IEEE Recommended Practice For Establishing Transformer

IEEE Std C57.110-1998
(Revision of IEEE Std C57.110-1986)
IEEE Recommended Practice for
Establishing Transformer Capability
When Supplying Nonsinusoidal Load
Currents
Sponsor
Transformers Committee
of the
IEEE Power Engineering Society
Approved 2 July 1998
IEEE-SA Standards Board
Abstract: Methods are developed to conservatively evaluate the feasibility of supplying additional
nonsinusoidal load currents from an existing installed dry-type or liquid-Þlled transformer, as a portion of the total load. ClariÞcation of the necessary application information is provided to assist in
properly specifying a new transformer expected to carry a load, a portion of which is composed of
nonsinusoidal load currents. A number of examples illustrating these methods and calculations
are presented. Reference annexes make a comparison of the document calculations to calculations found in other industry standards and suggested temperature rise methods are detailed for
reference purposes.
Keywords: current, eddy-current losses, harmonic current, harmonic load losses, harmonic loss
factor, harmonics, K-factor, load currents, nonsinusoidal, transformer
The Institute of Electrical and Electronics Engineers, Inc.
345 East 47th Street, New York, NY 10017-2394, USA
Copyright © 1999 by the Institute of Electrical and Electronics Engineers, Inc.
All rights reserved. Published 30 March 1999. Printed in the United States of America.
Print:
PDF:
ISBN 0-7381-0431-0
ISBN 0-7381-0841-3
SH94670
SS94670
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
written permission of the publisher.
IEEE Standards documents are developed within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE-SA) Standards Board. Members of the
committees serve voluntarily and without compensation. They are not necessarily members of the
Institute. The standards developed within IEEE represent a consensus of the broad expertise on the
subject within the Institute as well as those activities outside of IEEE that have expressed an interest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply
that there are no other ways to produce, test, measure, purchase, market, or provide other goods and
services related to the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the
time a standard is approved and issued is subject to change brought about through developments in
the state of the art and comments received from users of the standard. Every IEEE Standard is subjected to review at least every Þve years for revision or reafÞrmation. When a document is more
than Þve years old and has not been reafÞrmed, it is reasonable to conclude that its contents,
although still of some value, do not wholly reßect the present state of the art. Users are cautioned to
check to determine that they have the latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any interested party, regardless of
membership afÞliation with IEEE. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as
they relate to speciÞc applications. When the need for interpretations is brought to the attention of
IEEE, the Institute will initiate action to prepare appropriate responses. Since IEEE Standards represent a consensus of all concerned interests, it is important to ensure that any interpretation has
also received the concurrence of a balance of interests. For this reason, IEEE and the members of its
societies and Standards Coordinating Committees are not able to provide an instant response to
interpretation requests except in those cases where the matter has previously received formal consideration.
Comments on standards and requests for interpretations should be addressed to:
Secretary, IEEE-SA Standards Board
445 Hoes Lane
P.O. Box 1331
Piscataway, NJ 08855-1331
USA
Note: Attention is called to the possibility that implementation of this standard may
require use of subject matter covered by patent rights. By publication of this standard,
no position is taken with respect to the existence or validity of any patent rights in
connection therewith. The IEEE shall not be responsible for identifying patents for
which a license may be required by an IEEE standard or for conducting inquiries into
the legal validity or scope of those patents that are brought to its attention.
Authorization to photocopy portions of any individual standard for internal or personal use is
granted by the Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate
fee is paid to Copyright Clearance Center. To arrange for payment of licensing fee, please contact
Copyright Clearance Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA;
(978) 750-8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the Copyright Clearance Center.
Introduction
(This introduction is not part of IEEE Std C57-110-1998, IEEE Recommended Practice for Establishing Transformer
Capability When Supplying Nonsinusoidal Load Currents.)
The widespread use of static rectiÞcation equipment in industrial loads on small and medium power transformers has resulted in a dramatic increase in the harmonic content of the load current for this equipment. It
is quite common for the harmonic factor of the current to exceed 0.05 per unit, which is the limit speciÞed for
Òusual service conditionsÓ in IEEE Std C57.12.00-1993 and IEEE Std C57.12.01-1998. It is also well known
that higher harmonic content in the current causes higher eddy current loss in winding conductors and structural parts linked by the transformer leakage ßux Þeld and, consequently, higher operating temperatures.
For a number of years this recommended practice has provided guidance in conservative loading practices so
that overloading could be avoided for transformers carrying nonsinusoidal load currents. However, users
have communicated the need for certain clariÞcations to the IEEE Transformers Committee. A working
group was formed to respond to this need and has revised the subject recommended practice. Precise determination of the extra eddy-current loss produced by harmonic currents is a complex subject that is highly
dependent on the design and construction of the transformer and may involve sophisticated computer
analysis. The intent of the original document will be followed and such treatment will not be given. The
intent of this document is to present simple uniform methods of describing a load so that either a new transformer may be adequately described to the supplier or an existing transformer may be evaluated for conservative loading. More speciÞcally, it is expected that this standard would be used for the following situations:
a)
b)
For a new transformer which will be required to carry some nonsinusoidal load currents, but will not
be entirely devoted to a rectiÞer load.
For an existing transformer which was not originally speciÞed for supplying nonsinusoidal load currents, but is now required to supply a load, a portion of which is nonsinusoidal.
The increased use of electronic loads such as computers and adjustable-speed-drive motors in light industrial, commercial, and residential loads has created a need to apply the harmonic loading practices to liquidÞlled distribution transformers below the small and medium power ratings. In extending the practices down
to distribution ratings, it is recognized that the existing methods may be extremely conservative for smaller
ratings and that less extensive derating methods may apply.
Users of this revised document should also recognize that liquid-Þlled transformers may have different load
limitations than dry-type transformers and that the harmonic loading practices should treat the two transformer types differently when necessary.
Transformers which are intended to supply loads with high harmonic content must be speciÞed with a harmonic current distribution. The designer cannot ÒassumeÓ nor can the user expect the designer to use ÒstandardÓ or ÒtypicalÓ current distribution tables. If the harmonic content of the load is unknown, then both the
user and the transformer designer are at risk and reasonable steps should be taken to ensure a conservative
design for the application. Guidelines on how this information is used to develop proper transformer sizing
is provided in this document, but appropriate calculations speciÞc to the type of transformer design are the
responsibility of the designer. Approximate calculation techniques that provide conservative results are provided for the typical user who has much less information than the transformer designer.
In revising this recommended practice, the document was updated to current IEEE style formats and restructured to permit easier use. New sections were added to more clearly address new transformer speciÞcation
and liquid-Þlled transformers. The quantity f was deleted and FHL and FHLÐSTR, Harmonic Loss Factors for
winding eddy currents and for other stray losses were deÞned to simplify and expand the formulas. Additional examples were also added to clarify the formulas, to include liquid-Þlled transformers, and to emphasize the importance of the required load information and its impact on the transformer size. Annexes were
added for clariÞcation, one of which compares the Underwriters Laboratories, Inc. (UL) K-Factor deÞnition
Copyright © 1999 IEEE. All rights reserved.
iii
and the IEEE Std C57.110-1998 Harmonic Loss Factor deÞnition. The other annex presents information on
procedures for performing a temperature rise test.
Participants
The Accredited Standards Committee C57 had the following membership when it reviewed and approved
this document:
P. Orehek, Chair
J. D. Borst, Vice Chair
J. A. Gauthier, Secretary
Organization Represented
Name of Representative
Electric Light and Power Group ................................................................. P. E. Orehek (Delegation Chair)
T. Diamantis
K. S. Hanus
G. N. Miller (Alt.)
C. G. Niemann
S. Paiva
J. Sullivan
Institute of Electrical and Electronics Engineers ...............................................B. Patel (Delegation Chair)
W. B. Binder
J. D. Borst
J. H. Harlow
J. W. Matthews
National Electrical Manufacturers Association .................................... P. J. Hopkinson (Delegation Chair)
M. Austin
G. Coulter
S. Endersbe
A. Ghafourian
K. Linsley
R. L. Plaster
H. Robin
H. J. Sim (Alt.)
Tennessee Valley Authority............................................................................................................... F. Lewis
Underwriters Laboratories, Inc...................................................................................................M. Schacker
U.S. Department of Agriculture, Rural Utilities Services ............................................. Mehrdad Eskandary
U.S. Department of Energy, Western Area Power Administration.......................................... K. C. Wolohan
U.S. Department of the Navy, Civil Engineering Corps ................................................... C. M. Mandeville
At the time this recommended practice was completed, the Working Group on Recommended Practice for
Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents had the following membership:
Richard P. Marek, Chair
Anthony Siebert, Secretary
Roy A. Bancroft
Mike Butkiewicz
Max A. Cambre, Jr.
Jerry L. Corkran
James Deffenbaugh
Jerome M. Frank
Wayne Galli
Dudley L. Galloway
Michael E. Haas
Roger R. Hayes
Bryce Hesterman
Timothy L. Holdway
Philip J. Hopkinson
iv
Edward W. Hutter
Mike Iman
Charles W. Johnson, Jr.
Anthony J. Jonnatti
Sheldon P. Kennedy
Lawrence A. Kirchner
Alexander D. Kline
John G. Lackey
Timothy D. Lewis
Don MacMillan
Jim McIver
Nigel P. McQuin
Mike I. Mitelman
W. E. Morehart
Dhiru S. Patel
Wesley F. Patterson, Jr.
Linden W. Pierce
Guy Pregent
Jeewan L. Puri
Dilip R. Purohit
Subhas Sarkar
Michael Schacker
Wes W. Schwartz
Hyeong Jin Sim
Charles E. Simmons
Ronald W. Stoner
Copyright © 1999 IEEE. All rights reserved.
The following persons were on the balloting committee:
Edward J. Adolphson
Paul Ahrens
George Allen
Glenn Andersen
Stephen Antosz
Jim Antweiler
Javier Arteaga
Roy A. Bancroft
A. Bartek
William H. Bartley
Enrique Betancourt
Wallace B. Binder
Jerry H. Bishop
Thomas E. Blackburn III
Joe V. Bonucchi
John D. Borst
Max A. Cambre, Jr.
Jerry L. Corkran
James Deffenbaugh
Robert C. Degeneff
Alfonso M. Delgado
Bob Del Vecchio
Dieter Dohnal
Richard F. Dudley
John A. Ebert
Fred E. Elliott
Keith Ellis
Gary R. Engmann
Reto H. Fausch
Pierre T. Feghali
Joe Foldi
Michael A. Franchek
Jerome M. Frank
Wayne Galli
Dudley L. Galloway
Saurabh Ghosh
Harry D. Gianakouros
Ramsis S. Girgis
Richard D. Graham
Robert L. Grunert
Michael E. Haas
Ernst Hanique
James H. Harlow
Roger R. Hayes
Bryce Hesterman
Peter J. Hoeßer
Timothy L. Holdway
Philip J. Hopkinson
James D. Huddleston, III
John S. Hurst
Edward W. Hutter
Copyright © 1999 IEEE. All rights reserved.
Mike Iman
Robert W. Ingham
Charles W. Johnson, Jr.
Anthony J. Jonnatti
Lars-Erik Juhlin
Sheldon P. Kennedy
Lawrence A. Kirchner
Brian Klaponski
Alexander D. Kline
Egon Koenig
Barin Kumar
John G. Lackey
J. P. Lazar
Tim D. Lewis
Mark Loveless
Donald L. Lowe
Thomas Lundquist
Joe D. MacDonald
Don MacMillan
William A. Maguire
Richard P. Marek
Jose R. Marotta
John W. Matthews
Angie D. McCain
L. Bruce McClung
Jack W. McGill
Nigel P. McQuin
Charles Patrick McShane
Jack Moffat
Daleep C. Mohla
Harold R. Moore
W. E. Morehart
Daniel H. Mulkey
Chuck R. Murray
R. J. Musil
William H. Mutschler, Jr.
Carl G. Niemann
Larry Nunnery
Paul E. Orehek
Gerald A. Paiva
B. K. Patel
Dhiru S. Patel
Wesley F. Patterson, Jr.
David Payne
Paulette A. Payne
Carlos Peixoto
Dan D. Perco
Mark D. Perkins
Trevor Pfaff
Linden W. Pierce
R. Leon Plaster
Donald W. Platts
Guy Pregent
Richard L. Provost
Jeewan L. Puri
Dilip R. Purohit
Charles T. Raymond
George J. Reitter
J. C. Riboud
Pierre Riffon
Peter G. Risse
Chris A. Robbins
R. B. Robertson
Arlise L. Robinson, Jr
John R. Rossetti
Lawrence Salberg
Hazairin Samaulah
Mahesh P. Sampat
Subhas Sarkar
Leo J. Savio
Michael Schacker
Wes W. Schwartz
Pat Scully
Vic Shenoy
Stephen Shull
Anthony Siebert
Mark Siehling
Hyeong Jin Sim
Tarkeshwar Singh
Kenneth R. Skinger
James E. Smith
Jerry W. Smith
Leonard R. Smith
Steven L. Snyder
Ronald J. Stahara
L. R. Stensland
Peter G. Stewart
Ronald W. Stoner
John C. Sullivan
Ray C. Thomas
James A. Thompson
Thomas P. Traub
Subhash C. Tuli
Robert R. Turcotte, Jr.
John Vandermaar
Joseph J. Vaschak
Robert A. Veitch
Loren B. Wagenaar
Barry H. Ward
Joe D. Watson
D. W. Whitley
William G. Wimmer
F. N. Young
v
When the IEEE-SA Standards Board approved this standard on 2 July 1998, it had the following
membership:
Richard J. Holleman, Chair
Satish K. Aggarwal
Clyde R. Camp
James T. Carlo
Gary R. Engmann
Harold E. Epstein
Jay Forster*
Thomas F. Garrity
Ruben D. Garzon
Donald N. Heirman, Vice Chair
Judith Gorman, Secretary
James H. Gurney
Jim D. Isaak
Lowell G. Johnson
Robert Kennelly
E. G. ÒAlÓ Kiener
Joseph L. KoepÞnger*
Stephen R. Lambert
Jim Logothetis
Donald C. Loughry
L. Bruce McClung
Louis-Fran•ois Pau
Ronald C. Petersen
Gerald H. Peterson
John B. Posey
Gary S. Robinson
Hans E. Weinrich
Donald W. Zipse
*Member Emeritus
Noelle D. Humenick
IEEE Standards Project Editor
vi
Copyright © 1999 IEEE. All rights reserved.
Contents
1.
Overview.............................................................................................................................................. 1
1.1 Scope............................................................................................................................................ 1
1.2 Purpose......................................................................................................................................... 1
2.
References............................................................................................................................................ 1
3.
Definitions............................................................................................................................................ 2
3.1 Letter symbols.............................................................................................................................. 2
4.
General considerations......................................................................................................................... 3
4.1
4.2
4.3
4.4
4.5
4.6
4.7
5.
Design considerations for new transformer specification.................................................................. 10
5.1
5.2
5.3
5.4
5.5
5.6
5.7
6.
Transformer losses ....................................................................................................................... 3
Transformer capability equivalent ............................................................................................... 4
Basic data ..................................................................................................................................... 4
Transformer per-unit losses ......................................................................................................... 5
Transformer losses at measured currents..................................................................................... 5
Harmonic Loss Factor for winding eddy currents ....................................................................... 6
Harmonic Loss Factor for other stray losses................................................................................ 9
Harmonic current filtering ......................................................................................................... 10
Impact on the neutral ................................................................................................................. 10
Power factor correction equipment............................................................................................ 10
Electrostatic ground shields ....................................................................................................... 10
Design consideration outside the windings................................................................................ 10
Harmonic spectrum analysis ...................................................................................................... 11
Design consideration in the windings ........................................................................................ 11
Recommended procedures for evaluating the load capability of existing transformers.................... 12
6.1 Transformer capability equivalent calculation using design eddy-current loss data ................. 12
6.2 Transformer capability equivalent calculation using data available from
certified test report ..................................................................................................................... 18
6.3 Neutral bus capability for nonsinusoidal load currents that include third
harmonic components ................................................................................................................ 26
Annex A ...................................................................................................................................................... 27
Annex B ...................................................................................................................................................... 29
Annex C ...................................................................................................................................................... 32
Annex D ...................................................................................................................................................... 38
Copyright © 1999 IEEE. All rights reserved.
vii
IEEE Recommended Practice for
Establishing Transformer Capability
When Supplying Nonsinusoidal Load
Currents
1. Overview
Two methods are described in this recommended practice. The Þrst is intended to illustrate calculations by
those with access to detailed information on loss density distribution within each of the transformer windings. The second method is less accurate and is intended for use by those with access to transformer certiÞed
test report data only. It is anticipated that the Þrst method will emphasize the information necessary to specify a new transformer and show how this information is used by transformer design engineers, while the second method will be employed primarily by users. This recommended practice will provide methods for
conservatively evaluating the feasibility of applying nonsinusoidal load currents to existing transformers and
will clarify the requirements for specifying new transformers to supply nonsinusoidal loads.
1.1 Scope
This recommended practice applies only to two winding transformers covered by IEEE Std C57.12.00-1993,
IEEE Std C57.12.01-1998, and NEMA ST20-1992. It does not apply to rectiÞer transformers.
1.2 Purpose
The purpose of this document is to establish uniform methods for determining the capability of transformers
to supply nonsinusoidal load currents of known characteristics.
2. References
This recommended practice should be used in conjunction with the following publications. If the following
publications are superseded by an approved revision, the revision shall apply.
IEEE Std 100-1996, IEEE Standard Dictionary of Electrical and Electronics Terms, Sixth Edition.
Copyright © 1999 IEEE. All rights reserved.
1
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
IEEE Std C57.12.00-1993, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power,
and Regulating Transformers.1
IEEE Std C57.12.01-1998, IEEE Standard General Requirements for Dry-Type Distribution and Power
Transformers Including Those with Solid Cast and/or Resin-Encapsulated Windings.
IEEE Std C57.12.80-1978 (Reaff 1992), IEEE Standard Terminology for Power and Distribution Transformers.
IEEE Std C57.12.90-1993, IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and IEEE Guide for Short Circuit Testing of Distribution and Power Transformers.
IEEE Std C57.12.91-1995, IEEE Standard Test Code for Dry-Type Distribution and Power Transformers.
IEEE Std C57.91-1995, IEEE Guide for Loading Mineral-Oil-Immersed Transformers.
NEMA ST20-1992, Dry-Type Transformers for General Applications.2
3. DeÞnitions
All deÞnitions are in accordance with IEEE Std 100-1996, or are in accordance with the standards quoted in
the text.
3.1 Letter symbols
FHL
FHLÐSTR
h
hmax
I
I1
Ih
Imax
IR
I1ÐR
I2ÐR
IT
I1ÐT
I2ÐT
PEC
PECÐR
PECÐO
P
PDC
P2ÐDC
Harmonic loss factor for winding eddy currents
Harmonic loss factor for other stray losses
Harmonic order
Highest signiÞcant harmonic number (hmax = 25)
RMS load current (amperes)
RMS fundamental load current (amperes)
RMS current at harmonic ÒhÓ (amperes)
Maximum permissible rms nonsinusoidal load current (amperes)
RMS fundamental current under rated frequency and rated load conditions (amperes)
High voltage (HV) rms fundamental line current under rated frequency and rated load
conditions (amperes)
Low voltage (LV) rms fundamental line current under rated frequency and rated load
conditions (amperes)
RMS test current (amperes)
HV rms test current (amperes)
LV rms test current (amperes)
Winding eddy-current loss (watts)
Winding eddy-current loss under rated conditions (watts)
Winding eddy-current losses at the measured current and the power frequency (watts)
I2R loss portion of the load loss (watts)
Total calculated I2R losses at ambient temperature (watts)
LV calculated I2R losses at ambient temperature (watts)
1IEEE
publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway,
NJ 08855-1331, USA (http://www.standards.ieee.org/).
2NEMA publications are available from Global Engineering Documents, 15 Inverness Way East, Englewood, Colorado 80112, USA
(http://www.global.ihs.com/).
2
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
PAC
PLL
PLLÐR
PNL
POSL
POSLÐR
PTSLÐR
R
R1
R2
qg
qgÐR
qg1
qg1ÐR
qTO
qTOÐR
(pu)
IEEE
Std C57.110-1998
Measured impedance losses at ambient temperature (watts)
Load loss (watts)
Load loss under rated conditions (watts)
No load loss (watts)
Other stray loss (watts)
Other stray loss under rated conditions (watts)
Total stray loss under rated conditions (watts)
DC resistance (ohms)
DC resistance measured between two HV terminals (ohms)
DC resistance measured between two LV terminals (ohms)
Hottest-spot conductor rise over top-oil temperature (°C)
Hottest-spot conductor rise over top-oil temperature under rated conditions (°C)
Hottest-spot HV conductor rise over top-oil temperature (°C)
Hottest-spot HV conductor rise over top-oil temperature under rated conditions (°C)
Top-oil-rise over ambient temperature (°C)
Top-oil-rise over ambient temperature under rated conditions (°C)
This symbol modiÞer may be added to the listed symbols to represent a per-unit value of
that quantity. Current quantities are referred to the rated rms load current IR, and loss
quantities are referred to the rated load I2R loss density. e.g.: Ih(pu) and PECÐR(pu).
4. General considerations
4.1 Transformer losses
IEEE Std C57.12.90-1993 and IEEE Std C57.12.91-1995 categorize transformer losses as no-load loss
(excitation loss); load loss (impedance loss); and total loss (the sum of no-load loss and load loss). Load loss
is subdivided into I2R loss and Òstray loss.Ó Stray loss is determined by subtracting the I2R loss (calculated
from the measured resistance) from the measured load loss (impedance loss).
ÒStray lossÓ can be deÞned as the loss due to stray electromagnetic ßux in the windings, core, core clamps,
magnetic shields, enclosure or tank walls, etc. Thus, the stray loss is subdivided into winding stray loss and
stray loss in components other than the windings (POSL). The winding stray loss includes winding conductor
strand eddy-current loss and loss due to circulating currents between strands or parallel winding circuits. All
of this loss may be considered to constitute winding eddy-current loss, PEC. The total load loss can then be
stated as
PLL = P + PEC + POSL
watts
(1)
4.1.1 Harmonic current effect on I2R loss
If the rms value of the load current is increased due to harmonic components, the I2R loss will be increased
accordingly.
4.1.2 Harmonic current effect on PEC
Winding eddy-current loss (PEC) in the power frequency spectrum tends to be proportional to the square of
the load current and the square of frequency (see Crepaz [B5], Blume et al., [B3], Dwight [B6], and Bishop
and Gilker [B2])3. It is this characteristic that can cause excessive winding loss and hence abnormal winding
temperature rise in transformers supplying nonsinusoidal load currents.
3The
numbers in brackets preceded by the letter B correspond to those of the bibliography in Annex A.
Copyright © 1999 IEEE. All rights reserved.
3
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
4.1.3 Harmonic current effect on POSL
It is recognized that other stray loss (POSL) in the core, clamps, and structural parts will also increase at a rate
proportional to the square of the load current. However, these losses will not increase at a rate proportional to
the square of the frequency, as in the winding eddy losses. Studies by manufacturers and other researchers
have shown that the eddy-current losses in bus bars, connections and structural parts increase by a harmonic
exponent factor of 0.8 or less. Therefore, 0.8 will be used throughout this document.4 Temperature rise in
these regions will be less critical than in the windings for dry-type transformers. However, these losses must
be properly accounted for in liquid Þlled transformers.
4.1.4 DC Components of load current
Harmonic load currents are frequently accompanied by a dc component in the load current. A dc component
of load current will increase the transformer core loss slightly, but will increase the magnetizing current and
audible sound level more substantially. Relatively small dc components (up to the rms magnitude of the
transformer excitation current at rated voltage) are expected to have no effect on the load carrying capability
of a transformer determined by this recommended practice. Higher dc load current components may
adversely affect transformer capability and should be avoided.
4.1.5 Effect on top oil rise
For liquid-Þlled transformers, the top oil rise (qTO), will increase as the total load losses increase with harmonic loading. Any increase in other stray loss (POSL) will primarily affect the top oil rise.
4.2 Transformer capability equivalent
The transformer capability established by following the procedures in this recommended practice is based on
the following premises:
1)
2)
The transformer, except for the load harmonic current distribution, is presumed to be operated
in accordance with ÒUsual Service ConditionsÓ in IEEE Std C57.12.00-1993 or IEEE Std
C57.12.01-1998.
The transformer is presumed to be capable of supplying a load current of any harmonic content
provided that the total load loss, the load loss in each winding, and the loss density in the region
of the highest eddy-current loss do not exceed the levels for full load, rated frequency, sine
wave design conditions. It is further presumed that the limiting condition is the loss density in
the region of highest winding eddy-current loss; hence, this is the basis used for establishing
capability equivalency.5
4.3 Basic data
In order to perform the calculations in this recommended practice, the characteristics of the nonsinusoidal
load current must be deÞned either in terms of the magnitude of the fundamental frequency component or the
magnitude of the total rms current. Each harmonic frequency component must also be deÞned from power
system measurements. In addition, information on the magnitude of winding eddy-current loss density must
be available.
4See Annex
D, paragraph 2 for additional information on this topic.
simple methods of calculation of transformer capability equivalent given in this document assume that eddy currents at all harmonic frequencies generate loss in a constant path resistance. In fact, skin effect becomes more pronounced as frequency increases and
eddy-current loss is smaller than predicted. Thus, the methods presented in this document become increasingly conservative at the
higher harmonic included in the calculation, particularly those above the 19th.
5The
4
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
4.4 Transformer per-unit losses
Since the greatest concern about a transformer operating under harmonic load conditions will be for overheating of the windings, it is convenient to consider loss density in the windings on a per-unit basis (base
current is rated current and base loss density is the I2R loss density at rated current). Thus Equation (1)
applied to rated load conditions can be rewritten on a per-unit basis as follows:
PLLÐR(pu) = 1 + PECÐR(pu) + POSLÐR(pu)
pu
(2)
Given the eddy-current loss under rated conditions for a transformer winding or portion of a winding,
(PECÐR), the eddy-current loss due to any deÞned nonsinusoidal load current can be expressed as
h = h max
å
P EC = P ECÐ R
h=1
2
I hö 2
æ ---- h
è I Rø
watts
(3)
The I2R loss at rated load is one per-unit (by deÞnition). For nonsinusoidal load currents, the equation for the
rms current in per-unit form (base current is rated current), will be:
h = h max
I ( pu ) =
å
I h ( pu ) 2
pu
(4)
h=1
Equation (3) can also be written in per-unit form (base current is rated current and base loss density is the
I2R loss density at rated current):
h = h max
P EC ( pu ) = P EC Ð R ( pu )
å
I h ( pu ) 2 h 2
pu
(5)
h=1
4.5 Transformer losses at measured currents
Equations (2) through (5) assume that the measured application currents are taken at the rated currents of the
transformer. Since this is seldom encountered in the Þeld, a new term is needed to describe the winding eddy
losses at the measured current and the power frequency, PECÐO. Three assumptions in addition to the basic
premises of the Transformer Capability Equivalent are necessary to clarify the use of this term:
1)
2)
3)
The eddy losses are approximately proportional to the square of the frequency. This assumption
will cause any subsequent equations to be accurate for small conductors and low harmonics,
with errors on the high side, for a combination of larger conductors and higher harmonics.
The eddy losses are a function of the current in the conductors. Any equation for loss can then
be expressed in terms of the rms load current, I.
Superposition of eddy losses will apply, which will permit the direct addition of eddy losses
due to the various harmonics.
Equations (3) and (5) may now be written more generally in the following equation:
h = h max
P EC = P EC Ð O
å
h=1
2
I hö 2
æ --- h
èIø
watts
Copyright © 1999 IEEE. All rights reserved.
(6)
5
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
By removing the rms current term, I from the summation, the equation becomes
h = h max
å
2
Ih h
2
h=1
P EC = P EC Ð O ´ ----------------------------2
I
watts
(7)
The rms value of the nonsinusoidal load current is then given by
h = h max
I =
å
2
Ih
(8)
amperes
h=1
The rms current term, I may be expressed in terms of the component frequencies
h = h max
å
2
Ih h
2
h=1
P EC = P EC Ð O ´ ----------------------------h=h
å
(9)
watts
max
2
Ih
h=1
4.6 Harmonic Loss Factor6 for winding eddy currents
It is convenient to deÞne a single number which may be used to determine the capabilities of a transformer
in supplying power to a load. FHL is a proportionality factor applied to the winding eddy losses, which represents the effective rms heating as a result of the harmonic load current. FHL is the ratio of the total eddycurrent losses due to the harmonics, (PEC), to the eddy-current losses at the power frequency, as if no harmonic currents existed, (PECÐO). This deÞnition in equation form is
h = h max
2
F HL
2
å Ih h
P EC
h=1
= ---------------- = ----------------------------h = h max
P EC Ð O
2
å Ih
(10)
h=1
Equation (10) permits FHL to be calculated in terms of the actual rms values of the harmonic currents. Various measuring devices permit calculations to be made in terms of the harmonics normalized to the total rms
current or to the Þrst or fundamental harmonic. Equation (10) may be adapted to these situations by dividing
the numerator and denominator by either I1, the fundamental harmonic current, or by I, the total rms current
I1. These terms may now be applied to Equation (10) term by term, resulting in Equations (11) and (12).
h = h max
I 2 2
---h- h
I1
h=1
= ----------------------------------h = h max
Ih 2
å ---I 1-
å
F HL
(11)
h=1
Ih
Note that the quantity ---- may be directly read on a meter, by passing the computation procedure.
I1
6The
Harmonic Loss Factor is similar but not identical to the K-factor referenced in other standards. For a comparison of the Harmonic
Loss Factor with the K-factor deÞnition referenced in UL standards, see Annex B.
6
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
h = h max
I 2 2
---h- h
I
h=1
= ----------------------------------h = h max
Ih 2
å ---I-
å
F HL
(12)
h=1
In either case, FHL remains the same value, since it is a function of the harmonic current distribution and is
independent of the relative magnitude. Two examples may be used to clarify these deÞnitions. In both examples a nonsinusoidal load current of 1804 A rms will be used as the rated current. The load may be described
by the following harmonic distribution, normalized to the rms load current of 1804 A:
Ih
---I
Ih
h
1
1764
0.978
5
308.5
0.171
7
194.9
0.108
11
79.39
0.044
13
50.52
0.028
17
27.06
0.015
19
17.68
0.0098
The calculation is tabulated as follows:
Ih
---I
h
I hö
æ ---è Iø
2
2
h2
I hö 2
æ ---h
è Iø
1
0.978
0.9570
1
0.957
5
0.171
0.0290
25
0.731
7
0.108
0.0120
49
0.571
11
0.044
0.0020
121
0.234
13
0.028
0.00078
169
0.133
17
0.015
0.00023
289
0.065
19
0.0098
0.00010
361
0.035
S
Ñ
1.000
Ñ
2.726
Copyright © 1999 IEEE. All rights reserved.
7
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
The summation of the third column, (Ih/I)2, is equal to 1.000 and represents the rated rms load on a per-unit
basis. The Harmonic Loss Factor for this harmonic distribution is
2.726
F HL = ------------- =
1.000
This same loading example may also be described in terms of the harmonic currents normalized to the harmonic current of the fundamental frequency, as follows:
Ih
---I1
Ih
h
1
1764
1.000
5
308.5
0.175
7
194.9
0.110
11
79.39
0.045
13
50.52
0.029
17
27.06
0.015
19
17.68
0.010
Note that the values of the harmonic current, Ih, are the same in both examples, but the normalized values are
different since these values are normalized to the harmonic current of the fundamental frequency. The calculation is tabulated as follows:
Ih
---I1
h
8
I hö
æ ---è I 1ø
2
2
h2
I hö 2
æ ---h
è I 1ø
1
1.000
1.0000
1
1.0000
5
0.175
0.0306
25
0.7643
7
0.110
0.0122
49
0.5975
11
2.726
0.045
0.0020
121
0.2449
13
0.029
0.0008
169
0.1385
17
0.015
0.0002
289
0.0680
19
0.010
0.0001
361
0.0362
S
Ñ
1.0459
Ñ
2.8494
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
Whether the individual harmonic currents are normalized to the rms load current I, or to the fundamental
load current I1, the value of harmonic loss factor is the same:
2.726
2.8494
F HL = ------------- = ---------------- =
1.000
1.0459
4.7 Harmonic Loss Factor for other stray losses
Although the heating due to other stray losses is generally not a consideration for dry-type transformers, it
can have a substantial effect on liquid-Þlled transformers. A relationship similar to the Harmonic Loss Factor
for winding eddy losses exists for these other stray losses in a transformer, and may be developed in a similar
manner. However, the losses due to bus bar connections, structural parts, tank, etc. are proportional to the
square of the load current and the harmonic frequency to the 0.8 power, as stated in 4.1.3. This may be
expressed in a form similar to Equation (3).
h = h max
P OSL = P OSL Ð R
å
h=1
2
I h ö 0.8
æ ---- h
è I Rø
watts
(13)
The equations corresponding to the Harmonic Loss Factor, normalized to the fundamental current and normalized to the rms current respectively are
h = h max
F HL Ð STR
I h 2 0.8
--å I 1- h
h=1
= -------------------------------------h = h max
Ih 2
å ---I 1-
(14)
h=1
h = h max
I 2 0.8
---h- h
I
h=1
= -------------------------------------h = h max
Ih 2
å ---I-
å
F HL Ð STR
(15)
h=1
Using the harmonic distribution from the last example of the previous section, the calculation is tabulated for
the normalized fundamental current base, as follows:
Ih
---I1
h
I hö
æ ---è I 1ø
2
h0.8
2
I hö 1.140
0.8
æ ---h
è I 1ø
1
1.000
1.0000
1.0000
1.00000
5
0.175
0.0306
3.6239
0.11098
7
2.726
0.110
0.0122
4.7433
0.05739
11
0.045
0.0020
6.8095
0.01379
13
0.029
0.0008
7.7831
0.00655
17
0.015
0.0002
9.6463
0.00217
19
0.010
0.0001
10.5439
0.00105
S
Ñ
1.0459
Ñ
1.1919
1.1919
F HR Ð STR = ---------------- =
1.0459
Copyright © 1999 IEEE. All rights reserved.
9
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
5. Design considerations for new transformer speciÞcation
5.1 Harmonic current Þltering
When it is practical, the user may install Þlters on the secondary line to reduce some of the harmonic load
currents supplied to the transformer. If one of the harmonic frequencies is close to the resonant frequency
resulting from the Þltering circuit, current ampliÞcation at this frequency may occur.
5.2 Impact on the neutral
When the harmonic current frequencies include harmonic orders having multiples of three (3, 6, 9, etc.), zero
sequence currents ßow in the neutral. Over-sizing of this neutral may be required. In those circumstances, a
common practice is to double the neutral ampacity.
5.3 Power factor correction equipment
Power factor correction equipment is frequently installed to decrease utility costs. Care should be taken
when this is done, since current ampliÞcation at certain frequencies due to resonance in the circuit can be
quite high. In addition, the inductance which is reduced in the circuit generally allows higher harmonic currents to exist in the system. Harmonic heating effects from these conditions may be damaging to transformers and other equipment. The additional losses produced may also increase utility costs due to increased
wattage requirements, even though the load power factor was improved.
5.4 Electrostatic ground shields
Electrostatic ground shields are frequently speciÞed between the primary and secondary windings. The presence of electrostatic ground shields tends to reduce capacitive coupling between the windings. This reduces
the coupling of transients between the two windings. Line disturbances produced by converter equipment
connected to the transformer secondary will be reduced, but will not be eliminated on the primary side of the
transformer. The shields are not intended to reduce harmonic currents, but by virtue of their magnetic coupling to windings carrying such currents, additional heating losses are induced. The electrostatic shields are
a supplement but not necessarily a replacement for harmonic current Þltering. Therefore, Þltering may still
be needed to achieve the desired power quality.
The electrostatic shields also serve as protection to the secondary side of the transformer from transients that
may be impressed on the high-voltage winding. This is especially important for transformers with
ungrounded secondaries. Transients on the high-voltage side of a transformer can dramatically increase the
surge voltage seen on an ungrounded secondary winding from what may have been expected for a grounded
winding. This may damage transformer windings and parts or equipment connected on the secondary side of
the transformer. The presence of an electrostatic ground shield between the primary and secondary windings
reduces the magnitude of the transient coupled to the secondary windings.
5.5 Design consideration outside the windings
Harmonic currents can substantially increase the stray losses in structural parts outside of the windings.
Additional clearances, the use of non-magnetic materials in place of mild steel, the break up of potential circulation current paths, and the use of shielding materials should all be considered as ways to reduce the
effects of harmonic current heating in structural parts. These other stray losses, POSL, must be included in
the losses used to determine top oil rise, DqTO, under harmonic loading conditions.
10
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
5.6 Harmonic spectrum analysis
It is preferred that the harmonic spectrum to which the transformer will be subjected be speciÞed to the
transformer manufacturer at the time of quotation. An accurate analysis for proper sizing of the transformer
can only be made by evaluating the speciÞc harmonic spectrum. If the spectrum cannot be supplied, then the
userÕs calculation or estimate of FHL should be speciÞed. However, the unit will likely be conservatively
sized to compensate for the lack of speciÞc loading information. The specifying engineer must supply this
loading information, since the transformer manufacturer cannot assume values with no real knowledge of
the system to which the transformer will be applied. For liquid-Þlled transformers, stray losses other than the
winding eddy losses contribute to heating of the oil. Since FHLÐSTR is calculated with a different exponent,
the value of this factor must also be supplied by the specifying engineer if no spectrum analysis is provided.
The harmonic spectrum supplied should be identiÞed as to whether it is measured on the primary or secondary side of the transformer. If the harmonic spectrum is provided in per-unit form, then the fundamental
should be deÞned at the rated frequency of the transformer speciÞed.
5.7 Design consideration in the windings
Since harmonic currents can substantially increase the eddy-current losses in the windings, this increase of
losses must be considered in the temperature rise calculation when a new transformer is speciÞed. For each
winding, the per-unit eddy-current losses in the region of highest loss density can be deÞned for rated frequency operation at rated current by the transformer manufacturer in terms of Equation (2), with POSLÐR(pu)
equal to zero (since there is no other stray loss in the windings by deÞnition). The per-unit loss density in
these regions of highest eddy-current loss can then be recalculated for the deÞned nonsinusoidal load current
by combining Equations (2),(5),(8), and (11).
2
P LL ( pu ) = I ( pu ) ´ ( 1 + F HL ´ P EC Ð R ( pu ) )
pu
(16)
To adjust the per-unit loss density in the individual windings, the effect of FHL must be known on each winding. Thus the low voltage winding, with its larger conductor cross section may start with a lower loss density
and a lower temperature rise, but may increase more than the high-voltage winding and exhibit the hottest
spot in the transformer for harmonic loads. That is to say, there is one value of FHL for the load, but the
effects on different transformers and different windings within the same transformer can be different. For
liquid-Þlled transformers, heating of the oil by stray losses other than the eddy losses also affects the temperature rise of the windings.
In these mentioned regions, considering the per-unit loss density obtained by Equation (16) with a nonsinusoidal load current of 1 (pu) rms magnitude, limits of temperature and temperature rise given in IEEE Std
C57.12.00-1993 and IEEE Std C57.12.01-1998 must be met.
Copyright © 1999 IEEE. All rights reserved.
11
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
6. Recommended procedures for evaluating the load capability of existing
transformers7
6.1 Transformer capability equivalent calculation using design eddy-current loss
data
6.1.1 Typical calculations for dry-type transformers
The per-unit eddy-current loss in the region of highest loss density can be deÞned for rated frequency operation at rated current by the transformer manufacturer in terms of Equation (2), with POSLÐR(pu) equal to zero
(since there is no other stray loss in the windings by deÞnition).
The per-unit value of nonsinusoidal load current that will make the result of the Equation (16) calculation
equal to the design value of loss density in the highest loss region for rated frequency and for rated current
operation is given by Equation (17). This assumes that the normal life of the unit will be maintained. However, it is permissible to overload a unit with a resulting loss of life, and there are loading guides for this purpose.
P LL Ð R ( pu )
I max ( pu ) ---------------------------------------------------1 + F HL ´ P EC Ð R ( pu )
pu
(17)
Two examples illustrate the use of these formulas. Given a nonsinusoidal load current with the following
harmonic distribution, determine the maximum load current that can be continuously drawn (under standard
conditions) from an IEEE standard transformer having a rated full load current of 1200 A and whose winding eddy-current loss under rated conditions (PECÐR) at the point of maximum loss density is 15% of the
local I2R loss.
Ih
---I1
h
1
1.000
5
0.233
7
0.108
Ñ
Ñ
11
0.042
13
0.027
17
0.013
19
0.008
7The
user is cautioned that local and national electrical codes should be consulted before any installed unit is ofÞcially Òderated,Ó such
as changing the nameplate. Some units may not be ÒderatedÓ without violating these codes.
12
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
The maximum per-unit local loss density under rated conditions, PLLÐR(pu) is then 1.15 pu. Equations (16)
and (17) require values for Ih(pu)2, h2, and Ih(pu)2h2. These can be calculated and tabulated as follows:
Ih
---I1
h
I hö
æ ---è I 1ø
2
2
h2
I hö 2
æ ---h
è I 1ø
1
1.000
1.000
1
1.0000
5
0.233
0.0543
25
1.3572
7
0.108
0.0117
49
0.5715
11
0.042
0.0018
121
0.2134
13
0.027
0.0007
169
0.1232
17
0.013
0.0002
289
0.0488
19
0.008
0.0001
361
0.0231
S
0.885
pu
Ñ
1.0687
Ñ
3.3374
From Equation (16), the local loss density for the nonsinusoidal load current is:
PLL (pu) = 1.069 ´ (1 + 3.123 ´ 0.15) = 1.569 pu
and the maximum permissible nonsinusoidal load current with the given harmonic composition, from Equation (17), is:
I max ( pu ) =
1.15
--------------------------------------- =
1 + 3.123 ´ 0.15
or
I max = 0.885 ´ 1200 = 1062 A
Thus, with the given nonsinusoidal load current harmonic composition, the transformer capability is approximately 89% of its sinusoidal load current capability.
Copyright © 1999 IEEE. All rights reserved.
13
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
The following example of a nonsinusoidal load current has a strong third harmonic content with the following harmonic distribution:
Ih
---I
h
Ih
---I
h
1
0.969
11
0.1100
3
0.367
13
0.0709
5
0.354
15
0.0259
7
0.102
17
0.0568
9
0.0279
19
0.0472
Determine the maximum load current that can be continuously drawn (under standard conditions) from a
225 kVA standard transformer having a rated full load secondary current of 624.5 A and whose average
winding eddy-current loss under rated conditions (PECÐR) at the point of maximum loss density is 11.7% of
the local I2R loss.
The maximum per-unit local loss density under rated conditions, PLLÐR(pu) is then 1.117 pu. Equations (16)
and (17) require values for Ih(pu)2, h2, and Ih(pu)2h2. These can be calculated and tabulated as follows:
h
I hö
æ ---è Iø
2
2
h2
I hö 2
æ ---h
è Iø
1
0.9690
0.93896
1
0.9390
3
0.3670
0.13469
9
1.2122
5
0.3540
0.12532
25
3.1329
7
0.1020
0.01040
49
0.5098
9
0.0279
0.00078
81
0.0631
11
0.1100
0.01210
121
1.4641
13
0.0709
0.00503
169
0.8495
15
0.0259
0.00067
225
0.1509
17
0.0568
0.00323
289
0.9324
19
0.0472
0.00223
361
0.8043
S
14
Ih
---I
1.2334
10.06
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
From Equation (16), the local loss density for the nonsinusoidal load current is
PLL (pu) = 1.233 ´ (1. 8.156 ´ 0.117) = 2.410 pu
and the maximum permissible nonsinusoidal load current with the given harmonic composition, from Equation (17), is
I max ( pu ) =
1.117
------------------------------------------ =
1 + 8.156 ´ 0.117
or
Imax = 0.756 ´ 624.5 = 472.1 A
Thus, with the given nonsinusoidal load current harmonic composition, the transformer capability is approximately 76% of its sinusoidal load current capability.
6.1.2 Typical calculations for liquid-Þlled transformers
The calculations for liquid-Þlled transformers are similar to the dry-type, except the effect of all stray losses
must be addressed. As indicated by equations in IEEE Std C57.91-1995, for self-cooled ONAN8 mode, the
top oil rise is proportional to the total losses to the 0.8 exponent and may be estimated for the harmonic
losses, based on rated load and losses as shown below.
P LL + P NL 0.8
q TO = q TO Ð R ´ æ -------------------------------ö
è P LL Ð R + P NLø
°C
(18)
where
P LL = P + F HL ´ P EC + F HL Ð STR ´ P OSL
watts
(19)
The winding hot spot conductor rise is also proportional to the load losses to the 0.8 exponent and may be
calculated as follows:
P LL ( pu ) 0.8
q g = q g Ð R ´ æ ---------------------------ö
è P LL Ð R ( pu )ø
°C
(20)
This may then be written as
1 + F HL ´ P EC Ð R ( pu ) 0.8
q g = q g Ð R ´ æ ---------------------------------------------------- ö
è 1 + P EC Ð R ( pu ) ø
8Formerly
0.756 pudesignated
°C
(21)
as OA.
Copyright © 1999 IEEE. All rights reserved.
15
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
As an example, a 65 °C average winding rise, 80 °C hottest spot rise oil-Þlled transformer was designed for
a speciÞed harmonic current content. After installation, the actual harmonic currents were measured and the
current spectrum was supplied to the manufacturer with a request to check the temperature rises. At rated
load and 60 Hz, the tested losses were
No load
4072 W
I2R
27 821 W
Stray and eddy loss
4 060 W
Total loss
35 953 W
The measured temperature rises above ambient were
HV average rise
48.1 °C
LV average rise
47.6 °C
Top-oil rise
47.2 °C
Hot spot conductor rise
55.3 °C
The harmonic distribution was determined at a load, which was approximately 100% of the magnitude of the
fundamental current. The distribution, normalized to the fundamental, was supplied as follows:
Ih
---I1
h
16
h
Ih
---I1
1
1.00
13
0.0512
3
0.351
15
0.0425
5
0.169
17
0.0402
7
0.121
19
0.0387
9
0.0915
23
0.0321
11
0.0712
25
0.0286
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
The calculations to determine the Harmonic Loss Factors for the winding eddy losses and the other stray
losses are tabulated below.
Ih
---I1
h
I hö
æ ---è I 1ø
2
h2
I hö
æ ---è I 1ø
2
I hö
æ ---è Iø
2
2
I hö 0.8
æ ---h
è I 1ø
1
1.000
1.000000
1
1.000000
1.000000
1.000000
3
0.351
0.123201
9
1.108809
2.408225
0.296696
5
0.169
0.028561
25
0.714025
3.623898
0.103502
7
0.121
0.014641
49
0.717409
4.743276
0.069446
9
0.0915
0.008372
81
0.678152
5.799546
0.048555
11
0.0712
0.005069
121
0.613402
6.809483
0.034520
13
0.0512
0.002621
169
0.443023
7.783137
0.020403
15
0.0425
0.001806
225
0.406406
8.727161
0.015763
17
0.0402
0.001616
289
0.467036
9.646264
0.015589
19
0.0387
0.001498
361
0.540666
10.54394
0.015792
23
0.0321
0.001030
529
0.545087
12.28520
0.012659
25
0.0286
0.000818
625
0.511225
13.13264
0.010742
S
Ñ
1.189234
Ñ
7.745241
Ñ
1.643667
The third column summation results in an rms current value of 1.09 pu. The Þfth column summation results
in a Harmonic Loss Factor for the winding eddy losses of 6.51, and the seventh column summation results in
a Harmonic Loss Factor for the other stray losses of 1.38.
An engineering analysis indicated the division of the eddy and other stray losses to be
Eddy loss
316 W
Other stray loss
3744 W
Total stray loss
4060 W
In order to determine the top-oil rise, the total losses must be corrected to reßect the higher rms current
above the rated current and also the effects of the harmonic content.
PLL(pu) = PLLÐR(pu) ´ (1.09)2
Copyright © 1999 IEEE. All rights reserved.
17
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
Equation (19) is then tabulated as follows:
Type of loss
Rated losses
(watts)
Load losses
(watts)
Harmonic
multiplier
Corrected
losses
No-load
4072
4072
4072
I2R
27 821
33 034
33 034
Winding eddy
316
375
6.52
2446
Other stray
3744
4446
1.38
6153
Total losses
35 953
41 927
45 687
The top-oil rise for the speciÞed loading conditions may now be calculated by Equation (18):
45687 0.8
q TO = 47.2 ´ æ ---------------ö = 57.2 ° C
è 35953ø
The maximum per-unit eddy loss occurred in the high-voltage winding and was calculated to be an average
of 2% of the ohmic loss. Assuming that the maximum eddy loss at the hot spot region to be four times the
average eddy loss would give an eddy loss of 8% of the ohmic loss density at the hot spot location. The hot
spot conductor rise over top-oil temperature can be calculated by Equation (21).
0.8
1 + 6.52 ´ 0.08
q g = ( 55.3 Ð 47.2 ) ´ æ ------------------------------------ ´ 1.189 ö = 12.2 °C
è 1 + 0.08
ø
The hot spot conductor rise over ambient then becomes
57.2 + 12.2 = 69.4 °C
6.2 Transformer capability equivalent calculation using data available from certiÞed
test report
In order to make the calculation with limited data, certain assumptions have been made that are considered
to be conservative. These assumptions may be modiÞed based on guidance from the manufacturer for a particular transformer.
1)
The certiÞed test report includes all data listed in the appendixes to IEEE Std C57.12.90-1993 or
IEEE Std C57.12.91-1995.
2)
A portion of the stray loss, determined by the multipliers below, is assumed to be winding eddy-current loss. This is a conservative assumption and should not be followed if better data can be cited.
3)
18
a)
67% of the total stray loss is assumed to be winding eddy losses for dry-type transformers.
b)
33% of the total stray loss is assumed to be winding eddy losses for oil-Þlled transformers.
The I2R loss is assumed to be uniformly distributed in each winding.
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
4)
5)
The division of eddy-current loss between the windings is assumed to be as follows:9
a)
60% in the inner winding and 40% in the outer winding for all transformers having a maximum
self-cooled current rating of less than 1000 A (regardless of turns ratio).
b)
60% in the inner winding and 40% in the outer winding for all transformers having a turns ratio
of 4:1 or less.
c)
70% in the inner winding and 30% in the outer winding for all transformers having a turns ratio
greater than 4:1 and also having one or more windings with a maximum self cooled current rating greater than 1000 A.
The eddy-current loss distribution within each winding is assumed to be nonuniform.10 The maximum eddy-current loss density is assumed to be in the region of the winding hottest-spot and is
assumed to be 400% of the average eddy-current loss density for that winding. Finite element analyses and empirical data indicate that smaller ratings may show a uniform distribution of eddy-current
loss (Hwang [B11]).
As established in test codes IEEE Std C57.12.90-1993 and IEEE Std C57.12.91-1995, the stray loss component of the load loss is calculated by subtracting the I2R loss of the transformer from the measured load loss.
Therefore
2
2
P TSL Ð R = P LL Ð R Ð K ´ [ ( I 1 Ð R ) ´ R 1 + ( I 2 Ð R ) ´ R 2 ]
watts
11
(22)
where
K = 1.0 for single-phase transformers
= 1.5 for three-phase transformers
By assumption 2) of this section, a portion of the stray loss is taken to be eddy-current loss. For dry-type
transformers, the winding-eddy loss is assumed to be:
P EC Ð R = P TSL Ð R ´ 0.67
(23)
For oil-Þlled transformers, the winding eddy loss is assumed to be
P EC Ð R = P TSL Ð R ´ 0.33
watts
(24)
The other stray losses are then calculated as follows:
P OSL Ð R = P TSL Ð R Ð P EC Ð R
watts
(25)
9A
high percentage of the leakage ßux ßowing axially in and between the windings is attracted radially inward at the ends of the windings because there is a lower reluctance return path through the core leg than through the unit permeability space outside the windings.
As a result, the highest magnitude of the radial component of leakage ßux density (and highest eddy loss) occurs in the end regions of
the inner winding. In the absence of other information, the inner winding may be assumed to be the low-voltage winding. The eddy-loss
distribution assumptions 4) and 5) are very conservative.
10See footnote 8.
11NOTEÑMany test reports for three-phase transformers show the resistance of three phases in series. In these cases values for R and
1
R2 may be calculated as follows:
Delta winding: R1 or R2 = 2/9 of three-phase resistance
Wye winding: R1 or R2 = 2/3 of three-phase resistance
Copyright © 1999 IEEE. All rights reserved.
19
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
The low-voltage (inner) winding eddy-current loss can be calculated from the value of PECÐR determined
from Equations (23) or (24) as either 0.6 PECÐR watts or 0.7 PECÐR watts, depending on the transformer
turns ratio and current rating. Since by assumption 3) above, the I2R loss is assumed to be uniformly distributed within the winding, and by assumption 5), the maximum eddy-current loss density is assumed to be
400% of the average value, the low voltage winding eddy-current loss in per unit of that windingÕs I2R loss
will be either
2.4 ´ P EC Ð R
- pu
P EC Ð R ( pu ) = ----------------------------------------2
K ´ ( I 2 Ð R ) ´ R2
(26)
2.8 ´ P EC Ð R
- pu
P EC Ð R ( pu ) = ----------------------------------------2
K ´ ( I 2 Ð R ) ´ R2
(27)
or
The winding eddy losses for the outer or HV winding may be calculated in a similar manner. For liquidÞlled transformers, Equation (21) becomes
1 + 2.4 ´ F HL ´ P EC Ð R ( pu ) 0.8
q g1 = q g1 Ð R ´ æ ------------------------------------------------------------------ ö
è 1 + 2.4 ´ P EC Ð R ( pu ) ø
°C
(28)
1 + 2.8 ´ F HL ´ P EC Ð R ( pu ) 0.8
q g1 = q g1 Ð R ´ æ ------------------------------------------------------------------ ö
è 1 + 2.8 ´ P EC Ð R ( pu ) ø
°C
(29)
or
6.2.1 Typical calculations for dry-type transformers
Given a nonsinusoidal load current with the following harmonic distribution:
Ih
---I1
h
20
Ih
---I1
h
1
1.00
8
0.010
2
0.044
9
0.018
3
0.092
10
0.015
4
0.022
11
0.046
5
0.412
12
0.010
6
0.018
13
0.048
7
0.199
Ñ
Ñ
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
Determine the maximum load current that can be continuously drawn (under standard conditions) from an
IEEE Std C57.12.01-1998 dry-type transformer with the following characteristics taken from the certiÞed
test report.
Ñ
Ñ
Ñ
Ñ
High-voltage winding
13 800 V Delta
Resistance = 2.0679 W @ 100 ¡C*
Low-voltage winding
480 V Wye
Resistance = 0.000589 W @ 100 ¡C*
Rated capacity
2500 kVA, three-phase, 80 ¡C rise
Type AA
Load losses at 100 ¡C = 15 723 W
(*Resistances are the sum of the three phases in series.)
Ñ
Values for R1 and R2 can be determined using the note in 6.2:
R1 = 0.4595 W R2 = 0.000393 W
Ñ Values for I1-R and I2-R calculated from kVA and voltage ratings are as follows:
I1ÐR = 104.6 A I2ÐR = 3007 A
Ñ The total stray loss can be calculated from Equation (22) as follows:
PTSLÐR = 15 723 Ð 1.5 ´ (104.62 ´ 0.4595 + 30072 ´ 0.000393)
PTSLÐR = 15 723 Ð 1.5 ´ (5027 + 3554)
PTSLÐR = 15 723 Ð 12 872 = 2851 W
Ñ The winding eddy loss is then calculated by assumption 2) in 6.2 and by Equation (23).
PECÐR = 2851 ´ 0.67 = 1910 W
Since the transformer turns ratio exceeds 4:1 and the secondary current exceeds 1000 A, the low-voltage
winding eddy-current loss is 0.7 times PECÐR and Max PECÐR
1.003can
pu be calculated from Equation (27) as follows:
2.8 ´ 1910
Max P EC Ð R ( pu) = ------------------------- =
1.5 ´ 3554
Copyright © 1999 IEEE. All rights reserved.
21
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
As in the previous example, values for Ih(pu)2, h2, and Ih(pu)2h2 are required for the calculation of PLL(pu)
from Equation (16). These are calculated and tabulated as follows:
Ih
---I1
h
I hö
æ ---è I 1ø
2
2
h2
I hö 2
æ ---h
è I 1ø
1
1.000
1.000
1
1.0000
2
0.044
0.00194
4
0.00776
3
0.092
0.00846
9
0.07614
4
0.022
0.00048
16
0.00765
5
0.412
0.16974
25
4.24350
6
0.018
0.00032
36
0.01152
7
0.199
0.03960
49
1.9404
8
0.010
0.00010
64
0.0064
9
0.018
0.00032
81
0.02592
10
0.015
0.00023
100
0.02300
11
0.046
0.00212
121
0.25652
12
0.010
0.00010
144
0.01440
13
0.048
0.00230
169
0.38870
S
Ñ
1.226
Ñ
8.002
Applying the 3rd column summation in Equation (8) gives an rms value of the nonsinusoidal load current of
1.107. From Equation (16), the local loss density produced by the nonsinusoidal load current in the region of
highest eddy-current loss is
PLL (pu) = 1.226 ´ (1 + 1.003 ´ 6.528) = 9.253 pu
Thus, the rms value of the maximum permissible nonsinusoidal load current with the given harmonic composition, from Equation (17), is
I max ( pu ) =
2.003
------------------------------------------ = 0.515 A
1 + 6.528 ´ 1.003
or
Imax = 0.515 ´ 3007 = 1549 A
In this case, the transformer capability with the given nonsinusoidal load current harmonic composition is
approximately 52% of its sinusoidal load current capability.
22
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
6.2.2 Typical calculations for liquid-Þlled transformers
The next example illustrates the corrected temperature rise calculations for a liquid-Þlled transformer, meeting IEEE Std C57.12.00-1993, with the following characteristics taken from the certiÞed test report.
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
High-voltage winding
34 500 V Delta
Resistance = 18.207 W @ 75 ¡C*
Low-voltage winding
2400 V Wye
Resistance = 0.02491W @ 75 ¡C*
Rated capacity
2500 kVA, three-phase, 55 ¡C average winding rise, 65 ¡C hottest spot rise
Type OA
No-load losses = 5100 W
Load losses at 75 ¡C = 21941 W
(*Resistances are the sum of the three phases in series.)
Values for R1 and R2 can be determined using the note in 6.2:
R1 = 4.046 W R2 = 0.01661 W
Ñ Values for I1ÐR and I2ÐR calculated from kVA and voltage ratings are as follows:
I1ÐR = 41.8 A I2ÐR = 601.4 A
Ñ The total stray loss can be calculated from Equation (22) as follows:
PTSLÐR = 21 941 Ð 1.5 ´ (41.82 ´ 4.046 + 601.42 ´ 0.01661)
PTSLÐR = 21 941 Ð 1.5 ´ (7069 + 6008)
PTSLÐR = 21 941 Ð 19 615 = 2326 W
Ñ The winding eddy loss is then calculated by assumption 2) in 6.2 and by Equation (24).
PECÐR = 2326 ´ 0.33 = 767 W
Ñ By Equation (25), the other stray losses are:
POSLÐR = 2326 Ð 767 = 1559 W
Ñ
The data may be tabulated as follows:
No load
5100 W
I2R
19 615 W
Stray and eddy loss
2326 W
Total loss
27 041 W
The assumed temperature rises above ambient are
HV and LV average rise
55 °C
Top-oil rise
55 °C
Hot spot conductor rise
65 °C
Copyright © 1999 IEEE. All rights reserved.
23
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
The harmonic distribution was determined at a load which was approximately 75% of the magnitude of the
fundamental current. The distribution, normalized to the fundamental, was supplied as follows:
Ih
---I1
h
Ih
---I1
h
1
1.00
11
0.0712
3
0.453
13
0.0512
5
0.267
15
0.0425
7
0.186
17
0.0402
9
0.0915
19
0.0387
The calculations to determine the Harmonic Loss Factors for the winding eddy losses and the other stray
losses are tabulated below.
Ih
---I1
h
I hö
æ ---è I 1ø
2
2
h2
I hö 2
æ ---h
è I 1ø
h0.8
2
I hö 0.8
æ ---- h
è I 1ø
1
1.000
1.000000
1
1.000000
1.000000
1.000000
3
0.453
0.205209
9
1.846881
2.408225
0.494189
5
0.267
0.071289
25
1.782225
3.623898
0.258344
7
0.186
0.034596
49
1.695204
4.743276
0.164098
9
0.0915
0.008372
81
0.678152
5.799546
0.048555
11
0.0712
0.005069
121
0.613402
6.809483
0.034520
13
0.0512
0.002621
169
0.443023
7.783137
0.020403
15
0.0425
0.001806
225
0.406406
8.727161
0.015763
17
0.0402
0.001616
289
0.467036
9.646264
0.015589
19
0.0387
0.001498
361
0.540666
10.54394
0.015792
S
Ñ
1.332077
Ñ
9.472996
Ñ
2.067254
The third column summation results in an rms current value of 1.15 pu. The Þfth column summation results
in a Harmonic Loss Factor for the winding eddy losses of 7.11, and the seventh column summation results in
a Harmonic Loss Factor for the other stray losses of 1.55.
24
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
The division of the eddy and other stray losses is tabulated as follows:
Eddy loss
767 W
Other stray loss
1559 W
Total stray loss
2326 W
In order to determine the top-oil rise, the total losses must be corrected to reßect the lower rms current below
the rated current and also the effects of the harmonic content. The rms current corrected for the 75% load
results in the following multiplier to determine losses at the speciÞed load conditions:
PLL (pu) = 1.152 ´ 0.752 = 0.744
Equation (19) is tabulated as follows:
Type of loss
Rated losses
(watts)
No-load
5100
5100
5100
I2R
19 615
14 592
14 592
767
571
7.11
4060
Other stray
1559
1160
1.55
1798
Total losses
27 041
21 423
Winding
eddy
Rated losses
(watts)
Harmonic
multiplier
Corrected
losses
25 550
The top-oil rise may now be calculated by Equation (18).
25550 0.8
q TO = 55 ´ æ --------------- ö
= 52.6 °C
è 27041 ø
The rated inner or LV winding losses can be calculated as follows:
I2ÐR2 R = 1.5 ´ 601.42 ´ 0.01661 = 9011 W
The losses under the speciÞed load conditions are
I22 R = 9011 ´ (1.15 ´ 0.75)2 = 6704 W
By assumption 4) in 6.2, since the currents are less than 1000 A, it is assumed that 60% of the winding eddy
losses are in the LV winding. The maximum eddy loss at the hot spot region is assumed to be four times the
average eddy loss. The hot spot conductor rise over top-oil temperature can be calculated by Equation (20)
and (26), using watts rather than per unit values.
Copyright © 1999 IEEE. All rights reserved.
25
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
6704 + 4060 ´ 2.4 0.8
6704 + 9744 0.8
q g = ( 65 Ð 55 ) ´ æ -------------------------------------------- ö = 10 ´ æ ------------------------------ ö = 13.9 °C
è 9011 + 767 ´ 2.4 ø
è 9011 + 1841 ø
The hot spot conductor rise over ambient then becomes
52.6 + 13.9 = 66.5 °C
NOTEÑThis temperature rise exceeds the limit of the rated 65 °C hottest spot rise.
6.3 Neutral bus capability for nonsinusoidal load currents that include third
harmonic components
The presence of third harmonic components in the nonsinusoidal load current composition can introduce
zero-sequence currents into the neutral bus of a wye-connected transformer. Excessive heating of the neutral
bus may occur when the cumulative magnitude of the zero-sequence current for all phases exceeds the neutral bus capability.
When third harmonic components are found to be present in the nonsinusoidal load current for wye connected transformers, a measurement of the neutral bus ampacity is recommended to determine the magnitude of the zero-sequence current. The transformer manufacturer may then be consulted to determine the
capability of the neutral bus to carry the zero-sequence current.
26
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
Annex A
(informative)
Bibliography
[B1] Bewley, L. V., Two Dimensional Fields in Electrical Engineering, McMillan & Co., 1948.
[B2] Bishop, M. T., and Gilker, C., ÒHarmonic caused transformer heating evaluated by a portable PC-controlled meter,Ó 37th Annual Rural Electric Power Conference, 1993.
[B3] Blume, L. F., et al., Transformer Engineering, 2nd Ed., pp. 56Ð65, New York: John Wiley & Sons, Inc.,
1951.
[B4] Cox, M. D., and Galli, A. W., ÒTemperature rise of small oil-Þlled distribution transformers supplying
nonsinusoidal load currents,Ó IEEE Transactions on Power Delivery, vol. 11, no. 1, Jan. 1996.
[B5] Crepaz, S., ÒEddy current losses in rectiÞer transformers,Ó IEEE Transactions on Power Apparatus and
Systems, vol. PAS-89, no. 7, Sept./Oct. 1970.
[B6] Dwight, H. B., Electrical Coils and Conductors, Chapter 3, New York: McGraw-Hill Book Co, Inc.,
1945.
[B7] Field, A. B., ÒEddy Currents in Large Slot-Wound Conductors,Ó AIEE Proceedings, vol. 24, 1905.
[B8] Frank, J. M., ÒOrigin, development and design of K factor transformers,Ó IEEE Transactions On Industry Applications, Sept./Oct. 1997.
[B9] Hesterman, B., ÒTime-domain K-factor computation methods,Ó 29th International Power Conversion
Conference, Sept. 1994.
[B10] Hwang, M. D.; Grady, W. M.; and Sanders, H. W., Jr.; ÒAssessment of winding losses in transformers
due to harmonic currents,Ó International Conference on Harmonics in Power Systems, Worcester Polytechnic Institute, Worcester, Mass., Oct. 1984.
[B11] Hwang, M D.; Grady, W. M.; and Sanders, H. W., Jr.; ÒCalculation of winding temperatures in distribution transformers subjected to harmonic currents,Ó IEEE Transactions On Power Delivery, vol. 3, no. 3,
July 1988.
[B12] Hwang, M. D.; Grady, W. M.; and Sanders, H. W., Jr.; ÒDistribution transformer winding losses due to
nonsinusoidal currents,Ó IEEE Transactions On Power Delivery, vol. PWRD-2, no. 1, Jan. 1987.
[B13] Kelley, A.W.; Edwards, S.W.; Rhode, J.P.; and Baran, M. ÒTransformer derating for harmonic currents: A wideband measurement approach for energized transformers,Ó IEEE Industry Applications Conference, vol. 1, pp.840-847, Oct. 1995.
[B14] Kennedy, S. P., and Ivey, C. L., ÒApplication, design and rating of transformers containing harmonic
currents,Ó 1990 Annual Pulp and Paper Industry Technical Conference.
[B15] Massey, G. W., ÒEstimation methods for power system harmonic effects on power distribution transformers,Ó 37th Annual Rural Electric Power Conference, 1993.
[B16] MIT Electrical Engineering Staff, Magnetic Circuits and Transformers, Chapter 5, New York: John
Wiley & Sons, 1949.
Copyright © 1999 IEEE. All rights reserved.
27
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
[B17] Pierce, L. W., ÒTransformer design and application considerations for nonsinusoidal load currents,Ó
IEEE Transactions On Industry Applications, vol. 31, no. 3, pp. 633Ð645, May/June 1996.
[B18] UL 1561-1994, Dry-Type General Purpose and Power Transformers.
[B19] UL 1562-1994, Transformers, Distribution, Dry-TypeÑOver 600 Volts.
28
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
Annex B
(informative)
Comparison of UL K-factor deÞnition and IEEE Std C57.110-1998
Harmonic Loss Factor deÞnition
B.1 UL DeÞnition of K-Factor
The deÞnition for the K-factor rating for dry-type transformers is given in UL 1561-1994 and UL 15621994. Per Paragraph 7B.1 added to UL 1562 on May 12, 1992, UL deÞnes K-factor as follows:12
1)
ÒK-FACTORÑA rating optionally applied to a transformer indicating its suitability for use
with loads that draw nonsinusoidal currents.Ó
2)
ÒThe KÐ factor equals
¥
å I h ( pu)
2 2
h
h=1
where
Ih(pu)
h
3)
= the rms current at harmonic ÒhÓ (per unit of rated rms load current);
= the harmonic order.Ó
ÒK-factor rated transformers have not been evaluated for use with harmonic loads where the
rms current of any singular harmonic greater than the tenth harmonic is greater than 1/h of the
fundamental rms current.Ó
B.2 Relationship between K-factor and Harmonic Loss Factor
The UL deÞnition of K-factor is based on using the transformer rated current in the calculation of per-unit
current in the above equation. Substituting the rated current into the UL equation for the K-factor gives
¥
K - factor =
å
h=1
I 2 2 1
----h- h = ----2IR
IR
¥
å Ih
2 2
h
(B-1)
h=1
where
IR = rated rms load current of transformer.
The Harmonic Loss Factor, as deÞned by IEEE Std C57.110-1998, is given by Equation (11) as follows:
h = h max
I 2 2
---h- h
I1
h=1
= -------------------------------h = h max
Ih 2
å ---I 1-
å
F HL
h=1
12The
following standards should be consulted for a complete description of UL requirements for K-factor rated dry-type transformers:
1. UL 1561-1994, Dry-Type General Purpose and Power Transformers.
2. UL 1562-1994, Transformers, Distribution, Dry-TypeÑOver 600 Volts.
Copyright © 1999 IEEE. All rights reserved.
29
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
I1 is a constant and may be moved in front of the summation sign and eliminated as shown in Equation (B-2).
h = h max
F HL
h=h
max
1
2 2
2 2
------2- å I h h
Ih h
å
I1 h = 1
h=1
= ---------------------------------- = --------------------------h = h max
h = h max
1
2
2
------2- å I h
å Ih
I1 h = 1
h=1
(B-2)
Then rearranging Equation (B-2) gives
h = h max
å
h = h max
2 2
I h h = F HL
å
Ih
2
(B-3)
h=1
h=1
substituting the above in Equation (B-1) gives
h = h max
å
Ih
2
h=1
- F HL
K - factor = --------------------2
IR
(B-4)
The above equation gives the relationship of the Harmonic Loss Factor to the UL K-factor. The Harmonic
Loss Factor is a function of the harmonic current distribution and is independent of the relative magnitude.
The UL K-factor is dependent on both the magnitude and distribution of the harmonic current. For measurements of harmonic currents in existing installations the numerical value of the K-factor is different from the
numerical value of the Harmonic Loss Factor. For a set of harmonic load current measurements the calculation of the UL K-factor is dependent on the transformer rated secondary current. For a new transformer with
harmonic currents speciÞed as per unit of the rated transformer secondary current the K-factor and Harmonic Loss Factor have the same numerical values. The numerical value of the K-factor equals the numerical value of the Harmonic Loss Factor only when the square root of the sum of the harmonic currents
squared equals the rated secondary current of the transformer.
30
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
B.3 Example calculations
Assume an existing installation with a 2500 kVA, 480 V three-phase dry-type transformer. Harmonic load
current measurements were made as given in the table below. The K-factor is calculated as shown below.
IR = 3007.1 A
h2
h
Ih
Ih
----IR
Ihö
æ ---è I Rø
2
2
Ihö 2
æ ---- h
è I Rø
1
1
1764
0.5866117
0.3441133
0.3441133
5
25
308.5
0.1025905
0.0105248
0.2631205
7
49
194.9
0.0648133
0.0042008
0.2058373
11
121
79.39
0.0264009
0.0006970
0.0843376
13
169
50.52
0.0168002
0.0002822
0.0476999
17
289
27.06
0.0089987
0.0000810
0.0234023
19
361
17.68
0.0058794
0.0000346
0.0124789
S = K-factor =
0.9810
Similar calculations may be made for other transformer kVA ratings applied to the same set of harmonic
load current measurements as shown above. For transformers rated less than 1500 kVA, the rms value of the
harmonic load currents exceeds the rated transformer current. The results are summarized below for the
same set of harmonic current measurements. The Harmonic Loss Factor is calculated as shown in 4.6.
KVA
IR-rated
current
K-factor
Harmonic
Loss Factor
FHL
1500
1804.0
2.726
2.726
2000
2405.7
1.533
2.726
2500
3007.1
0.981
2.726
Copyright © 1999 IEEE. All rights reserved.
31
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
Annex C
(informative)
Temperature rise testing procedures
C.1 Proposed method of performing a rigorous temperature rise test13
The temperature rise test with harmonic secondary load should be made under normal service conditions of
the equipment, with the unit fully assembled and with its normal means of cooling. Liquid Þlled transformers will be Þlled to their proper liquid level. If transformers are equipped with thermal indicators, bushingtype current transformers, or the like, such devices should be assembled with the transformer.
The conditions under which the temperature limits apply are stated in either IEEE Std C57.12.01-1998 or
IEEE Std C57.12.00-1993 as applicable for dry or liquid-Þlled transformer types. Note that special temperature rise limits may apply for certain high harmonic load test conditions; these limits should be agreed on by
the manufacturer and the purchaser representative for speciÞc applications only. Unless otherwise speciÞed,
all transformers should be tested in the combination of connections and taps that gives rise to the highest
winding temperature rise in each test condition.
C.1.1 Standard deÞnitions and procedures
Refer to either IEEE Std C57.12.91-1995 or IEEE Std C57.12.90-1993 for the standard deÞnitions and procedures as appropriate to the particular design.
C.1.2 Transformer components temperature measurement
Due to the rapid spatial variation of the temperature within, and on the surface of, the various transformer
components, thermocouples in intimate contact are the preferred method of measuring temperature. The
need for several thermocouples within the coils and core of the transformer will necessitate these being
attached during the manufacture of the test specimen, due regard being made of the dielectric circumstances
in the design and routing of the thermocouples. Detailed drawings of the location and method of attachment
of all thermocouples should be included in the test report. Temperatures should be recorded at regular intervals, not exceeding 30 min.
C.1.2.1 Winding temperature measurement
Thermocouples should be attached directly to the winding turns, at locations determined from electromagnetic/thermal studies as having the highest expected temperature rises. Thermocouples should be Þtted on
three-phase transformers to at least the center phase and one outside phase winding group, and to both the
primary and secondary coils on all transformers. The average temperature rise of the windings should be
determined by the resistance method.
13This
test procedure is provided as a reference for a rigorous test of the transformer temperature rise. However, transformer manufacturers do not have the capability to test to this method, particularly as the size of the unit increases. Furthermore, at the time this document was developed, there have been reports of only a few small units having been tested according to this method. Nevertheless, the
procedure provides a comparison to the more practical, but much less accurate alternatives listed later in this annex. It is also hoped that
by documenting this procedure, an accurate reference may be provided by which more practical and more accurate methods of simulated load temperature rise testing might be developed.
32
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
C.1.2.2 Core temperature measurement
Thermocouples should be attached directly to the core surfaces at locations determined from electromagnetic/thermal studies as having the highest expected temperature rises. These are expected to be inside the
corners of the winding window in close proximity to the coils whose harmonic Þeld strengths are concentrated. The thermocouples should maintain Þrm contact with the surface and be thermally insulated from the
surrounding medium.
C.1.2.3 Structural and enclosure temperature measurement
Thermocouples or thermometers should be placed to record the maximum exterior enclosure temperatures
and the temperatures of internal structural parts susceptible to high temperature rises. In particular, iron or
alloy parts in close proximity to terminals carrying large currents or to the magnetic core, should be monitored for their temperature rise.
C.1.2.4 Liquid temperature measurement
In liquid-Þlled transformers the top liquid temperature should be measured by a thermocouple or suitable
thermometer immersed approximately 50 mm (2 in) below the top liquid surface. The average liquid temperature should be taken to be equal to the top liquid temperature minus half the difference in temperature of the
moving liquid at the top and the bottom of the cooling means. Where the bottom liquid temperature cannot
be measured directly, the temperature difference may be taken to be the difference between the surface temperature of the liquid inlet and outlet.
C.1.3 Electrical loading conditions
The intent of the temperature rise test under harmonically loaded conditions is to simulate, as closely as
practical, the actual in-service conditions. In so doing, the speciÞc current frequency spectra should be speciÞed for each loading condition to be tested, and these should be standardized or agreed by a speciÞc customer. The primary winding is to be energized directly from a sinusoidal source, with the secondary winding
loaded by a system capable of drawing the necessary harmonic currents.
C.1.3.1 Primary winding source characteristics
The primary winding should be directly connected to a power source whose open circuit voltage is sinusoidal, and equal to the rated voltage of the winding in its test tap connection. The impedance of the primary
winding sources should be related to the rating of the transformer to be tested by the following procedure.
Select the standard rating of a circuit breaker or switch whose rating is sufÞcient to supply the test transformer, the standard ratings being chosen from those approved by NEMA. Denote these selected values as
Vrated and Irated, and hence calculate the rated circuit load impedance as
V rated
Z L = ------------------------ for a three-phase circuit
3 ´ I rated
The primary winding source impedance should then lie within the range of 10Ð20% by magnitude of the
rated circuit load impedance, and the ratio of the source reactance to resistance should then lie between the
values of 5 and 7.
Example:
3.4 MVA, three-phase transformer, 3.8 kV primary voltage
Rated primary current = 516.6 A
Standard NEMA switch rating, 4.76 kV, 600 A
ZL = 4.58 W/phase
Copyright © 1999 IEEE. All rights reserved.
33
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
Minimum source impedance = 0.458 W/phase consisting of
complex impedance components in the range 0.090 + j 0.449
to 0.065 + j 0.453 W/phase.
Maximum source impedance = 0.916 W/phase consisting of
complex impedance components in the range 0.180 + j 0.898
to 0.130 + j 0.906 W/phase.
In the case of a single phase transformer, the equivalent calculation should be carried out to the same principles.
The primary winding source should not be modiÞed in its natural harmonic or regulation response, so as to
artiÞcially affect the natural high frequency regulation of the source by the test transformer. The transient
recovery voltage characteristics of the source are not speciÞcally set, and it is believed that its effect is negligible to the out come of the test. Note that the primary source must be capable of providing the power to support the losses in the test transformer and the secondary load circuit without over-load or a change of
frequency of more than 2%.
C.1.3.2 Secondary winding loading characteristics
The secondary winding, or windings, should be connected to a continually rated loading system capable of
drawing currents of the required magnitude and harmonic content. The loading system can consist of a combination of naturally commutating devices, or active switches, controlling the connection of linear or nonlinear devices. The predominant use of reactors and capacitors as loading devices is favorable, as this
reduces signiÞcantly the power demands on the primary winding source.
For low harmonic content loading tests the use of natural commutating devices, in conjunction with reactor
and resistive components has been found suitable. The transformer leakage reactance, stray cable and load
resistor leakage reactance have to be accounted for in the circuit design. Appreciable external reactance will
signiÞcantly reduce the harmonic content of the secondary currents.
For high harmonic content loading tests it is necessary to use active switch devices to enable chopped pulses
of current to be drawn from the secondary winding. Multiple loading circuits in parallel can be utilized to
share the continuous load and to generate speciÞc additive harmonic components.
Note that since different temperature rise conditions can result from different harmonic loading conditions
having the same Harmonic Loss Factor, FHL, the current frequency spectra achieved on test should be documented.
C.1.3.3 Electrical instrumentation requirements
The extended range of frequency of voltages and currents that are present in this test circuit place extra
demands upon the calibration and accuracy of the instrumentation system at higher frequencies. The complete system should have a proven acquisition bandwidth of not less than 3 kHz, including the voltage and
current transformers and the recording system. The Fourier analysis should be capable of resolving a 3 kHz
signal by utilizing data from a sufÞciently wide data window to maintain accuracy.
34
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
C.2 Alternate simulated load temperature rise testing procedures14
The purpose of the test is to establish the top oil temperature rise in steady-state condition, with dissipation of
total loss equal to the loss at the nonsinusoidal load current, and rated sinusoidal transformer voltage. The test
should also establish the average winding temperature rise above oil under the same conditions for liquidÞlled transformers, and the average winding temperature rise above ambient for dry-type transformers.
C.2.1 Test method
The test method used may be the loading-back method, the impedance kVA method, or the short circuit (separate load loss and excitation test) method in accordance with IEEE Std C57.12.90-1993 or IEEE Std
C57.12.91-1995 provided the load is adjusted to compensate for harmonic losses.
C.2.2 Dry-type transformers
The basic premise of the simulated test is to determine the temperature rises after inducing losses equivalent
to the losses generated by nonsinusoidal load current. These harmonic losses are simulated by increasing the
test current by an appropriate amount according to the following methods.
C.2.2.1 Load loss simulation Method I
As an alternate to the actual loading method described above, a less accurate simulation may be performed.
This simulation requires less equipment and should be used with caution, since it is possible to overload one
winding signiÞcantly. As such, the procedure is most suitable for small units where the winding eddy losses
are similar for both the high-voltage and low-voltage windings.
The load losses supplied by the transformer under test (PLLÐT) are monitored and maintained during the test.
These losses are determined as follows:
PLLÐT = PDC ´ (1 + FHL ´ PEC) ´ TC
W
(C-1)
where
PEC (pu) = assumed eddy-current losses under rated conditions in per unit of rated load I2R loss calculated
as follows:
P AC Ð P DC
------------------------ for transformers rated 300 kVA or less, and
2
P DC ´ T C
C ´ ( P AC Ð P DC )
--------------------------------------- for transformers rated more than 300 kVA
2
P 2 Ð DC ´ T C
C
= 0.7 for transformer having a turns ratio greater than 4:1 and having one or more windings with a
current rating greater than 1000 A, or
14CAUTIONARY
NOTE: This document gives simpliÞed calculation methods that can give reasonable estimates for loading. Implicit
within this simpliÞed method is the premise that for the same harmonic loss factor, the same losses and hence temperature rise will be
produced. This is not necessarily true. Harmonic loading of transformers gives rise to higher losses and their distribution within the
transformer is very different from standard 60 Hz losses, and their magnitudes and location are dependent upon complex calculations of
geometry and ßux penetration depths. These loading methods, therefore, do not give a good simulation of the loss spatial distribution,
and hence should not be used as deÞnitive methods for the determination of hot-spot temperatures in windings, core or structural components.
Copyright © 1999 IEEE. All rights reserved.
35
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
0.6 for all other transformers;
P2ÐDC = the I2R losses for the inner winding with the winding at ambient temperature; and
Ts + Tk
T C = ----------------- temperature correction factor
Ta + Tk
where
Ts = the maximum acceptable insulation system temperature rise plus 20 °C;
Ta = the ambient temperature at which the impedance losses and the I2R losses were determined;
Tk = 234.5 °C for copper windings or 225 °C for aluminum windings.
NOTEÑThe value of Tk may be as high as 230 °C for alloyed aluminum.
The impedance losses and the I2R losses should be determined in accordance with IEEE Std C57.12.90-1993
or IEEE Std C57.12.91-1995.
C.2.2.2 Load loss simulation Method II
This method is similar to Method I above, except it attempts to account for the different eddy-current losses
for each winding by establishing an equivalent harmonic current. It may therefore be more appropriate for
larger transformers and for units having large differences in the high-voltage and low-voltage winding eddy
losses. This simulation also requires less equipment than the actual loading method, but requires a number of
mathematical corrections.
The load current supplied by the transformer under test may be determined from Equation (17). The maximum designed current rating is deÞned as
I max ( pu ) =
P LL Ð R ( pu )
---------------------------------------------------1 + F HL ´ P EC Ð R ( pu )
pu
The per-unit test current required to simulate the losses for the harmonic loading in each winding, referred to
the rated current, is given by
I T ( pu ) =
1 + F HL ´ P EC Ð R ( pu )
----------------------------------------------------P LL Ð R ( pu )
pu
(C-2)
Since the per-unit eddy-current losses in each winding are normally not the same, the following factors are
deÞned for convenience:
a1 =
1 + F HL ´ P EC Ð 1 Ð R ( pu )
-----------------------------------------------------------=
P LL Ð 1 Ð R ( pu )
1 + F HL ´ P EC Ð 1 Ð R ( pu )
(C-3)
1 + F HL ´ P EC Ð 2 Ð R ( pu )
-----------------------------------------------------------=
P LL Ð 2 Ð R ( pu )
1 + F HL ´ P EC Ð 2 Ð R ( pu )
(C-4)
and
a2 =
36
Copyright © 1999 IEEE. All rights reserved.
IEEE
Std C57.110-1998
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
The current for each winding may then be calculated as follows:
I 1 Ð T = a1 ´ I 1 Ð R
amperes
(C-5)
amperes
(C-6)
and
I 2 Ð T = a2 ´ I 2 Ð R
Since the current of only one winding may determine the value of the test current, an intermediate value is
established as a compromise.
IT (pu) = a ´ IR (pu)
pu
(C-7)
where
a1 + a2
a = ----------------2
(C-8)
The individual temperature rise values determined from testing with this compromise load current are then
corrected by the following equations:
a1 2
q 1 = q 1 Ð T ´ æ ------ ö
èaø
(C-9)
a2 2
q 2 = q 2 Ð T ´ æ ------ ö
èaø
(C-10)
Note that this procedure overloads one winding during the temperature test. If the winding to be overloaded
is not capable of withstanding the expected temperature, a lower value of a may be used. This value should
not be less than the lower value of a1 and a2.
C.2.3 Liquid-Þlled transformers
The top-oil rise must Þrst be determined for liquid-Þlled transformers, before the winding temperature rises
may be established. This requires the injection of the total losses, which is composed of the load loss plus the
no load loss. The load loss is the total loss developed from the non-sinusoidal load current and includes the
winding dc losses, winding eddy losses and the other stray losses. The relationship of these losses is deÞned
by Equation (19):
P LL = P + F HL ´ P EC Ð R + F HL Ð STR ´ P OSL Ð R
W
The no-load loss corresponds to the rated transformer voltage. The total injected losses are then measured
and the fundamental power-frequency current is adjusted to give the speciÞed test value of the total loss.
When the top-oil temperature rise has been established, the test continues with a sinusoidal test current
equivalent to the total load loss (PLL). This condition is maintained for 1 h during which measurements of oil
and cooling medium temperatures are made. The equivalent test current is determined by Load Loss Simulation Method II, in section C.2.2.2 above. At the end of the temperature rise test, the temperatures of the two
windings are determined according to standard methods in the references noted in section C.2.1.
Copyright © 1999 IEEE. All rights reserved.
37
IEEE
Std C57.110-1998
IEEE RECOMMENDED PRACTICE FOR ESTABLISHING TRANSFORMER CAPABILITY
Annex D
(informative)
Tutorial discussion of transformer losses and the effect of harmonic currents on these losses
Power transformers with ratings up to 50 MVA are almost always of core form construction. High-voltage
and low-voltage windings are concentric cylinders surrounding a vertical core leg of rectangular or circular
cross section. The vertical core legs and the horizontal core yoke members that constitute the magnetic circuit are made up of thin steel laminations. In the top and bottom yoke regions there are usually external
clamping structures (clamps) that may be made of either metallic or insulating materials. Oil-immersed
transformers are contained within a steel tank, while dry-type transformers may be either freestanding or
surrounded by a metal enclosure. If direct current is passed through the transformer winding conductors, a
simple I2R loss will be produced, where R is the dc resistance of the winding. However, if an alternating current (ac) of the same magnitude is passed through the winding conductors, an additional loss is produced.
This can be explained as follows. When the transformer windings carry the ac current, each conductor is surrounded by an alternating electromagnetic Þeld whose strength is directly proportional to the magnitude of
the current. A picture of the composite Þeld produced by rated load current ßowing through all the winding
conductors is shown in Figure D.1, which is a cross-sectional view through the core, windings, clamps, and
tank. Each metallic conductor linked by the electromagnetic ßux experiences an internal induced voltage
that causes eddy currents to ßow in that conductor. The eddy currents produce losses that are dissipated in
the form of heat, producing an additional temperature rise in the conductor over its surroundings. This type
of extra loss beyond the I2R loss is frequently referred to as Òstray loss.Ó Although all of the extra loss is an
eddy-current loss, the portion in the windings is usually called Òeddy-current lossÓ (PEC), and the portion
outside the windings is called Òother stray lossÓ (POSL).
Eddy-current loss in winding conductors is proportional to the square of the electromagnetic Þeld strength
(or the square of the load current that produces the Þeld) and to the square of the ac frequency. Other stray
losses are generally proportional to current raised to a power slightly less than 1, because the depth of penetration of the electromagnetic ßux into the other metallic parts (usually steel) varies with the Þeld strength.
(For very high-frequency harmonic currents the electromagnetic ßux may not totally penetrate the winding
conductors either, but it is conservative to assume that the eddy-current loss, PEC, is proportional to the
square of the harmonic current frequency.) When a transformer is subjected to a load current having signiÞcant harmonic content, the extra eddy-current loss in winding conductors and in other metallic parts will elevate the temperature of those parts above their normal operating temperature under rated conditions.
Experience has shown that the winding conductors are the more critical parts for determination of acceptable
operating temperature, so the objective should be to prevent the losses in winding conductors under harmonic load conditions from exceeding the losses under rated frequency operating conditions.
The inner winding of a core form transformer typically has higher eddy-current loss than the outer winding,
because the electromagnetic ßux has a greater tendency to fringe inwardly toward the low reluctance path of
the core leg. Furthermore, the highest local eddy-current loss usually occurs in the end conductors of the
inside winding. This is a result of the fact that this is the region of highest radial electromagnetic ßux density
(closest spacing of the radially directed ßux lines in Figure D.1) and the radial ßux passes through the width
dimension of the rectangular winding conductor. Since the width dimension of a conductor is typically 3Ð5
times the thickness dimension and eddy-current loss is proportional to the square of the dimension, high loss
is produced in the end conductors. Certain simplifying assumptions have been made in this recommended
practice about the relative proportions of the eddy-current losses in the inner and outer windings and the
relation between average eddy-current losses and maximum local eddy-current losses. These assumptions,
which are conservative, may be used when speciÞc knowledge of the eddy-current loss magnitude is not
38
Copyright © 1999 IEEE. All rights reserved.
WHEN SUPPLYING NONSINUSOIDAL LOAD CURRENTS
IEEE
Std C57.110-1998
available. However, more accurate calculations can be made if design values of eddy-current losses are available from the transformer manufacturer.
The recommendations for determination of acceptable operating conditions contained in this recommended
practice are based on the calculation of a Òtransformer capability equivalent,Ó which establishes a current
derating factor for load currents having a given harmonic composition. Equation (17) provides a calculation
of the maximum rms value of a nonsinusoidal load current (in per unit of rated load current) that will ensure
that the losses in the highest loss density region of the windings do not exceed the design value of losses
under rated frequency operating conditions. Example cases are presented for the situations where design
eddy-current loss data are available from the manufacturer or where they are not.
Harmonic currents ßowing through transformer leakage impedance and through system impedance may also
produce some small harmonic distortion in the voltage waveform at the transformer terminals. Such voltage
harmonics also cause extra harmonic losses in the transformer core. However, operating experience has not
indicated that core temperature rise will ever be the limiting parameter for determination of safe magnitudes
of nonsinusoidal load currents.
Figure D.1ÑElectromagnetic Þeld produced by load current in a transformer
Copyright © 1999 IEEE. All rights reserved.
39