Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16050 ELECTRICAL GENERAL PART 1 - GENERAL 1.01 SUMMARY A. Description: 1. 2. 3. B. Related Documents: 1. 2. 3. 1.02 Provide all materials, tools, and labor for a complete electrical installation as shown on the contract documents and indicated in the specifications. Procure all permits and licenses. Coordinate the electrical installation with the following: a. Owner, State Architect, Engineer of Record b. Contractors of other trades. c. Local Electrical and Building Inspectors, or the authority having jurisdiction. Electrical, "E", drawings. All working drawings included in the contract documents. Specifications of the following divisions/sections: a. Division 0 - Conditions of the Contract b. Division 1 - General Requirements ABBREVIATIONS A. The following abbreviations are used throughout Division 16 specifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. AFF: ANSI: ASTM: HVAC: IEEE: IES: ITL: NEC: NECA: NEMA: Above Finished Floor American National Standards Institute American Society for Testing and Materials Heating, Ventilating and Air Conditioning Institute of Electrical and Electronic Engineers Illuminating Engineering Society Independent Testing Laboratories National Electrical Code National Electrical Contractor Association National Electrical Manufacturers Association Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 11. 12. 13. 1.03 "Provide" means to furnish and install. CODES AND STANDARDS A. Comply with the following codes and published standards which are applicable to the electrical installation of this project: 1. 2. 3. 4. 5. 6. 7. 1.05 National Fire Protection Association Not in Contract Underwriters Laboratories, Inc. DEFINITIONS A. 1.04 NFPA: NIC: UL: University of Georgia RCE 2013029 NFPA 70 - National Electrical Code, 2011 edition NFPA 101 - Life Safety Code, latest edition International Building Code with Georgia Amendments Underwriters Laboratories Electrical Construction Directory (green book) Underwriters Laboratories Electrical General Information (white book) NFPA 72 International Commercial Energy Code with Georgia Amendments STANDARDS FOR MATERIALS AND WORKMANSHIP A. Use materials that are new and, where UL or ITL has established standards, listed and/or labeled. B. Organize and execute work so that finished appearance is neat; mechanical, plumb when vertical and level when horizontal. PART 2 - PRODUCTS 2.01 MATERIALS A. Provide equipment, products and materials shown on the drawings, as specified in the specifications or added by addendum. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.02 University of Georgia RCE 2013029 PLYWOOD BACKBOARDS A. 3/4"x size indicated on the drawings, A/D grade, paint two coats gray enamel PART 3 - EXECUTION 3.01 VISIT TO SITE A. 3.02 3.03 PROTECTION OF MATERIALS A. Cover fixtures, equipment and apparatus for protection against dirt, water, chemical or mechanical damage before and during construction. B. Keep all conduit and other openings protected against entry of foreign matter. C. Restore the original finish, including shop coat, of fixtures, apparatus or equipment that has been damaged prior to substantial completion. COORDINATION A. 3.04 Prior to submitting bid, visit site and become familiar with the existing conditions relating to Division 16 work. Prior to rough-in of any materials, coordinate with subcontractors the physical clearances for and sequencing of Division 16 work as it interfaces with and relates to architectural, structural, plumbing, HVAC, and pool systems. SHOP DRAWINGS AND PRODUCT DATA SUBMITTALS A. Submit shop drawings and/or product data for the electrical equipment and materials listed below. Check for compliance with contract documents and certify compliance by affixing Electrical Contractor's "Approved" stamp and signature. 1. 2. Shop drawings and product data: a. Dimmer System b. Life Safety System Product data only: a. Conduits, Couplings, Connectors, and Fittings Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual b. c. d. e. f. g. 3.05 Wiring Devices and Coverplates (receptacles, switches) Fuses and Circuit Breakers Junction Boxes, Outlet Boxes, and Floor Boxes Lighting Fixtures and Lamps Disconnect Switches, Motor Starters, and Motor Switches Wire and Cable B. Refer to respective sections for submittal instructions where instructions have been prescribed. C. Obtain shop drawing review by engineer before purchase of any equipment requiring shop drawing submittals. CERTIFICATION AND TEST REPORTS A. 3.06 University of Georgia RCE 2013029 Submit the following certifications and test reports to the Architect: 1. Certifications: a. Life Safety System MAINTENANCE MANUALS AND OPERATING INSTRUCTIONS A. Submit the following maintenance manuals and operating instructions to the Architect: 1. Life Safety System 2. Dimmer System B. Use a separate three ring binder for each maintenance manual and include wiring diagrams, maintenance instructions, parts list, maintenance tools list, manufacturer's and nearest dealer's name, addresses and telephone numbers. Organize into sections with index thumb-tab markers. C. Use a three ring binder for operating instructions with a separate thumb-tab in each section for each system or major item. Include in the instructions start-up, operation sequence, control, shut-down, safety features and seasonal adjustments. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3.07 OPERATIONAL TEST A. 3.08 3.09 At the time of the substantial completion job observation, perform a test of all light fixtures, electrical systems, equipment, machinery and appliances, in the presence of the Architect or his representative, which demonstrates that all of Division 16 systems are operational. JOB OBSERVATION ASSISTANCE A. During all job observations, provide an electrician with tools and volt/ammeter to accompany Architect and/or his representative. B. Remove any covers, trims or wiring devices and open all cabinets, disconnect switches or other equipment served electrically and designated by the Architect or his representative. C. Restore removed or opened equipment to its installed or closed position after the job observation. OWNER INSTRUCTION AND ASSISTANCE A. 3.10 University of Georgia RCE 2013029 At substantial job completion job observation, instruct the Owner's operating personnel in the operation, sequencing, maintenance and safety/emergency provisions of the electrical systems. AS-BUILT DRAWINGS A. Record on one set of electrical drawings all changes, deviations and underground conduits. Transfer that information to a reproducible drawing and deliver the drawing to the Architect. END OF SECTION 16050 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 Electrical_16SECTION 16110 RACEWAYS PART 1 - GENERAL 1.01 SUMMARY A. Description: 1. B. Related Sections: 1. 1.02 Provide continuous conduit systems - beginning at the service point, to all distribution equipment and to every outlet and piece of electrical equipment with conduits, couplers, supports, hangers, fittings, bushings and accessories. Section 16050 - Electrical General. SUBMITTALS A. Manufacturers Product Data Sheets. PART 2 - PRODUCTS 2.01 RIGID STEEL AND INTERMEDIATE METALLIC CONDUIT A. Conduit: 1. 2. Rigid ferrous steel pipe, hot-dipped galvanized or sherardized with smooth interior. Acceptable Manufacturers: a. Allied b. Triangle c. Wheatland Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. University of Georgia RCE 2013029 Couplings and Connectors: 1. Couplings: a. Hot-dipped galvanized or sherardized ferrous steel, 2. Connectors: a. Steel or malleable iron, threaded with throat bushing, lock nuts and, where prescribed, grounding lugs. Erickson: a. Malleable iron, concrete tight. Acceptable Manufacturers: a. Appleton b. Crouse Hinds c. Steel City d. Thomas & Betts threaded. 3. 4. C: Joint Compound: 1. 2. D. Anti-seize lubricant with rust and corrosion inhibitors and colloidal copper. Acceptable Manufacturers: a. Thomas & Betts Expansion Fittings: 1. 2. Steel with three cap nuts, phenolic bushing, packing ring, metallic copper grounding ring and copper bonding jumper. Acceptable Products: a. Crouse Hinds "XJ" b. O.Z. Gedney "AX" or "DX" c. Appleton "XJ" 2.02 ELECTRICAL METALLIC TUBING A. Conduit: 1. 2. Thin wall ferrous steel tubing, hot-dipped galvanized, smooth interior, square and reamed ends. Acceptable Manufacturers: a. Allied b. Wheatland c. Triangle Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Couplings and Connectors: 1. 2. C. Couplings: a. Steel, compression type, installed where exposed to moisture. b. Steel, setscrew type, when installed indoors. Connectors: a. Steel, compression type with nylon insulated bushings, locknuts, and where prescribed, grounding lugs, installed where exposed to moisture. b. Steel, setscrew type with nylon insulated bushings, locknuts, and where prescribed, grounding lugs, installed indoors. Expansion Fittings: 1. 2. 2.03 University of Georgia RCE 2013029 Steel with three cap nuts, phenolic bushing, packing ring, metallic copper grounding ring and copper bonding jumper. Acceptable Products: a. Crouse Hinds "XJ" b. O.Z. Gedney "AX" or "DX" c. Appleton "XJ" LIQUIDTIGHT FLEXIBLE CONDUIT A. Conduit: 1. 2. Galvanized steel single strip, interlocked, smooth inside and out, with liquid-tight flexible polyvinyl chloride outer jacket. Acceptable Manufacturers: a. Carlon b. Wheatland c. Allied Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Fittings: 1. 2. 2.04 Threaded corrosion-resistant steel or malleable iron with insulated throat bushing, liquid tight, locknuts and external ground lugs. Acceptable Manufacturers: a. Appleton b. O.Z. Gedney c. Thomas & Betts FLEXIBLE METAL CONDUIT A. Conduit: 1. 2. B. Galvanized steel single strip, interlocked, smooth inside and out. Acceptable Manufacturers: a. AFC b. Alflex c. General Cable Fittings: 1. 2. 2.06 University of Georgia RCE 2013029 Threaded corrosion-resistant steel or malleable iron with insulated throat bushing and lock nuts. Acceptable Manufacturers: a. Appleton b. O.Z. Gedney c. Thomas & Betts SEALS A. Fire Rated Seals: 1. Flanged three-hour fire and smoke stop. 2. Acceptable Products: a. O.Z. Gedney "CFSF" Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. University of Georgia RCE 2013029 Thruwall Seals: 1. Malleable iron, hot-dipped galvanized sleeve and sealing ring with pressure rings and sealing grommets. 2. Acceptable Products: a. O.Z. Gedney "FSK" and "WSK" b. Spring City "WEP" or "WDP" c. Thunderline Link Seal PART 3 - EXECUTION 3.01 3.02 APPLICATIONS A. Provide Rigid Metal Conduit or Intermediate Metallic Conduit for feeders, areas where exposed to moisture, exposed on exterior surfaces, and exposed interior from floor to 10'-0" or where exposed to physical abuse. B. Provide Electrical Metallic Tubing (EMT) for interior power circuits, branch circuits and system circuits in walls, elevated concrete slabs (those not on grade), plenums, attics or exposed above 10'-0", where not exposed to moisture. C. Provide Flexible Metal Conduit for: 1. Final connection link (minimum of 12", maximum of 36") to: a. Motors. b. Transformers. c. Mechanical equipment. 2. Connections between junction boxes and accessible recessed lighting fixtures. D. Non-metallic Conduit is Not Used On This Project. E. Provide Liquid-tight Flexible Metal Conduit for final connecting link (minimum of 12", maximum of 36") to the following: 1. Equipment connection in damp locations CONDUIT SUPPORT A. Intervals: Maximum 10 feet on center and within 3 feet of each outlet box, junction box, cabinet or fitting. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. University of Georgia RCE 2013029 Conduits 3/4" and smaller: 1. 2. Method a. When single conduit: Attach directly to building structure or suspend with 1/4" rod. b. When multiple parallel and adjacent conduits and: 1) When horizontal at structure: Attach directly to structure or to support framing attached to structure. 2) When horizontally suspended: Attach to support framing, suspended from building structure. 3) When vertical: Attach to support framing attached to building structure, wall structure or suspended from building structure. Conduit attachment: a. When direct to structure or single conduit suspended: Spring steel friction, spring steel latching or clamped with bolts or screws. b. When on support framing: Two section bolted conduit clamp. 3. 4. 5. C. Structural steel attachment: a. When single conduit: Spring steel friction, clamp with bolt or bolted. b. When hanger rod: Clamp with bolt or bolted. Concrete attachment: Steel preformed conduit clamp. Attach clamp with expansion anchor installed in drilled hole or with power fastening anchor designed to meet concrete specification. In either case, maintain design support of 300% or greater of load. Wood attachment: Wood screws or bolted with design support of 300% or greater of load. For 1" or larger: 1. Method: a. When single conduit: Attach directly to building structure or suspend with threaded rod. b. When multiple parallel and adjacent conduits: Attach to support framing attached to building structure, wall structure or suspended from building structure. 2. Conduit attachment: a. When single conduit: Bolted clamp. b. When on support framing: Two section bolted conduit clamp. 3. Structural steel attachment: Beam clamps with bolts or bolted directly to steel. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4. 5. D. 3.03 University of Georgia RCE 2013029 Concrete attachment: Provide preset insert prior to concrete pour or coordinate drill locations with Architect. When drilling provide expansion anchors. In either case, maintain design support of 300% or greater of load. Wood attachment: Wood screws or bolted with design support of 300% or greater of load. Framing: 1. Attachment, suspension and bearing members capable of supporting 300% of load. INSTALLATION A. For conduit layout follow, generally, the diagrammatic layout shown on plans. Provide offsets and routing changes to avoid structural, architectural or equipment elements. B. Provide 1/2" minimum size conduit. C. Conceal all conduit except where shown to be exposed. Install conduit concealed above a lay-in ceiling with clearance to allow easy removal of ceiling panels. D. Install exposed conduit parallel with or perpendicular to building walls at greatest height possible. Paint exposed conduit two coats of color directed by Architect. E. Extend homeruns from outlets shown to panel designated. Do not combine homeruns. F. Use benders designed for the size and type of conduit. Limit each bend to 90 degrees or less with a radius 10 times conduit diameter or greater for telephone system and 6 times conduit diameter or greater for all other systems. G. Provide insulated bushings at each end of every conduit run. H. Provide joint compound on rigid steel conduit and intermediate metallic conduit joints. I. Provide an Erickson type coupling where two segments of a conduit run must be joined and neither can be rotated. J. Close all conduit ends during construction with plastic conduit plugs. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 K. Install conduit no greater than 1" trade size in concrete slabs. Route conduit between top and bottom reinforcing steel and space parallel runs a minimum of 3" apart. L. Install conduit above water and steam piping where possible. M. Maintain grounding of metallic raceways with clean and tight connections. Provide grounding conductor in all conduit. N. Provide ground lugs on all conduit connectors to service equipment enclosures. O. Provide grounding wedge lugs or locknuts designed to bite metal on conduit connectors to panel cabinet pull boxes. P. Seal all conduits which extend from the interior to the exterior of the building to prevent the circulation of air. Q. Provide a thruwall waterproof seal on each conduit that penetrates a wall at a below grade level. R. Provide an expansion fitting in each conduit crossing a building expansion joint and locate the fitting at the joint. Also provide expansion fittings in building conduits exceeding 100 feet at intervals of 100 feet. S. Provide a fire rated seal on each conduit that penetrates any floor or fire rated partition. Match seal rating to floor or partition rating. T. Where liquids are present, form drip loops in liquid-tight flexible conduit to prevent liquid from running into connections. U. Blow out and swab all conduit clear of trash and water prior to pulling wire. V. Provide a nylon pullcord in all empty conduits. END OF SECTION OF 16110 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16120 CONDUCTORS PART 1 - GENERAL 1.01 SUMMARY A. Description: 1. B. Related Sections: 1. 1.02 Provide continuous color coded conductors beginning at the distribution equipment, to each outlet and each piece of electrical energy consuming equipment. Section 16050 - Electrical General SUBMITTALS A. Manufacturers Product Data Sheets. PART 2 - PRODUCTS 2.01 CONDUCTORS A. Copper Conductors: 1. 2. Soft drawn annealed copper, 98 % conductivity, without weld, splice or joint throughout its length; uniform in cross section without flaws, scales, or other imperfections with THHN/THWN or XHHW insulation. Acceptable Manufacturers: a. Anaconda b. Phelps Dodge c. Pirelli Cable d. Rome e. Southwire f. Triangle Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Aluminum Conductors: 1. C. E. F. 2.02 Not Used Configuration: 1. 2. D. University of Georgia RCE 2013029 No. 10 and smaller: No. 8 and larger: Solid Stranded Insulation - 600 Volts: 1. No. 6 and smaller: 2. No. 4 and larger: THHN, THWN XHHW Jacket Color: 1. No. 8 and smaller: 2. No. 6 and larger: Uniform colored jacket Black Jacket Markings: 1. Voltage 2. Insulation type 3. Conductor Size 4. Conductor type COLOR CODING TAPE A. Vinyl 3/4" wide with uniform color and adhesive backing. B. Acceptable Manufacturers: 1. Brady 2. 3M 3. Plymouth 4. Thomas & Betts Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.03 SPLICE AND TAP MATERIALS A. No. 10 and smaller: 1. Crimp type: Cylindrically shaped conductor sleeve for crimping copper conductors. Insulated with nylon or plastic cover. 2. Twist on: Inner spiral spring or threads for holding and making electrical contact between copper conductors and with outer long skirted insulated cover of nylon or plastic. B. No. 8 and Larger: 1. Set-screw or bolted type: Metal connectors for joining copper to copper, with bolts or set-screws to apply pressure to conductors. Insulate with nylon or plastic cover or with electrical tape. 2. Pressure type: Metal connectors for joining copper to copper, copper to aluminum, or aluminum to aluminum with power operated crimping tool. Insulate with nylon or plastic cover or with electrical tape. C. Acceptable Manufacturers: 1. 2. 3. 4. 5. 6. 7. 2.04 University of Georgia RCE 2013029 AMP Burndy Ideal Ilsco Panduit 3M Thomas & Betts CONDUCTOR TERMINALS A. Copper conductors: High conductivity copper terminal designed to hold conductor and make electrical contact by bolt, setscrew or power crimp and with spade to match equipment receiving conductor. B. Acceptable Manufacturers: 1. 2. 3. 4. 5. Burndy Ideal Ilsco Panduit Thomas & Betts Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.05 CONDUCTOR HARNESS A. Plastic or nylon self-locking straps (commonly referred to as zip-ties or tiewraps). B. Acceptable Manufacturers: 1. 2. 2.06 Panduit Thomas & Betts WIRE PULLING LUBRICANT A. Lubricating, insulating and chemically neutral to conductors, conductor insulation and conduits. B. Acceptable Manufacturers: 1. 2. 3. 2.07 University of Georgia RCE 2013029 Greenlee Ideal Polywater ELECTRICAL TAPE A. Vinyl plastic; moisture tight, resistant to ultraviolet radiation, alkalies, acids and corrosion; chemically neutral to conductors and conductor insulation; fire retardant; and single thickness dielectric strength equal to or greater than 10,000V. B. Acceptable Manufacturers: 1. 2. Scotch/3M Plymouth Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 PART 3 - EXECUTION 3.01 INSTALLATION A. Install the number of copper conductors indicated with a minimum of two (2) power conductors and one ground conductor being installed in each conduit not prescribed to be empty. Aluminum conductors may not be used . B. Minimum Conductor Size: No. 12 C. Complete installation of raceway run prior to pulling conductors. D. Install insulated bushings in conduit fittings prior to pulling conductors. E. Use wire pulling lubricants to reduce stress on conductors. Pull all conductors of a run together. Use pulling methods, which do not damage the raceway or conductors. F. Color Coding: 1. 2. 3. No. 8 and smaller: Uniform colored jacket with respective color below. No. 6 and larger: Two wraps of tape applied within 6" of each conductor end with respective color below. Conductor Color Code: 208Y/120V 480Y/277V 240D/120V Phase A Black Brown Black Phase B Red Orange Blue Phase C Blue Yellow Orange (208V) Neutral White Gray White Ground Green Isolated Ground Green w/ Yellow Stripe 4. For Different Voltages in Same Enclosure: Use a colored stripe (not green) on one neutral to differentiate between systems. Keep stripe color consistent throughout project. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 G. At outlets leave a minimum of 12" of conductor ends at each fixture outlet, device outlet and equipment outlet box. H. Conductor Terminals: 1. Single: Use terminals on conductors no. 8 and larger where equipment receiving conductors do not have conductor lugs with set-screw(s) 2. Multiple: Install terminals on conductors where more than one conductor is connected to a single lug. I. Route conductors in all switchboards, panelboards, motor control centers and terminal cabinets parallel to or at right angle to the enclosure's sides and tops. Group and harness conductors in those enclosures using conductor harness straps. J. Prior to energizing conductor, megger test feeder conductors for continuity and shorts. Correct deficiencies prior to energizing. K. Tighten all bolted connections in and to mechanical lugs to torque rating specified per manufacturer’s recommendations. L. Tighten all conductors with mechanical connections, torqued in accordance with the conductor and/or connector manufacturers markings as well as the values referenced in the following publications: 1. Underwriters Laboratories Electrical Construction Directory (Green Book). 2. Underwriters Laboratories Electrical General Information (White Book). END OF SECTION 16120 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16130 BOXES PART 1 - GENERAL 1.01 SUMMARY A. Description: 1. B. Related Sections: 1. C. Section 16050 - Electrical General. Standards: 1. 1.02 Provide electrical boxes or, where prescribed, conduit bodies for devices, outlets, splice connection points, raceway junction and conductor pulling points complete with supports, covers and accessories. Underwriters Laboratories labeled and listed for application specified. SUBMITTALS A. Manufacturers Product Data Sheets. PART 2 - PRODUCTS 2.01 INTERIOR OUTLET BOXES AND EXTENSIONS A. Galvanized steel, UL listed for application with conduit knockouts and threaded holes for mounting devices and/or coverplates. B. Minimum Sizes: 1. 2. 3. 4. Single Device: 3"H x 2"W x 2"D Gang Device: 3"H x 2"W (per gang) x 2"D Octagonal: 4"W x 1-1/2"D Square: 4" Square x 1-1/2"D Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. Acceptable Manufacturers: 1. 2. 3. 4. 2.02 University of Georgia RCE 2013029 Appleton Raco Steel City American Electric JUNCTION AND PULL BOXES A. Dry Locations: Galvanized sheet steel, NEMA 1, welded seams and cover held by stainless steel screws or bolts. B. Damp or Wet Locations: Cast malleable iron with corrosion-resistant finish, NEMA 3R, threaded conduit entries, neoprene coverplate gasket, and coverplate held by stainless steel bolts. C. Acceptable Manufacturers: 1. Appleton 2. Crouse Hinds 3. Hoffman 4. Killark PART 3 - EXECUTION 3.01 DEVICE APPLICATIONS A. Boxes for switches, receptacles, dimmers (designed for device box mounting) and future devices: 1. For dry Locations: a. When recessed: 1) For construction other than concrete or masonry, use interior outlet box. b. When surface: Cast box with threaded hubs Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 3.02 GENERAL APPLICATIONS A. For lighting fixtures, equipment connections, pullboxes for conduit 1" and smaller, and junction boxes for conduits 1" and smaller. 1. Recessed Interior Box: a. For construction other than concrete or masonry, use octagonal or square interior outlet box. b. For concrete: Concrete box c. For masonry: Concrete box or square interior box with masonry extension. 2. Box Above an Accessible Ceiling: Octagonal or square interior outlet box. 3. Exposed Interior Box: a. Above 8'-0": Octagonal or square interior outlet box or conduit body. b. 8'-0" and below: Cast box or conduit body. C. Integrally Mounted Boxes: Boxes which are an integral part of an equipment assembly from the manufacturer and are UL listed for the application may be used in lieu of the boxes prescribed above. 3.03 JUNCTION BOXES AND PULL BOXES (conduits larger than 1") A. Junction boxes or conduit bodies where junction is exposed. 3.04 SUPPORT A. General: Support each box from the building structure independently of conduit as follows, utilizing a support system capable of carrying 300% of load. 1. 2. Surface: a. Structural Steel: Bolted directly to steel member or bolted to spring clip, which is clipped to steel member. b. Concrete: Power driven fastener or bolt to expansion anchor set in drilled hole. c. Wood: Screw or bolt to wood. Suspended: Bolted to engineered spring clip, which is clipped to suspended ceiling system. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3. University of Georgia RCE 2013029 Recessed: a. Drywall: Attach directly to stud or joist by screw or bolt; or directly to a galvanized steel support which is attached directly at each end to stud or joist by screw or bolt. 3.05 INSTALLATION A. Outlet locations indicated on the plans are approximate. Coordinate and determine the exact location at the building. The architect reserves the right to shift the exact location of any outlet 10 feet before it is permanently installed. B. Install boxes plumb when vertical, level when horizontal and flush adjacent surface when recessed. C. Where an outlet occurs in an architectural feature, center the outlet in same. D. Where the mounting height of a wall outlet is not shown, mount at height directed by Architect. Mounting heights are from finished floor to box centerline. E. The contractor may, with Architect's approval, slightly vary an outlet's mounting height so that the box's top or bottom occurs at a masonry joint. F. Where outlets at different levels are shown adjacent, install them on the same vertical line. G. Space wall switch outlets with first gang box 4" from door trim on the installed strike side. H. Locate boxes and conduit bodies so that covers are accessible and removable. I. Limit masonry cuts from outlet boxes so that coverplate covers the cut. J. Provide plaster rings for all boxes set in plaster walls or ceilings. K. Match configuration to application. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 L. Utilize box size (capacity) based upon NEC. M. For devices, utilize boxes designed to support the device independently of coverplate and so install. N. Cover unused conduit openings with plastic covers for sheet steel boxes and threaded plugs for cast boxes. O. Prior to pulling conductors or installing devices, clean boxes of dirt, debris and water. P. Cover all boxes and secure with screws or bolts. Q. Install pullboxes to limit pulling distance and/or pulling bends. R. Outlet boxes for devices surface mounted below 10’-0” shall be cast type with threaded hubs. END OF SECTION 16130 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16140 WIRING DEVICES PART 1 - GENERAL 1.01 1.02 SUMMARY A. Description: 1. Provide switches, receptacles, dimmers and other strap mounted wiring devices as shown on the drawings. B. Related Sections: 1. Section 16050 - Electrical General 2. Section 16130 - Boxes C. Standards: 1. Underwriters Laboratories listed and labeled. 2. NEMA ( configurations as listed ) SUBMITTALS A. Manufacturers Product Data Sheets. PART 2 - PRODUCTS 2.01 MANUFACTURER A. Acceptable Manufacturers of Switches, Receptacles, and Coverplates: 1. 2. 3. Products specified as standard of quality are manufactured by Hubbell Incorporated, Wiring Device Division; referred to as Hubbell. Products of manufacturers listed below meeting indicated standards and specified manufacturer's product data characteristics, except as modified below, are acceptable for use, subject to prior approval of proposed product list. a. Pass and Seymour/Legrand b. Leviton Manufacturers product numbers listed below do not include color selection. Refer to Section 16140, 2.05 for device colors Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.02 RECEPTACLES A. Duplex - 20A: 2-pole, 3-wire, 125 Volts, side wiring with ground screw, NEMA 5-20R. 1. B. Hubbell # GF5362. SWITCHES A. Single Pole Single Throw: 20 Ampere, 277 Volt AC, maintained contacts, quiet operating toggle, side/back wiring and ground screw. 1. B. Hubbell # 1221 Three Way Single Throw: 20 Ampere, 277 Volt AC, maintained contacts, quiet operating toggle, side/back wiring and ground screw. 1. 2.05 Hubbell # 5362. Duplex Ground Fault Circuit Interrupter - 20A: 2-pole, 3-wire, 125 Volts, pigtail wiring, thru wiring to protect receptacles downstream, test and reset buttons, NEMA 5-20R. 1. 2.03 University of Georgia RCE 2013029 Hubbell # 1223. COVERPLATES A. Stainless Steel Coverplates: 1. Raised shoulder style stainless steel, brushed finish, oversize ( 31/8" x 4-7/8" , single gang), in configurations up to six (6) gang as indicated on the drawings, screws to match finish, and openings to match device. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Plastic Coverplates: 1. C. Smooth finish nylon, oversize ( 3-1/8" x 4-7/8" , single gang ), in configurations up to six (6) gang as indicated on the drawings, screws to match finish, and openings to match device. Surface Mounted: 1. 2.06 University of Georgia RCE 2013029 Corrosion-resistant steel, rounded corners and edges, stainless steel screws, single or multiple gang as indicated on the drawings. Openings to match device(s) and construction to match box. DEVICE AND COVERPLATE COLOR/FINISH A. When the wiring device is flush mounted, the devices shall be gray with stainless steel coverplates. B. Devices installed in floor boxes or surface mounted boxes shall be brown. PART 3 - EXECUTION 3.01 INSTALLATION A. Install the type device indicated by symbol or legend at the location shown on the plans. B. Install devices after conductors are pulled and painting is completed. C. Install devices vertically, unless otherwise noted, with SPST switches having up as "ON" and receptacles having ground pin at bottom. D. Where more than one device is indicated at a location, the devices shall be mounted in combined sectional gang boxes and covered with a single plate. E. Coordinate location of devices with other trades and architectural features. Do not locate devices on two different finishes such as half on wall title and half on painted surface. END OF SECTION 16140 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16170 MOTOR AND EQUIPMENT CONNECTIONS PART 1 - GENERAL 1.01 SUMMARY A. Description: 1. Provide power wiring to each motor, all mechanical equipment, all kitchen equipment, and all miscellaneous equipment included in the contract documents. Power wiring is the system of conductors from the energy source to the equipment that conducts the electrical energy, which does work or provides heat. 2. Provide a disconnect switch, fused where prescribed, for each motor or piece of equipment. B. Related Sections: 1. Section 16440 - Disconnect Switches 2. Section 16475 – Over current Protection 3. Section 16050 - Electrical General PART 2 - PRODUCTS 2.01 STARTERS A. 2.02 MOTORS AND EQUIPMENT A. 2.03 Provided under other divisions except where specifically prescribed in Division 16 documents. Motors, mechanical equipment, kitchen equipment, etc., provided under other divisions. CONTROL AND INTERLOCK WIRING A. Control wiring, (i.e., HVAC controls, remote pushbutton stations, thermostats, etc.), is excluded except where specifically prescribed in Division 16 documents. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 PART 3 - EXECUTION 3.01 INSTALLATION A. Coordinate all rough-in and final power wiring and equipment connection with other subcontractors. B. Install and connect individually mounted starters provided by other subcontractors. C. Label each disconnect switch and starter with name of equipment it serves. D. Coordinate over current device rating with nameplate of motor or equipment which it protects. END OF SECTION 16170 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 1.02 SUMMARY A. Description 1. Provide disconnect switches in configurations as indicated on the drawings and described in part 3 of this specification, complete with enclosures and accessories. B. Related Sections 1. Section 16050 - Electrical General 2. Section 16170 - Motor and Equipment Connections 3. Section 16475 - Overcurrent Protection SUBMITTALS A. Manufacturers Product Data Sheets. PART 2 - PRODUCTS 1.01 MANUFACTURERS A. 1.02 Acceptable Manufacturers as Follows: 1. Square D DISCONNECT SWITCHES: A. Disconnect switches shall be heavy duty (NEMA Type HD), UL Listed. B. All switches shall have blades, which are fully visible in the "OFF" position when the switch door is open. All current carrying parts shall be plated to resist corrosion and promote cool operation. Switches shall have removable arc suppressors where necessary to permit easy access to line side lugs. Lugs shall be front removable and UL listed for 60 degrees C or 75 degrees C, aluminum or copper wires. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 C. Switches shall be quick-make, quick-break such that, during normal operation of the switch, the operation of the contacts shall not be capable of being restrained by the operating handle after the closing or opening action of the contacts has started. The operating handle shall be an integral part of the box, not the cover. Provisions for padlocking the switch in the "OFF" position with at least three locks shall be provided. Switches shall have a dual cover interlock to prevent unauthorized opening of the switch door when the handle is in the "ON" position, and to prevent closing of the switch mechanism with the door open. The handle position shall indicate whether the switch is "ON" or "OFF". D. Switches shall be furnished in NEMA 1 general purpose enclosures unless specified as NEMA 3R on the plans. Covers on NEMA 1 enclosures shall be attached with pin type hinges, NEMA 3R covers shall be securable in the open position. NEMA 3R enclosures for switches through 200 amperes shall have provisions for interchangeable bolt-on hubs. Hubs shall be as indicated on the plans. NEMA 3R enclosures shall be manufactured from galvanized steel. Enclosures shall have a gray baked enamel finish, electro deposited on cleaned, phosphatized steel. E. Switches shall be horsepower rated for ac and/or dc as indicated by the plans. All fusible switches rated 100 through 600 amperes at 240 volts and 30 through 600 amperes at 600 volts shall have a UL approved method of field conversion from standard Class H fuse spacing to Class J fuse spacing. The switch also must accept Class R fuses and have provisions for field installation of a UL listed rejection feature to reject all fuses except Class R. The UL listed short circuit rating of the switches shall be 200,000 rms symmetrical amperes when Class R or Class J fuses are used with the appropriate rejection scheme. The UL listed short circuit rating of the switch, when equipped with Class H fuses, shall be 10,000 rms symmetrical amperes. 800 and 1200 ampere switches shall have provisions for Class L fuses and shall have a UL listed short circuit rating of 200,000 rms symmetrical amperes. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1.03 University of Georgia RCE 2013029 MANUAL MOTOR STARTING SWITCHES - TOGGLE TYPE DISCONNECT SWITCHES A. Type K - Manual motor starting switches shall have a 30 ampere at 600 volt rating, terminal screws suitable for #10 awg or smaller wire, number of poles as indicated on drawings, and an oversized NEMA 1 or NEMA 3R enclosure. It shall be authorized for use on motor and non-motor loads. Provide unit with toggle switch, unless noted to be key operated. Provide pilot light if indicated on the plans. PART 3 - EXECUTION 3.01 INSTALLATION A. Provide units as described in Part 2, Section 1.02, unless shown to be toggle switch on the plans; listed as a 20 or 30 ampere, single pole disconnect; or due to space requirements where this switch will not fit or is not applicable. All of these described installations may use a manual motor starting switch - (toggle type disconnect switch). B. Install disconnect switch adjacent to equipment it serves or as located on the plans. C. Anchor enclosures firmly to walls and/or structural surfaces. END OF SECTION 16440 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16450 GROUNDING PART 1 - GENERAL 1.01 SUMMARY: A. Description: 1. B. Related Sections: 1. 2. 3. 1.02 Provide a grounding conductor system from the building panelboards radiating to every electrical power controlling and consuming device in the system. Section 16050 - Electrical General Section 16110 - Raceways Section 16120 - Conductors SUBMITTALS: A. Manufacturers Product Data Sheets PART 2 - PRODUCTS 2.01 GROUND CLAMPS: A. Bronze, U.L. listed, with configuration to match application. B. Acceptable Manufacturers: 1. 2. 3. 4. Burndy Ilsco Thomas & Betts O.Z. Gedney Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 PART 3 - EXECUTION 3.01 EQUIPMENT GROUNDING CONDUCTOR: A. 3.05 3.06 ADDITIONAL EQUIPMENT GROUNDING CONDUCTORS: A. Branch circuit and feeder conduits: Install a green insulated grounding conductor, as shown on the plans, in each branch circuit and feeder conduit. B. Wiring Devices: At both switches and receptacles, connect the grounding conductor to the grounding screw on the device. EQUIPMENT GROUNDING CONDUCTOR ROUTING: A. 3.07 General: Install a separate insulated copper conductor, color coded green, from respective panelboard ground bus to every controller and/or device. Route equipment grounding conductor with respective feeder, power wiring and branch circuit conductors. CONDUITS: A. All grounding electrode conductors, equipment grounding conductors and bonds where not internal to equipment enclosures shall be installed in conduit to within 6" of terminating clamp or exothermic weld. END OF SECTION 16450 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16475 OVERCURRENT PROTECTION PART 1 - GENERAL 1.01 SUMMARY A. Provide fuses and circuit breakers of ampere rating and U.L. Classification as indicated on the drawings. B. Related Sections: 1. 2. 3. 4. 1.02 Section 16050 - Electrical General Section 16440 - Disconnect Switches Section 16170 - Motor and Equipment Connections Section 16470 - Panelboards SUBMITTALS A. Product Data 1. 2. 3. Manufacturers: Product Data Sheets Time - Current Characteristic Curves (Average Melt) Current Limitation Curves PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Acceptable Manufacturers - Fuses: 1. 2. 3. Products specified as standard of quality are manufactured by Cooper Industries, Bussmann Division, referred to as Bussmann. Products of manufacturers listed below meeting indicated standards and specified manufacturer's product data characteristics, except as modified below, are acceptable for use, subject to prior approval of proposed product list. a. Gould Shawmut All fuses shall be of the same manufacturer. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Acceptable Manufacturers - Circuit Breakers 1. 2. 3. 2.02 University of Georgia RCE 2013029 Products specified as standard of quality are manufactured by Square D Company, referred to as Square D. Products of manufacturers listed below meeting indicated standards and specified manufacturer's product data characteristics, except as modified below, are acceptable for use, subject to prior approval of proposed product list. a. General Electric b. Siemens/ITE Circuit breakers shall be of the same manufacturer as the panelboard or enclosure in which they are installed. FUSES A. Mains, Feeders and Branch Circuits: 1. Circuits 601 to 6000 amperes shall be protected by current limiting BUSSMANN LOW-PEAK time-delay fuses KRP-C(amp)SP. Fuses shall employ "0" rings as positive seals between the end bells and the glass melamine fuse barrel. Fuse links shall be pure silver (99.9% pure) to limit the short circuit current let-through values to low levels and comply with NEC Sections requiring component protection. The terminals shall be peened. Fuses shall be timedelay and shall hold 500% of rated current for a minimum of 4 seconds, clear 20 times rated current in .01 seconds or less and be listed by Underwriters Laboratories Inc. with an interrupting rating of 300,000 amperes RMS symmetrical. The fuses shall be UL Class L. Fuses shall be "LOW-PEAK YELLOW" in color. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2. 2.03 University of Georgia RCE 2013029 Circuits 0 to 600 amperes shall be protected by current limiting BUSSMANN LOW-PEAK dual-element fuses LPN-RK, LPS-RK, or LPJ. All dual-element fuses shall have separate overload and short-circuit elements. Fuses shall incorporate a spring activated thermal overload element having a 284 degree Fahrenheit melting point alloy and shall be independent of the short-circuit clearing chamber. The fuse shall hold 500% of rated current for a minimum of 10 seconds (30A, 250V Class RK1 case size shall be a minimum of 8 seconds at 500% of rated current) and be listed by Underwriters Laboratories, Inc with an interrupting rating of 300,000 amperes RMS symmetrical. The fuses shall be Time-Delay UL Class RK1 or J to maintain the engineered protection of the system components. Fuses shall be "LOW-PEAK YELLOW" in color. MOLDED CASE CIRCUIT BREAKERS A. Description: 1. Circuit breakers shall be Square D FA, KA, LA, NH, PA and/or PC one, two or three pole molded case circuit breakers rated 15 through 2500 amperes, 120V.ac, 240V.ac, 277V.ac, 480V.ac, as specified on the drawings. Breakers shall have an interrupting rating to match the panel in which they are installed or as indicated on the drawings. Install GFCI type breakers where indicated in the schedule and to all pool equipment. All circuit breakers shall be UL and CSA listed, IEC 157-1 rated, meet NEMA Standard AB1-1975 and Federal Specification W-C-375B/GEN, when applicable. Breakers covered under this specification may be installed in panelboards, switchboards, individual enclosures, motor control centers, combination motor starters or 1-LINE busway plug-in units. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Construction: 1. C. University of Georgia RCE 2013029 Molded case circuit breakers shall have overcenter toggle-type mechanisms, providing quick-make, quick-break action. Breakers shall be calibrated for operation in an ambient temperature of 40 degrees C. Each circuit breaker shall have trip indication by handle position and shall be trip-free. Two and three pole breakers shall be common trip. Each circuit breaker shall have a permanent trip unit containing individual thermal and magnetic trip elements in each pole. Circuit breakers with frame sizes greater than 100 amperes shall have variable magnetic trip elements, which are set by a single adjustment (to assure uniform tripping characteristics in each pole). A push-to-trip button shall be provided on the cover for mechanically tripping the circuit breaker. The circuit breaker shall have reverse connection capability and be suitable for mounting and operating in any position. Terminations: 1. Circuit breakers shall have removable lugs. Lugs shall be UL listed for copper and aluminum conductors. Breakers shall be UL listed for installation of mechanical type or compression type lugs. PART 3 - EXECUTION 3.01 INSTALLATION A. Install fuses in all switches shown on the plans, which require fuses. B. Fuses shall not be installed in the switch until equipment is ready to be energized. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. 3.02 University of Georgia RCE 2013029 Install "LOW-PEAK YELLOW" NOTICE labels to alert the end user of the engineered level of protection of the electrical equipment. They shall be marked with the proper fuse rating, per the drawings, and placed in a conspicuous location on the enclosure. These labels are available with the spare fuse cabinet (SFC) and are also available upon request from Bussman. INSTALLATION - CIRCUIT BREAKERS A. Install circuit breakers in panelboards, switchboards, distribution panelboards, and enclosures as shown on the drawings. B. Terminate wiring into circuit breaker lug. Tighten lug to torque level as marked on the lug. END OF SECTION 16475 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16500 LIGHTING PART 1 - GENERAL 1.01 1.02 SUMMARY A. Description: 1. Provide lighting fixtures as prescribed in the lighting fixture schedule complete with housing, junction boxes, ballasts, lamp sockets, lamps, lenses, baffles and trims installed with support from building structure. Verbal description of fixture in schedule will take precedence over manufacturer number. B. Related Sections: 1. Section 16050 - Electrical General. C. Standards: 1. Underwriters Laboratories labeled and listed. 2. CBM Approved 3. ANSI C82.2 4. 1992 National Energy Conservation Act. SUBMITTALS A. Manufacturers Product Data Sheets. B. ITL certified photometric reports. PART 2 - PRODUCTS 2.01 LIGHT FIXTURES: As prescribed in lighting fixture schedule. 2.02 FLUORESCENT BALLAST A. Electronic: Solid state electronic, capable of operating one to four lamps. 1. Acceptable manufacturers as follows: a. Advance b. Motorola c. Magnatec Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 PART 3 - EXECUTION 3.01 INSTALLATION A. Support: 1. Support each fixture from the building structure. 2. Support in a manner that ensures the fixture weight being equally distributed from each support and the fixture remaining in a level position. 3. Provide support systems capable of carrying 300% of load imposed. B. For pendant or suspended fixtures mounted to suspended ceilings provide 1/4" steel rods above the suspended ceiling from building structure to fixture. Provide a minimum of two supports for each chassis and spaced a maximum of 4 feet on center. C. For recessed H.I.D., LED, and fluorescent fixtures recessed in a suspended ceiling, provide 2 #10 awg. wire supports from building structure to fixture. Provide a minimum of two supports for each chassis spaced a maximum of 4 feet on center and located on diagonal corners of the fixture. Provide tie down clips to secure fixture to the ceiling grid. D. For recessed single incandescent, provide #10 AWG steel hanging wire from building structure to fixture; minimum of 2 separate supports per fixture. E. For each recessed fixture, provide a trim to match the type ceiling (plaster, grid, exposed panel, etc.) in which it is being installed. F. Aim and adjust all fixtures with lamp position, tilt, shutters, rotation or other types of adjustment during installation. The Architect or his representative will determine the final aiming and adjustment of such fixtures during the substantial completion job visit. During the substantial completion job visit, the electrician shall be on hand, with all necessary equipment, to make these adjustments. The electrical contractor shall provide adjustment and/or aiming instruction to the owner or owner’s representative. Fixtures serving areas where day lighting dominates will be adjusted after sunset. END OF SECTION 16500 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16748 LIFE SAFETY SYSTEM PART 1- GENERAL 1.01 GENERAL REQUIREMENTS A. Provide a microprocessor based addressable fire alarm system. The system and components shall be supplied by one manufacturer. 1. The system shall include all required hardware, raceways, interconnecting wiring and software to accomplish the requirements of this specification and the contract drawings, whether itemized or not. 2. All equipment furnished shall be new and products of a single manufacturer. 3. In the interest of job coordination, the contractor shall contract with a single source for supplying job materials, services and programming, including final inspection/test services. 4. All references to model numbers and other pertinent information herein is intended to establish the standards of performance, quality and appearance and is based upon equipment designed and manufactured by Fire Lite . Other suppliers of this system shall provide background information to the engineer 10 days prior to bid and be listed in a pre-bid addendum. 1.02 MATERIALS AND SERVICES A. The system shall include, but not be limited to the following elements: 1. 2. 3. 4. 5. 6. 7. 8. 9. Fire Alarm Control Panels (FACP). Power supplies, batteries and battery chargers. Equipment enclosures. Addressable manual stations, relays, heat detectors and smoke detectors. Audible (voice evacuation) and synchronized visual evacuation signals. Remote Alphanumeric Annunciator with door release switches. Software and firmware as required to provide a complete functioning system. Wiring and raceway. Installation, testing and certification, and education labor. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1.03 University of Georgia RCE 2013029 SYSTEM OPERATION A. Actuation of any fire alarm initiating device shall immediately cause the following actions to be initiated: 1. Identify the type of alarm, specific device and location on the backlit LCD display at the fire alarm control panel and at the remote annunciators. 2. Cause the system alarm LED to flash at the fire alarm control panel. 3. Cause audible alarm signals to issue the voice evacuation signal from a pre-recorded message. 4. Cause all synchronized visual alarm signals to flash. 5. Activate signals to the mechanical control system to cause shut down designated air handling units. 6. Interface with the elevator controller to recall the elevator. 7. Activate the digital communicator to report the type of alarm and location to a remote monitoring station (required telephone line and charges for central station monitoring shall be the responsibility of the building owner). B. Operation of the alarm acknowledge switch at the fire alarm control panel or at the remote annunciator shall permit the silencing of the alarm signals during the alarm condition. The silencing of the alarm signals shall not prevent the resounding of the alarm devices should a subsequent alarm condition occur. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1.04 CODES AND REFERENCES A. 1.05 University of Georgia RCE 2013029 The publications listed below, form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. The latest version of each listed publication shall be used as a guide unless the authority having jurisdiction has adopted an earlier version. 1. Factory Mutual (FM) a. FM AG Approval Guide 2. National Fire Protection Association (NFPA) a. NFPA 70 National Electrical Code. b. NFPA 72 National Fire Alarm Code. c. NFPA 101 Life Safety Code. 3. Underwriters' Laboratories, Inc. (UL) a. Appropriate UL Standards. 4. Local, State and National Building Codes as adopted by the authorities having jurisdiction. QUALIFICATIONS OF THE INSTALLER A. The contractor must have successfully installed fire alarm systems of the same type and design as specified, or have a firm contractual agreement with a subcontractor having the required manufacturers' training and experience. 1.06 SUBMITTAL REQUIREMENTS A. Shop Drawings: The contractor shall include the following information in the equipment submittal: 1. Complete manufacturer's catalog data including supervisory power usage, alarm power usage, physical dimensions, finish and mounting requirements. Submit panel configuration and interconnection of modules and all other data as required to make an informed judgement regarding product suitability. At a minimum, data shall be submitted on the following: a. Fire alarm control panels and annunciators. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 b. c. d. B. Power supplies, batteries and battery chargers. Equipment enclosures. Manual stations, heat detectors, smoke detectors, and other alarm initiating devices. e. Addressable interface relays and control modules. f. Wire and cable. 2. Power calculations. a. Battery capacity calculations. b. Supervisory power requirements for all equipment. c. Alarm power requirements for all equipment. 3. Data describing more than one type of item shall be clearly marked to indicate the type the contractor intends to provide for a given application. 4. Complete drawings covering the following shall be submitted by the contractor for the proposed system: a. Floor plans showing all initiating, end of line, supervisory, indicating appliances, and output control devices. Raceways shall be shown, marked for size, conductor count with type and size. b. Wiring diagrams showing points of connection and terminals used for all electrical connections to the system devices and panels. Maintenance Manuals: A complete operation and maintenance manual with two sets of installation drawings shall be submitted prior to the final inspection. 1. 2. 3. The following information shall be inscribed on the cover: a. "OPERATION AND MAINTENANCE MANUAL" b. Building location. c. The name, address and phone number of the contractor, system manufacturer and system subcontractor. d. The name and phone number of the fire department required to respond to alarms at the project location. The manual shall be legible and easily read with large drawings folded and contained in pockets. Included in the manual shall be circuit drawings, wiring and control diagrams with data to explain detailed operation and control of each item of equipment and a control sequence describing start up instructions. Included shall be installation instructions, maintenance instructions, safety precautions, test procedures, performance data, and software documentation. A copy of the system certification and final tests results, as called out in Part 3 of this section of specifications shall be included in this manual. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1.07 University of Georgia RCE 2013029 MATERIAL REQUIREMENTS A. All equipment shall be new and unused. All components and systems shall be designed for uninterrupted duty. All equipment, materials, accessories, devices and other facilities covered by this specification or noted on contract drawings and installation specifications shall be the best suite for the intended use and shall be provided by a single manufacturer of if provided by different manufacturers, recognized as compatible by both manufacturers. B. System installation and operations shall be verified by the manufacturer’s representative and a verification certificate presented upon completion. The manufacturer’s representative shall be responsible for an on-site demonstration of the operation of the system and initial staff training as required by the Architect and Consulting Engineer. PART 2 – PRODUCTS 1.1 FIRE ALARM CONTROL PANEL The fire alarm control panel (FACP) shall be Fire Lite Audio Command Center25/50 Voice Evacuation Control Panel and shall be modular, incorporate all control electronics, relays, and necessary modules and components in a semiflush mounted cabinet with cylinder lock. The FACP shall comply with the applicable requirements for UL 864. Loss of power, including any batteries, shall not require the reloading of a program from any source. Upon restoration of power, start-up shall be immediate, automatic and shall not require manual operation. Loss of primary power or the sequence of applying primary or emergency power shall not affect the transmission of alarm, supervisory or trouble signals. Enclosures shall be provided with ample gutter space to allow proper clearance between the enclosure and live parts of the panel equipment. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 A. Each FACP shall be intelligent, with its own microprocessor and memory. Each FACP shall be UL listed independently as a fire alarm control unit. Each FACP shall be capable of automatically programming itself upon initialization and of creating the System Program, and automatically updating the initial System Program to accommodate added or deleted devices on any analog circuit. Each FACP shall be capable of identifying and programming a General Alarm condition for all installed devices. The system shall be capable of identifying the number of analog addressable circuits, the number of devices on all circuits, the device type and location. The system shall be capable of incorporating all new devices in the System Program. The system shall display at the control panel, the sensitivity of remote addressable photoelectric or ionization smoke sensor devices and thermal heat sensor devices. The system shall be capable of displaying 160 characters of system and user text (4 x 40 alphanumeric display). The control panel shall automatically return to the normal mode after a predetermined time (one hour) after being in the service mode. Addressable devices shall be individually identified by the system, and any quantity of addressable devices shall be in alarm at any time up to the total number connected to the system. B. The control panel shall be capable of supporting non-addressable as well as addressable devices. The control panel shall be capable of supporting conventional zones in addition to analog/addressable circuits. The control panel shall provide for addressable remote conventional zones that are hardwired to any point on any analog/addressable circuit. Individual input and output device addressability as well as remote sensitivity measurement shall be performed on the same pair of wires. The System shall be capable of having multiple addressable devices in alarm simultaneously. The FACP shall have a service mode to permit the arming and disarming of individual detection or output devices as well as manually operating output devices. Status of these devices shall be displayed upon command from the FACP. Control panel shall automatically return to normal mode in the event the panel remains unattended in the service mode. The control panel shall be able to receive and process alarms even in the service mode. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 C. The FACP shall be capable of: 1. 2. 3. 4. SmartStart auto initialization SmartStart Program Update Program all functions from the FACP front panel Counting the number of addressable devices within a Acircuit@ which are in alarm 5. Counting Acircuits@ which are in alarm 6. Counting the number of addressable devices which are in alarm on the system 7. Differentiating among the types of addressable devices such as ionization smoke sensors, photoelectric smoke sensors, thermal heat sensors, control elements, collective zone interfaces, point identification devices, and manual stations. 8. Assigning priorities to type of detectors, circuits or groups of detectors. 9. Transmitter disconnect switch which, when activated, disconnects the transmitting device and causes operation of the system trouble signals. 10. Indicate on the FACP alphanumeric display, as a minimum, the following: Building Number, Floor, Type of Device, and Device Address. D. The FACP shall be capable of assigning control functions on the basis of system initiation patterns of devices such as “anding” circuits, counting circuits, counting devices, “anding” groups and “anding” types of devices E. The FACP shall supervise each individual device on an initiating circuit such that trouble, supervisory, normal, pre-alarm and alarm thresholds are individually annunciated. Each device on an addressable initiating circuit shall be checked to include the following: sensitivity, response, opens, shorts, ground faults, functionality and status. The FACP shall report the failure of a device’s transmitting components, open or shorted, on an addressable initiating circuit. Each device shall be recognized and identified by location within the circuit, and other devices on the circuit shall continue to function properly. The FACP shall report by specific device and address, any device which has been removed from an addressable initiating circuit, and shall not disrupt the operation of the remaining devices. The system shall sound a trouble if the device replaced is a different type than the device removed. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 F. The FACP shall be completely equipped and be provided with twenty-five (25) percent spare initiating and indicating circuits, including modules, enclosure space, terminal strips, internal electronic memory and other necessary accessories complete and ready to accept future circuits. The FACP shall be capable of automatically updating the System Program to adjust for such changes. Hardware and software, which define system configuration and operation, shall be provided. Memory data and operating system software shall be contained in a non-volatile memory. The FACP shall provide power necessary for the devices connected to it, including relay and remote annunciators. A green LED shall be provided to indicate normal system power is functioning. G. The FACP shall be capable of measuring and adjusting the sensitivity of sensors, and shall include an alphanumeric display to display custom messages and give readings of sensor sensitivity, sensor by sensor. It shall be possible to change the sensor sensitivity from the FACP within maximum and minimum values as defined by the UL listing of the sensors. The system shall be capable of listing sensor sensitivity settings for permanent record. The FACP shall maintain a moving average of the sensors’ smoke chamber value to automatically compensate (move the threshold) for dust and dirty conditions that could affect detection operations. The system shall automatically maintain a constant smoke obscuration sensitivity for each sensor (via the floating threshold) by compensating for environmental factors. The smoke obscuration sensitivity shall be adjustable with the UL 268 window (0.5 percent to 4.0 percent) to compensate for any environment. The system shall automatically indicate when an individual sensor needs cleaning. When a sensor’s percentage of compensation reaches a predetermined value, a “Dirty Sensor” or equivalent trouble condition shall be audibly and visually indicated at the control panel for the individual sensor. To prevent false alarms, these “Dirty” conditions, shall in no way decrease the amount of smoke obscuration necessary for system activation. H. The system control panel shall continuously perform an automatic self-test routine on each sensor, which will functionally check sensor sensitivity and ensure the accuracy of the values being transmitted to the control panel. Any sensor that fails this test shall indicate a trouble condition and the sensor location at the control panel. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 I. It shall be possible to test, reset and alarm silence the system from the FACP. New unacknowledged alarms and troubles shall be distinctively displayed on the visual display and differentiated from previous alarm and troubles. The system shall automatically indicate the total quantity of alarms and of troubles, which have occurred prior to reset at the control unit. No alarm or trouble indication shall be re-setable until it has been acknowledged. It shall not be possible to reset the system until alarms have been acknowledged. J. The Voice Control Panel will be capable of detecting and annunciating the following conditions: Loss of Power (AC and DC), System Trouble, Ground Fault, Alarm, Microphone Trouble, Message Generator Trouble, Tone Generator Trouble, and Amplifier Fault. K. The Voice Control Panel shall be fully supervised including microphone, amplifier output, message generator, speaker wiring, and tone generation. L. Integral Digital Message Generator with a memory capacity for up to 60 seconds of messaging. The Digital Message Generator shall be capable of producing five distinct messages (12 seconds each). These messages shall field programmable without the use of additional equipment. Provide a built in alert tone generators with steady, slow whoop, high/low and chime tone which is field programmable. M. The panel shall provide a minimum of four (4) Class AB@ alarm circuits (expandable to sixteen). N. The may be configured for General Alarm All Call operation, Alarm by Zone as required. Activation of alarm devices shall activate immediate broadcast of the alarm signal to all areas. The alarm signal shall be broadcast until the FACP is reset. O. N. Provide field programming equipment, software devices, computers and other equipment necessary, including interconnection cables to accommodate field software programming changes. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.02 University of Georgia RCE 2013029 Remote Annunciator(s) A. Provide Remote Alphanumeric Annunciators with Back Box at front entry. Each annunciator provide an 160 character (4 x 40) alphanumeric LCD display, system control switches and a key operated enable switch. 2.03 Manual Stations A. Provide Addressable Manual Stations as indicated on the plans. Stations shall be constructed of die cast aluminum. Each station shall contain the electronic interface circuitry required for individual device identification, alarm reporting and trouble supervision. The manual stations shall communicate with the main control panel via the analog addressable circuit. Resetting the station after operation shall require opening the front cover for access to the alarm switch. Where stations are required to be surface mounted, the back box shall be factory painted the same color as the alarm station. 2.04 Smoke Detectors A. Provide Analog Addressable Photoelectric Smoke Sensors with Bases as shown on the plans. Sensors shall be listed to UL 268 and shall be documented compatible with the control equipment to which they are connected. Sensors shall be listed for both ceiling and wall-mount applications. Each sensor shall contain an LED that, when the control panel determines that a sensor is in the alarm or trouble condition, the control panel shall command the LED to turn on steady, indicating the abnormal condition. The sensor’s electronics shall be immune from false alarms caused by electromagnetic interference and radio frequency interference. Detectors shall be nominal 24 Vdc powered by the initiating circuit. All sensor addressing information shall be stored in the fixed base. Addressing information that is stored in the removable sensor is not acceptable. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.05 University of Georgia RCE 2013029 Duct Mount Smoke Detectors A. Provide Duct Mount Analog Addressable Photoelectric Smoke Detectors with Sampling Tubes and Addressable Control Relays as shown on the plans. Detectors shall be listed by UL or FM for duct installation, shall be provided with approved duct housing, mounted exterior to the duct, and shall be provided with perforated sampling tubes extending across the full width of the duct. 2.06 Thermal Sensors A. Provide Analog Addressable Thermal Sensors with Bases as shown on the plans. Sensors shall be of both combination rate-of-rise and fixed temperature type, and shall communicate actual heat values to the system control panel. Detector temperature setting shall be accomplished via the FACP. Each detector shall be uniquely identifiable to the FACP. Sensors shall be listed to UL 268 and shall be documented compatible with the control equipment to which they are connected. Sensors shall be listed for ceiling mount applications. Each sensor shall contain an LED that, when the control panel determines that a sensor is in the alarm or trouble condition, the control panel shall command the LED to turn on steady, indicating the abnormal condition. Detectors shall be nominal 24 Vdc powered by the initiating circuit. All sensor addressing information shall be stored in the fixed base. Addressing information that is stored in the removable sensor is not acceptable. 2.07 Addressable Remote Relays A. Provide Addressable Control Elements as required for interface with HVAC controls, elevator controls, elevator power shunt trip controls, door lock controls, access control system controls and other systems as designated on the plans. Each addressable control element shall be capable of providing feedback to the FACP for positive confirmation of the control devices activity. Addressable control elements shall include form AC@ dry contacts rated for 2 Amp @ 30 VDC / .5 Amp @120 VAC. Each RCE shall contain an integral LED that annunciates module activation. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.08 University of Georgia RCE 2013029 Alarm Signals A. Provide Speaker Strobe Alarm Signals as shown on the plans for all locations requiring audible and visual alarm signals. All strobes shall be synchronized and provide a minimum of 110 candela light output. B. Provide Synchronized Strobe Visual Alarm Signals as shown on the plans for all locations requiring visual only alarm signals. All strobes shall provide a minimum of 110 candela light output. 2.09 Remote Communicator: A. Provide a digital remote communicator (dialer) and connect into the new fire alarm panel. Required phone lines shall be furnished and installed by the building owner. PART 3 - EXECUTION 3.01 INSTALLATION A. Electrical Contractor shall furnish and install all conduit and outlet boxes, and shall furnish and install all equipment and wiring in accordance with applicable local, state, and national codes, the manufacturer's recommendations, these plans and specifications. The contractor may contract with a manufacturers authorized equipment installer for any portion of the installation, but is ultimately responsible for the complete installation Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3.02 University of Georgia RCE 2013029 TEST A. The contractor must contract with a manufacturers authorized agent or installation firm to test and certify the system meets all provisions of the specifications and that the system is fully functional. A service technician authorized by the manufacturer of the fire alarm equipment shall supervise and participate during all of the following checks, adjustments, and tests of the system. 1. 2. 3. 4. 5. 6. 7. 8. 9. B. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation. Open initiating device circuits and verify that the trouble signal actuates. Open and short signaling line circuits to verify that the trouble signal actuates. Open and short Notification Appliance Circuits and verify that trouble signal actuates. Ground all circuits and verify response of trouble signals. Check presence and audibility of tone at all alarm notification devices. Check installation, supervision, and operation of all addressable smoke detectors using the Walk Test. Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points. When the system is equipped with optional features, the manufacturer's manual should be consulted to determine the proper testing procedures. This is intended to address such items as verifying the controls performance by individually addressed or grouped devices, sensitivity monitoring, verification functionality and similar. The supervising agent of the manufacturer shall provide a completed test results form for inclusion in the maintenance manuals. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3.03 FINAL INSPECTION A. 3.04 3.05 University of Georgia RCE 2013029 At the final inspection, a trained representative shall demonstrate that the system functions properly in every respect. INSTRUCTION A. The Contractor and/or the Systems Manufacturer's representatives shall provide a typewritten "Sequence of Operation" to the Owner for inclusion in the maintenance manuals. B. Provide one four hour session of on-site instructions, with a complete and functioning system, for the designated owner representatives from the system manufacturer's authorized agent. This agent shall have a full working knowledge of this installed system and be fully prepared to present this information to the Owner to their satisfaction. "Hands-on" demonstrations of the operation of all system components and the entire system including program changes and functions shall be provided. PERMITS AND APPROVALS A. Permits necessary for installation of the work shall be obtained prior to the commencement of work. B. Prior to commencement and after completion of work, notify authorities having jurisdiction. C. All applicable portions of the National Electrical Code shall be implicitly followed, in particular with regard to material type and quality, circuitry extensions from and connections to outlet and junction boxes, panel boards and similar appurtenances. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3.06 University of Georgia RCE 2013029 WARRANTY A. The equipment manufacturer shall guarantee the system equipment to the Owner for a period of one (1) year from the date of final acceptance of the system. B. The contractor shall guarantee all wiring and raceways to be free from inherent mechanical or electrical defects for one (1) year from the date of final acceptance of the system. C. Copies of these warranties, along with phone numbers and addresses of the manufacturer, contractor, and supervising agent shall be included. END OF SECTION 16748 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 16760 STAGE and DIMMING EQUIPMENT 1. GENERAL 1.1 RELATED DOCUMENTS A. 1.2 GOVERNING CLAUSE A. 1.3 For the sake of brevity these specifications shall omit phrases such as "Contractor shall furnish and install", "unless otherwise indicated or specified", etc., but these phrases are nevertheless implied. Mention of materials and operations requires the Contractor to furnish and install such materials and perform such operations completely to the satisfaction of the Owner. SCOPE OF WORK A. 1.4 Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this section. One company shall be responsible for the installation of all aspects of the stage equipment in the Auditorium. Work under this section shall include the furnishing of all labor, materials, tools, transportation services, supervision, etc., necessary to complete installation of new stage equipment as well as any other items as herein listed, all as described in these specifications, as illustrated on the accompanying drawings; or as directed by the Architect or his Representative. Work includes the following: Motorized Rigging Dead Hung Rigging Stage Lighting, Dimming & Control System SUBSTITUTIONS: A. Specific fabric and items of equipment are specified by trade names. It has been determined by the Owner that these are the particular items desired by the owner and established a standard of quality, equipment function and/or process. It is not the purpose nor intent of these documents to eliminate competitive bids. In order to allow proper and fair comparison of pricing, contractors are required to submit their base bid price on the specified equipment. A contractor may submit an alternate bid based on equipment different from that specified only if that Contractor has received prior approval in writing from the Owner at least 10 days prior to bid. Accompanying each request shall be a letter specifically detailing each substitution including catalog data, specifications, swatches, operative samples, technical information, drawings, Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 performance and test data, and complete descriptive and functional information to assist in a fair evaluation. Failure to submit any substitution for prior approval or not providing sufficient data for evaluation shall require the exact item specified to be furnished. Owner's approval of a substitution for bid purposes will not relieve the contractor from the responsibility of meeting all specification criteria. If an approval of a substitution is granted, the Contractor shall be fully responsible for any and all changes (wiring, power, distribution, support structure, etc.) such substitution shall require. 1.5 DEFECTIVE OR NON-APPROVED MATERIALS A. 1.6 GUARANTEE A. B. C. 1.7 The Contractor shall guarantee all of the work that is performed under this contract, including all materials, and workmanship, for a period of one (1) year from the date of full acceptance of the work. Lamps for lighting fixtures shall be guaranteed against failure for thirty (30) days. Nothing in this guarantee shall cause repair or replacement by the Contractor where negligence, neglect or improper operation by the Owner has caused the failure of any equipment installed under this contract. DISCREPANCIES A. 1.8 Should any stage equipment be found defective, not meeting specifications, or that which has not been approved in writing by the Owner shall, upon discovery (including any time within the period of the guarantee), be replaced with the specified equipment or material at no additional cost. All equipment shall be sized to fit properly. The exact measurements are the responsibility of the Contractor. If there are discrepancies in the specifications, the Contractor shall ask for a clarification from the Owner. If no clarification is requested, the Owner's judgment shall rule. PRE-APPROVED STAGE EQUIPMENT CONTRACTORS A. One company shall be responsible for the installation of all aspects of the stage equipment as specified in this section. This shall include but not be limited to all rigging, curtains, tracks, motors and control, stage lighting fixtures, stage/house dimming, and dimming controls and miscellaneous equipment. The following companies have prior approval as STAGE EQUIPMENT CONTRACTORS: 1. Barbizon 404-681-5124 2. Magnum Companies 404-872-0553 3. Television Production Services 770-452-8700 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. C. D. 1.9 University of Georgia RCE 2013029 In order to be considered as a Stage Equipment Contractor on this project, each Contractor requesting approval must submit to the Architect at least ten (10) days prior to the date of bid opening a letter expressing his intent to bid. This letter shall include a list of at least five (5) projects of similar size and scope completed by this firm within the last five (5) years. If motorized line-shaft rigging is required on this project, the letter shall indicate the number of lineshaft set provided and installed and the manufacturer of the equipment on each of the five projects. Inspection of one completed installation may be requested by the Architect/Architect's Representative prior to consideration of request to bid. The stage equipment contractor shall have been in business under the same name for five (5) full years preceding the date of this bid doing work similar to the type specified. The decision of the Architect as to the capability of the Bidder to successfully complete and maintain the system, based on this pre-qualification information shall be final. Pre-Bid request letter shall include a statement that all major items of equipment shall be bid and supplied as specified, or shall contain details of all proposed substitute equipment for review by the Architect/Architect's Representative. Substitute equipment items to include specifications, parts numbers, and details of interconnection to proposed system. The decision of the Architect/Architect's Consultant as to the acceptability of substitute equipment shall be final. The Stage Equipment Contractor shall employ only fully trained stage riggers and mechanics, assisted by common laborers, for the erection of the stage equipment. The stage riggers shall be completely familiar with the type of equipment to be installed. A competent Job Superintendent shall be on the job at all times when work is in progress. He shall represent the Stage Equipment Contractor and all directions given by him shall be as binding as if given by the Stage Equipment Contractor. ACCEPTABLE EQUIPMENT MANUFACTURERS A. B. C. D. E. For the purposes of establishing a standard of quality desired on this project, the rigging hardware products of Electronic Theatre Controls of Middleton, Wisconsin are specified. The stage lighting dimming and control of Electronic Theatre Controls of Middleton, Wisconsin are specified. The stage lighting fixtures of Electronic Theatre Controls of Middleton, Wisconsin are specified. The electrical stage distribution hardware of Electronic Theatre Controls of Middleton, Wisconsin are specified. All other companies must receive prior approval to bid this project. Please refer to the section regarding substitutions. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1.10 University of Georgia RCE 2013029 DOCUMENTATION A. B. SHOP DRAWINGS: Shop drawings and equipment data sheets shall be submitted to the Owner under general provisions within 45 days after award of the contract. Failure to comply with this 45 day requirement shall be cause for disqualification of the selected Contractor and cancellation of contract without cost to the Owner, on the basis that the selected Contractor does not have the ability or intention to comply with the specifications. Approval of submitted equipment shall be obtained prior to equipment purchasing or fabrication. If shop drawings are rejected, correct and resubmit in the manner as specified. All shop drawing information shall be submitted at the same time; no partial submittal will be accepted. Drawings shall indicate complete details, dimensions, product types and locations of all equipment, clearances required, guides, cables, sets, Contractor fabricated equipment, and all other details required to completely describe the work to be performed. Submittals drawings shall be presented at a scale of not less than 1/8" = 1'-0" for conduit plans, 1/4" for equipment layouts, ½" = 1'-0" for mounting details, and ½" = 1'-0" for plate and panel details. Each sheet to allow space for approval stamps and have the name of the project, the contractors and/or the supplier's name, address telephone number, and the date submitted. Submit the following items for Owner's approval, prior to fabrication: 1. Stage plan view 2. Stage side section view 3. Gridiron layout indicating all stage equipment. 4. Electrical riser diagrams indicating the necessary control wiring for all dimming, distribution, and controls wire tag number for every connection. Show all terminal blocks with wire numbers and location. 5. Plan and elevation views indicating all electrical hardware locations and layout 6. Provide full dimensions for panel layouts with finishes and materials for all custom panels. 7. Details of installation and erection, including adjoining conditions and necessary clearances. 8. Indication by arrow and boxed caption of each variation from contract drawing and specifications, except those indicated as acceptable in specifications or on drawings RECORD DRAWINGS AND DATA: Submit in accordance with General Provisions. Also within 30 days of final test and completion of the installation, submit the following to the Owner: Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 1. 2. Three (3) complete sets of "as built and approved" drawings (rolled, not folded showing systems and elements as installed, including field modifications and adjustments. 2. Three (3) sets of maintenance data including a list indicating replacement parts lists for all items of equipment, wiring diagrams, control diagrams, any and all keys for cabinets, racks, key operated switches etc. and complete operation manuals. 3. Three (3) notarized Certificates of Flameproofing for each fabric used. 4. Three (3) Certificates of Guarantee C. INSTRUCTION OF OWNER PERSONNEL: This contractor or his representative, fully knowledgeable and qualified in systems operation, shall provide eight (8) hours of instruction to the Ownerdesignated personnel on the use and operation of this System. Designated instruction times shall be arranged through the Owner. D. PERMITS: Obtain all permits necessary for the execution of any work pertaining to the installation, and conform in all trades with all applicable local codes and with the National Electric Code. Obtain all permits necessary for operation of any equipment by the Owner. E. CLEAN UP: It shall be the responsibility of this Contractor to remove all debris from the building or site caused by his operations to a common trash point or receptacle on the job site, as determined by the Owner. THEATRICAL RIGGING EQUIPMENT 2.1 GENERAL STANDARDS A. B. C. Each hoist shall be fully tested under full rated load throughout its full travel distance with all its liftlines terminated to the hoist before the hoist is shipped from the manufacturer. Testing shall include: 1. Hoist operation 2. Hoist/motor speed 3. Liftline terminations under load 4. Braking and stopping under load 5. Load cell functions 6. Slack line detection 7. Position sensing 8. Hoist noise Only hoists that successfully pass pre-shipment testing shall be sent to any job site. A record of testing and its results shall be available for review at the manufacturer’s facility for at least one year after testing. Paint as required under this section shall be the manufacturer's standard finish and color except as noted. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual D. All equipment items shall be new and conform to applicable provisions of Underwriters' Laboratories (UL), American Standards Association (ASA), American National Standards Institute (ANSI), National Fire Protection Association (NFPA) Life Safety Code 01, National Electric Code (NEC) and PLASA. 1. Where acceptable equipment items are specified by catalog number only, device shall meet all published manufacturer's specifications. Where quantities or sizes are not given, refer to drawings. Where two or more products are listed, contractor may use either, at his discretion. Equipment shall not be substituted without specific written approval by the Architect under the substitution paragraphs of these specifications. 2. All pipe battens shall be fabricated from 1.5" Schedule 40 pipe. 3. All turnbuckles and cable clips shall be drop forged. 4. All turnbuckles and clips, tracks, chains and other items of incidental hardware shall be furnished plated or painted. Wire rope shall be galvanized. Fasteners, chain, and other miscellaneous hardware shall be either cadmium or zinc plated. 5. All materials used in this project shall be new, unused and of the latest design. Refurbished materials are not permitted. 6. In order to establish minimum standards of safety, a minimum factor of 8 shall be required for all equipment and hardware used on this project. In addition, the following factors shall be used: Cables and fittings Cable bending ratio Max. fleet angle Steel Bearings 2.2 University of Georgia RCE 2013029 10 Design Factor 26 times diameter 2 degrees 1/5 of yield Two times required load at full for 2000 hours HOISTS A. Hoists shall be purpose-designed and fabricated for overhead lifting of theatre lights, equipment, curtains and scenic elements, whether used on stage, in the auditorium or other places of public assembly where people shall move beneath the suspended or moving load. The systems shall incorporate mechanical, electrical and safety features that shall be inherent to this equipment; they shall provide an engineered, efficient device for overhead lifting. The mechanical, electrical and safety features of this hoisting and control system shall establish the standard of quality, performance and safety by which hoisting systems of other manufacture shall be evaluated. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. C. D. E. F. University of Georgia RCE 2013029 Each wire rope liftline shall adhere to a design factor of 10:1 with an ultimate strength of 4200 pounds. All load path components between the building structure and the batten shall exceed the breaking strength of the wire rope. The motor brake shall be rated at least at 125% of the motor torque. Standard configured hoists shall be capable of supporting a live load suspended from the batten as follows: 1. General purpose Variable Speed 0-180 fpm, 1000 pound capacity in standard configuration. Powerhead shall measure no more than 16” high x 16” w x 55 ¼” long and weigh 495 pounds 2. General purpose 30 fpm 800 pound capacity in standard configuration. Powerhead shall measure 16” high x 16” w x 47 1/2” long and weigh 395 pounds 3. General purpose 30 fpm 1300 pound capacity in standard configuration. Powerhead shall measure 16” high x 16” w x 47 1/2” long and weigh 395 pounds 4. General purpose 30 fpm 1900 pound capacit in standard configuration. Powerhead shall measure 16” high x 18” w x 53 1/2” long and weigh 580 pounds 5. Stage Electric 30 fpm 650 pound capacity in standard configuration. Powerhead shall measure 16” high x 16” w x 47 1/2” long and weigh 395 pounds 6. Stage Electric 30 fpm 1000 pound capacity in standard configuration. Powerhead shall measure 16” high x 16” w x 47 1/2” long and weigh 395 pounds The standard general purpose hoist shall consist of the following major components: 1) Powerhead, 2) compression tube with beam clamps, loft blocks, liftline and liftline terminations, Right Angle Cable Adjuster (RACA) and 3) pipe batten. The standard stage electric hoist shall consist of the following major components: 1) Powerhead, 2) Compression Tube with beam clamps, cable management system, loft blocks, liftline and liftline terminations Right Angle Cable Adjuster (RACA), 3) pipe batten and power/control distribution strip The hoist shall include the following features: 1. A Powerhead containing the following elements: the gear motor, motor brake, load brake, limit switches operating electronics, load sensor, slack line detector, absolute position sensors, cable drum assembly, and wire rope. 2. A Compression Tube that prevents hoist system lateral forces from transferring to the building. Hoists or hoisting systems that impose a lateral load on the building shall not be acceptable. 3. The hoist shall incorporate a built-in load cell. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 4. 5. G. 2.3 POWERHEAD A. B. 2.4 The Powerhead shall be a fully enclosed, powder coated sheet metal housing that shall prevent contact with moving and electrical parts and shall provide protection against dirt, dust and debris. For setup and maintenance, the following functions shall be available from the Powerhead: power and operating switches, address setting knobs, limit switch setting knobs, limit switch override button, indicators for power, status and communication. Each of these functions shall be clearly labeled. GEARMOTOR AND MOTOR BRAKE A. B. C. D. 2.5 The hoist shall incorporate a built-in slack line sensor. The hoist shall include the emergency contactor built into the hoist. The hoist shall be manufactured from UL Listed components and shall be UL Listed and tested as a complete system (not just UL listed parts). The gear motor and motor brake shall be an integral unit from a single manufacturer. It shall operate on 208 Volt or 480 Volt 60 Hz, 3 phase current for fixed speed units and 480 Volt, 60 Hz, 3 phase current for variable speed hoists. The motor brake shall be integral to the gear motor and shall be capable of holding 125% of the motor full load torque. The motor brake shall be spring actuated to apply and hold braking force. The motor brake shall be magnetically released and held open upon actuation. LOAD BRAKE A. Fixed Speed Hoists 1. The rotary disk load brake shall bring the moving load to a complete stop and shall hold the load in position in the event of a mechanical failure of the motor, motor brake or gearbox. 2. Noise from the load brake shall be minimally audible at any time in the operational cycle. 3. Normal hoist operation shall not be limited by heat or noise caused by the load brake. 4. The load brake shall be mechanically released when the load is moving in the up direction. The load brake shall be close when the hoist has stopped. The load brake shall always be engaged when the load has stopped moving either up or down. When lowering the load the load brake shall partially disengage to allow and control descent of the Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 batten. The load brake shall remain closed in the absence of rotational torque on the gearbox. 2.6 WIRE ROPE DRUM A. 2.7 LIMIT SWITCH A. 2.8 A position sensing system shall be built into the Powerhead to provide accurate position information. The system shall consist of two absolute sensor types that provide accurate position information for each batten at power-up of the system. Hoisting systems that require re-homing shall not be acceptable. Incremental encoders shall not be acceptable for position readout purposes. SLACK LINE DETECTOR A. 2.11 A load sensor shall be built into the Powerhead to create a profile of the actual load on the hoist as it travels through its normal cycle. The profile may be changed by “re-training” the profiling system whenever the suspended load is changed on the batten by activating a key-switch operated training cycle on the motor controller. The load sensor shall continuously monitor the load when load sensing is turned on. POSITION SENSOR A. 2.10 A limit switch assembly shall be mounted within the Powerhead for hard “normal” and “ultimate” end of travel limits. Hard end of travel limits shall be set/adjusted at the time of installation aided by an indicator light visible on the bottom panel of the Powerhead cover. Any system that indicates that the limit has been set by audible or tactile means only shall not be acceptable. LOAD SENSOR/LOAD PROFILING. A. 2.9 Shall wrap up to eight 3/16” diameter 7 x 19 galvanized aircraft (utility) wire rope liftlines up to 50’ long in a compact manner on the cable drum. They shall be managed by a wire rope (cable) keeper integral to the Powerhead. The drum design shall prevent wire rope from tangling or crossing over itself. The slack line detector shall be built into the Powerhead. When a slack line condition in excess of 15” develops in a liftline, the slack line detector shall remove power from the hoist. The batten shall be allowed to move only in the upward direction to allow removal of the cause of the slack line fault. LOCAL USER INTERFACE AT POWERHEAD A. User interface at the Powerhead control panel at the rear of the hoist shall include: Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1. 2. 3. 4. 2.12 Record of severe fault conditions with date and time stamp Record of E-stops, overloads, moves and power cycles Record of travel distance and peak loads since installation/inspection COMPRESSION TUBE AND BEAM CLAMPS A. B. C. D. E. F. 2.14 Hoist Up/Down Control Limit Switch override buttons (tool accessible) Address switches Status LED’s INFORMATION STORAGE WITHIN POWERHEAD A. B. C. 2.13 University of Georgia RCE 2013029 The Compression Tube shall be a continuous channel of extruded aluminum engineered in conjunction with the beam clamps to neutralize rigging-generated lateral forces on the building. The Compression Tube shall support the system loft blocks. Compression Tube sections shall be joined into a continuous assembly by a pair of dedicated splicing plates at each tube joint. The Compression Tube shall be installed only by means of dedicated beam clamps that allow the Compression Tube to snap into place and to fractionally move horizontally under load. Beam clamps shall be capable of attaching to horizontal beams, joists, truss flanges or flat steel plates measuring from 1/4” thick up to 1” thick and from 4” wide up to 14” wide placed no more than 14’0” apart. P650E, P800G, P1000E and P1300G Powerheads may be mounted on ¼” thick x 4” wide or larger steel structures if deemed sufficient by a structural engineer. P1500E, P1900G and V1000S hoists must be mounted on 3/8” x 6” wide or larger steel if deemed sufficient by a structural engineer. Support structures must be deemed sufficient by a structural engineer to support any forces imposed by the hoisting systems. Beam clamps shall accommodate up to ½” vertical misalignment. Hoist systems that do not neutralize hoist generated lateral forces on the building shall not be accepted for this project. LOFT BLOCKS A. B. Each loft block shall be an assembly of steel side plates, a wire rope idler, sheave, bearings, shaft locked against rotation and support hardware. Each loft block shall be inserted into the slot on the bottom of the Compression Tube. The blocks shall be positioned no closer than 4’-0” from each other, unless muled. Loft block sheaves shall measure 5” in diameter and contain a pair of press fit sealed ball bearings. Liftlines shall travel in a groove shaped and sized for 3/16” diameter wire rope per the latest edition of the Wire Rope Users’ Manual as published by the Wire Rope Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. D. 2.15 B. C. D. Each liftline shall be terminated in the Powerhead via a standard copper oval compression sleeve installed/crimped at the factory. Liftlines shall be terminated at the load hanger with a low profile Right Angle Cable Adjuster (RACA) ™, thimble and copper oval compression sleeve. The RACA and cable terminations at the batten shall be installed at the time of hoist installation. Batten trim shall be adjustable up to 6” via the RACA. Systems utilizing turnbuckles or chain to trim the batten shall not be accepted for this installation. HANGERS A. 2.17 Technical Board. The loft block sheave shall be concentric about the hub and shall be evenly balanced for ease of rotation. An idler shall be incorporated into the top assembly of the loft block to guide and support liftlines as they pass the block. Hoisting systems requiring the loft blocks to be mounted directly to the facility structure shall not be accepted for this project. LIFTLINE TERMINATIONS A. 2.16 University of Georgia RCE 2013029 Raceway hangers shall be specially shaped flat bar that shall support the wire rope termination hardware and secure the raceway and the pipe batten. CABLE MANAGEMENT FOR ELECTRICS A. PRODIGY CABLE MANAGEMENT for ELECTRICS 1. The load circuits and control wiring shall be fed to the distribution trough by a built-in cable management system that allows flat feeder cable to fold and store along the top of the connector strip. a. At high trim, the entire system shall be stored in 30” of vertical space from the bottom of the mounting steel to the horizontal centerline of the batten. Cable management systems requiring greater vertical storage space shall not be acceptable for this project. b. The cable management system shall be integral to the hoist system. c. The cable management system shall be UL LISTED. d. The flat cable shall meet the physical as well as thermal requirements of UL for 20 amp loads. Up to four flat cables may be fed from each end of the distribution system to provide power for 24 circuits from each end of the system for a maximum of 48 circuits total. e. Each flat cable shall include one ground wire and one data cable plus an individually insulated hot and an Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. University of Georgia RCE 2013029 individually insulated neutral conductor for each of six 120 Volt 20 Amp circuits. f. The connector strip shall be built to the length specified with outlets or pigtails located as specified or as shown on the construction drawings. Outlets or plugs shall be 15 amp grounded pin connectors, 15 amp twistlock connectors, or 15 amps Edison plugs. The distro trough may also contain connectors for Ethernet and/or DMX connections. g. Flat cable shall pass through a strain relief before entering a termination box at the designated end of the raceway. Within the raceway all wiring shall be attached at the factory to a terminal block. The flat cable, internal wiring and all components shall meet UL requirements and appropriate National Electrical Codes (NEC). h. Cable management systems that utilize cable cradles, cable reels or locate feeder or data cables outside the off stage edges of the electrics batten shall not be acceptable for this project. i. Hoisting systems utilizing cable management systems from third-party vendors shall be fully integrated into the hoisting system without additional structural changes or changes to the QuickTouch controller. Electrics line set hoisting systems that do not fully integrate cable management in the hoisting system and controller shall not be acceptable for this installation. Cable management systems that are not UL LISTED shall not be accepted for this installation. PANTOGRAPH CABLE MANAGEMENT FOR ELECTRICS 1. The load circuits and data wiring shall be fed to the distribution trough by one or more UL Listed Pantograph cable management systems that are specifically designed to interface with traditional stage distribution raceways. The pantograph shall allow the cable trays, feeder cable and data wiring to fold and store along the top of the connector strip without imposing a direct physical load on the connector strip. 2. The pantograph shall consist of a series of 18 ga. ventilated steel trays hinged to each other to allow the entire distance of travel required by the batten, up to 50’. The hinges and hinge attachment points shall be stiffened to prevent distortion of the pantograph. 3. The trays shall be connected to a moving trolley at the compression tube that allows relief as the system moves Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. University of Georgia RCE 2013029 slightly from side to side during ascent/descent of the batten. At the bottom, the pantograph shall be attached to a hinge point above the houselight or distribution trough in a manner that imposes no additional physical load on those assemblies. The flat cable in the trays shall exit the pantograph and enter a termination box on the distro strip where all electrical connections shall be made. 4. The flat cable shall be UL LISTED. 5. The pantograph shall support a double-high/double wide stack of flat cable and shall allow the flat cable to bend at each joint within required NEC bending radii. 6. The trays shall hinge open/closed as the batten is lowered/raised and shall not impede the movement of the line set 7. The trays shall be sufficiently stiff to support themselves and the flat cable they carry. At no time shall the trays bow, warp, sag or twist whether or not under load of the flat cable. 8. Flat cable in the pantograph tray shall never heat in excess of the rated temperature maximum of the flat cable when all circuits within the tray are loaded at maximum electrical capacity. 9. It shall be possible to provide power for up to sixteen 20 amp circuits plus ground and data via each pantograph. 10. These cable management systems shall interface with the circuit distribution trough with standard mechanical and electrical hardware purpose designed for this assembly. 11. Hoisting systems utilizing cable management systems from third-party vendors shall be fully integrated into the hoisting system without additional custom hardware, changes to any part of the pantograph or changes to the QuickTouch controller. 12. Hoisting systems that do not fully integrate cable management in the hoisting system and controller shall not be acceptable for this installation. TRADITIONAL CABLE MANAGEMENT FOR ELECTRICS 1. Load circuits and data wiring shall be fed to a standard stage distribution trough by multi-conductor SO cable supported by cable cradles suspended from one of the Prodigy hoist liftlines. The SO cable shall be held in place at the distro by means of a dedicated strain relief assembly. 2. Single or multiple multi-conductor SO cables and multiple cable cradles can be suspended from a single liftline so long as the Working Load Limit (WLL) of the liftline is not exceeded. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual D. 2.18 CONNECTOR STRIP—DISTRO and HOUSELIGHT TROUGH 1. A Houselight Trough shall be a formed sheet metal trough made from 18 ga. Steel. The trough shall be reinforced with 12 ga. formed steel at each utilized fixture attachment point. The trough shall enclose internal wiring to which fixture wiring is terminated within the trough. 2. The system may incorporate an internal barrier to permit emergency circuit wiring in the same trough. 3. The trough shall be powder coated. 4. Circuit wiring shall be supplied to the trough via an ETC Pantograph cable management system. 5. Cable management shall utilize an ETC Prodigy pantograph that allows up to sixteen line-voltage circuits, or a combination of line–voltage and up to two emergency circuits. Knockouts located 6” on-center are built into the raceway. The knockouts permit installation of houselights with canopy or stem mounts to attach directly to the raceway. Up to 50 pounds may be suspended between raceway supports. 6. Pantograph cable management and houselight distribution is UL LISTED for use with flat cable circuit distribution and fixture mounting as described above. 7. Houselight troughs are designed to be used without pipe battens. PIPE BATTEN A. B. C. 2.19 University of Georgia RCE 2013029 The pipe batten shall be 1½” schedule 40 grade A, seamless pipe fabricated in the largest possible lengths without splices. Battens of greater length shall be spliced by means of .120 x 1 9/16 dia. DOM tube 18” long with 9” of tube inserted into each half of the splice. The tight fitting splice tube shall be held in place by a pair of 3/8 x 2 ½” grade 5 hex bolts on each side of the joint. The bolts shall pass through the pipe at an angle of 90° to each other. There shall be two bolts on each side of the joint spaced 1” and 8” from the joint. Alternatively, one pair of bolts on one side of the joint may be replaced with either plug welds or tight fitting steel rivets. Pipes shall be straight and painted flat black. A safety-yellow batten cap shall be installed at each end of each pipe batten. The manufacturer shall provide up to four self-adhesive labels for each batten on which the rated batten load shall be written by the installer. POWER AND CONTROL DISTRIBUTION (PCD) Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual A. B. C. 2.20 University of Georgia RCE 2013029 Each hoist shall receive power and control via a pair of 8’-0” long jumper cables extending from the Powerhead to the source outlets. Receptacles shall be installed in a sheet metal junction box or trough with outlets. Each outlet shall be located no more than 6’-0” away from the rear face of each hoist. Each Powerhead shall include a power cord hardwired to the hoist with an appropriately sized twistlock connector at the PCD end and a removable control cable with a circular 9 pin connector at each end. Inclusion of a 20 amp 3 phase breaker in the PCD is optional. The wiring and connectors shall be barriered between high and low voltage. The power/distribution channel shall be UL LISTED for this application. QUICKTOUCH+ FIXED AND VARIABLE SPEED CONTROL SYSTEM A. GENERAL 1. The entire motor system shall be operated by a QuickTouch+ fixed and variable speed controller. It shall be purpose-designed and fabricated to manage and operate motors specifically designed for overhead lifting. Each system shall incorporate mechanical, electrical and safety features that shall be inherent to this equipment and shall provide an engineered, efficient device to control the equipment. The mechanical, electrical and safety features of this control system shall establish the standard of quality, performance and safety by which motor systems of other manufacture shall be evaluated. 2. The QuickTouch+ Control System shall consist of a surface, flush or rack mounted primary control panel and up to three remote E-stop stations. 3. The motor system shall also include one Fixed Speed Remote control device with 30’ of flexible cable that may be attached to the system at the QuickTouch+ control panel. 4. The controller shall include the following features: a. Key operated power switch b. LCD display for feedback/operating information c. Key operated motor load profile training/enable switch d. Latching motor selection buttons with rear illuminated naming tabs e. Rear illuminated hold-to-operate (dead-man) up and down operation buttons f. Recessed speed adjustment slide-pot g. Rotary data entry encoder h. Dedicated E-stop button i. Outlet for wired remote Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. C. D. University of Georgia RCE 2013029 j. Optional door k. Optional rack mount kit 5. The control system shall only employ the QuickTouch+ controller, a power and control distribution infrastructure and the motors. A System that requires separate drive cabinets or motor-starters shall not be acceptable. 6. The controller shall be UL LISTED and shall be fabricated from UL LISTED components. ENCLOSURE 1. The back box and face panel shall be fabricated from 16ga powder coated sheet steel specially formed to provide support for installation as well as support for all components installed within the housing. 2. The QuickTouch+ face panel shall be printed with complete labeling information to identify the function of each of the buttons in the control station. 3. The face panel shall identify the system as a QuickTouch+ controller for stage rigging. 4. The face panel shall be shades of grey. The ring surrounding the E-stop button shall be safety yellow and shall be rear illuminated 5. The steel panel to which all switches are mounted shall be removable via screws in the surface located underneath the face panel film. LCD SCREEN 1. The liquid crystal display shall be purpose designed to communicate all information in human readable text. 2. The screen shall be rear illuminated and shall be dimmable. 3. During system start up the screen shall show the progress of the motor diagnostics self-tests. Upon completion of the startup sequence the screen shall indicate that the system is “OK” or shall provide specific information should a fault be detected. Fault conditions shall be reported in human readable text. Systems that report fault conditions in a series of blinking lights shall not be acceptable for this installation. 4. When a motor is selected the LCD screen shall readout the motor name and number, the current batten position above the floor, the amount of weight suspended from the batten, the trim position that is recorded, as well as two bar graph scales that show the current position of the batten, top and bottom limits and the current weight suspended from the batten. MOTOR SELECTION/OPERATION BUTTONS Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1. E. F. G. University of Georgia RCE 2013029 There shall be rear illuminated motor selection buttons. Buttons shall remain illuminated until de-selected. 2. Up to four motors may be selected to move at one time. When the up or down button is pushed and held, each motor shall move to its next stop location. If the stop location is the adjustable trim position, the motor can be made to continue to travel in the selected direction by releasing and re-pressing the up or down hold-to-operate button until the next stop for the motor(s) is reached. 3. A maximum of four motors may move at one time and only in one direction at a time. 4. Although four motors moving at one time is the factory default, it shall be possible to increase the quantity of simultaneously moving motors to eight or reduce it to one. 5. The system software will limit the number of simultaneous moving motors. As a backup, there shall be dedicated hardware to detect and disable the system if the system attempts to move more than the configured maximum quantity of motors. 6. All buttons shall fit neatly within each of the cover panel cutouts on the controller. KEY SWITCHES 1. A key switch shall control power to the control system. The key must be in the lock and the key turned to the on position for the motor system to operate. 2. A separate key is required to turn on the load profiling system. That key must be in the lock and turned to the “ON” position for load profiling to function. 3. When load profiling is turned on the motor shall know the amount of weight that is supposed to be supported by the batten at any location in the path of travel. Should the weight exceed or be reduced below the profiled weight by a preset value, the motor shall stop operation until the fault is cleared. SLACK LINE DETECTOR 1. The slack line detector is located in the Powerhead. When a slack line condition occurs, it shall cease motor movement and result in a fault message on the LCD screen on the controller. Movement in the upward direction shall be possible to clear the fault. E-STOP 1. The E-stop button on the QuickTouch controller shall be a mushroom button with a rear illuminated ring surrounding the button. During normal operation the E-stop button shall be in the out position. An E-stop can be activated via this Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual H. I. University of Georgia RCE 2013029 button by firmly pressing the button in. The button shall latch and immediately cause a class zero stop of all fixed speed motors and a class one stop of all variable speed motors in the system. The LCD screen shall report this as an E-stop condition. To continue system operation the Estop button must be cleared by twisting the button to release the latch. Power to the control station must be cycled off/on to re-initiate the system. This action shall also initiate a self-test of the entire control system and contactors. 2. The illuminated ring around each E-stop button shall be dimmable. The status of the lighted ring shall provide additional information about the state of the system as follows: a. Ring at low intensity: no motor moving b. Ring at high intensity: motor(s) moving c. Ring blinking: system in E-stop condition 3. Up to three remote E-stop stations may be connected to the system. Each additional E-stop station shall operate in the same way as the primary E-stop at the QuickTouch control panel. SYSTEM DIAGNOSTICS 1. Upon energization the control system shall perform an automatic series of diagnostic tests that assure that all system safety functions are working. Should an error in the safety functions be determined, the controller shall report back a fault condition in the LCD display window and shall identify the nature of the fault. 2. Monthly, the system automatically shall perform an additional series of diagnostic tests to determine if there are any problems with any portion of the motor control system safety features. In the event of a problem, the controller shall report back a fault condition in the LCD display window and shall identify the nature of the fault. 3. Eleven months after a system inspection has been performed, the system shall remind the user to schedule a full system maintenance/inspection. The reminder shall remain in the system with a count-down calendar until it is turned off by the factory authorized and trained inspector. 4. The installing contractor shall be able to leave contact information within the system. This information shall be displayed at power up and in the event of severe fault conditions. REMOTE CONTROL PENDANT Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual An optional remote control pendant with 30’ long attached cable and plug shall be provided for the system. The remote control must be plugged to the QuickTouch control panel. When the remote control is plugged in the E-stop on the remote is active. Systems requiring “shunt plugs” to bypass an unplugged remote control connector shall not be acceptable. 2. The remote control provides up/down control for those motors that have been preselected at the QuickTouch controller. TRIM POSITIONS 1. It shall be possible easily to store (and delete) up to five (5) Trim positions per motor 2. The user shall be able to utilize three of these positions as general purpose trim positions, one as user programmable upper limit and one as user programmable lower limit 3. During normal operation, the hoist shall stop at every trim position, but it shall also be possible to select a specific trim position as the target position for the next move. SPEED CONTROL 1. The motor controller shall provide a recessed speed adjustment slider 2. It shall be possible to adjust the speed of a running variable speed motor via this slider. During movement the LCD screen shall show the actual speed of the selected motor 3. It shall be possible to pre-set the speed for the next move for the selected motors. The LCD screen shall display the preset speed for the selected motors. SYSTEM COMMISSIONING 1. It shall be possible to commission basic functionality of the system without a laptop computer or additional software. 2. A trained installer shall commission the full system via a laptop computer connected via the built-in USB port in the controller. USB connectivity shall not require special USB drivers. 3. Commissioning software shall feature an inspection report generator that allows a step by step inspection of the control system. Upon completion, the system shall generate an inspection report in PDF format. 1. J. K. L. University of Georgia RCE 2013029 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3. University of Georgia RCE 2013029 EXECUTION 3.1 GENERAL A. B. C. D. Installation of this equipment shall only be performed by ETC approved and factory trained theatrical rigging installers. Installation shall be performed in a workmanlike manner and shall strictly adhere to the standards of these specifications and ETC’s installation requirements. Where necessary, the installer may make adjustments to accommodate unforeseen impediments to installation. The completed work must achieve all electrical, safety and appearance requirements as established in these specifications. Work shall be performed in accordance with OSHA and local codes. On site welding shall only be performed per AWS D1.1 standards and with advanced approval from the architect or Owner’s representative. DIVISION OF RESPONSIBILITIES 1. The RIGGING contractor shall be responsible for providing and installing: a. Powerhead b. Compression Tube, Compression Tube splices and Compression Tube beam clamps c. Supplementary steel and/or mounting adapters for the hoisting systems, if required. d. Loft blocks e. Wire rope lift lines and terminations f. On electrics line sets: Cable Management system for distribution raceways, including low-voltage, ground and data wiring g. On electrics line sets: Factory prewired electrical termination boxes that are part of the cable management system. h. On electrics line sets: Factory prewired distribution raceway mounted at the bottom of the wire rope on the stage electrics sets i. Pipe batten attached to RACAs or Hanger Brackets j. Batten end caps k. Batten labels l. Attachment of the prewired twist-lock connector to the Power and Control Distribution outlet m. Attachment of the prewired circular pin connector data wire to the mating outlet on the Powerhead and on the Power and Control Distribution box Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 n. 2. 4. Termination of the low voltage data wiring at the controller and at all power and control distribution boxes and at each E-stop station o. Face plates for all Control Stations, E-stop Stations and Power and Control Distribution Boxes p. Set limit switches The ELECTRICAL contractor shall be responsible for providing and installing: a. All pipe, wiring and termination providing line voltage to all the Power and Control Distribution boxes b. All pipe and wiring connecting data lines between the first Power and Control Distribution Box and the Control station c. Pipe and wiring connecting data lines between Control Station and first E-Stop Station d. All pipe and wiring connecting data lines between all E-Stop Stations. e. Back boxes for all Power and Control Distribution Boxes, the Control Stations and all E-Stop Stations. f. All pipe and wiring and all terminations of line voltage of dimmed and non-dimmed circuits that terminate at the termination boxes mounted on/near the Compression Tube. INSTALLATION 4.1 GENERAL A. B. C. D. Installation of this equipment shall only be performed by ETC approved and factory trained theatrical rigging installers. Installation shall be performed in a workmanlike manner and shall strictly adhere to the standards of these specifications and ETC’s installation requirements. Where necessary, the installer may make adjustments to accommodate unforeseen impediments to installation. The completed work must achieve all electrical, safety and appearance requirements as established in these specifications. Work shall be performed in accordance with OSHA and local codes. On site welding shall only be performed per AWS D1.1 standards and with advanced approval from the architect or Owner’s representative. DIVISION OF RESPONSIBILITIES 1. The RIGGING contractor shall be responsible for providing and installing: a. Powerhead Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual b. 2. University of Georgia RCE 2013029 Compression Tube, Compression Tube splices and Compression Tube beam clamps c. Supplementary steel and/or mounting adapters for the hoisting systems, if required d. Loft blocks e. Wire rope lift lines and terminations f. On electrics line sets: Cable Management system for distribution raceways, including low-voltage, ground and data wiring g. On electrics line sets: Factory prewired electrical termination boxes that are part of the cable management system. h. On electrics line sets: Factory prewired distribution raceway mounted at the bottom of the wire rope on the stage electrics sets i. Pipe batten attached to RACAs or Hanger Brackets j. Batten end caps k. Batten labels l. Attachment of the prewired twist-lock connector to the Power and Control Distribution outlet m. Attachment of the prewired circular pin connector data wire to the mating outlet on the Powerhead and on the Power and Control Distribution box n. Termination of the low voltage data wiring at the controller and at all power and control distribution boxes and at each E-stop station o. Face plates for all Control Stations, E-stop Stations and Power and Control Distribution Boxes p. Set limit switches The ELECTRICAL contractor shall be responsible for providing and installing: a. All pipe, wiring and termination providing line voltage to all the Power and Control Distribution boxes b. All pipe and wiring connecting data lines between the first Power and Control Distribution Box and the Control station c. Pipe and wiring connecting data lines between Control Station and first E-Stop Station d. All pipe and wiring connecting data lines between all E-Stop Stations e. Back boxes for all Power and Control Distribution Boxes, the Control Stations and all E-Stop Stations f. All pipe and wiring and all terminations of line voltage of dimmed and non-dimmed circuits that terminate at Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 the termination boxes mounted on/near the Compression Tube. 4.2 STAGE DIMMING AND CONTROL SYSTEM A. Electrical requirements of the Stage Equipment Contractor: The Stage Equipment Contractor shall be responsible for providing to the electrical contractor all stage lighting and dimming hardware as specifically detailed in these specifications. This shall include: 1. Furnishing all equipment specified. 2. Hanging of connector strips on specified stage rigging hardware. 3. Set-up of the control console. 4. Demonstration of equipment to owner's representatives. 5. Lamping & Hanging all stage lighting fixtures. 6. All low voltage lighting control terminations. The Stage Equipment Contractor shall not be responsible for the following work; to be performed by the electrical contractor.: Any conduit Any wiring Power requirements and termination of same in dimmer rack Any load wiring, fixtures, or termination at fixtures for house lighting or emergency lighting Mounting of plugboxes, floor pockets, back boxes and gridiron junction boxes (locations to be coordinated with stage equipment contractor) B. FACTORY CHECK-OUT: This contract shall also include the services of a qualified engineer regularly employed by the manufacturer of the system who shall check the installation and ensure its proper operation. No part of the system shall be energized before being so checked and the installation approved. Failure to observe this provision shall automatically relieve the manufacturer of any responsibility concerning the proper operation of the system or any part thereof and the replacement of parts which may have been damaged by the premature energizing. This engineer shall be made promptly available on the job site within fourteen (14) days after the manufacturer has received written notice. 4.3 DIMMER RACKS A. B. The installation rack shall be the Sensor as manufactured by Electronic Theatre Controls, Inc., or equal. The fully digital dimmer rack shall consist of up to 48 dimmer module spaces. Sensor rack systems shall be UL Listed and CSA Approved, and shall be so labeled when delivered to job site. The dimmer rack shall be provided with wired spaces for all circuits. Dimmers shall be provided for all base circuits and blank modules Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. 4.4 University of Georgia RCE 2013029 provided for all expansion circuits. Provide base circuits indicated in bill of materials. The dimmer racks shall house all dimmer modules, control electronics, and branch circuit breakers. Provide module and breaker quantities as indicated below. System shall have the performance features that follow. 1. Rack shall be UL Listed and labeled. 2. Rack shall employ dead front construction of code gage steel. 3. Each rack must have a hinged locking door. 4. Each rack must have an electrostatic air filter. 5. Ventilation shall be by a low-noise fan activated by DMX level data. 6. In the event of an over-temperature situation, each dimmer shall be shut down independently as required. Systems that shut the entire rack down upon over-temp will not be accepted. 7. Each 48-module dimmer rack shall be provided with a keypad and LCD display for rack configuration, backup and fault indication. 8. Each rack shall maintain active scene for a userprogrammable period after loss of DMX-512 signal from console. 9. Standard control format shall be USITT DMX-512. Dimmer rack CEM must accept two independent DMX signals concurrently in a highest-takes-precedence manner for each dimmer. 10. Rack shall store a minimum of thirty-two user-programmable back-up looks which may be activated in case of loss of control signal. 11. Each dimmer must include discrete "boost" feature to allow over-voltage output to compensate for voltage drop in branch wiring and allow a true 120 volts at the fixture lamp or “trim” maximum voltage output to lengthen lamp life. 12. Each rack shall include a beacon which shall flash to indicate failures. DIMMER MODULES A. B. Dimmer modules shall be plug-in type. No more than two dimmers per module will be accepted. Modules shall be assembled of aluminum or steel. Dimmer modules with housings manufactured of plastic or a flammable material will not be accepted. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. D. E. F. G. H. I. J. 4.5 University of Georgia RCE 2013029 Each dimmer module shall contain fully magnetic circuit breakers(s), solid state switching module(s), choke(s) and connectors. Each dimmer must have the discreet capability to operate in a dimmed or a non-dimmed mode. This function shall be selectable from the control console or the rack-mounted keypad. Each dimmer circuit shall use solid state switching devices consisting of two silicon controlled rectifiers in an inverse parallel configuration, snubber network and all required gating circuitry on the high voltage side of an integral opto-coupled control voltage isolator. Dimmer modules shall include toroidal filters to reduce lamp filament sing and limit the radio frequency interference on line and load conductors. The current rise-time shall be not less than 500 microseconds measured at 90-degree conduction angle from 1090% of the output wave-form with the dimmer operating at rated load. Power efficiency shall be at least 97% at full load. Dimmer shall accept hot-patching of an incandescent load up to the full capacity of the dimmer. Dimmer output shall be regulated for incoming line voltage variations, except that the output voltage cannot be increased above a level equal to line voltage less dimmer insertion drop. Line regulation shall be +/- 1V over a 90-140 volt range for changes up to 10%. Load regulation shall be +/- 2V for 1-100% of rated current. Dimmers shall employ a scheme for compensation for harmonic distortion of the power line for any variation in load. Response to control shall be less than 25 milliseconds. DIMMER FEEDBACK SYSTEM A. B. C. D. E. F. Rack shall be provided with a feedback network to provide rack performance data to the control console. The network shall provide operational information, which shall be displayed on the rackmounted LCD display and on the control console color monitor. A hand-held remote does not meet this requirement. System shall annunciate DMX port errors at the rack and control console. System shall annunciate backup cue errors at the rack and control console.. System shall annunciate individual phase voltages and power frequency at the rack and control console. System shall annunciate control link address and recorded error log status indicators at the rack and control console. System shall annunciate panic status at the rack and control console. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual G. H. 4.6 University of Georgia RCE 2013029 System shall annunciate airflow obstruction errors at the rack and control console. System shall monitor cabinet temperature and annunciate overtemperature at the rack and control console. CONTROL ELECTRONICS MODULE A. B. General 1. The dimmer rack electronics shall be contained in one plug-in Control Electronics Module (CEM+). Each CEM+ shall plug into a dimming cabinet, with no discrete wire connections. A simple User interface shall be provided for system configuration, testing and diagnostics. There shall only be one model for all rack types. Electronics 1. The CEM+ shall be provided with an Ethernet control signal input. This input shall be fully configurable with a range of patching and priority programming capabilities. 2. Two optically isolated DMX512 inputs shall also be provided, allowing overlapping or separation of any control level. 2,500V of optical isolation shall be provided between the DMX512 inputs and the CEM+. This shall protect the DMX512 inputs from a failed control module and the CEM+ from failed DMX512 inputs. Systems that do not have optical isolation on a prewired factory plug-in device shall not be acceptable. 3. The CEM+ shall be completely digital, without employing any digital-to-analog de-multiplexing schemes or analog ramping circuits. a. In the event of data loss each rack shall maintain the last level for a user-programmable time of zero to five minutes or indefinitely, or may be programmed to fade to and play an emergency preset. Systems that do not offer this feature shall not be acceptable. 4. The CEM+ shall respond to control changes in less than 25 milliseconds. Dimmer outputs shall exhibit no oscillating or hunting for levels. Dimmers set to the same level shall output within ±1V of each other, regardless of phase or electronic module control. 5. Dimmer output shall be regulated for incoming line voltages. The regulation shall adjust for both RMS voltage changes and deformations in the incoming AC waveform. The CEM+ shall monitor and adjust each dimmer's output to maintain a constant power to the load. Regulation shall maintain the desired output voltage ±1V for the entire operating range (90-140V AC) with the exception that the maximum output Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. University of Georgia RCE 2013029 will be no greater than the line voltage minus dimmer insulation loss. The regulation shall compensate for dips and anomalies in the AC waveform on a dimmer-by-dimmer basis. There shall be no interaction between dimmers in the system or any other equipment. The output shall be nominally regulated to 120V, but shall be field adjustable on a dimmer-by-dimmer basis to allow for varying cable length. 6. The entire response to incoming line changes shall take no more than 25 milliseconds. Dimming systems that do not respond to line fluctuations and do not contain wave deformation detection shall not be acceptable. 7. The CEM+ shall contain diagnostic routines to allow the user to test and troubleshoot the system. The CEM+ shall contain a Test/Bypass switch to turn all dimmers on to full for testing. This switch shall bypass all electronics and shall force the fan on. 8. A system-wide panic circuit shall be provided. Any dimmer in any rack may be assigned to the panic circuit. 9. The CEM+ shall be able to record up to 128 backup looks. Backup looks shall be programmable by recording current dimmer levels (as set by the console), by entering dimmer levels on the CEM+ directly, or a combination of both methods. When a backup look is active, the DMX512 inputs shall be ignored in the default priority mode. 10. All system functions may be activated by the CEM+'s user interface and shall not require any remote unit. Systems that do not offer this feature shall not be acceptable. 11. The CEM+ shall be able to configure dimmers for ETC Dimmer Doubling, which allows a single dimmer to set two different levels on one dimmer circuit by splitting the AC power into positive and negative halves. User Interface 1. A backlit 6-button keypad and 2-line-by-20-character backlit LCD shall be provided for system configuration, testing and diagnostics. The backlit design of the panel controls shall provide for ease of use in dark environments. a. The six buttons shall be Accept, Back, Plus, Minus, Home and Test. 2. The front panel shall have four status LED indicators: a blue LED for power status and three green LEDs for Network, DMX A, and DMX B status. 3. A reset switch shall also be located on the front of the unit. 4. Menu functions: a. DMXA/B or EDMX data may be assigned sequentially from a starting control channel (base addressing) or Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual b. c. d. e. f. g. h. University of Georgia RCE 2013029 patched per control channel to any dimmer via the user interface. The dimmer curve shall be capable of being set on a per-channel basis. The default curve shall be the IES modified square law. Additional curves include: Square Law, Linear, and Sensor v2.0. The CEM+ shall also have the capability of storing up to three custom curves and shall have an adjustable Preheat, all assignable on a per dimmer basis. The dimmer mode shall also be capable of being set on a per-channel basis. Modes shall include: Normal, Dimmer Doubled, Switched (unregulated on/off with adjustable threshold), or Fluorescent with adjustable threshold. DMX Loss behavior can be set to Hold Last look, Wait and Fade, or Fade to Preset. Up to 128 presets may be programmed, recording any level, whether set in direct level menu or by a Data input. Presets shall be activated in the default fade time of 2 seconds. The direct level menu shall provide the ability to set a dimmer or groups of dimmers to a level. The CEM+ shall be capable of monitoring and displaying [LCD] incoming line voltage for all three phases. With installed current sensors the same display shall show amperage on each phase. This display shall not timeout. English, French, German and Spanish language support shall be built in. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 5. D. University of Georgia RCE 2013029 The CEM+ shall contain the following user displays: a. Status display to show rack identification and errors. Error Messages shall include, but not be limited to, the following: 1) Dimmer has shut down due to over temperature 2) DMX port A or B has an error or has failed 3) Phase A, B or C is below 90 volts 4) Phase A, B or C is above 140 volts 5) Rack has shut down due to air flow loss 6) Ambient temperature is below 0°C/32°F 7) Ambient temperature is above 40°C/104°F b. Rack has shut down - ambient temperature exceeds 46°C/115°F c. The ability to program and activate system-wide backup looks from face panel or web User Interface. d. About display shall allow monitoring of system, rack or dimmer status. 1) About System shall provide information about Panic circuits, Preset looks, and System name. 2) About Network shall provide IP address, gateway and net mask. 3) About Rack General shall provide information about rack name, ambient temperature, air filters and rack type. 4) About Rack Power shall provide information about power type, rack voltages, current per phase (only with current transformers), under voltage warnings. 5) About Rack Data shall provide status for DMXA, DMXB, EDMX and Network activity. 6) About Dimmer shall provide information about dimmer type, location, output level, control source, scale voltage, mode and curve. e. Setup display shall allow but not be limited to, configuring of rack addresses, dimmer firing mode, and scale voltage values. Dimmer Status Network 1. The Dimmer Status network shall provide remote monitoring, programming and backup functions for the system through any Sensor-compatible console, PC, or hand-held remote device. System information shall also be displayed on any system interface including the CEM+ and the devices listed Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual E. F. University of Georgia RCE 2013029 above. Systems that do not provide both types of user interface shall not be acceptable. 2. Dimmer Status network shall provide an integral link to connect all racks in the system for rack-to-rack communication. Information for all configuration and backup looks shall be stored in all CEM+’s to allow swapping of CEM+’s throughout the system. Systems not storing all configuration data and backup looks for each dimmer in all control modules shall not be acceptable. 3. A technician shall be able to program all parameters onsite, using a laptop personal computer. These parameters shall include, but not be limited to, defining rack type, module type, scale voltage for each dimmer, firing mode, curve, dimmer numbering and DMX512 port assignments. Systems requiring factory programming shall not be acceptable. Advanced Features 1. Sensor's Advanced Features (AF) option shall add an additional sensor in the individual dimmer modules. The AF option shall allow monitoring of current and output voltage on a dimmer-by-dimmer basis and provide information on lamp burnouts, dimmer status, and input voltages. 2. The CEM+ shall allow the user to record the loads of all AF dimmers in the system. The CEM+ shall, during operation, test each AF dimmer, determine its load, and compare it to the recorded load. Any change from recorded loads greater than five percent shall display an error on the CEM+ and any monitoring device on the ETCLink network. Physical 1. Dimmer control electronics shall be contained in one plug-in Control Electronics Module, housed in a formed steel body with an injection-molded face panel. 2. An airflow sensor shall be provided. In the event of inadequate airflow, the affected rack shall shut down until the error is corrected. 3. If the ambient room temperature drops below 0°C/32°F or rises above 40°C/104°F, a warning shall appear on the dimmer rack LCD. If the temperature rises above 46°C/115°F, the rack shall shut down until the condition is corrected. 4. Dimmer control electronics module shall operate at up to 120/208V, three phase, four wire + ground, 47 to 63 Hz. The CEM+ shall automatically compensate for frequency variations during operation. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4.7 University of Georgia RCE 2013029 LIGHTING SYSTEM AND ACCESSORIES A. General 1. The lighting control desk shall be a microprocessor-based system specifically designed to provide complete control of stage, studio, and entertainment lighting systems. The device shall be the Ion as manufactured by Electronic Theatre Controls, Inc., or equal. 2. The system shall provide control of 1024 outputs, 1536 outputs, 2048 outputs, 2560 outputs or 3072 outputs on a maximum of 10,000 control channels, patched across any number up to 99,999. Output shall be distributed over a 10/100MB Ethernet network using Net3/ACN, ETCNet 2, Avab and/or ArtNet protocols. The user shall be able to control the application of protocols at an individual address level. 3. The system shall support full bi-directional RDM communication with compatible devices via Net3 DMX/RDM Gateways. RDM communication shall adhere to ANSII standard E1.20-2006 Entertainment Technology – RDM – Remote Device Management Over DMX512 Networks. Supported RDM features shall include: a. Discovery and identification of RDM capable devices b. Setting of start addresses, operating modes and additional settings as exposed by connected devices and controllable via RDM c. Viewing of Sensor data as provided by connected devices. d. Error reported as provided by connected devices. 4. A maximum of 10,000 cues, 999 cue lists, 1000 groups, 1000 presets, 4 x 1000 palettes (Intensity, Focus, Color and Beam), 1000 effects, 1000 macros and 100 curves may be contained in non-volatile electronic memory and stored to an onboard hard drive or to any USB storage device. 5. Recorded cue lists may be played back simultaneously on a maximum of 200 faders. Channels shall respond to cue information by last instruction with discrete rate control provided for all cues. The desk may be placed in Tracking or Cue Only mode by the user as a system default and overridden on individual record actions as required. HTP/LTP intensity flags, assert, proportional, intensity master or manual master fade control and independent status may be placed on each cue list. It shall also be Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 6. 7. 8. 9. 10. 11. 12. 13. University of Georgia RCE 2013029 possible for a cue list to contribute to playback background states or to withhold such contributions. A Master Playback fader pair and dedicated Grand Master/Blackout shall be provided. Up to six USB fader wings may be connected to the desk, for a maximum of 300 submasters and/or 200 playback faders. USB fader wings may be rigidly connected to the main desk to provide a "single connected unit" with no external cables required. The wings also may be connected via USB cables and used "on the side." Virtual fader control is also provided. A high-resolution level wheel shall be provided to control intensity for selected channels and scrolling within selected displays. Four page-able high-resolution encoders shall be provided for control of non-intensity parameters. Nonintensity encoders may be operated in coarse or fine mode, with the amount of movement per revolution of the encoders in coarse mode definable by the user. Nonintensity parameters shall be controllable via the encoders or keypad controls, without need of an external pointing device. A high-resolution rate wheel shall also be provided. Rotary encoders for non-intensity parameters shall be labeled by means of an integral LCD display mounted below the encoders on the main desk. The display shall show the currently loaded functions of the encoders based on the current selections. Systems using encoders with no LCD labeling shall not be acceptable. Control and programming features for automated fixtures shall also include: a standard library of fixture profiles, the ability to copy and edit existing profiles and create new profiles, patch displays including channel and output addressing, 16-bit fade resolution, color characterization allowing color mixing and storing in Hue and Saturation or native device values. System information, including playback status, live output and blind values for all record targets shall be displayed on a maximum of two external high resolution DVI monitors, or one SVGA monitor, which may also be touch-screen(s). Only one display shall be required for operation. A context sensitive on-line Help feature shall explain and provide an example of the operation of each feature of the system. A fully integrated Virtual Media Server feature shall allow the user to map images and animations to a rig array. 40 such maps may be created, each with 12 layers. Systems that Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 14. 15. 16. 17. 18. 19. 20. University of Georgia RCE 2013029 rely on external hardware or software for this functionality shall not be acceptable. User-definable, interactive displays may be created. These displays, which can be used in live and blind operating modes, allow graphical layout of channels, desk buttons and programming tools. Standard symbols are provided, and the user may import his own symbols or graphics. Each symbol may be individually defined with data feedback characteristics. Non-interactive status information, such as a mirror of other user’s command lines, may also be included in the display. A graphical browser is provided for fast selection of these views. Multiple zoom factors and placements may be stored and recalled for each display. An optional, full-functioning, detachable alphanumeric keyboard shall be supported. The keyboard shall allow labeling of channels, cues, presets, groups, palettes, effects, macros, curves and the show. An integral electronic keyboard shall be provided. A row of softkeys shall be provided, which change function based on the selection and context of the desk. These softkeys shall be labeled via an adjacent LCD display that shows their current functions at all times. Systems using softkeys with no LCD display shall not be acceptable. Software upgrades shall be made by the user via a USB port; changing internal components shall not be required. It shall be possible to install software updates in all consoles, processor units and remotes from one device over the network. The operating software shall be loaded into program execution memory from the internal hard drive when the console is powered. In the event of an uncontrolled shutdown, the device shall return to its last output state when power is restored. Dimmer monitoring and configuration features shall be provided (in conjunction with ETC’s Sensor+, Sensor 3 or FDX dimming systems) to allow indication of dimming system status, dimmer load monitoring and show specific configurations. Show data may be created and modified on a personal computer, using either Windows XP or Windows 7 operating systems, with a free offline editing application. The offline editor may also run natively on Intel-based Macintosh platforms using OS X. The program shall also allow output Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 21. 22. 23. 24. 25. 26. University of Georgia RCE 2013029 to visualization software supporting the same protocols as the lighting system. A PC using Windows XP or Windows 7/8 or an Intel-based Macintosh computer using OS X running a client software application shall be able to connect to a control system via the network and view or modify current show data in an independent display environment, using an Eos Family Client Dongle. When connected without the dongle, the computer shall operate in Mirror Mode, with the device to be mirrored selectable by the user. Systems that do not provide client software that may run natively on the Apple platform in this environment shall not be acceptable. Synchronized backup shall be provided via another full desk on the network or by use of a remote processor unit. The backup unit (either full desk or rack mounted Remote Processor Unit (RPU) shall maintain synchronized playback with the master and shall take over control of the lighting system upon loss of communication with the master. Use of two RPUs to service and backup system output is also supported. Systems that do not offer this kind of instant backup from multiple sources shall not be acceptable. A maximum of four users may access and interact with show data simultaneously. Each user shall have an individual workspace and channel partitioning shall be supported. User identification may be assigned to more than one control device, allowing users to work in tandem, or allowing a designer/ALD to mirror the current display format, mode and command line of the associated programmer. Partitioned control allows discrete control of channel/parameter groupings by user. Partitioned control may be easily enabled and disabled with no need to merge show data from multiple users. Mirror mode shall allow the desk displays and operating modes to be mimicked on another connected device. Alternatively, the desk may mirror another device. The system shall allow remote control from external devices as follows: Client software running on a PC connected to the network, a remote video interface with keyboard, a purpose-built wireless remote focus unit (Radio Focus Remote). Universal fader wings may be attached to any of these devices for local fader control. Systems without these remote control devices shall not be acceptable. The system shall support a Telephone remote control that allows basic functions to be controlled from a standard wireless phone producing touch-tone signals. This allows Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. University of Georgia RCE 2013029 the use of a standard telephone for a low cost remote control. Systems that do not allow this function shall not be acceptable. 27. Show data may be created and modified on a personal computer, using either Windows XP or Windows 7/8 operating systems, with a free offline editing application. The offline editor may also run natively on Intel-based Macintosh platforms using OS X. The program shall also allow output to visualization software supporting the same protocols as the lighting system. 28. The system shall support up to 32 individual Time Code Event lists. Controls and Playback 1. Manual Control and Programming Section a. The programming keyboard shall be grouped by function. Major groupings shall be record target functions, numeric keys, level assignment functions, display navigation functions and controls. b. Non-intensity parameters may be set numerically or via the encoders. This control shall be fully interactive. In either case the current parameter value shall be displayed on the desk monitor and simultaneously on the integral LCD display. Systems using only a local LCD or only a video monitor shall not be acceptable. c. Only those parameters available for control in the active lighting system shall be displayed for control. d. Lamp controls provide direct access to luminaire functions such as striking and dousing arc lamps and calibrating entire fixtures or individual mechanisms of fixtures, as provided by the luminaire manufacturer. User access to these features is normalized across all manufacturers for ease of use. Use of a “control channel” for accessing these functions shall not be required and systems requiring use of a control channel shall not be acceptable. Lamp control commands maybe e staged, and channels which have been sent lamp on commands so indicated in live. e. Fan functions shall be provided both via command line operation and through encoder controls. f. Highlight shall be supported, with user definable highlight values. Lowlight conditions may be defined for selected, but not specified channels. Rem Dim command, at specific levels by channel, may be Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2. 3. University of Georgia RCE 2013029 optionally and automatically called with the highlight command. g. Fixtures with CMY or RBG color mixing may be set with direct CMY or RBG controls, as well as the Hue and Saturation encoders and/or color picker. Color may also be set directly to a gel match, via a graphic selection tool or from the command line. h. The Virtual Media Server function shall allow the user to create layouts of devices, identified as pixel maps. Media content (images, movies, text and procedurally generated effects) may then be applied, manipulated and stored. Stock content is provided and the user may import custom imagery and animations. i. Macros may be set to run as default. Default macros called manually shall post to the command line, but executed via cue lists shall run in the background. The user may override this behavior by defining the macro to always execute in the foreground or the background, regardless of the recall method. Startup, Shutdown and Disconnect macros may also be defined. Playback Section a. The master fader shall consist of a 60mm Master Fader pair with associated Load, Go and Stop/Back buttons. Additional playback faders may be configured via the virtual fader module or on the Universal Fader Wings. b. It shall be possible to instantaneously halt an active cue, back to the previous cue, manually override the intensity fade or manually override the entire fade. c. It shall be possible for a cue list to contribute to the background state or for the contents of each cue list to be withheld from such. d. The playback faders shall have the following associate controls: 1) Freeze, which halts the output of the fader 2) Stop Effect, which stops the action of an effect. 3) Filter, to assign filter states to a fader 4) Go to Cue 0, to reset a cue list. Fader Wings (Optional) a. Submaster and fader support shall be provided via optional fader wings. These wings are available in 1x20, 2x10 and 2x20 configurations. Up to six of these wings may be connected to the desk via internal or external USB. Via paging, access is Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. University of Georgia RCE 2013029 provided to all 300 faders, regardless of the number of physical wings attached. b. The 2x10 and 2x20 fader wings shall include a full length LCD for labeling and identification functions. Each fader shall have two associated hard buttons for various operations. Systems without a local display or fewer than two buttons per fader shall not be acceptable. c. Up to 300 proportional, fully overlapping additive, effect or inhibitive submasters may be defined. Submasters shall have colored LEDs to indicate submaster status. Each submaster may have fade up, dwell and down fade times. Each has a bump and assert/channel select button. Submasters may be set to independent, exclusive, shielded and proportional/intensity or effect master control. d. The submaster blind buffer shall be linked directly to live playback allowing live editing of live submaster content via the command line. e. It shall be possible to set submaster values directly from the command line. f. Up to 200 cue lists may be active concurrently. 4. Grand Master a. A dedicated grand master and blackout button are provided. b. The grand master shall proportionally fade intensity values to zero. Blackout shall send all intensity outputs to zero. Non-intensity outputs shall not be affected. No additional configuration shall be required to withhold non-intensity values from Grand Master and Blackout control. Display Controls 1. Format shall change the view of selected displays. 2. It shall be possible for the user to choose which parameter categories or parameters (s)he wishes to display. 3. Flexichannel shall change which channels are viewed in selected displays, as follows: a. All channels b. Patched channels c. Show channels d. Active/Moved channels e. Selected channels f. Manual Channels g. View channels (user identified list) h. Channels with discrete timing Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4. D. University of Georgia RCE 2013029 Expand shall extend the selected view sequentially across connected displays, vertically or horizontally. 5. [Time] depressed shall display discrete timing data. [Data] depressed shall display absolute values of referenced data. 6. User definable magic sheets shall provide alternative display of and access to channels and record targets. Multiple magic sheets may be created. 7. Playback status displays are provided with a variety of different formats. Indications are provided per cue for live moves (lights fading from zero and also moving nonintensity parameters) and dark moves (inactive lights which have stored non-intensity parameter moves). Operating Modes 1. Live Mode a. Channel lists may be constructed using the +, - and Thru keys as well as the direct selects. Channel selection and deselection is fully interactive, regardless of the method used. b. Levels may be set with the keypad, level wheel and non-intensity encoders. “Selected” channels shall be those last addressed and under keypad control. c. Sneak shall be used to restore specified channels to background states, default values, or to send them to specified values, in user specified or default times. d. Selected channels may be set at a level or held to current values while all other channels are set to zero using Rem Dim. Toggling Rem Dim shall restore all unselected channels to original levels. The Rem Dim level shall be user definable via the command line or with a default setup value. e. Channels may be recorded into groups for fast recall of commonly used channels. 1000 groups shall be available. Groups shall store selection order. The Offset function supports rapid creation of ordered groups, including reverse and random order. f. Parameter settings may be stored to Intensity, Focus, Color and Beam Palettes and to Presets. All referenced data may be stored to whole numbers or to up to 99 decimal places between each whole number. It shall be possible to store 1000 presets and 1000 of each palette type. g. Any collection of channel data, as determined by the use of “Record”, “Record Only, selective store commands and/or parameter filters may be stored to palettes (as appropriate to the type) and presets. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual h. i. j. k. l. University of Georgia RCE 2013029 The following conditions may be placed on a channel or channel parameter to be included with a cue record action. 1) Discrete fade time and/or delay 2) Block flag 3) Assert flag 4) IFCB Filters, which may be set at a parameter level. 999 cue lists may be stored. Cues may be recorded in any order. Up to 99 decimal cues may be inserted between any two whole number cues. Each cue may contain a maximum of twenty parts. Parameters may be automatically assigned to specific parts or assigned when the part is created. It shall be possible to record cues and cue parts with the following information: 1) Any collection of channel data, as determined by the use of “Record”, “Record Only” or selective store commands, combined with parameter filters. 2) Cue Level timing and delays for Intensity Up, Intensity Down, Focus, Color and Beam. 3) Follow or hang time 4) Link instruction 5) Loop value 6) Block, Assert, Allfade, Preheat and/or Mark Flag 7) Curve 8) Label and note 9) Execute list to trigger other activity Non-intensity channel parameters may be marked (preset), in two ways. Automark presets any parameters transitions in the cue just prior to intensity becoming active. Automark may be disabled on a cue or cue part basis, enabling a “live” move. Alternatively, non-intensity parameters may be marked to a specific cue with a single command instruction. It shall not be necessary to store these parameters directly into the cue in which the movement is to occur. Any channel parameter may be stored with an effect instruction. These effects may contain relative offsets from current value, or absolute instructions. Effects may be progressive action or on/off states. Entry and Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual m. n. o. p. q. r. s. t. u. v. University of Georgia RCE 2013029 exit behaviors shall modify the channel parameters activity when beginning and ending the effect. Update may be used to selectively add modified parameter data quickly to that parameter’s current source. It shall be possible to update inactive record targets. It shall also be possible to update back to the current source of the move instruction without specifying that cue via Trace. A context sensitive display provides detailed information regarding the results of the update command. Recall From quickly pulls specified data from record targets or other channels into the current view. Recall from on an HTP basis shall be provided. Copy To quickly copies selected data to specified channels or other record targets. Address and channel check functions shall be provided. Channel parameters may be “parked” at levels. Output addresses may also be parted directly. Parked levels shall not be added to any live record operations, nor may they be changed until the parked element is “unparked”. Address Park shall also be provided. About shall provide detailed status of selected channels or specified record targets. This shall include current source, current value, discrete timing, parked value, marked to and for indications. Background levels and current DMX output are also displayed. Channel usage indicates submaster and cue information and also provides a "dark moves" report on a per channel basis. 1000 snapshots may be stored which instantly recall specified front panel and display configurations. Live data may be displayed in a summary view, detailed table orientation or a user-defined magic sheet. Undo shall be used to sequentially step back through manual operations, record, update and delete actions. Redo functions shall be provided. Multiple undo commands may be executed at once. Home shall set selected channels non-intensity parameters to their default values. User definable home, on a per- channel/per- parameter basis shall be provided. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual w. x. 2. 3. 4. University of Georgia RCE 2013029 Move shall allow all show data to be moved from one record target to another. Query shall allow selection of channels by their current or possible state. Keywords and fixture types shall allow quick access to fixtures. Blind a. The Blind display allows viewing and modification of all record targets without affecting stage levels. b. Record target data may be displayed in a summary view, a detailed table orientation or a spreadsheet view, which allows quick data comparisons, move and replace with functions. c. Changes made in blind displays shall be automatically stored. d. Blind editing shall be possible for all record targets. e. Selection of what parameter data to view for blind editing shall be user configurable. Patch Display a. Patch shall be used to display and modify the system control channels with their associated library data. b. Each channel may be provided with a proportional patch level, preheat, curve, label, swap and invert functions. c. Offset functions in patch shall allow selection of channel ranges and shall allow the user to establish a “custom” footprint for any device output. d. A full library of profiles is provided, with the ability for the user to define “favorites” for fast selection. e. Custom color wheels, color scrolls and gobo wheels shall be defined in patch. These devices shall be created with a simple table and graphical user interface supported by images of major manufacturers. f. Copy to and Move functions shall be supported in patch. g. RDM discovery and device monitoring shall be supported. Setup/Browser a. Setup shall access system, show and desk configurations. b. The browser shall access show data storage, import, export, print to .pdf and clear functions, as well as show data utilities. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 c. E. It shall be possible to partially merge show files. Users shall be able to select as much or as little of the show file as required, with renumber tools. d. It shall be possible to import ASCII and Lightwright data files. It shall be possible to export as ASCII or .csv. Dimmer Monitoring and Configuration 1. The lighting control system shall provide communication with an ETC Sensor+, Sensor3 or FDX dimming system for remote monitoring and configuration of show specific functions from within the software application. 2. Circuit level configuration and monitoring functions shall include but not be limited to: a. Control mode (dimmable, switched, latch-lock, always on, off or fluorescent). b. Curves c. Control threshold d. Min and Max Scale Voltage e. Preheat f. Scale load 3. Rack Status messages shall include but not be limited to: a. State of UL924 panic closure b. DMX port error/failure c. Network error/failure d. A, B, C Phase below 90 or above 139 volts and headroom warning e. Ambient temperatures out of range 4. Circuit status shall include but not be limited to: a. Module type and location b. Output level c. Control Source d. Overtemp Advanced circuit feedback shall include but not be limited to: a. Load higher or lower than recorded value b. DC detected on output c. SCR failed on/off d. Breaker trip e. Module has been removed f. Load failure g. Shutdown due to Overtemp 5. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual F. G. H. University of Georgia RCE 2013029 Training Options 1. Training packages shall be available customizable to the individual venue preferences and needs. The level of training (beginner, intermediate or advanced) may be selected and training may be defined as an element of system commissioning or deferred to a later time. Interface Options 1. The unit shall support a variety of local interfaces. a. AC input. b. USB (five ports for connecting devices such as an alphanumeric keyboard, mouse, touch screens, USB Flash drive, fader wings, etc.) The desk shall provide four ports on the rear of the unit and one on the control service itself. c. Ethernet (one port) 802.3af compliant d. Two DVI video output connectors, supporting a maximum of two DVI monitors at 1280x1024 resolution minimum. e. One VGA output connector. f. Up to six fader wings may be attached to the main console via internal or external USB connections. Systems that do not allow the addition of fader wings shall not be acceptable. g. Two DMX512-A/RDM Ports h. Contact Closure Trigger via D-Sub Connector i. Phone Remote j. MIDI In/Out (MIDI Timecode, MIDI Show Control) Accessories 1. Net3 Radio Focus Remote 2. iRFR and iRFR Preview (application for iPhone, iPod Touch and iPad units) 3. aRFR (application for Android devices) 4. Net3 Remote Video Interface 5. 1 x 20, 2x10 and 2x20 Universal Fader Wings 6. Net 3Gateways a. Net3/ETCNet 2 to DMX/RDM Gateways (one to four ports) b. MIDI/SMPTE Gateways c. I/O Gateway with 12 analog inputs, 12 SPDT contact outputs, RD232 interface 7. Eos Family Client Software Kit Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual I. J. 4.8 University of Georgia RCE 2013029 Synchronized Backup 1. An optional Backup system shall consist of one of the following combinations of devices: a. Two networked desks b. One (or more) desk with one Remote Processor Unit (RPU) c. One (or more) desk with two Remote Processor Units (RPUs) Physical and Acoustical 1. All operator controls and electronics for a standard system shall be housed in a single desktop console, not to exceed 19” wide, 19” deep, 5.5” high, weighing 20 pounds. 2. Power shall be 95 – 240V AC at 50 or 60Hz, supplied via a detachable power cord. 3. At typical CPU utilization, the unit shall operate at ≤ 26 dBA. RADIO FOCUS REMOTE A. B. General 1. The Net3 Radio Focus Remote (RFR) shall be a wireless remote control device that allows access to a variety of system functions. The hand-held transmitter unit shall provide access to frequently used commands for dimmer and channel checks as well as extended functions of the console via softkeys. The receiver unit shall plug directly into the console via USB or may connect to the lighting system via Ethernet. 2. The RFR shall be compatible with the ETC Eos and Congo lighting control systems and their associated consoles, Remote Processor Units (RPUs) and lighting playback controllers. 3. The system shall support multiple units on one receiver as well multiple systems operating separately in the same area. 4. The system equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. Handheld Device or Transmitter 1. The transmitter unit shall have a slide switch (on/off), 24 keys for console commands, two rotary encoders with builtin switches and one backlit display. The unit shall also have a programmable “sleep” feature that helps to conserve battery life when the switch is left in the “on” position. 2. The keys of the transmitter unit shall be illuminated. The keys will be brightly lit while keys are pressed and the unit is Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. 4.9 University of Georgia RCE 2013029 transmitting. After the key is released, the keys will remain dimly lit for a period of time before the unit sleeps. 3. The transmitter shall have one dedicated command for each key on the unit with the exception of the six soft keys. Dedicated commands shall be displayed within each key. Softkey functions shall be accessed via a “More SK/Mode” key and shall be indicated within the built-in display. 4. Functionality of the unit shall be determined by the control system it is connected to. Eos systems shall provide Eos commands, and Congo systems shall provide Congo commands. 5. The transmitter unit shall be provided with rechargeable nickel metal hydride (NimH) batteries for power. These batteries should provide approximately two days of normal usage before requiring recharging. 6. The transmitter shall be a rugged steel unit, 2.7"(68mm) wide, 6.6"(168mm) high and 0.8"(20mm) deep, excluding the fixed helical antenna. The unit shall weigh 14 oz (400g), including antenna. The unit shall come complete with a hanging point for a wrist strap or lanyard. 7. The Radio Frequency Output for the transmitter shall be 2.410 GHz with 11 additional HF: channels available (2.410GHz - 2.465 GHz). 99 Network IDs available per channel. 8. The working range of the radio signal shall be 300’ (90m) in an indoor environment and 650’ (200m) in an outdoor, free field environment. Receiver Unit 1. The receiver unit shall be provided with a 6.6’ (2m) USB cable. The receiver may also be plugged into an available powered Ethernet port elsewhere in the system, however the maximum distance (cable length including cable inside the wall) from the power source shall be 330’ (100m). 2. The receiver unit shall be powered directly by the USB connection or by a Power-over-Ethernet connection. 3. A signal LED shall illuminate when the receiver is receiving radio signal from the transmitter. 4. The receiver shall be housed in a unit 2.8" (71mm) wide, 4.4" (112mm) high and 0.7" (45mm) deep, and shall weight 13 oz. (380g) including antenna. REMOTE PLUG-IN STATIONS A. The Remote Plug-in Stations shall consist of the appropriate connectors required for the system in use. These stations shall be available with DMX input & remote focus unit. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. C. D. E. 4.10 The following standard components shall be available for Remote Plug-in Stations: 1. RJ45 connectors for Network connections - Twisted Pair Custom combinations and custom control connections shall be available. Station faceplates shall be .80” aluminum, finished in fine texture, scratch-resistant black powder coat. Silk screened graphics shall be white. The station panel shall mount into an industry standard back box, depending on size and quantity of connectors. A terminal block shall be supplied for contractor terminations. DISTRIBUTION A. B. C. D. E. F. G. H. 4.11 University of Georgia RCE 2013029 Wiring devices shall be fabricated from 16-gauge cold rolled steel. Devices shall be properly cleaned, primed and painted with flat black baked enamel. Circuit numbers shall be 2" high. Individual pigtails and outlets shall be evenly spaced in connector strips, or as otherwise specified. Where a circuit would fall on a joint it shall be moved 3" towards the junction box end of the strip. Pigtails shall be three-wire type "SO" rubber jacketed cable sized for the circuit capacity. Connectors are 20A stage pin connectors. Internal wiring shall be sized to circuit capacity and terminated in feed through compression terminals at one end for ease of installation. Wire shall be rated at 125°. Devices except for wall mounted boxes shall be supplied with appropriate hardware for mounting as shown on the drawings. Connector strips shall have brackets on 5' centers. For connector strips provide multi-conductor SO type cable(s) as required to allow all devices to fly within 3’ above finished floor. Provide two (2) cable strain relief grips and one (1) cable cradle for each section of multi-conductor cable. Units to be sized for proper fit and function. Plug boxes shall be mounted as indicated with scheduled circuit outlets. Wiring devices shall be UL Laboratories Listed. SOURCE FOUR ELLIPSOIDALS A. B. C. The ellipsoidal spotlights shall be the Source Four spotlights. Source Four's high efficiency lamp shall utilize a compact tungsten filament contained in a krypton-filled quartz envelope. The lamp base shall be an integral die cast aluminum heat sink that reduces seal temperature and ensures proper lamp alignment. The lamp shall be 575 Watts with 16,500 lumens, with a color temperature of 3,250 K and have 300 hours of lamp life. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual D. E. F. 4.12 University of Georgia RCE 2013029 Source Four's optical train shall combine a compact filament lamp with a precision molded borosilicate, ellipsoidal reflector and a single aspheric lens to produce an optimum cosine field. Source Four ellipsoidal spotlights are constructed of rugged, die cast aluminum, finished in black, high temperature epoxy paint. Tools are not required for either lamp alignment or cleaning the reflector or lens. Precision tooled mechanical assemblies provide smooth operation, positive locking of adjustments and interchangeable components. Source Four ellipsoidals shall provide, but not be limited to: 1. Die cast aluminum housings 2. Integral cable clamp for power leads 3. Positive locking of lamp focus 4. Independent lamp alignment controls 5. High impact, thermally insulated knobs and shutter handles 6. Reflector secured with shock mounts 7. Rotating shutter assembly for keystone angles 8. Heavy gauge stainless steel shutters 9. Lens secured with silicone shock mounts 10. Interchangeable lens tubes for different fields 11. Teflon guides for smooth lens tube movement 12. Sturdy gel frame holders with two accessory slots 13. Top mounted, quick release gel frame retainer 14. Rugged steel yoke with two mounting positions 15. 300+ Rotation of fixture within yoke 16. Positive locking, hand operated yoke clutch SOURCE 4 PAR A. B. C. The instrument shall be a Source Four Par. The instrument shall utilize a 575 watt HPL lamp which is a compact tungsten filament contained in a krypton-filled quartz envelope. 1. The lamp shall mount axially within the reflector and shall be prefocused within the reflector. 2. The lamp base shall have a integral die cast aluminum heat sink that reduces seal temperature and ensures proper lamp alignment. 3. The lamp socket shall be ATP 220 nickel gold plated. 4. All versions of the instrument shall use only lamp type, the HPL lamp. Fixtures which require the purchasing of multiple lamp types to achieve different field angles shall not be acceptable. The spotlights are constructed of rugged, die cast aluminum, free of burrs and pits, finished in black, high temperature epoxy paint. Tools shall not be required for cleaning the reflector or lens Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual D. E. University of Georgia RCE 2013029 The spotlight shall provide, but not be limited to: 1. Integral cable clamp for power leads 2. High impact, thermally insulated knobs 3. Sealed reflector housing shall prevent all light leaks. Temperature control of reflector is obtained through 17 heat sink fins cast into the housing. 4. Interior of unit shall contain ten baffles to eliminate beam scattering and spill light. 5. Lamp socket shall be held into place by a brass self retaining screw. 6. Lens shall be secured with cast bosses and high temperature bronze spring release. No tools shall be required to change lenses. 7. Sturdy gel frame holders with two accessory slots and a top mounted, quick release gel frame retainer 8. Rotation of fixture within yoke 9. Positive locking, hand operated yoke clutch 10. Each unit shall be provided standard with colorframe and 36” bare lead. 11. Unit shall be nominally 11”long by 10” wide 12. Weight without “C” clamp shall be 8 lbs. The spotlight shall be UL and CUL approved 1. It shall be possible to change field type of the spotlight through interchangeable lenses. No tools shall be 2. 3. 4. possible while the unit is active. No tools shall be necessary for lens rotation. Fixtures, which require user to touch the lamp or lamp socket to orientate the beam, shall not be acceptable. Interchangeable lens sets shall consist of clear, very narrow spot, narrow spot, medium flood, and wide flood. Lenses shall be heat resistant, borosilicate glass. Beam orientation of MFL and WFL lenses shall be possible through rotation of lenses in a rotatable collar housed in the front of the unit. Collar shall be a high temperature heat resistant rotating collar with finger holds for precise movement. The optical train shall combine a compact filament lamp with modified parabolic and multifaceted reflector. Reflector efficiency shall be a minimum of 93%. Reflector shall be cast into a heat sink assembly. Reflector finish shall be an enhanced aluminum deposition. Reflectors of pressed aluminum sheet construction shall not be acceptable. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4.13 University of Georgia RCE 2013029 FRESNEL SPOTLIGHT A. B. C. D. General 1. The luminaire shall be a Source Four Fresnel spotlight as manufactured by Electronic Theatre Controls, Inc., or approved equal Lamp 1. The luminaire shall utilize only the HPL lamp, which shall consist of a compact tungsten filament contained in a krypton-filled quartz envelope 2. The lamp base shall have an integral die cast aluminum heat sink that reduces seal temperature and ensures proper lamp alignment 3. Luminaires that use lamps other than the HPL lamp shall not be acceptable 4. The lamp socket shall be ATP 220 nickel gold plated 5. The lamp shall be prefocused in relation to the reflector 6. The lamp shall be removable from the bottom of the fixture for re-lamping Optical 1. Luminaire shall use a Fresnel lens and provide soft-edged, but well-defined beam shaping with a barn door attachment 2. Luminaire shall provide a field angle zoom range of 20 degrees to 65 degrees 3. The optical train shall utilize a compact filament lamp with a modified spherical reflector 4. The luminaire shall output no less than 10,000 field lumens in full flood setting when fitted with 750W, 115V high out-put HPL lamp 5. Luminaires producing less than 10,000 field lumens in full flood setting with a 750W lamp shall not be acceptable 6. Reflector shall be molded borosilicate glass with multiple dichroic layers 7. Reflector efficiency shall be a minimum of 93% 8. Reflectors of pressed aluminum or other sheet metal construction shall not be acceptable Physical 1. The luminaire shall be constructed of rugged, die cast aluminum, free of burrs and pits, finished in black, high temperature paint 2. The luminaire shall provide, but not be limited to: a. 36” power lead with bare-ends b. Integral cable clamp for power leads c. Sealed housing with no light leaks Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 d. 3. 4. 5. 6. 4.14 Zoom adjustment by means of a large, side-mounted knob with integral locking lever e. Bottom-access lamp removal f. Lamp socket access door shall use a tool-free ¼-turn closure device g. Two accessory slots and a top mounted locking door for gel frames and beam control accessories 1) Accessory slots shall be completely surrounded by a rugged metal housing for elimination of light leaks around gel frames and other beam control accessories 2) Accessory slots shall be compatible with 7.5” beam control accessories, i.e. barn doors, gel frames, top hats, etc, such as used by Source Four PAR luminaires and other similarly-sized fixtures h. Rugged steel yoke i. Adjustable yoke mounting position for variable fixture balance point j. Positive locking, hand operated yoke clutch k. Large, rugged handle on rear of fixture l. Integrated safety cable mounting ring m. Color frame Unit shall be nominally 12.5”long by 9.5” wide Weight without “C” clamp shall be 13.25 lbs. The luminaire shall be capable of utilizing ETC Dimmer Doubling technology The luminaire shall be ETL and cETL listed to UL 1573 – the standard for stage and studio use and so labeled. COLOR MIXING LIGHT EMITTING DIODE WASH FIXTURE A. B. General 1. The fixture shall be a color-mixing high-intensity LED illuminator with DMX control of intensity and color. The fixture shall be a Desire D40 or D40 Studio as manufactured by Electronics Theatre Controls, Inc. or approved equal. 2. All LED fixtures shall be provided by a single manufacturer to ensure compatibility 3. The fixture shall be UL 1573 listed for stage and studio use 4. The fixture shall comply with the USITT DMX-512 A standard Physical 1. The fixture shall be contained in a rugged all-metal die-cast housing, free of burrs and pits. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2. C. D. University of Georgia RCE 2013029 The housing shall have a rugged black powdercoat finish a. White or silver/gray powdercoat finishes shall be available as color options b. Other powdercoat color options shall be available on request 3. Power supply, cooling and electronics shall be integral to each unit. 4. Fixture housing shall provide two easy-access slots for secondary lenses and other accessories a. Slots shall be equipped with locking retaining clip 5. The unit shall ship with: a. Theatrical-style hanging yoke as standard b. 5’ power lead with Edison connector as standard c. 25 deg. secondary lens as standard 6. Available options shall include but not be limited to: a. Yoke with floor stand conversion feature b. Bare-end, Stage-Pin or Twist-lock type-equipped power leads c. PowerCon to PowerCon cables for fixture power linking d. Multiple secondary lens options to include multiple angles in the following patterns: 1) Linear 2) Round 3) Oblong 7. Light output shall be via a round aperture a. Aperture and accessory slots shall accommodate standard 7.5” accessories such as used in other similar-sized fixtures b. Accessories available as options shall include but not be limited to: 1) Gel/diffusion frames 2) Top hats 3) Barndoors 4) Egg crate louvers 5) Concentric ring louvers 6) Multiple secondary lensing options ENVIRONMENTAL AND AGENCY COMPLIANCE 1. The fixture shall be UL and cUL LISTED and/or CE rated, and shall be so labeled when delivered to the job site. 2. The fixture shall be UL LISTED to the UL1573 standard for stage and studio use 3. The fixture shall be rated for IP-20 dry location use. THERMAL Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 1. E. F. University of Georgia RCE 2013029 Fixture shall be totally convection cooled, requiring no cooling fan. Fixtures which require an on-board cooling fan shall not be acceptable unless pre-approved 2. The fixture shall utilize advanced thermal management systems to maintain LED life to an average of 70% intensity after 50,000 hours of use a. Thermal management shall include multiple temperature sensors within the housing to include: 1) LED array circuit board temperatures 2) Temperature sensors placed on each individual LED color circuit 3) Fixture ambient 4) CPU b. Fixture user shall permit monitoring of temperature sensors via a legible LCD multi-line backlit display c. Fixtures that do not provide active thermal monitoring of LED circuits and other temperature readings shall not be acceptable 3. The fixture shall operate in an ambient temperature range of -20°C (-4°F) minimum, to 40° C (104°F) maximum ambient temperature. ELECTRICAL 1. The fixture shall be equipped with 100V to 240V 50/60 Hz internal power supply 2. The fixture shall support power in and thru operation a. Power in shall be via Neutrik® PowerCon™ input connector b. Power thru shall be via Neutrik ® PowerCon ™ output connector c. Fixture power wiring and accessory power cables shall be rated to support linking of multiple fixtures up to the capacity of a 15A breaker 3. The fixture requires power from non-dim source 4. Power supply outputs shall have self-resetting current limiting protection 5. Power supply shall have power factor correction LED Emitters 1. The fixture shall contain a minimum of 5 different LED colors to provide color characteristics as described in Section G below. 2. All LEDs used in the fixture shall be high brightness and proven quality from established and reputable LED manufacturers. a. Fixture shall utilize Luxeon® Rebel™ LED emitters Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 3. G. H. Manufacturer of LED emitters shall utilize an advanced production LED binning process to maintain color consistency. 4. LED emitters should be rated for nominal 50,000 hour LED life to 70% intensity 5. All LED fixtures (100% of each lot) shall undergo a minimum eight-hour burn-in test during manufacturing. 6. LED system shall comply with all relevant patents CALIBRATION 1. Fixture shall be calibrated at factory for achieve consistent color and intensity output between fixtures built at different times and/or from different LED lots or bins a. Calibration data shall be stored on the LED array as a permanent part of on-board operating system b. All arrays, including replacement arrays shall be calibrated to the same standard to insure consistency c. Fixtures not offering LED calibration shall not be acceptable COLOR 1. The fixture shall utilize an minimum of 40 LED emitters 2. The fixture shall be available in specialized LED arrays as outlined below: a. Desire D40 1) Red, Amber, Green, Cyan, Blue, Indigo and White LEDs in an array designed for broad spectrum color, light tints, and variable whites. This array shall be the Lustr+ array as manufactured by Electronic Theatre Controls, or approved equal (i) 2) Measured brightness of the Lustr+ array shall be greater than 2900 field lumens Red, Orange, Amber, Green, Cyan, Blue and Indigo LEDs in an array designed for broad spectrum deep colors. This array shall be the Vivid array as manufactured by Electronic Theatre Controls, or approved equal (i) 3) Measured brightness of the Vivid array shall be greater than 2500 field lumens Red, Orange, Amber, Green and Indigo LEDs in an array designed for extra-high brightness output in red/warm end of the spectrum. This shall be the Fire array as manufactured by Electronic Theatre Controls, or approved equal Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 (i) 4) Measured brightness of the Fire array shall be greater than 2500 field lumens Red, Orange, Green, Cyan, Blue and Indigo LEDs in an array designed for extra-high brightness output in the blue/cool end of the spectrum. This shall be the Ice array as manufactured by Electronic Theatre Controls, or approved equal (i) b. Measured brightness of the Ice array shall be greater than 1800 field lumens Desire D40 Studio 1) Warm White, Cool White, Red, Green, Blue and Indigo LEDs in an array designed for highbrightness variable color temperature white light output. This shall be the Studio HD array as manufactured by Electronic Theatre Controls, or approved equal (i) 2) Measure brightness of the Studio HD array shall be greater than 3100 field lumens All Warm White LEDs in an array designed for non-variable single color high-output, warm white light. This shall be the Studio Tungsten array as manufactured by Electronic Theatre Controls, or approved equal (i) 3) Measure brightness of the Studio tungsten array shall be greater than (TBD) field lumens All Cool White LEDs in an array designed for non-variable single color high-output, cool white light. This shall be the Studio Daylight array as manufactured by Electronic Theatre Controls, or approved equal (i) I. Measure brightness of the Studio Daylight array shall be greater than field lumens DIMMING 1. The LED system shall use 15-bit nonlinear scaling techniques for high-resolution dimming. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2. J. University of Georgia RCE 2013029 At least four different dimming curve options shall be accessible at the fixture’s User Interface a. Incandescent b. Standard c. Linear d. Quick 3. Dimming curves shall be optimized for smooth dimming over longer timed fades. 4. The LED system shall be digitally driven using high-speed pulse width modulation (PWM) 5. LED control shall be compatible with broadcast equipment in the following ways: a. PWM control of LED levels shall be imperceptible to video cameras and related equipment b. PWM rates shall be adjustable by the user at the fixture if necessary to avoid any visible interference to video cameras and related equipment CONTROL AND USER INTERFACE 1. The fixture shall be USITT DMX 512A-compatible via In and Thru 5-pin XLR connectors 2. The fixture shall be compatible with the ANSI RDM E1.20 standard a. All fixture functions shall accessible via RDM protocol for modification from suitably equipped control console b. Temperature sensors within the luminaire shall be viewable in real time via RDM c. Fixtures not offering RDM compatibility, feature set access or temperature monitoring via RDM shall not be compatible 3. The fixture shall be equipped with multi-line LCD display for easy-to-read status reports and configuration changes 4. The fixture shall be equipped with a six-button user-interface 5. The fixture shall offer multiple DMX input profile options to include: a. RGB - control of all individual LED colors via a threechannel profile 1) Red, Green, Blue b. HSI – control of all individual LED colors via a threechannel profile 1) Hue, Saturation, Intensity c. HSIC – control of all LED colors via a four-channel profile 1) Hue, Saturation, Intensity and Color Point Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 (i) 6. 7. 8. 9. Color point provides variable color temperature settings d. Direct – control of each individual color channel via an independent channel e. A variable-rate strobe channel shall be provided The fixture shall offer three output settings a. Boost mode - powers LEDs at maximum intensity and provides no compensation against LED ‘droop’ or intensity loss b. Regulated mode – slightly restricts maximum LED intensity levels to compensate against LED droop c. Protected mode – further restricts maximum LED intensity levels to compensate against LED droop and offer color consistency at highest permissible ambient temperatures (40C) d. Fixtures that do not provide regulated and protected operation modes are not acceptable The fixture shall offer additional user-definable options to including but not limited to: a. Display time out options b. Loss of data behavior options c. White point settings d. Red-shift option for tungsten dimming emulation The fixture shall offer five Quick Set-Ups to allow user to rapidly select different combinations of the numerous user options based on the desired usage situation, to include: a. General – for most situations b. Stage – when emulating incandescent fixtures is desired c. High Impact – when maximum output and effect is desired d. XT Arch – when color consistency and architectural characteristics are desired. e. Studio - when DMX or stand-alone of white light output is required with intensity, color temperature and color tint control parameters The fixture shall offer stand-alone functionality eliminating the need for a console a. Fixture shall ship with 24 preset colors accessible as a stand-alone feature b. Fixture shall ship with 12 Sequences accessible as a stand-alone feature c. Each color and sequence can be modified by the end user Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual d. e. f. 4.15 University of Georgia RCE 2013029 Fixtures can be linked together with standard DMX cables and controlled from designated master fixture 1) Up to 32 fixtures may be linked Fixtures in a stand-alone state shall restore to the settings present prior to power cycling, eliminating the need for reprogramming Fixtures without stand-alone operation features described in a, b, c, d, and e shall not be acceptable. PLATNUM SPOT 5R PRO A. B. C. General 1. The instrument shall be a Platnum Spot 5R Pro, as marketed by Elation and Acclaim Lighting, or approved equal. Features 1. CMY color mixing 16bit 2. Variable zoom (4 to 1) 3. Energy efficient 4. Supirior optics flat/even light field 5. 3 facet rotating prism 6. Motorized iris 7. 11 degree to 42 degree variable zoom beam angle 8. Variable frost filter (hybrid effect for wash) 9. Motorized focus 10. Featuring Philips MSD Platnum 5R Lamp Technical Specifications 1. DMX Channels: 23/21/34 3 x DMX Channel Modes 2. Control a. 3 pin DMX b. 5 pin DMX 3. Dimmer: Mechanical Dimmer 0-100% 4. Strobe: Variable speed shutter/strobe 5. Iris: Motorized Iris 6. Pan/Tilt: 540/630 x 265 7. Power supply: 120v – 240v 50/60hz 8. Power Consumption: 350w max 9. Lamp: MSD Platnum 5R 2,000 Hr 10. Lux: 6350 Lux / 590 fc @ 16’ All fixtures come complete with safety cable, c-clamp, color frame, grounded stage pin connector & lamp. All stage electric connector strips come with SO cable, kellum grips, cable cradles & gridiron junction box required to complete installation. 5. UNISON DRD SERIES RACK ENCLOSURES Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 5.1 University of Georgia RCE 2013029 RACK ENCLOSURES A. B. The rack enclosure shall be the Unison DRd Series Control Enclosure as manufactured by Electronic Theatre Controls, Inc., or equal. Mechanical 1. The Rack Enclosure shall be a surface mounted, deadfront switchboard, constructed of 18-guage formed steel panels with a hinged, lockable full-height door containing an integral electrostatic air filter. a. Filter shall be removable for easy cleaning. b. The enclosure shall support one control processor and one station power module plus accessories c. The enclosure door shall have an opening to allow limited access to the control module face panel. 2. All rack components shall be properly treated and finished. a. Exterior surfaces shall be finished in fine textured, scratch-resistant, epoxy paint. 3. The fully digital rack enclosure shall be available with six or twelve dimmer module spaces, one processor and a single station power supply, Rack dimensions and weights (without modules) shall not exceed: a. DRd6 21.9” H x 17” W x 9.6” D 38 lb. b. DRd12 31.0" H x 17” W x 9.6” D 51 lb. 4. A single low-noise fan shall be located at the top of each rack. The fan shall draw all intake air through the integral electrostatic air filter, over the surfaces of the module housing and out the top of the rack. a. The fan shall maintain the temperature of all components at proper operating levels with dimmers under full load, provided the ambient temperature of the dimmer room does not exceed 40°C/104°F. b. In the event of an over-temperature condition, only the affected dimmer module(s) shall shut down. A red indicator LED will flash and an error message shall appear on the Control Processor. 5. Rack Enclosures shall be designed to allow easy insertion and removal of dimmer and control modules without the use of tools. (230 volt racks with CE certification shall require a screwdriver.) a. Supports shall be provided for precise alignment of modules into power and signal connector blocks. b. With modules removed, racks shall provide clear front access to all load, neutral and control wire terminations. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 6. 7. 8. 9. University of Georgia RCE 2013029 Rack Enclosures shall support use of any combination of rack option cards designed to provide additional rack features. Rack option cards shall include: a. FLO - The Fluorescent Option Board shall provide termination for 4 wire low voltage electronic fluorescent dimming ballasts. FLO shall provide 24, 0-10Vdc outputs. b. DALI - The DALI Option Board shall provide termination for DALI fluorescent dimming ballasts. DRd shall provide 24, DALI outputs for up to 63 ballasts each in a broadcast mode. Optional floor mounting pedestal shall be available for the 12-module rack. Racks enclosures shall be designed for use with AX series auxiliary racks for Main Circuit Breaker, Main Lug, and cross bussing applications. Accessories a. RideThru Option (RTO) 1) The Rack Enclosure shall support an optional, short-term back-up power source for the control electronics. 2) The short-term back-up power source shall automatically engage upon the loss of normal power, seamlessly transitioning the supply power for the control electronics power to itself. 3) The short-term back-up power supply shall detect the return of normal power, and seamlessly return the control electronics to normal power. 4) The short-term back-up power source shall support the control electronics for at least 10 seconds. b. BatteryPack Option (BPO) 1) The Rack Enclosure shall support an optional, long-term back-up power source for the control electronics. 2) The long-term back-up power source shall automatically engage upon the loss of normal power, seamlessly transitioning the supply power for the control electronics power to itself. 3) The long-term back-up power supply shall detect the return of normal power, and seamlessly return the control electronics to normal power. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4) 5) C. University of Georgia RCE 2013029 A test switch/indicator shall be available without opening the rack door or removal of any modules/components. The long-term back-up power source shall supply power to the control electronics for at least 90 minutes. Electrical 1. Rack enclosures shall be available in 100, 120, 230, 240 and 277 volt, three-phase, main lug configurations. a. 120 volt rack enclosures shall be field configurable for single phase operation without the need for additional components 2. Rack enclosures shall be completely pre-wired by the manufacturer. The contractor shall provide input feed, load, and control wiring. 3. Standard Short Circuit Current Ratings (SCCR) shall be 22,000 at 100-277 Volt a. Higher SCCR ratings, up to 100,000 amps SCCR at 120V, shall be possible when used with an AX series Auxiliary Rack Enclosure. b. Higher SCCR ratings, up to 65,000 amps SCCR at 240V and 277V, shall be possible when used with an AX series Auxiliary Rack Enclosure. 4. All control wire connections shall be terminated via factory provided connectors. 5. Rack enclosures shall support dimming for incandescent, fluorescent, neon, cold cathode, electronic low voltage and magnetic low voltage transformer load types. 6. The rack enclosure shall support 16-bit DMX input 7. The rack enclosure shall support 65,000 steps of dimming. 8. The rack enclosure dimming engine shall support multiple dimmer curves including modified square law, linear, switched, fluorescent, pre-heat and electronic low voltage. 9. The rack enclosure shall support voltage regulation including, minimum and maximum scale voltages with offsets 10. Rack enclosure shall support a UL924 listed contact input for emergency lighting control bypass. a. Emergency lighting input shall support load shedding 11. Rack enclosures shall be designed to support the following wire terminations: a. AC b. Echelon link power (Belden 8471 or equivalent) c. 24Vdc (2- 16AWG Wire) Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 d. D. 5.2 DMX512A Port A (In or Out) (Belden 9729 or equivalent) e. DMX512A Port B (Out) (Belden 9729 or equivalent) f. RS232 Serial In/Out (Belden 9729 or equivalent) g. Unshielded Twisted Pair (UTP) Category 5/5e Ethernet h. Contact Closure In (14AWG to 26AWG Wire) i. Contact Closure Out (14AWG to 26AWG Wire) 1) Contact Closure Out shall provide 1A @ 30vDC 12. Station Power Modules a. Station power modules shall provide LinkPower for up to 32 stations and 1.5A@24VDC of Auxiliary (AUX) power. b. Station power repeater modules shall provide LinkPower for 30 stations and1.5A@24VDC of Auxiliary (AUX) power. c. Station power module shall support over-current/short protection for LinkPower and Auxiliary (AUX) power. LinkPower shall support fault detection on each leg of the balanced data bus. 13. All control wire connections shall be terminated via factory provided connectors. 14. Main feed lugs shall accept a maximum of 350 MCM wire. 15. Load terminals shall accept a maximum of #6 AWG wire. Thermal 1. Ambient room temperature: 0-40°C / 32-104°F AMBIENT HUMIDITY: 10-90% NON-CONDENSINGCONTROL PROCESSOR MODULES A. B. C. D. E. The Architectural Control Processor shall be the Unison Paradigm P-ACP Series Control Processor as manufactured by Electronic Theatre Controls, Inc., or equal. The Architectural Control Processor (ACP) assembly shall be designed for use in DRd Series Dimming Enclosures and ERn Series Control Enclosures. The processor shall utilize microprocessor based, solid state technology to provide multi-scene lighting and building control. ACP shall support functions such as station programming, macro sequencing, electronic lockout, room combine and astronomical time clock events. ACP station processor shall allow configuration of the control system via the menus. See software section for additional system details. When used in a dimming enclosure, the ACP shall allow access to dimming control menus including the status screen, dimming Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual F. G. H. I. J. K. 5.3 University of Georgia RCE 2013029 configuration screen, backup menu, test menu and configuration menu. One ACP shall be rated to drive 1024 channels of control, 1024 zones, 64 rooms, 512 presets, 62 button or button/fader stations and 6 Touchscreen Stations ACP module electronics shall be convection cooled. The ACP shall provide front-panel RJ45 jack, Secure Digital (SD) card slot, and Universal Serial Bus (USB) Port for configuration and data exchange. Architectural Lighting System configuration and program information shall be stored in flash memory, which does not require battery backup. The ACP shall be contained in a plug-in assembly and require no discrete wiring connections; all wiring shall be terminated into Dimming or Control Enclosure. The ACP shall support the following communications: 1. Echelon LinkPower 2. 10/100BaseTX, auto MDI/MDIX, 802.3af compliant Ethernet networking with TCP/IP, ESTA BSR E1.17 Advanced Control Networks (ACN) and ESTA BSR E1.31 (sACN) Protocols 3. EIA-232 serial protocol 4. ESTA DMX512A, configurable as input or output ports 5. Dry contact closure inputs 6. Dry contact closure outputs, rated at 1A@30VDC STATIONS A. B. C. D. E. F. The Lighting Control Stations shall be the Unison Heritage UH Series Control Stations as manufactured by Electronic Theatre Controls, Inc., or equal. Mechanical Unison Heritage Button and Button/Fader Stations shall operate using up to sixteen programmable faders and twelve programmable buttons. All button/fader stations shall be available with white, cream, ivory, gray or black faceplates, fader knobs, and buttons. 1. Manufacturer's standard colors shall conform to the RAL CLASSIC Standard. Stations shall have indicators lights at each button or fader. 1. Indicators shall be comprised of red, green and blue LED's 2. Indicator color and state (steady On, Blink, Off) shall be configured in software, and shall operate relative to the button or fader it is associated with. All faceplates shall be designed for flush or surface mounting. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual G. H. I. J. K. L. M. N. O. 5.4 University of Georgia RCE 2013029 Station faceplates shall be constructed of ABS plastic and shall use no visible means of attachment. Station faceplates shall be indelibly marked for each button or fader function. The manufacturer shall supply back boxes for flush mounted half gang stations and for all surface mounted stations. Functional The Unison Paradigm Control System shall be designed to allow control of lighting and associated systems via Button, Button/Fader, and Interface or Astronomical time clock controls. System shall allow the programming of presets, sequences, macros and time clock events. Station Button, Button/Fader, and Interface) control components shall be designed to operate standard default or custom system functions. Components shall operate default functions unless reassigned via LightDesigner, the Windows-based configuration program. Stations (Button and Button/Fader) shall allow programming of station and component electronic lockout levels via LightDesigner. Electrical Unison control station wiring shall be an Echelon® Link power network. 1. Link power shall utilize low-voltage Class II unshielded twisted pair, type Belden 8471 or equivalent, and one #14 ESD drain wire (when not installed in grounded metal conduit). 2. Touchscreen and Interface stations shall also require (2) #16 AWG stranded wires for 24Vdc operating power. 24Vdc wiring shall be topology free. 3. Network wiring may be bus, loop, home run, star or any combination of these. 4. Network insulation displacement connectors shall be provided with all stations. TOUCHSCREEN CONTROL STATION A. B. C. D. The Touchscreen Control Stations shall be the Unison Paradigm Touchscreen P-LCD Series Control Stations as manufactured by Electronic Theatre Controls, Inc., or equal. General Touchscreen stations shall support default and fully graphical control pages. The Touchscreen station shall operate using graphic buttons, faders and other images on at least 30 separate programmable control pages. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual E. F. G. University of Georgia RCE 2013029 Touchscreen stations shall also allow programming of page passcode, lock out and visibility levels. Mechanical 1. Touchscreen stations shall consist of a seven inch, backlit liquid crystal display (LCD) with a minimum resolution of 800 by 400 pixels and 12-bit color depth with a touch interface. 2. Touchscreen bezels shall be constructed of aluminum and shall have no visible means of attachment. a. The bezel shall install and remove without the use of tools. b. The bezel shall provide two working positions for the Touchscreen: service and operating. 3. The Touchscreen shall have a protective overlay over the display. a. The overlay shall reduce wear b. The overlay shall reduce glare 4. The manufacturer shall provide backboxes for all LCD stations. a. Flush back box dimensions shall be 7.94” wide x 5.33” high x 3.25” deep b. Surface back box dimensions shall be 8.3” wide x 5.6” high x 2.55” deep Electrical 1. Touchscreens shall be powered entirely by the System network. 2. Touchscreens shall connect to the System using an Ethernet network with Power over Ethernet (PoE) or the Unison control station Echelon® Link power network. a. Ethernet Network 1) Ethernet network shall be 10/100BaseTX, auto MDI/MDIX, 802.3af compliant. 2) Network shall utilize Unshielded Twisted Pair (UTP) Category 5 wiring. b. Echelon® Link power network. 1) Link power shall utilize low-voltage Class II unshielded twisted pair, type Belden 8471 or equivalent, and one #14 ESD drain wire (when not installed in grounded metal conduit). 2) Touchscreen stations shall also require (2) #16 AWG stranded wires for 24Vdc operating power. 24Vdc wiring shall be topology free. 3) Network wiring may be bus, loop, home run, star or any combination of these. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4) H. I. University of Georgia RCE 2013029 Network insulation displacement connectors shall be provided with all stations. Functional 1. System a. The Touchscreen shall support configuration firmware upload from a Paradigm Processor as proxy b. The Touchscreen shall support configuration or firmware upload from local removable media 2. Setup Mode a. There shall be a setup display that is separate from any user-defined configuration b. It shall be possible to view and modify connectivity settings c. It shall be possible to view status information d. It shall be possible to view and modify LCD screen settings e. It shall be possible to perform Touchscreen calibration f. It shall be possible to view and modify audio settings g. The appearance of the setup display shall be standard and not editable h. The setup display may be invoked from within the user-defined configuration and/or physical button on the Touchscreen i. There shall be a default protected method to invoke the setup display 3. Configurations a. It shall be possible to have multiple configurations stored within an LCD Station b. Only one configuration may be active on the LCD Station c. It shall be possible for Touchscreen Stations connected via the Echelon® Link power network to select a configuration automatically based on the configuration of the physical connection. d. Where multiple configurations are stored there shall be a boot menu to allow selection of a configuration e. Each configuration shall be identified as a different Station within the System Operation 1. The Unison Paradigm Control System shall be designed to allow control of lighting and associated systems via Touchscreen controls. System shall allow the control of presets, sequences, macros and time clock events. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual a. b. c. d. University of Georgia RCE 2013029 System presets shall be programmable via Button, Button/Fader, Touchscreen, or LightDesigner software. 1) Presets shall have a discrete fade time, programmable from zero to 84,600 seconds with a resolution of one hundred milliseconds. 2) Presets shall be selectable via Touchscreen stations. System macros and sequences shall be programmable via LightDesigner system software. 1) Macro and sequence steps shall provide user selectable steps, and allow the application of conditional logic. 2) Macro and sequences shall be activated by button, time clock event or LightDesigner software. System time clock events shall be programmable via the Touchscreen, LightDesigner system software, the processor user interface, or the internal web server. 1) Time clock events shall be assigned to system day types. Standard day types include: anyway, weekday, weekend, Sunday, Monday, Tuesday, Wednesday, Thursday, Friday and Saturday. System shall support programming of additional custom or special day types. 2) Time clock events shall be activated based on sunrise, sunset, time of day or periodic event. System shall automatically compensate for regions using a fully configurable daylight saving time. Touchscreen stations shall be designed to operate standard default or custom system functions. Components shall operate default functions unless reassigned via LightDesigner, the Windows-based configuration program. 1) Optional button functions include: preset selection, manual mode activation, record mode activation, station lockout, raise, lower, macro activation, and cue light, or room join/separate. 2) Optional fader functions include master control, individual channel control, fade rate control or preset master control. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual e. f. g. 5.5 University of Georgia RCE 2013029 Touchscreen stations shall allow programming of station and component electronic lockout levels via LightDesigner. It shall be possible to adjust LCD contrast and brightness. It shall be possible to program the station to dim during periods of inactivity. BUTTON STATIONS A. B. C. The Lighting Control Stations shall be the Unison Heritage UH Series Control Stations as manufactured by Electronic Theatre Controls, Inc., or equal. Mechanical 1. Unison Heritage Button and Button/Fader Stations shall operate using up to sixteen programmable faders and twelve programmable buttons. 2. All button/fader stations shall be available with white, cream, ivory, gray or black faceplates, fader knobs, and buttons. a. Manufacturer's standard colors shall conform to the RAL CLASSIC Standard. 3. Stations shall have indicators lights at each button or fader. a. Indicators shall be comprised of red, green and blue LED's b. Indicator color and state (steady On, Blink, Off) shall be configured in software, and shall operate relative to the button or fader it is associated with. 4. All faceplates shall be designed for flush or surface mounting. 5. Station faceplates shall be constructed of ABS plastic and shall use no visible means of attachment. 6. Station faceplates shall be indelibly marked for each button or fader function. 7. The manufacturer shall supply back boxes for flush mounted half gang stations and for all surface mounted stations. Functional 1. The Unison Paradigm Control System shall be designed to allow control of lighting and associated systems via Button, Button/Fader, and Interface or Astronomical time clock controls. System shall allow the programming of presets, sequences, macros and time clock events. 2. Station Button, Button/Fader, and Interface) control components shall be designed to operate standard default or custom system functions. Components shall operate default functions unless re-assigned via LightDesigner, the Windows-based configuration program. Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 3. D. 6. Stations (Button and Button/Fader) shall allow programming of station and component electronic lockout levels via LightDesigner. Electrical 1. Unison control station wiring shall be an Echelon® Link power network. a. Link power shall utilize low-voltage Class II unshielded twisted pair, type Belden 8471 or equivalent, and one #14 ESD drain wire (when not installed in grounded metal conduit). b. Touchscreen and Interface stations shall also require (2) #16 AWG stranded wires for 24Vdc operating power. 24Vdc wiring shall be topology free. c. Network wiring may be bus, loop, home run, star or any combination of these. d. Network insulation displacement connectors shall be provided with all stations. INSTALLATION 6.1 GENERAL A. B. C. 6.2 Verify that job conditions are ready to receive work of this section. Notify Architect of any existing condition, which will adversely affect execution. Beginning of execution will constitute acceptance of existing conditions. Verify that field measurements are as shown on shop drawings. Verify that mechanical, electrical, and other items affecting work of this section are in place and ready to receive the work. INSTALLATION A. B. C. Install using skilled workmen in accordance with manufacturer's printed instructions and recommendations. Install work in accordance highest industry standards. Handle materials to avoid dents and other damages. Set and secure materials and components rigid, plumb, and square. END OF SECTION 16760 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 SECTION 27 4000 AUDIO VISUAL SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The work required under this section of the specifications consists of the furnishing, installation, and programming of independent audio systems for the Talmadge Hall Auditorium at Rock Eagle 4H Center in Eatonton, Georgia. Reference floor plan drawings for all equipment locations. In addition to all audio visual components, the contractor shall be required to provide coordination with the electrical contractors for all raceway to support these technical systems. B. The audio visual scope of work will require the contractor to provide a complete, quality operating system. A factory-approved representative shall complete all system connections. A factory approved and factory trained representative of the contractor shall complete all onsite programming of equipment. C. The contractor shall provide all labor, materials, equipment, and supervision to install specified systems. The installation, testing, and commissioning of all equipment shall be the full responsibility of the audio visual contractor for this project. 1.2 QUALITY CRITERIA AND STANDARDS A. All audio visual wiring, devices, and equipment shall comply with applicable UL, NEC, and NEMA code standards. All audio visual equipment shall be UL-listed and labeled. B. Audio visual wiring systems shall conform to established trade and industry standards. The following specifications and standards are incorporated into and become a part of this Specification by reference. 1. 2. 3. 4. 5. C. AES14-1992 (r2004): – AES Standard for Professional Audio Equipment. AES26-2001– AES Recommended Practice for Professional Audio ICEA S-80-576 ICEA Standard for Communications Wire and Cable for Wiring of Premises NFPA 70 National Electric Code UL 50 Enclosures for Electrical Equipment Installer's Qualifications: 1. 2. Firm with at least 3 years of successful application, installation, and testing experience on specified systems and equipment. The Contractor must show proof of being in the audio visual trade for a minimum of three years and provide three (3) references with contact 16050-1 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 3. 4. 1.3 University of Georgia RCE 2013029 names and telephone numbers regarding successful completion of audio visual projects of similar scope and size. All supervisors and installers assigned to the installation of this system or any of its components shall have factory certification from each equipment manufacturer that they are qualified to install and test the provided products. Unqualified staff shall not be used for the installation of the equipment, system cables, and associated hardware. All installers assigned to the installation of this system or any of its components shall have a minimum of 3 years experience in the installation of the specified audio visual equipment and components. SUBMITTALS A. Product Data: Audio Visual contractor shall provide a numbered equipment list of the systems devices he is providing. The list shall include quantity of items, manufactures product number, description of item and audio visual specification that it represents. Submit manufacturer's technical product technical data sheet for each item of systems equipment in order of the numbered equipment list. Submittal shall include drawings that contain complete floor plans and reflected ceiling plans, wiring and schematic diagrams and other details required that demonstrate that the system has been coordinated and will function as a complete system. Drawings shall include vertical riser diagrams, equipment rack details, elevation drawings, connector faceplate details, sizes, and type of all cables and raceway. B. Test Plan: Contractor shall submit a test plan that defines the tests required to ensure that the system meets technical, operational, and performance specifications, 15 days prior to the proposed test date. The test plan must be approved before the start of any testing. The test plan shall identify the capabilities and functions to be tested, and include detailed instructions for the setup and execution of each test and procedures for evaluation and documentation of the results. C. Manufacturer Certification: Submit a letter from the manufacturer's representative stating the proposed systems being submitted for review are in accordance with the recommendations of the manufacturer. 1.4 A. 1.5 WARRANTY All equipment shall be new and shall be under warranty for a period of one (1) year, from the date of acceptance by the owner, against defects in equipment or workmanship. Failed equipment shall be replaced by the contractor at no cost to the owner. Owner's personnel may perform initial trouble investigation but replacement of failed equipment and escalated problem support will be handled by the contractor. ACCEPTABLE MANUFACTURERS 16050-2 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual A. 1.6 University of Georgia RCE 2013029 Reference Part 2 - Products Section of the specification for complete list of acceptable manufacturers. RECORD DRAWINGS A. At the time of final inspection, provide three (3) sets of complete data on Audio visual System equipment used in this project. This data shall be in bound form and shall include all shop drawings required for this project. B. All record drawings shall include "as built" system interconnection diagrams with major components identified and number and type of interconnecting conductors. C. Maintenance and operating instructions on all systems. D. Certification from system manufacturers that systems are installed in accordance with manufacturer's recommendations and are functioning correctly at the time of final inspection. E. As-built drawings to show raceway layout and wiring for all systems. F. Corrected point-to-point drawings for all systems with color code to show the actual as-built condition. PART 2 - PRODUCTS 2.1 A. 2.2 A. GENERAL MATERIALS REQUIREMENTS Provide all materials under this section of the specifications. Materials and equipment shall be the manufacturers’ latest standard design that has been in satisfactory use for at least 1 year prior to installation. See Part 3 - Execution specification section for additional product requirements. AUDIO MIXING CONSOLE Audio Mixing Console shall be of the digital type with remote stagebox Input and Output capabilities. Available system components shall include (but not be limited to) equalizers, filters, dynamics/gain controls, routers, delays, remote controls, meters, generators, and diagnostics. Channels shall gate silently for system response and clarity. Ethernet communications shall be utilized for software control and configuration. Audio mixer shall meet the following specifications: 1. 2. 3. Inputs: minimum 48, electronically balanced, on XLR plugs (via remote stage boxes or console surface. Preamps shall have -60 to +15 dbu sensitivity. Console controls shall be available via surface control, tablet PC/iPad and 16050-3 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 4. 5. 6. 7. 8. 9. B. 2.3 A. WIRELESS MICROPHONES Wireless microphones shall be of single rack unit multi-channel design. Signal transmission shall be digital to maximize the availability of RF channels for future expansion and digital system management and audio output shall be available via category 5e cabling. Antenna combining shall be built in to the systems without the need for expansion hardware. Wireless microphones shall meet the following specifications. 9. 10. 11. 12. 13. 2.4 A. digital computer interface through Ethernet connectivity. iPad control app is required. Input/Output expansion available via expansion card slot supporting Dante™ digital audio protocol. Dante™ Expansion card shall be provided. Minimum of 20 mixable output busses shall be available on a minimum of 24 outputs. Digital audio output shall be available via 2 channel AES-3 connection on XLR connector and via digital expansion card slot. Personal Monitor Mix connectivity through category 5e network cable shall be available via built-in connection or add-on option card. Acceptable: Allen & Heath GLD-80 (AR-2412 and AR-84 Stage Racks), or comparable by Midas, Roland, Soundcraft, Avid, Digico, or Yamaha. 1. 2. 3. 4. 5. 6. 7. 8. B. University of Georgia RCE 2013029 Four receivers in 1RU metal chassis with internal power supply Individual gain controls, LED meters, and XLR outputs for each channel 64 MHz tuning range (region dependent) Digital predictive switching diversity RF cascade ports to allow distribution of RF signal to another unit AES 256-bit encryption-enabled for secure transmission Dante™ digital networked audio over Ethernet Ethernet networking for frequency coordination and deployment across multiple receivers Up to 60 dB independently adjustable gain for each channel Audio and RF LED meters with peak indicator Switchable mic/line output level Provide two directional wideband, passive, paddle antennas (i.e. Shure PA805). Provide Minimum of 8 channels with 8 handheld dynamic transmitters and 8 body-pack transmitters with omni-directional lavaliere mics. Acceptable: Shure ULXD4Q receiver/ Shure ULXD-1 Body-Pack/ Shure ULXD2 Handheld Transmitters/ Shure PA805 antennas, or comparable by Sennheiser, Audio-technica, Lectrosonics, or AKG. EARSET MICROPHONE Earset Microphone shall be an extremely low profile head-worn microphone designed to provide maximum gain before feedback in general speech 16050-4 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 applications. Earset Microphone shall contain a condenser element that is held close to the mouth by a thin boom. Coordinate finish color with owner. Earset microphone shall meet the following specifications: 1. 2. 3. 4. 5. B. 2.5 A. Acceptable: Countryman E6 Omni or comparable from Sennheiser or DPA. STEREO DI Stereo Direct Injection Box with Unbalanced input and dual balanced output. Stereo or summed mono operation selectable by user. Built in ground lift switches to eliminate hum and a -20db pad. Outputs shall be left and right XLR males. Stereo DI boxes shall meet the following specifications. 1. 2. 3. B. 2.6 A. PERSONAL MIXERS (Add-Alternate) Personal Mixing units shall be provided for purposes of mixing individual monitor systems. These units shall connect via category 5e cabling and have the ability to independently create monitor mixes of a minimum of 16 channels for on-stage talent. 6. 2.7 A. 2 Male, Panel-mount XLR Connectors. 1 1/8” stereo TRS connector on 3ft tail. 2 DBT Passive Balancing Transformers Acceptable: RapcoHorizon LTI-1, or comparable by ProCo, Whirlwind, Countryman, or Radial. 1. 2. 3. 4. 5. B. Detachable cable with connector to match supplied wireless microphone transmitters. Frequency Response: 20 Hz to 20,000 Hz. Element Diameter: 0.1” Weight: .07 oz (2 grams). Provide quantity of three. Category 5 digital audio input connectivity. Minimum 16 mixable channels. Stereo Headphone Output. Direct connection to console via digital audio connection. Provide one set of Shure SE315 earphones and earphone cables with each mixer. Provide an additional two sets total of Shure SE425 earphones for use with low frequency instrument mixes. Acceptable: Allen & Heath ME-1 or comparable by My-Mix, Aviom, or Roland DIGITAL AUDIO SIGNAL PROCESSOR Audio DSP shall be rack mounted. All internal processing shall be digital 16050-5 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 (DSP). Software shall be provided for creating/connecting DSP system components within each hardware unit. Available system components shall include (but not be limited to) various forms of: mixers (including automatic), equalizers, filters, crossovers, dynamics/gain controls, routers, delays, remote controls, meters, generators, and diagnostics. Channels shall gate silently for system response and clarity. Ethernet communications shall be utilized for software control and configuration. Audio DSP shall meet the following specifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. B. 2.8 Inputs: minimum 8, electronically balanced, on plug-in barrier-strip connectors. Expandable Digital audio input and output capability Via AVB or Dante™ digital audio networking protocols. Digital Audio Connectivity shall support most current Dante™ Protocols. Maximum input level: +24dBu Equivalent Input Noise (EIN): Less than -125dBu with 150 Ohms source. Outputs: Eight, electronically balanced, on plug-in barrier-strip connectors. Maximum output level: +24dBu Digital Resolution/ Sample Rate: 24 bit, 48 kHz Frequency Response: 20 Hz to 20 KHz (+0/-.4 dB) Total Harmonic Distortion: Less than 0.04% (20Hz to 20 KHz, +4dBu output, mic level input) Dynamic Range: 107dB typical (20 Hz to 20 KHz). Connections shall allow sharing of digital audio within multi-unit systems. Software shall operate on a computer running Windows 8 or OSx After initial programming, systems may be controlled using TCP/IP, USB, or RS-232 serial communication by third party control systems (such as AMX), by PC computer, and/or by dedicated control devices. UL listed and shall follow AES48-2005 Grounding and EMC practices. Acceptable: Symetrix Edge or Radius DSPs or comparable by BSS or Biamp. MULTI-CHANNEL AUDIO AMPLIFIERS A. Amplifiers shall be rack mounted. Amplifiers shall be designed for use in a commercial sound re-enforcement application. Amplifiers shall contain circuit breaker for overload protection; high temperature automatic reset protection, and electronic output protection. Amplifier controls shall have on/off switch and pilot light, master gain control, signal input/output and input channel controls. Amplifiers shall not be loaded over 70% of the power output rating and shall be capable of power output ratings equivalent to or greater than the peak draw level of the associated speakers. B. Amplifier shall meet the following specifications: 1. Mounting: Rack mounted. 2. Outputs: Both low impedance (4/8 ohms) and constant voltage (70/100V). 3. Frequency Response: Within plus or minus 1 dB from 20 to 20,000 Hz. 4. Minimum Signal-to-Noise Ratio: 100 dB, at rated output. 16050-6 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 5. 6. 7. 8. 9. C. 2.9 University of Georgia RCE 2013029 Total Harmonic Distortion: Less than .3 percent at rated power output from 20 to 20,000 Hz. Power Draw at Idle: Less than 80 watts. Controls/Indicators: On/off, input levels, selection of bridge mode for each pair of channels, high pass filter. Power on, signal presence, and clipping indicators. Protection: Built-in circuits monitor both current and temperature. Cooling: Fan cooled. Acceptable: Lab Gruppen C series or comparable from Electrovoice or QSC. MAIN CLUSTER LOUDSPEAKERS A. Main cluster loudspeakers shall be mounted and arrayed as indicated in contract documents to provide optimum coverage of mid and far seating areas. Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be installed in full compliance with rigging methods approved by a structural engineer. Rigging shall include capability for independent horizontal and vertical angle adjustment. B. Main Loudspeaker specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. C. 2.10 A. Frequency Response: 40-18,000 Hz. Sensitivity: LF-101 dB, MF-104 dB, HF- 109 dB (1W/1m). Power Capacity, watts: LF-1000; MF/HF-300 (RMS). Max. Peak SPL: LF- 137 dB, MF- 135 dB, HF- 134 dB. Crossover Frequencies: 350, 1500 Hz. Nominal Impedance: LF- 4 ohms, MF/HF- 4 ohms. Coverage Pattern: 90 degrees by 40 degrees. Low Frequency Transducer: dual 12” with 4” voice coil. Mid Frequency Transducer: horn-loaded 10” High Frequency Transducer: 2.0" exit compression driver. Enclosure Type: Multi-ply hardwood, perforated metal grille. Enclosure Dimensions: 40.0"H x 24.0"W x 32.25"D. Enclosure Construction: Multi-ply hardwood, perforated metal grille, 12 attachment points, black finish. Weight: 206 lbs. Acceptable: Renkus-Heinz STX7/94. Required pricing alternate: Electrovoice EVF-1152D/96-BK. DELAY LOUDSPEAKERS Delay loudspeakers shall be mounted and arrayed as indicated in contract documents to provide optimum coverage of rear seating areas. Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be installed in full compliance with rigging methods approved by a structural engineer. Rigging shall include capability for independent horizontal and vertical angle adjustment. 16050-7 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual B. Delay Loudspeaker specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. C. 2.11 University of Georgia RCE 2013029 Frequency Response: 40-18,000 Hz. Sensitivity: LF-101 dB, MF-101 dB, HF- 109 dB (1W/1m). Power Capacity, watts: LF-800; MF/HF-150 (RMS). Max. Peak SPL: LF- 136 dB, MF- 130 dB, HF- 131 dB. Crossover Frequencies: 500, 1500 Hz. Nominal Impedance: LF- 4 ohms, MF/HF- 8 ohms. Coverage Pattern: 60 degrees by 40 degrees. Low Frequency Transducer: dual 12” with 3” voice coil. Mid Frequency Transducer: horn-loaded 8” High Frequency Transducer: 1.0" exit compression driver. Enclosure Type: Multi-ply hardwood, perforated metal grille. Enclosure Dimensions: 40.0"H x 24.0"W x 32.25"D. Enclosure Construction: Multi-ply hardwood, perforated metal grille, 12 attachment points, black finish. Weight: 186 lbs. Acceptable: Renkus-Heinz STX6/64. Required pricing alternate: Electrovoice EVF-1122D2/96-BK. DOWNFILL/CENTERFILL LOUDSPEAKERS A. Down Fill/ Center Fill loudspeakers shall be mounted and arrayed as indicated in contract documents to provide optimum coverage of near seating areas. Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be installed in full compliance with rigging methods approved by a structural engineer. Rigging shall include capability for independent horizontal and vertical angle adjustment. B. Down Fill/ Center Fill Loudspeaker specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. C. Frequency Response: 55-18,000 Hz. Sensitivity: 98 dB (1W/1m). Power Capacity, watts: LF- 600, HF- 150 (RMS). Nominal Impedance: LF- 4 ohms, HF- 8 ohms. Coverage Pattern: 120 degrees by 60 degrees, rotatable waveguide. Low Frequency Transducer: one 12” cone. High Frequency Transducer: 2.0" exit compression driver. Enclosure Type: Stage monitor shape, optimally vented. Enclosure Dimensions: 23.0" H x 14.25" W x 12.25" D. Enclosure Construction: Multi-ply hardwood, twelve universal M10 attachment points or u-bracket attachment points. Finish: Black with perforated metal grille. Weight: 67 lbs. Acceptable: Renkus-Heinz PNX121M Required pricing alternate: Electrovoice EVU-1082/95 (EVF-1122D2/96-BK for Center Fill position). 16050-8 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.12 University of Georgia RCE 2013029 SUBBASS LOUDSPEAKERS A. Subbass loudspeakers shall be portable and shall be ground supported in front of stage. Subs to provide low frequency extension of program audio. Provide quantity as indicated in plans. B. Subbass Loudspeaker specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. C. 2.13 Frequency Response: 45-200 Hz. Sensitivity: 100 dB (1W/1m). Power Capacity, watts: 2400 Program. Nominal Impedance: 4 ohms. Transducers: dual 18”. Enclosure Type: Vented. Enclosure Dimensions: 48.0"W x 22.5"H x 23.875"D. Enclosure Construction:0.75” birch plywood. Required Options: Speakon connectors. Finish: Black with black powder-coated perforated steel grille. Weight: 180 lbs. Acceptable: OAP TR218 or comparable from Electrovoice or Renkus-Heinz SURROUND SOUND LOUDSPEAKERS A. Surround sound loudspeakers shall be mounted on theater side and rear walls as indicated in contract documents to provide playback of surround sound channels in cinema applications. Audiovisual contractor to provide all rigging hardware. Loudspeakers shall be installed in full compliance with rigging methods approved by a structural engineer. Rigging shall include capability for vertical angle adjustment. B. Surround Sound Loudspeaker specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. C. Frequency Response: 80-20,000 Hz. Sensitivity: 94 dB (1W/1m). Power Capacity: 100 watts (RMS). Nominal Impedance: 8 ohms. Coverage Pattern: 120 degrees by 60 degrees, rotatable waveguide. Low Frequency Transducer: one 8” cone, 2” voice coil. High Frequency Transducer: 1.0" exit compression driver. Enclosure Type: Stage monitor shape, optimally vented. Enclosure Dimensions: 19.75" H x 9.75" W x 9.0" D. Enclosure Construction: Multi-ply hardwood, twelve universal attachment points or u-bracket attachment points. Finish: Black with perforated metal grille. Weight: 25 lbs. Acceptable: Renkus-Heinz TRX81 Required pricing alternate: Electrovoice EVU-1082/95. 16050-9 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.14 A. STAGE MONITOR LOUDSPEAKERS Monitor speakers shall be used for user defined needs as on-stage sound reinforcement for musicians and other talent. They will be powered by remote amplification using 12AWG speaker cable terminated with Neutrik NL4 connectors. Stage monitors shall meet the following specifications. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. B. 2.15 A. University of Georgia RCE 2013029 8” High-Output LF Transducer 1” Exit True Compression Driver 90° x 50° Coverage Pattern Rotatable Horn Design Integral Monitor Angle on Enclosure 200W Cont., 800W Peak Power Handling High Sensitivity, 123 dB Maximum SPL Built-In Pole Mount Integral Handle Pocket for Easy Carrying Provide one 15’ portable monitor cable with each unit. Acceptable: Electrovoice ZX1-90 or comparable by Tannoy, JBL, or RenkusHeinz. SURROUND SOUND DECODER Surround Sound Decode for Dolby and DTS should provide audio signal decoding and distribution for surround sound speaker systems. It should be capable of both 6.1 and 7.1 decode. Surround Sound Decoders should meet the following specifications. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Supports Dolby® and DTS® source formats and listening modes as well as PCM and analog audio — Dolby Digital, Dolby Digital EX, Dolby Pro Logic, Dolby Pro Logic II, Dolby Pro Logic IIx, DTS Digital Surround, DTSES® Discrete 6.1, DTS-ES Matrix 6.1, DTS 2-Channel, DTS 96/24®, DTS 96/24 ES Matrix, DTS Neo:6®, Uncompressed PCM, Analog stereo or mono Inputs: Four S/PDIF digital inputs on two optical connectors and two coaxial RCA connectors; one balanced or unbalanced stereo analog input on a 5-pole captive screw connector. Outputs: Three balanced or unbalanced stereo line level outputs on 6pole captive screw connectors for Front, Surround, and Back; two balanced or unbalanced mono line level outputs on 3-pole captive screw connectors for Center and Subwoofer. Automatic surround sound format detection and decoding. Seven channel, nine-band parametric EQ. Up to 100 ms lip sync adjustment on each input. Test signals for setup and calibration. Distance compensation adjustment for each speaker. Rack-mountable enclosure Front panel security lockout. 16050-10 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 11. 12. B. 2.16 University of Georgia RCE 2013029 RS-232 control port. Internal universal power supply. Acceptable: Extron SSP-7.1 or comparable by D&M Professional, Lexicon, or Crestron. NETWORK ROUTER A. The Network Router shall be rack mounted as provided in the contract documents and interfaced to the owner provided network. B. The Network Router shall meet the following specifications: 1. C. 2.6 Network switch minimum configuration shall be 24 x RJ45 10/100/1000 ports (IEEE 802.3 10Base-T, IEEE 802.3u 100Base-T, IEEE 802.3ab 1000Base-T gigabit Ethernet) Acceptable manufacturers shall be Netgear, Dell, Cisco, HP, or D-Link. LECTERN A. The Lectern shall provide a work service for presentations and shall be designed to contain electronic equipment and the system control panel. The interior shall have adjustable interior shelves, interior rack rails, and louvers for venting. Doors shall be security doors and a service access door with locks. The lectern shall have 4” heavy-duty lockable casters. Cabling between lectern and lectern interface wall box shall have a 3” floor grommet for power and audio visual cables. These audio visual cables shall be strain-relieved and encased in expandable sleeve material for the run to the floor box. Lighting shall be a Littelite as provided by manufacturer. Coordinate finish with architect in order to match wood wall trim finish. B. Lectern specifications of equipment shall include: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. Quantity=1. Size approximately 40”w x 28”d x 45”h Laminate finish Flat work surface Cut Out for cable connection box Security doors with lock Document camera pullout Tower pc compartment Adjustable shelf in pc compartment Service access doors with lock 14RU rack rails, single bay Casters Little Lite Grommets as required DC Ventilation fan 16050-11 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual C. Acceptable Manufacturers: 1. 2.17 University of Georgia RCE 2013029 In-View Furniture or comparable unit from Miller’s Millwork. FURNITURE-MOUNTABLE CABLE ENCLOSURE A. Furniture-Mountable Cable Enclosure shall be installed in lectern and shall provide capacity for interface with future video system. Provide with multiple cable grommets for audio and video cables to be installed at a future time. Contractor shall provide for mounting in Lectern. B. Furniture-Mountable Cable Enclosure shall meet the following specifications: 1. General a. Mounting: Furniture mount: With included hardware. b. Accessory Plates: various audio, video, control, and power receptacle connector plates are available. c. Dimensions: 7.0”x7.0” (top plate), 6.4” x 6.4” x 4.75” HxWxD (box). d. Min./max. Table thickness: 0.375" to 2.00". e. Enclosure type: Metal C. Acceptable: Extron Cable Cubby 600 or comparable from FSR. 2.18 GOOSE-NECK MICROPHONE A. Gooseneck microphone shall be mounted on lectern. It shall have shock mounted base with internal on/off switch. The microphone shall be for use in a commercial sound re-enforcement application. B. Goose Neck microphone shall meet the following specifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. C. Frequency Range: 30–18,000 Hz. Polar Pattern: Hypercardioid. Sensitivity at 1,000 Hz: 8.5 mV/ Pa. Equivalent Noise Level: 21 dB-A. Sound Pressure Level for 1% THD: 133 dB. S/N Ratio (A-weighted): 73 dB. Power Requirement: 9-52 volts. Connector: 3-pin XLR type. Finish: Dark gray matte. Size: Diameter 0.35 in. length 5.4 in. Included Accessories: Mount/adapter, Long gooseneck. Lectern microphone shall be of the same manufacture and model and shall have shock mount base unit that mounts into the lectern. Acceptable manufacturers include: 1. AKG. 2. Sennheiser. 3. Shure. 16050-12 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 2.19 University of Georgia RCE 2013029 HAND-HELD MICROPHONE/DIRECT BOX PACKAGE A. Hand-Held Microphone/ Direct Box Package shall be provided for use in supporting a variety of stage events and shall consist of a combination of suspended choir microphones, loose microphones, and stage boxes. Contractor to provide a 25’ XLR microphone cable with each loose microphone. Confirm final microphone and direct box models and finishes with owner. B. Acceptable: Provide the following microphones and direct boxes with no substitutions. 2.20 1. Shure MX202 B/C choir mic, quantity=8. 2. Shure DMK57-52 drum mic kit, quantity=1. 3. Shure SM57-LC general purpose mic, quantity=3. 4. Shure SM58-LC dynamic vocal mic, quantity=5. 5. Shure Beta 87A condenser vocal mic, quantity=2. 6. Shure SM-81-LC condenser overhead/piano mic, quantity=4. 7. Sennheiser e609 general purpose mic, quantity=2. 8. Rapco-Horizon DB-1 direct box, quantity=5. MICROPHONE STANDS A. Microphone stands shall be shall be provided for use with systems microphones and shall be for use in a commercial sound re-enforcement reinforcement application. B. Systems microphone stands include: 2.21 A. 1. Floor Base Stand with weighted base. a. 24” to 60” Telescoping stand b. Finish Black c. Base - 12" Diameter weighted or tripod type. d. 17” to 28” Telescoping boom arm (Finish Black) e. Provide Minimum quantity of 10 2. Acceptable manufacturers include: a. König & Meyer - 201/2 – Black with 21140 Boom Arm b. Ultimate c. On-Stage AMPLIFIER RACKS Floor mounted Amplifier Racks shall be vertical welded metal racks with uprights to mount equipment 19 inches wide. Uprights shall have 3-inch deep 16050-13 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 channels, 1-1/4 inches wide, drilled and tapped 12-24 in a 5/8 inch pattern. Racks shall be provided with a standard top cross-member and pre-drilled base plate to allow floor fastening. Vertical cable management devices shall be integral to the rack. Two power strips with six outlets each shall be mounted on the racks. B. Racks to be provided with the following additional features: 1. 2. 3. 4. 5. 6. 7. 8. 9. C. Acceptable manufacturers include: 1. 2. 3. 2.22 Finish: Textured black powder coat. Size: Racks to provide 44 equipment mounting spaces and to provide 24” of usable mounting depth minimum. Racks to be provided with lockable rear doors. Racks to be gang-able and provided with side panels. Racks to be provided with rack mount fan kit – 3 fans @ 315 CFM. Racks shall be provided with isolated ground power receptacles. Racks shall be electrically isolated from conduit at conduit entrance to racks. Provide safety ground wire from rack to panelboard per National Electrical Code. Racks shall be electrically isolated from concrete or metal floors using an insulation material beneath the rack. Provide quantity of three (3) racks. Mid Atlantic. Atlas-Soundolier Lowell POWER CONDITIONER A. Power conditioners shall be mounted in stage rack and shall be for use in a commercial sound reinforcement application. Power on sequencing shall be provided for amplifiers in rack through manual operation of power controls. B. Power conditioners shall meet the following specifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Maximum load: 20 amps (2400 watts at 120 VAC). Input Voltage Range: 85 to 135 VAC. Mains Wiring analyzer: Detects 1 normal mode and 5 fault modes. Spike Protection Modes: Line to neutral, neutral to ground, line to ground Spike Clamping Voltage: TVSS rating 400V peak, L-N, N-G, L-G (tested to UL 1449) Response time: One nanosecond Maximum surge current: 6,500 amps (8 x 20 µs pulse) Maximum spike energy: zero joules per node, 240 joules total protection. Noise attenuation: Transverse: >50 dB, 1 to 120 MHz Common mode: 20 dB at 150 kHz, rising to >40 dB, 1 to 120 MHz Mechanical: Dimensions: 1.75" H x 19" W x 8" D. Weight: 6 lbs (2.7 kg). Construction: Steel chassis, zinc chromate plating; .125" brushed and 16050-14 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual 14. 15. C. A. Cable Harness System shall be provided as shown in contract documents for infrastructure support of live events. Cable Harness System to consist of multipair cable and connectors that are suitable for touring use. Cabling to be premanufactured with one end cut to length and terminated in the field as required. Cable lengths should be determined from field measurements or drawing estimation. Cable Harness System specifications of equipment shall include: 2. 3. 4. Wall plates should be labeled with connector function using silk-screened text. Rack panels and patch-bays shall be suitable for installation in a standard equipment rack and should include lacing bars and stiffeners as required. Cable snakes and patch cords should be labeled with function using printed label covered with clear heat shrink. Custom components to be manufactured by a single vendor. Acceptable manufacturers include: 1. 2. 3. 2.23 Middle Atlantic SurgeX Furman Sound Inc. Tripp-Lite ETA Systems CABLE HARNESS SYSTEM 1. B. black anodized aluminum front panel; 3 oz. copper double-sided glass epoxy printed circuit board; all IC's in sockets. Power consumption: Switch off: 6 watts. Switch on: 8.5 watts Safety Agency Listings: UL listed, CUL listed. Acceptable manufacturers include: 1. 2. 3. 4. 5. 2.22 University of Georgia RCE 2013029 Rapco Horizon Whirlwind Pro-Co. WIRING & CONNECTORS A. Basic speaker cables shall be multi-pair cables, stranded, tinned copper. Cable shall be sized to provide optimum power to the end of the line speaker, with a minimum sizing of 14 gauge. Cable shall be UL listed type 246A. B. For balance of A/V cables and connectors, reference one-line diagram in contract documents and provide appropriate cables and connectors to ensure a fully functional audio visual system. C. The video cabling shall be coaxial cable that is capable of supporting digital SDI and HD-SDI video. 16050-15 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual D. 2.24 University of Georgia RCE 2013029 UTP cabling shall be at a minimum of the following requirements. 1. Minimum Bend Radius: 4.5 inches. 2. No. of Conductors: Eight insulated conductors 3. Standard lengths: 1000 Ft. 4. Nom. DCR: 22.8 ohms pr 1k ft. 5. Nominal Core Outside Diameter: 0.041 6. Nom. Pair-to-Pair Skew: Group 1:1.5 ns/ 100 m 7. Nominal Outside Diameter: 0.200 X 0.280 inches. 8. Nominal Impedance: 100 ohms. 9. Nominal Velocity of Propagation:71%. 10. Nominal Capacitance: 1pF/ft. 11. Nominal Attenuation at 155Mhz: -8.8 dB/100ft. TRANSIENT VOLTAGE SURGE SUPPRESSION A. Transient voltage surge suppression devices shall be provided to protect power strips in each rack and all equipment. Transient voltage surge suppression shall be provided for all audio visual equipment devices. B. Transient voltage surge suppression devices shall be an industrial-grade surge suppressor with EMI/RFI filtering. C. Transient voltage surge suppressors shall meet the technical requirements of SurgeX Professional AC Power Products. PART 3 - EXECUTION INSTALLATION 3.1 A. General: System components and appurtenances shall be installed in accordance with NFPA 70, manufacturer's instructions, and as shown. Necessary interconnections, services, and adjustments required for complete and operable audio visual systems shall be provided. Components shall be labeled in accordance with TIA/EIA 606. Penetrations in fire-rated construction shall be fire-stopped. A/V cables shall not be installed in the same raceway with AC power cables. Cables not installed in conduit or wire ways shall be properly secured and neat in appearance and, if installed in plenums or other spaces used for environmental air, shall comply with NFPA 70 requirements for this type of installation. B. Rack Mounted Equipment 1. 3.2 Rack mounted equipment shall be securely fastened to racks by means of the manufacturer's recommended fasteners. GROUNDING/BONDING 16050-16 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual A. University of Georgia RCE 2013029 Ground all equipment in accordance with the National Electrical Code. Ensure that a ground path exists to the building main electrical ground for all equipment. TESTING AND CHECK-OUT 3.3 A. Testing requirements apply to all equipment. Contractor to test each audio visual component as recommended by manufacturer. Test methods and test results shall be submitted to the owner prior to final inspection. B. Materials and documentation to be furnished under this specification are subject to inspections and tests. All components shall be terminated prior to testing. Equipment and systems will not be accepted until the required inspections and tests have been made, demonstrating that the audio visual systems conform to the specified requirements, and that the required equipment, systems, and documentation have been provided. TRAINING 3.4 A. The Contractor shall include in the base Contract all costs required to train owners operating and maintenance personnel in the use and maintenance of systems provided under this section of the Specifications. Instructors certified in writing by the manufacturer of the specific system shall conduct training sessions. B. Sessions shall be conducted for not less than four-hour periods during normal working hours, i.e., Monday through Friday, 8:00 AM to 5:00 PM. Training session schedules shall conform to the requirements of the owner; therefore, such schedules shall be submitted to owner for approval not less than two weeks prior to the training session. All training sessions shall be recorded for future use. At Owner's discretion, provisions shall be made to allow up to two owner personnel to participate in final system check out of all systems. C. Recordings shall be of professional quality for both video and audio and must be approved by the Owner/User. Provide two copies to Owner/User. Time to be included in base Contracts for specific systems shall be as follows: 1. Audio Visual Systems- 16 hours AS-BUILT DRAWINGS AND/OR DOCUMENTATION: 3.5 A. As-built drawings shall be provided noting the exact cable path and cable labeling information. The contractor shall provide drawings in .DWG format. As-builts shall be submitted to the owner on formatted CD’s, saved as .DXF or .DWG files. Redline hardcopies shall be provided as well. CAD generated asbuilt information shall be shown on a new layer named AS-BUILT. 1. System Acceptance: Before the owner accepts the system, the contractor 16050-17 Talmadge Auditorium – Rock Eagle Lighting, Audio-Visual University of Georgia RCE 2013029 shall be required to walk-through the installation with the owner's representative and the design engineer to verify proper installation and operation. END OF SECTION 27 4000 16050-18