Instructions For Switch, Terminal Strip and Mounting Bar Replacement For Linear, Rotary Valve or Actuator Constructions IMPORTANT: See separate instructions for Setting Mechanically Operated or Non Contact Switches. MAINTENANCE WARNING: To prevent the possibility of personal injury or property damage, turn off electrical power, before inspecting, rebuilding or removing valve position indicator. Also turn off electrical power and pressure to related systems. DISASSEMBLY AND REASSEMBLY Replacement of SPDT Mechanical Switches, Non Contact Switches or Terminal Strip with Mounting Bar 1. Disassemble switches in an orderly fashion paying careful attention to exploded views. Refer to Figure 1 for mechanical switches; Figure 2 for non contact switches. Note: For Series M position indicators (not shown on this form), when disassembling disconnect switch wiring from terminal strip first. When reassembling, install switch first. 2. Remove two switch mounting screws, switch and mounting columns from Switch 1 and Switch 2, (if present). Note columns are two different diameters. 3. Cut wire tie that secures switch wires to post in position indicator housing (not present on Series M). 4. For ease of access and wiring, loosen terminal strip by removing terminal strip mounting screws from center of strip. 5. Disconnect switch wires from terminal strip. 6. If a new terminal strip with mounting bar is installed disconnect supply wires and solenoid wires from terminal strip. 7. Remove mounting bar mounting screws using a 1/16I hex key wrench. 8. Reassemble mounting bar, terminal strip, switch mounting columns and switch(s) following exploded views and wiring diagram provided in position indicator housing cover. NOTE: Make electrical switch connections to terminal strip before installation of switches or terminal strip in indicator housing. e ASCO Valves MCMXCVII All Rights Reserved. SERIES C, L, M & S Form No.V6976 9. Install new wire tie when reassembling (not supplied in rebuild kit). 10. Refer to Torque Chart on page 2 of 4. 11. Test operate switches before returning the position indicator to service. 12. After it has been determined that the switches and indicator are operating correctly, return power supply to valve position indicator. Replacement of DPDT Switches or Terminal Strip with Mounting Bar 1. Disassemble switches in an orderly fashion paying careful attention to exploded view. Refer to Figure 3. 2. Remove two switch mounting screws (with flatwashers), upper insulator, switch and lower insulator. For dual switch constructions (as shown in Figure 3), remove spacers, upper insulator, switch and lower insulator. 3. Cut wire tie that secures switch wires to post in position indicator housing. 4. For ease of access and wiring, loosen terminal strip by removing terminal strip mounting screws from center of strip. 5. Disconnect switch wires from terminal strip. 6. If a new terminal strip with mounting bar is installed disconnect supply wires and solenoid wires from terminal strip. 7. Remove mounting bar mounting screws using a 1/16I hex key wrench. 8. Reassemble mounting bar, terminal strip, insulator spacers and switch following exploded views and wiring diagram provided in position indicator housing cover. NOTE: Make electrical switch connections to terminal strip before installation of switches or terminal strip in indicator housing. 9. Install new wire tie when reassembling (not supplied in rebuild kit). 10. Refer to Torque Chart on page 2 of 4. 11. Test operate switches before returning the valve position indicator to service. 12. After it has been determined that the switches and indicator are operating correctly, return power supply to valve position indicator. Printed in U.S.A. Page 1 of 4 50-60 Hanover Road, Florham Park, New Jersey 07932 Torque Chart Part Name All mounting screws Housing cover screws (not shown) Torque Value Inch - Pounds 20 maximum 30 ± 3 Torque Value Newton-Meters 2,3 maximum 3,4 ± 0,3 IMPORTANT Wiring diagram provided in housing cover terminal strip mounting bar long mounting screw (2) short mounting screw (2) mechanical switch 1 2 terminal strip mounting screw (see note 2) 3 4 5 6 7 mounting column (see note 1) terminal strip 8 mounting bar screw (see note 2) (1/16I hex key wrench) wire tie (used to retain wire leads from switch 2) (see note 3) Notes: 1. Columns are different diameters. 2. The number of screws will vary depending upon terminal strip size. 3. Install new wire tie at reassembly (not supplied in kit). IMPORTANT See Torque Chart Figure 1. Replacement of mechanical switch, terminal strip and mounting bar. Page 2 of 4 ASCO Valves Form No. V6976 50-60 Hanover Road, Florham Park, New Jersey 07932 IMPORTANT Wiring diagram provided in housing cover long mounting screw (2) terminal strip mounting bar 1 2 non-contact switch (see note 3) short mounting screw (2) terminal strip mounting screw (see note 2) 3 4 5 6 7 mounting column (see note 1) terminal strip 8 mounting bar screw (see note 2) (1/16I hex key wrench) wire tie (used to retain wire leads from switch 2) (see note 4) Notes: 1. Columns are different diameters. 2. The number of screws will vary depending upon terminal strip size. 3. Switch wires should be loosely twisted to contain wires in a bundle and avoid engagment with gears. 4. Install new wire tie at reassembly (not supplied in kit). IMPORTANT See Torque Chart Figure 2. Replacement of non contact switch, terminal strip and mounting bar. Form No.V6976 ASCO Valves Page 3 of 4 50-60 Hanover Road, Florham Park, New Jersey 07932 Figure 3. Replacement of DPDT switches, terminal strips and mounting bar. Page 4 of 4 ASCO Valves Form No. V6976 50-60 Hanover Road, Florham Park, New Jersey 07932