064-EN01-SEB_VarioKMT eng. 22.02.2002 11:13 Uhr Seite 1 Technical Data Standard Optional Insulation and resistance measurement Integrated, automatic or manual Megger BM 222 or similar up to resistance and insulation testing, , 1000 V via external jacks phase - phase and phase - neutral, 6 measurements Rinsu 200 kΩ ... 20 MΩ, UTest 500, 1000 V 10 Ω ... 2 kΩ with 6 V Megger BM 222 via external jacks Vario KMT Test Van System HV-testing DC-testing 0 ... 8 kV, IN: 150 mA, Isc: 580 mA 8 ... 80 kV, IN: 2,8 mA, Isc: 270 mA Automatic cut-off after breakdown or overcurrent, hard copy print-out Sheath fault testing Mantelfehlerprüfung F 54 kV eff. 0.1 Hz Cosine square voltage, maximal testing capacity 5 µF Hard copy print-out 0 ... 5 kV/0 ... 10 kV/0 ... 15 kV/0 ... 20 kV, max. 580 mA Prelocation TDR measurement with integrated reflectometer Measurement methods: Direct, comparison, differential, average 3-phase, colour display HV-methods ARM Plus® Decay Plus® Impulse current 0 ... 4 / 8 / 16 / 32 kV 32-80 kV 0 ... 4 / 8 / 16 / 32 kV Burning Evaluation and databank Software Winkis 0 ... 8 kV, Ik 550 mA 0 ... 80 kV, Ik 290 mA DC 0 ... 5 / 10 / 15 / 20 kV, 30 A / Ik: 60 A Acoustic and distance method with surge generator 0 ... 4 / 8 / 16 / 32 kV, up to 1280 J in each range Adjustable surge rate 3 ... 30 s 2 kV, 1200 J up to 2560 J in each range Doubling of discharge sequences Audio frequency AF Unit 200 with power output 200 W Frequencies: 480 Hz / 1.09 kHz / 9.8 kHz, Impedance: 0.5 Ω ... 2k Ω , automatic or manual impedance matching Other frequencies upon request Pinpointing Sheath fault location 0 ... 5 kV / 0 ... 10 kV / 0 ... 15 kV / 0 ... 20 kV, Earth fault probe for pinpointing max. 580 mA Power supply and Weight Netz 230 V, 50 Hz (16 A connection)) 120 V, 60 Hz Power input 1.6 kVA Maximum power input via isolation transformer 3.6 kVA Battery power with 2.5 kVA battery operating time > 4 h Generator 3.5 kVA or 5 kVA Weight 600 kg, standard up to 1300 kg (depending on options) DIN ISO 9001 ® Product Range : Instruments and Test Vans for Fault Location in Power and Telecommunication Networks and for Leak Detection in Water and Sewage Networks • Cable and Pipe Locators • Seminars SebaKMT Sales • 96148 Baunach/Germany • Phone +49 - (0) 9544 - 68 0 • Fax +49 - (0) 9544 - 2273 E-mail : sales@sebakmt.com • Internet : www.sebakmt.com Technical data subject to change without notice. Vario KMT_GB_02/02_Mon_Ru Three Phase, Computer Aided Measuring System for Testing and Fault Location of Power Distribution Cables in Low and Medium Voltage Networks 064-EN01-SEB_VarioKMT eng. 22.02.2002 11:13 Uhr Seite 2 Vario KMT Three phase, computer aided measuring system for testing and fault location of power distribution cables in low and medium voltage networks. The Vario KMT System is a modern and mainly automatic testing tool for fault location in power cables including standard cable testing. System operation is menu-guided by the central Control Unit. It is user friendly even for infrequent users during on-call duty and supports operator skills. All test results, operation references and messages are displayed on the large TFT colour-display (10.4’’). Fault prelocation method ARM Plus® Effective cable testing, maintaining the cable integrity of PE, XLPE and paper insulated cables with the patented 0.1 Hz Cosine Square Voltage, can be optionally integrated. The integrated automatic insulation and resistance measurement permits a quick decision making on the practical prelocation method without activating further devices. All fault location functions are operated via the central Control Unit. The following prelocation methods are available J 3-phase TDR measurement J arc reflection method ARM Plus®‚ J surge pulse method J arc reflection method Decay Plus®‚ (up to 80 kV) All results are displayed on the screen of the Control Unit. The patented ARM Plus®‚ method permits a considerably improved and simplified prelocation of high resistance and intermitting faults. The integrated high-performance surge generator (up to 1280 J standard) enables a pre- and pinpoint location in low and medium voltage networks. The modular concept and numerous options, that can also be retrofitted, offer the possibility of satisfying every customer need. TDR measurement Vario KMT control room with additional PC for a databank Technical Features Operational Performance Features J J Menu driven user friendly software in a selection of languages J The display is concisely structured in all operating methods and shows information on the status as well as the adjusted parameter J Central Control Unit with integrated TDR for all system functions J Hard copy of all test results J Comprehensive safety features and functions J Optional connection to GIS platforms such as SICAD and Smallworld for visual fault location assistance J J J J J J Installation in a Mercedes Sprinter Intelligent control and monitoring of the system through modern field bus technology (LON) guarantees highest safety and reliability The system is coupled to the connection system by an SF6 gasinsulated, combined function and phase switch Compact high voltage source in 100 kHz – converter technology, hence less weight and dimensions Optimized prelocation method for long-distance ranges for longer cable runs by a patented ARM Plus® and Decay Plus® method< Low power consumption permits a power supply from mains (10 A) or from a genset. Optionally, even battery operation is possible To extend the possibilities of the TDR, options can be connected such as a mains surge switch, the test unit for overhead power lines, or a mains filter Optional doubling of the surge energy to 2560 J Testing Control Unit