CT^ ALTERNATOR ANALYSIS AND INDUCTANCE PARAMETERS by JOSEPH EDWARD VANDERPOORTEN, B.S. A THESIS IN ELECTRICAL EiJGINEERING Submitted to the Graduate Faculty of Texas Tech University in Partial Fulfillment of the Requirements for the Degree of MASTER OF SCIENCE IN ELECTRICAL ENGINEERING / Approved, ^ ->t-. Chairman of the Committee /? / Accepted Dean of the Gradua December, 1976 - T- i^UU-ll^cH /JO./4/ ACKNOWLEDGEMENTS I <r. indebted to Dr. Tommy R. Burkes for his guidance in the direction of this thesis. I would also like to thank Dr. Stan Liberty and Dr. Arun Walvekar for their comments and observations on the material covered herein. 11 ABSTRACT This thesis deals with several aspects of rotating alternators. The subject of inductance parameter determination is discussed. Specific emphasis is placed on methods of bounding the values of the inductance of the damper or amortisseur winding. In addition, the fault analysis using the conservation of flux linkages is presented. Numerical examples are given of fault torques and currents for a variety of line fault situations. Ill TABLE OF CONTENTS Page li ACKNOWLEDGMENTS ABSTRACT iii LIST OF TABLES vi LIST OF FIGURES vii CHAPTER I. INTRODUCTION 1 II. MACHINE INDUCTANCE PARAMETERS Inductor Interaction 4 5 Two Circuit System 5 Approximating Mutual Inductances 8 Single Phase Machine Inductance Parameters 10 Field Self Inductance 11 Phase to Field Mutual Inductance 13 Phase Self Inductance 13 Three Phase Synchronous Machine Without Damper Windings ^^ Damper Windings 19 Damper Modeling 21 Damper Self Inductance 21 Quadrature Axis Damper to Field Mutual 23 Damper Winding Phase to Direct Mutual 23 Quadrature Axis Damper to Phase Mutual 24 Approximating Damper Mutuals 24 IV III. PHYSICAL REALIABILITY OF DAMPER WINDINGS 27 Lower Bound Physical Realizability of Three Phase Machines 27 Lower Bound Physical Realizability of Damper Self Inductances IV. 29 Upper Bounding Damper Self Inductances 35 FAULT ANALYSIS BY CONSERVATION OF FLUX LINKAGES 39 Two Coil System 39 3 Phase Synchronous Machine Without Damper Windings . . -43 V. 3 Phase Synchronous Machine with Damper Winding 48 Non Symmetrical Short Circuits 49 Single Phase to Ground 49 Phase to Phase Fault 52 Phase to Phase to Ground Fault 54 Calculation of Fault Torques 56 CONCLUSION 67 REFERENCES 69 LIST OF TABLES Table ^-1. 4-1. Lower Bound Realizability Criterion for a 3 Phase Machine With Damper Windings 28 Derivitative Values of Machine Inductance Parameters With Kespect to Rotor Shaft Angle 58 VI LIST OF FIGURES Figure Page II-l. Arbitrary 2 Circuit System in Space 6 II-2. Three Coupled Inductors 9 II-3. Single Phase Machine Model 12 II-3a. Phase A Self Inductance Variation 15 II-4. Three Phase Machine Without Damper Windings 16 II-5. Inverse Orientation of Flux Generated by Phase A and Phase B Windings 18 II-5a. Phase to Phase Mutual as a Function of Rotor Shaft Angle For a 3 Phase Alternator 20 II-6. Three Phase Machine with Damper Winding 22 11-7. Electrical Model of the Field to Damper to Phase Arrangement 25 III-l. Coupling Coefficients of Phase to Damper to Field Arrangement 37 IV-1. Electrical Diagram of Single Phase Machine Fault 40 IV-2. Electrical Diagram of Three Phase Machine Fault 45 IV-lab.Three Phase Short Without Damper Windings o = 0°, 45°. . .47 IV-lc. Three Phase Short Currents for Machine Without Damper Windings 0 = 180° 50 IV-2a. Three Phase Fault Currents for Machine With Damper Windings 0 = 0° 50 IV-2bc.Three Phase Fault Currents for Machine With Damper Windings 0 = 45°, 180° IV-3. 51 Single Phase to Ground Fault Current vn 53 IV-4- Phase to Phase Fault Current 53 IV-5. Phase to Phase to Ground Fault Current 55 IV-6ab.Fault Torque of Three Phase Machine Without Damper Windings 0 = 0°, 45° 62 IV-6c. Fault Torque of 3 Phase Machine Without Dampers 0^ = 180° .63 IV-7a. Fault Torque of 3 Phase Machine with Dampers 0^ = 0°. . . .63 IV-7bc.Fault Torque of 3 Phase Machine with Dampers 0^ = 45°, 180''64 IV-8a. Single Phase to Ground Fault Torque 65 IV-8b. Phase to Phase Fault Torque 65 IV-8c. Phase to Phase to Ground Fault Torque 66 IV-9. Tabulated Minimum and Maximum Torque for Phase A to Ground Fault for the Full Range of Shorting Angles 66 vin CHAPTER I INTRODUCTION The design and construction of synchronous rotating machines is a well established art. Large generation systems are built to with- stand virtually any kind of line fault situation. Modeling the fault response characteristics is an important part of the overall machine design process. An involved part of modeling an alternator is the determination of a set of inductance parameters to represent the electrical characteristics of the machine. The damper winding presents specific difficulties in the determination of its inductive parameters. The geometry of this "winding" does not lend itself easily to field theory estimates of its inductance. It can be shown by basic physical prop- erties of coupled inductors that damper inductive parameters are restricted to a specific range of values. This range is a function of the other inductive parameters and the physical configuration of the machine. Such ranging can be useful in the determination of the in- ductive parameters of the damper winding. In the early 1900's a principal known as the "conservation of flux linkages" was developed. In short this principal states that the magnetic flux linking any closed system having zero resistance and no voltage sources cannot change with time. Provided winding re- sistances are small, this principal can be applied to calculate the initial short circuit current response of a rotating machine. The theorem of conservation of flux linkages is the basis of the derivation of the well known transiant and sub transient reactance 2 parameters, x^' and x ^ " . The method described in this thesis takes advantage of the computational capabilities of a computer. In so doing, some of the approximations associated with the deriviation of transient and sub transient reactance parameters need not be made. The results should therefore be closer estimates of the actual fault characteristics of the machine. An interesting question to pose is why such aspects of machine transient analysis were not dealt with years ago. Rotating machines have long been in use so that the exact calculation of fault torques and currents has been of major importance to systems design. The answer to this question might be summed up in what might be called on "overkill" philosophy to machine design. The overkill design philosophy might be stated as simply overbuilding any machine component that might be subject to stress during a fault. A rough modeled calculation of the maximum possible limits of transient fault torques for machine mechanical design and fault currents for system breaker design is sufficient to assure system protection. The exacting analysis of the complex field interaction in a rotating machine is unnecessary in this case. Obviously this conservative approach to motor design is adequate for most alternator applications. Recent proposed applications of rotating machines have led to a need for more exacting criterion in their design. This is specific ally important if the overall weight of the machine is a constraint. This has opened up a need to Investigate transient models in detail. The intent of this thesis is not to approach the overall problem of transient modeling. It is intended to shed some light on the previously stated particulars so that future development of transient modeling criterion may be more exacting. CHAPTER II MACHINE INDUCTANCE PARAMETERS The inductance parameters of a rotating machine are used to relate the electrical characteristics of the machine terminals to 2 3 the physical configuration of inductors in the machine. * In this chapter a detailed study of these inductance parameters is presented. The development of this material includes the basic properties of coupled inductor systems, development of basic machine parameters and overall final development of a machine matrix for a three phase synchronous machine with damper windings. The development of the inductance parameters of a machine is relatively straight forward. Effectively the machine windings are modeled as simply oriented loop inductors. The basic problem is to model the electrical interaction as a function of the internal configuration of inductors in the machine. In this regard a machine can be thought of as a complex transformer which has varying inductance parameters are a function of specific machine constants and the instantaneous rotor shaft angle. To include saturation and resistive effects in our inductance parameters would unduly complicate the analysis. Past work has shown that neglecting resistance does not significantly alter the calculated fault current and torque response of the modeled device 4 for the first few cycles after the occurrence of the fault. Efficient machines are typically of low winding resistance. To neglect saturation effects leads to a linear flux current relationship. Straightforward methods exist for digital solution of coupled linear equations. It is important to note however, that depending on the fault situation, neglecting saturation effects may not be valid. Inductor linearity is strongly distorted if the flux density in the inductor achieves saturation levels. Inductor Interaction The electrical characteristics of inductor interaction are well understood, provided the parameters used accurately reflect the physical situation. Several methods exist to determine the exact values of inductances. through the device terminals. field theory techniques. First they can be directly measured Secondly, they can be calculated by In order to perform such a calculation a thorough understanding of the physical conditions in the machine must exist. In calculating self and mutual inductances by field theory techniques for any but the simplest idealized coil orientations, the exact expressions can be very involved. For this reason inductive parameter models for machines are derived from simple coupled inductor configurations. As a starting point to the development of inductive parameters for a machine consider a simple 2 circuit system. Two Circuit System Consider the circuit diagram of Figure II-l. Given a certain current I^ flowing through loop 1 a flux is generated which is a 1 /v Figure II-l. Arbitrary 2 circuit system in space linear function of the applied current. ^^ = L^I^ The parameter L^ is known as the self inductance of loop 1. 2-1 If this is in some type of simple loop configuration the inductance is a linear function of the total flux and the number of turns. h = -17 2-2 where N^ is the loops of circuit 1 I-j is the loop 1 current 4>1 is the flux from L, If an external flux source such as a second circuit generates an additional set of flux lines i^2iWhich penetrates the first circuit in the same direction as \i>-,, *21 = "21II 2-3 the overall combined flux through the first circuit is: 1^1 = L^I^ + M^2^2 2-4 Where M-i^ is called the mutual inductance and is dependent on the relative geometry of circuit 1 and 2 along with the permeability of the intervening substance. Combining flux linkage equations for both circuit 1 and circuit 2 we get ij^l = L^ I-j + M2112 2-5 8 Approximating Mutual Inductances At this point it is convient to deal with some of the problems related to the determination of damper winding parameters. Consider the coupled inductor circuit of Figure II-l redrawn in Figure II-2 with the addition of a single turn coil Lp that occupies an intervening space. The total flux \\>-^2 coupling L, to L2 can be written as *12 = V 1 2 = ^l"l2 2-6 Also the total flux !)/]„ linking L, to L Q can be written: *1D = V l D = 'l"lD 2-7 where <^-^2 ^^ ^^^ total flux from L, that couples L2 4>iQ is the total flux from L^ that couples Lr. ^12' '^ID ^^^ ^^^ respective mutuals I-i the current through L-, N2, Nrj are the respective turns of L2 and L^ Because L Q occupies the space between L, and L2 the following definition is made: K4']2 ~ *^1D 2-8 Where K is a constant whose value is less than one and can be approximated from the physical configuration. Rearranging equation 2-6 the result is: MI *12 = l i p 2-5 Figure II-2. Three coupled inductors 10 By equation 2-8 this implies that: ^2^1 *iD = -o7 ^"^^ The mutual inductance of L^ to LQ may be difficult to calculate. Based on the accuracy of K in Eq. 2-8 a good approximation of M^^ can be made. By eq. 2-7: ^ID-TTBy substituting this result into Eq. 2-10 one obtains: •^iD = 17 (nn^) = -mq ^-"'^ An analogous expression can be obtained to relate Lg to L2 as follows: ^2D K'N^ 2-13 Where K' is the analogous to the constant K in Eq. 2-8 and N-. is the inductor turns of Li. This technique to approximate the value of the mutual inductance of an intervening inductor will be useful when applied to damper windings. But first the inductive parameters of the rest of the rotating machine will be developed. Single Phase Machine Inductance Parameters The interactive coil arrangement of a rotating machine is dynamic in nature. For this reason the inductance parameters are modeled as functions of shaft angle. The shaft angle is arbitrarily referred to the phase winding of the machine. 11 Consider Figure II-3 of a single phase machine as an initial example. 0 is defined as the instantaneous rotor angle, A is the stator loop winding. The same form of the flux linkage equations in Eq. 2-5 can be applied to the machine in Figure 11-3 giving the following result: ^A = L A ( Q ) I A ^ ^FA^^^^F 2-14 % = f^AF^^^^A ^ Lp(0)lp where L^^ is the stator or phase self inductance Lp is the field or rotor self inductance My^P is the phase to field mutual inductance Mp^ is the field to phase mutual Inductance In light of the simplicity of this machine model, the form of each of these inductance parameters L A , Lp, and M«p can be easily arrived at as functions of rotor shaft angle. Field Self Inductance The field self inductance is a function of the air gap variation about the field winding. gap is a constant. For a cylindrical stator machine the air For this reason the field self inductance can be specified as a constant: Lp(0) = Lff For some machines the internal air gap between the field and the stator may be a function of shaft angle due to some non cylindrical aspect of the stator winding arrangement. In this case the field 12 Figure II-3. Single phase machine model 13 self inductance should reflect the added complexity. Phase to Field Mutual Inductance The phase to field mutual inductance is a periodic function with respect to the rotor shaft angle. It is a maximum at 0 = 0° when the field winding is directly in line with the phase winding. The mutual inductance is zero when the field loop in perpendicular to the phase loop at 0 = 90°. There can be no common flux linkages between F and A in that orientation. When the rotor is positioned at 0 = 180°, the mutual inductance is negative the original magnitude at 0 = 0°. Although design criterion for machine flux linkages may vary, a sinusoidal distribution between minimum and maximum is assumed in the development of these inductance parameters. For a sinusodal flux distribution the phase to field mutual is thus of the form: Mp- = M^p = Laf cos 0 1-15 Where Laf can be theoretically determined as the mutual inductance when the rotor is positioned at 0 = 0°. Phase Self Inductance The self inductance of the phase or stator winding is a function of the variation of the internal air gap about the rotor. As with any Inductor with a moving core the inductance value must always be positive. In the case of a single phase machine, superimposed on this positive level is a harmonic variation produced by the changing air gap about the rotor. If the rotor is cylindrical or non salient 14 pole, there is no self inductance variation. The rotor to phase air gap is a minimum at both 0 = 0 ° and 0 = 180°. This harmonic component is double the frequency of the shaft angle rotation. Due to the assumed sinusoidal flux distribution about the rotor and the fact that the air gap varies at twice the frequency of the rotor the following result is obtained: L^ = Steady level + rotor level change = Laao + Lg2 cos(20) 2-16 where Laao is the self inductance of the phase at a shaft angle of 45° and Lg2 is the increase in phase self inductance when the shaft angle is adjusted to 0 = 0°. The plot of the resultant self inductance is the periodic function of Figure II-3a. Having redefined the dynamic induction parameters M«p and L» in terms of machine constants Laao, Lg2 and Laf the flux equations can be rewritten: ibfl = [Laao + Lg2 cos(20)]Irt + [Laf cosojlr ^ ^ •" iPp = [Laf cos0]I^ + Lff lp 2-17 A development of the parameters of multi phase machines can now be considered in terms of those developed thus far. 3 Phase Synchronous Machine Without Damper Windings Consider the machine diagram of Figure II-4. The phase self inductances are identical to those of the single phase case except for the phase angle shifts for the B and C phase windings. The 15 Figure II-3a. Phase A self inductance variati on 16 Figure II-4. Three phase machine without damper windings 17 resultant equations are therefore: L^ = Laao + Lg2 cos(20) 2-18 Lg = Laao + Lg2 cos(23 + 120°) LQ = Laao + Lg2 cos(20 - 120°) Analogously the phase to field mutuals also incorporate the phase shift terms for B and C windings: ^AF ^ ^FA " ^^^ ^ ° ^ ^ 2-19 Mgp = Mpg = Laf cos (0 - 120°) MQP = Mp^ = Laf cos (0 + 120°) As with the single phase motor example, the field winding self Inductance is also modeled as a constant because of the cylindrical stator configuration. Lp = Lff = constant The remaining phase to phase mutuals are more involved. Consider the relative orientation of phase A to phase B in Figure II-5. The current I^^ through loop A is in an inverse orientation with respect to current Ig through loop B. Therefore, the opposing direction of the respective flux lines ipj^ and \p^ produces a negative mutual inductance M«g. The action of the salient pole rotor periodically distorts the flux lines between phase A and B. The flux line distortion is a function of the rotor to stator air gap geometry. produces the phase self inductance variation. This same air gap Thus the magnitude of this inductance level variation is the same for both phase self 18 Figure II-5. Inverse Orientation of flux generated by Phase A and Phase B windings. 19 inductance and the phase to phase mutual inductance. The graph of the mutual inductance for phase B to C is shown as a function of shaft angle in Figure II-5a. The phase to phase mutuals can thus be defined in the following form: M^g = Mg^ = -.5Lgo + Lg2 cos(20 - 120°) 2-20 '^AC " ^CA " --SLgo + Lg2 cos(20 + 120°) Mg^ = M^g = -.5Lgo + Lg2 cos(20) As stated previously, a variety of assumptions are made in the decivation of these inductance parameters. Restated these include cylindrical stator, sinusoidal flux distribution, linear inductances, and symmetrical rotor configuration. The degree of accuracy and precision of the numerical values of these inductance parameters is dependent in part on how closely the particular machine fits those approximations. Damper Windings Damper windings in synchronous machines are typically constructed as a series of equally spaced bars placed symmetrically about the field winding. The bars are all shorted together at the ends of this "squirrel cage" arrangement. This configuration is usually symme- trical about the rotor axis. Unlike the other windings previously discussed, damper windings respond significantly only under transient conditions. They are in fact not a winding in the usual sense at all but a metallic configuration that has important inductive properties in the fault response 20 Shaft Angle 270 36.0 -.5Lqo. Figure II-5a. Phase to phase mutual as a function of rotor shaft angle for three phase alternator. Mgp = -.5Lgo + Lg2 cos(20) 21 of the machine. Direct calculation of damper winding induction parameters by field theory techniques is a very complex problem. This problem may be partially avoided by relating the damper winding configuration to the other windings in the machine. It has been shown in Eqs. 2-12 and 2-13 that the mutual inductance of an unknown third winding can be related to the knowns of the first two windings. This is provided that this third inductor occupies the region between L-j and L2. It can be shown that this directly applies to several damper winding inductance parameters. The following chapter will deal with the problem of bracketing the values of the damper self inductances by physical constraints. The general model of the damper winding is now developed. Damper Modeling The components of the damper inductance are modeled as two seperate inductors along the perpendicular directions which correspond to the direct and quadrature rotor axes. The direct axis is in line with the rotor north and south pole and the quadrature axis leads it by 90° as shown in Figure 11-6. The damper is attached to the field winding in a symmetrical structure. The numerical form of the model of the inductance para- meters for both field and damper are thus similar. Damper Self Inductance As with the field winding, the damper sees a constant phase to damper air gap regardless of the position of the rotor. This is due to the fact that the stator is assumed to be cylindrical in struc- 22 Quadrature Axis Shorted Ring for Damper Winding Bars Direct Axis Figure II-6. Three phase machine with damper winding 23 ture as whown in Figure II-6. For this reason the self inductance of both the direct and quadrature axes of the damper winding are independent of the rotor position and designated by: Direct Axis Damper Self Inductance = LQ Quadrature Axis Damper Self Inductance = LQ If the field and stator configuration are cylindrical then LQ = L Q . In this case the air gap around the symmetrical damper winding is cylindrical. Quadrature Axis Damper to Field Mutual The inductance component of the damper along the quadrature axis is perpendicular to the field winding and will have no common flux linkages This direct to quadrature axis mutual \nur) is therefore by definition, equal to zero. Damper Winding Phase to Direct Mutual Because the direct axis of the damper winding is in the same orientation as the field winding its form and period is modeled identical to that of the field winding. Therefore the mutual induc- tance between the direct axis damper and the phase winding is of the analogous form: ^AKD ~ ^^^^ ^°^® 2-21a Mg^Q = Lakd cos(0 - 120°) M(,^Q = Lakd cos(0 + 120°) Where Lakd is the peak magnitude of the direct damper to phase mutual over a full shaft angle rotation. 24 Quadrature Axis Damper to Phase Mutual The quadrature axis to phase mutual inductance models the effect of the damper winding configuration in an orientation 90° ahead of the direct axis. The form of this mutual inductance parameter is thus identical to that of the direct mutual above with the appropriate 90° phase shift. M^^Q = Lakq cos(0 - 90°) = Lakq sine 2-21b Mgj^g = Lakq cos(0 - 120° - 90°) = Lakq sin(0 - 120°) M^I^Q = Lakq cos(0 + 120° - 90°) = Lakq sin(0 - 120°) Lakq is the peak quadrature damper to phase mutual over a full shaft angle rotation. For a cylindrical damper rotor arrangement the peak phase to damper mutual inductances for both quadrature and direct axes are identical. Therefore, it can be concluded that: Lakd = Lakq. Approximating Damper Winding Mutuals The derivation previously presented on approximating mutual inductances can now be directly applied to these damper mutuals. Con- sider Figure II-2 redrawn in Figure II-7 where Lp is the cylindrical field inductor, L-. is the damper winding loop inductor and L^ is the phase inductor of the cylindrical stator. The field to damper mutual can be approximated by Eq. 2-12 as follows: M = _L^_^ •^FKD K N^ where ^cun is the field to direct axis damper mutual 2-22 25 ^ AF Figure II-7. Electrical model of field to damper to phase arrangement. 26 Mp^ is the field to phase A mjtual inductance N^ is the number of phase A turns K is the proportion field to damper coupling flux that also couples the phase winding This value of K was generally defined in Eq. 2-8 and is thus defined In this field-damper-phase arrangement as follows: *FA " "^^FD 2-23 A good approximation can be made of the 2 unknowns NQ and K of Eq. 2-22. The damper inductances can be thought of as an equivalent single turn. Therefore, the value of NQ is one. All of the flux lines that pass from field to phase must pass through the damper winding configuration. Flux leakage is inherent in any coupled inductor system. Depending on the specifics of the damper to field configuration a good approximation may be a value of K near unity. Similiar arguments can be made in the derivation of the damper to phase mutual the expression is: " A K D = " F A / ( ^ ' Np) 2-24 Where Np is the number of turns of the field winding, and K'is defined as follows: •^^AD " *AF ^"^^ Chapter III discusses constraints that can be applied to damper self inductance values utilizing basic properties of these coupled inductor configurations. CHAPTER III PHYSICAL REALIZABILITY OF DAMPER WINDING SELF INDUCTANCE PARAMETERS The Inductance parameters of coupled inductor systems are by physical law constrained to a specific range of values with respect to one another. If a given inductive parameter is outside of this realizable range, the system in theory, could not be constructed. The specific criterion that will be used as a test for the lower limit of physical realizability is that the square of the mutual inductance cannot exceed the product of the self inductances in a coupled inductor system. This relationship is identical to stating that K <_ 1 where K is the coefficient of coupling. This constraint can be applied to any pair of windings in a machine. Generally the application of this criterion to the case of revolving inductors in a machine is much more complex than the analysis of static inductor configurations. Fortunately in the case of damper winding inductance parameters, expressions can be obtained which relate this constraint directly to the machine constrants. Effectively these expressions lead to a discrete lower and upper limit greater than zero for the damper winding self inductance values. Lower Bound Physical Realizability of 3 Phase Machines The model of a 3 phase machine developed in the previous chapter included 6 self inductance parameters: '-A' ^B' ^ C ^F' ^D* ^Q 27 28 CM Q A| _J Q O «T3 CVJ c\J «/) x: A| CL A I cr Q CO n so to CM o Q Iki C_) CM T- Li. C_) 4-> ra s: s: A| A| LL. 4J •r- CM cr i>^ C_) A| cr Q _J V) _j —J 1— cn •1c J3 •!- rsl c eali r wi CM CQ V) x : O" CQ OQ A| A| A| _J OQ —1 U. _l CQ _J Q _J CQ _l OQ _l <— E T3 OQ CM Q A| Q. U CM CM >»-M JC .|- CL 5 CM CM CM CM CQ •• 1 CO LU 1 CLJ ^ <_) ^ A| CQ -J <1 : A| C_) _l <a: 1 CM Q Ll, < A| Lu _l <: :i^ cy s^ 21 A| Q _l <: A| cr 1 < 29 For any 2 inductor system L^ L2 the physical r e a l i z a b i l i t y criterion ''• 2 L^L2 1 M^2 3-"' By applying Eq. 3-1 to all possible combinations of the previous set of inductors in a 3 phase machine the 15 relations of Table 3-1 must be satisfied for the given parameter set to be physically realizable. In general the application of Table 3-1 constraints to the full machine can be very tedious. This is due to the fact that most relationships are functions of rotor shaft angle. It will now be shown that the 0 dependence can be eliminated in the case of the damper winding parameters thus simplifying the application of Eq. 3-1. Lower Bound Physical Realizability of Damper Self Inductances Substituting in the 0 dependent expressions Eqs. 2-18, 2-21a, 2-21b for those Table 3-1 relationships dependent on damper self inductances the following results are obtained. [Laao + Lg2 cos(20)] LQ >^ [Lakd cos 0 ] ^ 3-2a [Laao + Lg2 cos(20 + 120)]Lr, 1 [Lakd cos(0 - 120°)] ^ 3-2b [Laao + Lg2 cos (20 - 120)]Ln >_ [Lakd cos(0 + 120°)] ^ 3-2c LFI-D >- ^FKD^ LQLQ >_ 0 ^-^' 3-2e For the quadrature damper self inductances the relations are: 2 [Laao + Lg2 C O S ( 2 O ) ] L Q >_ [Lakq sin o] 3-3a [Laao + Lg2 cos(20 + 120)]Ln > [Lakq sin(0 - 120)]^ ^" 3-3b [Laao + Lg2 cos(20 - 120)]Ln > [Lakq sin(0 + 120)]^ ^ 3-3c 30 LpLg >_ 0 3-3d LQLQ >_ 0 3-3e Expressions 3-2d,e and 3-3d,e deal with machine constants involving straightforward numerical comparisonss. The relationships of interest are therefore 3-2a,b,c and 3-3a,b,c corresponding to the phase winding to damper mutuals. By symmetry the configuration of each phase winding is a function of angle only. If a non 0 dependent expression is developed which corresponds to Exp. 3-2a for example, it is therefore also applicable to Exp. 3-2b and 3-2c. Thus a detailed study of Exp. 3-2a for the direct damper self inductance and Exp. 3-3a for the quadrature damper self inductance will lead to expressions which include all phases. Consider first the Expression 3-2a rewritten as follows: ^A^D ^ ^AD^ which implies M 0 I AD ^ (Lakd cos 0) ^ . ^D - L^ Laao + Lg2 cos(20) ^^"^ The maximum possible value for the term on the right is desired Taking the derivitative of Exp. 3-4 and setting it equal to zero the result is: 0 = -2Lakd^ cos 0 sin 0 Laao + Lg2 cos(20) 2 Lakd cos 0 Lg2 sin(20) (Laao + Lg2 cos(2:)) 3-5 Values of 0 which are solutions to Eq. 3-5 correspond to minima and maxima of Eq. 3-4. Multiplying through the squared self inductance 31 term of Eq. 3-5 the result is: 2 (-2Lakd cos 0 sine) (Laao + Lg2 cos(2:)) + 2Lakd^ Lg2 cos^ 0 sin(2e) = 0 3-6 The self impedance L^ term Laao + Lg2 cos(23) is always greater than zero. Therefore, the values of e which set Eq. 3-6 to zero fall into 2 groups: 0 = 0 ° , 180°, 360°, ...n(180°) correspond to the sine terms 0 = 90°, 270°, 450°, ...n(180°) + 90° correspond to the cosine terms Expanding Eq. 3-6 the result is: 2 -2Laao Lakd + 2Lakd 2 cos0 sino - 2Lg2 Lakd coss sin9 cos(20) cos^ 0 sin(20)Lg2 = 0 3-7 To find which 0 values correspond to maxima of Exp. 3-4 the 2nd derivitative test can be applied. Taking the derivitative of the left hand side of Eq. 3-7 the result is: -2Laao Lakd^[-sin e + cos^0] -2Lg2 Lakd^[-sin^0 cos(20) + cos^ e cos(2e) -2cos 0 sin 0 sin(2e)] +2Lakd^ Lg2[-2cos 0 sin e sin(20) 2 +2cos 0 cos(20)] 3-8 Substituting in all 0 values of interest into Exp. 3-8 for one period of shaft angle rotation 0 = 0° to 0 = 360° the results are: at 0 = 0°: -2Laao Lakd^ (1) -2Lg2 Lakd^ (1) + 2Lakd^ Lg2(2) 32 at 0 = 90°: -2Laao Lakd^ (-1) -2Lg2 Lakd^ (1) + 2Lakd^ Lg2 (0) at 0 = 180°: -2Laao Lakd^ (1) -2Lg2 Lakd^ (1) + 2Lakd^ Lg2 (2) 0 = 270°: -2Laao Lakd^ (-1) -2Lg2 Lakd^ (1) + 2Lakd^Lg2 (0) So terms which correspond to 0 = 0°, 180°, 360°, ...n(180°) are identical. They are equivalent to: -2Lakd^ (Laao - Lg2) 3-8 Those which correspond to 0 = 90°, 270°, 450° ...n(180°) + 90° being also equivalent are: 2Lakd^ (Laao - Lg2) 3-9 As stated in Chapter II Lg2 is always less than Laao because the phase self inductance is always positive. Therefore, Exp. 3-9 is always positive and Exp. 3-8 is always a negative term. This implies that 0 = 0°, 180°, 360° ...n(180°) correspond to Eq. 3-4 maxima. A check must also be made to determine whether the maxima of Eq. 3-4 during one shaft angle rotation correspond to absolute or local peak values. Substituting 0 = 0 ° into Eq. 3-4: . no ® " " , ^ K D ' ( Q ° ) _ Lakd^ "-D - L^ (0°) ' Laao + Lg2 0 = 180° U•D -> ^ K D ^ (13°°) Lakd^ L, (180°) Laao + Lg2 33 The results are identical, therefore the ninimum realizable valje of the direct damper self inductance is: LQ > Lakd^ Laao + Lg2 3-10 Similiarly it can be shown that the minimu;n realizable value of the quadrature axis damper inductance is: I > Lakq ^Q - Laao - Lg2 3 ,, "^ " A d e r i v a t i o n of Exp. 3-11 now f o l l o w s : The physical r e a l i z a b i l i t y Exp. 3-3a i s : > L^LQ M^Q2 3.33 Which implies M 2 2 I ^ ._AQ ^ Lakq sin 0 ^ -, ^ Q - L^ Uaao + Lg2 cos(20) •^'' ^ Taking the derivitative of 3-13, setting it equal to zero, and simplifying, the result is: 2 2 Lakq Laao sin 0 cos 0 + Lakq Lg2 sin 0 cos(20) + 2Lakq^ Lg2 sin^ 0 cos 0 = 0 3-14 A similiar range of solutions to the LQ case is found. 0 = 0 ° , 180°, 360° ...n(180°) corresponding to sine terms 0 = 90°, 270°, 450° ...90° + n(180°) corresponding to the cosine terms The second derivitative of Exp. 3-14 is: 34 Lakq Laao (cos 0 - sin^0) + Lakq^ Lg2 (cos^j cos(2:) 2 -sin 0 cos(29) -2sin0 cos9 sin(23) + 2 Lakq^ Lg2 (3 sin'^0 cos^O - sin^0) 3-15 Testing a full period of 0 values as in the LQ case, at 0 = 0° Exp. 3-15 is: Lakq^ Laao(+l) + Lakq^ Lg2(l) + 2Lakq^ Lg2(0) at 0 = 90°: Lakq^ Laao(-l) + Lakq^ Lg2(l) + 2Lakq^ Lg2(-1) at 0 = 180' Lakq Laao(+l) + Lakq^ Lgw(l) + 2Lakq^ Lg2(0) at 0 = 270°: Lakq^ Laao(-l) + Lakq^ Lg2(l) + 2Lakq^ Lg2(-1) Once again a grouping of identical solutions is obtained: for 0 = 0°, 180°, 360°, ...n(180°) Exp. 3-15 becomes Lakq (Laao + Lg2) which is always positive in value. For 0 = 90°, 270°, 450°, ...n(180°) + 90° Exp. 3-15 becomes -Lakq^(Laao + Lg2) which is always negative in value. So this result corresponds to 0 maxima of Exp. 3-13. Checking for relative or absolute maxima in Exp. 3-13 for 0 = 90°: I ^ Lakq^ sin^ (90°) D - Laao + Lg2 cos[2(90°)] Lakq^ Laao - Lg2 35 for 0 = 270°: I > Lakq^ sin(270°) Lakq^ D - Laao + Lg2 cosL2(270°)] ' Laao - Lg2 The maxima at 0 = 90°, 270°, 450° ...90° + n(180°) are thus identical. Therefore, expression 3-11 is the quadrature damper physical realizability constraint as desired. Upper Bounding Damper Self Inductances: It has been shown up to this point that Eq. 3-1 leads to an easy test for lower bound of damper winding self inductances. In- tuitively one might expect that some type of realizable upper dound must also exist. Searching for such a constraint in the realtions of Table 3-1 it is found that none of these expressions constrain any of the self inductance parameters in the machine. This result is easily understood because Eq. 3-1 limits only the maximum coupling between any two inductors, not the maximum value of the self inductance parameters involved. In order to come up with some form of limiting criterion to physical realizability of damper self inductances one must turn to some consideration of the physical configuration of the winding. Consider Eq. 3-1 rewritten in the following familiar form: K 12 M. '12 3-15 /Tal'-2 where K12 is the well known coefficient of coupling between inductor L, and L2. The coefficient of coupling, which has a value less than or equal to one, is a function of the mutual physical configuration 36 of any two inductors L^ and L2. A theoretical maximum value of a particular unknown self inductance parameter is constrained to be the minimum realizable value of the coefficient of coupling. This realiz- ability criterion is described for the general 2 inductor case as follows: h MAX < M 12 Kp 2 " ~Lp MIN ^ 3-16 where all of the terms on the right are known or closely approximated. Application of this criterion to the case of the self inductance of the damper winding presents similiar problems to those of the determination of the damper mutual as described in Eq. 2-22. Consider Figure III-l of the damper configuration, where the K terms are the coefficients of coupling of the respective windings. Eq. 2-23 relates the flux from field to phase to the flux coupling field to damper. The value of K in 2-23 is directly related to the amount of field flux that couples the damper but fails to couple the phase winding. The field winding is therefore more closely coupled to the damper than to the phase winding. The respective coupling coefficients should therefore reflect this fact as follows: •^FA ^ "^FD 3-17a Corresponding to the phase A coupling coefficient the following analogous expression can be stated: •^FA ^ '^AD 3-17b 37 ^"^ c^ 6 LD 'OF 6 ^ vJ Figure III-l. Coupling coefficients of phase to damper to field arrangement. 38 Knowing t h a t : _ iMaf K AF /TTL A'F M AKD and K AD 3-18 /TTL A"D and using Exp. 3-17b the r e s u l t is M AF M AKD 3-19 ' ' ^ ^ which Implies that: M, Lo < i-^^)' MAF L, 3-20 Analogously for the field to damper case: I < (JJ<D_ ^2 , -A M FA 3-21 Removing the 0 dependence from 3-20 and 3-21 the result is Ln < (^=f^)'Lff •D Laf 3-22a , ,Mfkd x2 /, ^ , ^x LQ < (-[jp-) (Laao + Lg2) 3-22b Exp. 3-22a,b are therefore the maximum limiting criterion for physical realizability of the damper winding inductance parameters in an alternator. The constraints which are placed on the damper self inductances effectively place a lower and upper bound on their inductance value. These constraints are completely stated in expressions 3-2d,e, 3-3d, 3-10, 3-11 and 3-22. Thus self inductance parameters of the damper winding can be easily tested to determine if they are physically realizable. CHAPTER IV FAULT ANALYSIS BY CONSERVATION OF FLUX LINKAGES The study of fault analysis using the pricipal of conservation of flux linkages is not new. Papers dealing with some aspects of this powerful tool date back to the early 1900s. The statement of this principal is straightforward and simple: "In any closed circuit without resistance the flux linkages must remain constant. It doesn't matter how many secondary circuits there are, or what the network involves, the theorem 4 is rigidly true." In this chapter the principal of conservation of flux linkages will be used in several ways. First it will be applied to the general question of short circuit analysis of rotating machines. The short circuit current response will then be used in the calculation of the torque response during the initial period after the fault. Two Coil System: The utility of the method of conservation of flux linkages becomes apparent when the self and mutual inductances are allowed to vary as a function of a third parameter. The case of analyzing a two winding rotating machine is now considered. The electrical fault is modeled as in Figure IV-1. problem is to calculate I«(0) and lp(0) for all 0 after t=0. Using the flux linkage equations presented in equation 2-14: 39 The 40 (p4=o t=0 6 \ / i Fo Figure IV-1. Electrical diagram of two winding machine fault 41 *A = Lftlft + M A F I F 4-1 *F = % ' A ' Lplp where L^ is the stator or phase self inductance Lp is the field inductance M^P is the stator to field mutual inductance also it must be given that If^ = Laao + Lg2 cos (20) Lp = machine constant M^P = Laf cos 0 where 0 is the designated shaft angle. Given the initial current vector 0 I t= 0 = 0 the initial flux vector can be calculated i> A. ^i Ip^ M,p(0) Ip Lff 0 The specific currents are now calculated as a function of shaft angle for the above initial conditions flux vector. The general case response equations are: \l>f^^ = (Laao + Lg2 cos(20) ly^(0) + (Laf cos0)lp(0) 4-3a IJ^PQ = (Laf cos?)I^(0) + Lff lp(0) 4-3b 42 Solving for the current response lp(0) and 1.(0) the result by Eq 4-3a is: ^fi^Q - Laf cos 0 1^.(9) Laao + Lg2 cos (23) A^^^ 4-4 Substituting this result into Eq. 4-3b i|^« - Laf cos e lr(0) *Fo = Laf cos 9 ( u a o > L92 cos (2o) ' ' •-" 'p^^' Laf cos 0 rl>f^^ Laf cos^ 0 lp(0) Uaao + Lg2 cos (2e) " Laao + Lg2 cos (20) ^ ^^^ ^F'^^ thus: Laf cos 0 \i) Ao ^ Fo " Laao + Lg2 cos (20) " ^f'®' ^^^^ Laf^ cos^ 0 lp(0) Laao + Lg2 cos(20) ^ 4-5 So the following closed form solution for the short circuit response is obtained: ij^c^ Laao + ipr^ Lg2 cos(20) - ii.^ Laf cos0 'Fo Ao lp(0) = 'Fo Lff Laao + Lff Lg2 cos(20) - Laf^ cos^0 lp(0) 4-7 Substituting the previous expression into Equation 4-4 a closed form solution of the phase A current is obtained. peated in matrix format for clarity. The procedure is re- Calculate the initial flux vector from the initial current vector: 4-8 ij^ = L I ^0 ""0 and thus the solution 0 0, 43 4-9 1(0) = [L(0)]"1 ^ Three Phase Synchronous Machine Without Damper Windings The technique applied to the previous case can now by simple extension be applied to larger systems. to be solved is stated as follows. The exact problem that is Given a specific machine with an open circuit phase windings, calculate the short circuit response for a full shaft angle rotation if phase A,B, and C are shorted together and the field winding is shorted to itself. This circuit is modeled in Figure Iv-2. The machine matrix is: ^A "AB "AC "AF "BA 4 "BC "BF "CA "CB "-C "CF "FA "FB "FC h L = Where the inductances and mutuals are the following restated functions of shaft angle. Lp = Lff ^BA = ^ B f^CB = ^BC f^CA = ^AC -.5Lgo + Lg2 cos (2e - 120°) -.5Lgo + Lg2 cos (2o) -.5Lgo + Lg2 cos (20 + 120°) L^ = Laao + Lg2 cos(20) Lg = Laao + Lg2 cos(20 - 120°) L^ = Laao + Lg2 cos(20 +120°) 4-10 44 M^P = Mp^ = Laf cos 0 Mgp = Mpg = Laf cos(0 - 1 2 0 ^ MQP = Mp^ = Laf cos(0 + 120°) Where Laao, Lg2, Lgo, Laf, Lff are all given machine constants flux linkage equation for this problem is: • ^ ^B • M *B BA ""B ^c ^^AF M BC M BF 'B = • ' A •"c ^CA ^CB k MCF 'c *F ^FA ^FB ^FC Lp ^F Now consider a numerical example. The machine constants are as follows: Laao = 1.964 X 10"^H Lg2 = 4.85 x 10"^H Lgo = 1.8362 x 10"^H Laf = 2.268 x 10"^H Lf = 3.024 X 10"^H For this example the field current is 200 amperes at the initial shaft angle of zero degrees. 0 0 0 200 The current vector is as follows: The 45 rcr o^ > F -Pb0 y o^ t=o a^ Figure IV-2. Electrical diagram of machine fault 'FO"(^' 46 For a shorting angle of zero degrees the initial flux vector is: >-2 cos 0) = 4.336 i>f^^ = 200 M^p(O) = 200(2.268 x 10"^ "^Bo " 200 Mgp(O) = 200[2.268 x 10"2 cos(0-120)] = -2.268 ^Co ^ ^°° ^ C F ' ° ' " 200[2.268 x 10"^ cos(0+120)] = -2.268 -2 = 6.048 I^PQ = 200 Lp = 200(3.024 x 10"^) 4-11 Thus the following matrix equation can be solved repetitively for the current response as a function of 0. M AB '^AC M M M % 4 ^CA M ^CB M 'TA "^FB BC M M FC -1 AF 4-536 IA(S) BF -2.268 IB(0) CF -2.268 1^(0) F. 6.048 lp(0) Digital computational techniques are now used on the matrix equations and the calculated currents are plotted over a range of shaft angles. 0^ + 0° £ 0 £ 360° + 0Q Where 0 is the angle at which the symmetric short takes place. the matrix listed above ij> corresponds to 0 = 0°. The resjlts are plotted for 3 seperate initial shorting angles. the current response for 0 For Figure IV-la shows = 0°, Fig. IV-lb for 0^ = 45° and Fig. IV-lc for 0Q = 180°. The calculated severity of the magnitude of the fault response is similiar for all three shorting angles although specific winding response varies as a function of shorting angle 47 LE <DEGREES> -2000 Figure IV-la. Three phase short currents for machine without damper windings at 0 = 0°. 2000 B u 0. E in z cr UJ X EC -2000 •- Figure IV-lb. at 0Q = 45°. Three phase short with damper windings 48 Three Phase Synchronous Machine With Damper 'bindings Inclusion of damper windings increases the size of the machine matrix by two. L= •A ^B M BA ^KD M BKD "^BKQ \ B M^ M k ^CF CKD "CKQ M, Mr-. "F L, "FB "FC M M FKD "\ FDKKQQ ^BKD ^CKD ^FKD ^D ^AKQ ^BKQ ^CKQ ^FKQ ^KDKQ LQ ^CA M FA •B ^C f^BC ^AF '\F \KD ^ K Q ' M Where the newly added terms are as previously stated, the following functions of shaft angle. '^AKD ~ ^^^^ ^ ° ^ ® M = Lakd cos (0 BKD 120°) 4-12 M, = Lakd cos (0 + 120°) CKD ^AKO ~ ^^^^ sin 0 M, = Lakq sin (0 - 120°) MQKQ = Lakq sin (0 + 120°) BKQ The f o l l o w i n g additional machine parameter values are included for the damper winding terms = 1.82 X lO'^H Lakd = 1.832 x 10"^H LQ Lakq = 1.773 x lO'^H Mpi^Q = 2.268 X lO'^H Ln = 1.861 X lO'^H ^FKQ = \ D K Q ~- ° ^ 49 Computer techniques are once again used to solve the matrix equation for the phase currents as a function of shaft angle. The results are plotted in Figure IV-2a,b,c. Figure IV=2a corresponds to an initial shorting angle of 0°, IV-2b corresponds to 0^ = 45° and IV=2c for 0 = 180°. The results indicate that the damper windings significantly increase the calculated fault currents. This is in line with the observed fault response of a machine with dampers. Damper windings also affect the specific shaping of the current response. Non Symmetrical Short Circuits The method of conservation of flux linkages can be applied to several connection configuration of a rotating machine provided the zero resistance assumption is maintained. By example several possible methods of fault analysis for non symmetrical short circuits follow. Single Phase to Ground Modifying the flux linkage equations to satisfy this criterion consists of removing the row and column terms from the matrix that corresponds to the two open circuited phases. The two open circuited phases cannot contribute to the maintenance of the flux vector during fault conditions. For example if phase A to ground fault is to be considered the flux linkage equations are: TEX^ST ppij VJBR^^"^ 50 E <DEEREXS> ^ 2000 m i*l 0 I t Q: a: 6 z X -2000 • Figure IV-lc. Three phase short without damper windings at 0Q = 180°. HOrr RHBUE <I>EBREXS> H0B0 Q 3000 hi £ 2000 ^ 1000 u Q: eft-B—I—^ a -1000 -2000 •' -3000 Figure IV-2a. Three phase short circuit currents for machine with damper windings at 0 = 0 ° . 51 E <DCSRCC:S> s a. 200B Figure IV-2b. Three phase short with damper windings at o = 45' E <PEGWELfa> X -2000 -3000 - Figure IV-2c. Three phase short with damper windings at o = 180°. 52 ^ A ^A ^AF 4*. '^FA ^F YD M ^AKD M FKD ^''AKQ f-l 'TKQ M I M AKD ' FKD ^D 'V^OKQ M M f*! I AKQ " F K Q ' \ D K Q ^Q 4*, D where as before IQ and IQ correspond to currents in the modeled damper windings. Given the machine data as used in the symmetrical short circuit case along with the same initial conditions. Fig. IV-3 is a plot of the calculated current response for the single phase to ground case. Although the shaping of phase A waveform is different, the peak magnitude of the single phase to ground current in this case is very close to that of the symmetrical fault. Phase to Phase Fault Calculation of the phase to phase fault follows a similiar procedure to that of the single phase to ground case above. The open circuit phase cannot contribute to the maintenance of the flux vector. As with the single phase to ground case the terms corresponding to that winding are thus removed. There is the additional constraint that the shorted phase currents are identical in magnitude and opposite in direction. This constraint can be applied using the same flux equation format. The resultant flux equations for the phase A to phase B fault are: 53 E <PESMEC5> Figure IV-3. Single phase to ground fault currents RNBLC <DCBrfEC5> ^N 3 0 0 0 B S^ 2 0 0 0 Figure IV-4. Phase to phase fault currents 54 *A ^A ^B *B ^^BA 4 0 = 1 M AF M ^AKD ^AKQ 1 M ^BF M '^BKD M 0 1 1 0 0 0 *F ^FA ^FD ° k ^FKD *D ^AKD ^BKD ° *Q '^AKQ ^BKQ 0 ^ ^KD4 ^A ^B - •F 'FKQ M KDKQ 'D M M LQ "^FKQ "^KDKQ 'Q > r Where row and column 3 correspond to the I^ = lg constraint. The term corresponding to I^^ in the current vector is ignored and should be calculated as zero for the full shaft angle rotation. A plot of this current response using the above modified flux equations is shown in Fig. IV-4. Phase to Phase to Ground Fault The difference between the double phase to ground case and the phase to phase case is simply the removal of the I = I constraint X from the flux linkage equations. y Effectively this is just an extension of the single phase to ground problem. For the phase A to phase B to ground case the flux linkage matrix is as follows: ^ ^ B h ^ ^( D ^A M "BA ^AB I ^B ^VA ^FB ^AF M FB h M M "AKD AKQ M M "BKD "BKQ ^FKD ^""FKQ ^AKD ^BKD ^FKD ^D ^KDKQ M AKQ '^BKQ ^CKQ ^KDKQ ^Q 55 Figure IV-5. Phase to phase to ground fault current; 56 A plot of the current response for the same initial conditions and machine parameters as previous is shown in Fig. IV-5. These three examples illustrate some of the calculatory procedures that may be used for the non symmetric fault conditions utilizing the principal of conservation of flux linkages. Calculation of Fault Torques2 Given the fault currents and inductance parameters the fualt torque can be readily calculated. A derivation of the fault torque leads to the following form of the expression. dL, dL« dL Torque = 1 / 2 l^ ^ . 1/2 I2 ^ ^ ... 1/2 I^ ^ dM,^ dM,, l/2Iil2-^-l/2l2li^-.-- dM V2I^M^-^ where L-j ... L^ represent all of the self inductance terms. ... M . represent all of the mutual inductance terms. Mi2» Applying this general torque expression to the case of a 3(j) machine without damper windings the result is: 9 dLft P dLp P dLp Torque = 1/2 l / - ^ + 1/2 l / - ^ + 1/2 l / -.^- + C de ^A d0 ' B do dM, 9 dLp dM-R dM 1/2IFSI^ V B ^ ^ ^ " A'C ^ dM I«I AT AF d3 + UBIT dM BF + I.I CT do ^B^C da ^\F d3 4-14a do If damper windings are also to be included, the following terms must also be added to Eq. 4-14a terms above 2 ^Ln D •do dM p dL. KI AKQ . ^B^Q I I^ 05 ^ 4-14b 57 4-14a cont. dM dM "^C^D AKD dM + Ir>I B^D d BKD dM, dM. ? ^ + I I ""^KD . . . "••KDKQ d3 V ^ D ^ 0 — ^ ^D^Q — d ^ Many of these terms are zero. The others can be easily determined from the machine parameter expressions of Eq. 4-10, and 4-12 and are listed in Table 4-1. 58 TABLE 4-1 dM AKD de "= -Lakd sin 0 ^'^BKD d0 " -Lakd sin(o-120°) ^^CKD do ~ -Lakd sin(0 + 120°) ^^KQ _ -Lakq cos 0 do ^^BKQ do ^ = Lakq cos (0 - 120°) ^^CKQ _ Lakq cos (0 + 120°) do ""FKD do - do ''LA do ''LB do do " -2Lg2 sin (20) do -2Lg2 sin (20 ''Lc do " -2Lg2 sin (2o ""BC do ' -2Lg2 sin (2o) ''"AC do do + 120°) -120) = 0 59 TABLE 4-1 cont. dM AB dQ- = -2Lg2 sin (20 - 120) dM AF do = -Laf sin o ^•\F ~ao- = -Laf sin(e - 120) dM CF de = -Laf sin(e + 120) 60 The currents calculated in Figures IV-la tnrough IV-5 previously presented are now substituted into the above torque expression Eq. 4-14 and plotted over the same shaft angle range. Figure 17-6 is the plot of the calculated torque for the 3 phase machine without dampers. IV-6a 0Q = 0° case IV-6b e^ - 45° case IV-6c e^ = 180° case Figure IV-7 is the plot of the calculated torque for the 3 phase machine with dampers case (lp - 200 Amperes) IV-7a 0Q = 0° case IV-7b 0Q = 45° case IV-7C O Q = 180° case Figure IV-8 is the plot of fault torque for the non symmetrical fault examples given. IV-8a Single phase to ground IV-8b Phase to phase IV-8c Phase to phase to ground Several conclusions about the calculated fault torques can be drawn. The torque response to a symmetric fault is independent of the initial shorting angle. This holds for the case of a machine with and without damper windings. The torque response to a non symmetrical short however is not independent of the starting short angle. This 61 effect is displayed graphically in Figure r.'-9 for a phase A to ground fault. The peak minimum and maximum torque is tabulated for a range of initial shorting angles from 0 to 360 degrees. (Ip^ = 200 Amperes) The maximum torque occurs when the field and phase loops are both in line at o^ = 0°, and o 0 = 180° when the short occurs. 0 When field and phase have no common flux linkages at the time of the short, the resultant fault torque is a minimum at o^ = 90° and 0^ = 270°. This kind of torque response can be easily explained. The orientation of the field winding at the time of the short determines the orientation of the initial flux vector. When the initial flux vector is in line with the shorted phase the peak value of current induced in that phase is a maximum. a maximum in this orientation. Thus the fault torque will be An analogous explanation can be used when the initial flux vector is perpendicular to the shorted phase winding. In general for any shorting configuration the minimum torque occurs at the shorting angle of minimum flux linkages, and the maximum torque occurs when the field flux linking the phase(s) are at a maximum. The calculation of fault currents and torques by the methods described is a simple procedure. In machine faults where it is valid to consider saturation and resistive effects as being negligable this can be a useful tool to their calculation. 62 SHHrr RNC B000 >EGREES> E000 X I H000 U 2000 ZI a fr* 5 -H000 -E000 -B000 Figure IV-6a. at 0Q = 0° Fault torque 3 phase machine without dampers SHBFT Rf •ETSREDES > B000 E000 X I H000 Z U 2000 U -2000 Z if fil W Id K S S 5 -H000 -5000 -BB00 Figure IV-6b. Fault torque 3 phase machine without dampers at o^ = 45°. 63 EGRECS > X I H000 -8000 •' Figure IV-6c. at 0Q = 180°. Fault torque 3 phase machine without dampers a 3 -10000 •' Figure IV-7a. at 0« = 0° Fault torque 3 phase machine with dampers ^ 64 10000 Z 5000 K tl N 1^ y Figure IV-7b. Fault torque 3 phase machine with dampers at 0^ = 45°. 0 SHPFT BNGLE .(<^EEWSr5> I00BSB • X I S000 a 1 1 a s/ H p 5 a a -10000 - Figure IV-7c. at 0Q = 180°. Fault torque 3 phase machine with dampers 65 Figure IV-8a. iS00a Single phase to ground fault torque 4 <I>EnREC5> a /a a K 3 a 3 -15000 -f Figure IV-8b. Phase to phase fault torque 66 i 0000 DEEREErS> • a Figure IV-8c. R a H a Phase to phase to ground fault torque Shaft Shorting Angle :s' 10,01)0 en c ctr O 00 o CO to c o Q. CO <U Dc; i-10,0 o Figure IV-9. Tabulated peak minimum and maximum torque for Phase A to ground fault for the full range of shorting angles. CHAPTER V CONCLUSION The determination of machine inductance parameters is a significant problem to the precise calculation of fault torques and currents. The damper winding due to their lack of external connections and complex configuration are a specific problem. By making appropriate approxi- mations with respect to the flux linking the damper winding, the damper mutual inductances can be determined. The values of the damper self Inductances can be constrained to range of values greater than zero through use of the physical realizability equations developed in Chapter III. Use of the principal of conversation of flux linkages and the bounding criterion on the damper winding has useful applications when applied to a theoretical model of a proposed machine. The machine windings other than those of the damper can be very closely approximated from proposed design specifications. For this reason the bounded values of the damper winding also bound the potential fault torque and current response. design. This can be a considerable aid to machine If the range of fault torque response is known, a closer estimation of such physical parameters as shaft diameter, internal bracing, etc., can be made. Thus the size and weight of a proposed alternator can be minimized through the more precise prediction of the fault response by the conservation of flux linkage method. A necessary future step in the analysis of the machine parameters is the determination of the effect on the model of resistance and 67 68 saturation and resistance effects is commonly done to simplify the mathematics. If saturation is to be considered the ^ = LI relation- ship used in this thesis must change to some form of ^i) = L(I)I. The added complexity this adds to the flux linkage equations would also require a computer to solve. If hysterisis effects are also to be included in the saturation model some type of state equation technique may be necessary. REFERENCES 1. R. E. Doherty and 0. E. Shirley, Reactance of Synchronous Machines and its Applications, American Institute of Electrical Engineers Transaction, 1918, Volume 37, Part 2, p. 1209. 2. A. E. Fitzgerald and Charles Kingsley, Jr., Electrical Machinery, New york: McGraw-Hill Book Company, Inc., 1961. 3. Olle I. Elgerd, Electrical Energy Systems Theory: An Introduction, New York: McGraw Hill Book Company, 1971. 4. R. F. Franklin, Short Circuit Currents in Synchronous Machines, American Institute of Electrical Engineers Transaction, 1925, Volume 44, pp. 420-429. 5. Samuel Seely, Electromechanical Energy Conversion, New York: McGrawHill Book Company, Inc. 1962. 6. George B. Thomas Jr., Calculus and Analytic Geometry, Reading Mass., Addison-Wesley Publishing Company, 1969, Part 1, pp. 118121. 7. Charles A. Desoer and Ernest S. Kuh, Basic Circuit Theory, New York: McGraw-Hill Book Company, 1969. 69 i p