LIMITRON™ Class L KLU — 600Vac, 601-4000A, Time-Delay Fuses Dimensions – in All other tolerances (± 0.02) 0.88" 1.75" 0.38" 0.38" 2" 2.5" 2" 2.5" 0.44" 1800 to 2000A 0.5" 2.38" 2.75" 3" 3.5" 1.38" 1.75" 0.81" All Slots and Holes 0.63" (± 0.03) 8.63" (± 0.09) 601 1000 1500 6.75" to 10.75" 5.75" to to (± 0.09) 800A 1200A 1600A 1.63" 1.38" 0.88" 2500A 3000A 3500 to 4000A 0.75" 0.75" 0.75" 3.5" 5" 4" 5" 6.75" 3.75" 4.75" 5.75" Terminals: Width (± 0.06), Thickness (± 0.03) Description: Advanced protection Class L time-delay, currentlimiting fuses. Time-delay – 5 seconds (minimum) at 500% of rated current. Catalog Symbol: KLU-(amp) Ratings: Volts — 600Vac Amps — 601-4000A* IR — 200kA Vac RMS Sym. Features: • KLU Limitron general purpose copper link fuses • Copper links result in a minimum 5 second time-delay at 500% ampere rating • Current-limiting – provides component short-circuit protection • 200kA interrupting rating complies with NEC® Sections 110.9 and 230.65 in today’s large capacity systems • Selective coordination (blackout prevention) Recommended Fuse Blocks — 601 to 1200 Amps† * Use KRP-CL for current ratings from 225 to 600 amps. Agency Infortmation: CE, UL Listed, Std. 248-10, Class L, Guide JDDZ, File E4273 CSA Certified, C22.2 No. 248.10, Class 1422-02, File 53787 RoHS Compliant Catalog Numbers 51215 51235 Poles 1 3 † No Agency listings available. No reducers available. Catalog Numbers (amps) KLU–601 KLU–650 KLU–700 KLU–800 KLU–1000 KLU–1200 KLU–1500 KLU–1600 KLU–1800 KLU–2000 KLU–2500 KLU–3000 KLU–4000 Carton Quantity and Weight Amp Rating 601-800 1000-1200 1500-1600 1800-2000 2500 3000 4000 0713 Carton Qty. 1 1 1 1 1 1 1 BU-SB13725 Page 1 of 3 Data Sheet # 1013 LIMITRON™ Class L KLU — 600Vac, 601-4000A, Time-Delay Fuses 4000A 1200A 1600A 2000A 3000A 300 800A Time-Current Curves - Average Melt AMP RATING 100 TIME IN SECONDS 10 1 CURRENT IN AMPS 0713 BU-SB13725 Page 2 of 3 100,000 1,000 0.01 10,000 0.1 Data Sheet # 1013 LIMITRON™ Class L KLU — 600Vac, 601-4000A, Time-Delay Fuses B 400,000 4000 3000 2500 2000 1600 1200 800 AMP RATING 100,000 10,000 10,000 200,000 1,000 100,000 A 1,000 INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES Current-Limitation Curves PROSPECTIVE SHORT-CIRCUIT CURRENT SYMMETRICAL RMS AMPS The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 0713 BU-SB13725 Page 3 of 3 Data Sheet # 1013