50KQ-3SB TM 50KQA, KQD007-019 CONSOLE WATER SOURCE HEAT PUMPS — PERFORMANCE DATA — CERTIFIED DIMENSION PRINTS © Copyright 2002 Carrier Corporation • Syracuse, New York 13221 Form 50KQ-3SB Replaces: 50KQ-2SB Printed in U.S.A. 7-02 Catalog No. 515-00017 Date: Supersedes: 50KQA 50KQD 50KQA, KQD007-019 CONSOLE WATER SOURCE HEAT PUMPS JOB NAME: LOCATION: BUYER: BUYER P.O.# UNIT NUMBER: MODEL NUMBER: PERFORMANCE DATA CERTIFIED BY: Rev: -3SB CARRIER# DATE: DESCRIPTION The 50KQA and KQD Water Source Heat Pumps are single package consoles with self-contained line voltage thermostats for commercial applications. Units are factory wired, piped, charged and tested, ready for installation. The low temperature unit (50KQD) is available with an extended operating range of 40 to 110 F. STANDARD FEATURES Standard safety features include: high-pressure switch, freeze protection switches, and loss of charge protection. Each unit is run tested at the factory to ensure proper operation of all components and safety switches. Anti-short cycle timer provides a minimum off-time to prevent unit from short cycling. Fan motors and compressors are sound isolated. The water-to-refrigerant heat exchanger has copper inner and steel outer tubing to provide corrosion resistance protection. Units are ARI (Air Conditioning & Refrigeration Institute) Standard 320-93 certified. Filter racks permit easy filter replacement. Convenient large service access panels can be used for on-site testing or refrigerant recovery. The standard Complete C electronic controls provide short cycle protection, random start, remote alarm, and intelligent reset. Self-diagnostic capability includes fault-type indication and memory. An optional Deluxe D electronic controller offers advanced system control capabilities such as night setback and emergency shutdown. PERFORMANCE DATA UNIT Operating Weight _____________________________________________ lbs Shipping Weight______________________________________________ lbs COOLING Total Capacity_______________________________________________Btuh Sensible Capacity ____________________________________________Btuh Unit CFM ____________________________ at ______________ in. wg ESP Total Heat of Rejection________________________________________Btuh Entering Air Temperature_______________ °F db ________________°F wb Entering Water Temperature______________________________________°F Leaving Water Temperature ______________________________________°F GPM_________________________________________________________ Water Pressure Drop____________________________________________ ft Unit Power Input _____________________________________________kW EER (ARI) ____________________________________________________ HEATING Total Capacity ______________________________________________ Btuh Unit CFM ___________________ at _______________________in. wg ESP Total Heat of Absorption______________________________________ Btuh Entering Air Temperature _______________________________________ °F Entering Water Temperature _____________________________________ °F Leaving Water Temperature _____________________________________ °F GPM _________________________________________________________ Water Pressure Drop ____________________________________________ ft Unit Power Input________________________________________________ COP (ARI) ____________________________________________________ ELECTRICAL DATA Power Supply to Unit _________ Volts___________Phase__________Hertz Compressor RLA _______________________________________________ Fan FLA ______________________________________________________ Unit Minimum Circuit Amps ______________________________________ Maximum Fuse Amps____________________________________________ FACTORY-INSTALLED OPTIONS Return Air Configurations: Return Bottom, Discharge Top with Left or Right configuration Return Front, Discharge Top with Left or Right configuration Base: 3-in. base 5-in. base Deluxe D Controls Locking Control Panel 2 Motorized Damper Motorized Water Valve Autoflow Regulator, 2.5 GPM per ton Autoflow Regulator, 3.0 GPM per ton PremierLink™ Controller Fused or Unfused Disconnect Switch 20 A Plug and Cord Cupronickel Heat Exchangers FIELD-INSTALLED ACCESSORIES Hose Kit (Stainless steel or galvanized) Hose Kit assemblies with GPM Autoflow valves Ball Valves (with and without Pressure Temperature ports) Y Strainers (with plugs and blow down valves) Solenoid Valves Thermostats Loop Controllers Adjoining Room Kit Discharge Grille for Adjoining Room Kit Duct Extension for Adjoining Room Kit __________________________________________________________ CERTIFIED DIMENSION PRINT 50KQA,KQD BOTTOM RETURN CABINET DIMENSIONS — RIGHT-HAND PIPING 5 (127) 16 (406) 1 1/2 (38) Air Discharge 30° Control Access Door 24 (610) Air Inlet AIR INLET AREA 9 1/2 (241) 48 (1219) 10 (254) FRONT VIEW 9 1/2 (241) 3 (76) R.H. Pipe & Electric Area 7 1/4 (184) 1 1/2 (38) 1 1/2 (38) 3 1/4 (83) 1 (25) 1 (25) *Optional 5-in. (127) subbase will increase damper opening to 3.63 in. (92) high and increase overall unit height by 2 in. (51). 4 1/2 (114) REAR VIEW REAR ACCESS 21 (533) 1 5/8 (41) DAMPER OPENING* 11 3/4 (298) 48 (1219) 3 (76) 13/16 (20) OPTIONAL DAMPER 18 1/8 (460) NOTE: All measurements in inches. Measurements in parentheses are in millimeters. 3 CERTIFIED DIMENSION PRINT 50KQA,KQD BOTTOM RETURN CABINET DIMENSIONS — LEFT-HAND PIPING 12 1/2 (317) 1 1/2 (38) 1 1/2 (38) Air Discharge 30° Control Access Door 24 (610) AIR INLET AREA AIR INLET 48 (1219) 9 1/2 (241) 7 1/4 (184) 1 1/2 (38) 3 (76) 10 (254) FRONT VIEW L.H. Pipe & Electric Area 9 1/2 (241) 1 1/2 (38) 3 1/4 (83) 1 (25) *Optional 5-in. (127) subbase will increase damper opening to 3.63 in. (92) high and increase overall unit height by 2 in. (51). 1 (25) REAR VIEW 4 1/2 (114) REAR ACCESS 21 (533) 1 5/8 (41) DAMPER OPENING* 11 3/4 (298) 13/16 (20) 3 (76) 18 1/8 (460) 48 (1219) NOTE: All measurements in inches. Measurements in parentheses are in millimeters. 4 OPTIONAL DAMPER CERTIFIED DIMENSION PRINT 50KQA,KQD FRONT RETURN CABINET DIMENSIONS — RIGHT-HAND PIPING AIRFLOW OPTIONS PLAN VIEW 16 (406) 5 (127) 1 1/2 (38) Air Discharge 30° Control Access Door 21 (533) Filter Air Inlet 48 (1219) 10 (254) FRONT VIEW NO DAMPER AVAILABLE WITH FRONT RETURN OPTION. 1 1/2 (38) 41 3/4 (1041) R.H. PIPE & ELECTRIC AREA 9 1/2 (241) BLOCK OFF PLATE ON BOTTOM OF CHASSIS 1 1/2 (38) 48 (1219) 3 1/4 (83) 1 (25) 1 (25) 4 1/2 (114) REAR VIEW 21 (533) REAR ACCESS 48 (1219) NOTE: All measurements in inches. Measurements in parentheses are in millimeters. 5 CERTIFIED DIMENSION PRINT 50KQA,KQD FRONT RETURN CABINET DIMENSIONS — LEFT-HAND PIPING 12.5 (318) 1.5 (38) 1.5 (38) Air Discharge 30° Control Access Door 21 (533) Filter Air Inlet 48 (1219) FRONT VIEW 10 (254) NO DAMPER AVAILABLE WITH FRONT RETURN OPTION. 41.75 (1060) 1.5 (38) L.H. PIPE & ELECTRIC AREA 9.5 (241) BLOCK OFF PLATE ON BOTTOM OF CHASSIS 0.75 (19) 3.5 (89) 48 (1219) 1 (25) 4.5 (114) REAR VIEW REAR ACCESS 20 (508) 48 (1219) NOTE: All measurements in inches. Measurements in parentheses are in millimeters. 6 1 (25) 21 (533) CERTIFIED DIMENSION PRINT CHASSIS DIMENSIONS 50KQA,KQD007,009,012,015,019 POWER SUPPLY IN 3 3/8 (86) 41 (1041) 2 (51) 1 (25) WATER OUT 30° WATER IN CONTROL BOX 4 (182) 3 1/2 (89) 6 1/2 (165) 1 5/16 (33) 20 7/16 (519) 2 (51) 16 9/16 (420) 13 1/2 (343) BLOWER DECK CONDENSATE RELIEF COMPRESSOR ACCESS PANEL BLOWER ACCESS PANEL 3 9/32 (83) 3/4 (19) 9 1/2 (241) 3/4 (19) FRONT VIEW (LH) SIDE VIEW (LH) POWER SUPPLY IN 3 3/8 (86) 41 (1041) 2 (51) WATER IN 1 (25) 30° WATER OUT CONTROL BOX 4 (182) 20 7/16 (519) 3 1/2 (89) BLOWER DECK 6 1/2 (165) 2 (51) 16 9/16 (420) BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 3/4 (19) 3/4 (19) FRONT VIEW (RH) 13 1/2 (343) CONDENSATE RELIEF 1 1/2 (33) 1 (25) 9 1/2 (241) SIDE VIEW (RH) NOTE: All measurements in inches. Measurements in parentheses are in millimeters. 7