TEMP CON Sel Cht Pg341-356 (Page 15)

advertisement

PID Temperature Controller with 3-Digit LED Display

48-DIN sized PID temperature controller with automatic tuning function and single, 3-digit LED display

■ J, K or E thermocouple or 3-wire Pt100 resistance thermometer input options

■ Relay, voltage pulse or analog 4-20mA output types

■ 2 levels of keypad security locking

■ Five-stage PV deviation bargraph

■ Selectable operation, PID, PD or ON/OFF

■ Automatic reset function in PD control

■ 8 function temperature alarm relay

■ Optional second alarm relay

■ Alarm hysteresis adjustable from 0.1 to 99.9˚C

■ Fast sampling period 0.25 seconds

■ Case and wiring connections identical to GCS-23A

FCS-13A and FCS-23A for ease of upgrading

■ IP54 protection

■ UL and CSA approved

New

Models

GCS-132

Options and ordering codes

GCS-132 – R / EJ AL2 100-240VAC

48x48mm PID controller with single

3-digit display and one alarm

Main control output:

Relay output

R

Signal voltage for SSR

Analogue current 4-20mA

S

A

100-240VAC supply

24VAC/DC supply

Without second alarm

PRICE

INFORMATION

AND ORDERING

AL2 With second alarm

J-thermocouple

K-thermocouple

E-thermocouple

Pt100 resistance thermometer

EJ

EK

EE

R

*

*For Pt100 input, please specify temperature range -19.9 to 99.9˚C or -199 to 400˚C

Please note: all models supplied with the following:

BL – Screw mounting bracket IP – IP54 protection

Specifications

Input type

Rated scale

Sensor resistance

Accuracy

Display

Control action

Proportional band

Integral time

Derivative time

Hysteresis in On/Off action

Proportional cycle

Output: relay types

Output: signal voltage types

Output: analogue types

Temperature alarm relay A1

Temperature alarm relay A2

Temp. alarms setting accuracy

Temperature alarms action

High limit alarm

Low limit alarm

Mounting

Front panel

Weight

Case material

(1)

(1)

High/low limits alarm

Dielectric strength (2)

(1)

High/low limits range alarm

Absolute value (process) alarm

Sensor correction (input shift)

Sensor break protection

Supply voltage

Power consumption

Ambient temperature

Ambient humidity

Insulation resistance (2)

K-thermocouple

0 to 999˚C

J-thermocouple E-thermocouple

0 to 999˚C

100 Ω or less

0 to 600˚C

±0.3% of full scale ± digit

3 digit red LED, 10mm high

DIN Pt100 RTD J Pt100 RTD

–19.9 to 99.9/–199 to 400˚C

10 Ω per wire or less

User-selectable: PID with autotune, PD with autoreset, on/off

0 to 999˚C (0.0 to 99.9 for Pt100 with decimal point) on/off action when set to 0. Factory set to 10˚C

1 to 999 secs (off when set to 0), Factory set to 200 secs

1 to 300 secs (off when set to 0), Factory set to 50 secs

0.1 to 99.9˚C, Factory set to 1.0˚C

1 to 120 seconds, Relay output type: Factory set to 30 secs; Signal voltage type: Factory set to 3 secs

SPNO: 250V, 3A resistive load; 250V, 1A inductive load, cos ø = 0.4

12VDC +2VDC/–0VDC 40mA, short-circuit protected

4 to 20mA DC – max. load resistance 550

SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4

SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4

±0.3% of full scale ±1 digit

ON/OFF action, hysteresis 0.1 to 99.9˚C. Factory set to 1.0˚C

Deviation from SV: -199 to + input range maximum value –19.9 to 99.9˚C for Pt100 with decimal point

Deviation from SV: -199 to + input range maximum value –19.9 to 99.9˚C for Pt100 with decimal point

Deviation from SV: ± (1 to input range maximum value) ±(0.1 to 99.9˚C) for Pt100 with decimal point

Deviation from SV: ± (1 to input range maximum value) ±(0.1 to 99.9˚C) for Pt100 with decimal point

Input range minimum value to input range maximum value

–100 to 100˚C (–10.0 to 10.0˚C for Pt 100 with decimal point) factory set to 0

Upscale: Control output off

85 to 264VAC 50/60Hz (100-240 VAC+10%-15%); 20 to 28 VDC/AC 50/60Hz

8VA approx.

0 to 50˚C

35 to 85% r.h. (non-condensing)

>10M

Ω at 500VDC

1.5k VAC for 1 min between: Sensor input terminals and ground, Power terminals and ground,

Control output terminals and ground, Alarm output terminals and ground, Sensor input terminals and

Power terminals, Control output terminals and Power terminals, Alarm output terminals and Power terminals

Flush

Membrane sheet keyboard, IP54

130g approx

Light grey polycarbonate, flame retardant and self-extinguishing

(1) Can be programmed to operate with or without ‘standby’ function (2) Do not apply voltage between sensor input terminals and control output terminals of GCS-132-S or GCS-132-A models

GCS-132

Wiring connections

Alarm output

85 to 264Vac or

20 to 28Vac/dc

A2

1

2

A1

3 COM

4 A1

5 A2

CT input

Relay contact output

Control output

6

7

8

A

9

B

10

B

RTD

(3-wire)

6

7

8

10

Non-contact voltage output or current output

Thermocouple

8

9

10 c

2-wire RTD

8

9

10

LINK

CT input for heater burnout option only.

With extension cables

Without extension cables

Notes: ● For ease of connection, especially when using cable trunking, all the terminals are designed to accept wires from the left (when

● looking from the rear of the unit).

If using a pre-wired, 2-wire Pt100 RTD, without connecting extension cables, a link should be added between terminals 9 and 10. If

● using extension cables, a third wire should be added from point C, one of the joins, as in the diagram above and all three wires should be the same gauge and length. If a simple link is added between terminals 9 and 10 in this case, no compensation for lead length will be applied.

As there is no fuse inside the temperature controller, it is recommended that one is provided in the external wiring to the power

● supply terminals.

The sensor wires should not be run adjacent to an AC power supply or the wires to the power supply terminals.

When using the relay contact output version it is recommended to provide an auxiliary relay to protect the contacts of the temperature controller’s built-in relay, even if the intended load capacity is smaller than that of the built-in contacts.

For ease of replacement without disconnecting the wiring, or to gain access to the internal programming switches, the unit can be withdrawn from the housing by pressing the release lever under the bezel and pulling firmly, holding the indents in the top and bottom of the bezel.

When re-assembling, ensure that the unit is the correct way up and that the sealing gasket has not been dislodged.

Accessories

FCSTC

FC-48-S

Finger-touch protection cover for the screw terminals.

Clear silicone rubber cover to enclose the complete bezel to give IP66 protection. Installed by placing over the bezel before the controller is panel mounted. Mounting then traps the cover between the controller and the panel for complete sealing. Operation of the keypad is still possible through the cover.

Dimensions and mounting

48

Mounting panel thickness 1 to 15mm

10 nX48-3+0.5

-0

Close mounting of n units

100

PRICE

INFORMATION

AND ORDERING

Individual mounting

45+0.5

-0