Design
The electronic plug-in type amplifier pQ 11 is used to control proportional pressure and directional control valves. It is mounted directly on the proportional solenoid and secured by means of a screw.
Function
The amplifier supplies a direct current for the control of the proportional solenoid. This current is proportional to the set point at the amplifier input. In conjunction with a proportional valve, this allows a pressure or a flow to be set to any desired value.
Accessories include set point adjusters.
l Control of one solenoid l Mounts directly on valve body l Standard voltage and current signals for set point inputs l Control from computer also possible l Impressed solenoid current, thus no change in the controlled variable due to environmental influences l
(e.g. temperatures and mains fluctuations)
Plug-in type connection for proportional solenoid with contact arrangement to DIN 43650, Type A or B.
Infinitely adjustable between 0 ... 270° l Supply via connector to DIN 43651 or cable, 2 m long
General parameters
Designation
Symbol
Design
Degree of protection
Mounting position
Ambient temperature range
ϑ
U
Weight
Connection
[°C]
[kg]
Drive electronics pQ11
0660689.0000
Optional
–20 ... +50
0.18
Cable 6 x 0.5mm
2 + PE 2 m long, screened
Alternatively:
6-pin + PE connector to DIN 43651
Stuttgarter Straße 120, D-70736 Fellbach
Tel.: +49 (0)7 11 / 52 09-0
Fax: +49 (0)7 11 / 52 09-6 14
Back
Electrical parameters
Supply with residual ripple
≤
10%
(U
B
) [VDC]
Output current for solenoid 1)
Current consumption
Plug-in type amplifier
Solenoid resistance R
20
Output for supply of set point adjusters
[
[mA]
[mA]
Ω
]
Zero point adjustment
(selectable via jumper)
Zero point shift (offset) at set point w = 0 or:
[% I
A max.]
Zero point jump with set point w
≥
2% [% I
A max.]
Drive limitation [% I
A max.]
Superimposed dither (amplitude) [% I
A max.]
Dither frequency
(internally selectable)
Ramp shaper
Adjustment time
(selectable via jumper)
Valid for rising or falling ramp
Ramp off:
Ramp on:
Set point w (selectable via jumper)
Voltage input
Set point U
E
Input resistance R i
Current input:
Set point I
E
Set point I
E
Input resistance R i
[
[Hz]
[ms] approx. [s]
[V]
Ω
[mA]
[mA]
[
Ω
]
]
Elektromagnetische Verträglichkeit
Störfestigkeit
18 ... 32
Version (see Type survey, Page 3)
0 ... 1000 mA
0 .. 400 0 ... 800 0 ... 1000
400
2.5 ... 28
15V, 3mA
0 ... 30
0 ... 30
10 ... 100
0 ... 30
40/80
< 2 2)
0.18 ... 18
0 ... 10
> 330k
0 ... 20
4 ... 20
< 135
2)
700
2.5 ... 14
800
2.5 ... 11
Einstrahlung nach EN 50140 und 50141
Burst nach DIN 50082 Teil 2
IEC 801-4
0 ... 2400 mA
0 ... 1600 0 ... 2400
1400
2.5 ... 7
2200
2.5 ... 4,5
1) selectable via jumper
2) with jump-like change of set point
∆ w
= 100%
2 7502961.06.11.96
A
B
C
Solenoid current selection
0 ... 1000 mA 0 ... 2400 mA
I
A max.
I
A max.
400 mA
800 mA
1000 mA
A
C
1600 mA
2400 mA
Design Output currents 1)
[mA]
0 ... 2400 mA 0 ... 1600 / 2400
0 ... 1000 mA 0 ... 400 / 800 /
1000
0 ... 2400 mA 0 ... 1600 / 2400
Form A
(wide) l l
Solenoid connection
Contact arrangement to
DIN 43650
Form B
(narrow) l l l l l l
Type of connection
Cable, 2 m long Connector to
DIN 43651 l l l l l l l l
Connection diagram
01
02
01
No.
02
01
02
01
02
1) internally switchable
2) Cable plug to be ordered separately (Cat. No. 0660689)
[mm]
01
Version with cable
Dimensional drawing
01
02
01
No.
02
01
02
01
02
02
Version with connector to DIN 43651
Cat. No.
5980081 2)
5980085
5980082 2)
5980086
5980083 2)
5980087
5980118
5980119
7502961.06.11.96
3
01
Version with cable
02
Version with connector to DIN 43651
1) Recommended fuse: M 1.0 A for amplifier 5980082, 5980083, 5980086 and 5980087
M 2.5 A for amplifier 5980081 and 5980085
2)
3)
For allocation, see table on Page 8, Item 3.4. Measurement at connection 2
Screen connection: Setpoint of 0 V.
4 7502961.06.11.96
Trimming potentiometer E "A B" (p/Q)
If the customer-specific working range represents only part of the valve adjustment range, the trimming potentiometer
"A B" can be used to match the working range to the full set point signal from 0 to 100%. This provides the possibility of assigning a defined pressure or a defined flow volume to the end point in order to obtain greater resolution.
Adjustment: Trimming potentiometer D1 "NUL"
Preselection: Jumper D2
(for instructions to this see Page 7)
Zero-shift (Fig. 1)
(Jumper D2 to position "OFS" = offset)
Via the trimming potentiometer "NUL“ the solenoid current can be increased. This provides the possibility of assigning a defined pressure or defined flow volume to the start point
(set point = 0)
Zero-step function (Fig. 2)
(Jumper D2 to position "SPR" = jump)
By means of the zero-step function, valve overlapping can be eliminated.
As soon as the setpoint adjustment is exceeded by more than 2% the solenoid current is raised corresponding to the adjustment of the trimming potentiometer "NUL". This way it is assured that with set point = 0 the solenoid current is
0 mA.
Fig. 1
(Fig. 3)
Trimming potentiometer F2 "RMP"
The ramp module provides a ramp-like change of the solenoid current if the set point changes abruptly. The final value of the solenoid current thereby corresponds to the set point. The adjustment time between two working points can be adjusted, measured with a set point change of
100%. By means of jumper F1 the ramp shaper can be disconnected.
Fig. 2
Trimming potentiometer C2 "OSZ"
In order to improve the hysteresis characteristics in a valve, static friction on the valve piston must be avoided. This is achieved by superimposing a dither signal on the valve current. Via the trimming potentiometer "OSZ" the amplitude of the superimposed current can be adjusted within the range of 0 to 30% of the rated current. Optimum setting is achieved when small changes in the set point are registered on the final control element. The minimum dither amplitude possible should be used at all times.
Fig. 3
7502961.06.11.96
5
Designation
E Modulation limitation "A B"
D1 Zero-point "NUL"
F2 Ramp "RMP"
C2 Superimposed dither "OSZ"
[mA]
[%I
A
max.] approx. [s]
[%I
A
max.]
Range adjustment
Direction of rotation on trimming potentiometer counterclockwise clockwise
10 ... 100%
0 ... 30
Basic setting, factory adjusted
100%
0
0.18 ... 18
0 ... 30
18
15
A Set point preselection
Set point 0 ... 10 V 1) 0 ... 20 mA 4 ... 20 mA
Switch positions
B Selection of solenoid current
Type 0 ... 1000 mA
0 ... 400 Output current range
[mA]
Jumpers A
0 ... 800
B
0 ... 1000
C
0 ... 2400 mA
0 ... 1600
A
0 ... 2400
C
1) 1)
1) Factory adjusted
6 7502961.06.11.96
C1 Superimposed dither
Frequency [Hz] 40 1) 80
Switch positions
D2 Zero-point adjustment
Zero-point shift
Zero jump
F1 Ramp shaper
Ramp OFF
Ramp ON
Jumper
Position "OFS" 1)
Position "SPR"
Jumper
Position "OFF" 1)
Position "ON"
1) Factory adjusted
G Check points
Mp1 = 0 V (reference potential)
Mp2 = Set point
Mp3 = Solenoid current
7502961.06.11.96
7
1.1 Supply: 18 ... 32 VDC, excess voltage leads to amplifier defects.
1.2 The plug-in type amplifier should not be installed too close to a power relay.
1.3 The conductors to the external set point adjusters
(drive) must be screened. The screening must be connected on one side to terminal 2.
(below order must be strictly adhered to).
2.1 Preselection of set point
On switch A "UE/IE"
Select switch position according to the given setpoint.
2.2 Selection of solenoid current
On jumpers B "IA"
Select jumper according to the required current value.
2.3 Dither
2.3.1 Dither frequency
On switch C1 "f" / Select 40 or 80 Hz
frequency via switch
2.3.2 Imposed dither (amplitude)
On trimming potentiometer C2 "OSZ"
For adjustment of the dither a setpoint
≤
20%
must be selected.
Turn trimming potentiometer clockwise until the
manipulated variable changes due to small changes
on the setpoint adjuster. Make sure, however,
always to select the smallest possible value.
2.4 Zero-point adjustment
2.4.1 Zero-point shift ("OFS")
a) Switch jumper D2 to position "OFS"
b) Adjust setpoint to zero
c) Turn trimming potentiometer D1 "NUL" clockwise
until the desired value of the flow volume or pres-
sure has been reached with the setpoint
adjusted to zero.
2.4.2 Zero-point jump
a) Switch jumper D2 to position "OFS"
b) Adjust setpoint to zero
c) Turn trimming potentiometer D1 "NUL" clockwise until the valve opens. Then turn it anticlockwise until the valve has closed again.
d) Switch jumper D2 to position "SPR"
2.5 Drive limitation
Trimming potentiometer E "AB"
a) Turn trimming potentiometer E "AB" approx. 12 counterclockwise
b) Adjust set point to max. value
c) Turn trimming potentiometer E "AB" clockwise
until the desired value of the flow volume or
pressure has been reached.
2.6 Ramp shaper
2.6.1 Ramp off
Switch jumper F1 to position "OFF"
2.6.2 Ramp on
a) Switch jumper F1 to position "ON"
b) Set trimming potentiometer F2 "RMP" to the
longest adjusting time by turning it clockwise.
c) By turning the trimming potentiometer F2
anticlockwise set the adjusting time so that the
desired transient response is achieved when the
set point is changed.
3.1 Measure the amplifier supply voltage
(+18 ... 32 V) between terminals 5 and 1, if necessary, check the supply cable and the fuse in this.
3.2 Measure the internal amplifier operating voltage
(+15 V) between terminals 4 and 1.
3.3 Measure the set point input signal
between check points Mp2 and Mp1
Measuring values according to table.
Check point
Check point Mp1 = 0 V (reference potential)
Check point Mp2 = Set point
Definition
Set point
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
Measured value
(measured against Mp1)
0 ... 10 V
0 ... 2 V
0.4 ... 2 V
3.4 Measuring the solenoid current
The solenoid current can be measured by means of a
voltmeter.
Check point Mp3 (solenoid current).
Measure U
Mp3
= f (I
solenoid
) for measurement of sole-
noid current by means of a voltmeter with R i
≥ 1 M Ω.
For assignment, see table.
Definition U = f (I
Solenoid
)
Type Assignment Measured value
(measured against
Mp1)
0 ... 1000 mA 1 mV corresp. to 3 mA 0 ... 325 mV
0 ... 2400 mA 1 mV corresp. to 10 mA 0 ... 240 mV
Measure between check points Mp3 and Mp1 and,
in the case of a plug-in type amplifier, also between
plug pins 2 and 6.
With setpoint = 0, the solenoid current must be 0 mA
(measurement 0 mV). The trimming potentiometer for
zero-point lift "NUL" must be set to zero (left-hand stop).
Important: The solenoid current can be measured only when the amplifier on the solenoid is plugged in.
8 7502961.06.11.96
Designation Specification
Set point adjuster
SE 01
Angle of rotation 270°
Set point adjuster
SE 02
Angle of rotation 360°
Set point adjuster
SE 03
Digital
Set point adjuster
SE 13
For pressure and flow volume
For pressure and flow volume
For pressure and flow volume
Transformer
TR 21
Transformer
TR 22
Plug connector for amplifiers 5980081,
5980082, 5980083 and
5980114
Set point switch 1)
SU 01
2 internal set points
Cat. No.
5998534
5998536
5998647
For pressure and flow volume
Output 0 ... 20 mA
Output 4 ... 20 mA
115/230 VAC
24 VDC, 3.0 A
380 VAC
24 VDC, 6.0 A
6-pin + PE
DIN 43651
5998774
5998775
5998609
5998611
0660689
5998737
1) Possible only with plug-in type version
Publication
7501675
7501782
7501783
7502504
7501789
–
7502595
7502961.06.11.96