Residual current devices DPNa Vigi Protection earth leakage protection PB104343-40 Function b The DPNa Vigi residual current device provides complete protection of final circuits (overcurrents and insulation faults): v protection of people against electric shocks by direct contacts (10 and 30 mA), v protection of people against electric shocks by indirect contacts (300 mA), v protection of installations from fire hazards (300 mA). b Fast closing. b Positive break indication. b Display of earth fault on the front panel. Catalogue numbers DPNa Vigi Auxiliaries 1P+N DB119073 Without auxiliaries Curve B N 1 Width in 9-mm modules Type A Type AC Rated current R Sensitivity 30 mA 300 mA 10 mA 30 mA 6A 10 A 13 A 19611 19613 - - - 19790 19791 19792 16 A 20 A 25 A 32 A 40 A 19615 19616 19617 19618 - - - 19793 19794 19795 19796 - Sensitivity 30 mA 300 mA 10 mA 30 mA 6A 19621 19430 - 19531 10 A 19623 19431 19304 19532 13 A - - - 19533 16 A 19625 19432 19305 19534 20 A 19626 19433 - 19535 25 A 19627 19434 - 19536 32 A 19628 19435 - 19537 40 A 19629 19436 - 19538 4 N 2 1P+N Curve C Rated current Voltage rating (Ue) Operating frequency Accessories 4 230 V AC 50/60 Hz Module 91902 Conformity with standards b National standard*. b European standard EN 61009. b International standard IEC 61009. * Information to be provided by the country. version: 1.1 91943E.indd Residual current devices DPNa Vigi (cont'd) Protection earth leakage protection Tightening torque 6 to 40 A 3.5 N.m Copper cables rigid PZ2 flexible or with end-piece DB112805 15 mm Rating DB112804 DB122728 Connection 5.5 mm Insulated connector 3 Comb busbar (bag of 2) 14885 13 outgoing feeders 14880 1 to 10 mm2 DB119152 2 1 to 16 mm2 24 outgoing feeders 14890 Mounting 4 5 Padlocking facility (bag of 2 parts) Spacer 6 Clip-on terminal markers 7 Interpole barrier 90943E.indd 26970 27062 27001 version: 1.1 Residual current devices DPNa Vigi (cont'd) Protection earth leakage protection Technical data Main characteristics Earth leakage protection with instantaneous tripping Setting temperature for ratings 6 to 40 A 10, 30, 300 mA Tripping curve Curve B: the magnetic tripping devices act at between 3 and 5 In Curve C: the magnetic tripping devices act at between 5 and 10 In 30°C Breaking capacity EN61009 Rated breaking capacity (Icn) Rated residual breaking and making capacity (IDm) 4,500 A 4,500 A Endurance Ratings (A) Mechanical endurance Number of O/C cycles 20,000 6 to 40 Electrical endurance under rated current Number of O/C cycles 20,000 y 20 A 10,000 u 25 A Autres caractéristiques Degree of protection IP4/IPxxD for the part outside of the enclosure Insulation voltage (Ui) 400 V Rated impulse withstand voltage (Uimp) 4 kV Service temperature Type AC: from -5°C to +60°C Type A and type A-si: from -25°C to +60°C Storage temperature -30°C to +70°C 8/20 µs impulse withstand 250 Â Limitation class 3 Insulation class 2 Tropicalization Treatment 2 (relative humidity 95% at 55°C) Dimensions DB122729 36 5.5 44 16 4.8 81 45 3.6 7 Weight Residual current device Type 1P+N Accessories page 91902 Comb busbars: page 91906 Auxiliaries: page 90142 DPNa Vigi 125 g Tightening torque: page 90179 version: 1.1 Interference: page 91105 Discrimination: page 91105 Test button: page 91105 91943E.indd