Three Phase Distribution Transformer Modeling for Power Flow

Volume 51, Number 1, 2010
39
Three Phase Distribution Transformer
Modeling for Power Flow Calculations of
Unbalanced Radial Distribution Systems
J.B.V. SUBRAHMANYAM and C. RADHAKRISHNA
Abstract - This paper presents a simple approach for modeling of distribution transformer in the three phase power flow algorithm
of unbalanced radial power distribution systems. For the transformer modeling symmetrical components theory is used and zero
sequence voltage and current updating for the power flow method is described. The method presented in this paper can solve the
voltage/current equations in the power flow algorithm for various types of transformer configurations. The validity and
effectiveness of the proposed method is demonstrated on a simple two-bus balanced and unbalanced system for grounded wye-delta
and delta-grounded wye transformer connections and on the IEEE 37 bus unbalanced radial distribution system. Results are in
agreement with the literature and show that the proposed model is valid and reliable.
Keywords - Distribution system, distribution transformer, three-phase load flow analysis, symmetrical components.
1.
INTRODUCTION
Load flow analysis is an important task for power
system planning and operation studies [1]. Certain
applications, particularly distribution automation and
optimization of a power system, require repeated load
flow solution and in these applications, it is very
important to solve the load flow problem as efficiently
as possible. The distribution system has some
characteristic features such as radial structure, high R/X
ratio, untransposed lines and unbalanced loads along
with single-phase and two-phase laterals. And also due
to the unbalance, distribution network matrices are ill
conditioned. Because of these features of distribution
networks, the conventional load flow methods such as;
Newton-Raphson and Gauss-Seidel methods generally
fail to converge in solving such networks. Recently
many researchers have paid attention to obtain the load
flow solution of distribution networks and various
methods are available in the literature to carry out the
load flow analysis of three-phase radial distribution
systems [2-15, 24]. These methods can be categorized
as the Z bus based methods [2-3, 13-14], the Newton
Raphson based methods [5, 7, 9, 10, 15], and the
Forward/ Backward sweep-based methods [4, 6, 8, 11,
12, 24].
Due to its low memory requirements, computation
efficiency and robust convergence characteristic,
Forward/Backward sweep-based methods have gained
the most popularity for distribution load flow analysis
in recent years. In these methods the problem of how to
handle distribution transformers of various winding
connections is the key to the unbalanced systems with
Manuscript received January 13, 2010.
multi voltage levels. In the past decades, several
methods for the modelling of three-phase transformers
have been proposed [17-28] as an alternative to the
classical modelling approach which is based on proper
modification of the nodal admittance matrices of the
transformers [16].
The implementation of nodal admittance matrices
based modelling of transformers [16-18, 20, 22, 25-28]
to the forward/backward sweep based methods is
proven to be difficult to employ and claimed to be
unsatisfactory due to relatively slow convergence
problems [27]. It may also cause singularity in the
connection matrix which appears on some special
connection types such as; delta-grounded wye or
grounded wye-delta transformers. The authors of [19,
21, 23, 24] employ different approaches to model
distribution transformers in a branch current based
feeder analysis. In study [19], voltage and current
equations were developed for three of the most
commonly used transformer connections based on their
equivalent circuits.
In studies [21, 23, 24], voltage/current equations
were derived in the matrix form for transformers of the
ungrounded wye-delta connections. However, these
methods are mainly based on circuit analysis with
Kirchhoff’s voltage and current laws. They are in need
to derive the individual formulae for different winding
connections from scratch.
In this paper, symmetrical components model of
distribution transformers is used for modeling and
incorporated into the unbalanced power flow methods.
General information about the symmetrical components
model of three-phase transformers is presented in
Section 2. In section 3 and 4 a detailed description of
the power flow algorithms used and the proposed
© 2010 – Mediamira Science Publisher. All rights reserved.
ACTA ELECTROTEHNICA
40
modeling procedure is explained in detail. Extensive
computation and comparisons have been done to verify
the approach, and the results are presented in Section 5.
2.
SYMMETRICAL COMPONENTS MODEL
OF THREE PHASE TRANSFORMERS
The method of symmetrical components, first
applied to power system by C.L. Fortescue [29] in
1918, is a powerful technique for analyzing unbalanced
three-phase systems. Fortescue defined a linear
transformation from phase components to a new set of
sequence components. The advantage of this
transformation is that for balanced three phase networks
the equivalent circuits obtained for the symmetrical
components, called sequence networks, are separated
into three uncoupled networks. As a result, sequence
networks for many cases of unbalanced three phase
systems are relatively easy to analyze.
The transformation between the phases and
sequence components are defined by;
⎡1 1 1 ⎤
⎢
⎥
A = ⎢1 a 2 a ⎥
⎢
2⎥
⎣1 a a ⎦
(1)
U = AU ′ and I = AI ′
(2)
⎡ 2π ⎤
⎥ , U ′ and I ′ denotes
⎣ 3⎦
Where A = exp ⎢ j
sequence voltages and currents, respectively.
Load injected current can be calculated as follow:
⎛S
I i = ⎜⎜ i
⎝ Vi
⎞
⎟⎟
⎠
∗
(3)
The voltages of the receiving end line segment
are calculated by using Kirchhoff’s voltage law as
given in eqn. (4)
⎡V ⎤ ⎡V ⎤ ⎡ z z z ⎤ ⎡ I ⎤
⎢ b ⎥ ⎢ b ⎥ ⎢ ba bb bc ⎥ ⎢ b ⎥
⎢Vq ⎥ = ⎢V p ⎥ − ⎢ z pq z pq z pq ⎥ ⎢ I pq ⎥
⎢ c ⎥ ⎢ c ⎥ ⎢ ca cb cc ⎥ ⎢ c ⎥
⎢⎣Vq ⎥⎦ ⎢⎣V p ⎥⎦ ⎢⎣ z pq z pq z pq ⎥⎦ ⎢⎣ I pq ⎥⎦
a
q
a
p
aa
pq
ab
pq
ac
pq
(6)
Z0
Where, Z 0 denotes the zero-sequence impedance
of transformer. The new sequence-voltages of
transformer secondary and primary bus voltages can be
calculated by using Kirchhoff’s Voltage Law as given
in eqns. (7) and (8) respectively.
⎡VS0 ⎤ ⎡VP0 ⎤ ⎡0 0 0 ⎤ ⎡I S0 ⎤ ⎡V 0 ⎤
S
⎢ ⎥ ⎢ ⎥ ⎢
⎥⎢ ⎥ ⎢ ⎥
⎢VS+ ⎥ = ⎢VP+ ⎥ − ⎢0 Z + 0 ⎥ ⎢I S+ ⎥ + ⎢ 0 ⎥ (7)
⎢ ⎥ ⎢ ⎥
⎢ −⎥ ⎢ −⎥ ⎢
−⎥ −
⎢⎣VS ⎥⎦ ⎢⎣VP ⎥⎦ ⎣0 0 Z ⎦ ⎢⎣I S ⎥⎦ ⎣ 0 ⎦
⎡VS0 ⎤ ⎡VP0 ⎤ ⎡0 0 0 ⎤ ⎡I S0 ⎤ ⎡I 0 Z 0 ⎤
⎢ ⎥ ⎢ ⎥ ⎢
⎥
⎥⎢ ⎥ ⎢
⎢VS+ ⎥ = ⎢VP+ ⎥ − ⎢0 Z + 0 ⎥ ⎢I S+ ⎥ − ⎢ 0 ⎥ (8)
⎢ ⎥ ⎢
⎢ −⎥ ⎢ −⎥ ⎢
⎥
−⎥ −
⎢⎣VS ⎥⎦ ⎢⎣VP ⎥⎦ ⎣0 0 Z ⎦ ⎢⎣I S ⎥⎦ ⎣ 0 ⎦
The voltages of the sending end line segment pq
are calculated by using Kirchhoff’s Voltage Law as
follows:
ab
ac ⎤ ⎡ a ⎤
⎡Vpa ⎤ ⎡Vqa ⎤ ⎡z aa
I pq
pq z pq z pq
⎥⎢ ⎥
⎢ ⎥ ⎢ ⎥ ⎢
bb bc ⎥ ⎢ b ⎥
⎢Vpb ⎥ = ⎢Vqb ⎥ + ⎢z ba
I pq
pq z pq z pq
⎥⎢ ⎥
⎢ ⎥ ⎢ ⎥ ⎢
⎢Vpc ⎥ ⎢Vqc ⎥ ⎢z ca
z cb z cc ⎥ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦ ⎣ pq pq pq ⎦ ⎣ pq ⎦
(9)
The sequence voltages of transformer primary side
can be calculated for grounded wye-delta and deltagrounded wye as follows:
⎡VP0 ⎤ ⎡VS0 ⎤ ⎡0 0 0 ⎤ ⎡I 0P ⎤ ⎡V 0 ⎤
P
⎢ ⎥ ⎢ ⎥ ⎢
⎥⎢ ⎥ ⎢ ⎥
⎢VP+ ⎥ = ⎢VS+ ⎥ − ⎢0 Z + 0 ⎥ ⎢I P+ ⎥ + ⎢ 0 ⎥ (10)
⎢ −⎥ ⎢ −⎥ ⎢
⎥
−⎥⎢ −⎥ ⎢
⎢⎣VP ⎥⎦ ⎢⎣VS ⎥⎦ ⎣0 0 Z ⎦ ⎢⎣I P ⎥⎦ ⎣ 0 ⎦
Where
transformer secondary
respectively.
(4)
and
primary
side,
I 0P + − shows the sequence current of transformer
voltages of the line segment pq, respectively;
Z is the line impedance matrix
I is the line current
Voltage mismatches can be calculated at each bus
as
( )
VP0
VS0 + − and VP0 + − show sequence voltages of
a
pq
Where,
Vp and Vq stand for the sending end, receiving end
ΔV ( k ) = V ( k ) − V ( k −1)
I 0P =
(5)
Zero sequence current I 0P flowing through the
primary side of transformer is defined by
primary side and
VP0
shows the zero-sequence voltage of transformer
primary side.
The transformation between the phases and
sequence components are defined by a transformation
matrix and the transformation is applied to both
voltages and currents of phase-components (U and I,
respectively) as given in eqs. (1) and (2). Normally, the
three-phase transformer is modeled in terms of its
symmetrical components under the assumption that the
power system is sufficiently balanced. The typical
symmetrical component models of the transformers for
the most common three-phase connections were given
in [30].
Volume 51, Number 1, 2010
3.
THREE PHASE POWER FLOW METHOD
Although the proposed algorithm can be extended
to solve systems with loops and distributed generation
buses, a radial network with only one voltage source is
used here to depict the principles of the algorithm. Such
a system can be modeled as a tree, in which the root is
the voltage source and the branches can be a segment of
feeder, a transformer, a shunt capacitor, or other
components between two buses. With the given voltage
magnitude and phase angle at the root and known
system load information, the power flow algorithm
needs to determine the voltages at all other buses and
currents in each branch. The proposed algorithm
employs an iterative method to update bus voltages and
branch currents. Several common connections of threephase transformers are modeled using the nodal
admittance matrices or different approaches employed
in a branch current based feeder analysis for
distribution system load flow calculation. The grounded
Wye-grounded Wye (GY-GY), grounded Wye-Delta
(GY-D), and Delta-grounded Wye (D-GY) connection
type transformers are most commonly used in the
distribution systems. In the proposed method there is no
need to use the nodal admittance matrices when the
GY-GY connection is used for distribution
transformers. The phase impedance matrices of
transformer can be used directly in the algorithm. The
other type of transformer connections needs to be
modeled and adapted to the power flow algorithm. In
this section, symmetrical components modeling for
distribution transformers of GY-D and D-GY winding
configurations are implemented into power flow
algorithm given in section IV.
4.
ALGORITHM FOR THREE PHASE POWER
FLOW WITH TRANSFORMER
SYMMETRICAL COMPONENTS
MODELLING
1. Read the line data and identify the nodes beyond a
particular node of the system.
2. Read load data and Initialize the bus voltages.
3. Calculate each bus current using eq. (3).
4. Calculate each branch current starting from the far
end branch and moving towards transformer
secondary side.
5. Calculate the sequence currents (Is’) of transformer
secondary current (Is) using eq. (2).
6. If Gy-D connection:
(a) Apply the phase shift Is’ = Is’ *ejπ/6 and set
Is0= 0
(b) Calculate the sequence voltages (Vp’) of
transformer primary bus using eq. (2), and zerosequence current (Ip0) using eq. (6)
(c) Calculate phase current Ip using Is+ and Isinstead of Ip+ and Ip- respectively.
(d) Continue to calculate branch current calculation
moving towards a certain swing bus.
41
(e) Calculate each line receiving end voltages
starting from swing bus and moving towards
the transformer primary bus using eq. (4).
(f) Calculate the sequence voltages (Vs’) of
transformer secondary bus using eq. (2).
(g) Calculate the sequence voltages (Vp’) of
transformer primary bus using eq. (2) and set
Vp0=0.
(h) Calculate the new sequence voltages of
transformer secondary bus using eq. (7).
(i) Apply the phase shift Vs’ =Vs’ *ejπ/6 and
calculate the phase voltages of transformer
secondary bus Vs using eq. (2).
(j) Continue the bus voltages calculation moving
towards the far end using eq. (4).
(k) Go to step 8
7. If D-Gy connection:
(a) Save the zero-sequence current (Is0= I0 ) and
apply the phase shift Is’ = Is’ *ejπ/6 and set Is0=0.
(b) Calculate phase-current Ip using Is+ and Isinstead of Ip+ and Ip- respectively.
(c) Continue to calculate branch current calculation
moving towards a certain swing bus.
(d) Calculate each line receiving end voltage
starting from swing bus and moving towards
the transformer primary bus using eq. (4).
(e) Calculate the sequence-voltages (Vp’) of
transformer primary bus using eq. (2) and set
Vp0=0.
(f) Calculate the new sequence voltages of
transformer secondary bus using eq. (8).
(g) Apply phase shift Vs’=Vs’*ejπ/6 and calculate the
phase voltages of transformer secondary bus Vs
using eq. (2).
(h) Continue the bus voltages calculation moving
towards the far end using eq. (4).
8. Calculate voltage mismatches ∆V(k)=||V(k)|-|V(k-1)||
9. Test for convergence, if no, go to step 3
10. Compute branch losses, total losses, quantity of
unbalance etc.
11. Stop.
5.
SIMULATION RESULTS AND ANALYSIS
5.1. Case Study 1: 2-bus URDS
To verify the proposed approach for the
transformer modeling, two transformer configurations
were included in both the proposed three-phase
distribution system power flow program and the
forward/backward substitution power flow method [28]
and the results obtained were compared. A two-bus
Fig. 1. Two Bus Sample System.
42
ACTA ELECTROTEHNICA
three-phase standard test system, given in fig. 1, is
used, and for simplification, the transformer in the
sample system is assumed to be at nominal rating,
therefore, the taps on the primary and secondary sides
are equal to 1.0. In addition, the voltage of the swing
bus (bus p) is assumed to be 1.0 pu and load is
balanced. The magnitudes and phase angles of bus‘s’
are given in Table 1 for each iteration. Secondly the
connection of transformer is changed to delta- grounded
wye, and the load is unbalanced, 50% load on phase A,
30% load on phase B, and 20% load on phase C, the
results are given in Table 2. It is observed that results
obtained match very well with those listed in the study
[28] and the proposed algorithm can reach the tolerance
of 0.00001 at fourth iteration. On the other hand, in the
results of the study [28], the voltages do not reach this
tolerance value for these two connection types.
Table 1. Voltage magnitudes and Phase angles for Grounded wye-delta of 2-Bus Sample System.
Three phase Power Flow Method proposed
Iter.
Phase A
Phase B
Phase C
No
|Va|
|Vb|
|Vc|
∠Va
∠Vb
∠Vc
0
1.00000
0.00 1.00000
-120.00 1.00000
120.00
1
0.97778
-31.18 0.97778
-151.18 0.97778
88.82
2
0.97686
-31.18 0.97686
-151.18 0.97686
88.82
3
0.97684
-31.18 0.97684
-151.18 0.97684
88.82
4
0.97684
-31.18 0.97684
-151.18 0.97684
88.82
5
0.97684
-13.18 0.97684
-151.18 0.97684
88.82
Comments: 1. All Voltage magnitudes are in pu.
2. All Angles in degrees
3. Iteration No. ‘0’ means initial guess
Forward/Backward Power Flow Method [28]
Phase A
Phase B
Phase C
|Va|
|Vb|
|Vc|
∠Va
∠Vb
∠Vc
1.00000
0.00 1.00000
-120.00 1.00000
120.00
0.99668
-32.84 0.99668
-152.84 0.99668
87.16
0.97590
-32.05 0.97591
-151.04 0.97596
88.96
0.97685
-31.18 0.97684
-151.19 0.97691
88.82
0.97688
-31.18 0.97685
-151.17 0.97680
88.83
0.97680
-31.18 0.97680
-151.18 0.97680
88.82
Table 2. Voltage magnitudes and Phase angles for delta-Grounded wye of 2-Bus Sample System.
Three phase Power Flow Method proposed
Iter.
Phase A
Phase B
Phase C
No
|Va|
|Vb|
|Vc|
∠Va
∠Vb
∠Vc
0
1.00000
0.00 1.00000
-120.00 1.00000
120.00
1
0.96684
28.22 0.97999
-91.06 0.98662
146.30
2
0.96473
28.22 0.97924
-91.06 0.98629
146.30
3
0.96466
28.21 0.97922
-91.06 0.98629
146.30
4
0.96465
28.21 0.97922
-91.06 0.98629
146.30
5
0.96465
28.21 0.97922
-91.06 0.98629
146.30
Comments: 1. All Voltage magnitudes are in p.u.
2. All Angles in degrees
3. Iteration No. ‘0’ means initial guess
Forward/Backward Power Flow Method [28]
Phase A
Phase B
Phase C
|Va|
|Vb|
|Vc|
∠Va
∠Vb
∠Vc
1.00000
0.00 1.00000
-120.00 1.00000
120.00
0.95950
30.60 0.97780
-89.19 0.98697
150.91
0.96612
28.03 0.97990
-91.17 0.98655
149.21
0.96460
28.24 0.97916
-91.05 0.98621
149.30
0.96473
28.21 0.97917
-91.06 0.98626
149.30
0.96473
28.21 0.97917
-91.06 0.98602
149.30
5.2. Case Study I1: 37-bus IEEE URDS
The proposed algorithm is tested on IEEE 37 node
unbalanced radial distribution system shown in Fig. 2.
This feeder is an actual feeder located in California.
The characteristics of the feeder are, three-wire delta
operating at a nominal voltage of 4.8 kV, all line
segments are underground, Substation voltage regulator
consisting of two single phase units connected in open
delta, all loads are “spot” loads and consist of constant
PQ, constant current and constant impedance and the
loading is very unbalanced. The line and load data are
given in [31]. For the load flow, base voltage and base
MVA are chosen as 4.8 kV and 30 MVA respectively.
The obtained voltage profile of 37 node URDS is
given table 3. From table 3, it is observed that the
minimum voltage in phase A, B, and C are 1.0212,
1.0309, and 1.354 respectively. The active power loss
in phase A, B and C are 29.67kW, 17.80kW and 24.09
kW respectively and the total reactive power loss in
phase A, B and C are 21.77kVAR, 13.95kVAR and
20.73 kVAR respectively.
6.
CONCLUSIONS
In this paper a simple and practical method to
include three-phase transformer modeling into the three
phase distribution load flow is presented. The
799
722
724
707
712
701
742
713
704
720
705
702
714
706
729
744
727
703
718
725
728
730
732
708
709
731
736
733
710
775
734
740
735
737
738
711
741
Fig. 2. Single line diagram of 37-bus IEEE URDS.
symmetrical
components
model
of
distribution
43
transformers is incorporated into the three phase power
flow algorithm. The most commonly used Grounded
wye-delta and delta-grounded wye connection
distribution transformers are modeled by using their
sequence-components and adapted to three phase power
flow algorithm. The proposed method is also tested on
the IEEE 37 bus unbalanced radial distribution system.
The 2 bus sample system results are compared with that
of the other existing method and it is observed that the
proposed technique is valid, reliable, effective and most
importantly it is easy to implement.
Table 3. Voltage magnitudes and Phase angles for IEEE 37bus URDS.
Node
Phase A
Phase B
No.
|Va|
|Vb|
∠Va
∠Vb
799
1.0438
0.00
1.0562
-120.06
701
1.0373
0.06
1.0481
-120.16
702
1.0339
0.05
1.0431
-120.22
703
1.0308
0.04
1.0394
-120.26
730
1.0285
0.07
1.0364
-120.23
709
1.0278
0.08
1.0354
-120.22
708
1.0266
0.09
1.0341
-120.20
733
1.0255
0.10
1.0333
-120.17
734
1.0238
0.12
1.0322
-120.14
737
1.0221
0.14
1.0313
-120.09
738
1.0215
0.15
1.031
-120.07
711
1.0213
0.16
1.0309
-120.08
741
1.0212
0.16
1.0309
-120.08
713
1.0333
0.06
1.0418
-120.23
704
1.0326
0.06
1.0399
-120.23
720
1.0324
0.07
1.0381
-120.26
706
1.0325
0.07
1.0378
-120.27
725
1.0325
0.06
1.0376
-120.27
705
1.0332
0.07
1.0417
-120.20
742
1.0332
0.07
1.0413
-120.20
1.0303
0.05
1.0388
-120.24
727
744
1.0300
0.04
1.0385
-120.24
729
1.0299
0.04
1.0384
-120.23
775
1.0278
0.08
1.0354
-120.22
731
1.0278
0.07
1.0349
-120.22
732
1.0000
0.00
1.0000
-120.06
710
1.0236
0.13
1.0315
-120.15
735
1.0235
0.14
1.0315
-120.16
740
1.0212
0.17
1.0309
-120.08
714
1.0325
0.06
1.0397
-120.23
718
1.0319
0.05
1.0394
-120.21
707
1.0326
0.05
1.0351
-120.27
722
1.0326
0.05
1.0348
-120.27
724
1.0327
0.03
1.0344
-120.28
728
1.0299
0.05
1.0383
-120.23
736
1.0238
0.10
1.0303
-120.17
712
1.0328
0.08
1.0412
-120.19
Comments: 1. All Voltage magnitudes are in pu.
2. All Angles in degrees
REFERENCES
1.
2.
3.
4.
5.
6.
7.
IEEE Tutorial Course on Power Distribution Planning, IEEE
Power Engineering Society, 92 EHO 381-6 PWR.
Shoults R.R, Chen M.S., and Schwobel L., 1987. Simplified feeder
modeling for load flow calculations, IEEE Trans. on Power
Systems, 2(1):168-174, 1987.
Chen T.-H., Chen M.-S., Hwang K.-J., Kotas P., and Chebli E.A.,
1919. Distribution system power flow analysis – A rigid
approach, IEEE Trans. on Power Delivery, 6:1146–1152.
Rajicic D., Ackovski R., and Taleski R., 1994. Voltage correction
power flow, IEEE Trans. on Power Delivery, 9:1056–1062.
Zimmerman R.D. and Chiang H.-D., 1995. Fast decoupled power
flow for unbalanced radial distribution systems, IEEE Trans. on
Power Systems, 10:2045–2052.
Cheng C.S. and Shirmohammadi D., 1995. A three-phase power
flow method for real-time distribution system analysis, IEEE
Trans. on Power Systems, 10:671–679.
Zhang F. and Cheng C.S., 1997. A modified Newton method for
radial distribution system power flow analysis, IEEE Trans. on
Power Systems, 12:389–397.
8.
9.
10.
11.
12.
13.
14.
|Vc|
1.0625
1.0526
1.0473
1.0435
1.0409
1.0402
1.0392
1.0384
1.0372
1.0365
1.0361
1.0356
1.0355
1.0462
1.0449
1.0434
1.0433
1.0432
1.0464
1.0463
1.0432
1.043
1.0431
1.0402
1.0400
1.0000
1.0364
1.0362
1.0354
1.0449
1.0449
1.0423
1.0422
1.0421
1.0429
1.0362
1.0460
Phase C
∠Vc
120.06
120.11
120.14
120.14
120.20
120.23
120.24
120.23
120.23
120.22
120.22
120.22
120.22
120.17
120.23
120.29
120.30
120.31
120.19
120.21
120.15
120.16
120.16
120.22
120.24
120.06
120.25
120.25
120.22
120.23
120.23
120.42
120.43
120.44
120.16
120.29
120.21
Thukaram D., Banda H.M.W., and Jerome J., 1999. A Robust
Three-Phase Power Flow Algorithm for Radial Distribution
Systems, Electric Power Systems Research, 50:227-236.
Da Costa V.M., Martins N., and Pereira J.L., 1999. Development in
the Newton Raphson power flow formulation based on current
injections, IEEE Trans. on Power Systems, 14(4):1320-1326.
Whei-Min Lin, Jen-Hao Teng, 2000. Three-Phase Distribution
Network Fast-Decoupled Power Flow Solutions, Electrical Power
and Energy Systems, 22:375-380.
Teng J.H., 2000. A Network-Topology Based Three-Phase Load
Flow for Distribution Systems, Proc. of National Science Council
ROC (A), 24(4):259-264.
P.A.N. Garcia, J.L.R. Pereira, S. Carneiro, V.M. Da Kosta and
N. Martins, 2000. Three-Phase Power Flow Calculations Using
the Current Injection Method, IEEE Trans. on Power Systems,
15(2):508-514.
J.H. Teng, 2002. A Modified Gauss-Seidel Algorithm of Threephase Power Flow Analysis in Distribution Networks, Electrical
Power and Energy Systems, 24:97-102.
Vieria J.C.M., Freitas W. and Morelato A., 2004. Phase–
Decoupled Method for Three-Phase Power-Flow Analysis of
Unbalanced Distribution Systems, IEE Proc.-Gener. Transm.
Distrib., 151(5):568-574.
44
ACTA ELECTROTEHNICA
15. Abdel-Akher M., Mohamed Nor K., and Abdul Rashid A.H., 2005.
Improved Three-Phase Power-Flow Methods Using Sequence
Components, IEEE Trans. on Power Systems, 20(3):1389-1397.
16. Chen M.S. and Dillon W.E., 1974. Power system modeling, Proc.
IEEE, 62:901–915.
17. Chen T.-H., Chen M.-S., Inoue T., Kotas P., and Chebli E.A.,
1991. Three-phase cogenerator and transformer models for
distribution system analysis, IEEE Trans. on Power Delivery,
6:1671–1681.
18. Chen T.-H. and Chang J.D., 1992. Open wye-open delta and open
delta-open delta transformer models for rigorous distribution
system analysis, Proc. Inst. Elect. Eng. C, 139(3):227–234.
19. Baran M.E. and Staton E.A., 1997. Distribution transformer models
for branch current based feeder analysis, IEEE Trans. Power
Systems, 12:698–703.
20. Tan A., Liu W.H., and Shirmohammadi D., 1997. Transformer and
load modeling in short circuit analysis for distribution systems,
IEEE Trans. on Power Systems, 12(3):1315–1332.
21. Kersting W.H., Phillips W.H., and Carr W., 1999. A new approach
to modeling three-phase transformer connections, IEEE Trans.
Ind. Application, 35:169–175.
22. Chen T.-H., Yang W.C., Guo T.Y., and Pu G.C., 2000. Modeling
and analysis of asymmetrical three-phase distribution transformer
banks with mid-tap connected to the secondary neutral conductor,
Electric Power Systems Research, 54(2):83–89.
23. Kersting W.H., 2001. Radial distribution test feeders, Proc. IEEE
Power Eng. Soc. Winter Meeting, 2:908–912.
24. Kersting W.H., Distribution System Modeling and Analysis. Boca
Raton, FL: CRC Press, 2002.
25. Moorthy S.S. and Hoadley D., 2002. A new phase coordinate
transformer model for Ybus analysis, IEEE Trans. Power
Systems, 17:951–956.
26. Irving M.R. and Al-Othman A.K., 2003. Admittance matrix models
of three-phase transformers with various neutral grounding
configurations, IEEE Trans. Power Systems, 18(3):1210–1212.
27. Wang Z., Chen F., and Li J., 2004. Implementing transformer
nodal admittance matrices into backward/forward sweep-based
power flow analysis for unbalanced radial distribution systems,
IEEE Trans. Power Systems, 19(4):1831–1836.
28. Xiao P., Yu D.C., and Yan W., 2006. A Unified Three-Phase
Transformer Model for Distribution Load Flow Calculations,
IEEE Trans. on Power System, 21(1):153 – 159.
29. Fortescue L., 1918. Method of Symmetrical Coordinates Applied
to the Solution of Polyphase Networks, Trans. AIEE, pt. II,
37:1027-1140.
30. Glover D., and Sarma M.S., Power System Analysis and Design,
Brooks/Cole, 2002, Ch. 8.
Distribution
test
feeders
–
web:
31. Radial
http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.html.
Prof. J.B.V. SUBRAHMANYAM
TRR Engineering College
Hyderabad 500 059
Andhra Pradesh, India
Phone: +91-96761-28777
E-mail: jbvsubrahmanyam@gmail.com
C. RADHAKRISHNA
Global Energy Consulting Engineers
Hyderabad 500034
Andhra Pradesh, India
E-mail: radhakrishna.chebiyam@gmail.com
J.B.V. Subrahmanyam received the B.Tech degree from JNTU
Kakinada, and M.E degree from Jadavpur University Kolkata and
presently pursuing Ph.D from JNTU-Hyderabad, India. He has very
rich experience in application of latest condition monitoring techniques
to reduce industry equipment breakdowns & application of modern
GPS & GIS technologies to power utilities to reduce power losses &
manage the power distribution utility business effectively. At present he
is a professor in the Electrical & Electronics Engineering Department,
TRREC, AP, India. He is actively involved in the research of planning
and optimization of unbalanced power distribution systems. His
research interests are computer applications in power systems planning,
analysis and control.
C. Radhakrishna has more than 35 years of experience in teaching &
research in Electrical engineering and published more than 85 papers in
international, national journals & conferences. He is the recipient of
Best Teacher award from Govt. of Andhra Pradesh, India and
Jawaharlal Birth Centenary award from IE (I), India. He was associated
with Jawaharlal Nehru Technological University (JNTU)-Hyderabad
for several years in various positions and was the founder Director of
Academic Staff College-JNTU-Hyderabad, India.