SPEC.) C/W SECURITY LOCKABLE LID
1-50mm RPVC
4 No. 8 RW90 POLE F2
2 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
(FROM JB TO POLE)
1-50mm RPVC
4 No. 8 RW90 POLE F2
2 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
1-50mm RPVC
4 No.10 RW90 POLE F1
2 No.10 RW90 SECURITY LTG
1 No.12 RW90 BOND
(FROM JB TO POLE)
TO
TU EX
RF IST
FIE . SY
LD NT
HO HE
CK TIC
EY
EXIST. 1-50mm RPVC
2 No. 12 RW90 GATE LOCKS
2 No. 10 RW90 SECURITY LTG
1 No. 12 RW90 BOND
PROPOSED 250W HPS SECURITY LUMINAIRE ON SPORTS LIGHT POLE
1
1-50mm RPVC
(EMPTY)
EXIST. 1-50mm RPVC
8 No. 6 RW90 SPORTS LIGHTING
1 No. 8 RW90 BOND
PROPOSED GALVANIZED STEEL SPORTSLIGHTING POLE WITH 1500W-347V M.H.
SPORTLIGHTS
SECURITY LUMINAIRE ON RED PHASE CONDUCTOR
BK
SECURITY LUMINAIRE ON BLACK PHASE CONDUCTOR
BL
SECURITY LUMINAIRE ON BLUE PHASE CONDUCTOR
F1
SPORTS LIGHTING POLE NUMBER
NOTES:
1-50mm RPVC
2 No. 4 RW90 SCOREBOARD PWR.
1 No. 8 RW90 BOND
1. ALL WORK SHALL CONFORM TO THE MOST CURRENT EDITION OF THE CANADIAN ELECTRICAL CODE C.S.A.-C22.1
AND ANY BULLETINS ISSUED BY THE ELECTRICAL SAFETY BRANCH.
1
2. SPORTSLIGHTING POLES, POLE TOP LUMINAIRE ASSEMBLY, INTERNAL WIRING HARNESS, ELECTRICAL
COMPONENT ENCLOSURE AND PRE-CAST CONCRETE BASE SHALL BE SUPPLIED AS A PACKAGE. PACKAGE DOES
NOT INCLUDE SECURITY LIGHTING, RECEPTACLE ENCLOSURE, AND RELATED WIRING.
EXIST. CONCRETE VAULT
F1
F2
SPILL LIGHT
BOUNDARY LINE
1
R
BK
3. IDENTIFY ALL CIRCUITS IN ALL JUNCTION BOXES, TERMINAL BLOCK IN SERVICE CABINET, AT THE DISCONNECT
BREAKER IN THE SPORTSLIGHTING BALLAST BOX AND SECURITY LIGHTING CIRCUITS IN THE POLE HANDHOLE
WITH SLEEVE TYPE WIRE MARKERS. EACH FEEDER SHALL BE LABELED WITH THE CIRCUIT No. (I.E. CCT1, CCT3,
CCT5. ETC).
1-50mm RPVC/32mm RMC
2 No. 4 RW90 SCOREBOARD PWR.
1 No. 8 RW90 BOND
(FROM PB TO SCOREBOARD)
1
4. ALL CONDUCTORS SHALL BE STRANDED COPPER WITH RW90 INSULATION. SPORTS LIGHTING CONDUCTORS
SHALL RUN CONTINUOUS WITH NO SPLICES.
1
5. CONTRACTOR SHALL EXCAVATE FOUNDATION AND GAIN APPROVAL FROM GEOTECHNICAL ENGINEER PRIOR TO
FOUNDATION INSTALLATION. BACK FILL SHALL MEET THE APPROVAL OF THE GEOTECHNICAL ENGINEER.
6. INSTALL CITY PADLOCKS ON SPORTSLIGHTING BALLAST BOXES AND RECEPTACLE ENCLOSURES.
35.0m
(TYP.)
TO EXIST.
PARKING LOT
LIGHTING
C
SCOREBOARD. REFER TO R.F. BINNIE
DESIGN DRAWINGS FOR EXACT
LOCATION AND TYPE OF SCOREBOARD.
EXIST. 1-50mm RPVC (120/240V)
3 No.10 RW90 PARKING LOT LIGHTING
3 No.10 RW90 PHOTOCELL
1 No.12 RW90 BOND
1-50mm RPVC/32mm RMC COMM.
1-2PR No.24 SCOREBOARD
CONTROL CABLE (BELDEN 9502)
(FROM PB TO SCOREBOARD)
EXIST. 1-50mm RPVC
(EMPTY)
7. CONDUITS SHALL BE INSTALLED IN A COMMON TRENCH.
1
8. A TRON HEB SERIES WATER-RESISTANT FUSE HOLDER C/W A 10A BUSS KTK 10 FUSE & 2 INSULATING BOOTS SHALL
BE INSTALLED IN EACH SECURITY LUMINAIRE LIVE CONDUCTOR, IN THE HANDHOLE.
9. BEFORE DMD CAN PROVIDE A FINAL INSPECTION THE CONTRACTOR MUST ENSURE THAT THE ENTIRE ELECTRICAL
SYSTEM IS FULLY FUNCTIONAL AND THAT SUBSTANTIAL COMPLETION HAS BEEN OBTAINED.
1
10. ALL EXPOSED CONDUIT SHALL BE RMC.
EXISTING SERVICE KIOSK
REFERENCE POINT
VALID MANUFACTURING LTD. WEATHERPROOF
LOCKABLE COMMUNICATION CABINET WITH
IN-USE COVER (POWDER COATED BLACK) C/W
COMMUNICATION CONNECTOR (COORDINATE
COMM. CONNECTOR DETAILS WITH
SCOREBOARD SUPPLIER). CABINET TO BE
MOUNTED SECURELY TO FENCE POST.
EXIST. 2-100mm RPVC
(SECONDARY SERVICE CONDUCTORS)
VALID MANUFACTURING LTD. WEATHERPROOF
LOCKABLE RECEPTACLE CABINET WITH IN-USE
COVER C/W 15A-120V GFCI RECEPTACLE AND 15A-1P
BREAKER (POWDER COATED BLACK). CABINET TO
BE MOUNTED SECURELY TO FENCE POST.
EXISTING BC HYDRO PAD MOUNT TRANSFORMER
EXIST. 3-75mm RPVC
(PRIMARY SERVICE CONDUCTORS)
1
1-50mm RPVC
4 No. 8 RW90 POLE F3
4 No.10 RW90 POLE F4
3 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
1
SPORTS LIGHTING DESIGN CRITERIA
35.0m
(TYP.)
FIELD TYPE
SYNTHETIC FIELD HOCKEY FIELD
FIELD DIMENSIONS
TO EXISTING
SERVICE
POLE
1-50mm RPVC
2 No. 4 RW90 RECEPTACLE (F3)
2 No. 8 RW90 RECEPTACLE (F4)
2 No. 6 RW90 RECEPTACLE (REF. AREA)
1 No. 8 RW90 BOND
101.4m X 61.0m
R
BL
F4
C
DESIGN CALCULATED
TAMANAWIS PARK
LOCATION
1
REFEREE AREA
DESIGN REQUIREMENTS
ITEM
EQUIPMENT TYPE
21.3m - 1500W MH SPORTSLIGHT C/W
EXTERNAL VISORS
MAINTAINED ILLUMINATION LEVEL (AVG.)
370 LUX
.
2.0:1
.
F3
1
50.0m
(TYP.)
1-50mm RPVC
(EMPTY)
UNIFORMITY RATIO (MAX.:MIN.)
50.0m
(TYP.)
1-50mm RPVC COMM.
1-2PR No.24 SCOREBOARD
CONTROL CABLE (BELDEN 9502)
64 AVENUE
1
DMD & Associates Ltd.
#12-17358 104A Avenue
Surrey, BC, Canada V4N 5M3
www.dmdeng.com
office@dmdeng.com
1-50mm RPVC
4 No.10 RW90 POLE F4
2 No.10 RW90 SECURITY LTG
1 No.12 RW90 BOND
(FROM JB TO POLE)
1-50mm RPVC
4 No. 8 RW90 POLE F3
2 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
SITE PLAN
0
1:500
1-50mm RPVC
4 No. 8 RW90 POLE F3
2 No.10 RW90 SECURITY LTG
1 No.10 RW90 BOND
(FROM JB TO POLE)
25
1-50mm RPVC
2 No. 4 RW90 RECEPTACLE (F3)
1 No. 8 RW90 BOND
1-25mm RPVC / RMC
2 No. 8 RW90 RECEPTACLE (F4)
1 No.10 RW90 BOND
(FROM JB TO RECEPTACLE ENCLOSURE)
1-25mm RPVC / RMC
2 No. 4 RW90 RECEPTACLE (F3)
1 No. 8 RW90 BOND
(FROM JB TO RECEPTACLE ENCLOSURE)
1-50mm RPVC
(EMPTY)
1-50mm RPVC (EMPTY)
(FROM JB TO POLE)
1-50mm RPVC (EMPTY)
(FROM JB TO POLE)
1-32mm RPVC/RMC COMM.
1-2PR No.24 SCOREBOARD
CONTROL CABLE (BELDEN 9502)
(FROM PB TO COMM. CABINET)
1-50mm RPVC
2 No. 4 RW90 RECEPTACLE (F3)
2 No. 6 RW90 RECEPTACLE (REF. AREA)
1 No. 8 RW90 BOND
1
1-32mm RPVC/RMC
2 No. 6 RW90 RECEPTACLE (REF. AREA)
1 No. 8 RW90 BOND
(FROM PB TO RECEPTACLE CABINET)
CONTRACTOR SHALL REFER TO MUNICIPAL RECORD / CIVIL DESIGN
DRAWINGS FOR ALL OTHER UTILITIES, SERVICE LOCATIONS, AND
DETAILS. THE EXACT LOCATION OF THESE UTILITIES SHALL BE
DETERMINED ON SITE BY THE CONTRACTOR.
PULL BOX LOCATIONS SHOWN FOR
DIAGRAMMATIC PURPOSE ONLY
ROB FRASER
CHECKED
DANIEL J. WONG
DATE
NOVEMBER 9, 2010
SCALE:
1:500
NOT FOR CONSTRUCTION
No.
DATE
BY
CHK'D
REVISION
.
2010-11-10
JF
ISSUED FOR REVIEW
.
2010-11-22
JF
ISSUED FOR REVIEW
.
2010-12-21
JF
ISSUED FOR REVIEW
.
2011-01-14
JF
ISSUED FOR TENDER
1
2011-02-08
JF
ISSUED FOR ADDENDUM
van der Zalm + associates inc.
Suite 1 - 8938 192nd Street, Surrey, BC V4N 3W8 Tel: (604) 882-0024
SPORTSFIELD LIGHTING
TAMANAWIS PARK
SYNTHETIC FIELD HOCKEY FIELD
SURREY, BC
PROJECT No.
1
1
1
1
1
1
1
1
SHEET No.
3215-10-01 of 03
DRAWING REFERENCE
1
DRAWN
2011-02-08
CHECK BEFORE YOU DIG
1
JASON FURNESS
SEAL
1-50mm RPVC
(EMPTY)
1
DESIGNED
1
REVISION
1 of 3
CANCEL PRINTS BEARING PREVIOUS LETTER
1
DMD (2010)
1
FOR EXISTING SPORTS LIGHTING
REFER TO DMD & ASSOCIATES
DRAWINGS 1398-05-01 TO -03
604/589-9010
Fax 604/589-9012
B.C. HYDRO
PMT
300kVA 25kV347/600V 3Ø 4W
K
1 - 100mm RPVC
(BCH SERVICE CONDUCTORS)
KIOSK ENCLOSURE
1-3/0 COPPER TO
20mmØ x 3000mm
LONG GROUND RODS
600A
3PSN
NEW BREAKERS AND PANELS SHALL BE
RATED FOR 18kA INTERRUPTING CURRENT
100:5
B.C. HYDRO
SERVICE METER
M
600V- 200V
84 CCT. 600A, 347/600V, 3Ø, 4W, DISTRIBUTION PANEL (18kA INTERRUPTING CURRENT)
C22
30A-3P
C24
30A-1P
C23
30A-3P
30A
3P
80A
3P
30A
3P
C1
30A-3P
30A
3P
C3
30A-3P
C2
30A-3P
CCT 29
15A
1P
30A
3P
30A
3P
C5
30A-3P
C18
15A-3P
C4
30A-3P
30A
3P
30A
3P
C6
30A-3P
30A
3P
C7
30A-3P
30A
3P
C8
30A-3P
30A
3P
C9
30A-3P
30A
3P
30A
3P
C11
30A-3P
C10
30A-3P
30A
3P
30A
3P
C13
30A-3P
C12
30A-3P
30A
3P
C14
30A-3P
30A
3P
30A
3P
C15
30A-3P
C16
30A-3P
15A
2P
LIGHTING CONTROL CABINET & FIELD
WIRING (SEE LIGHTING CONTROL
SCHEMATIC FOR WIRING DETAILS)
C17
30A-3P
FUTURE
WIRING
(TYP.)
& BOND
C21
30A-3P
CCT 25 & 27
30A
2P
15A-1P
2 No. 10 RW90
C20
30A-3P
20A-3P
3 No. 6 RW90 & BOND
HID LIGHTING
CONTACTORS
(TYPICAL)
20A-3P
3 No.10 RW90 & BOND
1 No. 10 RW90
20A-3P
20A-3P
2 No.12 RW90
WASHROOM
30HP IRRIGATION
POLE No. S1
POLE No. S2
POLE No. S3
POLE No. S4
BLD FEEDER
BOOSTER PUMP
7x1500W
7x1500W
7x1500W
7x1500W
4 No.10 RW90
& BOND
4 No.10 RW90
& BOND
4 No. 8 RW90
& BOND
4 No. 8 RW90
& BOND
4 No.10 RW90
& BOND
TERMINAL
BLOCK
(TYPICAL)
400W HPS
SECURITY LTG ON
SPORTS POLES
(3KVA)
SOUTH
SOUTH
SOUTH
SOUTH
SOUTH
NORTH
NORTH
NORTH
NORTH
NORTH
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
SOFTBALL
20 kW
20 kW
AND
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
(FUTURE)
(FUTURE)
BASKETBALL
FIELD HOCKEY
POLE No. A1
POLE No. B1
POLE No. C1
POLE No. A2
POLE No. B2
POLE No. A2
POLE No. B2
POLE No. C2
POLE No. A3
POLE No. B3
COURTS
(50.4kVA)
3.3 kW
11.7 kW
16.7 kW
3.3 kW
16.7 kW
3.3 kW
16.7 kW
16.7 kW
3.3 kW
11.7 kW
7 kW
TENNIS COURTS TENNIS COURTS
BALL HOCKEY
7.5 kVA 600V120/240V 1Ø 3W
DRY TYPE
(FUTURE)
16 CCT., 100A. 120/240V, 1Ø, 3W, LOAD CENTRE
FIELD
WIRING
(TYPICAL)
ZONE 2-D
SPARE
ZONE 3-N
GATE LOCKS (C19)
ZONE 3-D
SPARE
ZONE 4-N
POLES F1 & F2 (C20 & C21)
ZONE 4-D
POLES F3 & F4 (C22 & C23)
ZONE 5-N
SECURITY LIGHTING (C24)
ZONE 5-D
SPARE
ZONE 6-N
GATE LOCKS (C25)
ZONE 6-D
SPARE
ZONE 7-N
SPARE
ZONE 7-D
SPARE
ZONE 8-N
SPARE
ZONE 8-D
SPARE
15A
1P
15A
1P
15A
1P
15A
1P
15A
1P
20A
1P
15A
1P
15A
1P
15A
1P
KIOSK LIGHTS
2x100W
KIOSK RECEPTACLE
1440W
PARKING LOT
15A
1P
LIGHTING
PHOTOCELL
2 kW
GFCI
GATE
LOCKS
CONVENIENCE
RECEPTACLE
ENCLOSURE ON
POLE F1
(1.0kVA)
GFCI
CONVENIENCE
RECEPTACLE
ENCLOSURE ON
POLE F2
(1.0kVA)
GFCI
GFCI
GFCI
CONVENIENCE
RECEPTACLE
ENCLOSURE ON
POLE F3
(1.0kVA)
CONVENIENCE
RECEPTACLE
ENCLOSURE ON
POLE F4
(1.0kVA)
CONVENIENCE
RECEPTACLE
ENCLOSURE IN
REFEREE AREA
(1.0kVA)
TO
SCOREBOARD
(1.2kVA)
POWER
SUPPLY
120V AC
TO 24V DC MIN
20 WATTS
FIELD WIRING
KIOSK HEATER
500W
SKYLOGIX
LTG
CONTROLLER
(REFER TO
SKYLOGIX
WIRING
DIAGRAM
SKYLOGIX ARC 10
CONTROL SYSTEM 8 ZONE
UNIT IN NEMA 3R CABINET
MOUNTED TO SIDE OF
IRRIGATION KIOSK.
PLC PWR
1
& BOND
C19
15A-1P
FIELD WIRING
15A
1P
LIGHT
SWITCH
2 No. 1 RW90
& BOND
2 No. 4 RW90
& BOND
2 No. 6 RW90
T/STAT
POWER SUPPLY
& BOND
POLES S3 & S4 (C3 & C4)
SECURITY LIGHTING (C18)
15A
1P
2 No.10 RW90 & BOND
2 No.10 RW90
POLES S1 & S2 (C1 & C2)
ZONE 2-N
30A
2P
PARKING LOT
LIGHTING CONTROL
PANEL
POWER
SUPPLY
120V AC
TO 24V DC MIN
20 WATTS
LIGHTING CONTROL ZONES
(SKYLOGIX SYSTEM)
ZONE 1-D
& BOND
C25
15A-1P
1
2 No. 8 RW90
7-1800VA
FIXTURES
& BOND
7-1800VA
FIXTURES
FIELD HOCKEY
(50.4kVA)
ZONE 1-N
15A
1P
(HALF SIZE
CIRCUIT
BREAKER)
T
2 No. 4 RW90
7-1800VA
FIXTURES
20A
1P
(HALF SIZE
CIRCUIT
BREAKER)
2 No.12 RW90
SECURITY
LIGHTING
4-250W
(1.2 kVA)
7-1800VA
FIXTURES
20A
1P
(HALF SIZE
CIRCUIT
BREAKER)
20A
1P
(HALF SIZE
CIRCUIT
BREAKER)
F4
& BOND
F3
20A
1P
(HALF SIZE
CIRCUIT
BREAKER)
2 No. 4 RW90
F2
& BOND
F1
& BOND
POLE
NUMBER
(TYPICAL)
20A
1P
(HALF SIZE
CIRCUIT
BREAKER)
15A
1P
(HALF SIZE
CIRCUIT
BREAKER)
ELECTRICAL
CABINET ON
POLE (TYPICAL)
2 No. 8 RW90
3P BREAKERS
SUPPLIED WITH
CABINET (TYP.)
15A
1P
CONVENIENCE
RECEPTACLE
ENCLOSURE IN
OFFICIALS
BOOTH
GATE
LOCKS
SKYLOGIX USER ACCESS
KEYPAD MOUNTED ON
SKYLOGIX CABINET.
DMD & Associates Ltd.
#12-17358 104A Avenue
Surrey, BC, Canada V4N 5M3
www.dmdeng.com
office@dmdeng.com
604/589-9010
Fax 604/589-9012
DESIGNED
JASON FURNESS
DRAWN
ROB FRASER
CHECKED
DANIEL J. WONG
DATE
NOVEMBER 9, 2010
SERVICE KIOSK SINGLE LINE DIAGRAM
N.T.S.
EXISTING LOAD = 101.3 kVA
PROPOSED NEW LOAD = 57.8 kVA
NEW TOTAL LOAD = 159.1 kVA
FUTURE LOAD = 150.4 kVA
FUTURE TOTAL LOAD = 309.5 kVA
SYSTEM OPERATION:
RECOGNIZED PRODUCT LIST
1. OPERATION CONTROLLED VIA SKYLOGIX CONTROL AND USER KEYPAD (IE; LIGHTS ARE
ENABLED AND MAY OPERATE, FROM SUNDOWN TO A PRESET CURFEW TIME AS
DETERMINED BY THE CITY). CITY MAY OVERRIDE SKYLOGIX CONTROL VIA ON-AUTO-OFF
SWITCHES IN LIGHTING CONTROL CABINET. CONTRACTOR TO OBTAIN OPERATION
SCHEDULE FROM THE CITY AND SET-UP, COMMISION & TEST ALL LIGHTING CONTROLS.
PRODUCT
MANUFACTURER
SPECIFICATION
EXCEPTIONS / COMMENTS
SPORTS
LIGHTING
MUSCO LIGHTING OR
APPROVED ALTERNATE
GREEN LIGHT
SYSTEM
NO CONTROL LINK OR
SERVICE PLAN
SECURITY LUMINAIRE
G.E.
M.o.T.I.
FLAT GLASS
CONDUIT
IPEX
CSA C22-211.2
SCALE:
FOR EXISTING SPORTS LIGHTING
REFER TO DMD & ASSOCIATES
DRAWINGS 1398-05-01 TO -03
AS SHOWN
SEAL
NOT FOR CONSTRUCTION
2011-02-08
1. ALL SPORTS FIELD LTG. CONDUCTORS SHALL RUN CONTINUOUS WITH NO SPLICES.
No.
DATE
BY
CHK'D
REVISION
.
2010-11-10
JF
ISSUED FOR REVIEW
.
2010-11-22
JF
ISSUED FOR REVIEW
.
2010-12-21
JF
ISSUED FOR REVIEW
.
2011-01-14
JF
ISSUED FOR TENDER
1
2011-02-08
JF
ISSUED FOR ADDENDUM
van der Zalm + associates inc.
Suite 1 - 8938 192nd Street, Surrey, BC V4N 3W8 Tel: (604) 882-0024
2. INSTALL BOND IN EACH BRANCH CIRCUIT CONDUIT TO CEC REQUIREMENTS.
PLASTIC PULL
BOXES
WEST COAST ENGINEERING
M.o.T.I. LARGE ROUND PLASTIC
JUNCTION BOX COMPLETE WITH
LOCKABLE SECURITY LID
LOCKABLE SECURITY LID
SUPPLIED BY BILL MATHERS
CONTRACTING, PH: 604-825-7210,
FAX: 604-596-2042
SPORTSFIELD LIGHTING
TAMANAWIS PARK
SYNTHETIC FIELD HOCKEY FIELD
4. LABEL ALL TERMINAL BLOCKS WITH CIRCUITS AND POLE NUMBER.
RECEPTACLE
ENCLOSURE
5. CONTRACTOR TO COMMISSION, REPROGRAM, TEST & SET UP SKYLOGIX LIGHTING
CONTROL SYSTEM AS REQUIRED.
SURREY, BC
VALID MANUFACTURING
RWA 12015
PROJECT No.
DRAWING REFERENCE
1
1
SHEET No.
3215-10-02 of 03
REVISION
2 of 3
CANCEL PRINTS BEARING PREVIOUS LETTER
1
DMD (2010)
3. CONTRACTOR SHALL FIELD MEASURE AND RECORD THE ACTUAL VOLTAGE AND CURRENT
AT EACH BRANCH CIRCUIT BREAKER AND AT THE MAIN BREAKER IN THE LIGHTING CONTROL
CABINET AND AT EACH CIRCUIT BREAKER IN THE MUSCO BALLAST CABINETS ON EACH POLE.
THIS INFORMATION SHALL BE PROVIDED TO DMD & ASSOCIATES AT THE PROJECT
COMPLETION.