OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters’ Laboratories of Canada (ULC) Installation of a Fire Alarm System – CAN/ULC-S524-06 Verification of a Fire Alarm System – CAN/ULC-S537-04 Monitoring Fire Alarm Systems – CAN/ULC-S561-03 Objectives Discuss Compliance with the Ontario Building Code Identify the Code Requirements to install and verify a fire alarm system Identify the Code Requirements for the monitoring a fire alarm system. Underwriters’ Laboratories of Canada (ULC) Established August 15, 1920 Independent, not-for-profit product safety testing and certification organization, Standards Development Organization Offices in Toronto, Ottawa, Montreal, and Vancouver Tested products for public safety for over 80 years Accredited by the Standards Council of Canada Affiliate of Underwriters Laboratories Inc. Fire Alarm Installation BUILDING and ELECTRICAL PERMIT FIRE ALARM SYSTEM INSTALLED FIRE ALARM SYSTEM VERIFIED VERIFICATION Documentation ULC CERTIFICATE Protective Signaling Certificate Building Official Acceptance Occupancy Granted Code References OBC 3.2.4.5 (1) CAN/ULC-S524-06 OBC 3.2.4.5.(2) CAN/ULC-S537-04 OBC 3.2.4.7 (4) CAN/ULC-S561-03 OFC 6.3.1.2. (1) CAN/ULC-S536-04 Code Compliance Ontario Building Code- defines who needs a fire alarm system. Ontario Building Code – gives reference to the installation of the fire alarm system – CAN/ULC-S524 Ontario Building Code – gives reference on how the fire alarm system is to be Verified prior to occupancy. CAN/ULC-S537 Ontario Fire Code- gives reference to the ongoing maintenance of the fire alarm system –CAN/ULC-S536 What is Required to Comply to the AHJ New Building • Building and Electrical Permit • Fire Alarm System- Design/ Build documentation from the Engineer on record – Stamped by the AHJ • Fire Alarm System is installed to CAN/ULC-S524 • Verification – CAN/ULC-S537-04 • Documentation to be provided to the building owner and building official • Letter form the Engineer on record – Sign-off on the design/build • Letter from the Electrical Contractor- Installation to CAN/ULC-S524 • Verification Report- No Deficiencies • Certificate – Monitoring of the Fire Alarm System in Accordance with CAN/ULC-S561-03 Fire Alarm System This Standard CAN/ULC-S537 prescribes inspection and test procedures for the purpose of verifying that the fire alarm system is installed in conformance with the design and CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems, and performs all of its intended functions as designed. Who can perform a Verification? Any person who performs the verification of a fire alarm system should be familiar with this Standard and have received suitable formal training or sufficient experience acceptable to the authority having jurisdiction. •Company or Person other that the installing contractor 2 2 2 2 Independent Designer – Signed off Electrical contractor – Installation of Fire Alarm System Independent Alarm Company- Verification CFAA or ECAO Certified •Exception- Replacement or an addition of one device. Section 3: Verification Requirements Inspect & Test each fire alarm system – Installed to the requirements of CAN/ULC-S524 prior to occupancyReport Appendix C1- C6 – CAN/ULC-S537 Control Unit/Transponder – Tested as installed Additions, deletions, modifications replacements (including firmware and software changes – Tested to Section 6 under System Modifications Partial Occupancies and Stage replacement Inspection shall include damage or tampering Verification Procedures Continued Documentation: - CAN/ULC-S537-04- Verification of Fire Alarm Systems Report – Appendix C1 through C6 if applicable Sequence of operation Testing of all equipment and devices for correct operation • • • • Control Units , Transponders, Annunciators Data Communication Links, Isolator Modules Power Supply and Emergency Power Supply Smoke & Heat Detectors, Manual stations Documentation: Important • A copy of the verification report shall be given to the owner or the owner’s representative for the building and be kept available on site. System Modifications – Existing Buildings Field Devices added to an existing system • Compatible with control unit and other devices • Loading of the circuit has not been exceeded; • Emergency power provided is of sufficient capacity for the additional device(s); and • The input circuit to output circuit operation, including ancillary device circuits shall be tested for correct program operation, as per design and specification System Modifications Conventional Devices added, modifications, deletions • Test the device plus one on either side • Check the wiring ( supervision) • EOL Circuit to verified Replacement of a field device • Verified in accordance with this Standard Conventional Device added – Circuit from a common junction box • Test all devices served by that junction box. System Modifications Data Communication Links • • • • New and existing devices to be verified (Refer to 6.11) Computer based system (addressable) Software modifications Test all functions that could be affected by the change Addition, Modification, Deletion of Active Field Devices • • • • All changes shall be verified Operational test to be performed Correct Sequence of operation Compare before and after software (refer to 6.11B) System Modifications Control Unit and Transponder additions • Verify the Control Unit or Transponder and all the connected Devices Replacement of a Control Unit and Transponder • Verify in accordance with Section 4 for Control Units and Transponders • All existing Devices to be tested in accordance with CAN/ULCS536 Module Replacement • Verified for its intended function System Modifications Software Modifications • Re-verify all system functions affected by the modification accept the wiring supervision OR • Comparison Software utilizing mediums such as a printout or a compare program Fire Alarm System Monitoring 5.15.1 (CAN/ULC-S524) - The interconnection wiring from the fire alarm control unit or transponder to the fire signal receiving centre shall comply with CAN/ULC-S561, Installation and Services for Fire Signal Receiving Centres and Systems. CAN/ULC-S537-04 Appendix C2 (G) • Documentation to include the name and number of the Fire Signal Receiving Centre (CAN/ULC-S561) Qualified Personnel Qualified Personnel Appendix A • Must be knowledgeable about this Standard Acceptable to the AHJ • CFAA Certified or ECAO Knowledgeable about the Fire Alarm System Standard CAN/ULC-S561-03 Compliance to the OBC and OFC Course Title: Rev Date Fire/Sprinkler Alarm Monitoring Ontario Course Title: Rev Date Mandated in Ontario Signals to the Fire Department ONTARIO Ontario Building Code - 3.2.4.7 (4) Ontario Fire Code - 6.3.1.2, (2b) & (4) (CAN/ULC-S561) CAN/ULC-S561-03 Signals to the Fire Department New Buildings - OBC Existing Buildings –OFC CAN/ULC-S561-03 Contractors Shall Comply to OBC – Signals to the Fire Department by way of Fire Alarm Monitoring System in Compliance to CAN/ULC-S561-03 or NFPA 71 (Ontario). Shall provide a Certificate of Compliance attesting that the fire alarm monitoring system is in compliance to the applicable Standard. Submit document to AHJ Usually done by the electrical contractor sub-contracting the installation of the fire alarm transmitter and the connection with fire signal receiving centre. CAN/ULC-S561-03 Property Managers Shall Comply to NFC/OFC – Signals to the Fire Department by way of Fire Alarm Monitoring System in Compliance to CAN/ULC-S561-03 or NFPA 71 (Ontario). Shall provide a Certificate of Compliance attesting that the fire alarm monitoring system is in compliance to the applicable Standard. Submit document to AHJ Usually done by a ULC Listed Fire Alarm Monitoring/ Installation Company -Communications Systems – Clause 10 Methods of Communications: Passive or Active Maximum Time to receive a fire alarm signal from a protected premises – 60 seconds A communication system shall be continuously supervised to detect line faults Course Title: Rev Date Protected Premises Section 9 Course Title: Rev Date Proper “Certified” Installation Signaling Services – Clause 9.4 Fire Alarm Control Units: • Alarm, troubles and Supervisory Signals – Restoration • Power failure conditions – Restoration • Alarm Signal shall be transmitted regardless of an abnormal condition at the protected premises. • Fire Alarm Signal shall always be the highest priority • Integral communication devices in fire alarm panels shall be programmed to transmit alarm, trouble & supervisory conditions. Disposition of Signals – Clause 9.4.4 Fire Alarm Signals from a Fire Panel or Extinguishing System: • Contact fire department within 30 seconds • Contact persons designated by the owner within 5 minutes ULC Certificate Program Course Title: Rev Date What ULC Inspectors Look for? ULC Listed Transmitter Incoming power hardwired Transformer enclosed All wiring between fire alarm transmitter and the connected devices shall be in metal conduit Separate breaker (new installations) 24 hour standby power (batteries) Wiring is supervised Certificate Requirements Installation company is ULC Listed Monitoring Company is ULC Listed Contracts between the customer and Alarm Service (installation) Company Contracts Between the Alarm Service company and the monitoring company • Full Service companies excluded Regular Testing of System (ULC-S561) ULC Certificate posted on-site What Does a Certificate Mean? Installation meets CAN/ULC-S561-03 Equipment meets National Standards Monitored by ULC Listed Receiving Centre that meets CAN/ULC-S561-03 Care Contract in Place for Service and Test ULC will randomly audit premises ULC Certificate Improper Installation ¿The Unknown? • What you get when no one Polices system installations! Improper Installation Improper Installation Improper Installation Improper Installation ULC Certificate Program For CAN/ULC-S561-03 Compliant Systems, ULC can issue a Certificate stating Compliance to the StandardMeets OBC & OFC The ULC Certificate is the only proof that the entire fire alarm monitoring system is compliant Each site is issued a certificate is subject to a random audit Benefits of the ULC Certificate Extra Set of Eyes and Ears • Allows for a quicker inspection by Building and Fire Officials • Confidence in the Fire Alarm Monitoring System meets all the requirements of CAN/ULC-S561-03 • Systems are audited on a random basis • Non-compliant systems can result in the cancellation of the ULC Certificate Who can issue a ULC Certificate? Full Service Monitoring Station • Installation and monitoring – Same company Shared Service Monitoring Station with Installation Company • Two different companies Questions CAN/ULC-S561-03 THANK YOU Contact Information Alan Cavers, Area Manager, Fire & Security Systems Group, Underwriters Laboratories of Canada Phone- 1-416-697-6762 E-mail alan.n.cavers@ca.ul.com Protected Premises Improper Installation Improper Installation