I am writing in regards to the proposed Texas Real Estate Commission (TREC) Home Inspectors Standards of Practice that is being considered for adoption. While the Inspector’s Advisory Committee and the SOP Sub-committee have done an outstanding job addressing many of the issues with the old SOP I am of the opinion that there are several discrepancies and/or issues with the proposed SOP and I would like to bring just of them one to your attention for consideration prior to the potential adoption of the SOP in June. The Proposed SOP contains the following wording in the Electrical Section: (b) Specific limitations for service entrance and panels. The inspector is not required to: (1) determine present or future sufficiency of service capacity amperage, voltage, or the capacity of the electrical system; (2) test arc-fault circuit interrupter devices when the property is occupied or damage to personal property may result, in the inspector’s reasonable judgment; (3) report the lack of arc-fault circuit interrupter protection when the circuits are in conduit; (4) conduct voltage drop calculations; (5) determine the accuracy of overcurrent device labeling; (6) remove covers where hazardous as judged by the inspector; (7) verify the effectiveness of overcurrent devices; or (8) operate overcurrent devices. After having read (b)(3) and not being familiar with that exception I then asked one of the subcommittee members where it was stated in any formal context, i.e. a national code or the like. He told me NEC 210.12 exceptions 1 & 2 provided for that. Further examination of that code section led me to question the sub-committee’s interpretation of the rule & exceptions. Here is a page from www.NECPlus.com that describes that NEC code in more detail (note: I have paraphrased portions of that article for clarity and brevity): 210.12 Arc-Fault Circuit-Interrupter Protection. (A) Definition: Arc-Fault Circuit Interrupter (AFCI). A device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-energize the circuit when an arc fault is detected. (B) Dwelling Units. All 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter, combination-type, installed to provide protection of the branch circuit. Exception No. 1: Where RMC, IMC, EMT or steel armored cable, Type AC, meeting the requirements of 250.118 using metal outlet and junction boxes is installed for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a combination AFCI at the first outlet to provide protection for the remaining portion of the branch circuit. Exception No. 2: Where a branch circuit to a fire alarm system installed in accordance with 760.41(B) and 760.121(B) is installed in RMC, IMC, EMT, or steel armored cable, Type AC, meeting the requirements of 250.118, with metal outlet and junction boxes, AFCI protection shall be permitted to be omitted. Again, I do not see where there is a blanket statement that AFCI protection is not required for branch circuits in conduit, except for fire alarm systems. Clearly, Exception 1 still requires AFCI protection just not at the breaker box but rather at the first outlet. Unfortunately, at this point in time that would be impossible since such an outlet mounted AFCI doesn’t yet exist. I posed my AFCI/conduit question to several state & national Home Inspection industry technical leaders. Here is what a few of them had to say: I agree w/ Mike. This would not be the first nor will it be the last of incorrect code opinions that spew forth from the IC members. This is frankly why they have no business getting involved in code based inspections. – Texas based ICC certified inspector I view this with great apprehension, possibly because I remember what an absolute mess Texas made of their GFCI testing requirements, where they insist inspectors use something that isn't listed for what they must use it for, and where they must report as defective things which are not defective anywhere that has blue sky... but I digress. What do they mean by "when conduit is used?" Are they somehow under the impression that the exception applies to any installation with "conduit." First off, that word isn't used in the exceptions. Exception #1 talks about RMC, IMC, EMT, or steel-armored AC. The latter two are not conduits; one is a tubing system and the other is a cable system. Next, the exception only has to do with the LOCATION of the AFCI device, and is intended to accommodate the yet-to-be-manufactured "outlet-type" AFCI. No such device exists. There has never been an installation that utilizes exception #1. If they think they have seen one, take them on a snipe hunt next. This couldn't be more wrong. I can't wait to see how they define "missing AFCIs." If they can mangle it as badly as their misinterpretation of these exceptions, it should be a real howler. – Nationally known code book author Mike…IMO you are correct – Prior Inspector Committee member I have not found one TREC home inspector, code certified inspector nor any other person that agrees with paragraph (b)(3), as written, therefore I would ask that the Advisory Committee please reconsider that exception and delete it from the proposed SOP or, at a minimum, reword it. Regards, Mike Boyett TREC #7290