Aegis ring main unit providing intelligent solutions Why Aegis? • Cost effective • Safe • Maintenance free • Simple operation • Easy to install • Climate independent • Automation ready To find out more about us, visit: www.lucyswitchgear.com Contents Introduction to Lucy Switchgear 4 Product panorama: Lucy medium voltage and high voltage range 5 Introduction to Aegis 6 Installation and operating conditions 7 Safety features 8 Application examples 9 Aegis range presentation 10 Available configuration 12 Standards 12 Product characteristics 13 13 General L: LBS Load Break Switch 14 Standard features Optional features, factory fitted Optional features also available as retrofit Circuit Breaker; T or V modules Product presentation User interface and interlocking mechanism 15 Standard features Optional features, factory fitted Optional features also available as retrofit Circuit breaker protection 16 TLF Protection relays Protection CT (Current transformers) for TLF and relays Options and accessories 19 Secondary injection Actuators (motorised) Cable compartment Shunt trip coils Earth Fault Indicators (EFI) Air metering unit 20 Switchgear automation 21 Cable bushings and cable terminations 22 Technical data sheet 23 Dimensions 24 Order form 26 Page 3 Introduction to Lucy Switchgear Lucy Switchgear is a global leader in switching, protection and automation solutions for electrical distribution systems, with over 100 years’ industry experience. Today the company is a specialist in secondary power distribution, engineering high-performance medium voltage switchgear for utility, industrial and commercial applications, overhead line equipment and providing retrofit and automation solutions to customers internationally. Engineering excellence, based on a long tradition of expertise, coupled with state of the art technology to meet customers’ stringent specifications, make Lucy Switchgear one of the few companies that can offer truly bespoke solutions. We have the capability to manufacture units for any location, climate or situation and offers a complete product portfolio, with a wide scope of services and dedicated after sales support throughout the product lifecycle. A specialist UK research and development facility, with a continuous programme of R&D, ensures that Lucy Switchgear’s products are always at the cutting edge, designed to anticipate the evolving technical and market demands of our customers. And our multi-million pound, purpose built, state of the art UK manufacturing facility provides complete control over production. Lucy Switchgear is a truly international company with offices in China, Dubai, Malaysia and South Africa; manufacturing facilities in the United Arab Emirates, Saudi Arabia and India; and an established global network of industrial partners and contractors operating in over 50 countries worldwide. Ring main unit range evolution Trident Scimitar Sabre Aegis 1965 Page 4 1970 1975 1980 1985 1990 1995 2000 2005 2010 2015 Product panorama: Lucy medium voltage and high voltage range Rated voltage (up to) Mode of fault current interruption Insulation medium Rated current (up to) Mounting Installation condition Operation Aegis 24kV Vacuum SF6 630A Ground / Transformer Indoor / Outdoor Local / Remote Sabre 24kV Vacuum SF6 630A Ground / Transformer Indoor / Outdoor Local / Remote Scimitar 17.5kV Fuse SF6 630A Ground / Transformer Indoor / Outdoor Local / Remote Trident 15.5kV Fuse Oil 630A Ground / Transformer Indoor / Outdoor Local / Remote Rapier DSB 145kV - Air 2500A Structure Outdoor Local / Remote Rapier GX 38V - SF6 630A Pole Outdoor Local / Remote Rapier AX 36kV - Air 800A Pole Outdoor Local / Remote Ring main units Switch disconnectors Page 5 Introduction to Aegis Aegis is a new generation of Ring Main Units mainly designed for secondary distribution networks up to 24kV. This range is available in indoor and outdoor formats to suit various application needs. All the live parts and switching functions are insulated with SF6 gas and sealed in a stainless steel tank ensuring a high level of reliability, personnel safety and virtually maintenance free operation. The structural tank welding is performed by a robotic welding process ensuring high reliability with a product life expectancy of more than 30 years. The housing is fully treated using zinc coated steel and electro statically applied, oven cured paint to resist degradation from pollution and harsh climatic conditions. The transformer protection is by Vacuum Circuit Breaker. On request, the units can be supplied with integrated automation for remote monitoring and control functions. Characteristics: • 12kV, 17.5kV and 24kV ratings • Extensible and non extensible range with up to 4 switching functions in a single tank • Hermetically sealed stainless steel tank insensitive to environment • Intuitive single line mimic diagram for simple and safe operation • Vacuum Circuit Breaker enclosed in an SF6 insulated tank for extra protection against corrosion and pollution • P rovision for motor actuators for remote operation and control • Integrated cable testing facility on front face eliminating the need for cable disconnection • E asy integration with SCADA network for remote operation and control • S tandard RAL7032 paint finish with other colours available on request • Suitable for indoor and outdoor applications • V arious protection options (TLF, relays) to suit customer needs • Low roof height designed for kiosks and mini substations Page 6 Installation and operating conditions IP54 IP41 Outdoor metal clad non extensible units only Indoor extensible and non extensible Temperature De-rating Curves i. Indoor and outdoor type units ii. A mbient temperature for operation without derating: 40°C (for higher temperature applications please refer to temperature derating curve below) 700 iii. Average value over 24 hours max: 40°C 650 v. Insulation medium: SF6 Gas vi. Rated pressure at +20°C: 0.03 MPa vii. Interruption medium: vacuum * F or higher altitude applications please contact local Lucy Switchgear sales office. Rated Current (Amps) iv. M aximum altitude for operation without derating: 1000m (above sea level)* 630A at 40°C 600 550 500 450 400 350 300 40 45 50 55 60 65 Ambient Temperature ° C Page 7 Safety features Operation mechanism Earth and test facility T he mechanism consists of one operating shaft and one selector. The operating shaft is used for switching ON / OFF (Mains or Earth) and the selector is used for selection of the Mains or Earth positions. It is impossible to simultaneously close the Load Break Switch or Circuit Breaker and the Earth switch. The cable earth and test facility is an optional feature on the Load Break Switch and the Circuit Breaker. It is located at the front of the unit for ease of access. It is used for testing cable insulation and to locate faults in the circuit without the need to remove the main cables from the cable compartment, which improves the operator safety. The mechanism incorporates mechanical interlocks and padlocking facilities to improve operator safety. The cable test access cover is fully interlocked and cannot be opened until the Load Break Switch or Circuit Breaker Switch is in Earth ON position. The test bushings are earthed with a star bar which has to be removed for cable tests. Anti reflex mechanism: Ensures a time delay between switching operations to allow sufficient time for the main breaker to trip and clear a fault. Internal Arc withstand Aegis SF6 Gas insulated stainless steel tanks are fully internal arc rated and this feature is also available on the cable compartment (optional) to ensure maximum operator safety in the event of internal faults. As standard, all the tanks are rated for AF (operator safety from the front of the unit) and there is an option to request for AFL (front and side) and AFLR (front, side and back of the unit). For more details on IAC ratings, please refer to the technical data sheet on page 20. Page 8 Cable compartment The cable compartments are located at the front of the units with horizontal mounted DIN 400 type C bushings for ease of cable connection. Vacuum Circuit Breaker function has factory mounted protection CT (current transformers) on the cable bushings for ease of installation and to avoid any potential damage to CT during transit and connections. F or enhanced operator safety, the cable compartments are earthed and fully interlocked allowing access to the operator only if the function is in Earth ON position. There is an option of supplying these cable compartments with Internal Arc rating as per IEC standards. Earth bar in cable compartment VPIS A fully rated copper earth bar is mounted inside the cable compartment. This earth bar is used to connect the screened cable connectors through M12 size bolts. The bar runs through the width of the unit and protrudes 125mm to the rear of the cable compartment or connection to the main earthing system. For additional safety it is not possible to remove it while unit is live. VPIS (Voltage Presence Indication System) is an optional feature in the Aegis range. It is used for checking the presence of voltages in the cables. The VPIS gets a voltage signal through the voltage divider built into the cable bushings. They can also be fitted with neon lights and momentary latching push buttons to show voltage presence without needing external testing probes.  Two types of voltage presence indication device are offered: • Pfisterer sockets • N eon indicators with push-to-test buttons and phase comparator sockets Pfisterer sockets Neon indicator with push-to-test buttons Application examples The key areas of application are: Energy i. Generation: wind power, solar power ii.Distribution: compact substations Infrastructure: tunnels, airports, ports, underground railway stations Commercial buildings: hospitals, shopping centres, hotels, office buildings, data centres Industries: water and waste water, mining, minerals, automotive, iron and steel, paper and pulp, cement and petroleum Page 9 Aegis range presentation The Aegis range is available in four configurations, ranging from 1 function to 4 functions, as shown below. Functions available: SW: Switching functions: L: LBS - 12kV : 630A - 17.5kV: 400A - 24kV: 400A CB: Circuit breaker functions: V: VCB T: VCB - - - - 12kV: 630A 12kV: 250A 17.5kV: 250A 24kV: 250A Metering functions: M1: Busbar metering - 17.5kV: 630A 1-function 4-functions Page 10 2-functions 3-functions Non extensible: (12kV, 17.5kV and 24kV) This range has 3 and 4 functions insulated by SF6 gas in a single hermetically sealed stainless steel tank. This solution is available in indoor (IP41) and outdoor (IP54) versions and is perfectly suitable for integration into compact substations to form standard ring main secondary networks with transformer protection. Extensible: (12kV only) The extensible range is used to add another function on the left, right or both sides of switchgear installed in secondary networks. This range has 1,2,3 and 4 functions insulated by SF6 gas in a single hermetically sealed stainless steel tank. It is an ideal solution if additional functions are needed in the present or foreseeable future. Available in indoor (IP41), these units can be easily extended in any combination on site without specific tooling or floor preparation, and without the need to transfer SF6 gas. The units are extended as shown in these diagrams: Busbar extension system Extension bushings Page 11 Available configuration Non extensible (compact range) Extensible range Positions of the functions in the unit Types of functions Positions of the functions in the unit 1st 2nd 3rd 4th 1st 2nd 3rd 4th L L L L L L L L T T T T V V V V Types of functions 3 functions unit 1 function unit 4 functions unit 2 functions unit T T T T V V V V 3 functions unit 4 functions unit All of the extensible units are available in the following extensibility functions: • Left hand • Right hand • Both sides Standards International Standards IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-103 IEC 62271-200 Page 12 Product characteristics General Product presentation 1 EFI 2 Pressure indicator 3 Marshalling Box 4 Optional VPIS 5 Earth and Test Facility 6 Protection Relay 7 'Push To Trip' Button 8 Circuit Breaker Indication 1 3 2 5 6 10 7 14 8 9 Interlocked Cable Box Cover 10 Disconnector Indication 11 Cable Test and Cable Box Interlock 12 Disconnector Operation Collar 13 Operation Collar 14 Switch Indication 15 Operating Handle 4 13 11 12 15 9 User interface and interlocking mechanism Safety interlocking Each LBS and VCB module has safety interlocked access via a rotary knob on the fascia to enable access to the cable connection compartment and also the cable test access panel (if specified as an option) located on the fascia. Operating handle access shafts have the facility for individual padlocks. Circuit Breaker Load Break Switch Position Load Break Switch ON OFF OFF Earth ON Interlock status Selector Main Main Earth Earth Cable compartment interlock Locked Locked Locked Unlocked Earth & Test interlock (if fitted) Locked Locked Locked Unlocked Position Interlock status Circuit Breaker Selector ON OFF (Tripped) OFF (Reset) Earth ON Earth ON OFF (Tripped) Main Main Earth Earth Earth Earth Cable compartment interlock Locked Locked Locked Unlocked Locked Locked Earth & Test interlock (if fitted) Locked Locked Locked Unlocked Locked Locked Page 13 Product characteristics Switching functions L: LBS load break switch Standard features Optional features, factory fitted • T hree positions (ON, OFF & Earth), spring loaded mechanism, independent manual operation • Internal arc rating of cable compartment for additional safety • S ingle mechanism with two independent operating shafts, one for switch ON / OFF position and another for selecting in Mains and Earth operation • VPIS – Voltage Presence Indication System • Interlocked selector, locked from operation when switch is in ON position • S ingle line intuitive mimic diagram with clear indication to show the status of switch (ON, OFF or Earth positions) • Remote low gas pressure alarm,1N/O (only one per tank) • Remote switch position indicator (1N/O,1N/C and 2N/O,2NC) • F ully interlocked cable earth and test (E&T) facility without removing main cable connections • Wiring for motorisation • H orizontal cable terminations in front with DIN400 type C bushings Optional features also available as retrofit • F ully interlocked cable compartment allowing entry only if function is in Earth ON position Page 14 • Short circuit and Earth Fault Current Indicators (EFI) • G as pressure indicator with Red and Green sectors to indicate minimum permissible pressure for safe operation (only one per tank) • P adlock facility (8.5mm diameter hole) for all the operating positions • M otor operation for Load Break Switch (only if unit is pre wired for motorisation) • W ide range of cable clamps, and glands to accommodate 1 and 3 core cables (refer to cable compartment section on page 17 for further information) Product characteristics Circuit breaker: T or V modules T module 250A and 400A rated vacuum circuit breakers for transformer protection. V module: 630A rated vacuum circuit breaker for transformer / downstream network protection. • Internal arc rating of cable compartment for additional safety • Remote low gas pressure alarm,1N/O (only one per tank) • VPIS – Voltage Presence Indication System • R emote circuit breaker position indicator (1N/O,1N/C and 2N/O,2NC) Standard features • T hree functions (ON, OFF & Earth), two position spring loaded mechanism, independent manual operation • S ingle mechanism with two independent operating shafts, one for circuit breaker ON/OFF position and another for selecting disconnector in Mains or Earth (isolation) • Interlocked disconnector selector, locked from operation when circuit breaker is in ON position Optional features, factory fitted • F ully interlocked cable test facility without the need to remove main cable connections (refer to cable test facility for further information) • Self-powered relay for protection (customer specific) • TLF (Time Limit Fuses) for alternative protection • Wide range of Current transformers for TLF and Relay protection • Shunt trip coils for external tripping • Wiring for motorisation • Mechanical push-to-trip button for local operation • Trip coil for receiving tripping signal from relay or TLF devices • Protection function TLF or relay (customer specific) Optional features also available as retrofit • S ingle line intuitive mimic diagram with clear indication to show the status of switch (ON, OFF or Earth positions) • M otor operation for CB (only if unit is pre wired for motorisation) • G as pressure indicator with Red and Green sectors to indicate minimum permissible pressure for safe operation (only one per tank) • W ide range of cable clamps, and glands to accommodate 1 and 3 core cables (refer to cable compartment section on page 17 for further information) • H orizontal cable terminations at front of unit with DIN 400 C type bushings • P rotection CT (current transformers) mounted on cable bushings (customer specific) • F ully interlocked cable compartment allowing entry only if function is in Earth ON position • P adlock facility (8.5mm diameter hole) for all the operating positions Page 15 Product characteristics Circuit breaker protection Two types of protection devices are offered to protect the circuit breaker; TLF : Time limit fuses Protection relays TLF When utilised in conjunction with circuit breaker type ring main units, time limit fuses (TLF) are a cost effective method of providing fault protection for overcurrent and earth faults (optional) to a transformer of 2000kVA or less. It is a recognised method of protection and was developed to comply with EA 41-26 (now superseded by ENA TS 41-36) with fuse links in accordance with ENA TS 12-6. It should be noted that the TLF protection system is not a device for limiting overload levels of individual transformers. It should be used for fault protection only. T he TLF system provides protection for overcurrent and earth faults between the MV circuit breaker and the LV protection device. The selected TLF rating should be such that it allows for discrimination between the MV & LV devices. This will ensure that the circuit breaker does not open for faults beyond the LV distributorprotection device. hen fitted with TLF, the ring main unit can also be configured W to enable tripping of the circuit breaker from remote devices (Bukholtz, LV CB etc). Fuse dimensions: Length 57mm x Diameter 13mm Lucy Switchgear customers in Europe, the Middle East, Africa and Asia are currently using TLF protection system within their distribution networks. RMU TLF Transformer LV distribution Panel Page 16 Recommended TLF settings Transformer ratings (kVA) 200 315 500 Rated voltage (kV) CT ratio 50/5 Earth fault setting = 25A (instantaneous trip) CT ratio 100/5 Earth fault setting = 30A (instantaneous trip) 800 1000 1250 1600 3.3 10A 6.6 5A 10A 15A 11 3A 5A 10A 15A 13.8 3A 5A 10A 15A 3A 5A 7.5A 5A 10A 15A 5A 7.5A 12.5A 15A 11 5A 7.5A 10A 12.5A 15A 13.8 5A 7.5A 10A 12.5A 15A 5A 5A 24 3.3 2000 TLF fuse rating (A) 6.6 24 7.5A Advantage of vacuum circuit breaker with TLF over HV fuses Feature VCB with TLF Overall cost of units Fuse switch Similar Approximate fuse replacement cost $5 $50 2MVA* 1MVA Maximum rated normal current 630A 200A Physical size of fuses Small Large No Yes LV side HV side Very small with multi ratio CT Large Maximum rating of transformer, can be protected Possibility of some pollution while changing fuses causing PD and flash over issues Fuse location inside the unit Range of fuses required for different rated transformers *No issues with transfer current switching to IEC 62271-105, which minimizes the MVA rating Advantage of vacuum circuit breaker with TLF over protection relays Feature Installation cost of function Auxiliary power source for operation Delay in activation of trip function due to capacitor charging time lag VCB with TLF Protection relay Low High Not required As required Not delay Delay Employee training on setting tripping curves Not required Required Additional training on different manufacturer setting up procedure Not required Required Maintenance and repair cost Low High Operating temperature limitations None Up to 70 °C Range of fuses required for different rated transformers Yes Yes Over current and earth fault protection Yes Yes Page 17 Product characteristics Circuit breaker protection Protection relays Manufacturer The Aegis range can be fitted with self-powered relays for protecting the transformer or downstream network from fault currents by tripping the Circuit Breaker. These relays incorporate many advanced features and have a variety of settings to provide discrimination protection in networks. The self-powered feature eliminates reliance on external power sources and increases the performance and reliability of the protection function. Range Earth overcurrent • To the right are the technical characteristics of the Woodward WIP1 relay, offered as a standard on the Aegis range (if ordered with relay function). Other manufacturers’ relays can also be incorporated into the units on request. Number of earth overcurrent elements 2 Woodward WIP1 Functions Phase overcurrent • Short circuit protection • Number of overcurrent elements 2 Characteristics Display (measuring values and parameters) • Setting via buttons • Standard CT 1A LED pickup • LED trip indicator • Flag indication output • Fault memory • Clock • Password protection • Electro impulse and relay contact output • Number of output relays Protection CT (current transformers) for TLF and relays The protection CT are used in conjunction with Relays or TLF protection to protect a wide (kVA) range of distribution transformers. A comprehensive range of CT (current transformers) is available to suit varied application requirements. Dual Ratio CT 100/50/- Dual Ratio CT 200:100/- Triple Ratio CT 150:100:50/- An extensive range of additional CT’s are available on request, please contact our local sales office for more information. Page 18 3 C/O Input remote tripping • Interface O RS 485 interface with pro open data protocol O RS-485 interface with Modbus protocol O Additional power supply O Key • Standard O Option Other manufacturers’ relays are also available on request, please contact our local sales office for more information. Product characteristics Options and accessories Secondary injection Shunt trip coils S econdary injection is used to test the relays or TLF operation without switching on the high voltage supply to the unit. A low voltage is applied to the secondary side of the CT connection (located in terminal box) to test the operation of the protection devices at the time of commissioning and routine tests. Shunt trips are magnetic coils and are used to trip circuit breakers through local push buttons, RTUs or additional transformer protection devices. Shunt trips are available in the following voltages; Actuators (motorised) Aegis units are fitted with 24V DC motors, which can be powered from the Gemini remote terminal unit (RTU) 24V DC battery in the event of mains AC supply failure. • DC voltage: 12V, 24V, 48V and 110V Cable compartment Earth fault indicators (EFI) are used for rapid location and isolation of faults on medium voltage networks in open loop ring main networks. When the unit detects asymmetrical currents greater than 50A in the 3 phase cable an earth fault is indicated by means of a flashing LED or mechanical flag. • AC voltages: 110V, 240V • Multiple voltage range: 24VDC – 240VAC Earthfault indicators (EFI) ll the cable clamps, glands and cable A compartment sealing devices are available as retrofit options. Below is the list of clamps available in metal (steel) and plastics. • Single 3 core cable Below is the list of EFIs available for the Aegis range. • 3 single core cables An extensive range of additional cable compartment clamps and sealing devices are available on request, please contact our local sales office for more information. Single 3 core cable Manufacturer model: 3 single core cable Suparule Sensorform BLZ-50 BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 Features Power source 3.6V lithium ½ AA 850mAH battery 110-240V a.c. Voltage range CT on current carrying phase 1 – 38kV Trip current 50A Primary indication LED Flashing duration >1000 hrs Mech-flag (RED) - - Minimum fault duration LED Mech-flag (RED) LED 10 hrs - 10 hrs 2.5 cycles Manual reset Push button Automatic timer reset 4 or 8 hrs selectable 10 secs after mains restore Manual trip test Push button Operating temperature -40°C to +80°C Operating humidity 0-100% RH Ingress protection IP65 Current sensor diameter: CT100: 100mm • • • • • • CT150: 150mm O O O O O O CT300: 300mm O O O O O O Remote flashing LED indicator O O O O O O Auxiliary relay, 1N/O latching O O O O O O Key • Standard O Option Other manufacturers’ EFIs are also available on request, please contact our local sales office for more information. Page 19 Air metering unit AMU features • Busbar metering with extensibility on both sides • 17.5kV and 630A rating • Rated lighting impulse voltage (BIL) 95kV • Power frequency voltage 38kV • IP41 for indoor installation • DIN 400 type C bushings for busbar connection • 20kA/1sec IAC rating • Ambient operation temperature -25 ˚C to 40 ˚C • HV fuse protection for VT • Anti-condensation space heater (option) • Wide range of CT and VT AMU low voltage compartment • Facility to lock and seal the terminal (marshaling) box • Provision to disconnect and short circuit the CTs • DIN96 size KWH meter, ammeter and voltmeters • MCB/fuse protection for VT secondary side Air metering unit Page 20 Busbar metering Switchgear automation The Gemini RTU is an advanced, highly flexible and ultra-efficient solution for remote operation and control of electrical distribution networks. Enclosed in a stainless steel casing for maximum protection, the Gemini RTU is designed to operate in the most demanding environments. The key features of the Gemini range are: • Embedded auto change over and auto sectionalising functions • C ontrol and monitoring of up to 4 motorised functions (switches or circuit breakers) • Inbuilt earth and fault passage indicators • A dvanced monitoring of current, voltage, battery condition, temperature compensation, switchingstatus, automatic cooling system, gas pressure etc • F lexible communication through radio, RS232, RS485, packet data network, GSM, GPRS, PSTN, Bluetooth, ethernet TCP/IP, optical fibre and SMS messaging In addition to the features opposite, remotely monitored and controlled switchgear provides significant benefits to customers such as: • R educed time in diagnosing system anomalies as well as locating and isolating faulty sections of network • Faster response time and quick network reconfiguration • O ptimisation of asset management through the implementation of customised automation schemes • Advanced battery back to operate under mains AC input failure • R educed operational cost associated with routine network switching • F ully tested to ENATS (Energy Network Association Technical Standards), EMC and environmental standards • Increased operator safety Gemini RTU specification Enclosure General Degree of protection Operating temperature Relative humidity Method of mounting Dimensions Processor module RTU hardware Power supply Battery type Battery charger Control electronics Inner enclosure Ventilation Digital inputs Inputs / outputs Digital outputs Analogue inputs Expansion I/O module Communication interfaces Communications Protocols Communication media Switchgear interface Controls Indications Software Cables Configuration Stainless steel IP54 -25 to 60°C Up to 95% Floor, wall, pole or RMU switchgear H 600mm, W 400mm, D 210mm ARM9 microprocessor 110 / 230V AC supply – over and under-voltage protection 2 x 12V DC, sealed lead acid or high temperature NiMH Temperature compensated, fully protected PIC based processor with expandable I2C bus Stainless steel Microprocessor controlled, long life fan with baffle air intake filter 14 isolated digital inputs – expandable 8 isolated digital outputs – expandable 3 CT analogue inputs as standard (DIs reduced to 11) 3 AIs / 4 DIs; 7 DIs / 2 DOs 3 RS-232 for control (ethernet option), configuration and programming plus one expansion bus DNP3, IEC 60870-5-101/104 and modbus (others on request) RS-232 / 485, UHF / VHF radio, packet data, GSM / GPRS / EDGE, PTSN, leased or twisted pair lines, optical fibre, ethernet (TCP/IP) and Bluetooth Membrane push-button for open / close operations in conjunction with activate push-button up to four switching functions (standard 1, 2, 3 or 4 switch control formats) Selector control for off, local or remote modes RTU services such as DC / AC supplies, dummy control and debug LEDs Switch status LEDs for open / closed positions Control Output LEDs (illuminates when active) Configurable LED indications Plug-in, multi-core umbilicals to switchgear Windows-based software • Protocol parameters including device and I/O addresses for configuration of: • Parameters for the communications device • Parameters for digital, analogue and counter points • Automation sequences • Power saving routines • Battery tests Page 21 Cable bushings and cable terminations The bushings for each ring switch and circuit breakers are located at the front of the unit. All sets of bushings are type ‘C’ with in-line bolted connections M16 threaded in accordance with EN50181. The bushings are accessible by removing the interlocked cable compartment covers at the front of the unit. The maximum cable size that can be used is: • 300mm² 3 - core • 500mm² single - core. The following types of terminations can be used with the Aegis: Insulating bushing boot Heat shrink insulating bushing boot Profile 'C' bolted separable Page 22 Technical data sheet Circuit breaker V and T function General Rated voltage kV 12 17.5 24 Rated normal current Rated frequency Hz 50 60 50 V function A 630 - - T function A 250 250 400 400 Rated lightning impulse withstand voltage Directly earthed kV 95 95 125 Rated active load breaking current A 630 250 Across disconnector kV 110 110 145 Rated short circuit breaking current kA 20 21 20 Rated short circuit making current kA 50 54.6 50 A 25 31.5 31.5 Rated power frequency withstand voltage Directly earthed kV 38 38 50 Rated cable charging breaking current Across disconnector kV 45 45 60 Rated short time withstand current Protection Main electrical circuit Tank with HV parts IP IP67 1 sec kA - 21 - LV control box IP IP41 3 sec kA 20 - 20 Front face + mechanism IP IP41 Earthing circuit Cable box IP IP41 1 sec kA - 21 - Mechanical impact protection IK IK07 3 sec kA 20 - 20 Freestanding kA 1 sec 21kA 1 Sec Circuit breaker M1/2000 Optional cable box kA 1 sec 21kA 1 Sec Earth switch M0/1000 Internal arc rating Mechanical endurance class AF (gas chamber) Standard Electrical endurance class AFL (gas chamber) Optional Circuit breaker AFLR (gas chamber) Optional Earth switch SF6 gas Bar (G) 0.4 0.4 0.5 Tripping time Across disconnector Bar (G) 0 0 0.3 Operating sequence for mechanism Annual leakage rate ≤0.01% per annum≥ Installation conditions ms >80 °C Maximum altitude (without derating)* M 40 55 >80 >80 0-3min-CO-3min-CO Local: close / open Hand lever / pushbutton Remote: close / open Ambient air temperature (without derating) Motor / coil 55 1000 Relative humidity (max) - over period of 24hrs (IEC 62271-1, sub-clause 2.1) Load break switch: L function 95% * For higher altitude applications please contact local Lucy Switchgear sales office. BusBars Rated normal current A 630 400 400 Rated active load breaking current A 630 400 400 Rated short circuit making current kA 50 54.6 50 Rated cable charging breaking current A 10 10 16 Rated short time withstand current A 630 400 400 kA - 21 - Rated short time withstand current 1 sec E1 Operating mechanism Filled pressure Rated normal current E2/2000 Main electrical circuit 1 sec kA - 21 - 3 sec kA 20 - 20 3 sec kA 20 - 20 Earthing circuit Rated peak withstand current kA 50 54.6 50 1 sec kA - 21 - 3 sec kA 20 - 20 Mechanical endurance class Load break switch M2/5000 M2/5000 M2/5000 Earth switch M0/1000 M0/1000 M0/1000 Electrical endurance class short circuit making Load break switch E3/5 E1/2 E1/2 Earth switch E3/5 E1/2 E1/2 Operating mechanism Local: close / open Remote: close / open Hand Lever Motor Page 23 Dimensions Aegis ring main unit 500mm 1-function 840mm 2-functions 1235mm 3-functions 886mm B A 1650mm 50mm 4-functions Cable Termination Height (Distance between cable clamp and bushings) Dim A Dim B 450 1095 575 600 1245 727 800 1455 940 1: L function height is not affected with addition of E&T facility 2: For V & T functions with E&T facility add 150mm to overall height “A”of the unit Page 24 Dimensions Air metering unit 967mm 1244mm 617mm Page 25 Aegis order form To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office (addresses can be found on the back cover) Name: Company: Address: Tel no: Fax no: Email: Order number: Order quantity / number of units (please fill separate form for each type) Extensibility (choose any one) Non extensible Extensible left hand right hand both sides IP rating: Installation conditions (choose any one) IP54 Metal clad outdoor (available for non extensible range only) IP41 Indoor (available for extensible and non extensible range) Colour RA L7032 as standard (other colours are only available on request) Features common to all functions Voltage rating (choose any one)12KV 17.5kV 24kV Low gas pressure alarm 1N/O (tick if needed, only one per tank) Number of ways and functions needed at each position: Starting from the left, write any one of L, V or T in each box depending upon the number of ways needed. First SecondThirdFourth (e.g. 1 function) (e.g. 2 function) (e.g. 3 function) (e.g. 4 function) Voltage range Functions current ratings 12kV 17.5kV 24kV L 630A 400A 400A T 250A 250A 400A V 630A - - For example: Motor wiring (tick for each selected function, if needed) Motor for remote operation (tick for each selected function, if needed) Cable Earth & Test facility (E&T) (tick for each selected function, if needed) Cable bushings termination height (choose any one) 450 600 810 Cable box: Internal arc proof VPIS (choose any one) Neon indicator with push to test button Pfisterer socket Auxiliary switches (choose any one) 1N/O, 1N/C 2N/O, 2N/C Cable compartment Cable clamp material (choose any one) Metal Plastic Cable entry type (choose any one) 3 single core cable Single 3 core cable Page 26 L V T L Optional features applicable to L (Load Break Switch) function only Rated current (choose any one) 400 Amps (available for 17.5 and 24kV) 630 Amps (only available for 12kV) EFI (choose any one)BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 BLZ-50 Any other* Optional features applicable to V or T (Vacuum Circuit Breaker) function only Secondary injection (tick for each selected function, if needed) Protection device (choose any one) TLF (Time Limit Fuses) WIP1 Other* Protection (CT) current transformer for TLF or Relay (choose any one) Dual (Primary) Ratio CT 100:50/- Dual (Primary) Ratio CT 200:100/- Triple (Primary) Ratio CT 150:100:50/- Manual Push To Trip button (tick for each selected function, if needed) Shunt Trips (choose any one) 12V DC 24V DC 48V DC 110V DC 110V AC 240V AC Multiple voltage (24V DC - 240VDC) Note: The ring main units gas chamber are supplied with AFL (Front and sideways) rating. If you require units with AFLR (Front, side and rear) ratings please contact our local sales office. *Please fill the details in comment section below. Comments Page 27 Disclaimer Lucy Switchgear has a policy of continuous research and development and accordingly reserves the right to change the design and specification of its products without prior notice. Lucy Switchgear worldwide offices Lucy Middle East FZE PO Box 17335, Jebel Ali, Dubai, United Arab Emirates Tel: +97 148 129 999 Fax: +97 148 129 900 Email:salesme@lucyswitchgear.com Lucy Switchgear Ltd. Howland Road, Thame, Oxfordshire, OX9 3UJ, United Kingdom Tel: +44 1844 267 267 General Tel: +44 1844 267 222 Sales Fax: +44 1844 267 223 Email:salesuk@lucyswitchgear.com Lucy Switchgear Arabia Co. Ltd. Novotel Business Centre, P.O. Box 35340, Dammam 31488, Saudi Arabia Tel: +966 3 8147 910 Fax: +966 3 8147 914 Email:salessa@lucyswitchgear.com Lucy Asia Pacific Sdn Bhd L13A-03-03A, PJX-HM Shah Tower, No16A Jalan Persiaran Barat, 46050 Petaling Jaya, Selangor, Malaysia Tel: +603 74910700 Fax: +603 79316923 Email:salesmy@lucyswitchgear.com Lucy Switchgear (South Africa) Unit 2, Cranberry Industrial Park, Cranberry Street Laser Park, Honeydew, 2170, South Africa Tel: +27 11 025 7490 Fax: +27 11 794 3277 Email:salesza@lucyswitchgear.com Lucy Electric (Beijing) Co. Ltd. 卢西电器(北京)有限公司 北京市朝阳区东三环北路霞光里 18号佳程广场A座1122室 邮编:100027 电话:+86 1059 231 176 传真:+86 1059 231 177 电子邮件: salescn@lucyswitchgear.com Postal Address: P.O. Box 1078, Honeydew, 2040 To find out more about us, visit: www.lucyswitchgear.com LSAEG0114