Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page Prepared Verified Approved 0 22/10/2015 1 OF 13 T. Warren R. Caramanno R. Benini Operation: In standby to the mains or in Island mode Application: In standby to the mains or in Island mode Power: 20MW / 25MVA Prime power, 11kV, 3 phase, 50Hz, 0.8 p.f., 1500rpm @ ISO 3046 conditions with a 10% overload for one hour every 12 of the normal load. DGS-MT-2500 Code product: Client Specification Ref.ASCOT’s Offer ASCOT INDUSTRIAL Srl Zona Industriale Terza Strada 93012 Gela (CL) – Italy Last Modified Date 30/08/2013 TURNKEY PRICE LIST www.ascotinternational.com Tel. +39 0933 901192 Fax +39 0933 915614 sales@ascotinternational.com Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 2 OF 13 OVERVIEW Choosing the Ascot Group today means trusting an organisation with a 27 years experience in the international sphere, with a brand name which is a by word for quality and reliability. Since 1986, Ascot is manufacturing in Italy Diesel Generators and power plants specifically designed to work in different climatic condition for the International market. Ascot Group is considered as one of the most important players in the energy sector due to an active population of 34.254 generators, spread out globally in 42 countries. Choosing the Ascot Group means not only acquiring a quality product, designed to function in different parts of the world, but also a company which is capable of meeting all customer’s needs serviced by its partners’ network and Service Centers all encouraging technological innovation. The markets historically recognizes Ascot as a leader in the gen set and power plant sector thanks to its innovative products and technologies for generators and for the family of Hybrid solutions. This is the true know-how of Ascot, made of competence, flexibility, and understanding all its customer’s needs for which designs and manufacturers products order by order with a price structure, that is in proportion to the tailor made solutions offered. Key Benefits of Ascot’s solutions - Low emission and Long Life reliability thanks to European / best quality engines and components manufactured as per Ascot specifications; - Harsh environmental conditions capabilities thanks to the Ascot worldwide proven experience in designing & manufacturing of products to operate in any ambient conditions; - Design of tailor made solutions having low CAPEX and low OPEX. - Minimal Installation Costs thanks to all in one package. - Flexiblity & interchangeability units, thanks to the integrated features that operates in single or dual operation mode as standard configuration without any additional change. - All Ascot products are ready to be remotely controlled, on request, with web based management system, LAN system or GSM system or simply by free contacts for NOC. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 3 OF 13 INDEX 1. INTRODUCTION ............................................................................................................................................. 4 1.1. Benefits of MTU engine ....................................................................................................................... 4 1.2. Benefits of European Brand alternator ............................................................................................ 4 1.3. Benefits of gen set auxiliaries ............................................................................................................ 4 2. SCOPE OF SUPPLY ........................................................................................................................................ 4 3. REFERENCE ENVIRONMENTAL CONDITIONS .......................................................................................... 5 4. STANDARDS.................................................................................................................................................... 5 5. DIESEL GENERATING SET ............................................................................................................................. 5 5.1. DIESEL ENGINE ...................................................................................................................................... 5 5.2. ALTERNATOR ......................................................................................................................................... 6 5.3. BASE FRAME .......................................................................................................................................... 6 5.4. COUPLING ENGINE ALTERNATOR ................................................................................................... 6 5.5. BATTERIES ............................................................................................................................................... 6 5.6. ANTI VIBRATION MOUNT................................................................................................................... 6 5.7. OPTIONAL DAILY FUEL TANK ............................................................................................................ 6 5.8. PAINTING ............................................................................................................................................... 6 5.9. STEP UP TRANSFORMER – EACH GEN SET ..................................................................................... 7 6. GEN MV SYNCHRONISING AND CONTROL PANEL ............................................................................. 7 7. POWER PLANT AUXILIARY SERVICES TRANSFORMER ....................................................................... 11 8. OPTIONAL SOUND AND WEATHERPROOF 40’ CONTAINER EACH GEN SET ............................. 11 9. OPTIONAL WEATHERPROOF 20’ CONTAINER FOR MEDIUM VOLTAGE PANELS....................... 13 10. TYPICAL DRY WEIGHTS AND DIMENSIONS .................................................................................... 13 11. TESTING ................................................................................................................................................... 13 12. EXCLUSIONS ........................................................................................................................................... 13 Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 4 OF 13 1. INTRODUCTION We, ASCOT Industrial Srl who have over 27 years experience in the power sector, and most noticeably Medium Voltage gen sets to Middle Eastern countries for the last 12 years, so therefore, based on our experience, we propose Ascot Generating POWER PLANT with N°10 gen set DGSMT-2500 with MTU water cooled engine and European alternator. 1.1. Benefits of MTU engine • Constructed to the highest European standards • Low capital expenditure based on your requirements • Suitable for operation in harsh conditions with tropical radiator 1.2. Benefits of European Brand alternator • Constructed to the highest European standards • Low capital expenditure based on your requirements 1.3. Benefits of gen set auxiliaries • 2500kVA 0.4/11kV step up transformer for each gen set to raise the LV outgoing voltage to MV (for external installation) • LV & MV synchronising and control panels/switchgear which have been specifically designed for this application for best cost and operation characteristics • Auxiliary services transformer for supplying power to the low voltage loads • Optional 40’ sound and weatherproof high cube container to reduce the noise level of each gen set to 90dB(A) @ 1m and for protection from the elements • Optional 20’ container for medium voltage switchgear for protection from the elements • Optional 2000L free standing fuel tank for connection to your bulk fuel tank for greater autonomy 2. SCOPE OF SUPPLY 20MW / 25MVA POWER PLANT WITH N°10 GENERATING SET MODEL DGS-MT-2500 2000kW / 2500kVA Prime power each, 11kV, 3 phase, 50Hz, 0.8 p.f., 1500rpm @ ISO 3046 conditions with a 10% overload for one hour every 12 of the normal load. Each gen set supplied with: - MTU 20V 4000 G23 water cooled engine - European brand alternator - 0.4 / 11kV step up transformer Scope of supply power plant: - MV control and switchgear panels - Auxiliary services transformer Optional: - Gen Set 40’ sound and weatherproof high cube container 90dB(A) @ 1m - MV switchgear 40’ weatherproof container Document Level: TECHNICAL SPECIFICATION Revision Issue Date Page 20MW / 25MVA 11kV POWER PLANT 0 22/10/2015 5 OF 13 - 2000L free standing fuel tank 3. REFERENCE ENVIRONMENTAL CONDITIONS The power plant / generating sets can operate at the following ambient conditions without any deration. Altitude: 1000 mt a.s.l. Temperature: 40°C Humidity: 60% 4. STANDARDS Designed and manufactured in accordance with - Low Voltage Directives: 2006/95 CEE and subsequent changes - Machine Directive 2006/42 CEE and subsequent changes:. - CEI EN 61439 low voltage switchgear and controlgear assemblies. - CEI EN 61082: Preparation of used electro-technical documents . - EN 60073 CEI 16-3: Principal fundamentals of safety for the interface between man and machine, marking and identification; - EN 60204-1 CEI 44-5:Electrical industrial machines equipment. - CEI 11-20:Electrical energy production systems and continuous groups connected to the mains of category I & II. - ISO 8528 parts 1÷9:Reciprocating internal combustion driven engines coupled to alternating current generating sets. Designed and manufactured by ASCOT which is certified to UNI EN ISO 9001:2008. 5. DIESEL GENERATING SET 5.1. DIESEL ENGINE Manufacturer Type Continuous power @ ISO 3046 conditions Aspiration Electrical starter motor Governor Cooling system Speed Radiator type MTU 20V 4000 G23 2200kWm Turbocharged and aftercooled 24Vdc Electronic Water 1500rpm Heavy duty electro-radiator suitably sized to operate in tropical climates complete with fan guard protection Document Level: TECHNICAL SPECIFICATION Revision Issue Date Page 20MW / 25MVA 11kV POWER PLANT 5.2. 6 OF 13 ALTERNATOR Realisation Manufacturer Type Brushless, self exciting, self regulated ASCOT approved European brand TBD Bearings Standard continuous power Voltage Single 2500kVA at 1500rpm 400V at 1500rpm Voltage regulator limit Frequency ± 1,5% 50Hz Power factor 0,8 Insulation class H Temperature rise H Grade of protection RFI suppression Standards 5.3. 0 22/10/2015 IP23 VDE 0875K CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS49995000 BASE FRAME The generator is provided with a heavy duty base frame fabricated from steel sections; the base frame accurately aligns and supports the engine, the radiator and the alternator; the base frame is provided with lifting points. 5.4. COUPLING ENGINE ALTERNATOR The alternator casing is mounted to the engine by a solid flywheel housing and the rotor is connected to the engine flywheel through a flexible element to minimize torsion vibration within operating range. 5.5. BATTERIES One set of heavy duty lead acid batteries are provided with heavy starter cable and connections to the engine starter motor terminals for three consecutive starting attempts. 5.6. ANTI VIBRATION MOUNT A set of anti vibration mounts fitted between the set and the base frame are supplied to minimize the vibration of the units. Anti-vibration mounts between engine and baseframe & alternator and baseframe are provided. 5.7. OPTIONAL DAILY FUEL TANK A free standing fuel tank of 2000L is offered as an optional item and includes manual fuel refilling spout for connection to your bulk fuel tank. 5.8. PAINTING The complete assembly is finished with high quality painting for tropical climates. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT 5.9. Revision Issue Date Page 0 22/10/2015 7 OF 13 STEP UP TRANSFORMER – EACH GEN SET The outgoing voltage from each gen set alternator is stepped up by a transformer with the following characteristics: • Power 2500kVA • Cooling ONAN • 50Hz • Primary voltage: 0,4kV • Secondary voltage: 11kV • Primary connection: Delta • Secondary connection: Star + N • CEI Group: Dyn11 • LV / MV porcelain isolators • 5 position voltage selector at no load • Oil tank • Oil level gauge • Bucholz relay • Thermometer with 2 alarm contacts • Thermometer pocket • Lifting lugs • N°4 bidirectional wheels • Oil drain valve 6. GEN MV SYNCHRONISING AND CONTROL PANEL The gen set is supplied with a medium voltage synchronising and control panel for installation in your power room with the following technical characteristics. A) METAL ENCLOSED SWITCHGEAR 11kV 12,5 kA Supply of a metal enclosed switchgear our type "Normoclad C” with vacuum C.B or SF6. and single bar system, composed of following units : • N°1 Busbar measuring unit • N°1 Protection unit for aux services transformer • N°10 Gen set incoming unit • N°2 Outgoing to load • N°1 Common Low Voltage panel for control and protection of Low Voltage auxiliaries General features The metal-enclosed switchboards for indoor installation are made of standardized units employed in the transformer cabins, to control and protect lines, transformers, motors and capacitors, and usually in the M.V. electrical distribution. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 8 OF 13 Type Tests Switchboards passed positively the type tests in conformity with CEI 17-6 (IEC 298) standards at SINAL appointed labs and are used to pass the acceptance tests in conformity with standards CEI 17-6 (art.7). Standard References In compliance with standards : International IEC 60694-60298 Italian CEI EN 60694-60298 Ordinary Service Conditions ° In compliance with art.2 of the standard IEC 60694 ° min. ambient temperature (-5°C) ° max. Ambient temperature (+40°C) ° max.average humidity 95% ° height under 1.000 m. ° EM transient in secondary units under peak 1.6kV NOTE : for different service conditions, address to Ascot International Quality System The Ascot International quality system is in compliance with ISO 9001:2000 standard and is certified CSQ/IQNET (international Quality System Assessment and Certification Network). Environment Switchboards are manufactured following processes, treatments and using materials and components causing no pollution damage to environment. Manufacturing Characteristics The switchboards have the following characteristics : dimension Cubicles of 500, 700, 750 and 900 mm. Max. The switchboard can be placed against the wall, since the front side is easily accessible. max. service continuity and reliability The internal metallic segregations, which separate the cubicles, allow the personnel to replace fuses, circuit breakers, CT etc, even when the main busbars are on voltage. easy installation and connection The units are assembled in the factory and tested before shipping, therefore they need only to be fixed to the floor on site and then, coupled together and connected to the external circuits. versatility and flexibility Any technical requirement of extension on already installed switchboards can be met easily with any electrical layout to be carried out. easy operation and maintenance The front side switchboard inspection windows, the isolation and withdrawing of circuit-breakers and disconnector sallow a quick check-up and a long lasting maintenance. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 9 OF 13 surface treatments The cubicles are carried out by zinc-plated steel sheets UNI EN 10142 and sheets UNI EN 10111, then they are degreased and passivated. The external part is powder painted in RAL 7035 grey with orange peel bright effect. On request, other colours are at disposal. personnel safety Guaranteed by the following measures : ° earthed enclosure and earthed equipments’ and components’ bulk ° continuity of protection circuits ° IP3X protection for enclosure and IP2X for the cubicles diaphragms against contacts with part on voltage or in movement. ° use of insulating safe materials, with creepage distances suitable for much polluted environment installation The switchboards are suitable for the incoming medium voltage (M.V.) cables and auxiliary (L.V.) cables from the bottom. On request, the rotobloc switchboard may be suited to receive the cables from the top. The supporting plane should be perfectly smoothed and ready in compliance ASCOT drawings, which show the necessary holes, useful for the M.V./L.V. cables lines and cubicles fixing. Electrical Characteristics - rated voltage 24 kV - operating voltage 11kV - frequency 50 Hz - impulse withstand voltage 125 kV - rated current of main bus bars 630 A - short circuit current x 1" 12,5 kA - peak withstand current 40 kA - auxiliary voltage for signalling - indoor installation - copper bus bar air insulated - closet bottom - flame retardant wiring CEI 20-20 e 20-22 - earthing bar The Switchgear will be composed of units each equipped as below mentioned : Each power plant will be equipped as follow. N°1 BUSBAR MEASURING UNIT • • Equipped with : nr. 3 HCR fuses for PT protection nr. 3 Cast resin Potential transformers with : Ratio 13.200:√3 / 100:√3 – 100:√3 – 100:3 V Burdens 30VA in cl. 0,5 – 30VA cl. 3P .... V.. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT • • • • nr. nr. nr. nr. 1 1 1 1 Inside lighting plant Heaters with thermostat Terminal blocks Ancillary equipments and accessories N°1 PROTECTION UNIT • • • • • • • • • nr. nr. nr. nr. nr. nr. nr. nr. nr. Equipped with : 1 nr. 3 HCR fuses for PT protection 1 Fixed part for the C.B. above mentioned 1 Earthing switch complete with accessories 1 Capacitive dividers with signalling lamps 1 Kits Signalling Lamp 1 Inside lighting plant 1 Heaters with thermostat 1 Terminal blocks 1 Ancillary equipments and accessories N°10 GEN SET INCOMING UNIT • Equipped with : nr. 1 SF6 or Vacuum Circuit Breaker ABB SACE or similar - rated current 400 A - short time current for 1” 12,5 - Motorized - Electrical operated • • • • • nr. nr. nr. nr. nr. 1 1 1 1 3 - Removable execution Off Load Switch SRI Type Fixed part for the C.B. above mentioned Earthing switch complete with accessories Capacitive dividers with signalling lamps Cast resin current transformers with : Ratio 200/5-5A Burden 10VA in cl. 0,5 – 10 cl. 5P10 • nr. 2 Cast resin Potential transformers with : Ratio 13.200/100 / 100:/3 – 100:/3 – 100:3 V • • • • • • • Burdens 30VA in cl. 0,5 – 30VA cl. 3P nr. 1 Synchronizer control Panel nr. 1 Selector Switch for CB command nr. 1 Kits Signalling Lamp nr. 1 Inside lighting plant nr. 1 Heaters with thermostat nr. 1 Terminal blocks nr. 1 Ancillary equipments and accessories Revision Issue Date Page 0 22/10/2015 10 OF 13 Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 11 OF 13 N°2 OUTGOING TO LOAD • Equipped with : nr. 1 SF6 or Vacuum Circuit Breaker ABB SACE or similar - rated current 1250 A - short time current for 1” 12,5 kA - Electrical operated • • • • • - Removable execution nr. 1 Off Load Switch SRI Type nr. 1 Fixed part for the C.B. above mentioned nr. 1 Earthing switch complete with accessories nr. 1 Capacitive dividers with signalling lamps nr. 3 Cast resin current transformers with : Ratio 400/5-5A • • • • • • • Burden 10VA in cl. 0,5 – 10 cl. 5P10 nr. 1 Protection relay (50-51-50N-51N) nr. 1 Selector Switch for CB command nr. 1 Kits Signalling Lamp nr. 1 Inside lighting plant nr. 1 Heaters with thermostat nr. 1 Terminal blocks nr. 1 Ancillary equipments and accessories N°1 Common Low Voltage Control panel for protection of low voltage auxiliaries Circuit breaker for the supply of the auxiliary services to the 9 gen sets. 7. POWER PLANT AUXILIARY SERVICES TRANSFORMER The auxiliary services are supplied by a transformer with the following characteristics. § Cooling type oil § Porcelain insulators for LV & MV § Thermometric well § Lifting lugs § Steerable wheels § Earthing terminal 8. OPTIONAL SOUND AND WEATHERPROOF 40’ CONTAINER EACH GEN SET Description modifications container: We buy a 40 ft high cube container first trip, and apply structural modifications (reinforcement of the base, and the uprights) as dictated by “RINA”, in order to make the container suitable for the containment of the generator, so it can be transported. Detailed construction of the container: - Air intake: through grid panel specifically dimensioned, positioned laterally on the container. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 12 OF 13 - Air expulsion: through grid panel specifically dimensioned, positioned laterally or on the roof at the container. The output section must be higher (20%) in order to have a small depression within container - Double door: for entry to the container, with acoustic characteristics suitable to achieve the noise threshold expected. They can also have the grid panels for the air inlet. - Single door: for entry to the containers side control panel, with acoustic characteristics suitable to achieve the noise threshold expected. Only in this door, will be installed the porthole and the panic handle. - Door with porthole: to see inside the container, with acoustic characteristics suitable to achieve of noise threshold expected. All outside doors will be equipped with: - system pressure lock with padlock; - fixing to container with galvanized steel hinges; - gaskets capable of ensuring perfect water tightness and noise. - Dividing panel radiator: to divide the generator from the area of exhaust air. - Container walls: with acoustic characteristics suitable, to achieve of noise threshold expected. - Flooring: made with non-slip sheet metal. - Technical Connections including: positioning close to the electrical panel, should leave an opening for the passage of electric cables between the inside and the outside of the container, with the following dimensions: mm. - Lifting points: N.4 lifting points, in the bottom of the container, that is through the corner blocks. - Drain: sleeve ¾ “, on the flooring. - Inlet and outlet diesel: sleeve ½ “, position….. - Painting: typically the purchase color, RAL 5010 blue / gray RAL 7035, RAL 7035 Grey interior In the case where the color of the container has to be different it will incur an a extra cost. - Emergency stop push button: appropriately positioned. - Electrical system: internal lighting with lamp and switch with 230 V power outlet. Documents: - Drawing CAD 2D “As Built”. Certificate of compliance issued by “RINA” Approval Authority. Photometric Tests to a distance of 1 - 3 - 7 m, in correspondence with the middle points of the diagonals of the container. Document Level: TECHNICAL SPECIFICATION 20MW / 25MVA 11kV POWER PLANT Revision Issue Date Page 0 22/10/2015 13 OF 13 9. OPTIONAL WEATHERPROOF 20’ CONTAINER FOR MEDIUM VOLTAGE PANELS Protection from the elements for the medium voltage panels is provided by a weatherproof ISO 20 feet container with construction similar to the gen set container but excluding; radiator section, radiator air outlet and inlet section, etc. 10. TYPICAL DRY WEIGHTS AND DIMENSIONS Typical dry weights and dimensions are: Dimensions: Length 12192mm Width 2438mm Height 2896mm Weight 28000kg. 11. TESTING Full scale load and performance tests are carried out in accordance with the procedures of the Ascot quality control manual. 12. EXCLUSIONS It is understood that anything not specified in our offer is intended as out of our scope of supply, namely: • • • • • Civil works Installation and commissioning On site testing Neutral Earthing Resistor Power and connection cables