Conventional Fire Alarm Systems

advertisement
Conventional
Fire Alarm Systems
Contents
Introduction
Premier SX Conventional
Fire Alarm Panel
Premier Elite Conventional
Fire Alarm Panel
8
9
Zeta UV/IR Optical Flame Detectors
26-27
Zeta Conventional Manual Call Points
28
Zeta Conventional
Weatherproof Call Point
29
30
Premier Conventional Repeater Panel
10
Zeta Conventional Explosion Proof
Manual Call Point
Premier M Plus 8-24 Zone
Conventional Fire Alarm Panel
11
Miditone Conventional
Electronic Sounder
31
Premier M Plus Repeater Panel
12
Miditone Conventional Combined
Electronic Sounder & Flasher
32
Premier 48 M Plus 24-48 Zone
Conventional Fire Alarm Panel
13
Securetone Conventional
Electronic Sounder
33
Premier 48 M Plus Repeater Panel
14
Secure Light Xenon Flasher
34
Premier MX Conventional
Fire Alarm Panel
15
Maxitone Conventional Sounder and
Combined Sounder & Flasher
35
Fyreye Extra Conventional
Optical Smoke Detector
16
Zeta Conventional Fire Alarm Bells
36
Zeta Flame Proof Siren
37
Zeta Flame Proof Gong Bell
38
Zeta Magnetic Door Holders
39
Zeta Duct Unit
40
Fyreye Extra Conventional Rate of
Rise and Fixed Heat Detectors
2
3-7
17
Fyreye Extra Conventional
Opto-Heat Detector
18
Fyreye Conventional
Ultra-Violet Flame Detector
19
Fyreye Conventional Detector Bases
20
Premier Power Pack EN 54-4 Power
Supply with LCD Screen
41
Zeta Remote LED Indicator
21
Batteries
42
Fyreye 50 & 100m Reflective Beam
Smoke Detector
22-23
Fyreye 50 & 100m Auto-aligning Beam
Smoke Detector Systems 50 & 100m
24-25
Introduction
Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded
in 1985 and is a privately held UK manufacturer of Fire Alarm, Gas
Detection and Emergency Systems.
Our brand name is well known throughout the industry and is acclaimed in over forty
countries worldwide. We are currently represented in the UK, Europe, Africa, the
Middle East, Southern Asia & South America and this list continues to grow.
Complete System Supplier
Research & Development
To meet the requirements of our ever-changing market,
we pride ourselves on being a complete system
supplier. This means our customers can rely on us for
their entire system requirements.
As with all electronic equipment there is an ever
present drive to manufacture products that are
increasingly effective whilst becoming more cost
sensitive. To meet this objective we spend a significant
percentage of our profits on the continued development
of products, whether it be introducing new items, or
improving existing ones. We have a team of engineers &
designers all of whom have vast industry knowledge &
experience.
One of the main advantages of using a complete system
supplier, compared with a component supplier, is that
system wide compatibility is assured and there is one
point of contact.
Marketing our products as systems has played a vital
role in our worldwide success.
The Future
Our continued inward investment and constant
endeavour to offer the very best products is recognised
by our increased turnover and profit margin year-onyear. Our mission is to support our existing & future
customers by providing them with the highest quality
products, at the most competitive prices.
Customer Support & Product Warranty
As a manufacturer we always follow the market needs
closely to evaluate how we should adapt our product
range. This, combined with welcomed customer
feedback, has proved to be a successful formula for
meeting the current and future industry needs.
Statement Of Quality Policy
We maintain a Quality System, which conforms to BS EN
ISO9001:2008. We are committed, where applicable,
to manufacture in compliance with all appropriate
legislation & regulatory requirements.
We value our customers greatly and to ensure they have
the best experience we have a dedicated support team
who are able to assist with sales, technical or logistical
queries.
Our products carry a full 24 month manufacturers’
guarantee from the date of purchase. Our network
of authorised agents is fully trained on the use of our
products and will provide a helpful & friendly service.
3
Introduction to Fire
Alarm Systems
Fire Detection &
Alarm Systems BS5839
Fire alarm systems are used to detect a
fire, and to signal a warning alarm to the
appropriate source.
Risk Assessment
In general, there are 3 types of system;
1. Manual Fire Alarm Systems – which rely on manual
call points to signal an alarm
2. Life Protection Fire Alarm Systems – these are
designed to protect the occupants of a building
3. Property Protection Fire Alarm Systems – these
are designed to protect buildings
The warning may be simply ringing fire alarm sirens,
however if a building is likely to be unoccupied, it may
be more appropriate to signal to a monitoring station,
or at least send a message to the building owner via
telephone.
The ‘Fire precautions (Workplace) Regulations’ require
any business employing five or more persons to hold a
written ‘Fire Risk Assessment’ and ‘Emergency Plan’.
This must be periodically reviewed.
The local fire brigade can enforce compliance, and
close any building that does not meet this act.
In the event of a fire in a building without a written
‘Fire Risk Assessment’, those responsible may face fines
and imprisonment, and/or private litigation.
What the law requires you to do:
Complete a fire risk assessment for your work
place (considering all employees, the public,
disabled people and people with special needs).
Identify and record any significant findings or
persons at risk.
Provide and maintain fire precautions.
Provide information, instruction and training.
Nominate persons responsible to implement
your emergency plan.
Consult employees about the above nominations
and your proposals to improve fire precautions.
Inform other employees who may have work
places in the building about any significant risks
which may affect their safety and co-operate with
them to reduce/control these risks.
If you are not an employer, but control premises
which contain more than one workplace, you are
responsible for complying with fire regulations.
You must establish a suitable means of
contacting the emergency services.
Your employees must co-operate to ensure the
workplace is safe from fire and its effects.
4
System Zoning
Information
In order to aid identification of the source of a possible
fire, the protected building should be divided into
‘zones’. When deciding on a suitable zoning scheme
for a building, consideration should be given to the
size, any existing fire routines, escape routes, zone
accessibility, and structural fire compartmentation.
The following guide lines should be observed:
If the total floor area of the building is less
than 300m2 then the building needs only one zone,
regardless of the number of storeys.
Manual Call Points
A ‘Manual Call Point’ is a device which enables
personnel to raise an alarm in the event of a fire
incident by pressing a frangible element to activate the
alarm system.
Manual Call Points should be installed at a height of
1.2m above floor level at easily accessible, conspicuous
positions, on exit routes, at the entry floor landings of
staircases and at all exits to the open air.
If the total floor area is greater than
300m2:
The maximum area for a zone is 2000m2
If a stairwell (or similar) extends beyond one floor it
should be a separate zone.
If a zone covers more than one fire compartment
then the zone boundaries should follow the
compartment boundaries.
The search distance within the zone in order to
ascertain the position of the fire should not exceed
60m. Remember that the use of Remote Indicator
lamps may help to reduce the distance travelled.
1.2m - 1.4m
Manual Call Points should be spaced so that one may
always be found within a maximum distance of 45m
apart or 25m for disabled person.
45m Max. or
25m Max. for disabled person
60m Max.
If a building is divided between occupiers, zones
must not be shared between them.
5
Detector Information
Automatic Detectors
When deciding on the type of detector to be used in any area it is important to remember that the detector has to
discriminate between a genuine fire and the normal conditions existing therein.
Smoke Detectors
Heat Detectors General
In open spaces under flat horizontal ceilings, every
point should lie within 7.5m of a smoke detector.
In open spaces under flat horizontal ceilings, every
point should lie within 5.3m of a heat detector.
10.6m
7.5m
112m²
(10.6m x
10.6m)
56.3m²
(7.5m x
7.5m)
Room
boundary
7.5m
5.3m
5.3m
Smoke detection should be generally avoided in the
following areas to avoid unwanted alarms. They should
be protected by means of other detectors such as heat
detectors.
Contamination in dusty areas may cause unwanted
alarms and reduce the life of the detector.
Damp or humid conditions such as showers, bathrooms
and external areas should be avoided as the water
vapour may cause unwanted alarms and reduce the life
of the detector.
Detectors should not be mounted where gases, vapours
or fumes are present.
Detectors should never be used at low temperature
where ice or condensation can affect detector
sensitivity.
Kitchens, garages, welding shops and boiler houses
should generally be avoided.
6
Room
boundary
3.8m
Heat detectors are designed to either detect a
rapid rise in temperature or to operate at a fixed
temperature. Although they provide a slower response
time than smoke detectors they do provide a method of
protection for areas where smoke detectors cannot be
used.
Heat detectors should not be used for the protection of
life or where extensive property loss may be expected.
‘Rate of Rise’ Heat Detectors
‘Rate of Rise’ heat detectors respond to both rapid
increases of temperature and to fixed top temperature.
‘Fixed Temperature’ Heat Detectors
Fixed temperature heat detectors are available with
different temperature settings, and are normally
installed in kitchens, boiler rooms, etc.
Detection In Apex Roofs
Fire Alarm Sounders
If the ceiling is pitched or sloping, smoke will tend
to rise towards the highest point (apex) of the roof,
therefore detection should be placed in the apex. As
the slope tends to reduce the delay before smoke or
heat reaches the detectors, it is permissible to use a
greater spacing between the detectors mounted there.
Fire Alarm Sounders should be installed throughout the
building with an even distribution, to generally provide
a minimum sound level of 65dB(A) or 5dB(A) above any
background noise which is likely to persist for more
than 30 seconds.
Limits of Ceiling Height
65dB(A)
@ 500Hz - 1000Hz
+5dB(A)
@ 500Hz - 1000Hz
Background noise
Heat
Detector
Smoke
Detector
Heat
Detector
Smoke
Detector
Apex
<150mm
Apex
<600mm
Apex
>150mm
Apex
>600mm
Small Apex
= Standard Spacing
Large Apex
= Extended Spacing
Cabling
Where the alarm may have to arouse sleeping persons
e.g. Hotel bedrooms, nursing homes, etc, a minimum
sound level of 75dB(A) is required, at the bed head with
all the doors shut.
The operation of a Fire Alarm and Detection
System’ depends on the cabling and connections
between the components. It is essential that
connection between Manual Call Points and
Detectors function correctly when they are
operated.
Cables within the system are required to function
correctly for significant periods after being
attacked by fire. These include the power supply
cables to the control panel, the detection circuits
and the fire alarm sounder circuits. Thus the
cables chosen must be correctly rated to withstand
these conditions.
75dB(A)
All fire alarm sounders in a building should produce the
same sound, distinct from any other audible warning
devices in the building.
Where fire alarm sounders are required in extremely
noisy areas e.g. Machine shops, it may be necessary to
install additional ‘Visual Indication Beacons’.
7
Conventional Fire Alarm Systems /
Premier SX Conventional Fire Alarm Panel
(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)
The Premier SX control panel range is available
in 1, 2, 4, 6 and 8 zones, housed in a light grey
flame retardant ULV0 enclosure, designed to
meet modern architectural surroundings, with
a removable hinged door.
The Premier SX has been designed with ease of
installation in mind, in addition to the robust electronic
design expected from Zeta Alarm Systems.
73mm
Features
100mm
LPCB Approved to EN54 parts 2 & 4
One man test facility
Disablement facility for zones & sounders
Space for up to 7Ahr batteries
Sounder delay option (0 – 9 min)
Panel can be flush mounted
Flush Mount
8
Wall Mount
Model
NPSX1
NPSX2
NPSX4
NPSX6
NPSX8
Part No.
37-050
37-051
37-052
37-053
37-054
Mains Voltage
230V AC +10% / -15% @ 50/60Hz
System Voltage
24V DC (nominal)
Zone Voltage
21V DC (nominal)
Sounder Alarm Output
2 x 400mA @ 24V DC (nominal)
Fault Relay Output
1 x relay SELV @ 1A maximum
Fire Relay Output
1 x relay SELV @ 1A maximum
Zone Capacity
32 devices per zone
Remote Sounder Activation
Via N/O contact (class change)
Sounder Activation Delay
0-9 minutes in 1 minute increments
Zone End Of Line
IN4002 Diode (cathode stripe to +)
Sounder End Of Line
10K resistor
Charger Voltage
28.4V @ 20°C (with battery disconnected)
Zone Short Circuit Protection
100mA
Charger Short Circuit Protection
Battery voltage less than 20V
Enclosure Size
355 (l) x 275 (h) x 100 (d) mm
Weight
3.25kg (excluding batteries)
Conventional Fire Alarm Systems /
Premier Elite Conventional Fire Alarm Panel
(PE1, PE2, PE4, PE6, PE8)
The Premier Elite 1-8 zone fire alarm
panels are ideal for small to medium sized
installations. They meet all the requirements
of EN54 parts 2 & 4, and come in an
attractively styled enclosure.
The zonal output card gives a drive voltage to operate
zonal alarm relays, or a hardwired repeater panel.
Features
73mm
Fault relay (4, 6 & 8 zone only)
100mm
Alarm relay
Current limited charger to prevent flat batteries
drawing too much current (4, 6 & 8 zone only)
Built in diode base compatibility (4, 6 & 8 zone
only)
Sounder delay facility (4, 6 & 8 zone only)
Connection to optional add on zonal output card
(4, 6 & 8 zone only)
Zone disablement facility (4, 6 & 8 zone only)
Flush Mount
One man test facility (4, 6 & 8 zone only)
Wall Mount
Model
PE1
PE2
PE4
PE6
PE8
Part No.
37-040
37-041
37-042
37-043
37-044
Detection Zones
1
2
4
6
8
Mains Voltage
230V AC +10%/-15% @ 50/60Hz
System Voltage
24V DC (nominal)
Zone Voltage
22V DC (nominal)
Sounder Alarm Output
2 x 400mA @ 24V DC (nominal)
Fault Relay Output
N/A
Fire Relay Output
1 x relay SELV @ 1A maximum
Zone Capacity
20 Devices
32 Devices
Remote Sounder Activation
N/A
Via N/O Contacts
Sounder Activation Delay
N/A
0-9 minutes in 1 minute increments
Zone End Of Line
10K resistor
IN4002 Diode (cathode stripe to +)
Sounder End Of Line
10K resistor
10K resistor
Charger Voltage
27.6V DC (No Batt Connected)
28.4V @ 25°C (No Battery Connected)
Zone Short Circuit Protection
N/A
100mA
Charger Short Circuit Protection
N/A
Batteries less than 21V
Operating Temperature
0°C to 50°C
Enclosure Size
355 x 275 x 100mm
Weight
2.5kg (excluding batteries)
29V DC (nominal)
1 x relay SELV @ 1A maximum
3.25kg (excluding batteries)
9
Conventional Fire Alarm Systems /
Premier Conventional Repeater Panel
(PRE-REP)
The Premier Repeater panel is a hard-wired
repeater panel for use with the Premier SX (all
sizes), and the Premier Elite (4-8 zone) panels.
It is display only (no controls) and indicates power,
general fault, general fire & the zone in alarm. It also
has an internal buzzer to indicate that it requires
attention.
It comes supplied with an interface card to connect to
the Premier SX and Premier Elite (4-8 zone) panels.
73mm
100mm
Features
Zonal indication for fire
Common fault indication
Surface or semi flush fixing
Flush Mount
Model
PRE-REP
Part No.
37-045
Supply Voltage
20–35V DC
Supply Voltage
29V DC (nominal)
Connections
10
Wall Mount
A+
Supply +VE
0V
Supply –VE
GA
General Alarm
CF-
Common Fault
TN-
Tone (Buzzer Active)
Z1- to Z8-
Zonal Alarm
Operating Temperature
-0°C to 50°C
Enclosure Size
355 x 275 x 100mm
Weight
1kg
Conventional Fire Alarm Systems /
Premier M Plus 8-24 Zone Conventional Fire
Alarm Panel (PMP8, PMP16, PMP24)
The Premier M Plus control panels are designed
to fulfil the requirements of EN54 parts 2 & 4
as well as being easy to install, operate and
maintain.
Being of modular construction, the basic M Plus panel
has 8 zone capacity, expandable to 16, 20 and 24 zones.
The Premier M Plus is suitable for surface mounting or
semi-flush fitting (with just the door protruding).
Features
4 Common sounder circuits (150mA each)
Optional add-on zonal sounder circuits (50mA
Max.)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal
sounder boards)
One man test mode
Model
PMP8
PMP16
PMP24
Part No.
37-020
37-022
37-024
Detection Zones
8
16
24
Mains Voltage
230V AC +10% / -15% @ 50/60 Hz
System Voltage
24V DC (nominal)
Zone Voltage
21V DC
Sounder Alarm Output
4 x 150mA @ 24V DC
Fault Relay Output
1 x relay SELV @ 1A maximum
Fire Relay Output
1 x relay SELV @ 1A maximum
Zone Capacity
32 Devices
Remote Sounder Activation
N/A
Sounder Activation Delay
0 – 9 minutes in 1 minute increments
Zone End Of Line
IN4002 Diode
Sounder End Of Line
10KΩ Resistor
Charger Voltage
28.4V DC (batteries disconnected)
Zone Short Circuit Protection
100mA
Charger Short Circuit Protection
Batteries less than 20V
Charger Size
3.0 Amp
Operating Temperature
0°C - 50°C
Enclosure Size
485 x 477.5 x 125mm
11
Conventional Fire Alarm Systems /
Premier M Plus Repeater Panel
(PMP-REP, PMP-REP/M)
The Premier M Plus repeater is available in 2
versions – standard & multiple.
The standard repeater offers display & control
functions, however it is limited to one per system.
The second version allows multiple repeaters on the
same system however they do not have any control
functions (i.e. they cannot be used to silence or reset
the system).
A single repeater can be powered from the panels’
auxiliary 24V supply. If more than one repeater is to be
used, a separate 24V is required.
Model
PMP-REP
PMP-REP/M
Part No.
37-026
37-027
Functions
Display & control
Control only
Supply Voltage
20-30V DC
Max. Quantity Per System
1
Serial Repeater A
Connections
Serial Repeater B
+24V DC
0V
12
Operating Temperature
0°C to 50°C
Enclosure Size
375 x 335 x 125mm
Weight
TBC
5
Conventional Fire Alarm Systems /
Premier 48 M Plus 24-48 Zone Conventional
Fire Alarm Panel (PMP48/24, PMP48/32, PMP48/40, PMP48/48)
The Premier 48 M Plus control panels are designed to
fulfil the requirements of EN54 parts 2 & 4 as well as
being easy to install, operate & maintain.
Being of modular design, the basic panel has 24 zones
built in and it can be expanded to 32, 40 & 48 zones.
The construction of the panel is epoxy painted steel
enclosure, with top & rear cable entries.
Features
4 common sounder circuits (400mA each)
Optional add-on zonal sounder circuits (50mA
Max)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal
sounder boards)
One man test mode
Model
PMP48/24
PMP48/32
PMP48/40
PMP48/48
Part No.
37-030
37-032
37-034
37-036
32
40
48
Detection Zones
24
Supply Voltage
230V AC +10%/-15% @ 50/60 Hz
System Voltage
29V DC (nominal)
Zone Voltage
21V DC
Sounder Alarm Output
4 X 400mA @ 24V DC
Fault Relay Output
1 relay SELV @ 1A (normally energised)
Fire Relay Output
1 relay SELV @ 1A maximum
Other Connections
Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)
Zone Capacity
Up to 32 devices
Remote Sounder Activation
N/A
Sounder Activation Delay
0 to 9 minutes
Zone End Of Line
100μF capacitor
Sounder End Of Line
10K resistor
Charger Voltage
28.4V DC (Batteries disconnected)
Zone Short Circuit Protection
100mA
Charger Short Circuit Protection
Batteries less than 20V
Charger Size
3 Amp
IP Rating
IP43
Operating Temperature
0°C to 50°C
Enclosure Size
675 x 480 x 135mm
Weight
13kg
13
Conventional Fire Alarm Systems /
Premier 48 M Plus Repeater Panel
(PMP48-REP, PMP48-REP/M)
The Premier 48 M Plus repeater is available in
2 versions – standard & multiple.
The standard repeater offers display & control
functions, however is limited to one per system.
The second version allows multiple repeaters on the
same system however they do not have any control
functions (i.e. they cannot be used to silence or reset
the system).
A single repeater can be powered from the panels’
auxiliary 24V supply. If more than one repeater is to be
used, a separate 24V is required.
Model
PMP48-REP
PMP48-REP/M
Part No.
37-037
37-038
Functions
Display & control
Control only
Supply Voltage
20–30V DC
Maximum Quantity Per System
1
Serial Repeater A
Connections
Serial Repeater A
+24V DC
0V
14
Operating Temperature
0°C to 50°C
Enclosure Size
480 x 330 x 60mm
Weight
4.8kg
5
Conventional Fire Alarm Systems /
Premier MX Conventional Fire Alarm Panel
(MX-16 & MX-32)
The Premier MX ranges of panels are available
in either 16 or 32 zone versions and have been
approved by LPCB to EN54 parts 2 & 4.
The panels offer an extensive range of configuration
options whilst remaining easy to install and configure.
Model
MX-16
MX-32
Part No.
37-140
37-142
Detection Zones
16
32
Supply Voltage
230V AC +/- 10%
Zonal one-man test facility
System Voltage
24V DC (Nominal)
Zone Voltage
24V DC (Nominal) Relay, SELV @ 1A
Latching or non-latching zones
Zone End of Line
22uF, 35V Axial Capacitor
Sounder Output
4 X 1.0A @ 24V DC
Sounder EOL
3K9 Resistor
Aux DC Output
24V DC (Nominal) 1A
Repeater option
Yes
Remote
Evacuation
Remote Silence
Alarms
Panel Inputs
Remote Reset
Class Change
Panel Outputs
Fault Routing
Relay, SELV @ 1A
Fire Routing
Relay, SELV @ 1A
Features
LPCB Approved to EN54 parts 2 & 4
Delayed or non delayed zone operation
Standard or intrinsically safe zone mode
Short circuit to fire mode for compatibility with
old detectors
Fire Protection Relay,
SELV @ 1A
Disablement Active
(Open Collector
Output)
Evacuation Active
(Open Collector
Output)
Buzzer Active (Open
Collector Output)
Zonal or common alarm operation (requires
output expansion PCBs)
Latching or non-latching fault modes
Fault routing, fire routing & fire protection
relays can be programmed as 24V output
(monitored) or volt free
Fault routing, fire routing & fire protection
relays can have delayed operation in any
configuration
The panel is available as flush mount on request
Repeater panel option (up to 5 maximum per
panel)
RS 485 Repeater
Connection
Operating
Temperature
-5°C to 40°C
Size
325 x 370 x 126mm 400 x 441 x 131mm
Weight
7.05kg
9.35kg
15
Conventional Fire Alarm Systems /
Fyreye Extra Conventional
Optical Smoke Detector (FEOE2000)
The Fyreye Extra optical smoke detector uses
a pulsing IR LED & photodiode to detect IR
scatter caused by smoke entering the chamber.
The detector is particularly suitable for detecting
optically dense smoke, involving materials such as soft
furnishings, PVC, plastic, foam and all similar materials
which produce small visible particles (0.5 to 10μm).
The detector will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.
100mm
37mm
Features
Designed to meet EN54 requirements
Attractive design
Dual LEDs for 360° visibility
Lockable base to stop unauthorised removal
Compatible with all Fyreye bases
16
Model
FEOE2000
Part No.
80-022
Detector Class
Optical Smoke
Design Standard
EN54 part 7
Approval
DIFT
Operating Voltage
9-33V DC
Quiescent Current
65μA
Alarm Current @ 24V DC
53mA MAX
Operating Temperature
-10°C to +50°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH non-condensing
Alarm Condition
2.4% obscuration per metre
Coverage
100m2
IP Rating
IP43
Start-up Time
10 Seconds
Size (with Base)
100 x 37mm (101 x 53mm)
Weight (with Base)
95g (153g)
Conventional Fire Alarm Systems /
Fyreye Extra Conventional Rate of Rise and
Fixed Heat Detectors (FEHE2000 & FEFHE2000)
The Fyreye Rate of Rise heat detector
(FEHE2000) uses a thermistor arrangement
to sense a quick rise in temperature and also
a final threshold temperature of 57°C. The
Fyreye fixed heat detector (FEFHE2000) has a
single thermistor arrangement that gives an
alarm at a temperature of 90°C.
The detectors will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.
100mm
48mm
Features
Designed to meet EN54 requirement
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360° visibility
Compatible with all Fyreye bases
Model
FEHE2000
FEFHE2000
Part No.
80-038
80-039
Detector Class
Rate of Rise & Fixed Heat Detector
Fixed Heat Only
Design Standard
EN54 part 5
Approval
DIFT
Operating Voltage
9-33V DC
Quiescent Current
40μA
Alarm Current @ 24V DC
34mA
Operating Temperature
-10°C to +50°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH non-condensing
Alarm Condition
Rate of rise or fixed heat trigger @ 57°C
Coverage
50m²
IP Rating
IP43
Start-up Time
10 Seconds
Size (with Base)
100 x 48 mm (101 x 64 mm)
Weight (with Base)
75g (133g)
Fixed heat trigger @90°C
17
Conventional Fire Alarm Systems /
Fyreye Extra Conventional
Opto-Heat Detector (FEOH2000)
The Fyreye Extra opto-heat detector
incorporates both an optical chamber and
heat sensing element with advanced detection
technology & discrimination algorithms. This
multisensor is the perfect replacement for
ionisation detectors.
The detector will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.
Features
100mm
50mm
Advanced electronic technology used to
minimise false alarms
Designed to meet EN54 requirement
Built-in 10 seconds alarm verification
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360° visibility
Compatible with all Fyreye bases
18
Model
FEOH2000
Part No.
80-025
Detector Class
Optical / Heat
Design Standard
EN54
Approval
DIFT
Operating Voltage
17-20V DC
Quiescent Current
100μA
Alarm Current @ 24V DC
70mA MAX
Operating Temperature
-20°C to +60°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH non-condensing
Alarm Condition
3% obscuration per metre
Coverage
100m²
IP Rating
IP43
Start-up Time
10 Seconds
Size (with Base)
100 x 50mm (100 x 66mm)
Weight (with Base)
95g (153g)
Conventional Fire Alarm Systems /
Fyreye Conventional
Ultra-Violet Flame Detector
(FEUV2000)
The Fyreye ultra-violet flam detector is
particularly suited to applications where
flames can be expected to develop initially
rather than smoke. This is typically due to the
nature of the materials being protected for
instance camera film, computer, audio & video
tapes or disks.
The detector is for indoor use only and should not
be exposed to spurious sources of UV, such as sparks,
uncovered halogen lights, lightening, etc. as these may
trigger a false alarm.
Due to the operational nature of flame detectors it is
generally recommended to fit just one detector per
zone.
Features
0°
30°
30°
60°
60°
90°
90°
ANODE
CATHODE
UV EMISSION
POINT
0°
30°
Low profile shape
VERTICAL VIEWING
(top fig.)
The detector is solar blind and incorporates an
electronic filter to eliminate unwanted alarms
from naturally occurring phenomena
HORIZONTAL
VIEWING
(bottom fig.)
Fast response time
30°
60°
High immunity to electrical noise & RF
interference
60°
90°
90°
ANODE
CATHODE
Horizontal & Vertical Detector Field Of View
Model
FEUV2000
Part No.
80-045
Detector Class
Ultra Violet Flame Detector
Operating Voltage
12-28V DC
Quiescent Current
320μA
Alarm Current @ 24V DC
45-50mA
Operating Temperature
0°C to 45°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH non-condensing
Alarm Condition
10 seconds for 30mm flame @ 4 metres
Detection Angle
120°
UV Sensitivity
185-260nm
Size (with Base)
98 x 36mm (98 x 52mm)
Weight (with Base)
85g (143g)
19
Conventional Fire Alarm Systems /
Fyreye Conventional Detector Bases
(FE-CB, FE-DB, FE-RB)
FE-CB
FE-CB/S
There are 3 types of base available
for the Fyreye conventional range
of detectors namely common base,
diode base and relay base.
The Fyreye common base and diode
base are available in standard,
shallow or deep versions.
The common base is used on systems
that do not need to keep line
integrity on head removal and also
on addressable systems.
Model
20
FE-CB/D
The diode base is used on systems
that do need line integrity on
head removal. This would include
all conventional systems that mix
detectors & call points on the same
line (please note that the Premier M
Plus panels will need an active end
of line to work with diode bases).
The relay base is mainly used on 12V
security systems to signal detector
operation to the panel. They can
FE-CB
FE-CB/S
FE-CB/D
80-050S
80-050D
FE-RB
FE-DB
also be used on 24V fire systems
where the activation of a particular
detector requires a signal to nearby
equipment (for instance door
holders).
Please note that a remote led
indicator cannot be used with a relay
base as the detector cannot sink
enough current to operate both.
FE-DB
FE-DB/S
FE-DB/D
FE-RB
80-052
80-052S
80-052D
80-054
Part No.
80-050
Type
Common base
Supply Voltage
9-33V DC
Quiescent Current @ 24V
0μA
Alarm Current @ 24V
0mA
15mA
Relay Max Switching Power
N/A
30W, 50VA
Relay Max Switching Power
N/A
30W, 50VA
Diode base
Relay base
24V DC
Relay Max Switching Current N/A
1A resistive
Relay Max Switching Voltage N/A
50V AC
Relay Minimum Capability
N/A
10μA, 10mV
Relay Dropout Voltage
N/A
<6V
Operating Temperature
-20°C to 90°C (non-condensing or icing)
Max. Wind Speed
Not affected
Connections
L1in, L1out, L2, -R & Earth
Size
100 x 15mm 100 x 8mm
100 x 25mm 100 x 15mm 100 x 8mm
100 x 25mm 100 x 15mm
Weight
48g
61g
61.2g
42g
48.2g
42.2g
171.4g
Conventional Fire Alarm Systems /
Zeta Remote LED Indicator
(ZT-RL)
Remote LEDs indicators are used in
installations where a detector going to alarm is
likely to occur out of sight (for instance behind
a locked door or in a ceiling void). In these
instances the indicator will then show the
location of the alarm.
Features
Twin LED’s
Surface or flush mounting
Model
ZT-RL
Part No.
48-023
Input Voltage
5 – 30vdc
Quiescent Current
0mA
Alarm Current
12mA
Operating Temperature
0°C - 50°C
Max Humidity
95% Relative Humidity Non-condensing
IP Rating
IP41
Size
85 x 85 x 70mm
Weight
113g
21
Conventional Fire Alarm Systems /
Fyreye 50 & 100m Reflective Beam
Smoke Detector (ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)
The Fyreye reflective beam detectors comprise
of a single unit incorporating an infrared
transmitter & receiver. The signal is reflected
by a prism and analysed for smoke presence.
Should a predetermined level be reached then
the detector will signal an alarm.
The system is designed to be mounted so that the beam
will project between 0.3 and 0.6 metres below the
ceiling and parallel to it. Lateral detection may be up to
7.5 metres either side of the beam.
Features
70mm
126mm
120mm
50 or 100 metre reflective beam smoke detector
VdS approved
BS 5839 part 5
100mm
100mm
140mm
210mm
Complies fully to;
EN54 part 12
Single compact housing
Horizontal or vertical mounting
12-24V DC operation
9.5mm
Low current consumption
Latching or non latching alarm
Reflector targeting mode to ease set-up
Microprocessor controlled
Automatic contamination compensation
Selectable sensitivity
Robust construction
22
The Fyreye beam detectors are available with ranges of up to 50 or 100 metres and either 2 or 4
wire connections.
The 2 wire models (ZT-50RZ & ZT-100RZ)
are zone powered (please note these will
only work on Premier SX & M Plus panels).
The 4 wire models (ZT-50RV & ZT-100RV)
require an external 24V power supply and
have a fire & fault relay output for wide
compatibility.
Typical Applications
Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where
several regular smoke detectors would be aesthetically unacceptable.
Such places include;
Shopping centres
Open Plan offices
Heritage sites
Warehouses
Churches or mosques
Factories
Museums
Power stations
Leisure centres
and more
Model
ZT-50RZ
ZT-100RZ
ZT-50RV
ZT-100RV
Part No.
47-050
47-051
47-050A
47-051A
50-100m
5-50m
50-100m
Range
5-50m
Number of Wires
2
Supply Voltage
10.2V to 30V DC
Quiescent Current
<4mA
Operating Temperature
-30°C to 55°C
Max Humidity
95% RH non-condensing
Max Wind Speed
Not affected
Alarm Current
35mA (typical)
<15mA
Fire Output
470 OHM resistor placed across zone internally
Fire relay closing (relay contact is normally
open)
Fault Output
Schottky diode introduced between –VE in &
-VE out
Fault relay opening (relay contact is normally
closed)
Power Down Reset
<2 seconds
>5 seconds
4
Beam Misalignment Tolerance Detector ± 0.8°
at 35%
Prism ± 5.0°
Alarm Thresholds
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
Optical Wavelength
880nm
Construction
Flame Retardant ABS (Grey /Black)
IP Rating
IP50
Size
130 x 210 x 120mm
Weight
0.75kg
0.7kg
23
Conventional Fire Alarm Systems /
Fyreye 50 & 100m Auto-aligning Beam Smoke
Detector Systems 50 & 100m (ZT-5000R & ZT-5000R/100)
Based on the proven technology of the
standard Fyreye reflective beam detectors, the
Fyreye auto-aligning beam detector has been
designed to help improve ease of installation.
The system is ideally suited for the protection of
large areas where the use of traditional detection
technologies would prove to be too difficult and/or
costly to install.
The system combines an infrared transmitter and
receiver in the same discrete unit and operates by
projecting a well-defined beam to a reflective prism,
which returns the beam to the receiver for analysis.
Smoke in the beam path causes a drop in power, which,
if below a pre-determined level, results in an alarm
signal.
The system consists of 2 parts; the beam detector itself
and a low level control unit.
The system can be fully customised, according to local
conditions and installation guidelines; alarm thresholds
(sensitivity) and time to alarm/fault can be set from the
low level system controller.
Each detector head is independently configurable from
8m through to 100m and has its own individual fire
threshold. The system controller retains one set of fire
and fault relays that is common to all detectors that are
installed.
The system is supplied as either a 50 or 100 metre
version with a single detector head. Additional heads
and a long range kit (additional prisms to allow the
detector head to reach 100m) are available separately.
Additional System Components
ZT-5000R/DH - 47-072 - Fyreye Auto-aligning Single
Beam Detector Head 50m
ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligning
Single Beam Detector Head 100m
ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning Beam
Detector Long Range Kit
24
Features
Worldwide approvals including EN54:12 and
UL268
Up to 4 detectors per system controller
Each detector configurable from 8m to 100m
Integral LASER
Auto-align fast automatic beam alignment
Auto-optimise building movement and
contamination compensation
Low level system controller
20mm cable gland knockouts on system
controller
2-wire interface from system controller to
detector
202mm
135mm
81mm
135mm
230mm
135mm
Model
ZT-5000R
ZT-5000R/100
Part No.
47-070
47-071
Range
50m
100m
Number of Wires
4
Supply Voltage
14-28V DC
Operating Current
8-12mA (low current mode with 1 detector)
48-52mA (high current mode with 1-4 detectors)
Operating Temperature
-20°C to 55°C
Storage Temperature
-40°C to 85°C
Max Humidity
85% RH non-condensing
Max Wind Speed
Not affected
Alarm Current
35mA (typical)
Fire Output
Volt free relay contact
Fault Output
Volt free relay contact
Beam Misalignment Tolerance @ 35%
Detector ± 0.8°, Prism ± 5.0°
Alarm Thresholds
2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)
Optical Wavelengths
850nm
Construction
Flame Retardant ABS (Grey / Black)
IP Rating
IP54
Detector Size
135 x 135 x 135mm
Detector Weight
0.5kg
Controller Size
202 x 230 x 81mm
Controller Weight
0.9kg
25
Conventional Fire Alarm Systems /
Zeta UV/IR Optical Flame Detectors
(VS-200P & VS-200EX)
VS-200P
VS-200EX
The VS-200P & VS-200EX UV/IR flame detectors
detect fuel & gas fires at long distances with
the highest immunity to false alarms. The
detectors can detect a 0.1m² gasoline pan fire
at 30m in less than 5 seconds.
Typical
Applications
Non-hazardous (VS-200P)
Parking buildings
Warehouse
Waste disposal facilities
Culture centres
Hazardous (VS-200EX)
Offshore oil & gas
installations
Onshore oil & gas
installations and
pipelines
Petrochemical plants
Chemical plants
Shipbuilding facility
Automotive industry
Storage tank farms
Power generation
facility
Petrochemical plants
Painting industry
Warehouse
Waste disposal facility
Explosive & munitions
26
Features
UV/IR spectrum for medium distance detection
and high false alarm immunity
Compact & lighter design
User selectable sensitivity & functions
Multiple output options (relays for alarm & fault,
0-20mA (stepped) and RS-485/RS-232 spectrum
monitoring)
ATEX approved by DNV for explosion-proof (VS200EX UV/IR only)
CE certified
Model
VS-200P
VS-200EX
Part No.
47-150
47-151
Spectrum Response
UV /IR (Dual Bands)
Spectrum Response
(at highest sensitivity setting
for 0.1m² pan fire)
Fuel
n-Heptane
Gasoline
Diesel
LPG*
Distance
30m
30m
20m
20m
Fuel
Ethanol
IPA
Methanol
Distance
20m
25m
20m
*0.5m high / 0.2m width plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 20 seconds
Sensitivity Range
4 sensitivity ranges for 0.1m² n-Heptane pan fire from 15m to 65m
Field of View
Horizontal 90°, Vertical 90°
Built-in-Test
Manual (optionally Automatic)
Temperature Range
Operating/Storage: -40°C to 75°C
Humidity
Up to 95% non-condensing
Operating Voltage
24VDC norminal (17-31VDC)
Power Consumption
Standby: max. 35mA, Alarm: max. 75mA
Cable Entry
1 x M20 (ISO)
Wiring
AWG 16-26 (Str 1.5mm² to 0.13mm²)
Electromagnetic Compatibility
EMI/RFI protected to EN61000 series
Electrical Interface
The detector includes twelve(12) terminals with four(4) wiring options
Relays
Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC
Non-isolated “Source” configuration
0-20mA (stepped)
Fault:
Normal:
Alarm:
Materials
Polycarbonate Enclosure
0 +1mA
4mA±10%
20mA±10%
Bit Fault:
Warning:
Resistance
Loop:
2mA±10%
16mA±10%
Max. 800Ω
Heavy duty copper free aluminium (less than 1%) with bright grey
anodizing finish
Enclosure options - Stainless Steel 316L with electro polish finish
Mounting (Tilt Mount)
Stainless Steel
Heavy duty copper free aluminium (less than 1%) with grey epoxy
enamel finish
Options - Stainless Steel 316L with electro polish finish
Dimensions
Detector: 80 x 82 X 86
mm
Weight
Detector : 0.3kg (1.0kg
with cable gland /
1m-length cable / Tilt
Mount)
Water and Dust
IP66 per EN60529
EMI/RFI
CE Marking
Performance
EN54-10 (designed to
meet)
Detector: 83(d) x 126(l) mm
Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland /
1m-length
Detector (St. SUS316L): 2.0 kg
Tilt mount (aluminium/ St.): 0.3kg / 0.7kg
IP66 and IP67 per EN60529
ATEX Ex II 2 G
Exd IIC T6, -40°C to +75°C (DNV 09 ATEX 0000)
KFI (Korea)
EN54-10 (designed to meet)
27
Conventional Fire Alarm Systems /
Zeta Conventional Manual Call Points
(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)
The Zeta conventional manual call point has
a modern design and has been approved by
BSI to EN54 part 11. It is a resettable call
point that signals an alarm with a yellow flag
entering the window area and a red alarm LED.
There are two versions available; the ZT-CP2 call points
comes complete with a protective Perspex cover as
well as a “snaplatch” catch that needs to be broken off
before the call point cover can be lifted (this acts as a
deterrent to malicious activations and forms a Type B
call point). Alternatively the ZT-CP1 is supplied without
the Perspex cover & “snaplatch” and is single action or
Type A call point.
The recommended colour for these call points is red
however white is also available to meet architectural
requirements.
Features
BSI approved to EN54 part 11
Attractive design
28
Model
ZT-CP2
ZT-CP2/W
ZT-CP1
ZT-CP1/W
Part No.
43-300
43-314
43-301
43-317
Type
Type B
Element Type
Resettable
Alarm Activation
Break “snaplatch”, lift Perspex cover, press
element
Press element
Red
Type A
Colour
Red
Input Voltage
9-33V DC
White
Quiescent Current
0mA
Alarm Current
Typical 35mA (maximum 51mA)
Alarm Load
470 Ω resistor
Operating Temperature
-20°C to 50°C
Max Humidity
95% RH non-condensing
IP Rating
IP43
Size
111 x 100 x 67mm
105 x 100 x 58mm
Weight
198g
175g
White
Conventional Fire Alarm Systems /
Zeta Conventional Weatherproof Call Point
(ZT-CP2/WP)
The Zeta conventional weatherproof manual
call point is an IP65 rated call point which
complies with EN54 part 11. It is resettable
and signals an alarm with a yellow flag
entering the window area and a red alarm LED.
The call point comes complete with a protective Perspex
cover as well as a “snaplatch” catch that needs to be
broken off before the call point cover can be lifted (this
acts as a deterrent to malicious activations and forms a
Type B call point).
Features
Complies with EN54 part 11
Attractive design
Resettable element
Protective cover
Model
ZT-CP2/WP
Part No.
43-350
Type
Type B
Element Type
Resettable
Alarm Activation
Break “snaplatch”, lift Perspex cover, press element
Colour
Red
Input Voltage
9-33V DC
Quiescent Current
0mA
Alarm Current
Typical 35mA (maximum 51mA)
Alarm Load
470 Ω resistor
Operating Temperature
-20°C to 50°C
Max Humidity
95% RH non-condensing
IP Rating
IP65
Size
87 x 87 x 70mm
Weight
198g
29
Conventional Fire Alarm Systems /
Zeta Conventional Explosion Proof
Manual Call Point (ZT-BGU/WP/R & ZT-BGU/WP)
The Zeta conventional explosion proof manual
call point is manufactured from aluminium
with a built-in push button activator. The call
point is finished with red anti-corrosive epoxy
powder coating with 2 x 20mm cable entries.
This unit is equipped with a stainless steel
hammer and chain.
Two models are available; the ZT-BGU/WP/R with 470Ω
built-in resistor for connection to a standard fire alarm
system or the ZTBGU/WP for mains connection.
4 Holes - ø7
I
F
N
CASE O
FIRE
S
BR
E
AK
GL
105mm
2 Nos.0.75″ET
30
Hammer
S
185mm
A
Chain
Model
ZT-BGU/WP/R
ZT-BGU/WP
Part No.
43-300/WP
43-305/WP
Contact Rating
10 Amp
Voltage Rating
500V AV
Build-in Resistor
470Ω
IP Rating
IP65
Earthling
2No M6 eternal & 1No M5 internal
Size
TBC
Weight
1.5kg
N/A
Conventional Fire Alarm Systems /
Miditone Conventional Electronic Sounder
(ZMDD/8R & ZMDD/8W)
The Miditone sounder is a small, high output
conventional sounder which designed to meet
the requirements of EN54 part 3 and is CE
marked.
The sounder is a compact unit that fits a standard
European back box and can be either surface or flush
mounted. It has a choice of 8 tone patterns, selectable
by an internal dip switch and a sound output of 95dB @
1m with volume control.
It is available in red or white to meet architectural
requirements.
Features
Complies to EN54 part 3
95dB @ 1m sound output
8 Tone patterns
Flush or surface fixing
Model
ZMDD/8R
ZMDD/8W
Part No.
42-040
42-040A
Sound Output
See current consumption table
Colour
Red
Operating Voltage
9-30V DC
Quiescent Current
0mA
Alarm Current @ 24V
See current consumption table
Operating Temperature
-10°C to 50°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH Non Condensing
IP Rating
IP43
Size (with Back Box)
85 x 85 x 35mm (85 x 85 x 67mm)
Weight (with Back Box)
100g (150g)
White
DIL Switch Settings (SW4 N/A)
1
2
3
Tone Description
dB Level
Current (mA)
Off
Off
Off
Sweep Negative 1200- 500 Hz In 1 Second
97 (+/- 2dB)
21
On
Off
Off
Alternating 554 and 440Hz 0.5s Each
95 (+/- 2dB)
17
Off
On
Off
Continuous 660Hz
96 (+/- 2dB)
22
On
On
Off
Alternating 554Hz @ 0.1s/440Hz @ 0.4s
94 (+/- 2dB)
17
Off
Off
On
Intermittent 970Hz @ 0.5s On/Off
93 (+/- 2dB)
8-24
On
Off
On
Continuous 970Hz
95 (+/- 2dB)
25.5
Off
On
On
Sweep Positive 800-970Hz
99 (+/- 2dB)
25
On
On
On
Alternating 800 and 970Hz @ 0.25s Each
100 (+/- 2dB)
25
31
Conventional Fire Alarm Systems /
Miditone Conventional Combined Electronic
Sounder & Flasher (ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)
The Miditone combined sounder & flasher is a small, high
output conventional sounder & flasher which is designed
to meet the requirements of EN54 part 3 and is CE
marked.
The device is a compact unit that fits a standard
European back box and can be either surface or flush
mounted. It has a choice of 8 tone patterns, selectable
by an internal dip switch and a sound output of 95dB
@ 1m with volume control. This is an ideal solution to
upgrade an existing sounder to a combined sounder &
flasher.
It is available with either a red, amber, blue, clear or
green lens to meet architectural requirements.
Features
Complies to EN54 part 3
95dB @ 1m sound output
8 tone patterns
Flush or surface fixing
Model
ZMDF/8R
ZMDF/8A
ZMDF/8B
ZMDF/8C
ZMDF/8G
Part No.
42-024
42-024A
42-024B
42-02C
42-024G
Sound Output
See current consumption table
Lens Colour
Red
Blue
Clear
Green
Operating Voltage
17-30V DC
Quiescent Current
0mA
Alarm Current @ 24V
See current consumption table
Operating Temperature
-10°C to 50°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH non condensing
IP Rating
IP43
Size (with Back Box)
85 x 85 x 35mm (85 x 85 x 67mm)
Weight (with Back Box)
112g (162g)
Amber
DIL Switch Settings (SW4 N/A)
32
1
2
3
Tone Description
dB LEVEL
CURRENT (mA)
Off
Off
Off
Sweep Negative 1200- 500 Hz In 1 Second
102 (+/- 2dB)
35
On
Off
Off
Alternating 554 and 440Hz 0.5s Each
100 (+/- 2dB)
27
Off
On
Off
Continuous 660Hz
100 (+/- 2dB)
33
On
On
Off
Alternating 554Hz @ 0.1s/440Hz @ 0.4s
98 (+/- 2dB)
26
Off
Off
On
Intermittent 970Hz @ 0.5s On/Off
93 (+/- 2dB)
13 - 35
On
Off
On
Continuous 970Hz
103 (+/- 2dB)
37
Off
On
On
Sweep Positive 800-970Hz
103 (+/- 2dB)
45
On
On
On
Alternating 800 and 970Hz @ 0.25s Each
103 (+/- 2dB)
42
Conventional Fire Alarm Systems /
Securetone Conventional Electronic Sounder
(ZST/8R & ZST/8W)
The Securetone sounder is designed to be
aesthetically pleasing and unobtrusive. It has
an elegant round design and fits to its supplied
mounting plate with a bayonet action to avoid
unsightly screws.
It has 8 selectable tones with a volume adjust screw to
set the required sound level.
This product is designed to meet the requirements of
EN54 part 3 and is CE marked.
Features
85mm
8 selectable tones
Volume control
100mm
Model
ZST/8R
ZST/8W
Part No.
42-004
42-004A
Sound Output
100dBA @ 1 metre
Colour
Red
Operating Voltage
10-30V DC
Quiescent Current
0mA
Alarm Current @ 24V
35mA MAX
Operating Temperature
-0°C to 50°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH Non Condensing
IP Rating
IP43
Size (including Plate)
100 x 100 x 75mm (100 x 100 x 85mm)
Weight (including Plate)
230g (260g)
White
33
Conventional Fire Alarm Systems /
Secure Light Xenon Flasher
(ZTSL6/R & ZTSL6/A)
The Secure Light Xenon Flasher range is
designed to provide a visual warning at alarm
condition.
Both red and amber versions are available with the
lenses constructed of high-Impact and heat resistant
ACRYREX. The case is made of high-impact resistant ABS
plastic.
Features
97mm
Available in Red & Amber
Fits onto a standard outlet box
100mm
34
Model
ZST/8R
ZST/8W
Part No.
42-035
42-038
Colour
Red
Amber
Flash Energy
3 Watt
Flash Frequency
60 times per minute
Operating Voltage
20-30V DC
Quiescent Current
0mA
Alarm Current @ 24V
100mA MAX
Operating Temperature
-30°C to 60°C
Minimum Continuous Temperature
0°C
Maximum Humidity
95% RH Non Condensing
IP Rating
IP54
Size
97 x 100mm
Weight (including Plate)
231g
Conventional Fire Alarm Systems /
Maxitone Conventional Sounder and
Combined Sounder & Flasher (ZMT/8R, ZMT/8W & ZMTF/8R)
The Maxitone sounder is an ideal alternative
to fire bells and for external use. It is housed
in an attractive horn comprises of flame
retardant ABS. Eight selectable tones and
volume control are featured to meet most
requirements.
The Maxitone is also available with transparent
polycarbonate front which will provide both visual and
audible alarm.
Features
120mm
High output
8 selectable tones
Volume control
126mm
107mm
Model
ZMT/8R
ZMT/8W
ZMTF/8R
Part No.
42-001
42-001A
42-032
Sound Output
See current consumption table
Colour
Red
Operating Voltage
17-30V DC
Quiescent Current
DIL SWITCH SETTINGS (SW4 N/A)
1
2
3
Tone Description
dB Level
Current
(mA)
Off
Off
Off
Sweep Negative 1200500 Hz In 1 Second
101 (+/2dB)
27
0mA
On
Off
Off
Alternating 554 and
440Hz 0.5s Each
98 (+/2dB)
20
Alarm Current @
24V
See current consumption table
Off
On
Off
Continuous 660Hz
101 (+/2dB)
27
Operating
Temperature
-20°C to 60°C
On
On
Off
Alternating 554Hz @
0.1s/440Hz @ 0.4s
98 (+/2dB)
19
Minimum
Continuous
Temperature
0°C
Off
Off
On
Intermittent 970Hz @
0.5s On/Off
98 (+/2dB)
20
On
Off
On
Continuous 970Hz
103 (+/2dB)
29.3
Off
On
On
Sweep Positive 800970Hz
103 (+/2dB)
38
On
On
On
Alternating 800 and
970Hz @ 0.25s Each
102 (+/2dB)
35
White
Maximum Humidity 95% RH non condensing
IP Rating
IP65
Size
124 x 130 x 100mm
Weight
357g
Red
35
Conventional Fire Alarm Systems /
Zeta Conventional Fire Alarm Bells
(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)
ZTB8B
ZTB6B
55mm
152mm
152mm
The Zeta motorised fire alarm bells combine
styling and functional efficiency. They
incorporate a low power rotary centrifugal
mechanism, which gives a high sound output
with low current consumption at 24V dc.
The bells are available in 2 sizes; 6″ (152mm) and 8″
(203mm). These sizes suit a wide variety of installations.
55mm
203mm
203mm
There is a 230V ac version of the 6″ bell, and a 24V dc
Weatherproof version of the 8″ bell.
Features
Low current
Universally accepted fire evacuation signal
36
Model
ZTB6B
ZTB8B/230
ZTB8B
ZTB8B/WP
Part No.
41-003
41-004
41-005
41-006
Supply Voltage
18-30V dc
200-250V AC
Diameter
6″ (152mm)
8″ (203mm)
Quiescent Current
25mA
28mA
Nominal Output @ 1M
95dB(A)
97dB(A)
Dimensions
152 x 152 x 55mm
203 x 203 x 55mm
Weight
860g
960g
18-30V dc
1700g
1800g
Conventional Fire Alarm Systems /
Zeta Flame Proof Siren
(ZTSR/EXD24 & ZTSR/EXD230)
The Zeta flame proof siren is an explosion
proof siren available in either 24V or 230V
versions.
An intrinsically safe circuit is housed in the main
chamber and it is duly wired up to terminal chamber
through sealed bushes. The horn unit is placed on the
main chamber cover and the output signals are taken
through sealed coils. Neoprene ‘0’ rings are provided for
the weather proof protection.
170mm
240mm
390mm
Model
ZTSR/EXD24
ZTSR EXD230
Part No.
42-100/24
42-105/230
Type Of Protection
Flame proof – Exd T6 IP 65
Area Classification
Zone 1 & 2
Gas Groups
Group I, II A, II B, II C
Apparatus
Standard
IS - 2148
CMRI Certificate
CMRI / TC / S / H388
Approvals
CCE, DGFAS
Materials
Cast Aluminium LM 6
Weight
5 Kg (approx.)
Size
170 (w) x 390 (h) x 240 (d) mm
IP Protection
IP 65 to IS 13947 / 93
Finish
Anti corrosive Epoxy – Powder Coated
Cable Entry
2 x ¾″ ET
Gasket
Neoprene
Hardware
Stainless Steel
Terminals
4 x 2.5 sq. mm (standard) 6 x 2.5 sq.
mm (for looping)
Voltage
24 V DC
Output Current
600mA Peak. Galvanically Isolated
Power Rating
18 Watts
Sound Output
106 db 900 Hz On & Off alternatively
at 1C/s
Earthing
External: 2 Nos.
- M6
230 V AC – 50 Hz
Internal: 1 No. M5
37
Conventional Fire Alarm Systems /
Zeta Flame Proof Gong Bell
(ZTB8B/EXD/24)
The Zeta flame proof gong bell is an explosion
proof gong bell with a terminal chamber.
A highly reliable electric circuit is housed inside to
control the frequency of the gong operating spindle.
The operating spindle and dish are made out of stainless
steel thereby ensuring a long life.
The electric circuits are connected to terminals in
the terminal chamber through nipple. The covers are
provided with neoprene gaskets for weatherproof
protection.
225mm
160mm
285mm
38
Model
ZTB8B/EXD
Part No.
41-075
Type Of Protection
Flame proof – Exd T6 IP 65
Area Classification
Zone 1 & 2
Apparatus Standard
IS - 2148
Material
Cast Aluminium LM 6
Weight
3 Kg (approx.)
Size
225(w) x 285(h) x 160(d) mm
IP Protection
IP 65 to IS 13947 / 93
Finish
Anti Corrosive Epoxy –
Powder coated
Cable Entry
1 X 3/4″ ET
Gasket
Neoprene
Hardware
Stainless steel
Voltage
24V DC or 110V / 230V AC –
50 Hz
Power Rating
12 Watt
Sound Output
112db
Terminals
4 x 4 mm²
Earthing
External: 2 Nos – M6 Internal:
1 No. - M5
Conventional Fire Alarm Systems /
Zeta Magnetic Door Holders
(ZT-DR24 & ZT-DR240)
ZT-BR
The Zeta magnetic door holders are designed
to retain a fire door open against the force of
its own closing device. In the event of a fire,
the door holder magnet can be turned off by
the fire alarm, allowing the door to shut.
The manual release button is changeable from the base
side to left or right. Cable entry is possible from rear
side by means of enclosed exits from the base side, left
or right.
An optional bracket is also available for floor or wall
mounting (ZT-BR).
Features
Tested according to EN1155
Model
ZT-DR24
ZT-DR240
Part No.
50-001
50-002
Rated Voltage
24V DC
230V AC
Rated Current
65mA
6mA
Switch Through Aux
Yes
No
Needs Back EMF Diode
Yes
No
Holding Force
400 N
Size (Main Unit)
110 x 85 x 38mm
Dimensions (Keeper Plate)
55 x 55 x 50mm
Weight (Main Unit)
404g
Weight (Keeper Plate)
153g
39
Conventional Fire Alarm Systems /
Zeta Duct Unit
(ZT-DU, ZT-DU/12 & ZT-DU/230)
The Zeta duct unit allows air in a ventilation
duct to be monitored for smoke via a smoke
detector mounted externally in a sealed
chamber. The unit comes supplied with 2
sampling probes (one in & one out) which are
mounted through the duct in the centre of the
air flow.
There are 3 versions of the unit
available which are as follows;
ZT-DU – enclosure supplied with a Fyreye common base
(FE-CB) allowing either a conventional or addressable
Fyreye detector to be connected and wired as part a
system.
ZT-DU/12 – enclosure c/w Fyeye base and relay board
with form C relay outputs for alarm and for fault which
requires 12V power supply.
Test Point
ZT-DU/230 - enclosure c/w Fyeye base and relay board
with form C relay outputs for alarm and for fault which
requires 230V power supply.
Duct Wall
Please note for reliable smoke detection the air speed in
the duct must be at least 2.5m/s.
Features
Direction of Airflow
Fire and Fault relays
Option for latching or non-latching
Manual reset (latching option)
Model
40
ZT-DU
ZT-DU/12
ZT-DU/230
Part No.
48-011A
48-011B
48-011C
Supply Voltage
N/A
12V
230V
Stand by current
N/A
46mA (From 12v supply)
Alarm current
N/A
86mA (From 12v supply)
Fault current
N/A
26mA (From 12v supply)
Indications
N/A
Power, fault & alarm
1 x fault relay & 1 x alarm relay
Outputs
N/A
Size
190 x 227 x 70mm
Weight
728g
989g
Conventional Fire Alarm Systems /
Premier Power Pack EN 54-4 Power Supply
with LCD Screen (PP-2/12, PP-5/17)
The Premier Power Pack Power supply uses an
innovative design that allows the engineer to
view system status through the on board LCD
screen. The screen can display several power
supply parameters, including output voltage,
and output current.
The power supply itself uses a 3 state charger which
uses BOOST, FLOAT, and PULSE modes, depending on the
state of the battery.
The PSU will disconnect the batteries under mains fail
condition, when the batteries are fully discharged to
prevent damage to the batteries.
The PSU will also monitor the battery for high internal
resistance, and signal a fault if that condition is
detected.
Screen Information
Model
System Normal Screen
Part No.
46-300
Input Voltage
170-264V AC 47-63 Hz
2 . 0 A Output Voltage
28V DC Nominal
E R R A T I N G 3 0 V S Y S T E M N O R M A L D C Screen 1 - Main Information
M A I N S
: O K B A T T S
: O K V ( A ) = 2 9 . 5 C U R R E N T 46-305
S Y S T E M S A L A R M P R E M I
PP-5/17
P O W E R - P A C K Z E T A PP-2/12
V ( B ) = 2 9 . 5 0 . 1 2 A M P S 28V DC Nominal
Power Rating
75W
150W
Efficiency
79%
86%
Total Power
Output
2.0 Amp
5.0 Amp
Power Supply
Outputs
2 Fused Outputs
2 Fused Outputs
Maximum Current
Per Output
0.625mA
2.0 Amps
B A T T E R Y I M P : 0 . 0 0 3 7 Battery Charging
Current
750mA
920mA
C H A R G E R V O L T : 2 5 . 4 5 V
Fault Relay Rating
SELV 1A
SELV 1A
B O O S T IP Rating
IP30
IP30
S T A T E : G O O D Size
375 x 335 x 128mm 375 x 403 x 128mm
Screen 2 - Battery Info
C H A R G E T Y P E : B A T T E R Y Screen 3 - Misc.
E A R T H : 2 . 4 4 7 V C H A R G E R B A D C I R C U I
B A T T E R Y L V L
G O O D
T : O K X . X R
Screen 4 - Software Information
S o f
t w a r e
P S U : 2 V 0 0 S o f
t w a r e
L C D : 2 V 0 0 41
Conventional Fire Alarm Systems /
Batteries
(Z20201, Z20301, Z20651, Z21251 & Z21751)
As fire alarm systems are life safety systems,
they must have a battery backup to ensure full
functionality is maintained in the event of a
mains failure. All parts of the system (including
auxiliary power supplies) must have a battery
backup.
All the batteries stocked are 12V meaning that 2
batteries are required for a 24V systems. The standard
capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and
17Ah.
It is important to choose the correct battery size for the
system load to give the required standby time (usually
24 or 48 hours).
Battery Calculation
To calculate the required battery backup, we use the equation:Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x ISBY)]
Where:
TALM = Maximum time in hours required for the alarm [½ hour is most common time]
IALM = Total Alarm Current in amps for all alarm devices connected to the alarm
circuits
TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72
hr]
ISBY = Quiescent current in amps of control panel in fault condition [because of mains
failure] PLUS all loop devices
42
Model
Z20201
Z20301
Z20651
Z21251
Z21751
Part No.
46-002
46-100
46-003
46-105
46-004
Type
Sealed lead acid
Voltage
12V DC
Capacity
2.2 Ah
3.2 Ah
7.2 Ah
12 Ah
17 Ah
Size
178 x 34 x 65mm
132 x 59 x 65mm
151 x 65 x 98mm
150 x 98 x 103mm
178 x 75 x 168mm
Weight
1.0kg
1.25kg
2.5kg
3.5kg
5.8kg
Available now from:
Tel: +44 (0) 1792 455 175
Fax: +44 (0) 1792 455 176
E-mail: info@zetaalarmsystems.com
Web: www.zetaalarmsystems.com
Detection House
72-78 Morfa Road
Swansea
SA1 2EN
United Kingdom
Download