9. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Kranjska Gora 2009 CIGRÉ ŠK B5-8 Optimal earth fault protection for compensated MV distribution networks Martin Čelko ABB Oy, Distribution Automation – Finland E-mail: martin.celko@fi.abb.com Janne Altonen ABB Oy, Distribution Automation – Finland E-mail: janne.altonen@fi.abb.com Ari Wahlroos ABB Oy, Distribution Automation – Finland E-mail: ari.wahlroos@fi.abb.com Olli Rintamäki ABB Oy, Distribution Automation – Finland E-mail: olli.rintamaki@fi.abb.com Abstract – This paper deals with earth fault protection for compensated MV distribution networks. First, we review main characteristics and purpose of the compensated MV distribution network. Next, we describe the known methods for detecting earth faults in compensated distribution MV network. We conclude and describe what could be the optimal earth fault protection for compensated MV distribution networks. I. INTRODUCTION This paper focuses on earth fault (EF) protection in medium voltage distribution networks with a compensated neutral point. The way the neutral point is earthed is a basic problem which greatly affects the number of technical and also economic solutions of power systems [1]. The earthing of the distribution network via the coil is one of the most popular methods over the last years in electrical network design by which better power supply quality and reliability can be achieved. The main advantage of this earthing arrangement is the self-extinguishing of most of the arcing faults and the possibility of continuing the network operation during a sustained earth fault. Consequently the number of autoreclosings, interruptions and outages of the power supply for the customer is significantly reduced, and thus running expenses for the utility can be brought down. These networks are also known as resonant earthed, or according to the inventor, as Petersen coil earthed networks. The arc suppression coil was invented by W. Petersen in 1916 as the result of his pioneering work in investigating earth fault phenomena [2]. II. BASICS OF COMPENSATED NETWORKS The idea of earth fault current compensation is to cancel the network earth capacitance by an equal inductance connected to the neutral with a corresponding decrease in the EF current as shown in Fig. 1. The main benefit of earth fault current compensation is that most of the single phase-to-earth faults are cleared by themselves. This, in addition to the small fault currents, is due to the fact that when the arc is extinguished, the compensation coil continues to produce a voltage equal to the phase to neutral voltage, so that the voltage in the fault spot (across the arc) rises slowly and restriking is unlikely. Fig. 1. EF in a compensated network. 9. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Kranjska Gora 2009 CIGRÉ ŠK B5-8 In compensated networks the phase-to-earth voltages of the two sound phases are, in case of zero fault resistance, equal to phase-to-phase voltage as represented in Fig. 2. This must be taken into account when selecting the insulation of the equipment in order to minimize the risk of double phase-to-earth faults. I ef U0 = ( 1 2 1 2 ) + (3wC0 − ) wL R0 In the case of complete compensation, the neutral voltage can be simplified as follows: U0 R0 = E R0 + R f Fig. 2. Phasor diagrams of the currents and voltages during a single phase-to-earth fault in a compensated network. (3) (4) In the above equations it was assumed that no additional neutral resistor RL is used. If needed, the effect of RL can be taken into account by replacing R0 in the above equations by the parallel connection of RL and R0. III. METHODS FOR DETECTING EARTH FAULTS IN COMPENSATED NETWORKS Fig. 3. Equivalent circuit for the EF in a compensated network. The equivalent circuit for the EF in a compensated network is shown in Fig. 3. The circuit is a parallel resonance circuit, and if the compensation coil is tuned exactly to the system capacitance, the fault current has only a resistive component. This resistive current is due to the resistances of the coil and distribution lines together with the system leakage resistances R0. Often the earthing equipment is complemented with a parallel resistor RL, the task of which is to increase the earth fault current in order to make selective relay protection possible. Using the equivalent circuit of Fig. 3, we can write the following for the earth fault current: I ef = E 1 + R02 (wC0 − 1 2 ) wL ( R f + R0 ) 2 + R 2f R02 (wC0 − (1) In compensated networks directional EF protection is commonly applied together with residual overvoltage protection as a back-up. The directional EF protection measures the residual current I0 and the neutral voltage U0. The selectivity of the protection is based either on measurement of the angle ϕ between U0 and I0 or on the active component I0cosϕ. Often the magnitude of this component is very small and needs to be increased by means of a resistor connected in parallel to the compensation coil. Typical characteristic of the “phase angle measurement” and the “I0cosϕ measurement” is shown in Fig. 4. The tripping in case of “phase angle measurement” characteristic is permitted if the residual current I0 exceeds the setting and the neutral voltage U0 is above the setting and the phase angle between I0 and U0 is in the range ϕ0+/-∆ϕ, where ϕ0=0° and ∆ϕ=+/-80° (or +/-88°). In case the “I0cosϕ measurement” characteristic is used the tripping is initiated if both the active component I0cosϕ and the neutral voltage U0 exceed the setting value. 1 2 ) wL In the case of complete compensation, the above can be simplified as follows: I ef = E R f + R0 The neutral voltage correspondingly as follows: (2) can be calculated Fig. 4. Relay characteristics of the directional EF protection in compensated networks where a) is phase angle measurement and b) is I0cosϕ measurement. In completely compensated networks the residual current is usually mostly resistive (Fig. 1, ΣI02) and 9. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Kranjska Gora 2009 CIGRÉ ŠK B5-8 Fig. 5. Extended relay characteristic of directional EF protection used in compensated networks. IV. INTERMITTENT EF PROTECTION In compensated networks, especially in those with underground cables, a special type of fault is encountered – the intermittent EF. This kind of fault tends to be difficult for conventional directional EF (DEF) relays to detect due to highly irregular wave shape of residual current [3]. Whereas residual overvoltage (ROV) relays used typically as a substation back-up protection have better chances for fault detection because of more steady behavior of residual voltage. Due to this fact intermittent EF can often cause non-selective tripping of the substation. Intermittent EF can be characterized as a series of cable insulation breakdowns because of reduced voltage withstand of it. As shown in Fig. 6 the fault is initiated as the phase-to-earth voltage exceeds the reduced insulation level of the fault point and extinguishes mostly itself as soon as the fault current crosses zero for the first time. 0.4 residual current (kA) 0.3 Current (kA) Voltage x 102 (kV) the sensitivity of the relay located in the faulty feeder is about the same for both types of characteristics. This is not the case for the relay in the sound feeder where the residual current is almost all capacitive (Fig. 1, ΣI01) and its phase angle is very close to the operation area of the relay characteristic. If there is an excessive phase displacement error in the instrument transformer used for measuring the residual current then a nuisance tripping may happen. In the “I0cosϕ measurement” principle the security margin can be set higher and the risk of malfunction is somewhat smaller than in the “phase angle measurement” principle. In compensated networks the protection relay must also be able to operate selectively in case the compensation coil is temporarily out of operation and the network is operated as isolated. Traditionally, the relay characteristic is changed by an external control command received from the auxiliary switch of compensation coil disconnector. In modern relays this command can be received via the communication. In Fig. 5 another solution is shown, where the relay characteristic is wide enough to cover both types of network. The application of this so called extended operating sector makes the changing of the characteristic unnecessary. 0.2 residual voltage x 102 (kV) 0.1 0 -0.1 5 10 cycles -0.2 -0.3 -0.4 Fig. 6. Typical waveforms of residual current and voltage measured from a substation during an intermittent EF. The electrical characteristics of the intermittent fault can be described by forming a simplified equivalent circuit of the network involved and by modeling the fault point as a nonlinear resistor and ‘a spark gap’ with certain type of characteristic current-voltage curve as shown in Fig. 7. When an EF occurs, for example, in phase A, the phase-to-earth voltage becomes shorted by the fault. The energy stored in the phase-to-earth capacitance of the faulty phase discharges and this discharge current transient can be measured in the faulty phase of any feeder of the substation (e.g. IvA_DISCHARGE, Fig. 7). It can be further concluded that because the healthy phase-to-earth voltages increase during the fault, the phase-to-earth capacitances of the healthy phases are initially charged by a transient called the charge current transient. The total charge current transient of the whole network flows in the faulty phase of the faulty feeder (IB,C_CHARGE, Fig. 7). The healthy phases of the healthy feeders experience only a part of the total charge current being proportional to the respective portion of the total phase-to-earth capacitance (IvB_CHARGE and IvC_CHARGE, Fig. 7). 9. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Kranjska Gora 2009 CIGRÉ ŠK B5-8 I0v I0 j U0 counter_pos max_count_j spike detection_j 0 counter_neg drop-off time_j 0 operate time delay_j 0 start signal_j 0 spike detection_v max_count_v Fig. 8. Filtered and sampled residual current and voltage signals (top) in relation to the principal operation of the spike detection method (bottom). Indices _j and _v stand for faulty and healthy feeders respectively. Fig. 7. Simplified equivalent circuit model of the network during an intermittent EF. Indices _j and _v stand for faulty and healthy feeders respectively. The residual current transient that can be measured in the beginning of the healthy feeders (I0v, Fig. 7) is a sum of charge and discharge current transients generated in each feeder (IvA_DISCHARGE, IvB_CHARGE and IvC_CHARGE, Fig. 7). Whereas the residual current transient that can be measured in the beginning of the faulty feeder (I0j, Fig. 7) is a sum of charge and discharge current transients of the healthy feeders and the coil transient (IvA_DISCHARGE, IvB_CHARGE, IvC_CHARGE and IL, Fig. 7). Moreover, it should be noted that the polarities of I0j and I0v are opposite to each other. The frequency of the charge transient is typically between 200 Hz and 1000 Hz. The frequency of the discharge transient is generally much higher, practical values being 4-20 times the frequency of the charge transient. Because of the high frequency the impedance of the compensation coil is also high, which means that the transient of the EF current is unaffected by the reactance magnitude of the compensation coil (i.e. the degree of compensation). Conventional DEF and ROV relays have been designed to operate with more or less steady–state fundamental frequency current and voltage sinewaves. It is therefore evident that problems arise when the current and voltage waveforms are highly irregular and a dedicated functionality against intermittent EF is needed. Bearing this in mind algorithms have been developed and implemented in modern feeder terminals. The basic detection methods are typically based on spike detection with certain polarity and phase angle criterion methods. Fig. 8 shows typical residual current waveforms measured from both faulty (blue) and healthy (red) feeder where the operation of the protection is based on spike detection method. Fig. 9 shows the operation of the protection based on phase angle criterion method where the phase angle difference between the residual current and voltage phasors measured from both faulty (blue) and healthy (red) feeder is shown. The protection starts if the calculated phase angle difference is inside the defined operating sector and in the same time the residual current and voltage amplitudes are above the set values. 120 60 0 -60 -120 jv jj extended operating sector drop-off time_j 0 operate time delay_j 0 start signal_j (internal) 0 start signal_j 0 Fig. 9. Phase angle difference between filtered and sampled residual current and voltage signals (top) in relation to the principal operation of the phase angle criterion method (bottom). Indices _j and _v stand for faulty and healthy feeders respectively. Variety of field tests has been performed in practical utility networks. The general result from the tests was that in the faulty feeder both detection methods gave out the trip signals correctly. A few times in a healthy feeder the DEF function and a couple of times the intermittent earth fault function applying phase angle criterion gave out false starting signal, but did not trip, especially when the network was heavily under or overcompensated and the feeder in question had a high capacitive current contribution. It should be noted that these algorithms are subject to constant development work to further enhance the performance. 9. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Kranjska Gora 2009 CIGRÉ ŠK B5-8 V. CONCLUSIONS The basic ideas, features and advantages of compensated MV distribution networks have been described. The main focus has been on the directional earth fault protection methods. Special attention has been put to the challenge of protection relaying in compensated networks with underground cables – to the intermittent earth fault. The directional earth fault protection is usually based either on the “I0cosϕ measurement” principle, or on the “phase angle measurement” principle. It is typical to apply multiple stages, i.e. low-set and highset stages, which make it possible that the operating speed and sensitivity requirements set on earth fault protection by the authority can be optimally fulfilled. For example, the low-set stage can be applied only for alarming and set to detect as high resistive faults as possible, whereas one or two high-set stages are used for tripping with different operate time delays. This also enables that the autoreclosure shots and sequences can be different depending on the fault current magnitude. In compensated networks the directional earth fault protection relay must be able to work selectively in case the compensation coil is temporarily out of operation. The relay characteristic shall be able to be changed according to the actual network earthing type. In modern relays this information or command can be received via the communication. Finally it could be concluded that the optimal earth fault protection for compensated MV distribution networks, especially for those with underground cables, shall have multiple stage directional earth fault protection completed with the dedicated protection against intermittent earth faults. References [1] [2] [3] M. Lehtonen, T. Hakola “Neutral Earthing and Power System Protection“ ABB Transmit Oy, Relays and Network Control, 1996 E. Bjerkan, T. Venseth, “Locating Earth-Faults in Compensated Distribution Networks by means of Fault Indicators”, International Conference on Power Systems Transients, Canada, 2005 J. Altonen, O. Mäkinen, K. Kauhaniemi, K. Persson “Intermittent earth faults – need to improve the existing feeder earth fault protection schemes?“ CIRED 2003 Barcelona