GE Industrial Solutions 12kV-24kV New Compact Gas Insulated Ring Main Unit Leading the future of electrification GE GE is a diversified organization covering a myriad of market segments, including infrastructure, finance and media. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide. The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896. Industrial Solutions GE Industrial Solutions, a division of GE Energy Management, is a global leading provider in power distribution, offering a wide range of services and products which include medium and low voltage power distribution equipment and components, motor & control systems and service products that are safe, reliable and offer high performance. Honour 2010 World's Most Innovative Companies 2011 World’s Most Admired Companies 2009 World’s Most Respected Companies 2011 Best Global Brand 2008 World’s Most Respected Companies 2007 World’s Best R&D Companies 12kV-24kV New Compact Gas Insulated Ring Main Unit Leading the future of electrification Contents General Introduction About GE GE Industrial Solution Product Description Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06 Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08 Product Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08 Main Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 09 Advanced Manufacturing and Testing Process . . . . . . . . . . 10 Integrated solutions Basic Functional Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Common-gas Tank Ring Main Unit . . . . . . . . . . . . . . . . . . . . . 22 Switchgear Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Configurations Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Embedded SecoVac-R vacuum Circuit Breaker . . . . . . . . . . 30 Integrated Fuse Compartment . . . . . . . . . . . . . . . . . . . . . . . . . 30 SecoLBS Three Position Load Break Switch . . . . . . . . . . . . . 31 Cable Bushings With Integrated Sensors. . . . . . . . . . . . . . . . 31 Pressure Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Panel Padlock Device and Interlocks. . . . . . . . . . . . . . . . . . . . 32 Key Locking Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 LV Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Multilin 3 Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Typical Solutions & Installation Guide Outdoor Switching Substation . . . . . . . . . . . . . . . . . . . . . . . . . 48 SecoRMU Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 SecoRMU Control Circuit Principle Drawing . . . . . . . . . . . . . 52 SecoRMU Dimensions and Installation Foundation . . . . . . 55 SecoRMU Order Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit 12kV/17.5kV/24kV New Compact Gas Insulated Ring Main Unit Applications The traditional 12kV/17.5kV/24kV primary distribution network is mainly arranged as a Product Description radial network, or arranged as a combination of radial and tree network. Since many users are connected in "T" form to a power line, any maintenance or fault on the power line will make all the users connected suffering power off. A power supply system is not reliable enough. That's why today ring power supply systems are widely used in secondary distribution networks, thus helping to improve reliability. SecoRMU is such a kind of medium voltage switchgear used in ring power supply networks. With the features of completely sealed, modular design, flexible combination and extension, SecoRMU provides integrated solutions for most switching applications in urban-rural power cable upscale, power distribution network, wind farm, industry, O&G, underground installation, as well as municipal construction, commercial buildings, residential and other construction fields. 02 Product Description SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit + + + + 03 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Operating conditions Normal operating conditions The switchgears are fundamentally designed for the normal service conditions for indoor switchgears to IEC 60694. ●● Ambient temperature Maximum: +40°C Minimum: - 25°C ●● Humidity Max daily average relative humidity: 95% Product Description Max monthly average relative humidity: 90% ●● The maximum site altitude is 1000m above sea level ●● Seismic intensity: 9 degrees (IBC higher level) Special operating conditions In accordance with IEC60694, the manufacturer and end-user must agree on special operating conditions which deviate from operation under normal conditions. The manufacturer/supplier must be consulted in advance if special severe operating conditions are involved. SecoRMU is designed for use in the following applications: ●● Power Grid ●● Industrial Power Supply ●● Compact secondary substations ●● Wind power plants ●● Commercial buildings ●● Mining applications ●● Airports ●● Railway systems ●● Underground installations 04 Product Description Applications SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit 05 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Features & Benefits Modular, Compact, High performance SecoRMU gas insulated ring main unit is a compact, modularized, extendable or fixed gas insulated ring main unit with the primary conductive system sealed in a stainless SF6 gas tank, providing customers a safe, reliable, high-performance and maintenance-free product. Small and Compact Product Description SecoRMU uses a vacuum circuit breaker and adopts SF6 gas as the insulated medium in the gas tank. SF6 has strong electronegativity and excellent dielectric insulating performance. Its insulating strength is about 2-3 times the strenght of air in an uniform electric field. The excellent insulating performance of SF6 gas Maintaince free helps SecoRMU to realize its small and compact structure, as well as safety and reliability. Fully Modular Design/Extendable The basic functional module units K, T, V, C have uniform dimensions: 350×800×1380mm (width×depth×height). Convenient for system design, flexible replacement and upgrading. Each unit can extend to the left or right freely. Specially designed busbar connectors make the combination and extension of SecoRMU switchgear simple, safe and reliable. The big cable compartment also ensures a convenient cable installation and connection. 06 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Safe and Reliable Both the gas tank and the cable compartment are internal arc classified (20kA/1s), in order to ensure maximum personal safety. Three position switch for natural Advanced and Integrated Solutions SecoRMU is environment independent Adopting international advanced design, because its primary conductive system manufacturing and testing process, is fully sealed in the SF6 gas tank and will SecoRMU series ring main units have not be influenced by the outside world. simple structures, flexible operations and Its sealing is systematically checked by reliable interlocks. automatic helium leakage detection With the advanced sensor technology process at the factory, ensuring less than and up-to-date microcomputer 0.1% annual leakage rate. The gas tank protection relay, SecoRMU provides passed water immersed testing, reaching integrated solutions to meet different user IP67 protection grade. requirements.. Besides, SecoRMU realizes no clearance splicing for installing an extension, independent of the impact of dew, dust, salt fog, small animals, chemical substances, etc. Therefore, SecoRMU is free of maintenance and can be used under various severe operating conditions. Reliable Environment Independent/Very Low Maintenance Product Description interlocking. 07 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Standards Product Description SecoRMU is manufactured and tested in accordance with the latest version of: IEC62271-200 High-voltage switchgear and controlgear – Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52 kV IEC60265-1 High-voltage switches – Part1: Switches for rated voltages above 1 kV and less than 52 kV IEC62271-100 High-voltage switchgear and controlgear – Part 100: High-voltage alternating current circuit-breakers IEC62271-105 High-voltage switchgear and controlgear – Part 105: Alternating current switch-fuse combinations IEC60282-1 High-voltage Fuses –Part 1 Current limiting fuses IEC62271-102 High-voltage switchgear and controlgear – Part 102: Alternating current disconnectors and earthing switches IEC62271-1 The common specifications for high-voltage switchgear and controlgear standards IEC376-1971 Specification and acceptance of new Sulfur Hexafluoride IEC 60529 Degrees of protection provided by enclosures (IP code) IEC 60694 Common specifications for high-voltage switchgear and controlgear standards IBC-2012 International Building Code Product Type SER - □ - □ / □ □ □ Cable's entrance or exit mode L: left entrance exit R: right entrance exit LR: both sides entrance exit NA: non entrance exit Extension mode I: left extendable ID: both sides extendable D: right extendable NA: Non-extendable Rated current 630: 630A rated current Rated voltage 12: 12kV rated voltage 17: 17.5kV rated voltage 24: 24kV rated voltage Type of ring main unit K: load switch unit T: load switch-fuse combined unit V: vacuum circuit-breaker unit B: bus tie unit C1/C2: bus bar lift unit* M: measurement unit* VT: VT unit* P: Power supply unit (Common-tank ring main unit is combined freely by individual module units. For example, KT denotes a two-unit common-tank ring main unit made of one load switch unit and one load switch-fuse combined unit.) Product type For example: SER-V-12/630ID is a vacuum circuit-breaker unit with 12kV rated voltage and 630A rated current, both sides extendable . SER-KKT-12/630 is a three-unit common-tank ring main unit, made of two load switch units and one load switch-fuse combined unit, with 12kV rated voltage and 630A rated current, not extendable. *Note: C1/M/VT Air insulated C2 SF6 gas insulated 08 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Main Technical Data Unit Load Break Switch Unit Switch-fuse Unit Vacuum Circuit-breaker Unit Rated Voltage kV 12/17.5/24 12/17.5/24 12/17.5/24 Rated Current A 630 (1)* 630 Rated Frequency Hz 50 /60 50/60 50/60 Rated power Freq withstand voltage (1 min) kV 28/50/50 28/50/50 28/50/50 Rated lightening impulse withstand voltage (peak) kV 75/125/125 75/125/125 75/125/125 kA (peak) 52 82 52 - 20kA-3s 25kA-1s - 20kA-3s 25kA-1s kA - 31.5 20 kA (peak) 52 65 - 52 65 Operating Sequence - - - O-0.3s-CO-180s-CO O-0.3s-CO-15s-CO Electrical Endurance Capability class - E2 for load switch E2 for load switch E2 for breaker Transfer Current A - 1400 - Rated mainly active load-breaking current A 630 (1)* - Rated closed-loop breaking current A 630 - - Rated cable-charging breaking current A 16 - 31.5 Rated earth fault breaking current A 10 - - Rated cable- and line-charging breaking current under earth fault conditions A 45 - - Mechanical Endurance times 5000 5000 10000 Dimension (W×D×H) mm 350×800×1380 350×800×1380 350×800×1380 kg 160 180 200 Item Rated short-circuit making current Rated short time withstand current (main circuit) Rated short-circuit breaking current Peak withstand current for main circuit Weight Internal arc degree IP Degree Cable compartment 20kA 1s Gas tank 20kA 1s Enclosure IP3X Gas tank IP67 SF6 Gas pressure at 20℃ 0. 03MPa-relative SF6 Gas Annual Leakage Rate <0.1% Thickness of stainless steel gas tank 3.0mm Electric operation control voltage Product Description 12/17.5/24kV SecoRMU Rating and electrical performance 24/48/110/220V DC 110/220V AC (1)* Depending on the current rating of the fuse-link. Please refer to transformer-fuse selection table in page 34. 09 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Product Description Advanced Manufacturing and Testing Process TRUMPF CNC laser cutting/punching center NC HEDRICH vacuum resin mixture/pressure molding system The laser beam cutting precision of The epoxy resin insulating components, German TRUMPF CNC laser cutting/ such as SecoVac-R vacuum circuit-breaker, punching center is ±0.05mm, while the fuse compartment, cable connector, targeting precision of this machine is extension bushing, insulator, etc., are 0.02mm, ensuring the splicing clearance produced by Germany NC HEDRICH of the gas tank 0.1mm. vacuum resin mixture/pressure molding system, ensuring perfect insulation performance. The partial discharge is less than 0.5pC. TRUMPF three-dimensional fiveaxis CNC laser welding system with automatic helium protection The laser has the features of high accuracy and energy concentrating. The laser welding process can weld the stainless steel in a split second without using any solder, which is equal to plate bending. It usually makes deep and complete welding, ensuring the reliability and quality identity of the gas tank. The annual leakage rate is less than 0.1%. 10 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Product Description SEILER automatic helium leakage detection equipment German SEILER automatic helium leakage detection equipment guarantees sensitivity, accuracy and efficiency of the gas tank leakage detection, which ensures a leakage rate less than 0.1% per year and a service life of over 30 years. NC VOGEL mixture of silicone rubber/pressure molding system Power Diagnosix fully shielded partial discharge testing laboratory The silicon rubber insulation components, such as busbar connector, cable bushing, GE has a top-class fully shielded partial end plug etc., are produced by the Swiss discharge testing laboratory, with NC VOGEL mixture of silicone rubber/ advanced German Power Diagnosix partial pressure molding system. discharge detector. Partial discharge testing is performed to ensure the high quality of the product. 11 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Integrated solutions Integrated Solutions Basic functional modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 12 Common-gas Tank Ring Main Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Switchgear Extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Integrated Solutions Basic Functional Modules K Load break switch unit K Dimensions: Width: 350mm Depth: 800mm Height: 1380mm Function ●● Connect or disconnect the incoming/outgoing cable with the main busbar ●● Earthed three-phase cables ●● Making short circuit current Standard Configuration Optional Features ●● Three position load break and earthing switch ●● Left/right incoming or outgoing cable ●● Spring operating mechanism ●● Left/right extendable ●● Switch position indication for load break switch and earthing ●● Electrical operating mechanism switch DC24/48/110/220V, AC110/220V ●● Potential indicator ●● Short circuit and earth fault indicator ●● SF6 gas pressure Gauge ●● Ring CT and ampere meter ●● 630A busbar ●● Arrester ●● Earthing bar ●● Double cable plug ●● Interlock between the earthing switch and the door/operation ●● Auxiliary contacts for load break switch position shaft ●● Cable bushings with integrated sensors ●● Panel padlock device Integrated Solutions Weight: 186kg 3NO+3NC ●● Auxiliary contacts for earthing switch position 2NO+2NC 13 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit T Switch-fuse unit T Dimensions: Width: 350mm Depth: 800mm Height: 1380mm Weight: 180kg Integrated Solutions Function ●● Control and protect 1600kVA and below distribution transformers at 24kV rated voltage ●● Control and protect 1000kVA and below distribution transformers at 10kV rated voltage Standard Configuration Optional Features ●● Three position switch-fuse disconnector with upstream ●● Left/right incoming or outgoing cable earthing switch mechanically linked with downstream earthing ●● Left/right extendable switch ●● Electrical operating mechanism ●● Spring operating mechanism ●● Switch position indication for switch-fuse disconnector and earthing switch DC24/48/110/220V, AC110/220V ●● Opening coil DC24/48/110/220V, AC110/220V ●● Fuse compartment ●● Short circuit and earth fault indicator ●● Potential indicator ●● Ring CT and ampere meter ●● SF6 gas pressure Gauge ●● Arrester ●● 630A busbar ●● Double cable plug ●● Earthing bar ●● Load break switch position auxiliary contacts ●● Interlock between the earthing switch and the door/operation shaft ●● Cable bushings with integrated sensors ●● Panel padlock device 3NO+3NC ●● Auxiliary contacts for earthing switch position 2NO+2NC ●● Auxiliary contacts for fuse blown 1NO ●● Fuse (Please refer to transformer-fuse selection table on page 34) 14 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit V Vacuum circuit-breaker unit V Dimensions: Width: 350mm Depth: 800mm Height: 1380mm Weight: 227kg Scheme 1 Scheme 2 ●● Used for circuit protection, motor protection and transformer protection Standard Configuration Optional Features ●● Three position disconnector and earthing switch ●● Left/right incoming or outgoing cable ●● 630A vacuum circuit-breaker ●● Left/right extendable ●● Operating mechanism of the vacuum circuit-breaker ●● Electrical operating mechanism of vacuum circuit-breaker ●● Mechanical interlock and position indicator for vacuum circuit- breaker and three position disconnector and earthing switch ●● Potential indicator ●● SF6 gas pressure Gauge ●● 630A busbar DC24/48/110/220V, AC110/220V ●● Closing coil DC24/48/110/220V, AC110/220V ●● Opening coil DC24/48/110/220V, AC110/220V ●● Earthing bar ●● Ring CT and ampere meter ●● Interlock between the earthing switch and the door/operation ●● Arrester shaft ●● Operating mechanism interlock between vacuum circuit breaker and disconnector ●● Cable bushings with integrated sensors ●● Panel padlock device ●● Protection relay and protection CT Integrated Solutions Function ●● Double cable plug ●● Auxiliary contacts for vacuum circuit-breaker position 4NO+4NC ●● Auxiliary contacts for disconnector position 2NO+2NC ●● Auxiliary contacts for earthing switch position 1NO+1NC 15 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit B Bus tie unit B Dimensions: Width: 350mm Depth: 800mm Height: 1380mm Weight: 160kg Integrated Solutions Function ●● Used for busbar coupling Standard Configuration Optional Features ●● Two position load break switch ●● Left/right incoming or outgoing cable ●● Operating mechanism ●● Left/right extendable ●● Switch position indicator ●● Electrical operating mechanism of load break switch ●● SF6 gas pressure Gauge ●● 630A busbar ●● Panel padlock device 16 DC24/48/110/220V, AC110/220V ●● Auxiliary contacts for load break switch position 3NO+3NC SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit C Bus lifting unit C Dimensions: Width: 350mm Depth: 800mm Height: 1380mm Weight: 100kg ●● Used for connecting with incoming/outgoing cables Standard Configuration Optional Features ●● 630A busbar ●● C1 Air insulated adopted ●● Potential indicator ●● C2 SF6 gas insulated adopted Integrated Solutions Function ●● Earthing bar 17 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit M Metering unit M Dimensions: 12kV 24kV Width: 600mm Width: 800mm Depth: 800mm Depth: 1000mm Height: 1380mm Height: 1380mm Weight: 480kg Weight: 550kg Integrated Solutions Function 18 ●● Air insulated, used for electric power measurement Standard Configuration Optional Features ●● 630A busbar ●● Two current transformers ●● Three current transformers ●● Two potential transformers ●● Three potential transformers ●● Arrester ●● Fuse for protecting VT ●● A watt-hour meter ●● Potential indicator ●● A var-hour meter SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit VC Vacuum circuit-breaker & Bus tie unit + + + + + + VC Dimensions: M 12kV 24kV* Width: 700mm Width: 830mm Depth: 800mm Depth: 800mm Height: 1380mm Height: 1380mm Weight: 300kg Weight: 350kg * Pls. contact GE for further information. ●● Used as a tie breaker Standard Configuration Optional Features ●● Three position disconnector and earthing switch ●● Electrical operating mechanism of vacuum circuit-breaker ●● 630A vacuum circuit-breaker ●● Operating mechanism of the vacuum circuit-breaker ●● Mechanical interlock and position indicator for vacuum circuit- breaker and three position disconnector and earthing switch ●● Potential indicator DC24/48/110/220V, AC110/220V ●● Closing coil DC24/48/110/220V, AC110/220V ●● Opening coil DC24/48/110/220V, AC110/220V ●● SF6 gas pressure Gauge ●● Ring CT and ampere meter ●● 630A busbar ●● Auxiliary contacts for disconnector position ●● Earthing bar ●● Interlock between the earthing switch and the door/operation shaft ●● Operating mechanism interlock between vacuum circuit- Integrated Solutions Function 2NO+2NC ●● Auxiliary contacts for earthing switch position 1NO+1NC ●● Cable plugs used for busbar coupling breaker and disconnector ●● Cable bushings with integrated sensors ●● Panel padlock device ●● Relay and protection CT 19 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit VT VT unit VT Dimensions: 12kV 24kV Width: 600mm Width: 800mm Depth: 800mm Depth: 1000mm Height: 1380mm Height: 1380mm Weight: 280kg Weight: 330kg Integrated Solutions Function ●● Monitor busbar voltage, providing voltage-lost signal Standard Configuration Optional Features ●● 630A busbar ●● Three potential transformers ●● Two potential transformers ●● Disconnector ●● Fuse for protecting VT ●● Arrester ●● A voltmeter ●● Potential indicator 20 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit KPT Disconnector & VT unit Kpt Dimensions: 12kV Width: 480/600mm Depth: 800mm Height: 1380mm Weight: 300kg V V ●● Monitor busbar voltage, providing voltage-lost signal Standard Configuration Optional Features ●● Three position disconnector and earthing switch ●● Left/right incoming or outgoing cable ●● Spring operating mechanism ●● Electrical operating mechanism ●● Position indicator of disconnector and earthing switch DC24/48/110/220V, AC110/220V ●● Potential indicator ●● Short circuit and earth fault indicator ●● SF6 gas pressure Gauge ●● Arrester ●● 630A busbar ●● VT cable connector ●● Earthing bar ●● Auxiliary contacts for disconnector position ●● Interlock between the earthing switch and the door/operation shaft ●● Cable bushings with integrated sensors ●● Panel padlock device Integrated Solutions Function 3NO+3NC ●● Three potential transformers ●● Auxiliary contacts for earthing switch position 2NO+2NC ●● 1 set of three-phase VT ●● Fuse for protecting VT ●● A voltmeter 21 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Common-gas Tank Ring Main Unit SecoRMU provides economical schemes for putting multi units into a common tank. One gas tank can accommodate up to 5 modules combined freely. Each unit is extendable and capable of splicing with other individual-gas tanks or common-gas tank units. KK Dimensions: Width: 700mm Depth: 800mm Height: 1380mm KT Dimensions: Integrated Solutions Width: 700mm Depth: 800mm Height: 1380mm C2K Dimensions: Width: 700mm Depth: 800mm Height: 1380mm C2T Dimensions: Width: 700mm Depth: 800mm Height: 1380mm 22 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit C2V Dimensions: Width: 700mm Depth: 800mm Height: 1380mm VV Dimensions: Depth: 800mm Height: 1380mm KKK Integrated Solutions Width: 700mm Dimensions: Width: 1050mm Depth: 800mm Depth: 1380mm KKT Dimensions: Width: 1050mm Depth: 800mm Depth: 1380mm 23 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Common-gas Tank Ring Main Unit KTK Dimensions: Width: 1050mm Depth: 800mm Height: 1380mm KTT Dimensions: Width: 1050mm Depth: 800mm Integrated Solutions Height: 1380mm KKKK Dimensions: Width: 1400mm Depth: 800mm Height: 1380mm KTTT Dimensions: Width: 1400mm Depth: 800mm Height: 1380mm 24 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit KKTT Dimensions: Width: 1400mm Depth: 800mm Height: 1380mm KTKT Dimensions: Width: 1400mm Depth: 800mm KKKKK Dimensions: Width: 1750mm Integrated Solutions Height: 1380mm Depth: 800mm Height: 1380mm KTTTK Dimensions: Width: 1750mm Depth: 800mm Height: 1380mm 25 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Common-gas Tank Ring Main Unit KTTTT Dimensions: Width: 1750mm Depth: 800mm Height: 1380mm KKKKT Dimensions: Width: 1750mm Integrated Solutions Depth: 800mm Height: 1380mm KKKTT Dimensions: Width: 1750mm Depth: 800mm Height: 1380mm KKTTT Dimensions: Width: 1750mm Depth: 800mm Height: 1380mm 26 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Switchgear Extension The extendable feature allows customers to build functional module units into various solutions to suit their requirements. With specially designed busbar connectors, SecoRMU realizes no clearance splicing. No dimension is needed for installing an extension, which protects the product against the harmful effects of dust, water, solid foreign objects etc., realizing high reliability. SecoRMU can be extended on site without handling SF6 gas, or requiring any special floor preparation, realizing simple installation. Besides, SecoRMU can protect operators from the risk of touching external live parts, ensuring safe operation. Wrong connection Integrated Solutions between phases is impossible to happen. 27 Configurations SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Configurations Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Embedded SecoVac-R vacuum Circuit-breaker . . . . . . . . . . . . . . . 30 Integrated Fuse Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 SecoLBS Three Position Load Break Switch . . . . . . . . . . . . . . . . . . . 31 Cable Bushings With Integrated Sensors . . . . . . . . . . . . . . . . . . . . . 31 Pressure relief device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Panel Padlock Device and Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . 32 Key Locking Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 LV compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 28 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Configurations Overview SecoRMU is a new compact modular switchgear, with a high-quality stainless steel gas tank containing all live parts and switching functions. The gas tank is manufactured through a laser cutting and laser welding process. The entire series includes individualgas tank solution and common-gas tank solution. Each unit is extendable and uses a Pressure Gauge Metering Compartment Gas Tank Busbar Extension Configurations busbar connector for switchgear extension. Fuse Compartment Operating Mechanism Enclosure Pressure Relief Device Cable Bushing 29 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit VCB Configurations Operating Mechanism of VCB Embedded SecoVac-R Vacuum Circuit-breaker Bus Extension Mature embedded SecoVac Series VCB Gas Tank technology Operating Mechanism ●● Three-phase in one module. Horizontal arrangement ●● Most compact V panel. The width of V Fuse Compartment panel is 350mm, which is exactly the same as K, T, C modules ●● HEDRICH equipment and high quality epoxy resin ensure perfect insulation performance ●● Class E2/M2/C2. Mechanical endurance 10,000 times Integrated Fuse Compartment Cast three-phase entrance/exit cable connectors and fuse compartment together. The fuse compartment is triangular arranged inside the gas tank and independent of environmental influence. 30 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Load Break Switch SecoLBS Three Position Load Break Switch Pressure Relief Device The three position load break switch uses with a pressure relief device. When an SF6 gas as the arc extinguishing medium. internal arc fault occurs, the pressure relief ●● A moving contact assembly with 3 device will open, allowing the pressurized Each gas tank of SecoRMU is equipped stable positions (closed, open and gas flowing to the pressure relief channel earthed), makes natural interlocking. at the bottom of the gas tank, to release Such design makes simultaneous the pressure. The rated bursting point is 2 closing of the switch or circuit-breaker times the standard atmospheric pressure. Configurations Operating Mechanism of LBS and the earthing switch impossible ●● The earthing switch has a short circuit making capacity, as required by the standards ●● With clear mechanical position indicator ●● Class M2/E3. Mechanical endurance Cable Bushings With Integrated Sensors 5000 times An integrated sensor inside the cable bushing, provides a voltage signal to the potential indicator. The indicator can display whether the cable is live or not. 31 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Panel Padlock Device and Interlocks There is a main circuit schematic diagram and mechanical position indicator on each unit’s front cover. The highly reliable indicator connects with the main spindle without any indermediate mechanism. All operating mechanisms are situated outside the SF6 gas tank and behind the front cover. That way, it’s easy to access the operating mechanisms if retrofit or service should be required. Configurations Padlock 2 1 Both Load Break Switch and Earthing Switch are Locked Earthing Switch Locked Push the interlock selector to the left switch is in closed position. In the VCB panel, it is only possible to or right, to expose the corresponding When interlocking is fitted, the cable lever the interlock to permit operating the operation holes to operate the earthing cabinet can only be accessed when the disconnector or the earthing switch when switch or the load break switch/ earthing switch is in the closed position. the VCB is in open position. disconnector. So is the fuse compartment cover. Carry out the operation through the It’s impossible to bring the load break interlock selector to prevent mis-operation. switch or the disconnector in open It’s impossible to operate the load break position if the cable compartment cover is switch/disconnector when the earthing not mounted properly switch is in earthed position or operate the earthing switch when the load break 32 Load Break Switch Locked SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Key Locking Applications Medium-voltage locking system between panels or between panels and upstream or downstream equipment are widely used in both IEC and GB market. The purpose is to prohibit incorrect operation and bring users the following benefits: Locking systems guarantee: ●● Safety of personnel ●● Safety of equipment ●● Continuity of operation SecoRMU can achieve the following applications by use of Castell, Fortress and China local brand Lock. Application 1: SecoRMU in semi-crossed locking Prohibits the closing of the earthing switch of the downstream switchgear unless the upstream switchgear is locked in the open 1 key for 2 lock Key 1 Configurations position. Application 2: SecoRMU in crossed locking Prohibits the closing of the earthing switch unless the upstream and downstream switchgear is locked in the open position. Lock 3 Lock 1 Lock 4 Key 1 Key 2 Lock 2 2 key for 2 lock (Key 1 for Lock 1&2, key 2 for Lock 3&4) 33 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Key Locking Applications Application 3: SecoRMU in interlocking between two incoming feeders Prohibits the closing of the earthing switch unless the upstream and downstream switchgear is locked in the open position. 1 key for 2 lock Configurations Key 1 Application 4: SecoRMU in interlocking of two incoming feeders and a bus tie Prohibits the closing the other two switchgears unless one of the switchgear is locked in the open position. Lock 1 Lock 2 Key 1 Key 1 2 key for 3 lock 34 Lock 3 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Application 5: SecoRMU in interlocking on transformer feeders Prohibits access to the transformer unless the earthing switch has been locked in the closed position. Configurations Lock 2 Lock 1 Key 1 1 key for 2 lock Lock 2 on the Transformer Access Door Application 6: T panel/ low voltage side Prohibits closing of the earthing switch and access to any protection unit fuses unless the main LV circuit breaker has been locked in the open position or disconnected position. Lock 2 Lock 1 Key 1 35 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Key Locking Applications Application 7: SecoRMU in Anti-parelling cross interlocking Prohibits the closing the switchgears at the same time and also prohibits the access to the alive cable between the RMUs. (This is one of the typical RMU application in the Australia mining industry). Key 1 Key X Key 3 Key X Key 4 Configurations Key 2 Key 1 Key 2 Key X Key 3 Key 4 Key X Legend Unlock, free key Locked, no key *Note 1. Key lock is not available on the load break switch side of T panel 2. Key lock retrofit on site is not recommended and not possible for every case. Please contact GE for further information. 36 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit LV Compartment Dimensions: n×350(w)*380(D)*400(H) mm The LV compartment on top of the switchgear can be equipped with a condensation monitor, a remote terminal Configurations unit, an I/O terminal module, additional protection relays, communication devices etc. LV Compartment 37 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Protection Transformer/Line Protection SecoRMU offers two methods for transformer protection: Protected by a Switch-fuse Combination The striker pin of the fused holder can activate the spring charging mechanism of the load break switch when a fault occurs. The load break switch will trip immediately and the current will be broken by the fuse. Fuse Replacement Configurations According to IEC recommendations, when a fuse has blown, all three fuses should be replaced. The dimension of the fuse-link: Length after triggering 26 45 Φ76 33 33 442 * If fuse diameter < 76mm, a pilot sleeve must be on the no-striker end of the fuse before fuse installation. Recommended Fuse Ratings for Transformer ( Normal operating with no overload, -25℃ <Ø< 40℃ ) Service voltage Un (kV) 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 Rated voltage range of fuse-link 10/12kV 10 16 20 20 25 31.5 40 40 50 63 80 100 * * 6/12KV 15/17.5kV 4 10 16 16 20 20 25 31.5 40 40 50 63 * * 20/24kV 4 10 10 16 16 20 20 25 31.5 40 40 50 63 80 Transformer output (kVA) 1)* Please contact GE for further information. 2)Table above is based on EFEN type fuses. If other brand fuse is required, please contact GE. 38 10/24KV SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SEG WIC1 Ring CT When using a vacuum circuit-breaker for WIC1 is a CT-powered protection relay transformer and line protection, WIC1 with minimal space requirement which CT-powered protection relay of SEG complies with the highest demands for a (supplied as an option) can be used to digital protection device. It also has simple provide protection against short circuit, but safe wiring, and high electromagnetic overcurrent and grounding fault. interference immunity. Configurations Protected by VCB in Combination with a Relay Product description In the WIC1 the following protection functions are included: ●● 3 phase definite time overcurrent and short circuit protection with variable tripping times (ANSI 50/51) ●● 3 phase overcurrent protection with selectable inverse time characteristics and definite time short circuit current element (ANSI 50/51) ●● Definite time earth overcurrent protection by internal calculation (ANSI 50N/51N) 39 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit User Interface The adjustment of WIC1 protection functions is done via DIP switches. Each protective parameter is binary coded set by 4 DIP switches. Therefore, there are 16 incorporations available in total. It is also possible to read out the stored fault values and setting values of the WIC1. The interface can be found at the left of the relay and also above the DIP switch block. Configurations Switch block; Switch No. 40 Setting parameter 1; 1-4 IS: Rated CT current 1; 5-8 Choice of characteristics 2; 1-4 I>: Pick-up value of the definite time overcurrent element or startvalue of the inverse time characteristic. 2; 5–8 tI>: Tripping time of the definite time overcurrent element or factor 'a' of the inverse time characteristic 3; 1-4 I>>: Pick-up value of the short circuit element 3; 5-8 tI>>: Tripping time of the short circuit element 4; 1-4 Ie>: Pick-up value of the definite time earth overcurrent element 4; 5-8 tIe>: Tripping time of the definite time earth overcurrent element. If there is no earth fault function, the DIP switch block 4 is not incorporated. SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit CTs for the WIC1 There are six different transformation ratio CTs for the protection system WIC1, depending on the rated primary current. OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON DIP1-3 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON DIP-4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON HEX-Schalter Is 0 1 2 3 4 5 6 7 8 9 A B C D E F WIC1-W1 8 9 10 11 12 13 14 15 16 17 18 20 22 24 26 28 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 WIC1-W2 16 18 20 22 24 26 28 30 32 34 36 40 44 48 52 56 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 WIC1-W3 32 36 40 44 48 52 56 60 64 68 72 80 88 96 104 112 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 WIC1-W4 64 72 80 88 96 104 112 120 128 136 144 160 176 192 208 224 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 WIC1-W5 128 144 160 176 192 208 224 240 256 272 288 320 352 384 416 448 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 WIC1-W6 256 288 320 352 384 416 448 480 512 544 576 640 704 768 832 896 Teststrom CD 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.80 0.88 0.96 1.04 1.12 In the WIC1, the earth current is calculated and cannot be measured. Zero-sequence CT is not necessary to install. Transformation Ratio 25:1 50:1 100:1 200:1 400:1 800:1 Configurations DIP1-1 DIP1-2 41 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Measurement, Protection and Control For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/3Series.htm Multilin 3 Series Configurations Intuitive industrial and utility protective relay systems for feeders, motors and transformers Key benefits ●● Easy-to-use and cost effective protection and control for feeders, motors and transformers ●● Effortless draw-out construction eliminates requirements for test switches and reduces downtime ●● Environmental monitoring system to alarm on destructive operating conditions to enable preventative maintenance ●● Easy-to-use interface and set up in one simple step ●● Accelerated Life Cycle Tested to ensure reliability of relay operation under abnormal conditions ●● Advanced power system diagnostics to increase reliability through fault and disturbance recording capabilities ●● Arc Flash mitigation via zone intertripping, flex curves and multiple setting groups ●● Application flexibility with the use of programmable logic elements ●● Large backlit display with 40 characters for easy viewing of relay information and settings ●● Flexible communications with multiple ports & protocols to allow seamless integration into new and existing infrastructure ●● Easy access to information via multiple communication network options including USB, Serial, Fiber & Copper Ethernet ●● Reduced wiring with support for remote I/O ●● Reduced setup and configuration time with the Simplified Motor Setup screen ●● Powerful Security Audit Trail tool to increase security and minimize system risks by tracking setting changes Applications ●● Advanced protection, monitoring & control relays for feeders (Multilin 350), motors (Multilin 339) and transformers (Multilin 345) ●● Industrial feeders with enhanced breaker monitoring and diagnostics 42 ●● Distribution utility downstream breaker protection ●● Medium voltage utility feeders with advanced control features including, cold load pickup, auto reclose and multiple setting groups SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Features Easy-to-use Protection & control Drawout construction (for Multilin 350 Feeder Protection System) The Multilin 3 Series offers a complete ●● Phase, neutral and ground TOC and IOC drawout feature, eliminating the need for ●● Undervoltage, overvoltage, frequency rewiring after testing has been concluded. ●● Neutral/ground directional The withdrawable feature also eradicates ●● Negative sequence overcurrent the need to disconnect communication ●● ANSI, IAC, IEC, flex curves ●● Cable Thermal Model protection Overview cables, e.g. fiber, copper, RJ45, etc and helps retain the communication status ●● Breaker failure The Multilin 3 Series of protection relays even after a relay has been withdrawn ●● Cold load pick-up are highly functional, economical from its case. ●● Four-shot auto reclose protection relays for feeders, motors and ●● 8 digital inputs, 7 contact outputs transformers. By providing an economical ●● Two setting groups system for protection, control, monitoring ●● Event Recorder: 256 events with 1ms time stamping ●● Oscillography with 32 samples per cycle and digital states ●● IRIG-B clock synchronization ●● Relay & Asset Health Diagnostics ●● Security audit trail and metering, and with both local and Configurations Metering & monitoring remote user interfaces in one assembly, the Multilin 3 Series relays effectively eliminate the need for expensive discrete components. The Multilin 3 Series provides detailed diagnostic information allowing users to troubleshoot and minimize downtime. Detailed diagnostics are provided via the Advanced communications User interface and programming 256 1ms time stamped event recorder ●● 4x20 character LCD display and the 192 cycle Oscillography report Easy integration into new or existing ●● Control panel with 12 LED indicators sampled at 32 samples per cycle. infrastructure ●● Front USB and rear serial, Ethernet and The robust Multilin 3 Series streamlines With several Ethernet and serial port user work flow processes and simplifies options and a variety of communication engineering tasks such as configuration, protocols, the Multilin 3 Series provides GOOSE, ModBus™ RTU, ModBus™ wiring, testing, commissioning, and advanced and flexible communication TCP/IP, DNP 3.0, IEC 60870-5-104, IEC maintenance. This cost-effective relay selections, enabling seamless integration 60870-5-103 also offers enhanced features such as into new or existing applications. diagnostics, preventative maintenance, The Multilin 3 Series supports various device health reports and advanced industry standard protocols such as, IEC security features. 61850 & IEC 61850 GOOSE, Modbus RTU, Fiber ports ●● Multiple protocols - IEC 61850 & 61850 EnerVista™ software ●● An industry-leading suite of software tools that simplifies every aspect of working with Multilin devices Modbus TCP/IP, DNP3.0, IEC 60870-5-104 and IEC 60870-5-103. ●● Document and software archiving toolset to ensure reference material and device utilities are up-to-date 43 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Enhanced diagnostics EnerVistaTM Launchpad Security Preventative maintenance EnerVista™ Launchpad is a complete set of Security audit trail The Multilin 3 Series allows users to track powerful device setup and configuration tools The Multilin 3 Series monitors security relay exposure to extreme environmental that is included in the SR relays at no extra and reliability of asset protection. The conditions by monitoring and alarming charge. Multilin 3 Series protection devices at high temperatures. This data allows ●● Set up the Multilin 3 Series Relays - and any offer complete traceability of any users to proactively schedule regular other Multilin device - in minutes. Retrieve relay setting and command changes, maintenance work and upgrading and view oscillography and event data at allowing the user to quickly identify the click of a button changes made to the relay. activities. ●● Build an instant archive on any of the All relays utilize EnerVista setup TM software for communication, monitoring latest Multilin manuals, service advisories, and metering. Actual values, setpoints, application notes, specifications or status, trending and waveform capture firmware for your SR Relay ●● Automatic document and software version Configurations information can all be viewed via the software and can be used for updates via the internet and detailed e-mail troubleshooting. notification of new releases User Interface ●● SETPOINT GROUP 1, 2: These indicators are continuously on if the corresponding group provides settings for protection elements. TRIP: The indicator turns on when the relay detects a trip condition. Operates the trip relay to open the breaker. ALARM: While the relay detects an alarm condition, the indicator flashes. PICKUP: Indicator lights steady when any protection feature pickup threshold exceeded. ●● DISPLAY: 4 line text for easy viewing of key data. ●● LEDs: 10 LED indicators for quick diagnostics. ●● KEYPAD: Ten button keypad for access to device interrogation and change of settings. ●● FRONT PORT: An electrically isolated front USB communication port. Protection Features ANSI Device Numbers & Functions BUS BUS VT 52 79 TRIP 3 CLOSE 1 50N 2 51P 2 51N 1 CLP 1 50_2 1 50BF 49 1 1 59X 59_2 1 1 59N 81U 1 81O 2 2 METERING 1 79 50G/ 51G 51G 50G TRANSIENT RECORDER EVENT RECORDER 1 350 RELAY 44 27X 1 MONITORING 50P LOAD 59P 27P 1 2 Device Number 27P 27X 49 50P 50N 50G 50BF 50_2 51P 51G 51N 59P 59X 59N 59_2 67G 67N 79 81U 81O CLP Function Phase Undervoltage Auxiliary Undervoltage Thermal Model Phase Instantaneous Overcurrent Neutral Instantaneous Overcurrent Ground/Sensitive Ground Instantaneous Overcurrent Breaker Failure Negative Sequence Overcurrent Phase Timed Overcurrent Ground Timed Overcurrent Neutral Timed Overcurrent Phase Overvoltage Auxiliary Overvoltage Neutral Overvoltage Negative Sequence Overvoltage Ground Directional Overcurrent Neutral Directional Overcurrent Autoreclose Underfrequency Overfrequency Cold Load Pickup Latched Lockout available as a standard feature SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Electric Operating Mechanism Busbar Connectors SecoLBS load break switch and SecoVac-R Specially designed for ring main unit's vacuum circuit-breaker can be equipped expansion and connection, the busbar with an electric operating mechanism connectors have compact structures and with remote control functions, without small connecting resistances. This way, influencing the structure and dimension of the connection between ring main units the module. is reliable and convenient. The busbar Motor power supply: 24VDC, 48VDC, connector, with the shape of an inner 110VDC, 220VDC. cone, adopts shielded silicon rubber to 40W 12r/min motor for LBS mechanism; fully seal and insulate the interconnecting 70W 50r/min motor for VCB mechanism. busbar and terminal busbar bushing. It Pressure Gauge/Density Relay Configurations Accessories can also be reserved for future expansion. Each gas tank is equipped with a pressure gauge or density relay in the front panel, observing SF6 gas pressure or density, in order to ensure the safety and reliability of the operations. End Plug Operating Handle Used for sealing the end terminal of the Used for operating the mechanism ring main units on both sides. Keep the manually. switchgear for future extension. 45 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit 268 100 Applicable standards: EN50181 DIN47636 ●● Shielded type (touchable), non-shielded Configurations Accessories Cable Terminal 46 type (untouchable) ●● Front plug cable connector, rear plug cable connector, rear plug lightning conductor ●● Cross section of cable: 35mm2~400mm2 ●● For 2 cables per phase connections, door with additional depth is provided, but maintaining same foundation Operating Handle layout as a standard unit (Front Used for charging the spring of the VCB cable connector, or front plug cable mechanism. connector + rear plug arrester). If 3 plug cable connector + rear plug cables or more are required (nonstandard panel), please contact GE Fault Indicator Panels are equipped with short-circuit/ grouding fault indicator to locate the faults. Sensors are installed on the HV cables, thus monitoring and displaying accurately. Typical Solutions & Installation Guide Outdoor switching substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 SecoRMU Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 SecoRMU Control Circuit Principle Drawing . . . . . . . . . . . . . . . . . . . 52 SecoRMU Dimensions and Installation Foundation . . . . . . . . . . . . 55 SecoRMU Order Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Typical Solutions& Installation Guide SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit 47 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit Typical Solutions & Installation Guide Outdoor Switching Substation The outdoor ring main unit substation adopts a metal-enclosed prefabricated structure, with excellent mechanical strength. Its protection degree can reach IP53, which protect the machine against the harmful effects of the ingress of water and solid foreign objects (like small animals). Ventilation There are louvers on the upper and lower sections of each side of the enclosure, with removable filters fitted inside. Thermal Insulation The roof is lined with double-layer high-quality heat insulation Typical Solutions& Installation Guide foam. Anti-condensation The slope of the roof is designed more than 3°. The big roof cover, combined with good ventilation, prevents the switching substation from condensating. Typical combination 3-way unit 1350× 1200× 1750 4-way unit 1700× 1200× 1750 5-way unit 2050× 1200× 1750 6-way unit 2400× 1200× 1750 Metering unit + 4-way unit 2300× 1200× 1750 Metering unit + 5-way unit 2650× 1200× 1750 4-way unit + metering unit + 2-way unit 3000× 1200× 1750 * If a special dimension is required, please contact GE. 48 Dimension (Width × Depth × Height mm) SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Dimensions SecoRMU K Panel 120 120 4 3 5 4-11×18 25 300 350 NO. 1 2 3 4 5 Title 720 800 Typical Solutions& Installation Guide (868) 1262 1380 110 K gas tank assembly Earthing copper bar between panels Earthing bar Vertical earthing busbar Assembly of K frame 49 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Dimensions SecoRMU T Panel 110 120 120 1262 1380 1 6 2 (560) Typical Solutions& Installation Guide 5 3 4 3 300 350 NO. 1 2 3 4 5 6 50 25 Title T gas tank assembly Earthing copper bar between panels Vertical earthing busbar Earthing copper Assembly of T frame Fuse holder 720 800 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU V Panel 120 1 120 7 850 480 1380 1262 6 2 3 4 3 300 350 NO. 1 2 3 4 5 6 7 4-11×18 Title 25 720 800 Typical Solutions& Installation Guide (550) 5 V gas tank assembly Earthing copper bar between panels Vertical earthing busbar Earthing copper Assembly of V frame CB operating device Operate machine (manual) 51 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Control Circuit Principle Drawing K N L 1ZK 9 101 Manual closing 13 14 5 1 RC M5 M2 14 13 2 1 2 1 109 138 SBS 13 14 RA 3 D1 D4 D2 D3 135 2 1 M4 X2 105 3 2 1 Remote tripping 102 Manual tripping Tripping relay LBS tripping indication LBS closing indication 1 Rectifying circuit RA 11 7 401 M RC 11 7 Code name. SA1 SB,SBS 1ZK RA RC M1' ,M1 ~ M6 D1 ~ D4 VR SQ 2 1 1 X2 SBS X1 M1 M4 SB X1 M1' M2 14 13 201 Closing relay Remote opening SBS1 23 24 SA1 RA 1 9 5 108 SB RC 136 Remote closing Red Black 402 RC 6 10 202 VR Motor RA 6 10 Component name and type Quantity Button with lock LA39-11Y/AU Button LA39-11/r g MCB Opening relay Closing relay Position switch LXW16-11AL42 Diode Voltage Dependent Resistor Electric live indicator DXN8A-T3/S 1 2 1 1 1 7 4 1 1 Remark Technical requirement Remark: In figuration, the load switch is in the opening position and the earthing switch is in the closing position. RC: Closing Relay RA: Opening Relay M1': Load break switch operation handle interlock switch M1: Earthing switch operation handle interlock switch M2~M4: Travel switch for load break switch position M5~M6: Travel switch for earthing switch position 52 Closing circuit SA1 13 14 M Remote closing Tripping circuit 106 Typical Solutions& Installation Guide Breaker 1ZK SB1 Power supply SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit T L N 1ZK Breaker 1ZK Remote closing 106 SB Manual closing 13 14 9 RC 5 1 RA RC M5 9 1 14 13 2 1 RA KT 14 13 KT 5 9 M2 2 1 109 M2 M1 2 1 2 1 1 3 TQ A1 A2 M4 3 1 136 Remote opening SBS1 SA1 23 24 X2 135 2 1 M3 X2 105 3 SBS X1 D1 D4 D2 D3 201 102 Reverse charging relay Remote tripping Manual tripping LBS tripping indication LBS closing indication 1 Rectifying circuit RA 11 7 RC 11 7 Code name. SA1 SB,SBS 1ZK RA RC KT M1' ,M1 ~ M7 D1 ~ D4 VR SQ SBS 13 14 M3 SB X1 Closing relay Timing relay 14 13 M7 3 1 2 M1' 401 Red M VR Black 402 RC 10 6 202 Motor RA 6 10 Component name and type Quantity Button with lock LA39-11Y/AU Button LA39-11/r g MCB Charging relay Closing relay Timing relay ST6P-2 0.5 ~ 5s Position switch LXW16-11AL42 Diode Voltage Dependent Resistor Electric live indicator DXN8A-T3/S Remark 1 2 1 1 1 1 8 4 1 1 Typical Solutions& Installation Guide SA1 13 14 Closing circuit 101 M Remote closing Tripping circuit SB1 Power supply Technical requirement Remark: In figuration, the load switch is in the opening position and the earthing switch is in the closing position. RC: Closing Relay RA: Opening Relay M1': Load break switch operation handle interlock switch M1: Earthing switch operation handle interlock switch M2~M4: Travel switch for load break switch position M5~M6: Travel switch for earthing switch position M7: Charging travel switch TQ: Opening Coil 53 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Control Circuit Principle Drawing V 14 1ZK SA1 Power supply 1ZK Breaker 101 Remote closing SB1 SB 13 14 106 Remote closing M1 M1' QF 2 1 2 1 2 4 CK1 3 HQ 1 2 A1 A2 Remote opening SBS1 1 QF 3 138 1 X2 135 6 8 QF X2 105 5 HR X1 TQ 3 A1 A2 QF HG X1 Manual closing Remote tripping M7 SBS 13 14 136 102 Manual tripping VCB tripping indication VCB closing indication 7 VR D1 D4 D2 D3 CK2 3 1 2 Typical Solutions& Installation Guide 201 Rectifying circuit 401 Red M Black D5 Code name. Component name and type SA1 SB,SBS 1ZK M1' ,M1 ~ M6 D1 ~ D4 VR KA AP Button with lock LA39-11Y/AU Button LA39-11/r g MCB Position switch LXW16-11AL42 Diode Voltage-dependent resistor Relay SCM 4C0/DC24V 5A Relay protect equipment ST260 1 2 1 7 4 1 1 1 Remark: In figuration, the VCB is in the opening position and uncharging while the 3-position switch is in the earthing position. HQ: Closing Coil TQ: Opening coil QF: VCB Auxiliary switch M1': Disconnector operation handle interlock switch M1: Earthing switch operation handle interlock switch M2~M4: Travel switch for load break switch position M5~M6: Travel switch for earthing switch position M7: Limit switch of cable compartment door 54 Quantity Technical requirement CK1~CK3: VCB charging position switch Motor 202 Remark Closing circuit 13 N Tripping circuit L M SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Dimensions and Installation Foundation Unit 800 720 25 K T A D V B C 350 300 M VT P 600 550 1)A foundation is made up of two pieces of 10# channel steel (as shown below). 2)The depth of the cable trench is determined by 110 requirements of the technical specifications. %RWWRPYLHZ Back to wall 500mm suggested 480 the actual cable types, as well as meeting the 3)Each ring main unit has the same depth, while the distance between the hole's center of two 800 770 different channel steels is 720mm. The panel can be fixed on the channel steel by the spot welding process. Gas tank 2SHUDWLQJPHFKDQLVPFRPSDUWPHQW 50 Primary and secondary cable installation hole 6HFWLRQYLHZRIFDEOHWUHQFK 720 545 ≥800mm suggested 100 50 10# channel steel M16 mounting hole Channel steel top view Typical Solutions& Installation Guide 868 Pressure release channel 1380 Pressure relief device 55 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Dimensions and Installation Foundation 1200 770 Front Side Back Side Bottom View 2400 2300 350 350 350 1200 10# channel steel 350 Operating mechanism compartment 800 600 3mm above the ground K T K T PT 10# channel steel 148.5 550 A-A Entry cover plate 290 1200 2420 2080 1840 Front 1750 A-A view On left and right 95 Ladder 960 980 1540 30 302 1750 1675 Gas tank Back 56 Front view Side view 1685 1990 Cable port 240 1685 1482 Cable port Angle steel for cable fixation Typical Solutions& Installation Guide 750 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Order Form Customer Contact Person Project Tel Address Fax Delivery Time E-mail Power Supply Type⑥ Quantity Quantity Quantity Rated Voltage 12kV□ 17.5kV□ 24kV□ Rated Current Operating Voltage of Electric Mechanism DC24V□ DC48V□ DC110V□ DC220V□ AC110V□ AC220V□ 3 B □ □ 4 V □ 5 C 6 □ □ / / □ □ □ / / / / / / □ / □ □ / □ / / / □ □ / / / M / / / □ □ / / / 7 VT / / / □ □ / / / 8 P / / □ □ / / Quantity (Set)⑥ □ Cable Connector⑤ □ SR3 T WIC1 2 3CT/3VT □ 2CT/2VT □ Fuse Current④ Electric K Relay Protection Type① 1 CT/ VT No. Manual Cable's Entrance or Exit Mode③ Extension Mode② Type① No. Operating Mechanism 630A□ Remark C / / T □ □ □ / / □ □ □ / / □ □ / / / □ □ □ / Quantity (Set)⑥ □ □ / Cable Connector⑤ □ SR3 T WIC1 □ Relay Protection 3CT/3VT □ CT/ VT 2CT/2VT Electric K Fuse Current④ Manual Cable's Entrance or Exit Mode③ Extension Mode② Operating Mechanism / Remark Typical Solutions& Installation Guide Individual Ring Main Unit Common-tank Ring Main Unit 9 10 / 57 SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit SecoRMU Order Form 3CT/3VT WIC1 SR3 / □ □ / / □ □ / □ □ / / T □ □ / □ □ □ / K □ □ / □ □ / / / □ □ / / K / K / / □ □ K / / □ □ □ □ □ / K □ □ □ □ □ / K □ □ / □ □ / / / □ □ / / K / / □ □ T / / □ □ □ □ □ / T / / □ □ □ □ □ / □ □ □ □ □ / T Typical Solutions& Installation Guide / Quantity (Set)⑥ 2CT/2VT □ Cable Connector⑤ Fuse Current④ Electric 13 Relay Protection Manual Cable's Entrance or Exit Mode③ Extension Mode② Type① No. 12 CT/ VT □ K 11 Operating Mechanism Remark Optional Accessories Name 14 Quantity Name Operating Handle Check Phase Apparatus Padlock Auxiliary Contact ( 1NO+ 1NC) Busbar Connector Busbar Terminal Plug Cover Quantity Others Note①: 1) K – Load switch unit; T - Load switch-fuse combined unit; B - Bus tie unit; V - Vacuum circuit-breaker unit; C - Busbar lift unit; M - Metering unit; VT – VT unit. 2) Common-tank ring main unit is combined freely by individual C, T or K ring main unit. A common-tank RMU can be assembled by maximum 5 individual units. Note②: Please remark the extension mode of the RMU products. Remark "D" if it's right extendable. Remark "I" if it's left extendable. Remark "ID" if it's both sides extendable. Remark "/" if it's not extendable. Note③: Please remark the cable's entrance or exit mode if the RMU is connected by cable. Remark "R" if it's right entrance-exit. Remark "L" if it's left entrance-exit. Remark "LR" if it's both sides entrance-exit. Remark "/" if there is no entrance-exit cable. Note④: Please refer to the transformer-fuse selection table (shown in page 34) for reference. Note⑤: Please notice the specifications (such as size, type etc.) of the cable connector. Note⑥: Example: please fill the blank of quantity item "9" if the scheme is P+K+M+TT+B+TT+M+K+P. 58 Greater China Shanghai 4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech Park, Shanghai, China 201203 T : +86 21 3877 7888 F : +86 21 3877 7600 Taiwan 6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480 T : +886 2 2183 7000 F : +886 2 2516 6829 South East Asia Malaysia Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur Sentral Kuala Lumpur, Malaysia 50470 T : +603 2273 9788 F : +603 2273 7988 Philippines 8F Net Cube Building, 30th Street, Corner 3rd Avenue, Crescent West Park, Global City Taguig 1634 T : +63 2 877 7000 F : +63 2 846 0629 Indonesia BRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46 Jakarta 10210 T: +62 21 573 0430 F: +62 21 574 7089 Thailand 25th floor, CRC Tower, All Seasons Place, 87/2 Wireless Road, Lumpini, Pathumwan, Bangkok 10330 T : +66 2 648 0240 F : +66 2 648 0200 Vietnam Saigon Centre, Unit 1, Floor 7, Le Loi Boulevard, District 1 HoChiMinh City T : +84 8 3914 6700 F : +84 8 3827 8229 Singapore 240 Tanjong Pagar Road, #06-00 GE Tower Singapore 088540 T : +65 6326 3718 F : +65 6326 3015 India India Polt No. 42/1 & 45/14, Electronic City-Phase II Bangalore-560100 T: (080) 41434000 F: (080) 41434199 Australia & New Zealand Australia 125-127 Long Street, Smithfield, Sydney, NSW 2164 T : +61 2 8788 6911 F : +61 2 8788 7224 North Asia Japan 11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-ku Tokyo 107-6111 T : +81 3 3588 5288 F : +81 3 3585 3010 New Zealand Level 1, 8 Tangihua Street, Auckland, North Island T : +64 9 353 6706 F : +64 9 353 6707 Korea 22, Daewangpangyo-ro 712 beon-gil, Bundang-gu, Seongnam-si, Gyeonggi-do, 463-400, Korea T: +82-31-620-6000 F: +82-31-620-7070 Europe & Middle East Spain P.I. Clot del Tufau, s/n, E-08295 Sant Vicenç de Castellet T: +34 900 993 625 Belgium Nieuwevaart 51, B-9000 Gent T: +32 (0)9 265 21 11 Finland Kuortaneenkatu 2, FI-00510 Helsinki T: +358 (0)10 394 3760 France Paris Nord 2, 13, rue de la Perdrix F-95958 Roissy CDG Cédex T: +33 (0)800 912 816 Poland Ul. Odrowaza 15, 03-310 Warszawa T: +48 22 519 76 00 and Ul. Leszczyńska 6, Bielsko-Biała 43-300 T: +48 33 828 62 33 Italy Centro Direzionale Colleoni Via Paracelso 16, Palazzo Andromeda B1 I-20864 Agrate Brianza (MB) T: +39 039 637 3701 Netherlands Parallelweg 10, Nl-7482 CA Haaksbergen T: +31 (0)53 573 03 03 Germany Robert-Bosch Str. 2a, 50354 Hürth-Efferen T: +49 (0) 2233/ 9719-0 Portugal Rua Camilo Castelo Branco, 805, Apartado 2770 4401-601 Vila Nova de Gaia T: +351 22 374 60 00 Hungary Vaci ut 81-83. H-1139 Budapest T: +36 1 447 6050 Latin America Latin America 790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USA T: +1 305 551 5155 Chile Vespucio Norte, Avenida Presidente Eduardo Frei Montalva 6001, Edificio N° 66 Comuna: Conchalí, Sector el Cortijo, Santiago T: (56 2) 928-4700 North America USA 41 Woodford Avenue, Plainville CT, USA 06062 and 12305 Kurland Drive, Houston, TX USA 77034 T: +1 800-431-7867 Brazil Av. María Coelho Aguiar, 215, Bloco C - 6.Andar Jd.São Luiz, 05804-900, São Paulo T: +55 11 36141900 Mexico Av. Churubusco 3900 Nte, Col. Industrial Benito Juárez Monterrey, N.L. 64517 T: (01-800) 800-1968 Russia 27/8, Electrozavodskaya street, Moscow, 107023 T: +7 495 937 11 11 South Africa Unit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685 P.O. Box 76672 Wendywood 2144 T: +27 11 238 3000 United Arab Emirates Injaz Building, 3rd Floor Dubai Internet City, PO Box 11549, Dubai T: +971 4 4546912 United Kingdom 2 The Arena, Downshire Way Bracknell, Berkshire RG12 1PU T: +44 (0) 800 587 1239 GE Industrial Solutions You may be interested in other MV Seco-family products For more information, please visit www.geindustrial.com For more information, please visit www.geindustrial.com Printing Code: IN201302B10EN © Copyright GE Industrial Solutions 2013