ELECTRICAL ADDENDUM To: Date: Hoa Ha, P.Eng. Firm: Project Number: RF Binnie & Associates Ltd. 101 – 19232 Enterprise Way Surrey, BC V3S 6J9 DMD & Associates Ltd. #12-17358 104A Avenue Surrey, BC V4N 5M3 604/589-9010 Fax 604/589-9012 Re: 2011-02-08 3215-10 From: Jason Furness, P.Eng. Tamanawis Park – Field Hockey Field #2 Surrey, BC Comments: The following changes/additions are required to the electrical design drawings 3215-10-01 to -03 of -03 (all changes indicated via revision 1 on the attached revised sheets 1 and 2): Sheet 1: 1. 2. 3. Scoreboard power circuit added. Receptacle cabinet added to the referee area c/w power circuit back to service kiosk. Communication cabinet added to the referee area c/w comm. duct, boxes and cable to the scoreboard. 1. 2. 3. 7-1800VA fixtures per pole, not 8-1800VA fixtures per pole. 20A-1P (half size circuit breaker) added for receptacle circuit in referee area. 15A-1P (half size circuit breaker) added for scoreboard power circuit. Sheet 2: Sheet 3: No changes required. Pacific Northwest Office: 1770 Front Street, PMB # 267 Lynden WA 98264 Toll Free: 877/249-8080 www.dmdeng.com The following changes are required to the electrical specifications: 1. The following change is made to SPECIFICATIONS – Sports Lighting, Item 2.01 Manufacturers: Item A, which shall now read: Available Products: Subject to compliance with requirements, products that may be incorporated in the work include: 1. Musco Lighting “Green Lighting System” (CONTROL LINK AND SERVICE PLAN WILL NOT BE REQUIRED) 2. Engineer Approved Alternate (refer to 1.02 above). 2. The following change is made to SPECIFICATIONS – Sports Lighting, Item 3.04 Independent Testing and Observations: Item A, which shall now read: The owners engineer will field measure and document the on-field illumination levels and uniformities in accordance with IESNA LM-5. Off-site spill light levels will also be measured along the residential boundary line. Levels will be measured at approximately 100 hours of lamp operation. Initial levels (at between 50 and 100 hours) shall be within 10 percent (10 %) of those shown on the Suppliers design. If the lighting fails to meet the required levels additional cost for the engineer to re-measure and retest the field lighting ($1,000.00 per test) shall be paid for by the lighting supplier. Supplier measurement of the lighting levels will not be acceptable. 1-50mm RPVC 4 No.10 RW90 POLE F1 4 No. 8 RW90 POLE F2 3 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND EXIST. 1-50mm RPVC 8 No. 6 RW90 SPORTS LIGHTING 1 No. 8 RW90 BOND LEGEND: 1-50mm RPVC 2 No. 8 RW90 RECEPTACLE (F1) 2 No. 4 RW90 RECEPTACLE (F2) 2 No. 4 RW90 SCOREBOARE PWR. 2 No.10 RW90 GATE LOCKS 1 No. 8 RW90 BOND EXIST. 1-50mm RPVC 2 No. 10 RW90 SECURITY LTG 2 No. 1 RW90 RECEPT. PWR. 1 No. 12 RW90 BOND 1-30mm RPVC/RMC 2 No.10 RW90 GATE LOCKS 1 No.12 RW90 BOND (FROM JB TO GATE LOCK) TO EXIST. IRRIGATION BOOSTER PUMP AND IRRIGATION PLC EXIST. 1-75mm RPVC 2 No. 10 RW90 SECURITY LTG 2 No. 12 RW90 GATE LOCKS 2 No. 1 RW90 RECEPT. PWR. 1 No. 12 RW90 BOND 1 No.12 RW90 BOND 2 No. 8 RW90 RECEPTACLE (F1) 2 No. 4 RW90 RECEPTACLE (F2) 2 No. 4 RW90 RECEPTACLE (F3) 2 No. 8 RW90 RECEPTACLE (F4) 2 No. 4 RW90 SCOREBOARE PWR. 2 No. 6 RW90 RECEPTACLE (REF. AREA) 2 No.10 RW90 GATE LOCKS 1 No. 6 RW90 BOND EXIST. 1-75mm RPVC (EMPTY) 4 No.10 RW90 POLE F1 4 No. 8 RW90 POLE F2 4 No. 8 RW90 POLE F3 4 No.10 RW90 POLE F4 4 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND 1 1-50mm RPVC 2 No. 4 RW90 RECEPTACLE (F2) 2 No. 4 RW90 SCOREBOARE PWR. 2 No.10 RW90 GATE LOCKS 1 No. 8 RW90 BOND PROPOSED UNDERGROUND RPVC CONDUIT AND CONDUCTORS 1-25mm RPVC / RMC 2 No. 4 RW90 RECEPTACLE (F2) 1 No. 8 RW90 BOND (FROM JB TO RECEPTACLE ENCLOSURE) 1 EXISTING UNDERGROUND RPVC CONDUIT AND CONDUCTORS R 1-50mm RPVC (EMPTY) (FROM JB TO POLE) 1-50mm RPVC (EMPTY) 1-50mm RPVC (EMPTY) (FROM JB TO POLE) 1-30mm RPVC/RMC 2 No.10 RW90 GATE LOCKS 1 No.12 RW90 BOND (FROM JB TO GATE LOCK) EXIST. IRRIGATION KIOSK PROPOSED LARGE ROUND PLASTIC PULL BOX (MoTI SPEC.) C/W SECURITY LOCKABLE LID (LABELED 'COMM') C PROPOSED GFCI 120V RECEPTACLE ENCLOSURE 1-25mm RPVC / RMC 2 No. 8 RW90 RECEPTACLE (F1) 1 No.10 RW90 BOND (FROM JB TO RECEPTACLE ENCLOSURE) EXIST. 1-75mm RPVC 16 No. 6 RW90 SPORTS LIGHTING 1 No. 8 RW90 BOND EXIST. 1-75mm RPVC 3 No. 6 RW90 IRRIGATION BOOSTER PUMP 2 No. 10 RW90 IRRIGATION PLC PWR 2 No. 10 RW90 WASHROOM BLD. FEEDER 1 No. 8 RW90 BOND PROPOSED LARGE ROUND PLASTIC PULL BOX (MoTI SPEC.) C/W SECURITY LOCKABLE LID 1-50mm RPVC 4 No. 8 RW90 POLE F2 2 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND (FROM JB TO POLE) 1-50mm RPVC 4 No. 8 RW90 POLE F2 2 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND 1-50mm RPVC 4 No.10 RW90 POLE F1 2 No.10 RW90 SECURITY LTG 1 No.12 RW90 BOND (FROM JB TO POLE) TO TU EX RF IST FIE . SY LD NT HO HE CK TIC EY EXIST. 1-50mm RPVC 2 No. 12 RW90 GATE LOCKS 2 No. 10 RW90 SECURITY LTG 1 No. 12 RW90 BOND PROPOSED 250W HPS SECURITY LUMINAIRE ON SPORTS LIGHT POLE 1 1-50mm RPVC (EMPTY) EXIST. 1-50mm RPVC 8 No. 6 RW90 SPORTS LIGHTING 1 No. 8 RW90 BOND PROPOSED GALVANIZED STEEL SPORTSLIGHTING POLE WITH 1500W-347V M.H. SPORTLIGHTS SECURITY LUMINAIRE ON RED PHASE CONDUCTOR BK SECURITY LUMINAIRE ON BLACK PHASE CONDUCTOR BL SECURITY LUMINAIRE ON BLUE PHASE CONDUCTOR F1 SPORTS LIGHTING POLE NUMBER NOTES: 1-50mm RPVC 2 No. 4 RW90 SCOREBOARD PWR. 1 No. 8 RW90 BOND 1. ALL WORK SHALL CONFORM TO THE MOST CURRENT EDITION OF THE CANADIAN ELECTRICAL CODE C.S.A.-C22.1 AND ANY BULLETINS ISSUED BY THE ELECTRICAL SAFETY BRANCH. 1 2. SPORTSLIGHTING POLES, POLE TOP LUMINAIRE ASSEMBLY, INTERNAL WIRING HARNESS, ELECTRICAL COMPONENT ENCLOSURE AND PRE-CAST CONCRETE BASE SHALL BE SUPPLIED AS A PACKAGE. PACKAGE DOES NOT INCLUDE SECURITY LIGHTING, RECEPTACLE ENCLOSURE, AND RELATED WIRING. EXIST. CONCRETE VAULT F1 F2 SPILL LIGHT BOUNDARY LINE 1 R BK 3. IDENTIFY ALL CIRCUITS IN ALL JUNCTION BOXES, TERMINAL BLOCK IN SERVICE CABINET, AT THE DISCONNECT BREAKER IN THE SPORTSLIGHTING BALLAST BOX AND SECURITY LIGHTING CIRCUITS IN THE POLE HANDHOLE WITH SLEEVE TYPE WIRE MARKERS. EACH FEEDER SHALL BE LABELED WITH THE CIRCUIT No. (I.E. CCT1, CCT3, CCT5. ETC). 1-50mm RPVC/32mm RMC 2 No. 4 RW90 SCOREBOARD PWR. 1 No. 8 RW90 BOND (FROM PB TO SCOREBOARD) 1 4. ALL CONDUCTORS SHALL BE STRANDED COPPER WITH RW90 INSULATION. SPORTS LIGHTING CONDUCTORS SHALL RUN CONTINUOUS WITH NO SPLICES. 1 5. CONTRACTOR SHALL EXCAVATE FOUNDATION AND GAIN APPROVAL FROM GEOTECHNICAL ENGINEER PRIOR TO FOUNDATION INSTALLATION. BACK FILL SHALL MEET THE APPROVAL OF THE GEOTECHNICAL ENGINEER. 6. INSTALL CITY PADLOCKS ON SPORTSLIGHTING BALLAST BOXES AND RECEPTACLE ENCLOSURES. 35.0m (TYP.) TO EXIST. PARKING LOT LIGHTING C SCOREBOARD. REFER TO R.F. BINNIE DESIGN DRAWINGS FOR EXACT LOCATION AND TYPE OF SCOREBOARD. EXIST. 1-50mm RPVC (120/240V) 3 No.10 RW90 PARKING LOT LIGHTING 3 No.10 RW90 PHOTOCELL 1 No.12 RW90 BOND 1-50mm RPVC/32mm RMC COMM. 1-2PR No.24 SCOREBOARD CONTROL CABLE (BELDEN 9502) (FROM PB TO SCOREBOARD) EXIST. 1-50mm RPVC (EMPTY) 7. CONDUITS SHALL BE INSTALLED IN A COMMON TRENCH. 1 8. A TRON HEB SERIES WATER-RESISTANT FUSE HOLDER C/W A 10A BUSS KTK 10 FUSE & 2 INSULATING BOOTS SHALL BE INSTALLED IN EACH SECURITY LUMINAIRE LIVE CONDUCTOR, IN THE HANDHOLE. 9. BEFORE DMD CAN PROVIDE A FINAL INSPECTION THE CONTRACTOR MUST ENSURE THAT THE ENTIRE ELECTRICAL SYSTEM IS FULLY FUNCTIONAL AND THAT SUBSTANTIAL COMPLETION HAS BEEN OBTAINED. 1 10. ALL EXPOSED CONDUIT SHALL BE RMC. EXISTING SERVICE KIOSK REFERENCE POINT VALID MANUFACTURING LTD. WEATHERPROOF LOCKABLE COMMUNICATION CABINET WITH IN-USE COVER (POWDER COATED BLACK) C/W COMMUNICATION CONNECTOR (COORDINATE COMM. CONNECTOR DETAILS WITH SCOREBOARD SUPPLIER). CABINET TO BE MOUNTED SECURELY TO FENCE POST. EXIST. 2-100mm RPVC (SECONDARY SERVICE CONDUCTORS) VALID MANUFACTURING LTD. WEATHERPROOF LOCKABLE RECEPTACLE CABINET WITH IN-USE COVER C/W 15A-120V GFCI RECEPTACLE AND 15A-1P BREAKER (POWDER COATED BLACK). CABINET TO BE MOUNTED SECURELY TO FENCE POST. EXISTING BC HYDRO PAD MOUNT TRANSFORMER EXIST. 3-75mm RPVC (PRIMARY SERVICE CONDUCTORS) 1 1-50mm RPVC 4 No. 8 RW90 POLE F3 4 No.10 RW90 POLE F4 3 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND 1 SPORTS LIGHTING DESIGN CRITERIA 35.0m (TYP.) FIELD TYPE SYNTHETIC FIELD HOCKEY FIELD FIELD DIMENSIONS TO EXISTING SERVICE POLE 1-50mm RPVC 2 No. 4 RW90 RECEPTACLE (F3) 2 No. 8 RW90 RECEPTACLE (F4) 2 No. 6 RW90 RECEPTACLE (REF. AREA) 1 No. 8 RW90 BOND 101.4m X 61.0m R BL F4 C DESIGN CALCULATED TAMANAWIS PARK LOCATION 1 REFEREE AREA DESIGN REQUIREMENTS ITEM EQUIPMENT TYPE 21.3m - 1500W MH SPORTSLIGHT C/W EXTERNAL VISORS MAINTAINED ILLUMINATION LEVEL (AVG.) 370 LUX . 2.0:1 . F3 1 50.0m (TYP.) 1-50mm RPVC (EMPTY) UNIFORMITY RATIO (MAX.:MIN.) 50.0m (TYP.) 1-50mm RPVC COMM. 1-2PR No.24 SCOREBOARD CONTROL CABLE (BELDEN 9502) 64 AVENUE 1 DMD & Associates Ltd. #12-17358 104A Avenue Surrey, BC, Canada V4N 5M3 www.dmdeng.com office@dmdeng.com 1-50mm RPVC 4 No.10 RW90 POLE F4 2 No.10 RW90 SECURITY LTG 1 No.12 RW90 BOND (FROM JB TO POLE) 1-50mm RPVC 4 No. 8 RW90 POLE F3 2 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND SITE PLAN 0 1:500 1-50mm RPVC 4 No. 8 RW90 POLE F3 2 No.10 RW90 SECURITY LTG 1 No.10 RW90 BOND (FROM JB TO POLE) 25 1-50mm RPVC 2 No. 4 RW90 RECEPTACLE (F3) 1 No. 8 RW90 BOND 1-25mm RPVC / RMC 2 No. 8 RW90 RECEPTACLE (F4) 1 No.10 RW90 BOND (FROM JB TO RECEPTACLE ENCLOSURE) 1-25mm RPVC / RMC 2 No. 4 RW90 RECEPTACLE (F3) 1 No. 8 RW90 BOND (FROM JB TO RECEPTACLE ENCLOSURE) 1-50mm RPVC (EMPTY) 1-50mm RPVC (EMPTY) (FROM JB TO POLE) 1-50mm RPVC (EMPTY) (FROM JB TO POLE) 1-32mm RPVC/RMC COMM. 1-2PR No.24 SCOREBOARD CONTROL CABLE (BELDEN 9502) (FROM PB TO COMM. CABINET) 1-50mm RPVC 2 No. 4 RW90 RECEPTACLE (F3) 2 No. 6 RW90 RECEPTACLE (REF. AREA) 1 No. 8 RW90 BOND 1 1-32mm RPVC/RMC 2 No. 6 RW90 RECEPTACLE (REF. AREA) 1 No. 8 RW90 BOND (FROM PB TO RECEPTACLE CABINET) CONTRACTOR SHALL REFER TO MUNICIPAL RECORD / CIVIL DESIGN DRAWINGS FOR ALL OTHER UTILITIES, SERVICE LOCATIONS, AND DETAILS. THE EXACT LOCATION OF THESE UTILITIES SHALL BE DETERMINED ON SITE BY THE CONTRACTOR. PULL BOX LOCATIONS SHOWN FOR DIAGRAMMATIC PURPOSE ONLY ROB FRASER CHECKED DANIEL J. WONG DATE NOVEMBER 9, 2010 SCALE: 1:500 NOT FOR CONSTRUCTION No. DATE BY CHK'D REVISION . 2010-11-10 JF ISSUED FOR REVIEW . 2010-11-22 JF ISSUED FOR REVIEW . 2010-12-21 JF ISSUED FOR REVIEW . 2011-01-14 JF ISSUED FOR TENDER 1 2011-02-08 JF ISSUED FOR ADDENDUM van der Zalm + associates inc. Suite 1 - 8938 192nd Street, Surrey, BC V4N 3W8 Tel: (604) 882-0024 SPORTSFIELD LIGHTING TAMANAWIS PARK SYNTHETIC FIELD HOCKEY FIELD SURREY, BC PROJECT No. 1 1 1 1 1 1 1 1 SHEET No. 3215-10-01 of 03 DRAWING REFERENCE 1 DRAWN 2011-02-08 CHECK BEFORE YOU DIG 1 JASON FURNESS SEAL 1-50mm RPVC (EMPTY) 1 DESIGNED 1 REVISION 1 of 3 CANCEL PRINTS BEARING PREVIOUS LETTER 1 DMD (2010) 1 FOR EXISTING SPORTS LIGHTING REFER TO DMD & ASSOCIATES DRAWINGS 1398-05-01 TO -03 604/589-9010 Fax 604/589-9012 B.C. HYDRO PMT 300kVA 25kV347/600V 3Ø 4W K 1 - 100mm RPVC (BCH SERVICE CONDUCTORS) KIOSK ENCLOSURE 1-3/0 COPPER TO 20mmØ x 3000mm LONG GROUND RODS 600A 3PSN NEW BREAKERS AND PANELS SHALL BE RATED FOR 18kA INTERRUPTING CURRENT 100:5 B.C. HYDRO SERVICE METER M 600V- 200V 84 CCT. 600A, 347/600V, 3Ø, 4W, DISTRIBUTION PANEL (18kA INTERRUPTING CURRENT) C22 30A-3P C24 30A-1P C23 30A-3P 30A 3P 80A 3P 30A 3P C1 30A-3P 30A 3P C3 30A-3P C2 30A-3P CCT 29 15A 1P 30A 3P 30A 3P C5 30A-3P C18 15A-3P C4 30A-3P 30A 3P 30A 3P C6 30A-3P 30A 3P C7 30A-3P 30A 3P C8 30A-3P 30A 3P C9 30A-3P 30A 3P 30A 3P C11 30A-3P C10 30A-3P 30A 3P 30A 3P C13 30A-3P C12 30A-3P 30A 3P C14 30A-3P 30A 3P 30A 3P C15 30A-3P C16 30A-3P 15A 2P LIGHTING CONTROL CABINET & FIELD WIRING (SEE LIGHTING CONTROL SCHEMATIC FOR WIRING DETAILS) C17 30A-3P FUTURE WIRING (TYP.) & BOND C21 30A-3P CCT 25 & 27 30A 2P 15A-1P 2 No. 10 RW90 C20 30A-3P 20A-3P 3 No. 6 RW90 & BOND HID LIGHTING CONTACTORS (TYPICAL) 20A-3P 3 No.10 RW90 & BOND 1 No. 10 RW90 20A-3P 20A-3P 2 No.12 RW90 WASHROOM 30HP IRRIGATION POLE No. S1 POLE No. S2 POLE No. S3 POLE No. S4 BLD FEEDER BOOSTER PUMP 7x1500W 7x1500W 7x1500W 7x1500W 4 No.10 RW90 & BOND 4 No.10 RW90 & BOND 4 No. 8 RW90 & BOND 4 No. 8 RW90 & BOND 4 No.10 RW90 & BOND TERMINAL BLOCK (TYPICAL) 400W HPS SECURITY LTG ON SPORTS POLES (3KVA) SOUTH SOUTH SOUTH SOUTH SOUTH NORTH NORTH NORTH NORTH NORTH SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL SOFTBALL 20 kW 20 kW AND FIELD FIELD FIELD FIELD FIELD FIELD FIELD FIELD FIELD FIELD (FUTURE) (FUTURE) BASKETBALL FIELD HOCKEY POLE No. A1 POLE No. B1 POLE No. C1 POLE No. A2 POLE No. B2 POLE No. A2 POLE No. B2 POLE No. C2 POLE No. A3 POLE No. B3 COURTS (50.4kVA) 3.3 kW 11.7 kW 16.7 kW 3.3 kW 16.7 kW 3.3 kW 16.7 kW 16.7 kW 3.3 kW 11.7 kW 7 kW TENNIS COURTS TENNIS COURTS BALL HOCKEY 7.5 kVA 600V120/240V 1Ø 3W DRY TYPE (FUTURE) 16 CCT., 100A. 120/240V, 1Ø, 3W, LOAD CENTRE FIELD WIRING (TYPICAL) ZONE 2-D SPARE ZONE 3-N GATE LOCKS (C19) ZONE 3-D SPARE ZONE 4-N POLES F1 & F2 (C20 & C21) ZONE 4-D POLES F3 & F4 (C22 & C23) ZONE 5-N SECURITY LIGHTING (C24) ZONE 5-D SPARE ZONE 6-N GATE LOCKS (C25) ZONE 6-D SPARE ZONE 7-N SPARE ZONE 7-D SPARE ZONE 8-N SPARE ZONE 8-D SPARE 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P 20A 1P 15A 1P 15A 1P 15A 1P KIOSK LIGHTS 2x100W KIOSK RECEPTACLE 1440W PARKING LOT 15A 1P LIGHTING PHOTOCELL 2 kW GFCI GATE LOCKS CONVENIENCE RECEPTACLE ENCLOSURE ON POLE F1 (1.0kVA) GFCI CONVENIENCE RECEPTACLE ENCLOSURE ON POLE F2 (1.0kVA) GFCI GFCI GFCI CONVENIENCE RECEPTACLE ENCLOSURE ON POLE F3 (1.0kVA) CONVENIENCE RECEPTACLE ENCLOSURE ON POLE F4 (1.0kVA) CONVENIENCE RECEPTACLE ENCLOSURE IN REFEREE AREA (1.0kVA) TO SCOREBOARD (1.2kVA) POWER SUPPLY 120V AC TO 24V DC MIN 20 WATTS FIELD WIRING KIOSK HEATER 500W SKYLOGIX LTG CONTROLLER (REFER TO SKYLOGIX WIRING DIAGRAM SKYLOGIX ARC 10 CONTROL SYSTEM 8 ZONE UNIT IN NEMA 3R CABINET MOUNTED TO SIDE OF IRRIGATION KIOSK. PLC PWR 1 & BOND C19 15A-1P FIELD WIRING 15A 1P LIGHT SWITCH 2 No. 1 RW90 & BOND 2 No. 4 RW90 & BOND 2 No. 6 RW90 T/STAT POWER SUPPLY & BOND POLES S3 & S4 (C3 & C4) SECURITY LIGHTING (C18) 15A 1P 2 No.10 RW90 & BOND 2 No.10 RW90 POLES S1 & S2 (C1 & C2) ZONE 2-N 30A 2P PARKING LOT LIGHTING CONTROL PANEL POWER SUPPLY 120V AC TO 24V DC MIN 20 WATTS LIGHTING CONTROL ZONES (SKYLOGIX SYSTEM) ZONE 1-D & BOND C25 15A-1P 1 2 No. 8 RW90 7-1800VA FIXTURES & BOND 7-1800VA FIXTURES FIELD HOCKEY (50.4kVA) ZONE 1-N 15A 1P (HALF SIZE CIRCUIT BREAKER) T 2 No. 4 RW90 7-1800VA FIXTURES 20A 1P (HALF SIZE CIRCUIT BREAKER) 2 No.12 RW90 SECURITY LIGHTING 4-250W (1.2 kVA) 7-1800VA FIXTURES 20A 1P (HALF SIZE CIRCUIT BREAKER) 20A 1P (HALF SIZE CIRCUIT BREAKER) F4 & BOND F3 20A 1P (HALF SIZE CIRCUIT BREAKER) 2 No. 4 RW90 F2 & BOND F1 & BOND POLE NUMBER (TYPICAL) 20A 1P (HALF SIZE CIRCUIT BREAKER) 15A 1P (HALF SIZE CIRCUIT BREAKER) ELECTRICAL CABINET ON POLE (TYPICAL) 2 No. 8 RW90 3P BREAKERS SUPPLIED WITH CABINET (TYP.) 15A 1P CONVENIENCE RECEPTACLE ENCLOSURE IN OFFICIALS BOOTH GATE LOCKS SKYLOGIX USER ACCESS KEYPAD MOUNTED ON SKYLOGIX CABINET. DMD & Associates Ltd. #12-17358 104A Avenue Surrey, BC, Canada V4N 5M3 www.dmdeng.com office@dmdeng.com 604/589-9010 Fax 604/589-9012 DESIGNED JASON FURNESS DRAWN ROB FRASER CHECKED DANIEL J. WONG DATE NOVEMBER 9, 2010 SERVICE KIOSK SINGLE LINE DIAGRAM N.T.S. EXISTING LOAD = 101.3 kVA PROPOSED NEW LOAD = 57.8 kVA NEW TOTAL LOAD = 159.1 kVA FUTURE LOAD = 150.4 kVA FUTURE TOTAL LOAD = 309.5 kVA SYSTEM OPERATION: RECOGNIZED PRODUCT LIST 1. OPERATION CONTROLLED VIA SKYLOGIX CONTROL AND USER KEYPAD (IE; LIGHTS ARE ENABLED AND MAY OPERATE, FROM SUNDOWN TO A PRESET CURFEW TIME AS DETERMINED BY THE CITY). CITY MAY OVERRIDE SKYLOGIX CONTROL VIA ON-AUTO-OFF SWITCHES IN LIGHTING CONTROL CABINET. CONTRACTOR TO OBTAIN OPERATION SCHEDULE FROM THE CITY AND SET-UP, COMMISION & TEST ALL LIGHTING CONTROLS. PRODUCT MANUFACTURER SPECIFICATION EXCEPTIONS / COMMENTS SPORTS LIGHTING MUSCO LIGHTING OR APPROVED ALTERNATE GREEN LIGHT SYSTEM NO CONTROL LINK OR SERVICE PLAN SECURITY LUMINAIRE G.E. M.o.T.I. FLAT GLASS CONDUIT IPEX CSA C22-211.2 SCALE: FOR EXISTING SPORTS LIGHTING REFER TO DMD & ASSOCIATES DRAWINGS 1398-05-01 TO -03 AS SHOWN SEAL NOT FOR CONSTRUCTION 2011-02-08 1. ALL SPORTS FIELD LTG. CONDUCTORS SHALL RUN CONTINUOUS WITH NO SPLICES. No. DATE BY CHK'D REVISION . 2010-11-10 JF ISSUED FOR REVIEW . 2010-11-22 JF ISSUED FOR REVIEW . 2010-12-21 JF ISSUED FOR REVIEW . 2011-01-14 JF ISSUED FOR TENDER 1 2011-02-08 JF ISSUED FOR ADDENDUM van der Zalm + associates inc. Suite 1 - 8938 192nd Street, Surrey, BC V4N 3W8 Tel: (604) 882-0024 2. INSTALL BOND IN EACH BRANCH CIRCUIT CONDUIT TO CEC REQUIREMENTS. PLASTIC PULL BOXES WEST COAST ENGINEERING M.o.T.I. LARGE ROUND PLASTIC JUNCTION BOX COMPLETE WITH LOCKABLE SECURITY LID LOCKABLE SECURITY LID SUPPLIED BY BILL MATHERS CONTRACTING, PH: 604-825-7210, FAX: 604-596-2042 SPORTSFIELD LIGHTING TAMANAWIS PARK SYNTHETIC FIELD HOCKEY FIELD 4. LABEL ALL TERMINAL BLOCKS WITH CIRCUITS AND POLE NUMBER. RECEPTACLE ENCLOSURE 5. CONTRACTOR TO COMMISSION, REPROGRAM, TEST & SET UP SKYLOGIX LIGHTING CONTROL SYSTEM AS REQUIRED. SURREY, BC VALID MANUFACTURING RWA 12015 PROJECT No. DRAWING REFERENCE 1 1 SHEET No. 3215-10-02 of 03 REVISION 2 of 3 CANCEL PRINTS BEARING PREVIOUS LETTER 1 DMD (2010) 3. CONTRACTOR SHALL FIELD MEASURE AND RECORD THE ACTUAL VOLTAGE AND CURRENT AT EACH BRANCH CIRCUIT BREAKER AND AT THE MAIN BREAKER IN THE LIGHTING CONTROL CABINET AND AT EACH CIRCUIT BREAKER IN THE MUSCO BALLAST CABINETS ON EACH POLE. THIS INFORMATION SHALL BE PROVIDED TO DMD & ASSOCIATES AT THE PROJECT COMPLETION.