Special Feature High Resistance Grounding… Is It More Than Just a Big Heater? by Chris Gingras Magna Electric Corp. A s part of our standard testing and inspection routine during maintenance outages and commissioning, we inspect and test the neutral grounding resistor, commonly referred to as a NGR. A NGR is connected to the X0 point or star connection point of a wye-connected transformer. The purpose of the NGR is to control the amount of current flow into a ground fault in the event of insulation failure of one of the normally energized conductors to ground. When a ground fault occurs the current path back to the source (which in this case is the wye connected power transformer) contains a high resistance. In many cases the ground fault current is limited to 10 amperes or less. When the ground fault current exceeds a specified pickup point, a NGR monitor or ground-fault relay is used to alarm the presence of the ground fault, or trip the upstream breaker to clear the faulted circuit. The Canadian Electrical Code states that any system rated 5 kV or less that does not serve single-phase loads is permitted to sustain a ground fault if the available current is limited to 10 amperes or less and an audible or visual alarm is present to enunciate the presence of a ground fault. When properly applied, a NGR can prevent catastrophic damage to equipment and injury to personnel. When specifying, designing, or commissioning a system which is to contain a NGR, a few important items should be considered. First and foremost, is the system going to service single-phase loads? Secondly, what is the phase-to-ground voltage rating required for the NGR? This needs to be known in order to properly select the required resistance, which is point three. What is the maximum ground fault current the system should be designed to handle? I have come across errors in each of these design steps during commissioning, maintenance, and call outs. First, does the system service single-phase loads? If a system services single-phase loads and uses a high-resistance grounding system, nuisance trips may occur and the single-phase loads will receive lower voltage than expected. Energized with no load, the single-phase system will appear normal. Once load is applied, the voltage at the load will drop considerably and www.netaworld.org the upstream ground-fault protection may trip. This is due to the fact that the single phase load is now connected in series electrically with a relatively large resistance. Once the load is turned on, the voltage drop across the resistance is large and the voltage at the singlephase load is limited. Next, what is the voltage rating and resistance required of the NGR? Instances have come up where the designer has taken the phase-to-phase rating of the system and chosen the resistance of the NGR based on that voltage. While this may not seem to be a huge oversight, the ground-fault current will not reach the expected value. A system improperly designed may not detect a ground fault. For example, a 4160 volt wyeconnected system has a phase-toground voltage of 2400 volts. A proper resistance rating for a five ampere NGR is 480 ohms. If the phase-tophase voltage is used for the resistance calculation the NGR would be specified to be 832 ohms. In this case the maximum permissible ground fault current would be 2.9 amperes, which may be well below the ground-fault alarm or trip setting. If this ground fault is left unchecked, it will only be a matter of time before another phase faults to ground and the system will now have a phase-to-phase fault. Fall 2008 NETA WORLD Another very commonly missed design and commissioning step when working with high resistance grounded systems is the insulation coordination. Now that we have inserted a high resistance between the X0 bushing and system ground, the phase-to-ground voltage on the unfaulted phases may now measure as high as the phase-to-phase voltage in the event of a ground fault. This is due to the fact that the neutral point voltage is shifted from ground potential by the voltage drop across the grounding resister. Since the resister limits ground-fault current to a low value, there is little voltage drop in the faulted phase. Thus, the faulted phase is at ground potential while the other two phases remain close to the normal phase-to-phase voltage raising their voltage to ground to that value. If this system has surge arresters installed, the maximum continuous operating voltage (MCOV) of the arrester may be exceeded during the ground fault. For example, suppose that a 4160 volt phase-to-phase system has a 100 ampere NGR installed on the neutral bushing (X0) of the source transformer. For a solidly grounded system, a surge arrester would be chosen which would have a rating in the neighborhood of 10-15 percent higher than the phase-to-ground voltage, which in this case is 2400 volts. If this arrester were installed on a system as described previously, the MCOV of the arresters would be exceeded on the unfaulted phases in the event of a ground fault. I have come across situations in the past where a system was changed from a solidly-grounded system to a high-resistance grounded system and the surge arresters were not changed to ones having a higher voltage rating. When you receive a call out and someone tells you that they had two of three surge arresters fail in a particular location, I would first investigate the ratings of the surge arresters before continuing on the trail for the source of the problem. The reason for having only two surge arresters fail is due to the fact that only two phase-to-ground voltages have exceeded the arrester MCOV rating during a single phase-to-ground fault. In a recent maintenance outage we were asked to test the two main transformers at an industrial plant. Each transformer was rated for 20 MVA and they were connected in delta on the primary and wye on the secondary with an NGR on the star point; the NGR’s are rated for 100 amperes. During the routine inspection of the NGR’s, we noticed that the connection between the transformer and NGR was no longer made. The crimped lug on the cable from the NGR was found disconnected from its intended connection point and hanging loose inside the NGR enclosure. Not only was the one NGR not connected to the X0 bushing, but the second transformer which is commonly paralleled with the first had a broken connection from the NGR to the main ground grid, which left this NGR floating from ground as well. In the event of a ground fault in this case, the ground fault relays would not detect any problem. The system disturbance would need to advance to the point of a phase-to-phase fault before any relaying would detect a problem since there is no path back to the source. This NETA WORLD Fall 2008 poses a serious personnel and equipment risk, and this is one of the many reasons why the NETA Maintenance Testing Specifications should be followed when performing maintenance or acceptance testing. We depend on the proper operation of our electrical systems to provide continuity of service, proper personnel and equipment protection in the event of system abnormalities, and proper isolation of faulted systems. It is key that grounding systems are inspected and tested on a regular basis along with the source transformers. Chris Gingras, Technical Services Manager for Magna Electric Corporation in Regina, SK, has 10 years of experience in plant start-up, commissioning, maintenance, and design of relay protection and control systems rated up to 365 kV. Chris has performed arc-flash hazard assessment studies and designed and installed numerous turn key arc-flash mitigation relay systems to protect personnel and equipment from the dangers of arc-flash hazards. He is a NETA Certified Level IV Test Technician. www.netaworld.org