Specifications

advertisement
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16050
ELECTRICAL GENERAL
PART 1 - GENERAL
1.01
SUMMARY
A.
Description:
1.
2.
3.
B.
Related Documents:
1.
2.
3.
1.02
Provide all materials, tools, and labor for a complete electrical
installation as shown on the contract documents and indicated in
the specifications.
Procure all permits and licenses.
Coordinate the electrical installation with the following:
a.
Owner, State Architect, Engineer of Record
b.
Contractors of other trades.
c.
Local Electrical and Building Inspectors, or the authority
having jurisdiction.
Electrical, "E", drawings.
All working drawings included in the contract documents.
Specifications of the following divisions/sections:
a.
Division 0 - Conditions of the Contract
b.
Division 1 - General Requirements
ABBREVIATIONS
A.
The following abbreviations are used throughout Division 16
specifications:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
AFF:
ANSI:
ASTM:
HVAC:
IEEE:
IES:
ITL:
NEC:
NECA:
NEMA:
Above Finished Floor
American National Standards Institute
American Society for Testing and Materials
Heating, Ventilating and Air Conditioning
Institute of Electrical and Electronic Engineers
Illuminating Engineering Society
Independent Testing Laboratories
National Electrical Code
National Electrical Contractor Association
National Electrical Manufacturers Association
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
11.
12.
13.
1.03
"Provide" means to furnish and install.
CODES AND STANDARDS
A.
Comply with the following codes and published standards which are
applicable to the electrical installation of this project:
1.
2.
3.
4.
5.
6.
7.
1.05
National Fire Protection Association
Not in Contract
Underwriters Laboratories, Inc.
DEFINITIONS
A.
1.04
NFPA:
NIC:
UL:
University of Georgia
RCE 2013029
NFPA 70 - National Electrical Code, 2011 edition
NFPA 101 - Life Safety Code, latest edition
International Building Code with Georgia Amendments
Underwriters Laboratories Electrical Construction Directory (green
book)
Underwriters Laboratories Electrical General Information (white
book)
NFPA 72
International Commercial Energy Code with Georgia Amendments
STANDARDS FOR MATERIALS AND WORKMANSHIP
A.
Use materials that are new and, where UL or ITL has established
standards, listed and/or labeled.
B.
Organize and execute work so that finished appearance is neat;
mechanical, plumb when vertical and level when horizontal.
PART 2 - PRODUCTS
2.01
MATERIALS
A.
Provide equipment, products and materials shown on the drawings, as
specified in the specifications or added by addendum.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.02
University of Georgia
RCE 2013029
PLYWOOD BACKBOARDS
A.
3/4"x size indicated on the drawings, A/D grade, paint two coats gray
enamel
PART 3 - EXECUTION
3.01
VISIT TO SITE
A.
3.02
3.03
PROTECTION OF MATERIALS
A.
Cover fixtures, equipment and apparatus for protection against dirt, water,
chemical or mechanical damage before and during construction.
B.
Keep all conduit and other openings protected against entry of foreign
matter.
C.
Restore the original finish, including shop coat, of fixtures, apparatus or
equipment that has been damaged prior to substantial completion.
COORDINATION
A.
3.04
Prior to submitting bid, visit site and become familiar with the existing
conditions relating to Division 16 work.
Prior to rough-in of any materials, coordinate with subcontractors the
physical clearances for and sequencing of Division 16 work as it interfaces
with and relates to architectural, structural, plumbing, HVAC, and pool
systems.
SHOP DRAWINGS AND PRODUCT DATA SUBMITTALS
A.
Submit shop drawings and/or product data for the electrical equipment
and materials listed below. Check for compliance with contract
documents and certify compliance by affixing Electrical Contractor's
"Approved" stamp and signature.
1.
2.
Shop drawings and product data:
a.
Dimmer System
b.
Life Safety System
Product data only:
a.
Conduits, Couplings, Connectors, and Fittings
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
b.
c.
d.
e.
f.
g.
3.05
Wiring Devices and Coverplates (receptacles, switches)
Fuses and Circuit Breakers
Junction Boxes, Outlet Boxes, and Floor Boxes
Lighting Fixtures and Lamps
Disconnect Switches, Motor Starters, and Motor Switches
Wire and Cable
B.
Refer to respective sections for submittal instructions where instructions
have been prescribed.
C.
Obtain shop drawing review by engineer before purchase of any
equipment requiring shop drawing submittals.
CERTIFICATION AND TEST REPORTS
A.
3.06
University of Georgia
RCE 2013029
Submit the following certifications and test reports to the Architect:
1.
Certifications:
a.
Life Safety System
MAINTENANCE MANUALS AND OPERATING INSTRUCTIONS
A.
Submit the following maintenance manuals and operating instructions to
the Architect:
1.
Life Safety System
2.
Dimmer System
B.
Use a separate three ring binder for each maintenance manual and
include wiring diagrams, maintenance instructions, parts list, maintenance
tools list, manufacturer's and nearest dealer's name, addresses and
telephone numbers. Organize into sections with index thumb-tab
markers.
C.
Use a three ring binder for operating instructions with a separate
thumb-tab in each section for each system or major item. Include in the
instructions start-up, operation sequence, control, shut-down, safety
features and seasonal adjustments.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.07
OPERATIONAL TEST
A.
3.08
3.09
At the time of the substantial completion job observation, perform a test of
all light fixtures, electrical systems, equipment, machinery and appliances,
in the presence of the Architect or his representative, which demonstrates
that all of Division 16 systems are operational.
JOB OBSERVATION ASSISTANCE
A.
During all job observations, provide an electrician with tools and
volt/ammeter to accompany Architect and/or his representative.
B.
Remove any covers, trims or wiring devices and open all cabinets,
disconnect switches or other equipment served electrically and designated
by the Architect or his representative.
C.
Restore removed or opened equipment to its installed or closed position
after the job observation.
OWNER INSTRUCTION AND ASSISTANCE
A.
3.10
University of Georgia
RCE 2013029
At substantial job completion job observation, instruct the Owner's
operating personnel in the operation, sequencing, maintenance and
safety/emergency provisions of the electrical systems.
AS-BUILT DRAWINGS
A.
Record on one set of electrical drawings all changes, deviations and
underground conduits. Transfer that information to a reproducible
drawing and deliver the drawing to the Architect.
END OF SECTION 16050
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
Electrical_16SECTION 16110
RACEWAYS
PART 1 - GENERAL
1.01
SUMMARY
A.
Description:
1.
B.
Related Sections:
1.
1.02
Provide continuous conduit systems - beginning at the service
point, to all distribution equipment and to every outlet and piece of
electrical equipment with conduits, couplers, supports, hangers,
fittings, bushings and accessories.
Section 16050 - Electrical General.
SUBMITTALS
A.
Manufacturers Product Data Sheets.
PART 2 - PRODUCTS
2.01
RIGID STEEL AND INTERMEDIATE METALLIC CONDUIT
A.
Conduit:
1.
2.
Rigid ferrous steel pipe, hot-dipped galvanized or sherardized with
smooth interior.
Acceptable Manufacturers:
a.
Allied
b.
Triangle
c.
Wheatland
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
University of Georgia
RCE 2013029
Couplings and Connectors:
1.
Couplings:
a.
Hot-dipped galvanized or sherardized ferrous steel,
2.
Connectors:
a.
Steel or malleable iron, threaded with throat bushing, lock
nuts and, where prescribed, grounding lugs.
Erickson:
a.
Malleable iron, concrete tight.
Acceptable Manufacturers:
a.
Appleton
b.
Crouse Hinds
c.
Steel City
d.
Thomas & Betts
threaded.
3.
4.
C:
Joint Compound:
1.
2.
D.
Anti-seize lubricant with rust and corrosion inhibitors and colloidal
copper.
Acceptable Manufacturers:
a.
Thomas & Betts
Expansion Fittings:
1.
2.
Steel with three cap nuts, phenolic bushing, packing ring, metallic
copper grounding ring and copper bonding jumper.
Acceptable Products:
a.
Crouse Hinds "XJ"
b.
O.Z. Gedney "AX" or "DX"
c.
Appleton "XJ"
2.02 ELECTRICAL METALLIC TUBING
A.
Conduit:
1.
2.
Thin wall ferrous steel tubing, hot-dipped galvanized, smooth
interior, square and reamed ends.
Acceptable Manufacturers:
a.
Allied
b.
Wheatland
c.
Triangle
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Couplings and Connectors:
1.
2.
C.
Couplings:
a.
Steel, compression type, installed where exposed to
moisture.
b.
Steel, setscrew type, when installed indoors.
Connectors:
a.
Steel, compression type with nylon insulated bushings,
locknuts, and where prescribed, grounding lugs, installed
where exposed to moisture.
b.
Steel, setscrew type with nylon insulated bushings, locknuts,
and where prescribed, grounding lugs, installed indoors.
Expansion Fittings:
1.
2.
2.03
University of Georgia
RCE 2013029
Steel with three cap nuts, phenolic bushing, packing ring, metallic
copper grounding ring and copper bonding jumper.
Acceptable Products:
a.
Crouse Hinds "XJ"
b.
O.Z. Gedney "AX" or "DX"
c.
Appleton "XJ"
LIQUIDTIGHT FLEXIBLE CONDUIT
A.
Conduit:
1.
2.
Galvanized steel single strip, interlocked, smooth inside and out,
with liquid-tight flexible polyvinyl chloride outer jacket.
Acceptable Manufacturers:
a.
Carlon
b.
Wheatland
c.
Allied
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Fittings:
1.
2.
2.04
Threaded corrosion-resistant steel or malleable iron with insulated
throat bushing, liquid tight, locknuts and external ground lugs.
Acceptable Manufacturers:
a.
Appleton
b.
O.Z. Gedney
c.
Thomas & Betts
FLEXIBLE METAL CONDUIT
A.
Conduit:
1.
2.
B.
Galvanized steel single strip, interlocked, smooth inside and out.
Acceptable Manufacturers:
a.
AFC
b.
Alflex
c.
General Cable
Fittings:
1.
2.
2.06
University of Georgia
RCE 2013029
Threaded corrosion-resistant steel or malleable iron with insulated
throat bushing and lock nuts.
Acceptable Manufacturers:
a.
Appleton
b.
O.Z. Gedney
c.
Thomas & Betts
SEALS
A.
Fire Rated Seals:
1.
Flanged three-hour fire and smoke stop.
2.
Acceptable Products:
a.
O.Z. Gedney "CFSF"
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
University of Georgia
RCE 2013029
Thruwall Seals:
1.
Malleable iron, hot-dipped galvanized sleeve and sealing ring with
pressure rings and sealing grommets.
2.
Acceptable Products:
a.
O.Z. Gedney "FSK" and "WSK"
b.
Spring City "WEP" or "WDP"
c.
Thunderline Link Seal
PART 3 - EXECUTION
3.01
3.02
APPLICATIONS
A.
Provide Rigid Metal Conduit or Intermediate Metallic Conduit for feeders,
areas where exposed to moisture, exposed on exterior surfaces, and
exposed interior from floor to 10'-0" or where exposed to physical abuse.
B.
Provide Electrical Metallic Tubing (EMT) for interior power circuits, branch
circuits and system circuits in walls, elevated concrete slabs (those not on
grade), plenums, attics or exposed above 10'-0", where not exposed to
moisture.
C.
Provide Flexible Metal Conduit for:
1.
Final connection link (minimum of 12", maximum of 36") to:
a.
Motors.
b.
Transformers.
c.
Mechanical equipment.
2.
Connections between junction boxes and accessible recessed
lighting fixtures.
D.
Non-metallic Conduit is Not Used On This Project.
E.
Provide Liquid-tight Flexible Metal Conduit for final connecting link
(minimum of 12", maximum of 36") to the following:
1.
Equipment connection in damp locations
CONDUIT SUPPORT
A.
Intervals: Maximum 10 feet on center and within 3 feet of each outlet box,
junction box, cabinet or fitting.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
University of Georgia
RCE 2013029
Conduits 3/4" and smaller:
1.
2.
Method
a.
When single conduit: Attach directly to building structure or
suspend with 1/4" rod.
b.
When multiple parallel and adjacent conduits and:
1)
When horizontal at structure: Attach directly to
structure or to support framing attached to structure.
2)
When horizontally suspended: Attach to support
framing, suspended from building structure.
3)
When vertical: Attach to support framing attached to
building structure, wall structure or suspended from
building structure.
Conduit attachment:
a.
When direct to structure or single conduit suspended: Spring
steel friction, spring steel latching or clamped with bolts or
screws.
b.
When on support framing: Two section bolted conduit
clamp.
3.
4.
5.
C.
Structural steel attachment:
a.
When single conduit: Spring steel friction, clamp with bolt or
bolted.
b.
When hanger rod: Clamp with bolt or bolted.
Concrete attachment: Steel preformed conduit clamp. Attach
clamp with expansion anchor installed in drilled hole or with power
fastening anchor designed to meet concrete specification. In either
case, maintain design support of 300% or greater of load.
Wood attachment: Wood screws or bolted with design support of
300% or greater of load.
For 1" or larger:
1.
Method:
a.
When single conduit: Attach directly to building structure or
suspend with threaded rod.
b.
When multiple parallel and adjacent conduits: Attach to
support framing attached to building structure, wall structure
or suspended from building structure.
2.
Conduit attachment:
a.
When single conduit: Bolted clamp.
b.
When on support framing: Two section bolted conduit
clamp.
3.
Structural steel attachment: Beam clamps with bolts or bolted
directly to steel.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4.
5.
D.
3.03
University of Georgia
RCE 2013029
Concrete attachment: Provide preset insert prior to concrete pour
or coordinate drill locations with Architect. When drilling provide
expansion anchors. In either case, maintain design support of
300% or greater of load.
Wood attachment: Wood screws or bolted with design support of
300% or greater of load.
Framing:
1.
Attachment, suspension and bearing members capable of
supporting 300% of load.
INSTALLATION
A.
For conduit layout follow, generally, the diagrammatic layout shown on
plans. Provide offsets and routing changes to avoid structural,
architectural or equipment elements.
B.
Provide 1/2" minimum size conduit.
C.
Conceal all conduit except where shown to be exposed. Install conduit
concealed above a lay-in ceiling with clearance to allow easy removal of
ceiling panels.
D.
Install exposed conduit parallel with or perpendicular to building walls at
greatest height possible. Paint exposed conduit two coats of color
directed by Architect.
E.
Extend homeruns from outlets shown to panel designated. Do not
combine homeruns.
F.
Use benders designed for the size and type of conduit. Limit each bend
to 90 degrees or less with a radius 10 times conduit diameter or greater
for telephone system and 6 times conduit diameter or greater for all other
systems.
G.
Provide insulated bushings at each end of every conduit run.
H.
Provide joint compound on rigid steel conduit and intermediate metallic
conduit joints.
I.
Provide an Erickson type coupling where two segments of a conduit run
must be joined and neither can be rotated.
J.
Close all conduit ends during construction with plastic conduit plugs.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
K.
Install conduit no greater than 1" trade size in concrete slabs. Route
conduit between top and bottom reinforcing steel and space parallel runs
a minimum of 3" apart.
L.
Install conduit above water and steam piping where possible.
M.
Maintain grounding of metallic raceways with clean and tight connections.
Provide grounding conductor in all conduit.
N.
Provide ground lugs on all conduit connectors to service equipment
enclosures.
O.
Provide grounding wedge lugs or locknuts designed to bite metal on
conduit connectors to panel cabinet pull boxes.
P.
Seal all conduits which extend from the interior to the exterior of the
building to prevent the circulation of air.
Q.
Provide a thruwall waterproof seal on each conduit that penetrates a wall
at a below grade level.
R.
Provide an expansion fitting in each conduit crossing a building expansion
joint and locate the fitting at the joint. Also provide expansion fittings in
building conduits exceeding 100 feet at intervals of 100 feet.
S.
Provide a fire rated seal on each conduit that penetrates any floor or fire
rated partition. Match seal rating to floor or partition rating.
T.
Where liquids are present, form drip loops in liquid-tight flexible conduit to
prevent liquid from running into connections.
U.
Blow out and swab all conduit clear of trash and water prior to pulling wire.
V.
Provide a nylon pullcord in all empty conduits.
END OF SECTION OF 16110
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16120
CONDUCTORS
PART 1 - GENERAL
1.01
SUMMARY
A.
Description:
1.
B.
Related Sections:
1.
1.02
Provide continuous color coded conductors beginning at the
distribution equipment, to each outlet and each piece of electrical
energy consuming equipment.
Section 16050 - Electrical General
SUBMITTALS
A.
Manufacturers Product Data Sheets.
PART 2 - PRODUCTS
2.01
CONDUCTORS
A.
Copper Conductors:
1.
2.
Soft drawn annealed copper, 98 % conductivity, without weld,
splice or joint throughout its length; uniform in cross section without
flaws, scales, or other imperfections with THHN/THWN or XHHW
insulation.
Acceptable Manufacturers:
a.
Anaconda
b.
Phelps Dodge
c.
Pirelli Cable
d.
Rome
e.
Southwire
f.
Triangle
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Aluminum Conductors:
1.
C.
E.
F.
2.02
Not Used
Configuration:
1.
2.
D.
University of Georgia
RCE 2013029
No. 10 and smaller:
No. 8 and larger:
Solid
Stranded
Insulation - 600 Volts:
1.
No. 6 and smaller:
2.
No. 4 and larger:
THHN, THWN
XHHW
Jacket Color:
1.
No. 8 and smaller:
2.
No. 6 and larger:
Uniform colored jacket
Black
Jacket Markings:
1.
Voltage
2.
Insulation type
3.
Conductor Size
4.
Conductor type
COLOR CODING TAPE
A.
Vinyl 3/4" wide with uniform color and adhesive backing.
B.
Acceptable Manufacturers:
1.
Brady
2.
3M
3.
Plymouth
4.
Thomas & Betts
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.03
SPLICE AND TAP MATERIALS
A.
No. 10 and smaller:
1.
Crimp type: Cylindrically shaped conductor sleeve for crimping
copper conductors. Insulated with nylon or plastic cover.
2.
Twist on: Inner spiral spring or threads for holding and making
electrical contact between copper conductors and with outer long
skirted insulated cover of nylon or plastic.
B.
No. 8 and Larger:
1.
Set-screw or bolted type: Metal connectors for joining copper to
copper, with bolts or set-screws to apply pressure to conductors.
Insulate with nylon or plastic cover or with electrical tape.
2.
Pressure type: Metal connectors for joining copper to copper,
copper to aluminum, or aluminum to aluminum with power operated
crimping tool. Insulate with nylon or plastic cover or with electrical
tape.
C.
Acceptable Manufacturers:
1.
2.
3.
4.
5.
6.
7.
2.04
University of Georgia
RCE 2013029
AMP
Burndy
Ideal
Ilsco
Panduit
3M
Thomas & Betts
CONDUCTOR TERMINALS
A.
Copper conductors: High conductivity copper terminal designed to hold
conductor and make electrical contact by bolt, setscrew or power crimp
and with spade to match equipment receiving conductor.
B.
Acceptable Manufacturers:
1.
2.
3.
4.
5.
Burndy
Ideal
Ilsco
Panduit
Thomas & Betts
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.05
CONDUCTOR HARNESS
A.
Plastic or nylon self-locking straps (commonly referred to as zip-ties or tiewraps).
B.
Acceptable Manufacturers:
1.
2.
2.06
Panduit
Thomas & Betts
WIRE PULLING LUBRICANT
A.
Lubricating, insulating and chemically neutral to conductors, conductor
insulation and conduits.
B.
Acceptable Manufacturers:
1.
2.
3.
2.07
University of Georgia
RCE 2013029
Greenlee
Ideal
Polywater
ELECTRICAL TAPE
A.
Vinyl plastic; moisture tight, resistant to ultraviolet radiation, alkalies, acids
and corrosion; chemically neutral to conductors and conductor insulation;
fire retardant; and single thickness dielectric strength equal to or greater
than 10,000V.
B.
Acceptable Manufacturers:
1.
2.
Scotch/3M
Plymouth
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Install the number of copper conductors indicated with a minimum of two
(2) power conductors and one ground conductor being installed in each
conduit not prescribed to be empty. Aluminum conductors may not be
used .
B.
Minimum Conductor Size: No. 12
C.
Complete installation of raceway run prior to pulling conductors.
D.
Install insulated bushings in conduit fittings prior to pulling conductors.
E.
Use wire pulling lubricants to reduce stress on conductors. Pull all
conductors of a run together. Use pulling methods, which do not damage
the raceway or conductors.
F.
Color Coding:
1.
2.
3.
No. 8 and smaller: Uniform colored jacket with respective color
below.
No. 6 and larger: Two wraps of tape applied within 6" of each
conductor end with respective color below.
Conductor Color Code:
208Y/120V
480Y/277V
240D/120V
Phase A
Black
Brown
Black
Phase B
Red
Orange
Blue
Phase C
Blue
Yellow
Orange (208V)
Neutral
White
Gray
White
Ground
Green
Isolated Ground
Green w/ Yellow Stripe
4.
For Different Voltages in Same Enclosure: Use a colored stripe
(not green) on one neutral to differentiate between systems. Keep
stripe color consistent throughout project.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
G.
At outlets leave a minimum of 12" of conductor ends at each fixture outlet,
device outlet and equipment outlet box.
H.
Conductor Terminals:
1.
Single: Use terminals on conductors no. 8 and larger where
equipment receiving conductors do not have conductor lugs with
set-screw(s)
2.
Multiple: Install terminals on conductors where more than one
conductor is connected to a single lug.
I.
Route conductors in all switchboards, panelboards, motor control centers
and terminal cabinets parallel to or at right angle to the enclosure's sides
and tops. Group and harness conductors in those enclosures using
conductor harness straps.
J.
Prior to energizing conductor, megger test feeder conductors for continuity
and shorts. Correct deficiencies prior to energizing.
K.
Tighten all bolted connections in and to mechanical lugs to torque rating
specified per manufacturer’s recommendations.
L.
Tighten all conductors with mechanical connections, torqued in
accordance with the conductor and/or connector manufacturers markings
as well as the values referenced in the following publications:
1.
Underwriters Laboratories Electrical Construction Directory (Green
Book).
2.
Underwriters Laboratories Electrical General Information (White
Book).
END OF SECTION 16120
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16130
BOXES
PART 1 - GENERAL
1.01
SUMMARY
A.
Description:
1.
B.
Related Sections:
1.
C.
Section 16050 - Electrical General.
Standards:
1.
1.02
Provide electrical boxes or, where prescribed, conduit bodies for
devices, outlets, splice connection points, raceway junction and
conductor pulling points complete with supports, covers and
accessories.
Underwriters Laboratories labeled and listed for application
specified.
SUBMITTALS
A.
Manufacturers Product Data Sheets.
PART 2 - PRODUCTS
2.01
INTERIOR OUTLET BOXES AND EXTENSIONS
A.
Galvanized steel, UL listed for application with conduit knockouts and
threaded holes for mounting devices and/or coverplates.
B.
Minimum Sizes:
1.
2.
3.
4.
Single Device: 3"H x 2"W x 2"D
Gang Device: 3"H x 2"W (per gang) x 2"D
Octagonal:
4"W x 1-1/2"D
Square:
4" Square x 1-1/2"D
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
Acceptable Manufacturers:
1.
2.
3.
4.
2.02
University of Georgia
RCE 2013029
Appleton
Raco
Steel City
American Electric
JUNCTION AND PULL BOXES
A.
Dry Locations: Galvanized sheet steel, NEMA 1, welded seams and
cover held by stainless steel screws or bolts.
B.
Damp or Wet Locations: Cast malleable iron with corrosion-resistant
finish, NEMA 3R, threaded conduit entries, neoprene coverplate gasket,
and coverplate held by stainless steel bolts.
C.
Acceptable Manufacturers:
1.
Appleton
2.
Crouse Hinds
3.
Hoffman
4.
Killark
PART 3 - EXECUTION
3.01 DEVICE APPLICATIONS
A.
Boxes for switches, receptacles, dimmers (designed for device box
mounting) and future devices:
1.
For dry Locations:
a.
When recessed:
1)
For construction other than concrete or masonry, use
interior outlet box.
b.
When surface: Cast box with threaded hubs
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
3.02 GENERAL APPLICATIONS
A.
For lighting fixtures, equipment connections, pullboxes for conduit 1" and
smaller, and junction boxes for conduits 1" and smaller.
1.
Recessed Interior Box:
a.
For construction other than concrete or masonry, use
octagonal or square interior outlet box.
b.
For concrete: Concrete box
c.
For masonry: Concrete box or square interior box with
masonry extension.
2.
Box Above an Accessible Ceiling: Octagonal or square interior
outlet box.
3.
Exposed Interior Box:
a.
Above 8'-0": Octagonal or square interior outlet box or
conduit body.
b.
8'-0" and below: Cast box or conduit body.
C.
Integrally Mounted Boxes: Boxes which are an integral part of an
equipment assembly from the manufacturer and are UL listed for the
application may be used in lieu of the boxes prescribed above.
3.03 JUNCTION BOXES AND PULL BOXES (conduits larger than 1")
A.
Junction boxes or conduit bodies where junction is exposed.
3.04 SUPPORT
A.
General: Support each box from the building structure independently of
conduit as follows, utilizing a support system capable of carrying 300% of
load.
1.
2.
Surface:
a.
Structural Steel: Bolted directly to steel member or bolted to
spring clip, which is clipped to steel member.
b.
Concrete: Power driven fastener or bolt to expansion
anchor set in drilled hole.
c.
Wood: Screw or bolt to wood.
Suspended: Bolted to engineered spring clip, which is clipped to
suspended ceiling system.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.
University of Georgia
RCE 2013029
Recessed:
a.
Drywall: Attach directly to stud or joist by screw or bolt; or
directly to a galvanized steel support which is attached
directly at each end to stud or joist by screw or bolt.
3.05 INSTALLATION
A.
Outlet locations indicated on the plans are approximate. Coordinate and
determine the exact location at the building. The architect reserves the
right to shift the exact location of any outlet 10 feet before it is
permanently installed.
B.
Install boxes plumb when vertical, level when horizontal and flush
adjacent surface when recessed.
C.
Where an outlet occurs in an architectural feature, center the outlet in
same.
D.
Where the mounting height of a wall outlet is not shown, mount at height
directed by Architect. Mounting heights are from finished floor to box
centerline.
E.
The contractor may, with Architect's approval, slightly vary an outlet's
mounting height so that the box's top or bottom occurs at a masonry joint.
F.
Where outlets at different levels are shown adjacent, install them on the
same vertical line.
G.
Space wall switch outlets with first gang box 4" from door trim on the
installed strike side.
H.
Locate boxes and conduit bodies so that covers are accessible and
removable.
I.
Limit masonry cuts from outlet boxes so that coverplate covers the cut.
J.
Provide plaster rings for all boxes set in plaster walls or ceilings.
K.
Match configuration to application.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
L.
Utilize box size (capacity) based upon NEC.
M.
For devices, utilize boxes designed to support the device independently of
coverplate and so install.
N.
Cover unused conduit openings with plastic covers for sheet steel boxes
and threaded plugs for cast boxes.
O.
Prior to pulling conductors or installing devices, clean boxes of dirt, debris
and water.
P.
Cover all boxes and secure with screws or bolts.
Q.
Install pullboxes to limit pulling distance and/or pulling bends.
R.
Outlet boxes for devices surface mounted below 10’-0” shall be cast
type with threaded hubs.
END OF SECTION 16130
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16140
WIRING DEVICES
PART 1 - GENERAL
1.01
1.02
SUMMARY
A.
Description:
1.
Provide switches, receptacles, dimmers and other strap mounted
wiring devices as shown on the drawings.
B.
Related Sections:
1.
Section 16050 - Electrical General
2.
Section 16130 - Boxes
C.
Standards:
1.
Underwriters Laboratories listed and labeled.
2.
NEMA
( configurations as listed )
SUBMITTALS
A.
Manufacturers Product Data Sheets.
PART 2 - PRODUCTS
2.01
MANUFACTURER
A.
Acceptable Manufacturers of Switches, Receptacles, and Coverplates:
1.
2.
3.
Products specified as standard of quality are manufactured by
Hubbell Incorporated, Wiring Device Division; referred to as
Hubbell.
Products of manufacturers listed below meeting indicated
standards and specified manufacturer's product data
characteristics, except as modified below, are acceptable for use,
subject to prior approval of proposed product list.
a.
Pass and Seymour/Legrand
b.
Leviton
Manufacturers product numbers listed below do not include color
selection. Refer to Section 16140, 2.05 for device colors
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.02
RECEPTACLES
A.
Duplex - 20A: 2-pole, 3-wire, 125 Volts, side wiring with ground screw,
NEMA 5-20R.
1.
B.
Hubbell # GF5362.
SWITCHES
A.
Single Pole Single Throw: 20 Ampere, 277 Volt AC, maintained contacts,
quiet operating toggle, side/back wiring and ground screw.
1.
B.
Hubbell # 1221
Three Way Single Throw: 20 Ampere, 277 Volt AC, maintained contacts,
quiet operating toggle, side/back wiring and ground screw.
1.
2.05
Hubbell # 5362.
Duplex Ground Fault Circuit Interrupter - 20A: 2-pole, 3-wire, 125 Volts,
pigtail wiring, thru wiring to protect receptacles downstream, test and reset
buttons, NEMA 5-20R.
1.
2.03
University of Georgia
RCE 2013029
Hubbell # 1223.
COVERPLATES
A.
Stainless Steel Coverplates:
1.
Raised shoulder style stainless steel, brushed finish, oversize ( 31/8" x 4-7/8" , single gang), in configurations up to six (6) gang as
indicated on the drawings, screws to match finish, and openings to
match device.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Plastic Coverplates:
1.
C.
Smooth finish nylon, oversize ( 3-1/8" x 4-7/8" , single gang ), in
configurations up to six (6) gang as indicated on the drawings,
screws to match finish, and openings to match device.
Surface Mounted:
1.
2.06
University of Georgia
RCE 2013029
Corrosion-resistant steel, rounded corners and edges, stainless
steel screws, single or multiple gang as indicated on the drawings.
Openings to match device(s) and construction to match box.
DEVICE AND COVERPLATE COLOR/FINISH
A.
When the wiring device is flush mounted, the devices shall be gray with
stainless steel coverplates.
B.
Devices installed in floor boxes or surface mounted boxes shall be brown.
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Install the type device indicated by symbol or legend at the location shown
on the plans.
B.
Install devices after conductors are pulled and painting is completed.
C.
Install devices vertically, unless otherwise noted, with SPST switches
having up as "ON" and receptacles having ground pin at bottom.
D.
Where more than one device is indicated at a location, the devices shall
be mounted in combined sectional gang boxes and covered with a single
plate.
E.
Coordinate location of devices with other trades and architectural
features. Do not locate devices on two different finishes such as half on
wall title and half on painted surface.
END OF SECTION 16140
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16170
MOTOR AND EQUIPMENT CONNECTIONS
PART 1 - GENERAL
1.01
SUMMARY
A.
Description:
1.
Provide power wiring to each motor, all mechanical equipment, all
kitchen equipment, and all miscellaneous equipment included in
the contract documents. Power wiring is the system of conductors
from the energy source to the equipment that conducts the
electrical energy, which does work or provides heat.
2.
Provide a disconnect switch, fused where prescribed, for each
motor or piece of equipment.
B.
Related Sections:
1.
Section 16440 - Disconnect Switches
2.
Section 16475 – Over current Protection
3.
Section 16050 - Electrical General
PART 2 - PRODUCTS
2.01
STARTERS
A.
2.02
MOTORS AND EQUIPMENT
A.
2.03
Provided under other divisions except where specifically prescribed in
Division 16 documents.
Motors, mechanical equipment, kitchen equipment, etc., provided under
other divisions.
CONTROL AND INTERLOCK WIRING
A.
Control wiring, (i.e., HVAC controls, remote pushbutton stations,
thermostats, etc.), is excluded except where specifically prescribed in
Division 16 documents.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Coordinate all rough-in and final power wiring and equipment connection
with other subcontractors.
B.
Install and connect individually mounted starters provided by other
subcontractors.
C.
Label each disconnect switch and starter with name of equipment it
serves.
D.
Coordinate over current device rating with nameplate of motor or
equipment which it protects.
END OF SECTION 16170
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16440
DISCONNECT SWITCHES
PART 1 - GENERAL
1.01
1.02
SUMMARY
A.
Description
1.
Provide disconnect switches in configurations as indicated on the
drawings and described in part 3 of this specification, complete with
enclosures and accessories.
B.
Related Sections
1.
Section 16050 - Electrical General
2.
Section 16170 - Motor and Equipment Connections
3.
Section 16475 - Overcurrent Protection
SUBMITTALS
A.
Manufacturers Product Data Sheets.
PART 2 - PRODUCTS
1.01
MANUFACTURERS
A.
1.02
Acceptable Manufacturers as Follows:
1.
Square D
DISCONNECT SWITCHES:
A.
Disconnect switches shall be heavy duty (NEMA Type HD), UL Listed.
B.
All switches shall have blades, which are fully visible in the "OFF" position
when the switch door is open. All current carrying parts shall be plated to
resist corrosion and promote cool operation. Switches shall have
removable arc suppressors where necessary to permit easy access to line
side lugs. Lugs shall be front removable and UL listed for 60 degrees C
or 75 degrees C, aluminum or copper wires.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
C.
Switches shall be quick-make, quick-break such that, during normal
operation of the switch, the operation of the contacts shall not be capable
of being restrained by the operating handle after the closing or opening
action of the contacts has started. The operating handle shall be an
integral part of the box, not the cover. Provisions for padlocking the
switch in the "OFF" position with at least three locks shall be provided.
Switches shall have a dual cover interlock to prevent unauthorized
opening of the switch door when the handle is in the "ON" position, and to
prevent closing of the switch mechanism with the door open. The handle
position shall indicate whether the switch is "ON" or "OFF".
D.
Switches shall be furnished in NEMA 1 general purpose enclosures
unless specified as NEMA 3R on the plans. Covers on NEMA 1
enclosures shall be attached with pin type hinges, NEMA 3R covers shall
be securable in the open position. NEMA 3R enclosures for switches
through 200 amperes shall have provisions for interchangeable bolt-on
hubs. Hubs shall be as indicated on the plans. NEMA 3R enclosures
shall be manufactured from galvanized steel. Enclosures shall have a
gray baked enamel finish, electro deposited on cleaned, phosphatized
steel.
E.
Switches shall be horsepower rated for ac and/or dc as indicated by the
plans. All fusible switches rated 100 through 600 amperes at 240 volts
and 30 through 600 amperes at 600 volts shall have a UL approved
method of field conversion from standard Class H fuse spacing to Class J
fuse spacing. The switch also must accept Class R fuses and have
provisions for field installation of a UL listed rejection feature to reject all
fuses except Class R. The UL listed short circuit rating of the switches
shall be 200,000 rms symmetrical amperes when Class R or Class J
fuses are used with the appropriate rejection scheme. The UL listed short
circuit rating of the switch, when equipped with Class H fuses, shall be
10,000 rms symmetrical amperes. 800 and 1200 ampere switches shall
have provisions for Class L fuses and shall have a UL listed short circuit
rating of 200,000 rms symmetrical amperes.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.03
University of Georgia
RCE 2013029
MANUAL MOTOR STARTING SWITCHES - TOGGLE TYPE DISCONNECT
SWITCHES
A.
Type K - Manual motor starting switches shall have a 30 ampere at 600
volt rating, terminal screws suitable for #10 awg or smaller wire, number of
poles as indicated on drawings, and an oversized NEMA 1 or NEMA 3R
enclosure. It shall be authorized for use on motor and non-motor loads.
Provide unit with toggle switch, unless noted to be key operated. Provide
pilot light if indicated on the plans.
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Provide units as described in Part 2, Section 1.02, unless shown to be
toggle switch on the plans; listed as a 20 or 30 ampere, single pole
disconnect; or due to space requirements where this switch will not fit or is
not applicable. All of these described installations may use a manual
motor starting switch - (toggle type disconnect switch).
B.
Install disconnect switch adjacent to equipment it serves or as located on
the plans.
C.
Anchor enclosures firmly to walls and/or structural surfaces.
END OF SECTION 16440
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16450
GROUNDING
PART 1 - GENERAL
1.01
SUMMARY:
A.
Description:
1.
B.
Related Sections:
1.
2.
3.
1.02
Provide a grounding conductor system from the building
panelboards radiating to every electrical power controlling and
consuming device in the system.
Section 16050 - Electrical General
Section 16110 - Raceways
Section 16120 - Conductors
SUBMITTALS:
A.
Manufacturers Product Data Sheets
PART 2 - PRODUCTS
2.01
GROUND CLAMPS:
A.
Bronze, U.L. listed, with configuration to match application.
B.
Acceptable Manufacturers:
1.
2.
3.
4.
Burndy
Ilsco
Thomas & Betts
O.Z. Gedney
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
PART 3 - EXECUTION
3.01
EQUIPMENT GROUNDING CONDUCTOR:
A.
3.05
3.06
ADDITIONAL EQUIPMENT GROUNDING CONDUCTORS:
A.
Branch circuit and feeder conduits: Install a green insulated grounding
conductor, as shown on the plans, in each branch circuit and feeder
conduit.
B.
Wiring Devices: At both switches and receptacles, connect the grounding
conductor to the grounding screw on the device.
EQUIPMENT GROUNDING CONDUCTOR ROUTING:
A.
3.07
General: Install a separate insulated copper conductor, color coded green,
from respective panelboard ground bus to every controller and/or device.
Route equipment grounding conductor with respective feeder, power
wiring and branch circuit conductors.
CONDUITS:
A.
All grounding electrode conductors, equipment grounding conductors and
bonds where not internal to equipment enclosures shall be installed in
conduit to within 6" of terminating clamp or exothermic weld.
END OF SECTION 16450
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16475
OVERCURRENT PROTECTION
PART 1 - GENERAL
1.01
SUMMARY
A.
Provide fuses and circuit breakers of ampere rating and U.L.
Classification as indicated on the drawings.
B.
Related Sections:
1.
2.
3.
4.
1.02
Section 16050 - Electrical General
Section 16440 - Disconnect Switches
Section 16170 - Motor and Equipment Connections
Section 16470 - Panelboards
SUBMITTALS
A.
Product Data
1.
2.
3.
Manufacturers: Product Data Sheets
Time - Current Characteristic Curves (Average Melt)
Current Limitation Curves
PART 2 - PRODUCTS
2.01
MANUFACTURERS
A.
Acceptable Manufacturers - Fuses:
1.
2.
3.
Products specified as standard of quality are manufactured by
Cooper Industries, Bussmann Division, referred to as Bussmann.
Products of manufacturers listed below meeting indicated
standards and specified manufacturer's product data
characteristics, except as modified below, are acceptable for use,
subject to prior approval of proposed product list.
a.
Gould Shawmut
All fuses shall be of the same manufacturer.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Acceptable Manufacturers - Circuit Breakers
1.
2.
3.
2.02
University of Georgia
RCE 2013029
Products specified as standard of quality are manufactured by
Square D Company, referred to as Square D.
Products of manufacturers listed below meeting indicated
standards and specified manufacturer's product data
characteristics, except as modified below, are acceptable for use,
subject to prior approval of proposed product list.
a.
General Electric
b.
Siemens/ITE
Circuit breakers shall be of the same manufacturer as the panelboard or
enclosure in which they are installed.
FUSES
A.
Mains, Feeders and Branch Circuits:
1.
Circuits 601 to 6000 amperes shall be protected by current limiting
BUSSMANN LOW-PEAK time-delay fuses KRP-C(amp)SP. Fuses
shall employ "0" rings as positive seals between the end bells and
the glass melamine fuse barrel. Fuse links shall be pure silver
(99.9% pure) to limit the short circuit current let-through values to
low levels and comply with NEC Sections requiring component
protection. The terminals shall be peened. Fuses shall be timedelay and shall hold 500% of rated current for a minimum of 4
seconds, clear 20 times rated current in .01 seconds or less and be
listed by Underwriters Laboratories Inc. with an interrupting rating
of 300,000 amperes RMS symmetrical. The fuses shall be UL
Class L. Fuses shall be "LOW-PEAK YELLOW" in color.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.
2.03
University of Georgia
RCE 2013029
Circuits 0 to 600 amperes shall be protected by current limiting
BUSSMANN LOW-PEAK dual-element fuses LPN-RK, LPS-RK, or
LPJ. All dual-element fuses shall have separate overload and
short-circuit elements. Fuses shall incorporate a spring activated
thermal overload element having a 284 degree Fahrenheit melting
point alloy and shall be independent of the short-circuit clearing
chamber. The fuse shall hold 500% of rated current for a minimum
of 10 seconds (30A, 250V Class RK1 case size shall be a minimum
of 8 seconds at 500% of rated current) and be listed by
Underwriters Laboratories, Inc with an interrupting rating of 300,000
amperes RMS symmetrical. The fuses shall be Time-Delay UL
Class RK1 or J to maintain the engineered protection of the system
components. Fuses shall be "LOW-PEAK YELLOW" in color.
MOLDED CASE CIRCUIT BREAKERS
A.
Description:
1.
Circuit breakers shall be Square D FA, KA, LA, NH, PA and/or PC
one, two or three pole molded case circuit breakers rated 15
through 2500 amperes, 120V.ac, 240V.ac, 277V.ac, 480V.ac, as
specified on the drawings. Breakers shall have an interrupting
rating to match the panel in which they are installed or as indicated
on the drawings. Install GFCI type breakers where indicated in the
schedule and to all pool equipment. All circuit breakers shall be UL
and CSA listed, IEC 157-1 rated, meet NEMA Standard AB1-1975
and Federal Specification W-C-375B/GEN, when applicable.
Breakers covered under this specification may be installed in
panelboards, switchboards, individual enclosures, motor control
centers, combination motor starters or 1-LINE busway plug-in units.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Construction:
1.
C.
University of Georgia
RCE 2013029
Molded case circuit breakers shall have overcenter toggle-type
mechanisms, providing quick-make, quick-break action. Breakers
shall be calibrated for operation in an ambient temperature of 40
degrees C. Each circuit breaker shall have trip indication by handle
position and shall be trip-free. Two and three pole breakers shall
be common trip. Each circuit breaker shall have a permanent trip
unit containing individual thermal and magnetic trip elements in
each pole. Circuit breakers with frame sizes greater than 100
amperes shall have variable magnetic trip elements, which are set
by a single adjustment (to assure uniform tripping characteristics in
each pole). A push-to-trip button shall be provided on the cover for
mechanically tripping the circuit breaker. The circuit breaker shall
have reverse connection capability and be suitable for mounting
and operating in any position.
Terminations:
1.
Circuit breakers shall have removable lugs. Lugs shall be UL listed
for copper and aluminum conductors. Breakers shall be UL listed
for installation of mechanical type or compression type lugs.
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Install fuses in all switches shown on the plans, which require fuses.
B.
Fuses shall not be installed in the switch until equipment is ready to be
energized.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
3.02
University of Georgia
RCE 2013029
Install "LOW-PEAK YELLOW" NOTICE labels to alert the end user of the
engineered level of protection of the electrical equipment. They shall be
marked with the proper fuse rating, per the drawings, and placed in a
conspicuous location on the enclosure. These labels are available with
the spare fuse cabinet (SFC) and are also available upon request from
Bussman.
INSTALLATION - CIRCUIT BREAKERS
A.
Install circuit breakers in panelboards, switchboards, distribution
panelboards, and enclosures as shown on the drawings.
B.
Terminate wiring into circuit breaker lug. Tighten lug to torque level as
marked on the lug.
END OF SECTION 16475
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16500
LIGHTING
PART 1 - GENERAL
1.01
1.02
SUMMARY
A.
Description:
1.
Provide lighting fixtures as prescribed in the lighting fixture
schedule complete with housing, junction boxes, ballasts, lamp
sockets, lamps, lenses, baffles and trims installed with support from
building structure. Verbal description of fixture in schedule will take
precedence over manufacturer number.
B.
Related Sections:
1.
Section 16050 - Electrical General.
C.
Standards:
1.
Underwriters Laboratories labeled and listed.
2.
CBM Approved
3.
ANSI C82.2
4.
1992 National Energy Conservation Act.
SUBMITTALS
A.
Manufacturers Product Data Sheets.
B.
ITL certified photometric reports.
PART 2 - PRODUCTS
2.01
LIGHT FIXTURES: As prescribed in lighting fixture schedule.
2.02
FLUORESCENT BALLAST
A.
Electronic: Solid state electronic, capable of operating one to four lamps.
1.
Acceptable manufacturers as follows:
a.
Advance
b.
Motorola
c.
Magnatec
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Support:
1.
Support each fixture from the building structure.
2.
Support in a manner that ensures the fixture weight being equally
distributed from each support and the fixture remaining in a level
position.
3.
Provide support systems capable of carrying 300% of load
imposed.
B.
For pendant or suspended fixtures mounted to suspended ceilings provide
1/4" steel rods above the suspended ceiling from building structure to
fixture. Provide a minimum of two supports for each chassis and spaced
a maximum of 4 feet on center.
C.
For recessed H.I.D., LED, and fluorescent fixtures recessed in a
suspended ceiling, provide 2 #10 awg. wire supports from building
structure to fixture. Provide a minimum of two supports for each chassis
spaced a maximum of 4 feet on center and located on diagonal corners of
the fixture. Provide tie down clips to secure fixture to the ceiling grid.
D.
For recessed single incandescent, provide #10 AWG steel hanging wire
from building structure to fixture; minimum of 2 separate supports per
fixture.
E.
For each recessed fixture, provide a trim to match the type ceiling (plaster,
grid, exposed panel, etc.) in which it is being installed.
F.
Aim and adjust all fixtures with lamp position, tilt, shutters, rotation or
other types of adjustment during installation. The Architect or his
representative will determine the final aiming and adjustment of such
fixtures during the substantial completion job visit. During the substantial
completion job visit, the electrician shall be on hand, with all necessary
equipment, to make these adjustments. The electrical contractor shall
provide adjustment and/or aiming instruction to the owner or owner’s
representative. Fixtures serving areas where day lighting dominates will
be adjusted after sunset.
END OF SECTION 16500
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16748
LIFE SAFETY SYSTEM
PART 1- GENERAL
1.01
GENERAL REQUIREMENTS
A.
Provide a microprocessor based addressable fire alarm system. The system
and components shall be supplied by one manufacturer.
1.
The system shall include all required hardware, raceways,
interconnecting wiring and software to accomplish the requirements of
this specification and the contract drawings, whether itemized or not.
2.
All equipment furnished shall be new and products of a single
manufacturer.
3.
In the interest of job coordination, the contractor shall contract with a
single source for supplying job materials, services and programming,
including final inspection/test services.
4.
All references to model numbers and other pertinent information
herein is intended to establish the standards of performance, quality
and appearance and is based upon equipment designed and
manufactured by Fire Lite .
Other suppliers of this system shall provide background information to the engineer
10 days prior to bid and be listed in a pre-bid addendum.
1.02
MATERIALS AND SERVICES
A.
The system shall include, but not be limited to the following elements:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Fire Alarm Control Panels (FACP).
Power supplies, batteries and battery chargers.
Equipment enclosures.
Addressable manual stations, relays, heat detectors and smoke
detectors.
Audible (voice evacuation) and synchronized visual evacuation
signals.
Remote Alphanumeric Annunciator with door release switches.
Software and firmware as required to provide a complete functioning
system.
Wiring and raceway.
Installation, testing and certification, and education labor.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.03
University of Georgia
RCE 2013029
SYSTEM OPERATION
A.
Actuation of any fire alarm initiating device shall immediately cause the
following actions to be initiated:
1.
Identify the type of alarm, specific device and location on the backlit
LCD display at the fire alarm control panel and at the remote
annunciators.
2.
Cause the system alarm LED to flash at the fire alarm control panel.
3.
Cause audible alarm signals to issue the voice evacuation signal from
a pre-recorded message.
4.
Cause all synchronized visual alarm signals to flash.
5.
Activate signals to the mechanical control system to cause shut down
designated air handling units.
6.
Interface with the elevator controller to recall the elevator.
7.
Activate the digital communicator to report the type of alarm and
location to a remote monitoring station (required telephone line and
charges for central station monitoring shall be the responsibility of the
building owner).
B.
Operation of the alarm acknowledge switch at the fire alarm control panel or
at the remote annunciator shall permit the silencing of the alarm signals
during the alarm condition. The silencing of the alarm signals shall not
prevent the resounding of the alarm devices should a subsequent alarm
condition occur.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.04
CODES AND REFERENCES
A.
1.05
University of Georgia
RCE 2013029
The publications listed below, form a part of this specification to the extent
referenced. The publications are referenced in the text by the basic
designation only. The latest version of each listed publication shall be used
as a guide unless the authority having jurisdiction has adopted an earlier
version.
1.
Factory Mutual (FM)
a.
FM AG Approval Guide
2.
National Fire Protection Association (NFPA)
a.
NFPA 70 National Electrical Code.
b.
NFPA 72 National Fire Alarm Code.
c.
NFPA 101 Life Safety Code.
3.
Underwriters' Laboratories, Inc. (UL)
a.
Appropriate UL Standards.
4.
Local, State and National Building Codes as adopted by the
authorities having jurisdiction.
QUALIFICATIONS OF THE INSTALLER
A.
The contractor must have successfully installed fire alarm systems of the
same type and design as specified, or have a firm contractual agreement
with a subcontractor having the required manufacturers' training and
experience.
1.06 SUBMITTAL REQUIREMENTS
A.
Shop Drawings: The contractor shall include the following information in the
equipment submittal:
1.
Complete manufacturer's catalog data including
supervisory power usage, alarm power usage, physical dimensions, finish
and mounting requirements. Submit panel configuration and interconnection
of modules and all other data as required to make an informed judgement
regarding product suitability. At a minimum, data shall be submitted on the
following:
a.
Fire alarm control panels and annunciators.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
b.
c.
d.
B.
Power supplies, batteries and battery chargers.
Equipment enclosures.
Manual stations, heat detectors, smoke detectors, and other
alarm initiating devices.
e.
Addressable interface relays and control modules.
f.
Wire and cable.
2.
Power calculations.
a.
Battery capacity calculations.
b.
Supervisory power requirements for all equipment.
c.
Alarm power requirements for all equipment.
3.
Data describing more than one type of item shall be clearly marked to
indicate the type the contractor intends to provide for a given
application.
4.
Complete drawings covering the following shall be submitted by the
contractor for the proposed system:
a.
Floor plans showing all initiating, end of line, supervisory,
indicating appliances, and output control devices. Raceways
shall be shown, marked for size, conductor count with type and
size.
b.
Wiring diagrams showing points of connection and terminals
used for all electrical connections to the system devices and
panels.
Maintenance Manuals: A complete operation and maintenance manual with
two sets of installation drawings shall be submitted prior to the final
inspection.
1.
2.
3.
The following information shall be inscribed on the cover:
a.
"OPERATION AND MAINTENANCE MANUAL"
b.
Building location.
c.
The name, address and phone number of the contractor,
system manufacturer and system subcontractor.
d.
The name and phone number of the fire department required
to respond to alarms at the project location.
The manual shall be legible and easily read with large drawings folded
and contained in pockets. Included in the manual shall be circuit
drawings, wiring and control diagrams with data to explain detailed
operation and control of each item of equipment and a control
sequence describing start up instructions. Included shall be
installation instructions, maintenance instructions, safety precautions,
test procedures, performance data, and software documentation.
A copy of the system certification and final tests results, as called out
in Part 3 of this section of specifications shall be included in this
manual.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.07
University of Georgia
RCE 2013029
MATERIAL REQUIREMENTS
A.
All equipment shall be new and unused. All components and systems shall
be designed for uninterrupted duty. All equipment, materials, accessories,
devices and other facilities covered by this specification or noted on contract
drawings and installation specifications shall be the best suite for the
intended use and shall be provided by a single manufacturer of if provided by
different manufacturers, recognized as compatible by both manufacturers.
B.
System installation and operations shall be verified by the manufacturer’s
representative and a verification certificate presented upon completion. The
manufacturer’s representative shall be responsible for an on-site
demonstration of the operation of the system and initial staff training as
required by the Architect and Consulting Engineer.
PART 2 – PRODUCTS
1.1
FIRE ALARM CONTROL PANEL
The fire alarm control panel (FACP) shall be Fire Lite Audio Command Center25/50 Voice Evacuation Control Panel and shall be modular, incorporate all
control electronics, relays, and necessary modules and components in a semiflush mounted cabinet with cylinder lock. The FACP shall comply with the
applicable requirements for UL 864. Loss of power, including any batteries, shall
not require the reloading of a program from any source. Upon restoration of
power, start-up shall be immediate, automatic and shall not require manual
operation. Loss of primary power or the sequence of applying primary or
emergency power shall not affect the transmission of alarm, supervisory or
trouble signals. Enclosures shall be provided with ample gutter space to allow
proper clearance between the enclosure and live parts of the panel equipment.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
A. Each FACP shall be intelligent, with its own microprocessor and memory.
Each FACP shall be UL listed independently as a fire alarm control unit.
Each FACP shall be capable of automatically programming itself upon
initialization and of creating the System Program, and automatically updating
the initial System Program to accommodate added or deleted devices on any
analog circuit. Each FACP shall be capable of identifying and programming a
General Alarm condition for all installed devices. The system shall be
capable of identifying the number of analog addressable circuits, the number
of devices on all circuits, the device type and location. The system shall be
capable of incorporating all new devices in the System Program. The system
shall display at the control panel, the sensitivity of remote addressable
photoelectric or ionization smoke sensor devices and thermal heat sensor
devices. The system shall be capable of displaying 160 characters of system
and user text (4 x 40 alphanumeric display). The control panel shall
automatically return to the normal mode after a predetermined time (one
hour) after being in the service mode. Addressable devices shall be
individually identified by the system, and any quantity of addressable devices
shall be in alarm at any time up to the total number connected to the system.
B. The control panel shall be capable of supporting non-addressable as well as
addressable devices. The control panel shall be capable of supporting
conventional zones in addition to analog/addressable circuits. The control
panel shall provide for addressable remote conventional zones that are
hardwired to any point on any analog/addressable circuit. Individual input
and output device addressability as well as remote sensitivity measurement
shall be performed on the same pair of wires. The System shall be capable
of having multiple addressable devices in alarm simultaneously. The FACP
shall have a service mode to permit the arming and disarming of individual
detection or output devices as well as manually operating output devices.
Status of these devices shall be displayed upon command from the FACP.
Control panel shall automatically return to normal mode in the event the panel
remains unattended in the service mode. The control panel shall be able to
receive and process alarms even in the service mode.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
C. The FACP shall be capable of:
1.
2.
3.
4.
SmartStart auto initialization
SmartStart Program Update
Program all functions from the FACP front panel
Counting the number of addressable devices within a Acircuit@
which are in alarm
5. Counting Acircuits@ which are in alarm
6. Counting the number of addressable devices which are in alarm
on the system
7. Differentiating among the types of addressable devices such as
ionization smoke sensors, photoelectric smoke sensors, thermal
heat sensors, control elements, collective zone interfaces, point
identification devices, and manual stations.
8. Assigning priorities to type of detectors, circuits or groups of
detectors.
9. Transmitter disconnect switch which, when activated,
disconnects the transmitting device and causes operation of the
system trouble signals.
10. Indicate on the FACP alphanumeric display, as a minimum, the
following: Building Number, Floor, Type of Device, and Device
Address.
D. The FACP shall be capable of assigning control functions on the basis of
system initiation patterns of devices such as “anding” circuits, counting
circuits, counting devices, “anding” groups and “anding” types of devices
E. The FACP shall supervise each individual device on an initiating circuit such
that trouble, supervisory, normal, pre-alarm and alarm thresholds are
individually annunciated. Each device on an addressable initiating circuit
shall be checked to include the following: sensitivity, response, opens, shorts,
ground faults, functionality and status. The FACP shall report the failure of a
device’s transmitting components, open or shorted, on an addressable
initiating circuit. Each device shall be recognized and identified by location
within the circuit, and other devices on the circuit shall continue to function
properly. The FACP shall report by specific device and address, any device
which has been removed from an addressable initiating circuit, and shall not
disrupt the operation of the remaining devices. The system shall sound a
trouble if the device replaced is a different type than the device removed.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
F. The FACP shall be completely equipped and be provided with twenty-five
(25) percent spare initiating and indicating circuits, including modules,
enclosure space, terminal strips, internal electronic memory and other
necessary accessories complete and ready to accept future circuits. The
FACP shall be capable of automatically updating the System Program to
adjust for such changes. Hardware and software, which define system
configuration and operation, shall be provided. Memory data and operating
system software shall be contained in a non-volatile memory. The FACP
shall provide power necessary for the devices connected to it, including relay
and remote annunciators. A green LED shall be provided to indicate normal
system power is functioning.
G. The FACP shall be capable of measuring and adjusting the sensitivity of
sensors, and shall include an alphanumeric display to display custom
messages and give readings of sensor sensitivity, sensor by sensor. It shall
be possible to change the sensor sensitivity from the FACP within maximum
and minimum values as defined by the UL listing of the sensors. The system
shall be capable of listing sensor sensitivity settings for permanent record.
The FACP shall maintain a moving average of the sensors’ smoke chamber
value to automatically compensate (move the threshold) for dust and dirty
conditions that could affect detection operations. The system shall
automatically maintain a constant smoke obscuration sensitivity for each
sensor (via the floating threshold) by compensating for environmental factors.
The smoke obscuration sensitivity shall be adjustable with the UL 268
window (0.5 percent to 4.0 percent) to compensate for any environment. The
system shall automatically indicate when an individual sensor needs cleaning.
When a sensor’s percentage of compensation reaches a predetermined
value, a “Dirty Sensor” or equivalent trouble condition shall be audibly and
visually indicated at the control panel for the individual sensor. To prevent
false alarms, these “Dirty” conditions, shall in no way decrease the amount of
smoke obscuration necessary for system activation.
H. The system control panel shall continuously perform an automatic self-test
routine on each sensor, which will functionally check sensor sensitivity and
ensure the accuracy of the values being transmitted to the control panel. Any
sensor that fails this test shall indicate a trouble condition and the sensor
location at the control panel.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
I. It shall be possible to test, reset and alarm silence the system from the
FACP. New unacknowledged alarms and troubles shall be distinctively
displayed on the visual display and differentiated from previous alarm and
troubles. The system shall automatically indicate the total quantity of alarms
and of troubles, which have occurred prior to reset at the control unit. No
alarm or trouble indication shall be re-setable until it has been acknowledged.
It shall not be possible to reset the system until alarms have been
acknowledged.
J. The Voice Control Panel will be capable of detecting and annunciating the
following conditions: Loss of Power (AC and DC), System Trouble, Ground
Fault, Alarm, Microphone Trouble, Message Generator Trouble, Tone
Generator Trouble, and Amplifier Fault.
K. The Voice Control Panel shall be fully supervised including microphone,
amplifier output, message generator, speaker wiring, and tone generation.
L. Integral Digital Message Generator with a memory capacity for up to 60
seconds of messaging. The Digital Message Generator shall be capable of
producing five distinct messages (12 seconds each). These messages shall
field programmable without the use of additional equipment. Provide a built in
alert tone generators with steady, slow whoop, high/low and chime tone
which is field programmable.
M. The panel shall provide a minimum of four (4) Class AB@ alarm circuits
(expandable to sixteen).
N. The may be configured for General Alarm All Call operation, Alarm by Zone
as required. Activation of alarm devices shall activate immediate broadcast
of the alarm signal to all areas. The alarm signal shall be broadcast until the
FACP is reset.
O. N. Provide field programming equipment, software devices, computers and
other equipment necessary, including interconnection cables to
accommodate field software programming changes.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.02
University of Georgia
RCE 2013029
Remote Annunciator(s)
A.
Provide Remote Alphanumeric Annunciators with Back Box at front entry.
Each annunciator provide an 160 character (4 x 40) alphanumeric LCD display, system
control switches and a key operated enable switch.
2.03
Manual Stations
A.
Provide Addressable Manual Stations as indicated on the plans. Stations
shall be constructed of die cast aluminum. Each station shall contain the electronic
interface circuitry required for individual device identification, alarm reporting and
trouble supervision. The manual stations shall communicate with the main control
panel via the analog addressable circuit. Resetting the station after operation shall
require opening the front cover for access to the alarm switch. Where stations are
required to be surface mounted, the back box shall be factory painted the same color
as the alarm station.
2.04
Smoke Detectors
A.
Provide Analog Addressable Photoelectric Smoke Sensors with Bases as
shown on the plans. Sensors shall be listed to UL 268 and shall be
documented compatible with the control equipment to which they are
connected. Sensors shall be listed for both ceiling and wall-mount
applications. Each sensor shall contain an LED that, when the control
panel determines that a sensor is in the alarm or trouble condition, the
control panel shall command the LED to turn on steady, indicating the
abnormal condition. The sensor’s electronics shall be immune from false
alarms caused by electromagnetic interference and radio frequency
interference. Detectors shall be nominal 24 Vdc powered by the initiating
circuit. All sensor addressing information shall be stored in the fixed base.
Addressing information that is stored in the removable sensor is not
acceptable.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.05
University of Georgia
RCE 2013029
Duct Mount Smoke Detectors
A.
Provide Duct Mount Analog Addressable Photoelectric Smoke
Detectors with Sampling Tubes and Addressable Control Relays as
shown on the plans. Detectors shall be listed by UL or FM for duct
installation, shall be provided with approved duct housing, mounted
exterior to the duct, and shall be provided with perforated sampling tubes
extending across the full width of the duct.
2.06
Thermal Sensors
A.
Provide Analog Addressable Thermal Sensors with Bases as shown on
the plans. Sensors shall be of both combination rate-of-rise and fixed temperature
type, and shall communicate actual heat values to the system control panel. Detector
temperature setting shall be accomplished via the FACP. Each detector shall be
uniquely identifiable to the FACP. Sensors shall be listed to UL 268 and shall be
documented compatible with the control equipment to which they are connected.
Sensors shall be listed for ceiling mount applications. Each sensor shall contain an
LED that, when the control panel determines that a sensor is in the alarm or trouble
condition, the control panel shall command the LED to turn on steady, indicating the
abnormal condition. Detectors shall be nominal 24 Vdc powered by the initiating circuit.
All sensor addressing information shall be stored in the fixed base. Addressing
information that is stored in the removable sensor is not acceptable.
2.07
Addressable Remote Relays
A.
Provide Addressable Control Elements as required for interface with
HVAC controls, elevator controls, elevator power shunt trip controls, door
lock controls, access control system controls and other systems as
designated on the plans. Each addressable control element shall be
capable of providing feedback to the FACP for positive confirmation of the
control devices activity. Addressable control elements shall include form
AC@ dry contacts rated for 2 Amp @ 30 VDC / .5 Amp @120 VAC. Each
RCE shall contain an integral LED that annunciates module activation.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.08
University of Georgia
RCE 2013029
Alarm Signals
A.
Provide Speaker Strobe Alarm Signals as shown on the plans for
all locations requiring audible and visual alarm signals. All strobes shall be
synchronized and provide a minimum of 110 candela light output.
B.
Provide Synchronized Strobe Visual Alarm Signals as shown on the plans
for all locations requiring visual only alarm signals. All strobes shall provide a minimum
of 110 candela light output.
2.09
Remote Communicator:
A.
Provide a digital remote communicator (dialer) and connect into the
new fire alarm panel. Required phone lines shall be furnished and
installed by the building owner.
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Electrical Contractor shall furnish and install all conduit and outlet boxes, and
shall furnish and install all equipment and wiring in accordance with
applicable local, state, and national codes, the manufacturer's
recommendations, these plans and specifications. The contractor may
contract with a manufacturers authorized equipment installer for any portion
of the installation, but is ultimately responsible for the complete installation
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.02
University of Georgia
RCE 2013029
TEST
A.
The contractor must contract with a manufacturers authorized agent or
installation firm to test and certify the system meets all provisions of the
specifications and that the system is fully functional. A service technician
authorized by the manufacturer of the fire alarm equipment shall supervise
and participate during all of the following checks, adjustments, and tests of
the system.
1.
2.
3.
4.
5.
6.
7.
8.
9.
B.
Before energizing the cables and wires, check for correct connections
and test for short circuits, ground faults, continuity, and insulation.
Open initiating device circuits and verify that the trouble signal
actuates.
Open and short signaling line circuits to verify that the trouble signal
actuates.
Open and short Notification Appliance Circuits and verify that trouble
signal actuates.
Ground all circuits and verify response of trouble signals.
Check presence and audibility of tone at all alarm notification devices.
Check installation, supervision, and operation of all addressable
smoke detectors using the Walk Test.
Each of the alarm conditions that the system is required to detect
should be introduced on the system. Verify the proper receipt and the
proper processing of the signal at the FACP and the correct activation
of the control points.
When the system is equipped with optional features, the
manufacturer's manual should be consulted to determine the proper
testing procedures. This is intended to address such items as
verifying the controls performance by individually addressed or
grouped devices, sensitivity monitoring, verification functionality and
similar.
The supervising agent of the manufacturer shall provide a completed test
results form for inclusion in the maintenance manuals.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.03
FINAL INSPECTION
A.
3.04
3.05
University of Georgia
RCE 2013029
At the final inspection, a trained representative shall demonstrate that the
system functions properly in every respect.
INSTRUCTION
A.
The Contractor and/or the Systems Manufacturer's representatives shall
provide a typewritten "Sequence of Operation" to the Owner for inclusion in
the maintenance manuals.
B.
Provide one four hour session of on-site instructions, with a complete and
functioning system, for the designated owner representatives from the
system manufacturer's authorized agent. This agent shall have a full working
knowledge of this installed system and be fully prepared to present this
information to the Owner to their satisfaction. "Hands-on" demonstrations of
the operation of all system components and the entire system including
program changes and functions shall be provided.
PERMITS AND APPROVALS
A.
Permits necessary for installation of the work shall be obtained prior to the
commencement of work.
B.
Prior to commencement and after completion of work, notify authorities
having jurisdiction.
C.
All applicable portions of the National Electrical Code shall be implicitly
followed, in particular with regard to material type and quality, circuitry
extensions from and connections to outlet and junction boxes, panel boards
and similar appurtenances.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.06
University of Georgia
RCE 2013029
WARRANTY
A.
The equipment manufacturer shall guarantee the system equipment to the
Owner for a period of one (1) year from the date of final acceptance of the
system.
B.
The contractor shall guarantee all wiring and raceways to be free from
inherent mechanical or electrical defects for one (1) year from the date of
final acceptance of the system.
C.
Copies of these warranties, along with phone numbers and addresses of the
manufacturer, contractor, and supervising agent shall be included.
END OF SECTION 16748
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 16760
STAGE and DIMMING EQUIPMENT
1.
GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
GOVERNING CLAUSE
A.
1.3
For the sake of brevity these specifications shall omit phrases such
as "Contractor shall furnish and install", "unless otherwise indicated
or specified", etc., but these phrases are nevertheless implied.
Mention of materials and operations requires the Contractor to
furnish and install such materials and perform such operations
completely to the satisfaction of the Owner.
SCOPE OF WORK
A.
1.4
Drawings and general provisions of Contract, including General and
Supplementary Conditions and Division 1 Specification sections,
apply to work of this section.
One company shall be responsible for the installation of all aspects
of the stage equipment in the Auditorium. Work under this section
shall include the furnishing of all labor, materials, tools,
transportation services, supervision, etc., necessary to complete
installation of new stage equipment as well as any other items as
herein listed, all as described in these specifications, as illustrated
on the accompanying drawings; or as directed by the Architect or
his Representative. Work includes the following:
Motorized Rigging
Dead Hung Rigging
Stage Lighting, Dimming & Control System
SUBSTITUTIONS:
A.
Specific fabric and items of equipment are specified by trade
names. It has been determined by the Owner that these are the
particular items desired by the owner and established a standard of
quality, equipment function and/or process. It is not the purpose nor
intent of these documents to eliminate competitive bids. In order to
allow proper and fair comparison of pricing, contractors are
required to submit their base bid price on the specified equipment.
A contractor may submit an alternate bid based on equipment
different from that specified only if that Contractor has received
prior approval in writing from the Owner at least 10 days prior to
bid. Accompanying each request shall be a letter specifically
detailing each substitution including catalog data, specifications,
swatches, operative samples, technical information, drawings,
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
performance and test data, and complete descriptive and functional
information to assist in a fair evaluation. Failure to submit any
substitution for prior approval or not providing sufficient data for
evaluation shall require the exact item specified to be furnished.
Owner's approval of a substitution for bid purposes will not relieve
the contractor from the responsibility of meeting all specification
criteria. If an approval of a substitution is granted, the Contractor
shall be fully responsible for any and all changes (wiring, power,
distribution, support structure, etc.) such substitution shall require.
1.5
DEFECTIVE OR NON-APPROVED MATERIALS
A.
1.6
GUARANTEE
A.
B.
C.
1.7
The Contractor shall guarantee all of the work that is performed
under this contract, including all materials, and workmanship, for a
period of one (1) year from the date of full acceptance of the work.
Lamps for lighting fixtures shall be guaranteed against failure for
thirty (30) days.
Nothing in this guarantee shall cause repair or replacement by the
Contractor where negligence, neglect or improper operation by the
Owner has caused the failure of any equipment installed under this
contract.
DISCREPANCIES
A.
1.8
Should any stage equipment be found defective, not meeting
specifications, or that which has not been approved in writing by the
Owner shall, upon discovery (including any time within the period of
the guarantee), be replaced with the specified equipment or
material at no additional cost.
All equipment shall be sized to fit properly. The exact
measurements are the responsibility of the Contractor. If there are
discrepancies in the specifications, the Contractor shall ask for a
clarification from the Owner. If no clarification is requested, the
Owner's judgment shall rule.
PRE-APPROVED STAGE EQUIPMENT CONTRACTORS
A.
One company shall be responsible for the installation of all aspects
of the stage equipment as specified in this section. This shall
include but not be limited to all rigging, curtains, tracks, motors and
control, stage lighting fixtures, stage/house dimming, and dimming
controls and miscellaneous equipment. The following companies
have prior approval as STAGE EQUIPMENT CONTRACTORS:
1.
Barbizon 404-681-5124
2.
Magnum Companies 404-872-0553
3.
Television Production Services 770-452-8700
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
C.
D.
1.9
University of Georgia
RCE 2013029
In order to be considered as a Stage Equipment Contractor on this
project, each Contractor requesting approval must submit to the
Architect at least ten (10) days prior to the date of bid opening a
letter expressing his intent to bid. This letter shall include a list of at
least five (5) projects of similar size and scope completed by this
firm within the last five (5) years. If motorized line-shaft rigging is
required on this project, the letter shall indicate the number of lineshaft set provided and installed and the manufacturer of the
equipment on each of the five projects. Inspection of one
completed installation may be requested by the Architect/Architect's
Representative prior to consideration of request to bid. The stage
equipment contractor shall have been in business under the same
name for five (5) full years preceding the date of this bid doing work
similar to the type specified. The decision of the Architect as to the
capability of the Bidder to successfully complete and maintain the
system, based on this pre-qualification information shall be final.
Pre-Bid request letter shall include a statement that all major items
of equipment shall be bid and supplied as specified, or shall contain
details of all proposed substitute equipment for review by the
Architect/Architect's Representative. Substitute equipment items to
include specifications, parts numbers, and details of interconnection
to proposed system. The decision of the Architect/Architect's
Consultant as to the acceptability of substitute equipment shall be
final.
The Stage Equipment Contractor shall employ only fully trained
stage riggers and mechanics, assisted by common laborers, for the
erection of the stage equipment. The stage riggers shall be
completely familiar with the type of equipment to be installed. A
competent Job Superintendent shall be on the job at all times when
work is in progress. He shall represent the Stage Equipment
Contractor and all directions given by him shall be as binding as if
given by the Stage Equipment Contractor.
ACCEPTABLE EQUIPMENT MANUFACTURERS
A.
B.
C.
D.
E.
For the purposes of establishing a standard of quality desired on
this project, the rigging hardware products of Electronic Theatre
Controls of Middleton, Wisconsin are specified.
The stage lighting dimming and control of Electronic Theatre
Controls of Middleton, Wisconsin are specified.
The stage lighting fixtures of Electronic Theatre Controls of
Middleton, Wisconsin are specified.
The electrical stage distribution hardware of Electronic Theatre
Controls of Middleton, Wisconsin are specified.
All other companies must receive prior approval to bid this project.
Please refer to the section regarding substitutions.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.10
University of Georgia
RCE 2013029
DOCUMENTATION
A.
B.
SHOP DRAWINGS: Shop drawings and equipment data sheets
shall be submitted to the Owner under general provisions within 45
days after award of the contract. Failure to comply with this 45 day
requirement shall be cause for disqualification of the selected
Contractor and cancellation of contract without cost to the Owner,
on the basis that the selected Contractor does not have the ability
or intention to comply with the specifications. Approval of
submitted equipment shall be obtained prior to equipment
purchasing or fabrication. If shop drawings are rejected, correct
and resubmit in the manner as specified. All shop drawing
information shall be submitted at the same time; no partial submittal
will be accepted. Drawings shall indicate complete details,
dimensions, product types and locations of all equipment,
clearances required, guides, cables, sets, Contractor fabricated
equipment, and all other details required to completely describe the
work to be performed. Submittals drawings shall be presented at a
scale of not less than 1/8" = 1'-0" for conduit plans, 1/4" for
equipment layouts, ½" = 1'-0" for mounting details, and ½" = 1'-0"
for plate and panel details. Each sheet to allow space for approval
stamps and have the name of the project, the contractors and/or
the supplier's name, address telephone number, and the date
submitted. Submit the following items for Owner's approval, prior to
fabrication:
1.
Stage plan view
2.
Stage side section view
3.
Gridiron layout indicating all stage equipment.
4.
Electrical riser diagrams indicating the necessary control
wiring for all dimming, distribution, and controls wire tag
number for every connection. Show all terminal blocks with
wire numbers and location.
5.
Plan and elevation views indicating all electrical hardware
locations and layout
6.
Provide full dimensions for panel layouts with finishes and
materials for all custom panels.
7.
Details of installation and erection, including adjoining
conditions and necessary clearances.
8.
Indication by arrow and boxed caption of each variation from
contract drawing and specifications, except those indicated
as acceptable in specifications or on drawings
RECORD DRAWINGS AND DATA: Submit in accordance with
General Provisions. Also within 30 days of final test and completion
of the installation, submit the following to the Owner:
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
1.
2.
Three (3) complete sets of "as built and approved" drawings
(rolled, not folded showing systems and elements as
installed, including field modifications and adjustments.
2.
Three (3) sets of maintenance data including a list indicating
replacement parts lists for all items of equipment, wiring
diagrams, control diagrams, any and all keys for cabinets,
racks, key operated switches etc. and complete operation
manuals.
3.
Three (3) notarized Certificates of Flameproofing for each
fabric used.
4.
Three (3) Certificates of Guarantee
C.
INSTRUCTION OF OWNER PERSONNEL: This contractor or his
representative, fully knowledgeable and qualified in systems
operation, shall provide eight (8) hours of instruction to the Ownerdesignated personnel on the use and operation of this System.
Designated instruction times shall be arranged through the Owner.
D.
PERMITS: Obtain all permits necessary for the execution of any
work pertaining to the installation, and conform in all trades with all
applicable local codes and with the National Electric Code. Obtain
all permits necessary for operation of any equipment by the Owner.
E.
CLEAN UP: It shall be the responsibility of this Contractor to
remove all debris from the building or site caused by his operations
to a common trash point or receptacle on the job site, as
determined by the Owner.
THEATRICAL RIGGING EQUIPMENT
2.1
GENERAL STANDARDS
A.
B.
C.
Each hoist shall be fully tested under full rated load throughout its
full travel distance with all its liftlines terminated to the hoist before
the hoist is shipped from the manufacturer. Testing shall include:
1.
Hoist operation
2.
Hoist/motor speed
3.
Liftline terminations under load
4.
Braking and stopping under load
5.
Load cell functions
6.
Slack line detection
7.
Position sensing
8.
Hoist noise
Only hoists that successfully pass pre-shipment testing shall be
sent to any job site. A record of testing and its results shall be
available for review at the manufacturer’s facility for at least one
year after testing.
Paint as required under this section shall be the manufacturer's
standard finish and color except as noted.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
D.
All equipment items shall be new and conform to applicable
provisions of Underwriters' Laboratories (UL), American Standards
Association (ASA), American National Standards Institute (ANSI),
National Fire Protection Association (NFPA) Life Safety Code 01,
National Electric Code (NEC) and PLASA.
1.
Where acceptable equipment items are specified by catalog
number only, device shall meet all published manufacturer's
specifications. Where quantities or sizes are not given,
refer to drawings. Where two or more products are listed,
contractor may use either, at his discretion. Equipment shall
not be substituted without specific written approval by the
Architect under the substitution paragraphs of these
specifications.
2.
All pipe battens shall be fabricated from 1.5" Schedule 40
pipe.
3.
All turnbuckles and cable clips shall be drop forged.
4.
All turnbuckles and clips, tracks, chains and other items of
incidental hardware shall be furnished plated or painted.
Wire rope shall be galvanized. Fasteners, chain, and other
miscellaneous hardware shall be either cadmium or zinc
plated.
5.
All materials used in this project shall be new, unused and of
the latest design. Refurbished materials are not permitted.
6.
In order to establish minimum standards of safety, a
minimum factor of 8 shall be required for all equipment and
hardware used on this project. In addition, the following
factors shall be used:
Cables and fittings
Cable bending ratio
Max. fleet angle
Steel
Bearings
2.2
University of Georgia
RCE 2013029
10 Design Factor
26 times diameter
2 degrees
1/5 of yield
Two times required load at full for 2000 hours
HOISTS
A.
Hoists shall be purpose-designed and fabricated for overhead lifting
of theatre lights, equipment, curtains and scenic elements, whether
used on stage, in the auditorium or other places of public assembly
where people shall move beneath the suspended or moving load.
The systems shall incorporate mechanical, electrical and safety
features that shall be inherent to this equipment; they shall provide
an engineered, efficient device for overhead lifting. The mechanical,
electrical and safety features of this hoisting and control system
shall establish the standard of quality, performance and safety by
which hoisting systems of other manufacture shall be evaluated.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
C.
D.
E.
F.
University of Georgia
RCE 2013029
Each wire rope liftline shall adhere to a design factor of 10:1 with an
ultimate strength of 4200 pounds. All load path components
between the building structure and the batten shall exceed the
breaking strength of the wire rope. The motor brake shall be rated
at least at 125% of the motor torque.
Standard configured hoists shall be capable of supporting a live
load suspended from the batten as follows:
1.
General purpose Variable Speed 0-180 fpm, 1000 pound
capacity in standard configuration. Powerhead shall
measure no more than 16” high x 16” w x 55 ¼” long and
weigh 495 pounds
2.
General purpose 30 fpm 800 pound capacity in standard
configuration. Powerhead shall measure 16” high x 16” w x
47 1/2” long and weigh 395 pounds
3.
General purpose 30 fpm 1300 pound capacity in standard
configuration. Powerhead shall measure 16” high x 16” w x
47 1/2” long and weigh 395 pounds
4.
General purpose 30 fpm 1900 pound capacit in standard
configuration. Powerhead shall measure 16” high x 18” w x
53 1/2” long and weigh 580 pounds
5.
Stage Electric 30 fpm 650 pound capacity in standard
configuration. Powerhead shall measure 16” high x 16” w x
47 1/2” long and weigh 395 pounds
6.
Stage Electric 30 fpm 1000 pound capacity in standard
configuration. Powerhead shall measure 16” high x 16” w x
47 1/2” long and weigh 395 pounds
The standard general purpose hoist shall consist of the following
major components: 1) Powerhead, 2) compression tube with beam
clamps, loft blocks, liftline and liftline terminations, Right Angle
Cable Adjuster (RACA) and 3) pipe batten.
The standard stage electric hoist shall consist of the following major
components: 1) Powerhead, 2) Compression Tube with beam
clamps, cable management system, loft blocks, liftline and liftline
terminations Right Angle Cable Adjuster (RACA), 3) pipe batten
and power/control distribution strip
The hoist shall include the following features:
1.
A Powerhead containing the following elements: the gear
motor, motor brake, load brake, limit switches operating
electronics, load sensor, slack line detector, absolute
position sensors, cable drum assembly, and wire rope.
2.
A Compression Tube that prevents hoist system lateral
forces from transferring to the building. Hoists or hoisting
systems that impose a lateral load on the building shall not
be acceptable.
3.
The hoist shall incorporate a built-in load cell.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
4.
5.
G.
2.3
POWERHEAD
A.
B.
2.4
The Powerhead shall be a fully enclosed, powder coated sheet
metal housing that shall prevent contact with moving and electrical
parts and shall provide protection against dirt, dust and debris.
For setup and maintenance, the following functions shall be
available from the Powerhead: power and operating switches,
address setting knobs, limit switch setting knobs, limit switch
override button, indicators for power, status and communication.
Each of these functions shall be clearly labeled.
GEARMOTOR AND MOTOR BRAKE
A.
B.
C.
D.
2.5
The hoist shall incorporate a built-in slack line sensor.
The hoist shall include the emergency contactor built into the
hoist.
The hoist shall be manufactured from UL Listed components and
shall be UL Listed and tested as a complete system (not just UL
listed parts).
The gear motor and motor brake shall be an integral unit from a
single manufacturer. It shall operate on 208 Volt or 480 Volt 60 Hz,
3 phase current for fixed speed units and 480 Volt, 60 Hz, 3 phase
current for variable speed hoists.
The motor brake shall be integral to the gear motor and shall be
capable of holding 125% of the motor full load torque.
The motor brake shall be spring actuated to apply and hold braking
force.
The motor brake shall be magnetically released and held open
upon actuation.
LOAD BRAKE
A.
Fixed Speed Hoists
1.
The rotary disk load brake shall bring the moving load to a
complete stop and shall hold the load in position in the
event of a mechanical failure of the motor, motor brake or
gearbox.
2.
Noise from the load brake shall be minimally audible at any
time in the operational cycle.
3.
Normal hoist operation shall not be limited by heat or noise
caused by the load brake.
4.
The load brake shall be mechanically released when the
load is moving in the up direction. The load brake shall be
close when the hoist has stopped. The load brake shall
always be engaged when the load has stopped moving
either up or down. When lowering the load the load brake
shall partially disengage to allow and control descent of the
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
batten. The load brake shall remain closed in the absence
of rotational torque on the gearbox.
2.6
WIRE ROPE DRUM
A.
2.7
LIMIT SWITCH
A.
2.8
A position sensing system shall be built into the Powerhead to
provide accurate position information. The system shall consist of
two absolute sensor types that provide accurate position
information for each batten at power-up of the system. Hoisting
systems that require re-homing shall not be acceptable.
Incremental encoders shall not be acceptable for position readout
purposes.
SLACK LINE DETECTOR
A.
2.11
A load sensor shall be built into the Powerhead to create a profile of
the actual load on the hoist as it travels through its normal cycle.
The profile may be changed by “re-training” the profiling system
whenever the suspended load is changed on the batten by
activating a key-switch operated training cycle on the motor
controller. The load sensor shall continuously monitor the load
when load sensing is turned on.
POSITION SENSOR
A.
2.10
A limit switch assembly shall be mounted within the Powerhead for
hard “normal” and “ultimate” end of travel limits. Hard end of travel
limits shall be set/adjusted at the time of installation aided by an
indicator light visible on the bottom panel of the Powerhead cover.
Any system that indicates that the limit has been set by audible or
tactile means only shall not be acceptable.
LOAD SENSOR/LOAD PROFILING.
A.
2.9
Shall wrap up to eight 3/16” diameter 7 x 19 galvanized aircraft
(utility) wire rope liftlines up to 50’ long in a compact manner on the
cable drum. They shall be managed by a wire rope (cable) keeper
integral to the Powerhead. The drum design shall prevent wire
rope from tangling or crossing over itself.
The slack line detector shall be built into the Powerhead. When a
slack line condition in excess of 15” develops in a liftline, the slack
line detector shall remove power from the hoist. The batten shall
be allowed to move only in the upward direction to allow removal of
the cause of the slack line fault.
LOCAL USER INTERFACE AT POWERHEAD
A.
User interface at the Powerhead control panel at the rear of the
hoist shall include:
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.
2.
3.
4.
2.12
Record of severe fault conditions with date and time stamp
Record of E-stops, overloads, moves and power cycles
Record of travel distance and peak loads since
installation/inspection
COMPRESSION TUBE AND BEAM CLAMPS
A.
B.
C.
D.
E.
F.
2.14
Hoist Up/Down Control
Limit Switch override buttons (tool accessible)
Address switches
Status LED’s
INFORMATION STORAGE WITHIN POWERHEAD
A.
B.
C.
2.13
University of Georgia
RCE 2013029
The Compression Tube shall be a continuous channel of extruded
aluminum engineered in conjunction with the beam clamps to
neutralize rigging-generated lateral forces on the building.
The Compression Tube shall support the system loft blocks.
Compression Tube sections shall be joined into a continuous
assembly by a pair of dedicated splicing plates at each tube joint.
The Compression Tube shall be installed only by means of
dedicated beam clamps that allow the Compression Tube to snap
into place and to fractionally move horizontally under load.
Beam clamps shall be capable of attaching to horizontal beams,
joists, truss flanges or flat steel plates measuring from 1/4” thick up
to 1” thick and from 4” wide up to 14” wide placed no more than 14’0” apart. P650E, P800G, P1000E and P1300G Powerheads may
be mounted on ¼” thick x 4” wide or larger steel structures if
deemed sufficient by a structural engineer. P1500E, P1900G and
V1000S hoists must be mounted on 3/8” x 6” wide or larger steel if
deemed sufficient by a structural engineer. Support structures must
be deemed sufficient by a structural engineer to support any forces
imposed by the hoisting systems. Beam clamps shall
accommodate up to ½” vertical misalignment.
Hoist systems that do not neutralize hoist generated lateral forces
on the building shall not be accepted for this project.
LOFT BLOCKS
A.
B.
Each loft block shall be an assembly of steel side plates, a wire
rope idler, sheave, bearings, shaft locked against rotation and
support hardware. Each loft block shall be inserted into the slot on
the bottom of the Compression Tube. The blocks shall be
positioned no closer than 4’-0” from each other, unless muled.
Loft block sheaves shall measure 5” in diameter and contain a pair
of press fit sealed ball bearings. Liftlines shall travel in a groove
shaped and sized for 3/16” diameter wire rope per the latest edition
of the Wire Rope Users’ Manual as published by the Wire Rope
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
D.
2.15
B.
C.
D.
Each liftline shall be terminated in the Powerhead via a standard
copper oval compression sleeve installed/crimped at the factory.
Liftlines shall be terminated at the load hanger with a low profile
Right Angle Cable Adjuster (RACA) ™, thimble and copper oval
compression sleeve. The RACA and cable terminations at the
batten shall be installed at the time of hoist installation.
Batten trim shall be adjustable up to 6” via the RACA.
Systems utilizing turnbuckles or chain to trim the batten shall not be
accepted for this installation.
HANGERS
A.
2.17
Technical Board. The loft block sheave shall be concentric about
the hub and shall be evenly balanced for ease of rotation.
An idler shall be incorporated into the top assembly of the loft block
to guide and support liftlines as they pass the block.
Hoisting systems requiring the loft blocks to be mounted directly to
the facility structure shall not be accepted for this project.
LIFTLINE TERMINATIONS
A.
2.16
University of Georgia
RCE 2013029
Raceway hangers shall be specially shaped flat bar that shall
support the wire rope termination hardware and secure the raceway
and the pipe batten.
CABLE MANAGEMENT FOR ELECTRICS
A.
PRODIGY CABLE MANAGEMENT for ELECTRICS
1.
The load circuits and control wiring shall be fed to the
distribution trough by a built-in cable management system
that allows flat feeder cable to fold and store along the top
of the connector strip.
a.
At high trim, the entire system shall be stored in 30” of
vertical space from the bottom of the mounting steel
to the horizontal centerline of the batten. Cable
management systems requiring greater vertical
storage space shall not be acceptable for this project.
b.
The cable management system shall be integral to
the hoist system.
c.
The cable management system shall be UL LISTED.
d.
The flat cable shall meet the physical as well as
thermal requirements of UL for 20 amp loads. Up to
four flat cables may be fed from each end of the
distribution system to provide power for 24 circuits
from each end of the system for a maximum of 48
circuits total.
e.
Each flat cable shall include one ground wire and one
data cable plus an individually insulated hot and an
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
University of Georgia
RCE 2013029
individually insulated neutral conductor for each of six
120 Volt 20 Amp circuits.
f.
The connector strip shall be built to the length
specified with outlets or pigtails located as specified
or as shown on the construction drawings. Outlets or
plugs shall be 15 amp grounded pin connectors, 15
amp twistlock connectors, or 15 amps Edison plugs.
The distro trough may also contain connectors for
Ethernet and/or DMX connections.
g.
Flat cable shall pass through a strain relief before
entering a termination box at the designated end of
the raceway. Within the raceway all wiring shall be
attached at the factory to a terminal block. The flat
cable, internal wiring and all components shall meet
UL requirements and appropriate National Electrical
Codes (NEC).
h.
Cable management systems that utilize cable cradles,
cable reels or locate feeder or data cables outside the
off stage edges of the electrics batten shall not be
acceptable for this project.
i.
Hoisting systems utilizing cable management systems
from third-party vendors shall be fully integrated into
the hoisting system without additional structural
changes or changes to the QuickTouch controller.
Electrics line set hoisting systems that do not fully
integrate cable management in the hoisting system
and controller shall not be acceptable for this
installation. Cable management systems that are not
UL LISTED shall not be accepted for this installation.
PANTOGRAPH CABLE MANAGEMENT FOR ELECTRICS
1.
The load circuits and data wiring shall be fed to the
distribution trough by one or more UL Listed Pantograph
cable management systems that are specifically designed
to interface with traditional stage distribution raceways. The
pantograph shall allow the cable trays, feeder cable and
data wiring to fold and store along the top of the connector
strip without imposing a direct physical load on the
connector strip.
2.
The pantograph shall consist of a series of 18 ga. ventilated
steel trays hinged to each other to allow the entire distance
of travel required by the batten, up to 50’. The hinges and
hinge attachment points shall be stiffened to prevent
distortion of the pantograph.
3.
The trays shall be connected to a moving trolley at the
compression tube that allows relief as the system moves
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
University of Georgia
RCE 2013029
slightly from side to side during ascent/descent of the
batten. At the bottom, the pantograph shall be attached to
a hinge point above the houselight or distribution trough in a
manner that imposes no additional physical load on those
assemblies. The flat cable in the trays shall exit the
pantograph and enter a termination box on the distro strip
where all electrical connections shall be made.
4.
The flat cable shall be UL LISTED.
5.
The pantograph shall support a double-high/double wide
stack of flat cable and shall allow the flat cable to bend at
each joint within required NEC bending radii.
6.
The trays shall hinge open/closed as the batten is
lowered/raised and shall not impede the movement of the
line set
7.
The trays shall be sufficiently stiff to support themselves and
the flat cable they carry. At no time shall the trays bow,
warp, sag or twist whether or not under load of the flat
cable.
8.
Flat cable in the pantograph tray shall never heat in excess
of the rated temperature maximum of the flat cable when all
circuits within the tray are loaded at maximum electrical
capacity.
9.
It shall be possible to provide power for up to sixteen 20 amp
circuits plus ground and data via each pantograph.
10. These cable management systems shall interface with the
circuit distribution trough with standard mechanical and
electrical hardware purpose designed for this assembly.
11. Hoisting systems utilizing cable management systems from
third-party vendors shall be fully integrated into the hoisting
system without additional custom hardware, changes to any
part of the pantograph or changes to the QuickTouch
controller.
12. Hoisting systems that do not fully integrate cable
management in the hoisting system and controller shall not
be acceptable for this installation.
TRADITIONAL CABLE MANAGEMENT FOR ELECTRICS
1.
Load circuits and data wiring shall be fed to a standard stage
distribution trough by multi-conductor SO cable supported
by cable cradles suspended from one of the Prodigy hoist
liftlines. The SO cable shall be held in place at the distro by
means of a dedicated strain relief assembly.
2.
Single or multiple multi-conductor SO cables and multiple
cable cradles can be suspended from a single liftline so
long as the Working Load Limit (WLL) of the liftline is not
exceeded.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
D.
2.18
CONNECTOR STRIP—DISTRO and HOUSELIGHT TROUGH
1.
A Houselight Trough shall be a formed sheet metal trough
made from 18 ga. Steel. The trough shall be reinforced with
12 ga. formed steel at each utilized fixture attachment point.
The trough shall enclose internal wiring to which fixture
wiring is terminated within the trough.
2.
The system may incorporate an internal barrier to permit
emergency circuit wiring in the same trough.
3.
The trough shall be powder coated.
4.
Circuit wiring shall be supplied to the trough via an ETC
Pantograph cable management system.
5.
Cable management shall utilize an ETC Prodigy pantograph
that allows up to sixteen line-voltage circuits, or a
combination of line–voltage and up to two emergency
circuits. Knockouts located 6” on-center are built into the
raceway. The knockouts permit installation of houselights
with canopy or stem mounts to attach directly to the
raceway. Up to 50 pounds may be suspended between
raceway supports.
6.
Pantograph cable management and houselight distribution is
UL LISTED for use with flat cable circuit distribution and
fixture mounting as described above.
7.
Houselight troughs are designed to be used without pipe
battens.
PIPE BATTEN
A.
B.
C.
2.19
University of Georgia
RCE 2013029
The pipe batten shall be 1½” schedule 40 grade A, seamless pipe
fabricated in the largest possible lengths without splices. Battens of
greater length shall be spliced by means of .120 x 1 9/16 dia. DOM
tube 18” long with 9” of tube inserted into each half of the splice.
The tight fitting splice tube shall be held in place by a pair of 3/8 x 2
½” grade 5 hex bolts on each side of the joint. The bolts shall pass
through the pipe at an angle of 90° to each other. There shall be
two bolts on each side of the joint spaced 1” and 8” from the joint.
Alternatively, one pair of bolts on one side of the joint may be
replaced with either plug welds or tight fitting steel rivets. Pipes
shall be straight and painted flat black.
A safety-yellow batten cap shall be installed at each end of each
pipe batten.
The manufacturer shall provide up to four self-adhesive labels for
each batten on which the rated batten load shall be written by the
installer.
POWER AND CONTROL DISTRIBUTION (PCD)
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
A.
B.
C.
2.20
University of Georgia
RCE 2013029
Each hoist shall receive power and control via a pair of 8’-0” long
jumper cables extending from the Powerhead to the source outlets.
Receptacles shall be installed in a sheet metal junction box or
trough with outlets. Each outlet shall be located no more than 6’-0”
away from the rear face of each hoist.
Each Powerhead shall include a power cord hardwired to the hoist
with an appropriately sized twistlock connector at the PCD end and
a removable control cable with a circular 9 pin connector at each
end. Inclusion of a 20 amp 3 phase breaker in the PCD is optional.
The wiring and connectors shall be barriered between high and low
voltage.
The power/distribution channel shall be UL LISTED for this
application.
QUICKTOUCH+ FIXED AND VARIABLE SPEED CONTROL SYSTEM
A.
GENERAL
1.
The entire motor system shall be operated by a
QuickTouch+ fixed and variable speed controller. It shall be
purpose-designed and fabricated to manage and operate
motors specifically designed for overhead lifting. Each
system shall incorporate mechanical, electrical and safety
features that shall be inherent to this equipment and shall
provide an engineered, efficient device to control the
equipment. The mechanical, electrical and safety features
of this control system shall establish the standard of quality,
performance and safety by which motor systems of other
manufacture shall be evaluated.
2.
The QuickTouch+ Control System shall consist of a surface,
flush or rack mounted primary control panel and up to three
remote E-stop stations.
3.
The motor system shall also include one Fixed Speed
Remote control device with 30’ of flexible cable that may be
attached to the system at the QuickTouch+ control panel.
4.
The controller shall include the following features:
a.
Key operated power switch
b.
LCD display for feedback/operating information
c.
Key operated motor load profile training/enable switch
d.
Latching motor selection buttons with rear illuminated
naming tabs
e.
Rear illuminated hold-to-operate (dead-man) up and
down operation buttons
f.
Recessed speed adjustment slide-pot
g.
Rotary data entry encoder
h.
Dedicated E-stop button
i.
Outlet for wired remote
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
C.
D.
University of Georgia
RCE 2013029
j.
Optional door
k.
Optional rack mount kit
5.
The control system shall only employ the QuickTouch+
controller, a power and control distribution infrastructure and
the motors. A System that requires separate drive cabinets
or motor-starters shall not be acceptable.
6.
The controller shall be UL LISTED and shall be fabricated
from UL LISTED components.
ENCLOSURE
1.
The back box and face panel shall be fabricated from 16ga
powder coated sheet steel specially formed to provide
support for installation as well as support for all components
installed within the housing.
2.
The QuickTouch+ face panel shall be printed with complete
labeling information to identify the function of each of the
buttons in the control station.
3.
The face panel shall identify the system as a QuickTouch+
controller for stage rigging.
4.
The face panel shall be shades of grey. The ring surrounding
the E-stop button shall be safety yellow and shall be rear
illuminated
5.
The steel panel to which all switches are mounted shall be
removable via screws in the surface located underneath the
face panel film.
LCD SCREEN
1.
The liquid crystal display shall be purpose designed to
communicate all information in human readable text.
2.
The screen shall be rear illuminated and shall be dimmable.
3.
During system start up the screen shall show the progress of
the motor diagnostics self-tests. Upon completion of the
startup sequence the screen shall indicate that the system
is “OK” or shall provide specific information should a fault be
detected. Fault conditions shall be reported in human
readable text. Systems that report fault conditions in a
series of blinking lights shall not be acceptable for this
installation.
4.
When a motor is selected the LCD screen shall readout the
motor name and number, the current batten position above
the floor, the amount of weight suspended from the batten,
the trim position that is recorded, as well as two bar graph
scales that show the current position of the batten, top and
bottom limits and the current weight suspended from the
batten.
MOTOR SELECTION/OPERATION BUTTONS
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.
E.
F.
G.
University of Georgia
RCE 2013029
There shall be rear illuminated motor selection buttons.
Buttons shall remain illuminated until de-selected.
2.
Up to four motors may be selected to move at one time.
When the up or down button is pushed and held, each
motor shall move to its next stop location. If the stop
location is the adjustable trim position, the motor can be
made to continue to travel in the selected direction by
releasing and re-pressing the up or down hold-to-operate
button until the next stop for the motor(s) is reached.
3.
A maximum of four motors may move at one time and only in
one direction at a time.
4.
Although four motors moving at one time is the factory
default, it shall be possible to increase the quantity of
simultaneously moving motors to eight or reduce it to one.
5.
The system software will limit the number of simultaneous
moving motors. As a backup, there shall be dedicated
hardware to detect and disable the system if the system
attempts to move more than the configured maximum
quantity of motors.
6.
All buttons shall fit neatly within each of the cover panel
cutouts on the controller.
KEY SWITCHES
1.
A key switch shall control power to the control system. The
key must be in the lock and the key turned to the on
position for the motor system to operate.
2.
A separate key is required to turn on the load profiling
system. That key must be in the lock and turned to the “ON”
position for load profiling to function.
3.
When load profiling is turned on the motor shall know the
amount of weight that is supposed to be supported by the
batten at any location in the path of travel. Should the
weight exceed or be reduced below the profiled weight by a
preset value, the motor shall stop operation until the fault is
cleared.
SLACK LINE DETECTOR
1.
The slack line detector is located in the Powerhead. When a
slack line condition occurs, it shall cease motor movement
and result in a fault message on the LCD screen on the
controller. Movement in the upward direction shall be
possible to clear the fault.
E-STOP
1.
The E-stop button on the QuickTouch controller shall be a
mushroom button with a rear illuminated ring surrounding
the button. During normal operation the E-stop button shall
be in the out position. An E-stop can be activated via this
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
H.
I.
University of Georgia
RCE 2013029
button by firmly pressing the button in. The button shall
latch and immediately cause a class zero stop of all fixed
speed motors and a class one stop of all variable speed
motors in the system. The LCD screen shall report this as
an E-stop condition. To continue system operation the Estop button must be cleared by twisting the button to
release the latch. Power to the control station must be
cycled off/on to re-initiate the system. This action shall also
initiate a self-test of the entire control system and
contactors.
2.
The illuminated ring around each E-stop button shall be
dimmable. The status of the lighted ring shall provide
additional information about the state of the system as
follows:
a.
Ring at low intensity: no motor moving
b.
Ring at high intensity: motor(s) moving
c.
Ring blinking: system in E-stop condition
3.
Up to three remote E-stop stations may be connected to the
system. Each additional E-stop station shall operate in the
same way as the primary E-stop at the QuickTouch control
panel.
SYSTEM DIAGNOSTICS
1.
Upon energization the control system shall perform an
automatic series of diagnostic tests that assure that all
system safety functions are working. Should an error in the
safety functions be determined, the controller shall report
back a fault condition in the LCD display window and shall
identify the nature of the fault.
2.
Monthly, the system automatically shall perform an
additional series of diagnostic tests to determine if there are
any problems with any portion of the motor control system
safety features. In the event of a problem, the controller
shall report back a fault condition in the LCD display
window and shall identify the nature of the fault.
3.
Eleven months after a system inspection has been
performed, the system shall remind the user to schedule a
full system maintenance/inspection. The reminder shall
remain in the system with a count-down calendar until it is
turned off by the factory authorized and trained inspector.
4.
The installing contractor shall be able to leave contact
information within the system. This information shall be
displayed at power up and in the event of severe fault
conditions.
REMOTE CONTROL PENDANT
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
An optional remote control pendant with 30’ long attached
cable and plug shall be provided for the system. The remote
control must be plugged to the QuickTouch control panel.
When the remote control is plugged in the E-stop on the
remote is active. Systems requiring “shunt plugs” to bypass
an unplugged remote control connector shall not be
acceptable.
2.
The remote control provides up/down control for those
motors that have been preselected at the QuickTouch
controller.
TRIM POSITIONS
1.
It shall be possible easily to store (and delete) up to five (5)
Trim positions per motor
2.
The user shall be able to utilize three of these positions as
general purpose trim positions, one as user programmable
upper limit and one as user programmable lower limit
3.
During normal operation, the hoist shall stop at every trim
position, but it shall also be possible to select a specific trim
position as the target position for the next move.
SPEED CONTROL
1.
The motor controller shall provide a recessed speed
adjustment slider
2.
It shall be possible to adjust the speed of a running variable
speed motor via this slider. During movement the LCD
screen shall show the actual speed of the selected motor
3.
It shall be possible to pre-set the speed for the next move for
the selected motors. The LCD screen shall display the preset speed for the selected motors.
SYSTEM COMMISSIONING
1.
It shall be possible to commission basic functionality of the
system without a laptop computer or additional software.
2.
A trained installer shall commission the full system via a
laptop computer connected via the built-in USB port in the
controller. USB connectivity shall not require special USB
drivers.
3.
Commissioning software shall feature an inspection report
generator that allows a step by step inspection of the
control system. Upon completion, the system shall
generate an inspection report in PDF format.
1.
J.
K.
L.
University of Georgia
RCE 2013029
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.
University of Georgia
RCE 2013029
EXECUTION
3.1
GENERAL
A.
B.
C.
D.
Installation of this equipment shall only be performed by ETC
approved and factory trained theatrical rigging installers.
Installation shall be performed in a workmanlike manner and shall
strictly adhere to the standards of these specifications and ETC’s
installation requirements. Where necessary, the installer may
make adjustments to accommodate unforeseen impediments to
installation. The completed work must achieve all electrical, safety
and appearance requirements as established in these
specifications.
Work shall be performed in accordance with OSHA and local
codes.
On site welding shall only be performed per AWS D1.1 standards
and with advanced approval from the architect or Owner’s
representative.
DIVISION OF RESPONSIBILITIES
1.
The RIGGING contractor shall be responsible for providing
and installing:
a.
Powerhead
b.
Compression Tube, Compression Tube splices and
Compression Tube beam clamps
c.
Supplementary steel and/or mounting adapters for the
hoisting systems, if required.
d.
Loft blocks
e.
Wire rope lift lines and terminations
f.
On electrics line sets: Cable Management system for
distribution raceways, including low-voltage, ground
and data wiring
g.
On electrics line sets: Factory prewired electrical
termination boxes that are part of the cable
management system.
h.
On electrics line sets: Factory prewired distribution
raceway mounted at the bottom of the wire rope on
the stage electrics sets
i.
Pipe batten attached to RACAs or Hanger Brackets
j.
Batten end caps
k.
Batten labels
l.
Attachment of the prewired twist-lock connector to the
Power and Control Distribution outlet
m.
Attachment of the prewired circular pin connector data
wire to the mating outlet on the Powerhead and on
the Power and Control Distribution box
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
n.
2.
4.
Termination of the low voltage data wiring at the
controller and at all power and control distribution
boxes and at each E-stop station
o.
Face plates for all Control Stations, E-stop Stations
and Power and Control Distribution Boxes
p.
Set limit switches
The ELECTRICAL contractor shall be responsible for
providing and installing:
a.
All pipe, wiring and termination providing line voltage
to all the Power and Control Distribution boxes
b.
All pipe and wiring connecting data lines between the
first Power and Control Distribution Box and the
Control station
c.
Pipe and wiring connecting data lines between
Control Station and first E-Stop Station
d.
All pipe and wiring connecting data lines between all
E-Stop Stations.
e.
Back boxes for all Power and Control Distribution
Boxes, the Control Stations and all E-Stop Stations.
f.
All pipe and wiring and all terminations of line voltage
of dimmed and non-dimmed circuits that terminate at
the termination boxes mounted on/near the
Compression Tube.
INSTALLATION
4.1
GENERAL
A.
B.
C.
D.
Installation of this equipment shall only be performed by ETC
approved and factory trained theatrical rigging installers.
Installation shall be performed in a workmanlike manner and shall
strictly adhere to the standards of these specifications and ETC’s
installation requirements. Where necessary, the installer may
make adjustments to accommodate unforeseen impediments to
installation. The completed work must achieve all electrical, safety
and appearance requirements as established in these
specifications.
Work shall be performed in accordance with OSHA and local
codes.
On site welding shall only be performed per AWS D1.1 standards
and with advanced approval from the architect or Owner’s
representative.
DIVISION OF RESPONSIBILITIES
1.
The RIGGING contractor shall be responsible for providing
and installing:
a.
Powerhead
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
b.
2.
University of Georgia
RCE 2013029
Compression Tube, Compression Tube splices and
Compression Tube beam clamps
c.
Supplementary steel and/or mounting adapters for the
hoisting systems, if required
d.
Loft blocks
e.
Wire rope lift lines and terminations
f.
On electrics line sets: Cable Management system for
distribution raceways, including low-voltage, ground
and data wiring
g.
On electrics line sets: Factory prewired electrical
termination boxes that are part of the cable
management system.
h.
On electrics line sets: Factory prewired distribution
raceway mounted at the bottom of the wire rope on
the stage electrics sets
i.
Pipe batten attached to RACAs or Hanger Brackets
j.
Batten end caps
k.
Batten labels
l.
Attachment of the prewired twist-lock connector to the
Power and Control Distribution outlet
m.
Attachment of the prewired circular pin connector data
wire to the mating outlet on the Powerhead and on
the Power and Control Distribution box
n.
Termination of the low voltage data wiring at the
controller and at all power and control distribution
boxes and at each E-stop station
o.
Face plates for all Control Stations, E-stop Stations
and Power and Control Distribution Boxes
p.
Set limit switches
The ELECTRICAL contractor shall be responsible for
providing and installing:
a.
All pipe, wiring and termination providing line voltage
to all the Power and Control Distribution boxes
b.
All pipe and wiring connecting data lines between the
first Power and Control Distribution Box and the
Control station
c.
Pipe and wiring connecting data lines between
Control Station and first E-Stop Station
d.
All pipe and wiring connecting data lines between all
E-Stop Stations
e.
Back boxes for all Power and Control Distribution
Boxes, the Control Stations and all E-Stop Stations
f.
All pipe and wiring and all terminations of line voltage
of dimmed and non-dimmed circuits that terminate at
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
the termination boxes mounted on/near the
Compression Tube.
4.2
STAGE DIMMING AND CONTROL SYSTEM
A.
Electrical requirements of the Stage Equipment Contractor: The
Stage Equipment Contractor shall be responsible for providing to
the electrical contractor all stage lighting and dimming hardware as
specifically detailed in these specifications. This shall include:
1.
Furnishing all equipment specified.
2.
Hanging of connector strips on specified stage rigging
hardware.
3.
Set-up of the control console.
4.
Demonstration of equipment to owner's representatives.
5.
Lamping & Hanging all stage lighting fixtures.
6.
All low voltage lighting control terminations.
The Stage Equipment Contractor shall not be responsible for the following work; to be
performed by the electrical contractor.:
Any conduit
Any wiring
Power requirements and termination of same in dimmer rack
Any load wiring, fixtures, or termination at fixtures for house lighting or emergency
lighting
Mounting of plugboxes, floor pockets, back boxes and gridiron junction boxes (locations
to be coordinated with stage equipment contractor)
B.
FACTORY CHECK-OUT: This contract shall also include the
services of a qualified engineer regularly employed by the
manufacturer of the system who shall check the installation and
ensure its proper operation. No part of the system shall be
energized before being so checked and the installation approved.
Failure to observe this provision shall automatically relieve the
manufacturer of any responsibility concerning the proper operation
of the system or any part thereof and the replacement of parts
which may have been damaged by the premature energizing. This
engineer shall be made promptly available on the job site within
fourteen (14) days after the manufacturer has received written
notice.
4.3
DIMMER RACKS
A.
B.
The installation rack shall be the Sensor as manufactured by
Electronic Theatre Controls, Inc., or equal. The fully digital dimmer
rack shall consist of up to 48 dimmer module spaces. Sensor rack
systems shall be UL Listed and CSA Approved, and shall be so
labeled when delivered to job site.
The dimmer rack shall be provided with wired spaces for all circuits.
Dimmers shall be provided for all base circuits and blank modules
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
4.4
University of Georgia
RCE 2013029
provided for all expansion circuits. Provide base circuits indicated in
bill of materials.
The dimmer racks shall house all dimmer modules, control
electronics, and branch circuit breakers. Provide module and
breaker quantities as indicated below. System shall have the
performance features that follow.
1.
Rack shall be UL Listed and labeled.
2.
Rack shall employ dead front construction of code gage
steel.
3.
Each rack must have a hinged locking door.
4.
Each rack must have an electrostatic air filter.
5.
Ventilation shall be by a low-noise fan activated by DMX
level data.
6.
In the event of an over-temperature situation, each dimmer
shall be shut down independently as required. Systems
that shut the entire rack down upon over-temp will not be
accepted.
7.
Each 48-module dimmer rack shall be provided with a
keypad and LCD display for rack configuration, backup and
fault indication.
8.
Each rack shall maintain active scene for a userprogrammable period after loss of DMX-512 signal from
console.
9.
Standard control format shall be USITT DMX-512. Dimmer
rack CEM must accept two independent DMX signals
concurrently in a highest-takes-precedence manner for
each dimmer.
10. Rack shall store a minimum of thirty-two user-programmable
back-up looks which may be activated in case of loss of
control signal.
11. Each dimmer must include discrete "boost" feature to allow
over-voltage output to compensate for voltage drop in
branch wiring and allow a true 120 volts at the fixture lamp
or “trim” maximum voltage output to lengthen lamp life.
12. Each rack shall include a beacon which shall flash to
indicate failures.
DIMMER MODULES
A.
B.
Dimmer modules shall be plug-in type. No more than two dimmers
per module will be accepted.
Modules shall be assembled of aluminum or steel. Dimmer
modules with housings manufactured of plastic or a flammable
material will not be accepted.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
D.
E.
F.
G.
H.
I.
J.
4.5
University of Georgia
RCE 2013029
Each dimmer module shall contain fully magnetic circuit
breakers(s), solid state switching module(s), choke(s) and
connectors.
Each dimmer must have the discreet capability to operate in a
dimmed or a non-dimmed mode. This function shall be selectable
from the control console or the rack-mounted keypad.
Each dimmer circuit shall use solid state switching devices
consisting of two silicon controlled rectifiers in an inverse parallel
configuration, snubber network and all required gating circuitry on
the high voltage side of an integral opto-coupled control voltage
isolator.
Dimmer modules shall include toroidal filters to reduce lamp
filament sing and limit the radio frequency interference on line and
load conductors. The current rise-time shall be not less than 500
microseconds measured at 90-degree conduction angle from 1090% of the output wave-form with the dimmer operating at rated
load.
Power efficiency shall be at least 97% at full load.
Dimmer shall accept hot-patching of an incandescent load up to the
full capacity of the dimmer.
Dimmer output shall be regulated for incoming line voltage
variations, except that the output voltage cannot be increased
above a level equal to line voltage less dimmer insertion drop. Line
regulation shall be +/- 1V over a 90-140 volt range for changes up
to 10%. Load regulation shall be +/- 2V for 1-100% of rated
current. Dimmers shall employ a scheme for compensation for
harmonic distortion of the power line for any variation in load.
Response to control shall be less than 25 milliseconds.
DIMMER FEEDBACK SYSTEM
A.
B.
C.
D.
E.
F.
Rack shall be provided with a feedback network to provide rack
performance data to the control console. The network shall provide
operational information, which shall be displayed on the rackmounted LCD display and on the control console color monitor. A
hand-held remote does not meet this requirement.
System shall annunciate DMX port errors at the rack and control
console.
System shall annunciate backup cue errors at the rack and control
console..
System shall annunciate individual phase voltages and power
frequency at the rack and control console.
System shall annunciate control link address and recorded error log
status indicators at the rack and control console.
System shall annunciate panic status at the rack and control
console.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
G.
H.
4.6
University of Georgia
RCE 2013029
System shall annunciate airflow obstruction errors at the rack and
control console.
System shall monitor cabinet temperature and annunciate overtemperature at the rack and control console.
CONTROL ELECTRONICS MODULE
A.
B.
General
1.
The dimmer rack electronics shall be contained in one
plug-in Control Electronics Module (CEM+). Each CEM+
shall plug into a dimming cabinet, with no discrete wire
connections. A simple User interface shall be provided for
system configuration, testing and diagnostics. There shall
only be one model for all rack types.
Electronics
1.
The CEM+ shall be provided with an Ethernet control signal
input. This input shall be fully configurable with a range of
patching and priority programming capabilities.
2.
Two optically isolated DMX512 inputs shall also be provided,
allowing overlapping or separation of any control level.
2,500V of optical isolation shall be provided between the
DMX512 inputs and the CEM+. This shall protect the
DMX512 inputs from a failed control module and the CEM+
from failed DMX512 inputs. Systems that do not have
optical isolation on a prewired factory plug-in device shall
not be acceptable.
3.
The CEM+ shall be completely digital, without employing any
digital-to-analog de-multiplexing schemes or analog
ramping circuits.
a.
In the event of data loss each rack shall maintain the
last level for a user-programmable time of zero to five
minutes or indefinitely, or may be programmed to fade
to and play an emergency preset. Systems that do not
offer this feature shall not be acceptable.
4.
The CEM+ shall respond to control changes in less than 25
milliseconds. Dimmer outputs shall exhibit no oscillating or
hunting for levels. Dimmers set to the same level shall
output within ±1V of each other, regardless of phase or
electronic module control.
5.
Dimmer output shall be regulated for incoming line voltages.
The regulation shall adjust for both RMS voltage changes
and deformations in the incoming AC waveform. The CEM+
shall monitor and adjust each dimmer's output to maintain a
constant power to the load. Regulation shall maintain the
desired output voltage ±1V for the entire operating range
(90-140V AC) with the exception that the maximum output
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
University of Georgia
RCE 2013029
will be no greater than the line voltage minus dimmer
insulation loss. The regulation shall compensate for dips
and anomalies in the AC waveform on a dimmer-by-dimmer
basis. There shall be no interaction between dimmers in the
system or any other equipment. The output shall be
nominally regulated to 120V, but shall be field adjustable on
a dimmer-by-dimmer basis to allow for varying cable length.
6.
The entire response to incoming line changes shall take no
more than 25 milliseconds. Dimming systems that do not
respond to line fluctuations and do not contain wave
deformation detection shall not be acceptable.
7.
The CEM+ shall contain diagnostic routines to allow the user
to test and troubleshoot the system. The CEM+ shall
contain a Test/Bypass switch to turn all dimmers on to full
for testing. This switch shall bypass all electronics and shall
force the fan on.
8.
A system-wide panic circuit shall be provided. Any dimmer in
any rack may be assigned to the panic circuit.
9.
The CEM+ shall be able to record up to 128 backup looks.
Backup looks shall be programmable by recording current
dimmer levels (as set by the console), by entering dimmer
levels on the CEM+ directly, or a combination of both
methods. When a backup look is active, the DMX512 inputs
shall be ignored in the default priority mode.
10. All system functions may be activated by the CEM+'s user
interface and shall not require any remote unit. Systems
that do not offer this feature shall not be acceptable.
11. The CEM+ shall be able to configure dimmers for ETC
Dimmer Doubling, which allows a single dimmer to set two
different levels on one dimmer circuit by splitting the AC
power into positive and negative halves.
User Interface
1.
A backlit 6-button keypad and 2-line-by-20-character backlit
LCD shall be provided for system configuration, testing and
diagnostics. The backlit design of the panel controls shall
provide for ease of use in dark environments.
a.
The six buttons shall be Accept, Back, Plus, Minus,
Home and Test.
2.
The front panel shall have four status LED indicators: a blue
LED for power status and three green LEDs for Network,
DMX A, and DMX B status.
3.
A reset switch shall also be located on the front of the unit.
4.
Menu functions:
a.
DMXA/B or EDMX data may be assigned sequentially
from a starting control channel (base addressing) or
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
b.
c.
d.
e.
f.
g.
h.
University of Georgia
RCE 2013029
patched per control channel to any dimmer via the
user interface.
The dimmer curve shall be capable of being set on a
per-channel basis. The default curve shall be the IES
modified square law. Additional curves include:
Square Law, Linear, and Sensor v2.0. The CEM+
shall also have the capability of storing up to three
custom curves and shall have an adjustable Preheat,
all assignable on a per dimmer basis.
The dimmer mode shall also be capable of being set
on a per-channel basis. Modes shall include: Normal,
Dimmer Doubled, Switched (unregulated on/off with
adjustable threshold), or Fluorescent with adjustable
threshold.
DMX Loss behavior can be set to Hold Last look, Wait
and Fade, or Fade to Preset.
Up to 128 presets may be programmed, recording
any level, whether set in direct level menu or by a
Data input. Presets shall be activated in the default
fade time of 2 seconds.
The direct level menu shall provide the ability to set a
dimmer or groups of dimmers to a level.
The CEM+ shall be capable of monitoring and
displaying [LCD] incoming line voltage for all three
phases. With installed current sensors the same
display shall show amperage on each phase. This
display shall not timeout.
English, French, German and Spanish language
support shall be built in.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
5.
D.
University of Georgia
RCE 2013029
The CEM+ shall contain the following user displays:
a.
Status display to show rack identification and errors.
Error Messages shall include, but not be limited to,
the following:
1)
Dimmer has shut down due to over
temperature
2)
DMX port A or B has an error or has failed
3)
Phase A, B or C is below 90 volts
4)
Phase A, B or C is above 140 volts
5)
Rack has shut down due to air flow loss
6)
Ambient temperature is below 0°C/32°F
7)
Ambient temperature is above 40°C/104°F
b.
Rack has shut down - ambient temperature exceeds
46°C/115°F
c.
The ability to program and activate system-wide
backup looks from face panel or web User Interface.
d.
About display shall allow monitoring of system, rack
or dimmer status.
1)
About System shall provide information about
Panic circuits, Preset looks, and System name.
2)
About Network shall provide IP address,
gateway and net mask.
3)
About Rack General shall provide information
about rack name, ambient temperature, air
filters and rack type.
4)
About Rack Power shall provide information
about power type, rack voltages, current per
phase (only with current transformers), under
voltage warnings.
5)
About Rack Data shall provide status for
DMXA, DMXB, EDMX and Network activity.
6)
About Dimmer shall provide information about
dimmer type, location, output level, control
source, scale voltage, mode and curve.
e.
Setup display shall allow but not be limited to,
configuring of rack addresses, dimmer firing mode,
and scale voltage values.
Dimmer Status Network
1.
The Dimmer Status network shall provide remote monitoring,
programming and backup functions for the system through
any Sensor-compatible console, PC, or hand-held remote
device. System information shall also be displayed on any
system interface including the CEM+ and the devices listed
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
E.
F.
University of Georgia
RCE 2013029
above. Systems that do not provide both types of user
interface shall not be acceptable.
2.
Dimmer Status network shall provide an integral link to
connect all racks in the system for rack-to-rack
communication. Information for all configuration and backup
looks shall be stored in all CEM+’s to allow swapping of
CEM+’s throughout the system. Systems not storing all
configuration data and backup looks for each dimmer in all
control modules shall not be acceptable.
3.
A technician shall be able to program all parameters onsite,
using a laptop personal computer. These parameters shall
include, but not be limited to, defining rack type, module
type, scale voltage for each dimmer, firing mode, curve,
dimmer numbering and DMX512 port assignments.
Systems requiring factory programming shall not be
acceptable.
Advanced Features
1.
Sensor's Advanced Features (AF) option shall add an
additional sensor in the individual dimmer modules. The AF
option shall allow monitoring of current and output voltage
on a dimmer-by-dimmer basis and provide information on
lamp burnouts, dimmer status, and input voltages.
2.
The CEM+ shall allow the user to record the loads of all AF
dimmers in the system. The CEM+ shall, during operation,
test each AF dimmer, determine its load, and compare it to
the recorded load. Any change from recorded loads greater
than five percent shall display an error on the CEM+ and
any monitoring device on the ETCLink network.
Physical
1.
Dimmer control electronics shall be contained in one plug-in
Control Electronics Module, housed in a formed steel body
with an injection-molded face panel.
2.
An airflow sensor shall be provided. In the event of
inadequate airflow, the affected rack shall shut down until
the error is corrected.
3.
If the ambient room temperature drops below 0°C/32°F or
rises above 40°C/104°F, a warning shall appear on the
dimmer rack LCD. If the temperature rises above
46°C/115°F, the rack shall shut down until the condition is
corrected.
4.
Dimmer control electronics module shall operate at up to
120/208V, three phase, four wire + ground, 47 to 63 Hz.
The CEM+ shall automatically compensate for frequency
variations during operation.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4.7
University of Georgia
RCE 2013029
LIGHTING SYSTEM AND ACCESSORIES
A.
General
1.
The lighting control desk shall be a microprocessor-based
system specifically designed to provide complete control of
stage, studio, and entertainment lighting systems. The
device shall be the Ion as manufactured by Electronic
Theatre Controls, Inc., or equal.
2.
The system shall provide control of 1024 outputs, 1536
outputs, 2048 outputs, 2560 outputs or 3072 outputs on a
maximum of 10,000 control channels, patched across any
number up to 99,999. Output shall be distributed over a
10/100MB Ethernet network using Net3/ACN, ETCNet 2,
Avab and/or ArtNet protocols. The user shall be able to
control the application of protocols at an individual address
level.
3.
The system shall support full bi-directional RDM
communication with compatible devices via Net3 DMX/RDM
Gateways. RDM communication shall adhere to ANSII
standard E1.20-2006 Entertainment Technology – RDM –
Remote Device Management Over DMX512 Networks.
Supported RDM features shall include:
a.
Discovery and identification of RDM capable devices
b.
Setting of start addresses, operating modes and
additional settings as exposed by connected devices
and controllable via RDM
c.
Viewing of Sensor data as provided by connected
devices.
d.
Error reported as provided by connected devices.
4.
A maximum of 10,000 cues, 999 cue lists, 1000 groups,
1000 presets, 4 x 1000 palettes (Intensity, Focus, Color and
Beam), 1000 effects, 1000 macros and 100 curves may be
contained in non-volatile electronic memory and stored to
an onboard hard drive or to any USB storage device.
5.
Recorded cue lists may be played back simultaneously on a
maximum of 200 faders. Channels shall respond to cue
information by last instruction with discrete rate control
provided for all cues. The desk may be placed in Tracking
or Cue Only mode by the user as a system default and
overridden on individual record actions as required.
HTP/LTP intensity flags, assert, proportional, intensity
master or manual master fade control and independent
status may be placed on each cue list. It shall also be
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
6.
7.
8.
9.
10.
11.
12.
13.
University of Georgia
RCE 2013029
possible for a cue list to contribute to playback background
states or to withhold such contributions.
A Master Playback fader pair and dedicated Grand
Master/Blackout shall be provided.
Up to six USB fader wings may be connected to the desk, for
a maximum of 300 submasters and/or 200 playback faders.
USB fader wings may be rigidly connected to the main desk
to provide a "single connected unit" with no external cables
required. The wings also may be connected via USB cables
and used "on the side." Virtual fader control is also
provided.
A high-resolution level wheel shall be provided to control
intensity for selected channels and scrolling within selected
displays. Four page-able high-resolution encoders shall be
provided for control of non-intensity parameters. Nonintensity encoders may be operated in coarse or fine mode,
with the amount of movement per revolution of the
encoders in coarse mode definable by the user. Nonintensity parameters shall be controllable via the encoders
or keypad controls, without need of an external pointing
device. A high-resolution rate wheel shall also be provided.
Rotary encoders for non-intensity parameters shall be
labeled by means of an integral LCD display mounted
below the encoders on the main desk. The display shall
show the currently loaded functions of the encoders based
on the current selections. Systems using encoders with no
LCD labeling shall not be acceptable.
Control and programming features for automated fixtures
shall also include: a standard library of fixture profiles, the
ability to copy and edit existing profiles and create new
profiles, patch displays including channel and output
addressing, 16-bit fade resolution, color characterization
allowing color mixing and storing in Hue and Saturation or
native device values.
System information, including playback status, live output
and blind values for all record targets shall be displayed on
a maximum of two external high resolution DVI monitors, or
one SVGA monitor, which may also be touch-screen(s).
Only one display shall be required for operation.
A context sensitive on-line Help feature shall explain and
provide an example of the operation of each feature of the
system.
A fully integrated Virtual Media Server feature shall allow the
user to map images and animations to a rig array. 40 such
maps may be created, each with 12 layers. Systems that
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
14.
15.
16.
17.
18.
19.
20.
University of Georgia
RCE 2013029
rely on external hardware or software for this functionality
shall not be acceptable.
User-definable, interactive displays may be created. These
displays, which can be used in live and blind operating
modes, allow graphical layout of channels, desk buttons
and programming tools. Standard symbols are provided,
and the user may import his own symbols or graphics.
Each symbol may be individually defined with data
feedback characteristics. Non-interactive status
information, such as a mirror of other user’s command lines,
may also be included in the display. A graphical browser is
provided for fast selection of these views. Multiple zoom
factors and placements may be stored and recalled for each
display.
An optional, full-functioning, detachable alphanumeric
keyboard shall be supported. The keyboard shall allow
labeling of channels, cues, presets, groups, palettes,
effects, macros, curves and the show. An integral electronic
keyboard shall be provided.
A row of softkeys shall be provided, which change function
based on the selection and context of the desk. These
softkeys shall be labeled via an adjacent LCD display that
shows their current functions at all times. Systems using
softkeys with no LCD display shall not be acceptable.
Software upgrades shall be made by the user via a USB
port; changing internal components shall not be required. It
shall be possible to install software updates in all consoles,
processor units and remotes from one device over the
network.
The operating software shall be loaded into program
execution memory from the internal hard drive when the
console is powered. In the event of an uncontrolled
shutdown, the device shall return to its last output state
when power is restored.
Dimmer monitoring and configuration features shall be
provided (in conjunction with ETC’s Sensor+, Sensor 3 or
FDX dimming systems) to allow indication of dimming
system status, dimmer load monitoring and show specific
configurations.
Show data may be created and modified on a personal
computer, using either Windows XP or Windows 7 operating
systems, with a free offline editing application. The offline
editor may also run natively on Intel-based Macintosh
platforms using OS X. The program shall also allow output
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
21.
22.
23.
24.
25.
26.
University of Georgia
RCE 2013029
to visualization software supporting the same protocols as
the lighting system.
A PC using Windows XP or Windows 7/8 or an Intel-based
Macintosh computer using OS X running a client software
application shall be able to connect to a control system via
the network and view or modify current show data in an
independent display environment, using an Eos Family
Client Dongle. When connected without the dongle, the
computer shall operate in Mirror Mode, with the device to be
mirrored selectable by the user. Systems that do not
provide client software that may run natively on the Apple
platform in this environment shall not be acceptable.
Synchronized backup shall be provided via another full desk
on the network or by use of a remote processor unit. The
backup unit (either full desk or rack mounted Remote
Processor Unit (RPU) shall maintain synchronized playback
with the master and shall take over control of the lighting
system upon loss of communication with the master. Use of
two RPUs to service and backup system output is also
supported. Systems that do not offer this kind of instant
backup from multiple sources shall not be acceptable.
A maximum of four users may access and interact with show
data simultaneously. Each user shall have an individual
workspace and channel partitioning shall be supported.
User identification may be assigned to more than one
control device, allowing users to work in tandem, or allowing
a designer/ALD to mirror the current display format, mode
and command line of the associated programmer.
Partitioned control allows discrete control of
channel/parameter groupings by user. Partitioned control
may be easily enabled and disabled with no need to merge
show data from multiple users.
Mirror mode shall allow the desk displays and operating
modes to be mimicked on another connected device.
Alternatively, the desk may mirror another device.
The system shall allow remote control from external devices
as follows: Client software running on a PC connected to
the network, a remote video interface with keyboard, a
purpose-built wireless remote focus unit (Radio Focus
Remote). Universal fader wings may be attached to any of
these devices for local fader control. Systems without these
remote control devices shall not be acceptable.
The system shall support a Telephone remote control that
allows basic functions to be controlled from a standard
wireless phone producing touch-tone signals. This allows
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
University of Georgia
RCE 2013029
the use of a standard telephone for a low cost remote
control. Systems that do not allow this function shall not be
acceptable.
27. Show data may be created and modified on a personal
computer, using either Windows XP or Windows 7/8
operating systems, with a free offline editing application.
The offline editor may also run natively on Intel-based
Macintosh platforms using OS X. The program shall also
allow output to visualization software supporting the same
protocols as the lighting system.
28. The system shall support up to 32 individual Time Code
Event lists.
Controls and Playback
1.
Manual Control and Programming Section
a.
The programming keyboard shall be grouped by
function. Major groupings shall be record target
functions, numeric keys, level assignment functions,
display navigation functions and controls.
b.
Non-intensity parameters may be set numerically or
via the encoders. This control shall be fully
interactive. In either case the current parameter value
shall be displayed on the desk monitor and
simultaneously on the integral LCD display. Systems
using only a local LCD or only a video monitor shall
not be acceptable.
c.
Only those parameters available for control in the
active lighting system shall be displayed for control.
d.
Lamp controls provide direct access to luminaire
functions such as striking and dousing arc lamps and
calibrating entire fixtures or individual mechanisms of
fixtures, as provided by the luminaire manufacturer.
User access to these features is normalized across all
manufacturers for ease of use. Use of a “control
channel” for accessing these functions shall not be
required and systems requiring use of a control
channel shall not be acceptable. Lamp control
commands maybe e staged, and channels which
have been sent lamp on commands so indicated in
live.
e.
Fan functions shall be provided both via command
line operation and through encoder controls.
f.
Highlight shall be supported, with user definable
highlight values. Lowlight conditions may be defined
for selected, but not specified channels. Rem Dim
command, at specific levels by channel, may be
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.
3.
University of Georgia
RCE 2013029
optionally and automatically called with the highlight
command.
g.
Fixtures with CMY or RBG color mixing may be set
with direct CMY or RBG controls, as well as the Hue
and Saturation encoders and/or color picker. Color
may also be set directly to a gel match, via a graphic
selection tool or from the command line.
h.
The Virtual Media Server function shall allow the user
to create layouts of devices, identified as pixel maps.
Media content (images, movies, text and procedurally
generated effects) may then be applied, manipulated
and stored. Stock content is provided and the user
may import custom imagery and animations.
i.
Macros may be set to run as default. Default macros
called manually shall post to the command line, but
executed via cue lists shall run in the background.
The user may override this behavior by defining the
macro to always execute in the foreground or the
background, regardless of the recall method. Startup,
Shutdown and Disconnect macros may also be
defined.
Playback Section
a.
The master fader shall consist of a 60mm Master
Fader pair with associated Load, Go and Stop/Back
buttons. Additional playback faders may be
configured via the virtual fader module or on the
Universal Fader Wings.
b.
It shall be possible to instantaneously halt an active
cue, back to the previous cue, manually override the
intensity fade or manually override the entire fade.
c.
It shall be possible for a cue list to contribute to the
background state or for the contents of each cue list
to be withheld from such.
d.
The playback faders shall have the following
associate controls:
1)
Freeze, which halts the output of the fader
2)
Stop Effect, which stops the action of an effect.
3)
Filter, to assign filter states to a fader
4)
Go to Cue 0, to reset a cue list.
Fader Wings (Optional)
a.
Submaster and fader support shall be provided via
optional fader wings. These wings are available in
1x20, 2x10 and 2x20 configurations. Up to six of
these wings may be connected to the desk via
internal or external USB. Via paging, access is
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
University of Georgia
RCE 2013029
provided to all 300 faders, regardless of the number
of physical wings attached.
b.
The 2x10 and 2x20 fader wings shall include a full
length LCD for labeling and identification functions.
Each fader shall have two associated hard buttons for
various operations. Systems without a local display or
fewer than two buttons per fader shall not be
acceptable.
c.
Up to 300 proportional, fully overlapping additive,
effect or inhibitive submasters may be defined.
Submasters shall have colored LEDs to indicate
submaster status. Each submaster may have fade up,
dwell and down fade times. Each has a bump and
assert/channel select button. Submasters may be
set to independent, exclusive, shielded and
proportional/intensity or effect master control.
d.
The submaster blind buffer shall be linked directly to
live playback allowing live editing of live submaster
content via the command line.
e.
It shall be possible to set submaster values directly
from the command line.
f.
Up to 200 cue lists may be active concurrently.
4.
Grand Master
a.
A dedicated grand master and blackout button are
provided.
b.
The grand master shall proportionally fade intensity
values to zero. Blackout shall send all intensity
outputs to zero. Non-intensity outputs shall not be
affected. No additional configuration shall be required
to withhold non-intensity values from Grand Master
and Blackout control.
Display Controls
1.
Format shall change the view of selected displays.
2.
It shall be possible for the user to choose which parameter
categories or parameters (s)he wishes to display.
3.
Flexichannel shall change which channels are viewed in
selected displays, as follows:
a.
All channels
b.
Patched channels
c.
Show channels
d.
Active/Moved channels
e.
Selected channels
f.
Manual Channels
g.
View channels (user identified list)
h.
Channels with discrete timing
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4.
D.
University of Georgia
RCE 2013029
Expand shall extend the selected view sequentially across
connected displays, vertically or horizontally.
5.
[Time] depressed shall display discrete timing data. [Data]
depressed shall display absolute values of referenced data.
6.
User definable magic sheets shall provide alternative display
of and access to channels and record targets. Multiple
magic sheets may be created.
7.
Playback status displays are provided with a variety of
different formats. Indications are provided per cue for live
moves (lights fading from zero and also moving nonintensity parameters) and dark moves (inactive lights which
have stored non-intensity parameter moves).
Operating Modes
1.
Live Mode
a.
Channel lists may be constructed using the +, - and
Thru keys as well as the direct selects. Channel
selection and deselection is fully interactive,
regardless of the method used.
b.
Levels may be set with the keypad, level wheel and
non-intensity encoders. “Selected” channels shall be
those last addressed and under keypad control.
c.
Sneak shall be used to restore specified channels to
background states, default values, or to send them to
specified values, in user specified or default times.
d.
Selected channels may be set at a level or held to
current values while all other channels are set to zero
using Rem Dim. Toggling Rem Dim shall restore all
unselected channels to original levels. The Rem Dim
level shall be user definable via the command line or
with a default setup value.
e.
Channels may be recorded into groups for fast recall
of commonly used channels. 1000 groups shall be
available. Groups shall store selection order. The
Offset function supports rapid creation of ordered
groups, including reverse and random order.
f.
Parameter settings may be stored to Intensity, Focus,
Color and Beam Palettes and to Presets. All
referenced data may be stored to whole numbers or
to up to 99 decimal places between each whole
number. It shall be possible to store 1000 presets and
1000 of each palette type.
g.
Any collection of channel data, as determined by the
use of “Record”, “Record Only, selective store
commands and/or parameter filters may be stored to
palettes (as appropriate to the type) and presets.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
h.
i.
j.
k.
l.
University of Georgia
RCE 2013029
The following conditions may be placed on a channel
or channel parameter to be included with a cue record
action.
1)
Discrete fade time and/or delay
2)
Block flag
3)
Assert flag
4)
IFCB Filters, which may be set at a parameter
level.
999 cue lists may be stored. Cues may be recorded in
any order. Up to 99 decimal cues may be inserted
between any two whole number cues. Each cue may
contain a maximum of twenty parts. Parameters may
be automatically assigned to specific parts or
assigned when the part is created.
It shall be possible to record cues and cue parts with
the following information:
1)
Any collection of channel data, as determined
by the use of “Record”, “Record Only” or
selective store commands, combined with
parameter filters.
2)
Cue Level timing and delays for Intensity Up,
Intensity Down, Focus, Color and Beam.
3)
Follow or hang time
4)
Link instruction
5)
Loop value
6)
Block, Assert, Allfade, Preheat and/or Mark
Flag
7)
Curve
8)
Label and note
9)
Execute list to trigger other activity
Non-intensity channel parameters may be marked
(preset), in two ways. Automark presets any
parameters transitions in the cue just prior to intensity
becoming active. Automark may be disabled on a cue
or cue part basis, enabling a “live” move.
Alternatively, non-intensity parameters may be
marked to a specific cue with a single command
instruction. It shall not be necessary to store these
parameters directly into the cue in which the
movement is to occur.
Any channel parameter may be stored with an effect
instruction. These effects may contain relative offsets
from current value, or absolute instructions. Effects
may be progressive action or on/off states. Entry and
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
m.
n.
o.
p.
q.
r.
s.
t.
u.
v.
University of Georgia
RCE 2013029
exit behaviors shall modify the channel parameters
activity when beginning and ending the effect.
Update may be used to selectively add modified
parameter data quickly to that parameter’s current
source. It shall be possible to update inactive record
targets. It shall also be possible to update back to the
current source of the move instruction without
specifying that cue via Trace. A context sensitive
display provides detailed information regarding the
results of the update command.
Recall From quickly pulls specified data from record
targets or other channels into the current view. Recall
from on an HTP basis shall be provided.
Copy To quickly copies selected data to specified
channels or other record targets.
Address and channel check functions shall be
provided.
Channel parameters may be “parked” at levels.
Output addresses may also be parted directly. Parked
levels shall not be added to any live record
operations, nor may they be changed until the parked
element is “unparked”. Address Park shall also be
provided.
About shall provide detailed status of selected
channels or specified record targets. This shall
include current source, current value, discrete timing,
parked value, marked to and for indications.
Background levels and current DMX output are also
displayed. Channel usage indicates submaster and
cue information and also provides a "dark moves"
report on a per channel basis.
1000 snapshots may be stored which instantly recall
specified front panel and display configurations.
Live data may be displayed in a summary view,
detailed table orientation or a user-defined magic
sheet.
Undo shall be used to sequentially step back through
manual operations, record, update and delete actions.
Redo functions shall be provided. Multiple undo
commands may be executed at once.
Home shall set selected channels non-intensity
parameters to their default values. User definable
home, on a per- channel/per- parameter basis shall
be provided.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
w.
x.
2.
3.
4.
University of Georgia
RCE 2013029
Move shall allow all show data to be moved from one
record target to another.
Query shall allow selection of channels by their
current or possible state. Keywords and fixture types
shall allow quick access to fixtures.
Blind
a.
The Blind display allows viewing and modification of
all record targets without affecting stage levels.
b.
Record target data may be displayed in a summary
view, a detailed table orientation or a spreadsheet
view, which allows quick data comparisons, move and
replace with functions.
c.
Changes made in blind displays shall be automatically
stored.
d.
Blind editing shall be possible for all record targets.
e.
Selection of what parameter data to view for blind
editing shall be user configurable.
Patch Display
a.
Patch shall be used to display and modify the system
control channels with their associated library data.
b.
Each channel may be provided with a proportional
patch level, preheat, curve, label, swap and invert
functions.
c.
Offset functions in patch shall allow selection of
channel ranges and shall allow the user to establish a
“custom” footprint for any device output.
d.
A full library of profiles is provided, with the ability for
the user to define “favorites” for fast selection.
e.
Custom color wheels, color scrolls and gobo wheels
shall be defined in patch. These devices shall be
created with a simple table and graphical user
interface supported by images of major
manufacturers.
f.
Copy to and Move functions shall be supported in
patch.
g.
RDM discovery and device monitoring shall be
supported.
Setup/Browser
a.
Setup shall access system, show and desk
configurations.
b.
The browser shall access show data storage, import,
export, print to .pdf and clear functions, as well as
show data utilities.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
c.
E.
It shall be possible to partially merge show files.
Users shall be able to select as much or as little of the
show file as required, with renumber tools.
d.
It shall be possible to import ASCII and Lightwright
data files. It shall be possible to export as ASCII or
.csv.
Dimmer Monitoring and Configuration
1.
The lighting control system shall provide communication with
an ETC Sensor+, Sensor3 or FDX dimming system for
remote monitoring and configuration of show specific
functions from within the software application.
2.
Circuit level configuration and monitoring functions shall
include but not be limited to:
a.
Control mode (dimmable, switched, latch-lock, always
on, off or fluorescent).
b.
Curves
c.
Control threshold
d.
Min and Max Scale Voltage
e.
Preheat
f.
Scale load
3.
Rack Status messages shall include but not be limited to:
a.
State of UL924 panic closure
b.
DMX port error/failure
c.
Network error/failure
d.
A, B, C Phase below 90 or above 139 volts and
headroom warning
e.
Ambient temperatures out of range
4.
Circuit status shall include but not be limited to:
a.
Module type and location
b.
Output level
c.
Control Source
d.
Overtemp
Advanced circuit feedback shall include but not be limited to:
a.
Load higher or lower than recorded value
b.
DC detected on output
c.
SCR failed on/off
d.
Breaker trip
e.
Module has been removed
f.
Load failure
g.
Shutdown due to Overtemp
5.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
F.
G.
H.
University of Georgia
RCE 2013029
Training Options
1.
Training packages shall be available customizable to the
individual venue preferences and needs. The level of
training (beginner, intermediate or advanced) may be
selected and training may be defined as an element of
system commissioning or deferred to a later time.
Interface Options
1.
The unit shall support a variety of local interfaces.
a.
AC input.
b.
USB (five ports for connecting devices such as an
alphanumeric keyboard, mouse, touch screens, USB
Flash drive, fader wings, etc.) The desk shall provide
four ports on the rear of the unit and one on the
control service itself.
c.
Ethernet (one port) 802.3af compliant
d.
Two DVI video output connectors, supporting a
maximum of two DVI monitors at 1280x1024
resolution minimum.
e.
One VGA output connector.
f.
Up to six fader wings may be attached to the main
console via internal or external USB connections.
Systems that do not allow the addition of fader wings
shall not be acceptable.
g.
Two DMX512-A/RDM Ports
h.
Contact Closure Trigger via D-Sub Connector
i.
Phone Remote
j.
MIDI In/Out (MIDI Timecode, MIDI Show Control)
Accessories
1.
Net3 Radio Focus Remote
2.
iRFR and iRFR Preview (application for iPhone, iPod Touch
and iPad units)
3.
aRFR (application for Android devices)
4.
Net3 Remote Video Interface
5.
1 x 20, 2x10 and 2x20 Universal Fader Wings
6.
Net 3Gateways
a.
Net3/ETCNet 2 to DMX/RDM Gateways (one to four
ports)
b.
MIDI/SMPTE Gateways
c.
I/O Gateway with 12 analog inputs, 12 SPDT contact
outputs, RD232 interface
7.
Eos Family Client Software Kit
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
I.
J.
4.8
University of Georgia
RCE 2013029
Synchronized Backup
1.
An optional Backup system shall consist of one of the
following combinations of devices:
a.
Two networked desks
b.
One (or more) desk with one Remote Processor Unit
(RPU)
c.
One (or more) desk with two Remote Processor Units
(RPUs)
Physical and Acoustical
1.
All operator controls and electronics for a standard system
shall be housed in a single desktop console, not to exceed
19” wide, 19” deep, 5.5” high, weighing 20 pounds.
2.
Power shall be 95 – 240V AC at 50 or 60Hz, supplied via a
detachable power cord.
3.
At typical CPU utilization, the unit shall operate at ≤ 26 dBA.
RADIO FOCUS REMOTE
A.
B.
General
1.
The Net3 Radio Focus Remote (RFR) shall be a wireless
remote control device that allows access to a variety of
system functions. The hand-held transmitter unit shall
provide access to frequently used commands for dimmer
and channel checks as well as extended functions of the
console via softkeys. The receiver unit shall plug directly
into the console via USB or may connect to the lighting
system via Ethernet.
2.
The RFR shall be compatible with the ETC Eos and Congo
lighting control systems and their associated consoles,
Remote Processor Units (RPUs) and lighting playback
controllers.
3.
The system shall support multiple units on one receiver as
well multiple systems operating separately in the same
area.
4.
The system equipment has been tested and found to comply
with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules.
Handheld Device or Transmitter
1.
The transmitter unit shall have a slide switch (on/off), 24
keys for console commands, two rotary encoders with builtin switches and one backlit display. The unit shall also have
a programmable “sleep” feature that helps to conserve
battery life when the switch is left in the “on” position.
2.
The keys of the transmitter unit shall be illuminated. The
keys will be brightly lit while keys are pressed and the unit is
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
4.9
University of Georgia
RCE 2013029
transmitting. After the key is released, the keys will remain
dimly lit for a period of time before the unit sleeps.
3.
The transmitter shall have one dedicated command for each
key on the unit with the exception of the six soft keys.
Dedicated commands shall be displayed within each key.
Softkey functions shall be accessed via a “More SK/Mode”
key and shall be indicated within the built-in display.
4.
Functionality of the unit shall be determined by the control
system it is connected to. Eos systems shall provide Eos
commands, and Congo systems shall provide Congo
commands.
5.
The transmitter unit shall be provided with rechargeable
nickel metal hydride (NimH) batteries for power. These
batteries should provide approximately two days of normal
usage before requiring recharging.
6.
The transmitter shall be a rugged steel unit, 2.7"(68mm)
wide, 6.6"(168mm) high and 0.8"(20mm) deep, excluding
the fixed helical antenna. The unit shall weigh 14 oz (400g),
including antenna. The unit shall come complete with a
hanging point for a wrist strap or lanyard.
7.
The Radio Frequency Output for the transmitter shall be
2.410 GHz with 11 additional HF: channels available
(2.410GHz - 2.465 GHz). 99 Network IDs available per
channel.
8.
The working range of the radio signal shall be 300’ (90m) in
an indoor environment and 650’ (200m) in an outdoor, free
field environment.
Receiver Unit
1.
The receiver unit shall be provided with a 6.6’ (2m) USB
cable. The receiver may also be plugged into an available
powered Ethernet port elsewhere in the system, however
the maximum distance (cable length including cable inside
the wall) from the power source shall be 330’ (100m).
2.
The receiver unit shall be powered directly by the USB
connection or by a Power-over-Ethernet connection.
3.
A signal LED shall illuminate when the receiver is receiving
radio signal from the transmitter.
4.
The receiver shall be housed in a unit 2.8" (71mm) wide,
4.4" (112mm) high and 0.7" (45mm) deep, and shall weight
13 oz. (380g) including antenna.
REMOTE PLUG-IN STATIONS
A.
The Remote Plug-in Stations shall consist of the appropriate
connectors required for the system in use. These stations shall be
available with DMX input & remote focus unit.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
C.
D.
E.
4.10
The following standard components shall be available for Remote
Plug-in Stations:
1.
RJ45 connectors for Network connections - Twisted Pair
Custom combinations and custom control connections shall be
available.
Station faceplates shall be .80” aluminum, finished in fine texture,
scratch-resistant black powder coat. Silk screened graphics shall
be white.
The station panel shall mount into an industry standard back box,
depending on size and quantity of connectors. A terminal block
shall be supplied for contractor terminations.
DISTRIBUTION
A.
B.
C.
D.
E.
F.
G.
H.
4.11
University of Georgia
RCE 2013029
Wiring devices shall be fabricated from 16-gauge cold rolled steel.
Devices shall be properly cleaned, primed and painted with flat
black baked enamel. Circuit numbers shall be 2" high.
Individual pigtails and outlets shall be evenly spaced in connector
strips, or as otherwise specified. Where a circuit would fall on a
joint it shall be moved 3" towards the junction box end of the strip.
Pigtails shall be three-wire type "SO" rubber jacketed cable sized
for the circuit capacity. Connectors are 20A stage pin connectors.
Internal wiring shall be sized to circuit capacity and terminated in
feed through compression terminals at one end for ease of
installation. Wire shall be rated at 125°.
Devices except for wall mounted boxes shall be supplied with
appropriate hardware for mounting as shown on the drawings.
Connector strips shall have brackets on 5' centers.
For connector strips provide multi-conductor SO type cable(s) as
required to allow all devices to fly within 3’ above finished floor.
Provide two (2) cable strain relief grips and one (1) cable cradle for
each section of multi-conductor cable. Units to be sized for proper
fit and function.
Plug boxes shall be mounted as indicated with scheduled circuit
outlets.
Wiring devices shall be UL Laboratories Listed.
SOURCE FOUR ELLIPSOIDALS
A.
B.
C.
The ellipsoidal spotlights shall be the Source Four spotlights.
Source Four's high efficiency lamp shall utilize a compact tungsten
filament contained in a krypton-filled quartz envelope. The lamp
base shall be an integral die cast aluminum heat sink that reduces
seal temperature and ensures proper lamp alignment.
The lamp shall be 575 Watts with 16,500 lumens, with a color
temperature of 3,250 K and have 300 hours of lamp life.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
D.
E.
F.
4.12
University of Georgia
RCE 2013029
Source Four's optical train shall combine a compact filament lamp
with a precision molded borosilicate, ellipsoidal reflector and a
single aspheric lens to produce an optimum cosine field.
Source Four ellipsoidal spotlights are constructed of rugged, die
cast aluminum, finished in black, high temperature epoxy paint.
Tools are not required for either lamp alignment or cleaning the
reflector or lens. Precision tooled mechanical assemblies provide
smooth operation, positive locking of adjustments and
interchangeable components.
Source Four ellipsoidals shall provide, but not be limited to:
1.
Die cast aluminum housings
2.
Integral cable clamp for power leads
3.
Positive locking of lamp focus
4.
Independent lamp alignment controls
5.
High impact, thermally insulated knobs and shutter handles
6.
Reflector secured with shock mounts
7.
Rotating shutter assembly for keystone angles
8.
Heavy gauge stainless steel shutters
9.
Lens secured with silicone shock mounts
10. Interchangeable lens tubes for different fields
11. Teflon guides for smooth lens tube movement
12. Sturdy gel frame holders with two accessory slots
13. Top mounted, quick release gel frame retainer
14. Rugged steel yoke with two mounting positions
15. 300+ Rotation of fixture within yoke
16. Positive locking, hand operated yoke clutch
SOURCE 4 PAR
A.
B.
C.
The instrument shall be a Source Four Par.
The instrument shall utilize a 575 watt HPL lamp which is a
compact tungsten filament contained in a krypton-filled quartz
envelope.
1.
The lamp shall mount axially within the reflector and shall be
prefocused within the reflector.
2.
The lamp base shall have a integral die cast aluminum heat
sink that reduces seal temperature and ensures proper
lamp alignment.
3.
The lamp socket shall be ATP 220 nickel gold plated.
4.
All versions of the instrument shall use only lamp type, the
HPL lamp. Fixtures which require the purchasing of multiple
lamp types to achieve different field angles shall not be
acceptable.
The spotlights are constructed of rugged, die cast aluminum, free of
burrs and pits, finished in black, high temperature epoxy paint.
Tools shall not be required for cleaning the reflector or lens
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
D.
E.
University of Georgia
RCE 2013029
The spotlight shall provide, but not be limited to:
1.
Integral cable clamp for power leads
2.
High impact, thermally insulated knobs
3.
Sealed reflector housing shall prevent all light leaks.
Temperature control of reflector is obtained through 17 heat
sink fins cast into the housing.
4.
Interior of unit shall contain ten baffles to eliminate beam
scattering and spill light.
5.
Lamp socket shall be held into place by a brass self retaining
screw.
6.
Lens shall be secured with cast bosses and high
temperature bronze spring release. No tools shall be
required to change lenses.
7.
Sturdy gel frame holders with two accessory slots and a top
mounted, quick release gel frame retainer
8.
Rotation of fixture within yoke
9.
Positive locking, hand operated yoke clutch
10. Each unit shall be provided standard with colorframe and 36”
bare lead.
11. Unit shall be nominally 11”long by 10” wide
12. Weight without “C” clamp shall be 8 lbs.
The spotlight shall be UL and CUL approved
1.
It shall be possible to change field type of the spotlight
through interchangeable lenses. No tools shall be
2.
3.
4.
possible while the unit is active. No tools shall be necessary
for lens rotation. Fixtures, which require user to touch the
lamp or lamp socket to orientate the beam, shall not be
acceptable.
Interchangeable lens sets shall consist of clear, very narrow
spot, narrow spot, medium flood, and wide flood. Lenses
shall be heat resistant, borosilicate glass.
Beam orientation of MFL and WFL lenses shall be possible
through rotation of lenses in a rotatable collar housed in the
front of the unit. Collar shall be a high temperature heat
resistant rotating collar with finger holds for precise
movement.
The optical train shall combine a compact filament lamp with
modified parabolic and multifaceted reflector. Reflector
efficiency shall be a minimum of 93%. Reflector shall be
cast into a heat sink assembly. Reflector finish shall be an
enhanced aluminum deposition. Reflectors of pressed
aluminum sheet construction shall not be acceptable.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4.13
University of Georgia
RCE 2013029
FRESNEL SPOTLIGHT
A.
B.
C.
D.
General
1.
The luminaire shall be a Source Four Fresnel spotlight as
manufactured by Electronic Theatre Controls, Inc., or
approved equal
Lamp
1.
The luminaire shall utilize only the HPL lamp, which shall
consist of a compact tungsten filament contained in a
krypton-filled quartz envelope
2.
The lamp base shall have an integral die cast aluminum heat
sink that reduces seal temperature and ensures proper
lamp alignment
3.
Luminaires that use lamps other than the HPL lamp shall not
be acceptable
4.
The lamp socket shall be ATP 220 nickel gold plated
5.
The lamp shall be prefocused in relation to the reflector
6.
The lamp shall be removable from the bottom of the fixture
for re-lamping
Optical
1.
Luminaire shall use a Fresnel lens and provide soft-edged,
but well-defined beam shaping with a barn door attachment
2.
Luminaire shall provide a field angle zoom range of 20
degrees to 65 degrees
3.
The optical train shall utilize a compact filament lamp with a
modified spherical reflector
4.
The luminaire shall output no less than 10,000 field lumens
in full flood setting when fitted with 750W, 115V high out-put
HPL lamp
5.
Luminaires producing less than 10,000 field lumens in full
flood setting with a 750W lamp shall not be acceptable
6.
Reflector shall be molded borosilicate glass with multiple
dichroic layers
7.
Reflector efficiency shall be a minimum of 93%
8.
Reflectors of pressed aluminum or other sheet metal
construction shall not be acceptable
Physical
1.
The luminaire shall be constructed of rugged, die cast
aluminum, free of burrs and pits, finished in black, high
temperature paint
2.
The luminaire shall provide, but not be limited to:
a.
36” power lead with bare-ends
b.
Integral cable clamp for power leads
c.
Sealed housing with no light leaks
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
d.
3.
4.
5.
6.
4.14
Zoom adjustment by means of a large, side-mounted
knob with integral locking lever
e.
Bottom-access lamp removal
f.
Lamp socket access door shall use a tool-free ¼-turn
closure device
g.
Two accessory slots and a top mounted locking door
for gel frames and beam control accessories
1)
Accessory slots shall be completely
surrounded by a rugged metal housing for
elimination of light leaks around gel frames and
other beam control accessories
2)
Accessory slots shall be compatible with 7.5”
beam control accessories, i.e. barn doors, gel
frames, top hats, etc, such as used by Source
Four PAR luminaires and other similarly-sized
fixtures
h.
Rugged steel yoke
i.
Adjustable yoke mounting position for variable fixture
balance point
j.
Positive locking, hand operated yoke clutch
k.
Large, rugged handle on rear of fixture
l.
Integrated safety cable mounting ring
m.
Color frame
Unit shall be nominally 12.5”long by 9.5” wide
Weight without “C” clamp shall be 13.25 lbs.
The luminaire shall be capable of utilizing ETC Dimmer
Doubling technology
The luminaire shall be ETL and cETL listed to UL 1573 – the
standard for stage and studio use and so labeled.
COLOR MIXING LIGHT EMITTING DIODE WASH FIXTURE
A.
B.
General
1.
The fixture shall be a color-mixing high-intensity LED
illuminator with DMX control of intensity and color. The
fixture shall be a Desire D40 or D40 Studio as
manufactured by Electronics Theatre Controls, Inc. or
approved equal.
2.
All LED fixtures shall be provided by a single manufacturer
to ensure compatibility
3.
The fixture shall be UL 1573 listed for stage and studio use
4.
The fixture shall comply with the USITT DMX-512 A
standard
Physical
1.
The fixture shall be contained in a rugged all-metal die-cast
housing, free of burrs and pits.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.
C.
D.
University of Georgia
RCE 2013029
The housing shall have a rugged black powdercoat finish
a.
White or silver/gray powdercoat finishes shall be
available as color options
b.
Other powdercoat color options shall be available on
request
3.
Power supply, cooling and electronics shall be integral to
each unit.
4.
Fixture housing shall provide two easy-access slots for
secondary lenses and other accessories
a.
Slots shall be equipped with locking retaining clip
5.
The unit shall ship with:
a.
Theatrical-style hanging yoke as standard
b.
5’ power lead with Edison connector as standard
c.
25 deg. secondary lens as standard
6.
Available options shall include but not be limited to:
a.
Yoke with floor stand conversion feature
b.
Bare-end, Stage-Pin or Twist-lock type-equipped
power leads
c.
PowerCon to PowerCon cables for fixture power
linking
d.
Multiple secondary lens options to include multiple
angles in the following patterns:
1)
Linear
2)
Round
3)
Oblong
7.
Light output shall be via a round aperture
a.
Aperture and accessory slots shall accommodate
standard 7.5” accessories such as used in other
similar-sized fixtures
b.
Accessories available as options shall include but not
be limited to:
1)
Gel/diffusion frames
2)
Top hats
3)
Barndoors
4)
Egg crate louvers
5)
Concentric ring louvers
6)
Multiple secondary lensing options
ENVIRONMENTAL AND AGENCY COMPLIANCE
1.
The fixture shall be UL and cUL LISTED and/or CE rated,
and shall be so labeled when delivered to the job site.
2.
The fixture shall be UL LISTED to the UL1573 standard for
stage and studio use
3.
The fixture shall be rated for IP-20 dry location use.
THERMAL
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
1.
E.
F.
University of Georgia
RCE 2013029
Fixture shall be totally convection cooled, requiring no
cooling fan. Fixtures which require an on-board cooling fan
shall not be acceptable unless pre-approved
2.
The fixture shall utilize advanced thermal management
systems to maintain LED life to an average of 70% intensity
after 50,000 hours of use
a.
Thermal management shall include multiple
temperature sensors within the housing to include:
1)
LED array circuit board temperatures
2)
Temperature sensors placed on each
individual LED color circuit
3)
Fixture ambient
4)
CPU
b.
Fixture user shall permit monitoring of temperature
sensors via a legible LCD multi-line backlit display
c.
Fixtures that do not provide active thermal monitoring
of LED circuits and other temperature readings shall
not be acceptable
3.
The fixture shall operate in an ambient temperature range of
-20°C (-4°F) minimum, to 40° C (104°F) maximum ambient
temperature.
ELECTRICAL
1.
The fixture shall be equipped with 100V to 240V 50/60 Hz
internal power supply
2.
The fixture shall support power in and thru operation
a.
Power in shall be via Neutrik® PowerCon™ input
connector
b.
Power thru shall be via Neutrik ® PowerCon ™ output
connector
c.
Fixture power wiring and accessory power cables
shall be rated to support linking of multiple fixtures up
to the capacity of a 15A breaker
3.
The fixture requires power from non-dim source
4.
Power supply outputs shall have self-resetting current
limiting protection
5.
Power supply shall have power factor correction
LED Emitters
1.
The fixture shall contain a minimum of 5 different LED colors
to provide color characteristics as described in Section G
below.
2.
All LEDs used in the fixture shall be high brightness and
proven quality from established and reputable LED
manufacturers.
a.
Fixture shall utilize Luxeon® Rebel™ LED emitters
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
3.
G.
H.
Manufacturer of LED emitters shall utilize an advanced
production LED binning process to maintain color
consistency.
4.
LED emitters should be rated for nominal 50,000 hour LED
life to 70% intensity
5.
All LED fixtures (100% of each lot) shall undergo a minimum
eight-hour burn-in test during manufacturing.
6.
LED system shall comply with all relevant patents
CALIBRATION
1.
Fixture shall be calibrated at factory for achieve consistent
color and intensity output between fixtures built at different
times and/or from different LED lots or bins
a.
Calibration data shall be stored on the LED array as a
permanent part of on-board operating system
b.
All arrays, including replacement arrays shall be
calibrated to the same standard to insure consistency
c.
Fixtures not offering LED calibration shall not be
acceptable
COLOR
1.
The fixture shall utilize an minimum of 40 LED emitters
2.
The fixture shall be available in specialized LED arrays as
outlined below:
a.
Desire D40
1)
Red, Amber, Green, Cyan, Blue, Indigo and
White LEDs in an array designed for broad
spectrum color, light tints, and variable whites.
This array shall be the Lustr+ array as
manufactured by Electronic Theatre Controls,
or approved equal
(i)
2)
Measured brightness of the Lustr+ array
shall be greater than 2900 field lumens
Red, Orange, Amber, Green, Cyan, Blue and
Indigo LEDs in an array designed for broad
spectrum deep colors. This array shall be the
Vivid array as manufactured by Electronic
Theatre Controls, or approved equal
(i)
3)
Measured brightness of the Vivid array
shall be greater than 2500 field lumens
Red, Orange, Amber, Green and Indigo LEDs
in an array designed for extra-high brightness
output in red/warm end of the spectrum. This
shall be the Fire array as manufactured by
Electronic Theatre Controls, or approved equal
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
(i)
4)
Measured brightness of the Fire array
shall be greater than 2500 field lumens
Red, Orange, Green, Cyan, Blue and Indigo
LEDs in an array designed for extra-high
brightness output in the blue/cool end of the
spectrum. This shall be the Ice array as
manufactured by Electronic Theatre Controls,
or approved equal
(i)
b.
Measured brightness of the Ice array
shall be greater than 1800 field lumens
Desire D40 Studio
1)
Warm White, Cool White, Red, Green, Blue
and Indigo LEDs in an array designed for highbrightness variable color temperature white
light output. This shall be the Studio HD array
as manufactured by Electronic Theatre
Controls, or approved equal
(i)
2)
Measure brightness of the Studio HD
array shall be greater than 3100 field
lumens
All Warm White LEDs in an array designed for
non-variable single color high-output, warm
white light. This shall be the Studio Tungsten
array as manufactured by Electronic Theatre
Controls, or approved equal
(i)
3)
Measure brightness of the Studio
tungsten array shall be greater than
(TBD) field lumens
All Cool White LEDs in an array designed for
non-variable single color high-output, cool
white light. This shall be the Studio Daylight
array as manufactured by Electronic Theatre
Controls, or approved equal
(i)
I.
Measure brightness of the Studio
Daylight array shall be greater than field
lumens
DIMMING
1.
The LED system shall use 15-bit nonlinear scaling
techniques for high-resolution dimming.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.
J.
University of Georgia
RCE 2013029
At least four different dimming curve options shall be
accessible at the fixture’s User Interface
a.
Incandescent
b.
Standard
c.
Linear
d.
Quick
3.
Dimming curves shall be optimized for smooth dimming over
longer timed fades.
4.
The LED system shall be digitally driven using high-speed
pulse width modulation (PWM)
5.
LED control shall be compatible with broadcast equipment in
the following ways:
a.
PWM control of LED levels shall be imperceptible to
video cameras and related equipment
b.
PWM rates shall be adjustable by the user at the
fixture if necessary to avoid any visible interference to
video cameras and related equipment
CONTROL AND USER INTERFACE
1.
The fixture shall be USITT DMX 512A-compatible via In and
Thru 5-pin XLR connectors
2.
The fixture shall be compatible with the ANSI RDM E1.20
standard
a.
All fixture functions shall accessible via RDM protocol
for modification from suitably equipped control
console
b.
Temperature sensors within the luminaire shall be
viewable in real time via RDM
c.
Fixtures not offering RDM compatibility, feature set
access or temperature monitoring via RDM shall not
be compatible
3.
The fixture shall be equipped with multi-line LCD display for
easy-to-read status reports and configuration changes
4.
The fixture shall be equipped with a six-button user-interface
5.
The fixture shall offer multiple DMX input profile options to
include:
a.
RGB - control of all individual LED colors via a threechannel profile
1)
Red, Green, Blue
b.
HSI – control of all individual LED colors via a threechannel profile
1)
Hue, Saturation, Intensity
c.
HSIC – control of all LED colors via a four-channel
profile
1)
Hue, Saturation, Intensity and Color Point
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
(i)
6.
7.
8.
9.
Color point provides variable color
temperature settings
d.
Direct – control of each individual color channel via an
independent channel
e.
A variable-rate strobe channel shall be provided
The fixture shall offer three output settings
a.
Boost mode - powers LEDs at maximum intensity and
provides no compensation against LED ‘droop’ or
intensity loss
b.
Regulated mode – slightly restricts maximum LED
intensity levels to compensate against LED droop
c.
Protected mode – further restricts maximum LED
intensity levels to compensate against LED droop and
offer color consistency at highest permissible ambient
temperatures (40C)
d.
Fixtures that do not provide regulated and protected
operation modes are not acceptable
The fixture shall offer additional user-definable options to
including but not limited to:
a.
Display time out options
b.
Loss of data behavior options
c.
White point settings
d.
Red-shift option for tungsten dimming emulation
The fixture shall offer five Quick Set-Ups to allow user to
rapidly select different combinations of the numerous user
options based on the desired usage situation, to include:
a.
General – for most situations
b.
Stage – when emulating incandescent fixtures is
desired
c.
High Impact – when maximum output and effect is
desired
d.
XT Arch – when color consistency and architectural
characteristics are desired.
e.
Studio - when DMX or stand-alone of white light
output is required with intensity, color temperature
and color tint control parameters
The fixture shall offer stand-alone functionality eliminating
the need for a console
a.
Fixture shall ship with 24 preset colors accessible as
a stand-alone feature
b.
Fixture shall ship with 12 Sequences accessible as a
stand-alone feature
c.
Each color and sequence can be modified by the end
user
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
d.
e.
f.
4.15
University of Georgia
RCE 2013029
Fixtures can be linked together with standard DMX
cables and controlled from designated master fixture
1)
Up to 32 fixtures may be linked
Fixtures in a stand-alone state shall restore to the
settings present prior to power cycling, eliminating the
need for reprogramming
Fixtures without stand-alone operation features
described in a, b, c, d, and e shall not be acceptable.
PLATNUM SPOT 5R PRO
A.
B.
C.
General
1.
The instrument shall be a Platnum Spot 5R Pro, as marketed
by Elation and Acclaim Lighting, or approved equal.
Features
1.
CMY color mixing 16bit
2.
Variable zoom (4 to 1)
3.
Energy efficient
4.
Supirior optics flat/even light field
5.
3 facet rotating prism
6.
Motorized iris
7.
11 degree to 42 degree variable zoom beam angle
8.
Variable frost filter (hybrid effect for wash)
9.
Motorized focus
10. Featuring Philips MSD Platnum 5R Lamp
Technical Specifications
1.
DMX Channels: 23/21/34 3 x DMX Channel Modes
2.
Control
a.
3 pin DMX
b.
5 pin DMX
3.
Dimmer: Mechanical Dimmer 0-100%
4.
Strobe: Variable speed shutter/strobe
5.
Iris: Motorized Iris
6.
Pan/Tilt: 540/630 x 265
7.
Power supply: 120v – 240v 50/60hz
8.
Power Consumption: 350w max
9.
Lamp: MSD Platnum 5R 2,000 Hr
10. Lux: 6350 Lux / 590 fc @ 16’
All fixtures come complete with safety cable, c-clamp, color frame, grounded
stage pin connector & lamp. All stage electric connector strips come with SO
cable, kellum grips, cable cradles & gridiron junction box required to
complete installation.
5.
UNISON DRD SERIES RACK ENCLOSURES
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
5.1
University of Georgia
RCE 2013029
RACK ENCLOSURES
A.
B.
The rack enclosure shall be the Unison DRd Series Control
Enclosure as manufactured by Electronic Theatre Controls, Inc., or
equal.
Mechanical
1.
The Rack Enclosure shall be a surface mounted, deadfront
switchboard, constructed of 18-guage formed steel panels
with a hinged, lockable full-height door containing an
integral electrostatic air filter.
a.
Filter shall be removable for easy cleaning.
b.
The enclosure shall support one control processor
and one station power module plus accessories
c.
The enclosure door shall have an opening to allow
limited access to the control module face panel.
2.
All rack components shall be properly treated and finished.
a.
Exterior surfaces shall be finished in fine textured,
scratch-resistant, epoxy paint.
3.
The fully digital rack enclosure shall be available with six or
twelve dimmer module spaces, one processor and a single
station power supply, Rack dimensions and weights
(without modules) shall not exceed:
a.
DRd6 21.9” H x 17” W x 9.6” D
38 lb.
b.
DRd12
31.0" H x 17” W x 9.6” D 51 lb.
4.
A single low-noise fan shall be located at the top of each
rack. The fan shall draw all intake air through the integral
electrostatic air filter, over the surfaces of the module
housing and out the top of the rack.
a.
The fan shall maintain the temperature of all
components at proper operating levels with dimmers
under full load, provided the ambient temperature of
the dimmer room does not exceed 40°C/104°F.
b.
In the event of an over-temperature condition, only
the affected dimmer module(s) shall shut down. A red
indicator LED will flash and an error message shall
appear on the Control Processor.
5.
Rack Enclosures shall be designed to allow easy insertion
and removal of dimmer and control modules without the use
of tools. (230 volt racks with CE certification shall require a
screwdriver.)
a.
Supports shall be provided for precise alignment of
modules into power and signal connector blocks.
b.
With modules removed, racks shall provide clear front
access to all load, neutral and control wire
terminations.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
6.
7.
8.
9.
University of Georgia
RCE 2013029
Rack Enclosures shall support use of any combination of
rack option cards designed to provide additional rack
features. Rack option cards shall include:
a.
FLO - The Fluorescent Option Board shall provide
termination for 4 wire low voltage electronic
fluorescent dimming ballasts. FLO shall provide 24,
0-10Vdc outputs.
b.
DALI - The DALI Option Board shall provide
termination for DALI fluorescent dimming ballasts.
DRd shall provide 24, DALI outputs for up to 63
ballasts each in a broadcast mode.
Optional floor mounting pedestal shall be available for the
12-module rack.
Racks enclosures shall be designed for use with AX series
auxiliary racks for Main Circuit Breaker, Main Lug, and
cross bussing applications.
Accessories
a.
RideThru Option (RTO)
1)
The Rack Enclosure shall support an optional,
short-term back-up power source for the
control electronics.
2)
The short-term back-up power source shall
automatically engage upon the loss of normal
power, seamlessly transitioning the supply
power for the control electronics power to itself.
3)
The short-term back-up power supply shall
detect the return of normal power, and
seamlessly return the control electronics to
normal power.
4)
The short-term back-up power source shall
support the control electronics for at least 10
seconds.
b.
BatteryPack Option (BPO)
1)
The Rack Enclosure shall support an optional,
long-term back-up power source for the control
electronics.
2)
The long-term back-up power source shall
automatically engage upon the loss of normal
power, seamlessly transitioning the supply
power for the control electronics power to itself.
3)
The long-term back-up power supply shall
detect the return of normal power, and
seamlessly return the control electronics to
normal power.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4)
5)
C.
University of Georgia
RCE 2013029
A test switch/indicator shall be available
without opening the rack door or removal of
any modules/components.
The long-term back-up power source shall
supply power to the control electronics for at
least 90 minutes.
Electrical
1.
Rack enclosures shall be available in 100, 120, 230, 240 and
277 volt, three-phase, main lug configurations.
a.
120 volt rack enclosures shall be field configurable for
single phase operation without the need for additional
components
2.
Rack enclosures shall be completely pre-wired by the
manufacturer. The contractor shall provide input feed, load,
and control wiring.
3.
Standard Short Circuit Current Ratings (SCCR) shall be
22,000 at 100-277 Volt
a.
Higher SCCR ratings, up to 100,000 amps SCCR at
120V, shall be possible when used with an AX series
Auxiliary Rack Enclosure.
b.
Higher SCCR ratings, up to 65,000 amps SCCR at
240V and 277V, shall be possible when used with an
AX series Auxiliary Rack Enclosure.
4.
All control wire connections shall be terminated via factory
provided connectors.
5.
Rack enclosures shall support dimming for incandescent,
fluorescent, neon, cold cathode, electronic low voltage and
magnetic low voltage transformer load types.
6.
The rack enclosure shall support 16-bit DMX input
7.
The rack enclosure shall support 65,000 steps of dimming.
8.
The rack enclosure dimming engine shall support multiple
dimmer curves including modified square law, linear,
switched, fluorescent, pre-heat and electronic low voltage.
9.
The rack enclosure shall support voltage regulation
including, minimum and maximum scale voltages with
offsets
10. Rack enclosure shall support a UL924 listed contact input for
emergency lighting control bypass.
a.
Emergency lighting input shall support load shedding
11. Rack enclosures shall be designed to support the following
wire terminations:
a.
AC
b.
Echelon link power (Belden 8471 or equivalent)
c.
24Vdc (2- 16AWG Wire)
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
d.
D.
5.2
DMX512A Port A (In or Out) (Belden 9729 or
equivalent)
e.
DMX512A Port B (Out) (Belden 9729 or equivalent)
f.
RS232 Serial In/Out (Belden 9729 or equivalent)
g.
Unshielded Twisted Pair (UTP) Category 5/5e
Ethernet
h.
Contact Closure In (14AWG to 26AWG Wire)
i.
Contact Closure Out (14AWG to 26AWG Wire)
1)
Contact Closure Out shall provide 1A @
30vDC
12. Station Power Modules
a.
Station power modules shall provide LinkPower for up
to 32 stations and 1.5A@24VDC of Auxiliary (AUX)
power.
b.
Station power repeater modules shall provide
LinkPower for 30 stations and1.5A@24VDC of
Auxiliary (AUX) power.
c.
Station power module shall support over-current/short
protection for LinkPower and Auxiliary (AUX) power.
LinkPower shall support fault detection on each leg of
the balanced data bus.
13. All control wire connections shall be terminated via factory
provided connectors.
14. Main feed lugs shall accept a maximum of 350 MCM wire.
15. Load terminals shall accept a maximum of #6 AWG wire.
Thermal
1.
Ambient room temperature: 0-40°C / 32-104°F
AMBIENT HUMIDITY: 10-90% NON-CONDENSINGCONTROL
PROCESSOR MODULES
A.
B.
C.
D.
E.
The Architectural Control Processor shall be the Unison Paradigm
P-ACP Series Control Processor as manufactured by Electronic
Theatre Controls, Inc., or equal.
The Architectural Control Processor (ACP) assembly shall be
designed for use in DRd Series Dimming Enclosures and ERn
Series Control Enclosures.
The processor shall utilize microprocessor based, solid state
technology to provide multi-scene lighting and building control.
ACP shall support functions such as station programming, macro
sequencing, electronic lockout, room combine and astronomical
time clock events. ACP station processor shall allow configuration
of the control system via the menus. See software section for
additional system details.
When used in a dimming enclosure, the ACP shall allow access to
dimming control menus including the status screen, dimming
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
F.
G.
H.
I.
J.
K.
5.3
University of Georgia
RCE 2013029
configuration screen, backup menu, test menu and configuration
menu.
One ACP shall be rated to drive 1024 channels of control, 1024
zones, 64 rooms, 512 presets, 62 button or button/fader stations
and 6 Touchscreen Stations
ACP module electronics shall be convection cooled.
The ACP shall provide front-panel RJ45 jack, Secure Digital (SD)
card slot, and Universal Serial Bus (USB) Port for configuration and
data exchange.
Architectural Lighting System configuration and program
information shall be stored in flash memory, which does not require
battery backup.
The ACP shall be contained in a plug-in assembly and require no
discrete wiring connections; all wiring shall be terminated into
Dimming or Control Enclosure.
The ACP shall support the following communications:
1.
Echelon LinkPower
2.
10/100BaseTX, auto MDI/MDIX, 802.3af compliant Ethernet
networking with TCP/IP, ESTA BSR E1.17 Advanced
Control Networks (ACN) and ESTA BSR E1.31 (sACN)
Protocols
3.
EIA-232 serial protocol
4.
ESTA DMX512A, configurable as input or output ports
5.
Dry contact closure inputs
6.
Dry contact closure outputs, rated at 1A@30VDC
STATIONS
A.
B.
C.
D.
E.
F.
The Lighting Control Stations shall be the Unison Heritage UH
Series Control Stations as manufactured by Electronic Theatre
Controls, Inc., or equal.
Mechanical
Unison Heritage Button and Button/Fader Stations shall operate
using up to sixteen programmable faders and twelve programmable
buttons.
All button/fader stations shall be available with white, cream, ivory,
gray or black faceplates, fader knobs, and buttons.
1.
Manufacturer's standard colors shall conform to the RAL
CLASSIC Standard.
Stations shall have indicators lights at each button or fader.
1.
Indicators shall be comprised of red, green and blue LED's
2.
Indicator color and state (steady On, Blink, Off) shall be
configured in software, and shall operate relative to the
button or fader it is associated with.
All faceplates shall be designed for flush or surface mounting.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
G.
H.
I.
J.
K.
L.
M.
N.
O.
5.4
University of Georgia
RCE 2013029
Station faceplates shall be constructed of ABS plastic and shall use
no visible means of attachment.
Station faceplates shall be indelibly marked for each button or fader
function.
The manufacturer shall supply back boxes for flush mounted half
gang stations and for all surface mounted stations.
Functional
The Unison Paradigm Control System shall be designed to allow
control of lighting and associated systems via Button, Button/Fader,
and Interface or Astronomical time clock controls. System shall
allow the programming of presets, sequences, macros and time
clock events.
Station Button, Button/Fader, and Interface) control components
shall be designed to operate standard default or custom system
functions. Components shall operate default functions unless reassigned via LightDesigner, the Windows-based configuration
program.
Stations (Button and Button/Fader) shall allow programming of
station and component electronic lockout levels via LightDesigner.
Electrical
Unison control station wiring shall be an Echelon® Link power
network.
1.
Link power shall utilize low-voltage Class II unshielded
twisted pair, type Belden 8471 or equivalent, and one #14
ESD drain wire (when not installed in grounded metal
conduit).
2.
Touchscreen and Interface stations shall also require (2) #16
AWG stranded wires for 24Vdc operating power. 24Vdc
wiring shall be topology free.
3.
Network wiring may be bus, loop, home run, star or any
combination of these.
4.
Network insulation displacement connectors shall be
provided with all stations.
TOUCHSCREEN CONTROL STATION
A.
B.
C.
D.
The Touchscreen Control Stations shall be the Unison Paradigm
Touchscreen P-LCD Series Control Stations as manufactured by
Electronic Theatre Controls, Inc., or equal.
General
Touchscreen stations shall support default and fully graphical
control pages.
The Touchscreen station shall operate using graphic buttons,
faders and other images on at least 30 separate programmable
control pages.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
E.
F.
G.
University of Georgia
RCE 2013029
Touchscreen stations shall also allow programming of page passcode, lock out and visibility levels.
Mechanical
1.
Touchscreen stations shall consist of a seven inch, backlit
liquid crystal display (LCD) with a minimum resolution of
800 by 400 pixels and 12-bit color depth with a touch
interface.
2.
Touchscreen bezels shall be constructed of aluminum and
shall have no visible means of attachment.
a.
The bezel shall install and remove without the use of
tools.
b.
The bezel shall provide two working positions for the
Touchscreen: service and operating.
3.
The Touchscreen shall have a protective overlay over the
display.
a.
The overlay shall reduce wear
b.
The overlay shall reduce glare
4.
The manufacturer shall provide backboxes for all LCD
stations.
a.
Flush back box dimensions shall be 7.94” wide x
5.33” high x 3.25” deep
b.
Surface back box dimensions shall be 8.3” wide x 5.6”
high x 2.55” deep
Electrical
1.
Touchscreens shall be powered entirely by the System
network.
2.
Touchscreens shall connect to the System using an Ethernet
network with Power over Ethernet (PoE) or the Unison
control station Echelon® Link power network.
a.
Ethernet Network
1)
Ethernet network shall be 10/100BaseTX, auto
MDI/MDIX, 802.3af compliant.
2)
Network shall utilize Unshielded Twisted Pair
(UTP) Category 5 wiring.
b.
Echelon® Link power network.
1)
Link power shall utilize low-voltage Class II
unshielded twisted pair, type Belden 8471 or
equivalent, and one #14 ESD drain wire (when
not installed in grounded metal conduit).
2)
Touchscreen stations shall also require (2) #16
AWG stranded wires for 24Vdc operating
power. 24Vdc wiring shall be topology free.
3)
Network wiring may be bus, loop, home run,
star or any combination of these.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4)
H.
I.
University of Georgia
RCE 2013029
Network insulation displacement connectors
shall be provided with all stations.
Functional
1.
System
a.
The Touchscreen shall support configuration firmware
upload from a Paradigm Processor as proxy
b.
The Touchscreen shall support configuration or
firmware upload from local removable media
2.
Setup Mode
a.
There shall be a setup display that is separate from
any user-defined configuration
b.
It shall be possible to view and modify connectivity
settings
c.
It shall be possible to view status information
d.
It shall be possible to view and modify LCD screen
settings
e.
It shall be possible to perform Touchscreen calibration
f.
It shall be possible to view and modify audio settings
g.
The appearance of the setup display shall be
standard and not editable
h.
The setup display may be invoked from within the
user-defined configuration and/or physical button on
the Touchscreen
i.
There shall be a default protected method to invoke
the setup display
3.
Configurations
a.
It shall be possible to have multiple configurations
stored within an LCD Station
b.
Only one configuration may be active on the LCD
Station
c.
It shall be possible for Touchscreen Stations
connected via the Echelon® Link power network to
select a configuration automatically based on the
configuration of the physical connection.
d.
Where multiple configurations are stored there shall
be a boot menu to allow selection of a configuration
e.
Each configuration shall be identified as a different
Station within the System
Operation
1.
The Unison Paradigm Control System shall be designed to
allow control of lighting and associated systems via
Touchscreen controls. System shall allow the control of
presets, sequences, macros and time clock events.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
a.
b.
c.
d.
University of Georgia
RCE 2013029
System presets shall be programmable via Button,
Button/Fader, Touchscreen, or LightDesigner
software.
1)
Presets shall have a discrete fade time,
programmable from zero to 84,600 seconds
with a resolution of one hundred milliseconds.
2)
Presets shall be selectable via Touchscreen
stations.
System macros and sequences shall be
programmable via LightDesigner system software.
1)
Macro and sequence steps shall provide user
selectable steps, and allow the application of
conditional logic.
2)
Macro and sequences shall be activated by
button, time clock event or LightDesigner
software.
System time clock events shall be programmable via
the Touchscreen, LightDesigner system software, the
processor user interface, or the internal web server.
1)
Time clock events shall be assigned to system
day types. Standard day types include:
anyway, weekday, weekend, Sunday, Monday,
Tuesday, Wednesday, Thursday, Friday and
Saturday. System shall support programming
of additional custom or special day types.
2)
Time clock events shall be activated based on
sunrise, sunset, time of day or periodic event.
System shall automatically compensate for
regions using a fully configurable daylight
saving time.
Touchscreen stations shall be designed to operate
standard default or custom system functions.
Components shall operate default functions unless reassigned via LightDesigner, the Windows-based
configuration program.
1)
Optional button functions include: preset
selection, manual mode activation, record
mode activation, station lockout, raise, lower,
macro activation, and cue light, or room
join/separate.
2)
Optional fader functions include master control,
individual channel control, fade rate control or
preset master control.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
e.
f.
g.
5.5
University of Georgia
RCE 2013029
Touchscreen stations shall allow programming of
station and component electronic lockout levels via
LightDesigner.
It shall be possible to adjust LCD contrast and
brightness.
It shall be possible to program the station to dim
during periods of inactivity.
BUTTON STATIONS
A.
B.
C.
The Lighting Control Stations shall be the Unison Heritage UH
Series Control Stations as manufactured by Electronic Theatre
Controls, Inc., or equal.
Mechanical
1.
Unison Heritage Button and Button/Fader Stations shall
operate using up to sixteen programmable faders and
twelve programmable buttons.
2.
All button/fader stations shall be available with white, cream,
ivory, gray or black faceplates, fader knobs, and buttons.
a.
Manufacturer's standard colors shall conform to the
RAL CLASSIC Standard.
3.
Stations shall have indicators lights at each button or fader.
a.
Indicators shall be comprised of red, green and blue
LED's
b.
Indicator color and state (steady On, Blink, Off) shall
be configured in software, and shall operate relative
to the button or fader it is associated with.
4.
All faceplates shall be designed for flush or surface
mounting.
5.
Station faceplates shall be constructed of ABS plastic and
shall use no visible means of attachment.
6.
Station faceplates shall be indelibly marked for each button
or fader function.
7.
The manufacturer shall supply back boxes for flush mounted
half gang stations and for all surface mounted stations.
Functional
1.
The Unison Paradigm Control System shall be designed to
allow control of lighting and associated systems via Button,
Button/Fader, and Interface or Astronomical time clock
controls. System shall allow the programming of presets,
sequences, macros and time clock events.
2.
Station Button, Button/Fader, and Interface) control
components shall be designed to operate standard default
or custom system functions. Components shall operate
default functions unless re-assigned via LightDesigner, the
Windows-based configuration program.
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
3.
D.
6.
Stations (Button and Button/Fader) shall allow programming
of station and component electronic lockout levels via
LightDesigner.
Electrical
1.
Unison control station wiring shall be an Echelon® Link
power network.
a.
Link power shall utilize low-voltage Class II
unshielded twisted pair, type Belden 8471 or
equivalent, and one #14 ESD drain wire (when not
installed in grounded metal conduit).
b.
Touchscreen and Interface stations shall also require
(2) #16 AWG stranded wires for 24Vdc operating
power. 24Vdc wiring shall be topology free.
c.
Network wiring may be bus, loop, home run, star or
any combination of these.
d.
Network insulation displacement connectors shall be
provided with all stations.
INSTALLATION
6.1
GENERAL
A.
B.
C.
6.2
Verify that job conditions are ready to receive work of this section.
Notify Architect of any existing condition, which will adversely affect
execution. Beginning of execution will constitute acceptance of
existing conditions.
Verify that field measurements are as shown on shop drawings.
Verify that mechanical, electrical, and other items affecting work of
this section are in place and ready to receive the work.
INSTALLATION
A.
B.
C.
Install using skilled workmen in accordance with manufacturer's
printed instructions and recommendations.
Install work in accordance highest industry standards. Handle
materials to avoid dents and other damages.
Set and secure materials and components rigid, plumb, and
square.
END OF SECTION 16760
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
SECTION 27 4000
AUDIO VISUAL SYSTEMS
PART 1 - GENERAL
1.1
DESCRIPTION
A.
The work required under this section of the specifications consists of the
furnishing, installation, and programming of independent audio systems for the
Talmadge Hall Auditorium at Rock Eagle 4H Center in Eatonton, Georgia.
Reference floor plan drawings for all equipment locations. In addition to all
audio visual components, the contractor shall be required to provide
coordination with the electrical contractors for all raceway to support these
technical systems.
B.
The audio visual scope of work will require the contractor to provide a complete,
quality operating system. A factory-approved representative shall complete all
system connections. A factory approved and factory trained representative of
the contractor shall complete all onsite programming of equipment.
C.
The contractor shall provide all labor, materials, equipment, and supervision to
install specified systems. The installation, testing, and commissioning of all
equipment shall be the full responsibility of the audio visual contractor for this
project.
1.2
QUALITY CRITERIA AND STANDARDS
A.
All audio visual wiring, devices, and equipment shall comply with applicable UL,
NEC, and NEMA code standards. All audio visual equipment shall be UL-listed
and labeled.
B.
Audio visual wiring systems shall conform to established trade and industry
standards. The following specifications and standards are incorporated into
and become a part of this Specification by reference.
1.
2.
3.
4.
5.
C.
AES14-1992 (r2004): – AES Standard for Professional Audio Equipment.
AES26-2001– AES Recommended Practice for Professional Audio
ICEA S-80-576 ICEA Standard for Communications Wire and Cable for
Wiring of Premises
NFPA 70 National Electric Code
UL 50 Enclosures for Electrical Equipment
Installer's Qualifications:
1.
2.
Firm with at least 3 years of successful application, installation, and
testing experience on specified systems and equipment.
The Contractor must show proof of being in the audio visual trade for a
minimum of three years and provide three (3) references with contact
16050-1
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
3.
4.
1.3
University of Georgia
RCE 2013029
names and telephone numbers regarding successful completion of audio
visual projects of similar scope and size.
All supervisors and installers assigned to the installation of this system or
any of its components shall have factory certification from each
equipment manufacturer that they are qualified to install and test the
provided products. Unqualified staff shall not be used for the installation
of the equipment, system cables, and associated hardware.
All installers assigned to the installation of this system or any of its
components shall have a minimum of 3 years experience in the
installation of the specified audio visual equipment and components.
SUBMITTALS
A.
Product Data: Audio Visual contractor shall provide a numbered equipment list
of the systems devices he is providing. The list shall include quantity of items,
manufactures product number, description of item and audio visual specification
that it represents. Submit manufacturer's technical product technical data sheet
for each item of systems equipment in order of the numbered equipment list.
Submittal shall include drawings that contain complete floor plans and reflected
ceiling plans, wiring and schematic diagrams and other details required that
demonstrate that the system has been coordinated and will function as a
complete system. Drawings shall include vertical riser diagrams, equipment
rack details, elevation drawings, connector faceplate details, sizes, and type of
all cables and raceway.
B.
Test Plan: Contractor shall submit a test plan that defines the tests required to
ensure that the system meets technical, operational, and performance
specifications, 15 days prior to the proposed test date. The test plan must be
approved before the start of any testing. The test plan shall identify the
capabilities and functions to be tested, and include detailed instructions for the
setup and execution of each test and procedures for evaluation and
documentation of the results.
C.
Manufacturer Certification: Submit a letter from the manufacturer's
representative stating the proposed systems being submitted for review are in
accordance with the recommendations of the manufacturer.
1.4
A.
1.5
WARRANTY
All equipment shall be new and shall be under warranty for a period of one (1)
year, from the date of acceptance by the owner, against defects in equipment
or workmanship. Failed equipment shall be replaced by the contractor at no
cost to the owner. Owner's personnel may perform initial trouble investigation
but replacement of failed equipment and escalated problem support will be
handled by the contractor.
ACCEPTABLE MANUFACTURERS
16050-2
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
A.
1.6
University of Georgia
RCE 2013029
Reference Part 2 - Products Section of the specification for complete list of
acceptable manufacturers.
RECORD DRAWINGS
A.
At the time of final inspection, provide three (3) sets of complete data on Audio
visual System equipment used in this project. This data shall be in bound form
and shall include all shop drawings required for this project.
B.
All record drawings shall include "as built" system interconnection diagrams
with major components identified and number and type of interconnecting
conductors.
C.
Maintenance and operating instructions on all systems.
D.
Certification from system manufacturers that systems are installed in
accordance with manufacturer's recommendations and are functioning correctly
at the time of final inspection.
E.
As-built drawings to show raceway layout and wiring for all systems.
F.
Corrected point-to-point drawings for all systems with color code to show the
actual as-built condition.
PART 2 - PRODUCTS
2.1
A.
2.2
A.
GENERAL MATERIALS REQUIREMENTS
Provide all materials under this section of the specifications. Materials and
equipment shall be the manufacturers’ latest standard design that has been in
satisfactory use for at least 1 year prior to installation. See Part 3 - Execution
specification section for additional product requirements.
AUDIO MIXING CONSOLE
Audio Mixing Console shall be of the digital type with remote stagebox Input
and Output capabilities. Available system components shall include (but not be
limited to) equalizers, filters, dynamics/gain controls, routers, delays, remote
controls, meters, generators, and diagnostics. Channels shall gate silently for
system response and clarity. Ethernet communications shall be utilized for
software control and configuration. Audio mixer shall meet the following
specifications:
1.
2.
3.
Inputs: minimum 48, electronically balanced, on XLR plugs (via remote
stage boxes or console surface.
Preamps shall have -60 to +15 dbu sensitivity.
Console controls shall be available via surface control, tablet PC/iPad and
16050-3
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
4.
5.
6.
7.
8.
9.
B.
2.3
A.
WIRELESS MICROPHONES
Wireless microphones shall be of single rack unit multi-channel design. Signal
transmission shall be digital to maximize the availability of RF channels for
future expansion and digital system management and audio output shall be
available via category 5e cabling. Antenna combining shall be built in to the
systems without the need for expansion hardware. Wireless microphones shall
meet the following specifications.
9.
10.
11.
12.
13.
2.4
A.
digital computer interface through Ethernet connectivity.
iPad control app is required.
Input/Output expansion available via expansion card slot supporting
Dante™ digital audio protocol.
Dante™ Expansion card shall be provided.
Minimum of 20 mixable output busses shall be available on a minimum of
24 outputs.
Digital audio output shall be available via 2 channel AES-3 connection on
XLR connector and via digital expansion card slot.
Personal Monitor Mix connectivity through category 5e network cable
shall be available via built-in connection or add-on option card.
Acceptable: Allen & Heath GLD-80 (AR-2412 and AR-84 Stage Racks), or
comparable by Midas, Roland, Soundcraft, Avid, Digico, or Yamaha.
1.
2.
3.
4.
5.
6.
7.
8.
B.
University of Georgia
RCE 2013029
Four receivers in 1RU metal chassis with internal power supply
Individual gain controls, LED meters, and XLR outputs for each channel
64 MHz tuning range (region dependent)
Digital predictive switching diversity
RF cascade ports to allow distribution of RF signal to another unit
AES 256-bit encryption-enabled for secure transmission
Dante™ digital networked audio over Ethernet
Ethernet networking for frequency coordination and deployment across
multiple receivers
Up to 60 dB independently adjustable gain for each channel
Audio and RF LED meters with peak indicator
Switchable mic/line output level
Provide two directional wideband, passive, paddle antennas (i.e. Shure
PA805).
Provide Minimum of 8 channels with 8 handheld dynamic transmitters and
8 body-pack transmitters with omni-directional lavaliere mics.
Acceptable: Shure ULXD4Q receiver/ Shure ULXD-1 Body-Pack/ Shure ULXD2 Handheld Transmitters/ Shure PA805 antennas, or comparable by
Sennheiser, Audio-technica, Lectrosonics, or AKG.
EARSET MICROPHONE
Earset Microphone shall be an extremely low profile head-worn microphone
designed to provide maximum gain before feedback in general speech
16050-4
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
applications. Earset Microphone shall contain a condenser element that is held
close to the mouth by a thin boom. Coordinate finish color with owner. Earset
microphone shall meet the following specifications:
1.
2.
3.
4.
5.
B.
2.5
A.
Acceptable: Countryman E6 Omni or comparable from Sennheiser or DPA.
STEREO DI
Stereo Direct Injection Box with Unbalanced input and dual balanced output.
Stereo or summed mono operation selectable by user. Built in ground lift
switches to eliminate hum and a -20db pad. Outputs shall be left and right XLR
males. Stereo DI boxes shall meet the following specifications.
1.
2.
3.
B.
2.6
A.
PERSONAL MIXERS (Add-Alternate)
Personal Mixing units shall be provided for purposes of mixing individual
monitor systems. These units shall connect via category 5e cabling and have
the ability to independently create monitor mixes of a minimum of 16 channels
for on-stage talent.
6.
2.7
A.
2 Male, Panel-mount XLR Connectors.
1 1/8” stereo TRS connector on 3ft tail.
2 DBT Passive Balancing Transformers
Acceptable: RapcoHorizon LTI-1, or comparable by ProCo, Whirlwind,
Countryman, or Radial.
1.
2.
3.
4.
5.
B.
Detachable cable with connector to match supplied wireless microphone
transmitters.
Frequency Response: 20 Hz to 20,000 Hz.
Element Diameter: 0.1”
Weight: .07 oz (2 grams).
Provide quantity of three.
Category 5 digital audio input connectivity.
Minimum 16 mixable channels.
Stereo Headphone Output.
Direct connection to console via digital audio connection.
Provide one set of Shure SE315 earphones and earphone cables with
each mixer.
Provide an additional two sets total of Shure SE425 earphones for use
with low frequency instrument mixes.
Acceptable: Allen & Heath ME-1 or comparable by My-Mix, Aviom, or Roland
DIGITAL AUDIO SIGNAL PROCESSOR
Audio DSP shall be rack mounted. All internal processing shall be digital
16050-5
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
(DSP). Software shall be provided for creating/connecting DSP system
components within each hardware unit. Available system components shall
include (but not be limited to) various forms of: mixers (including automatic),
equalizers, filters, crossovers, dynamics/gain controls, routers, delays, remote
controls, meters, generators, and diagnostics. Channels shall gate silently for
system response and clarity. Ethernet communications shall be utilized for
software control and configuration. Audio DSP shall meet the following
specifications:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
B.
2.8
Inputs: minimum 8, electronically balanced, on plug-in barrier-strip
connectors.
Expandable Digital audio input and output capability Via AVB or Dante™
digital audio networking protocols.
Digital Audio Connectivity shall support most current Dante™ Protocols.
Maximum input level: +24dBu
Equivalent Input Noise (EIN): Less than -125dBu with 150 Ohms source.
Outputs: Eight, electronically balanced, on plug-in barrier-strip
connectors.
Maximum output level: +24dBu
Digital Resolution/ Sample Rate: 24 bit, 48 kHz
Frequency Response: 20 Hz to 20 KHz (+0/-.4 dB)
Total Harmonic Distortion: Less than 0.04% (20Hz to 20 KHz, +4dBu
output, mic level input)
Dynamic Range: 107dB typical (20 Hz to 20 KHz).
Connections shall allow sharing of digital audio within multi-unit systems.
Software shall operate on a computer running Windows 8 or OSx
After initial programming, systems may be controlled using TCP/IP, USB,
or RS-232 serial communication by third party control systems (such as
AMX), by PC computer, and/or by dedicated control devices.
UL listed and shall follow AES48-2005 Grounding and EMC practices.
Acceptable: Symetrix Edge or Radius DSPs or comparable by BSS or Biamp.
MULTI-CHANNEL AUDIO AMPLIFIERS
A.
Amplifiers shall be rack mounted. Amplifiers shall be designed for use in a
commercial sound re-enforcement application. Amplifiers shall contain circuit
breaker for overload protection; high temperature automatic reset protection,
and electronic output protection. Amplifier controls shall have on/off switch and
pilot light, master gain control, signal input/output and input channel controls.
Amplifiers shall not be loaded over 70% of the power output rating and shall be
capable of power output ratings equivalent to or greater than the peak draw
level of the associated speakers.
B.
Amplifier shall meet the following specifications:
1.
Mounting: Rack mounted.
2.
Outputs: Both low impedance (4/8 ohms) and constant voltage
(70/100V).
3.
Frequency Response: Within plus or minus 1 dB from 20 to 20,000 Hz.
4.
Minimum Signal-to-Noise Ratio: 100 dB, at rated output.
16050-6
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
5.
6.
7.
8.
9.
C.
2.9
University of Georgia
RCE 2013029
Total Harmonic Distortion: Less than .3 percent at rated power output
from 20 to 20,000 Hz.
Power Draw at Idle: Less than 80 watts.
Controls/Indicators: On/off, input levels, selection of bridge mode for
each pair of channels, high pass filter. Power on, signal presence, and
clipping indicators.
Protection: Built-in circuits monitor both current and temperature.
Cooling: Fan cooled.
Acceptable: Lab Gruppen C series or comparable from Electrovoice or QSC.
MAIN CLUSTER LOUDSPEAKERS
A.
Main cluster loudspeakers shall be mounted and arrayed as indicated in
contract documents to provide optimum coverage of mid and far seating areas.
Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be
installed in full compliance with rigging methods approved by a structural
engineer. Rigging shall include capability for independent horizontal and
vertical angle adjustment.
B.
Main Loudspeaker specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
C.
2.10
A.
Frequency Response: 40-18,000 Hz.
Sensitivity: LF-101 dB, MF-104 dB, HF- 109 dB (1W/1m).
Power Capacity, watts: LF-1000; MF/HF-300 (RMS).
Max. Peak SPL: LF- 137 dB, MF- 135 dB, HF- 134 dB.
Crossover Frequencies: 350, 1500 Hz.
Nominal Impedance: LF- 4 ohms, MF/HF- 4 ohms.
Coverage Pattern: 90 degrees by 40 degrees.
Low Frequency Transducer: dual 12” with 4” voice coil.
Mid Frequency Transducer: horn-loaded 10”
High Frequency Transducer: 2.0" exit compression driver.
Enclosure Type: Multi-ply hardwood, perforated metal grille.
Enclosure Dimensions: 40.0"H x 24.0"W x 32.25"D.
Enclosure Construction: Multi-ply hardwood, perforated metal grille, 12
attachment points, black finish.
Weight: 206 lbs.
Acceptable: Renkus-Heinz STX7/94. Required pricing alternate: Electrovoice
EVF-1152D/96-BK.
DELAY LOUDSPEAKERS
Delay loudspeakers shall be mounted and arrayed as indicated in contract
documents to provide optimum coverage of rear seating areas. Audiovisual
contractor to provide all rigging hardware. Loudspeakers shall be installed in
full compliance with rigging methods approved by a structural engineer. Rigging
shall include capability for independent horizontal and vertical angle
adjustment.
16050-7
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
B.
Delay Loudspeaker specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
C.
2.11
University of Georgia
RCE 2013029
Frequency Response: 40-18,000 Hz.
Sensitivity: LF-101 dB, MF-101 dB, HF- 109 dB (1W/1m).
Power Capacity, watts: LF-800; MF/HF-150 (RMS).
Max. Peak SPL: LF- 136 dB, MF- 130 dB, HF- 131 dB.
Crossover Frequencies: 500, 1500 Hz.
Nominal Impedance: LF- 4 ohms, MF/HF- 8 ohms.
Coverage Pattern: 60 degrees by 40 degrees.
Low Frequency Transducer: dual 12” with 3” voice coil.
Mid Frequency Transducer: horn-loaded 8”
High Frequency Transducer: 1.0" exit compression driver.
Enclosure Type: Multi-ply hardwood, perforated metal grille.
Enclosure Dimensions: 40.0"H x 24.0"W x 32.25"D.
Enclosure Construction: Multi-ply hardwood, perforated metal grille, 12
attachment points, black finish.
Weight: 186 lbs.
Acceptable: Renkus-Heinz STX6/64. Required pricing alternate: Electrovoice
EVF-1122D2/96-BK.
DOWNFILL/CENTERFILL LOUDSPEAKERS
A.
Down Fill/ Center Fill loudspeakers shall be mounted and arrayed as indicated
in contract documents to provide optimum coverage of near seating areas.
Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be
installed in full compliance with rigging methods approved by a structural
engineer. Rigging shall include capability for independent horizontal and
vertical angle adjustment.
B.
Down Fill/ Center Fill Loudspeaker specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
C.
Frequency Response: 55-18,000 Hz.
Sensitivity: 98 dB (1W/1m).
Power Capacity, watts: LF- 600, HF- 150 (RMS).
Nominal Impedance: LF- 4 ohms, HF- 8 ohms.
Coverage Pattern: 120 degrees by 60 degrees, rotatable waveguide.
Low Frequency Transducer: one 12” cone.
High Frequency Transducer: 2.0" exit compression driver.
Enclosure Type: Stage monitor shape, optimally vented.
Enclosure Dimensions: 23.0" H x 14.25" W x 12.25" D.
Enclosure Construction: Multi-ply hardwood, twelve universal M10
attachment points or u-bracket attachment points.
Finish: Black with perforated metal grille.
Weight: 67 lbs.
Acceptable: Renkus-Heinz PNX121M Required pricing alternate: Electrovoice
EVU-1082/95 (EVF-1122D2/96-BK for Center Fill position).
16050-8
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.12
University of Georgia
RCE 2013029
SUBBASS LOUDSPEAKERS
A.
Subbass loudspeakers shall be portable and shall be ground supported in front
of stage. Subs to provide low frequency extension of program audio. Provide
quantity as indicated in plans.
B.
Subbass Loudspeaker specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
C.
2.13
Frequency Response: 45-200 Hz.
Sensitivity: 100 dB (1W/1m).
Power Capacity, watts: 2400 Program.
Nominal Impedance: 4 ohms.
Transducers: dual 18”.
Enclosure Type: Vented.
Enclosure Dimensions: 48.0"W x 22.5"H x 23.875"D.
Enclosure Construction:0.75” birch plywood.
Required Options: Speakon connectors.
Finish: Black with black powder-coated perforated steel grille.
Weight: 180 lbs.
Acceptable: OAP TR218 or comparable from Electrovoice or Renkus-Heinz
SURROUND SOUND LOUDSPEAKERS
A.
Surround sound loudspeakers shall be mounted on theater side and rear walls
as indicated in contract documents to provide playback of surround sound
channels in cinema applications. Audiovisual contractor to provide all rigging
hardware. Loudspeakers shall be installed in full compliance with rigging
methods approved by a structural engineer. Rigging shall include capability for
vertical angle adjustment.
B.
Surround Sound Loudspeaker specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
C.
Frequency Response: 80-20,000 Hz.
Sensitivity: 94 dB (1W/1m).
Power Capacity: 100 watts (RMS).
Nominal Impedance: 8 ohms.
Coverage Pattern: 120 degrees by 60 degrees, rotatable waveguide.
Low Frequency Transducer: one 8” cone, 2” voice coil.
High Frequency Transducer: 1.0" exit compression driver.
Enclosure Type: Stage monitor shape, optimally vented.
Enclosure Dimensions: 19.75" H x 9.75" W x 9.0" D.
Enclosure Construction: Multi-ply hardwood, twelve universal attachment
points or u-bracket attachment points.
Finish: Black with perforated metal grille.
Weight: 25 lbs.
Acceptable: Renkus-Heinz TRX81 Required pricing alternate: Electrovoice
EVU-1082/95.
16050-9
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.14
A.
STAGE MONITOR LOUDSPEAKERS
Monitor speakers shall be used for user defined needs as on-stage sound
reinforcement for musicians and other talent. They will be powered by remote
amplification using 12AWG speaker cable terminated with Neutrik NL4
connectors. Stage monitors shall meet the following specifications.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
B.
2.15
A.
University of Georgia
RCE 2013029
8” High-Output LF Transducer
1” Exit True Compression Driver
90° x 50° Coverage Pattern
Rotatable Horn Design
Integral Monitor Angle on Enclosure
200W Cont., 800W Peak Power Handling
High Sensitivity, 123 dB Maximum SPL
Built-In Pole Mount
Integral Handle Pocket for Easy Carrying
Provide one 15’ portable monitor cable with each unit.
Acceptable: Electrovoice ZX1-90 or comparable by Tannoy, JBL, or RenkusHeinz.
SURROUND SOUND DECODER
Surround Sound Decode for Dolby and DTS should provide audio signal
decoding and distribution for surround sound speaker systems. It should be
capable of both 6.1 and 7.1 decode. Surround Sound Decoders should meet
the following specifications.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Supports Dolby® and DTS® source formats and listening modes as well
as PCM and analog audio — Dolby Digital, Dolby Digital EX, Dolby Pro
Logic, Dolby Pro Logic II, Dolby Pro Logic IIx, DTS Digital Surround, DTSES® Discrete 6.1, DTS-ES Matrix 6.1, DTS 2-Channel, DTS 96/24®, DTS
96/24 ES Matrix, DTS Neo:6®, Uncompressed PCM, Analog stereo or
mono
Inputs: Four S/PDIF digital inputs on two optical connectors and two
coaxial RCA connectors; one balanced or unbalanced stereo analog input
on a 5-pole captive screw connector.
Outputs: Three balanced or unbalanced stereo line level outputs on 6pole captive screw connectors for Front, Surround, and Back; two
balanced or unbalanced mono line level outputs on 3-pole captive screw
connectors for Center and Subwoofer.
Automatic surround sound format detection and decoding.
Seven channel, nine-band parametric EQ.
Up to 100 ms lip sync adjustment on each input.
Test signals for setup and calibration.
Distance compensation adjustment for each speaker.
Rack-mountable enclosure
Front panel security lockout.
16050-10
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
11.
12.
B.
2.16
University of Georgia
RCE 2013029
RS-232 control port.
Internal universal power supply.
Acceptable: Extron SSP-7.1 or comparable by D&M Professional, Lexicon, or
Crestron.
NETWORK ROUTER
A.
The Network Router shall be rack mounted as provided in the contract
documents and interfaced to the owner provided network.
B.
The Network Router shall meet the following specifications:
1.
C.
2.6
Network switch minimum configuration shall be 24 x RJ45 10/100/1000
ports (IEEE 802.3 10Base-T, IEEE 802.3u 100Base-T, IEEE 802.3ab
1000Base-T gigabit Ethernet)
Acceptable manufacturers shall be Netgear, Dell, Cisco, HP, or D-Link.
LECTERN
A.
The Lectern shall provide a work service for presentations and shall be
designed to contain electronic equipment and the system control panel. The
interior shall have adjustable interior shelves, interior rack rails, and louvers for
venting. Doors shall be security doors and a service access door with locks.
The lectern shall have 4” heavy-duty lockable casters. Cabling between
lectern and lectern interface wall box shall have a 3” floor grommet for power
and audio visual cables. These audio visual cables shall be strain-relieved and
encased in expandable sleeve material for the run to the floor box. Lighting
shall be a Littelite as provided by manufacturer. Coordinate finish with architect
in order to match wood wall trim finish.
B.
Lectern specifications of equipment shall include:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Quantity=1.
Size approximately 40”w x 28”d x 45”h
Laminate finish
Flat work surface
Cut Out for cable connection box
Security doors with lock
Document camera pullout
Tower pc compartment
Adjustable shelf in pc compartment
Service access doors with lock
14RU rack rails, single bay
Casters
Little Lite
Grommets as required
DC Ventilation fan
16050-11
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
C.
Acceptable Manufacturers:
1.
2.17
University of Georgia
RCE 2013029
In-View Furniture or comparable unit from Miller’s Millwork.
FURNITURE-MOUNTABLE CABLE ENCLOSURE
A.
Furniture-Mountable Cable Enclosure shall be installed in lectern and shall
provide capacity for interface with future video system. Provide with multiple
cable grommets for audio and video cables to be installed at a future time.
Contractor shall provide for mounting in Lectern.
B.
Furniture-Mountable Cable Enclosure shall meet the following specifications:
1.
General
a.
Mounting: Furniture mount: With included hardware.
b.
Accessory Plates: various audio, video, control, and power
receptacle connector plates are available.
c.
Dimensions: 7.0”x7.0” (top plate), 6.4” x 6.4” x 4.75” HxWxD (box).
d.
Min./max. Table thickness: 0.375" to 2.00".
e.
Enclosure type: Metal
C.
Acceptable: Extron Cable Cubby 600 or comparable from FSR.
2.18
GOOSE-NECK MICROPHONE
A.
Gooseneck microphone shall be mounted on lectern. It shall have shock
mounted base with internal on/off switch. The microphone shall be for use in a
commercial sound re-enforcement application.
B.
Goose Neck microphone shall meet the following specifications:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
C.
Frequency Range: 30–18,000 Hz.
Polar Pattern: Hypercardioid.
Sensitivity at 1,000 Hz: 8.5 mV/ Pa.
Equivalent Noise Level: 21 dB-A.
Sound Pressure Level for 1% THD: 133 dB.
S/N Ratio (A-weighted): 73 dB.
Power Requirement: 9-52 volts.
Connector: 3-pin XLR type.
Finish: Dark gray matte.
Size: Diameter 0.35 in. length 5.4 in.
Included Accessories: Mount/adapter, Long gooseneck.
Lectern microphone shall be of the same manufacture and model and
shall have shock mount base unit that mounts into the lectern.
Acceptable manufacturers include:
1.
AKG.
2.
Sennheiser.
3.
Shure.
16050-12
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
2.19
University of Georgia
RCE 2013029
HAND-HELD MICROPHONE/DIRECT BOX PACKAGE
A.
Hand-Held Microphone/ Direct Box Package shall be provided for use in
supporting a variety of stage events and shall consist of a combination of
suspended choir microphones, loose microphones, and stage boxes.
Contractor to provide a 25’ XLR microphone cable with each loose microphone.
Confirm final microphone and direct box models and finishes with owner.
B.
Acceptable: Provide the following microphones and direct boxes with no
substitutions.
2.20
1.
Shure MX202 B/C choir mic, quantity=8.
2.
Shure DMK57-52 drum mic kit, quantity=1.
3.
Shure SM57-LC general purpose mic, quantity=3.
4.
Shure SM58-LC dynamic vocal mic, quantity=5.
5.
Shure Beta 87A condenser vocal mic, quantity=2.
6.
Shure SM-81-LC condenser overhead/piano mic, quantity=4.
7.
Sennheiser e609 general purpose mic, quantity=2.
8.
Rapco-Horizon DB-1 direct box, quantity=5.
MICROPHONE STANDS
A.
Microphone stands shall be shall be provided for use with systems
microphones and shall be for use in a commercial sound re-enforcement
reinforcement application.
B.
Systems microphone stands include:
2.21
A.
1.
Floor Base Stand with weighted base.
a.
24” to 60” Telescoping stand
b.
Finish Black
c.
Base - 12" Diameter weighted or tripod type.
d.
17” to 28” Telescoping boom arm (Finish Black)
e.
Provide Minimum quantity of 10
2.
Acceptable manufacturers include:
a.
König & Meyer - 201/2 – Black with 21140 Boom Arm
b.
Ultimate
c.
On-Stage
AMPLIFIER RACKS
Floor mounted Amplifier Racks shall be vertical welded metal racks with
uprights to mount equipment 19 inches wide. Uprights shall have 3-inch deep
16050-13
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
channels, 1-1/4 inches wide, drilled and tapped 12-24 in a 5/8 inch pattern.
Racks shall be provided with a standard top cross-member and pre-drilled base
plate to allow floor fastening. Vertical cable management devices shall be
integral to the rack. Two power strips with six outlets each shall be mounted on
the racks.
B.
Racks to be provided with the following additional features:
1.
2.
3.
4.
5.
6.
7.
8.
9.
C.
Acceptable manufacturers include:
1.
2.
3.
2.22
Finish: Textured black powder coat.
Size: Racks to provide 44 equipment mounting spaces and to provide 24”
of usable mounting depth minimum.
Racks to be provided with lockable rear doors.
Racks to be gang-able and provided with side panels.
Racks to be provided with rack mount fan kit – 3 fans @ 315 CFM.
Racks shall be provided with isolated ground power receptacles.
Racks shall be electrically isolated from conduit at conduit entrance to
racks. Provide safety ground wire from rack to panelboard per National
Electrical Code.
Racks shall be electrically isolated from concrete or metal floors using an
insulation material beneath the rack.
Provide quantity of three (3) racks.
Mid Atlantic.
Atlas-Soundolier
Lowell
POWER CONDITIONER
A.
Power conditioners shall be mounted in stage rack and shall be for use in a
commercial sound reinforcement application. Power on sequencing shall be
provided for amplifiers in rack through manual operation of power controls.
B.
Power conditioners shall meet the following specifications:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Maximum load: 20 amps (2400 watts at 120 VAC).
Input Voltage Range: 85 to 135 VAC.
Mains Wiring analyzer: Detects 1 normal mode and 5 fault modes.
Spike Protection Modes: Line to neutral, neutral to ground, line to ground
Spike Clamping Voltage: TVSS rating 400V peak, L-N, N-G, L-G (tested
to UL 1449)
Response time: One nanosecond
Maximum surge current: 6,500 amps (8 x 20 µs pulse)
Maximum spike energy: zero joules per node, 240 joules total protection.
Noise attenuation: Transverse: >50 dB, 1 to 120 MHz
Common mode: 20 dB at 150 kHz, rising to >40 dB, 1 to 120 MHz
Mechanical: Dimensions: 1.75" H x 19" W x 8" D.
Weight: 6 lbs (2.7 kg).
Construction: Steel chassis, zinc chromate plating; .125" brushed and
16050-14
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
14.
15.
C.
A.
Cable Harness System shall be provided as shown in contract documents for
infrastructure support of live events. Cable Harness System to consist of multipair cable and connectors that are suitable for touring use. Cabling to be premanufactured with one end cut to length and terminated in the field as required.
Cable lengths should be determined from field measurements or drawing
estimation. Cable Harness System specifications of equipment shall include:
2.
3.
4.
Wall plates should be labeled with connector function using silk-screened
text.
Rack panels and patch-bays shall be suitable for installation in a standard
equipment rack and should include lacing bars and stiffeners as required.
Cable snakes and patch cords should be labeled with function using
printed label covered with clear heat shrink.
Custom components to be manufactured by a single vendor.
Acceptable manufacturers include:
1.
2.
3.
2.23
Middle Atlantic
SurgeX
Furman Sound Inc.
Tripp-Lite
ETA Systems
CABLE HARNESS SYSTEM
1.
B.
black anodized aluminum front panel; 3 oz. copper double-sided glass
epoxy printed circuit board; all IC's in sockets.
Power consumption: Switch off: 6 watts. Switch on: 8.5 watts
Safety Agency Listings: UL listed, CUL listed.
Acceptable manufacturers include:
1.
2.
3.
4.
5.
2.22
University of Georgia
RCE 2013029
Rapco Horizon
Whirlwind
Pro-Co.
WIRING & CONNECTORS
A.
Basic speaker cables shall be multi-pair cables, stranded, tinned copper. Cable
shall be sized to provide optimum power to the end of the line speaker, with a
minimum sizing of 14 gauge. Cable shall be UL listed type 246A.
B.
For balance of A/V cables and connectors, reference one-line diagram in
contract documents and provide appropriate cables and connectors to ensure a
fully functional audio visual system.
C.
The video cabling shall be coaxial cable that is capable of supporting digital SDI
and HD-SDI video.
16050-15
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
D.
2.24
University of Georgia
RCE 2013029
UTP cabling shall be at a minimum of the following requirements.
1.
Minimum Bend Radius: 4.5 inches.
2.
No. of Conductors: Eight insulated conductors
3.
Standard lengths: 1000 Ft.
4.
Nom. DCR: 22.8 ohms pr 1k ft.
5.
Nominal Core Outside Diameter: 0.041
6.
Nom. Pair-to-Pair Skew: Group 1:1.5 ns/ 100 m
7.
Nominal Outside Diameter: 0.200 X 0.280 inches.
8.
Nominal Impedance: 100 ohms.
9.
Nominal Velocity of Propagation:71%.
10. Nominal Capacitance: 1pF/ft.
11. Nominal Attenuation at 155Mhz: -8.8 dB/100ft.
TRANSIENT VOLTAGE SURGE SUPPRESSION
A.
Transient voltage surge suppression devices shall be provided to protect power
strips in each rack and all equipment. Transient voltage surge suppression
shall be provided for all audio visual equipment devices.
B.
Transient voltage surge suppression devices shall be an industrial-grade surge
suppressor with EMI/RFI filtering.
C.
Transient voltage surge suppressors shall meet the technical requirements of
SurgeX Professional AC Power Products.
PART 3 - EXECUTION
INSTALLATION
3.1
A.
General: System components and appurtenances shall be installed in
accordance with NFPA 70, manufacturer's instructions, and as shown.
Necessary interconnections, services, and adjustments required for complete
and operable audio visual systems shall be provided. Components shall be
labeled in accordance with TIA/EIA 606. Penetrations in fire-rated construction
shall be fire-stopped. A/V cables shall not be installed in the same raceway
with AC power cables. Cables not installed in conduit or wire ways shall be
properly secured and neat in appearance and, if installed in plenums or other
spaces used for environmental air, shall comply with NFPA 70 requirements for
this type of installation.
B.
Rack Mounted Equipment
1.
3.2
Rack mounted equipment shall be securely fastened to racks by means
of the manufacturer's recommended fasteners.
GROUNDING/BONDING
16050-16
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
A.
University of Georgia
RCE 2013029
Ground all equipment in accordance with the National Electrical Code. Ensure
that a ground path exists to the building main electrical ground for all
equipment.
TESTING AND CHECK-OUT
3.3
A.
Testing requirements apply to all equipment. Contractor to test each audio
visual component as recommended by manufacturer. Test methods and test
results shall be submitted to the owner prior to final inspection.
B.
Materials and documentation to be furnished under this specification are
subject to inspections and tests. All components shall be terminated prior to
testing. Equipment and systems will not be accepted until the required
inspections and tests have been made, demonstrating that the audio visual
systems conform to the specified requirements, and that the required
equipment, systems, and documentation have been provided.
TRAINING
3.4
A.
The Contractor shall include in the base Contract all costs required to train
owners operating and maintenance personnel in the use and maintenance of
systems provided under this section of the Specifications. Instructors certified
in writing by the manufacturer of the specific system shall conduct training
sessions.
B.
Sessions shall be conducted for not less than four-hour periods during normal
working hours, i.e., Monday through Friday, 8:00 AM to 5:00 PM. Training
session schedules shall conform to the requirements of the owner; therefore,
such schedules shall be submitted to owner for approval not less than two
weeks prior to the training session. All training sessions shall be recorded for
future use. At Owner's discretion, provisions shall be made to allow up to two
owner personnel to participate in final system check out of all systems.
C.
Recordings shall be of professional quality for both video and audio and must
be approved by the Owner/User. Provide two copies to Owner/User. Time to
be included in base Contracts for specific systems shall be as follows:
1.
Audio Visual Systems- 16 hours
AS-BUILT DRAWINGS AND/OR DOCUMENTATION:
3.5
A.
As-built drawings shall be provided noting the exact cable path and cable
labeling information. The contractor shall provide drawings in .DWG format.
As-builts shall be submitted to the owner on formatted CD’s, saved as .DXF or
.DWG files. Redline hardcopies shall be provided as well. CAD generated asbuilt information shall be shown on a new layer named AS-BUILT.
1.
System Acceptance: Before the owner accepts the system, the contractor
16050-17
Talmadge Auditorium – Rock Eagle
Lighting, Audio-Visual
University of Georgia
RCE 2013029
shall be required to walk-through the installation with the owner's
representative and the design engineer to verify proper installation and
operation.
END OF SECTION 27 4000
16050-18
Download