i-on160 Installation Guide

advertisement
i-on1000EX
Security System
Installation Guide
Issue 2
© Eaton’s Security Business. 2014
IN NO EVENT WILL EATON’S SECURITY BUSINESS BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL , OR INDIRECT LOSS OR
DAMAGE, INCIDENTAL DAMAGES, STATUTORY DAMAGES, EXEMPLARY DAMAGES, LOSS OF PROFITS, LOSS OF REVENUE,
LOSS OF ANTICIPATED SAVINGS, LOSS OF BUSINESS OR OPPORTUNTIY, LOSS OF GOODWILL OR INJURY TO
REPUTATION, LIQUIDATED DAMAGES OR LOSS OF USE, EVEN IF INFORMED OF THE POSSIBILITY OF SUCH DAMAGES.
EATON’S SECURITY BUSINESS’S LIABILITY FOR DAMAGES ARISING OUT OF OR RELATED TO A PRODUCT SHALL IN NO
CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT FROM WHICH THE CLAIM ARISES. TO THE EXTENT PERMITTED
BY APPLICABLE LAW, THESE LIMITATIONS AND EXCLUSIONS WILL APPLY WHETHER EATON’S SECURITY BUSINESS’S
LIABILITY ARISES FROM BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING BUT NOT LIMITED TO
NEGLIGENCE), STRICT LIABILITY, BY OPERATION OF LAW, OR OTHERWISE.
Every effort has been made to ensure that the contents of this book are correct. The contents of this book
are subject to change without notice.
Printed and published in the U.K.
This manual applies to the i-on1000EX control unit with version 4.04 software and higher.
For Your Safety
This book contains several passages alerting you to potential problems or hazards. Each of these are
marked by the words Note, Caution or WARNING.:
Note:
Describes conditions that may affect the proper functioning of the equipment (but will not
damage the equipment).
Caution:
Describes actions that will physically damage the equipment and prevent its proper
function.
WARNING:
Describes actions that are hazardous to health, or cause injury or death.
Please pay particular attention to these marked passages.
Other Publications for the i-on1000EX:
The following guides are available from the Eaton’s Security Business website (www.coopersecurity.co.uk):
Quick User Guide
Brief instructions for setting and unsetting alarm systems based on
i-on control units.
i-on Range Engineering Guide
A detailed description of the Installer’s programming options
available for all i-on control units.
i-on Range Administrator’s Guide
Detailed notes for the system administrator of an alarm system
based on the i-on40, i-on30EX, i-on50EX i-on160EX and
i-on1000EX.
Web Server Setup Guide
Instructions on how to configure a Windows PC or laptop to use the
built-in web browser interface for installation programming.
Eaton’s Security Business
Downloader Quick Guide
Instructions for how to installer Eaton’s Security Business
Downloader on your PC or laptop, and connect to i-on control units.
i-on Updater Installation and User
Guide
Instructions on how to install Updater on your PC and use it to
update the software on your i-on control unit (not available for ion16).
Page ii
CONTENTS
1. Introduction ..................................................... 1
Communications ............................................ 1
Partitions ....................................................... 1
Installer Programming Interface...................... 2
About this Guide ............................................ 2
2. Before You Begin ............................................ 3
Preparation ....................................................... 3
Radio Site Survey .......................................... 3
Siting the Control Unit and Wired Zone
Expanders ..................................................... 3
Siting Keypads ............................................... 3
Siting Wireless Zone Expanders..................... 3
Guided Tour ..................................................... 4
The Control Unit ............................................. 4
Keypads ........................................................ 6
Expanders ..................................................... 8
Power Availability............................................ 10
Bus Cabling Requirements ............................. 10
Cable Type .................................................. 10
Cable Segregation ....................................... 10
Cable Configuration and Length ................... 10
Bus Termination........................................... 11
Voltage Drop................................................ 11
3. Installation ..................................................... 13
Step 1. Fit the Control Unit Case ..................... 13
Fitting........................................................... 13
Fitting Plastic Feet and Tamper Sleeve ........ 13
Fitting tamper Shroud................................... 13
Fitting Case Back to Wall ............................. 13
Installing the Lid/Back Tamper ..................... 13
Step 2. Run Bus Cable ................................... 14
Step 3. Fit and Connect the Keypad(s) ............ 14
Siting the Keypad(s) ..................................... 14
Fitting Keypads ............................................ 14
Connecting Keypads .................................... 14
Keypad Addressing ...................................... 15
Backlight Control for i-KP01 ......................... 15
Backlight Control for KEY-K01/KP01/KPZ01 15
Tone Volume – All Keypads ......................... 17
Engineering Keypad..................................... 17
Step 4. Fit and Connect Expanders ................. 17
Connecting an Expander to the Bus ............. 18
Addressing Expanders ................................. 18
Expander Loudspeakers .............................. 18
Step 5. Connect Control Unit to Mains ............ 18
Mains Cabling .............................................. 18
Step 6. Connect Wired Zones ......................... 18
Four Wire Closed Circuit Connections .......... 18
Two-Wire Closed Circuit Connections .......... 19
Fully-Supervised Loop Connections ............. 19
Step 7. Connect Wired Outputs....................... 20
Wired External Sounders (Optional) ............. 20
Auxiliary Tamper .......................................... 20
Wired Outputs on Expanders ....................... 20
Wired External Sounders on Expanders ....... 21
Remote Loudspeakers (Optional) ................. 21
Output on KEY-KPZ01 ................................. 22
Step 8. Fit a Plug-By Communicator ............... 22
Step 9. Fit and Connect Battery ...................... 23
Step 10. Power-up, Select Main Settings and Set
Addresses ........................................................ 23
Leaving the Installer Menu ........................... 25
Re-Entering the Installer Menu..................... 25
Defaulting Access Codes ............................. 26
Restoring Factory Defaults at the Control Unit
.................................................................... 26
Transferring to Another Keypad ................... 27
Step 11. Commission the System ................... 27
Install Detectors and Other Peripherals ........ 27
Program the System .................................... 28
Handover to the User ................................... 28
Installer Menu ................................................. 29
4. Maintenance .................................................. 31
Replacing or Removing Wired Keypads ....... 31
5. Technical Specification ................................ 31
General .......................................................... 31
Capacities ...................................................... 31
Security .......................................................... 32
Power Supply ................................................. 32
EN50131-6 ratings ....................................... 32
Electromagnetic Compatibility ......................... 33
Outputs .......................................................... 33
Sounder Volume Levels (at 1m) ................... 33
Fuses ............................................................. 33
Electrical Safety.............................................. 33
Other .............................................................. 33
Radio Expander and Keypads ...................... 33
Compliance Statements .................................. 34
Compatible Equipment ................................... 34
HUD ............................................................ 34
Detectors ..................................................... 34
Sounders ..................................................... 34
Setting / Unsetting – Keypads ...................... 34
Setting / Unsetting - Fobs............................. 34
Communicators ........................................... 34
Accessories ................................................. 34
Page iii
i-on1000EX
This page is intentionally blank.
Page iv
i-on1000EX
1. Introduction
external siren, 4-button remote control, radio Hold
Up device and remote radio keypad.
The i-on1000EX is a control unit for a hybrid
wired/wirefree alarm system intended for
domestic, commercial or industrial use.
This control unit is designed and approved to be
used as part of a Security Grade 3 system. The
control unit is also approved to operate as part of
a Security Grade 2 system.
The control unit comprises a steel case containing
the control unit PCB (printed circuit board), power
supply and space for up to two backup batteries.
If you install any radio devices, this will limit
approval to Security Grade 2.
The control unit PCB provides terminals for 10
buses. Each bus allows you to connect up to 25
peripheral devices using standard 7/0.2mm fourwire alarm cable. The peripheral devices can be
any mixture of keypads or zone expanders (for
wireless or wired detectors).
Alternatively, for retrofit applications, a "pair
buses" option (displayed during initial
configuration) allows a bus to support double the
number of devices, up to a system maximum of
250. The Pair Buses option allows you to pair
consecutively numbered buses (e.g. 0 and 1, or 4
and 5). In this case, you connect devices to the
first bus (e.g. 0) and leave the second bus in the
pair unconnected.
Note: If the system uses radio HUDs and no other
radio transmitters, the system can be approved as
Grade 3, provided the rest of the system meets
Grade 3 standards.
Communications
The i-on1000EX provides sockets for an add-on
communication module. The available modules
are:
i-dig02
(ATS2)
A switched telephone network
(PSTN) module that allows the
control unit to report alarm
information using standard
protocols such as Fast Format, SIA
and Contact ID, and can also send
text messages over the Public
Switched Telephone Network
(PSTN). The i-dig02 also allows
remote maintenance using Eaton’s
Security Business Downloader
software.
i-sd02
(ATS2)
A speech dialler and PSTN module
that allows the control unit to send
recorded speech messages and
report alarm information using
standard protocols such as Fast
Format, SIA and Contact ID. The
module can also send text
messages over the PSTN. The
i-sd02 also allows remote
maintenance using Eaton’s Security
Business Downloader software.
i-gsm02
(ATS2)
A GSM module that allows alarm
reporting, speech messaging and
SMS text messaging over the
mobile phone network. Note that a
SIM card is not included with the
module.
The control unit PCB also provides a range of
connectors for outputs and communicators.
The i-on1000EX can use i-kp01 keypads fitted
with firmware version 2.0 and above. The keypad
allows end users to set and unset the system, and
the installer to configure the control unit. The
keypad also contains an integral proximity tag
reader, which allows end users to control the
system without having to remember access
codes.
The following types of keypad are also available
for connection to the i-on1000EX:
KEY-K01
This keypad has no internal prox
reader, and is supplied in a square
format case.
KEY-KP01
This product, supplied in the same
case as the KEY-K01, has an
internal prox reader and also
provides terminals for an external
KEY-EP prox reader.
KEY-KPZ01
This product, supplied in the same
case as the KEY-K01, has an
internal prox reader and also
provides terminals for up to two
zones, a programmable output and
an external KEY-EP prox reader.
Note that the i-on1000EX must be fitted with at
least one wired keypad.
A range of wireless peripherals is available for
operation with the wireless expanders. These
include a door contact/universal transmitter, a
passive infra-red detector, smoke detector,
The control unit also provides outputs that can be
used to fit an external “plug by” communicator.
To comply with EN50131 at Security Grade 2, you
must fit at least an ATS2 communicator (for
example, the i-dig02).
To be approved at Security Grade 3, use the plugby communicator outputs to connect the control
unit to an ATS4 communicator.
Partitions
The i-on1000EX allows you to create up to 50
partitions and allocate zones freely to one or more
Page 1
Introduction
partitions (although it is recommended that each
zone belongs to only one partition, simply to make
the resulting system easier to program).
Each partition can have a full-set level and one
part-set level. In full set, the control unit pays
attention to all detectors. In part set, the control
unit ignores detectors that do not have the Part
Set attribute.
During installation, you can allocate keypads,
sounders or outputs to any partition.
For a detailed description of the Installer’s
programming menu, please read the Engineering
Guide available from www.coopersecurity.co.uk.
Installer Programming Interface
Once fitted and powered up, you can program the
control unit through any wired keypad connected
to the bus cable. The Installer menu allows you to
specify all the operating parameters for an
individual installation.
If you wish, you can also program the system from
a PC or laptop connected to the Ethernet port on
the control unit PCB. The control unit contains a
web page server, and you can use any web
browser to see a complete version of the Installer
menu. Please see the Web Server Setup Guide
for more instructions.
Note that Eaton’s Security Business recommend
using Internet Explorer. Other browsers may not
be fully compatible with the built-in web browser
interface.
In addition, it is possible to connect a PC or laptop
to the mini USB port on the control unit PCB and
use Eaton’s Security Business Downloader
software to program the control unit.
Note: Some programming options can make the
installation non-compliant with EN50131. The
relevant options are noted in the “Installer Menu”
section of the Engineering Guide.
About this Guide
This guide shows the simple procedure required
to physically install the control unit, connect
keypads, expanders and power supplies and
power up the system for the first time.
When you have completed the physical
installation, please consult the Engineering Guide
for details of configuring the system to meet your
customer’s requirements. For your convenience,
page 29 of this installation guide contains a
condensed reference table of the Installer menu.
Page 2
i-on1000EX
i-on1000EX
2. Before You Begin
Preparation
Before installation, you should carry out a survey
of the site. You need to know how many and what
kind of detectors will be monitored by the control
unit. You also need to assess where any radio
expanders must be placed in order to receive
radio signals from their detectors successfully.
Radio Site Survey
If you intend to fit radio expanders, you should
conduct signal strength tests. Eaton’s Security
Business produce the Scantronic 790r hand-held
signal-strength meter and 734r-01 test transmitter
for this purpose. Please read the 790r manual for
details.
Please be aware of the following:
 The 790r signal-strength meter readings
should be used only as an guide when initially
checking the site.
 A reading of four green LEDs or higher
indicates an acceptable signal strength.
 Once you have installed the alarm system,
you should put the control unit in the Installer
test menu and test the received signal
strength from each radio transmitter.
 A signal strength reading of two or more units
by the control unit from each transmitter
should provide reliable operation in the
installed system. (Note: if you take the signal
strength using Eaton’s Security Business
Downloader or the web browser interface
while the panel is in user mode, the minimum
acceptable signal strength is four units.
Ensure that the control unit is in Installer
mode when reading signal strengths
remotely.)
 When you record the signal-strength readings
for later inspection, you should record the
readings taken from the control unit of the
installed system while it is in the Installer
menu.
Please be aware that the signal strength received
from a transmitter can change after installation
because of local environmental changes. For
example, users switching on laptops nearby, or
moving metal cabinets from their original position
can all affect the signal from a transmitter. Please
read Eaton’s Security Business publication
”Guidance Notes for Wireless Alarm System
Installations” obtainable from
www.coopersecurity.co.uk for more information
about the factors affecting radio signal strength.
Siting the Control Unit and Wired Zone
Expanders
WARNING Ensure that the fixings are strong
enough to support the weight of the control unit,
its lid and two 17Ah lead-acid batteries. The total
weight of the control unit plus batteries can be up
to 18kg.
Do site the unit:
 Upright, batteries at the bottom. (This does
not apply to the wired zone expander.)
 Within a protected area.
Do NOT site the unit:
 In the entry or exit areas, or outside the area
covered by the alarm system.
 Next to electronic equipment, particularly
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial
mains equipment.
Siting Keypads
Do site the keypad(s):
Within the area protected by the alarm
system.
 At a convenient height and location for the
user.
 Out of sight of potential intruders.
Do NOT site the keypad(s):
 Next to electronic equipment, particularly
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial
mains equipment.
 Where the length of cable run from the control
unit or an EXP-PSU will reduce the voltage at
the keypad below 10.5V (see Cable
Configuration and Length).
Note: Do not fit any keypad with a prox reader
closer than one meter to any other type of prox
reader. This includes other keypads with prox
readers, external prox readers such as the KEYEP, or prox readers used by other systems (for
example access control systems). If you mount
prox readers closer together than one meter
(including on the other side of walls) then the two
prox readers will interfere and may not work
correctly.
Siting Wireless Zone Expanders
Do site the unit:
 Upright.
 Within a protected area.
 As high as possible. However, do make sure
that the unit is on a similar level to the
transmitters or receivers.
 More than 10m from another radio expander.
Page 3
Before You Begin
Do NOT site the unit:
 In the entry or exit areas, or outside the area
covered by the alarm system.
 Close to or on large metal structures.
 Closer than one metre to mains wiring, metal
water or gas pipes, or other metal surfaces.
 Lower than two metres from the floor (ideally).
 Inside metal enclosures.
 Next to electronic equipment, particularly
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial
mains equipment.
Note: Some window glasses, especially those
sold as “insulating” or “energy conserving” may be
coated with thin metal or conducting films. These
glasses are particularly poor at transmitting radio
waves.
Guided Tour
CAUTION: All printed circuit boards for the
i-on1000EX, its expanders and keypads have
been tested for Electromagnetic Compatibility
(EMC). However, when handling the PCBs you
must take the standard precautions for handling
static-sensitive devices.
The Control Unit
To gain access to the interior of the control unit,
undo the screw at the bottom of the lid. Slide the
lid vertically up, then swing the bottom of the lid
out before moving the lid down and away from the
case.
Figure 1 Opening the Control Unit.
WARNING: When connected to the mains with
power applied, mains voltages are present on the
shrouded heads of the terminal screws of the
mains connector.
Page 4
i-on1000EX
i-on1000EX
Before You Begin
1. Case back.
2. Cable entry holes for
loudspeakers, siren/strobes and
communicators.
3. Fixing holes.
4. Plastic PCB tray.
5. Printed Circuit Board (PCB).
6. Cable entry holes for detector
and keypad wiring.
7. Hole for back tamper fitting.
8. Space for batteries (two of).
9. Mains cable anchor point.
10. Cable entry hole for mains.
Figure 2 Control Unit
1. Plug by output connectors.
2. USB socket (Mini B).
3. Panel location sounder.
4. Lid tamper connector.
5. Reset Codes pins.
6. Engineering keypad connector.
7. Bus connectors (10 of).
8. Aux power output.
9. Bus pair activity LED (one per bus pair).
10. Bus termination pins (1 per bus)
11. Bus activity LEDs (two per bus)
12. Output connectors.
13. Kickstart pins (Batt 1 only).
14. Battery connectors (two of).
15. 20Vac connector.
16. Bell and strobe connector 2.
17. Bell and strobe connector 1.
18. Connectors for loudspeakers and aux
tampers (2 of)
19. Ethernet activity.
20. Ethernet socket.
21. Heartbeat LED.
22. Sockets for plug on module.
23. Plug on Comms activity LED.
Figure 3 Control Unit Printed Circuit Board
Page 5
Before You Begin
i-on1000EX
3
Keypads
i-kp01 Controls and Displays
1
1
2
2
3
3
8
4
5
A
1
2 abc
3 def
B
4 ghi
5 jkl
6 mno
C
7 pqrs
8 tuv
9 wxyz
D
*
0
#
4
7
6
1. LCD display (2 x 20 characters).
2. Programming keys.
3. Navigation keys
4. Alert LEDs
5. Setting and unsetting keys
6. Programmable HUA keys
7. Number/text keys.
8. Set/Unset LEDs.
1. Central keyhole.
2. Rear tamper shroud.
3. Cable entry.
4. Fixing holes.
Figure 6 Keypad Rear Housing
Figure 4 Controls and Displays
Opening the i-kp01
Note: For EN50131-3:2009, 8.7 the keypad is a
type B ACE, fixed.
To open the keypad, first gently prise off the trim
on the front and remove the two screws. Next,
carefully lever the front of the keypad (containing
the PCB and display) away from the keypad rear
housing.
1
2
4
3
Figure 5 Opening the Keypad
1. Sounder.
2. Sounder volume control.
3. Tamper switch.
4. a) Address Jumpers (not used for i-onEX)
b) Jumpers for LED function:
5. RS485 termination jumper
6. Connector for control unit bus.
Figure 7 i-KP01 Keypad PCB
Page 6
i-on1000EX
Before You Begin
3
KEY-K01/KP01/KPZ01 Controls and Displays
1
2
3
A
A
1
B
4 ghi
C
2 abc
3 def
5 jkl
6 mno
7 pqrs
8 tuv
9 wxyz
*
0
#
1
B
2 ab c
4 g hi
C
3 def
5 jkl
7 p qrs
6 mn o
8 tuv
9 w x yz
D
*
0
#
D
4
2
1
A
1
2 abc
3 def
B
4 ghi
5 jkl
6 mno
C
7 pqrs
8 tuv
9 wxyz
D
*
0
#
5
6
7
Figure 9 Opening the Keypad
5
1. LCD display
2. Programming keys.
3. Navigation keys. This key has built-in alert
LEDs.
4. Setting and unsetting keys. The ABCD
keys have built-in status LEDs that can show
the setting status of the system. These LEDs
can be disabled, see page 15.
5. Plastic caps covering screws (shown
closed and open).
6. Hold Up Alarm (HUA) keys.
7. Number/text keys.
Figure 8 KEY-K01/KP01/KPZ01 Controls and
Displays
Opening the KEY-K01/KP01/KPZ01
To open the unit, unclip the caps covering the
screws on the front. (You may need to gently push
the bottom edge of the caps in with the end of a
small screwdriver to start them.) Remove the two
screws hidden underneath (see Figure 9). Gently
swing the lower side of the front out from the back
box by about 10mm and then slide the front
upwards to disengage the top catches. (Be careful
not to pull the lower side of the front more than
about 25mm away from the back while the top
catches are engaged, or you may break the
catches.)
1. Central keyhole.
2. Fixing holes.
3. Cable entry.
4. Tamper block
Figure 10 Keypad Rear Housing
1. Jumpers:
1a Addressing (not used for i-onEX)
1b LED function and RS485 bus
termination.
2. Sounder volume control.
3. Tamper switch.
4. Sounder.
5. Connector for control unit bus.
Figure 11 KEY-K01 Keypad PCB
Page 7
Before You Begin
i-on1000EX
1
2
3
4
BRIGHT
TERM
2
3
6a
6b
6
5
4
Z1 Z2
1. Tamper switch.
2. Sounder.
3. Connector for KEY-EP.
4. Sounder volume control.
5. Connector for control unit bus.
6. Jumpers for:
6a Addressing (not used).
6b LED functions and RS485 bus
termination.
Figure 12 KEY-KP01 Keypad PCB
0V 12V D0 D1 LED
EXT READER
0V 12V A
B OP
1. Tamper switch.
2. Sounder.
3. Connector for KEY-EP. Terminals for
zones
4. Sounder volume control
5. Connector for control unit bus and output
terminal.
6. Jumpers for addressing and LED function:
6a Addressing (not used)
6b LED functions and RS485 bus
termination.
Figure 13 KEY-KPZ01 Keypad PCB
Expanders
To open any of the expander cases, undo the single screw,
pull the top of the lid away from the case and then lift out.
Figures 14, 15 and 16 show the interiors of the wired and
radio expanders.
1
2
1
3
4
5
18
6
17
7
1
1
16
8
15
9
14
10
10
11
1
19
12
1. Cable entry (also behind PCB).
2. Central keyhole.
3. PCB.
4. Relay card (i-rc01) connector.
5. Aux power.
6. Link to enable/disable front/rear tamper
switch.
7. Lid tamper (rear tamper behind pcb).
8. Zone connectors
9. Bus termination jumper.
10. Fixing holes.
11. Addressing button.
12. Engineering keypad connector
13. Bus cable connector.
14. Sounder.
15. Zone connectors.
16. Bus address display.
17. Aux power.
18. Loudspeaker connectors.
19. Outputs.
13
Figure 14 EXP-10 Wired Expander
Page 8
i-on1000EX
Before You Begin
1
2
1
3
4
5
18
6
17
7
1
1
16
8
15
1
19
9
14
10
10
11
12
1. Cable entry (also behind PCB).
2. Central keyhole.
3. PCB.
4. Relay card (i-rc01) connector.
5. Aux power.
6. Link to enable/disable front/rear
tamper switch.
7. Lid tamper (rear tamper behind pcb).
8. Zone connectors
9. Bus termination jumper.
10. Fixing holes.
11. Engineering keypad connector.
12. Addressing button.
13. Bus cable connector.
14. Sounder.
15. Zone connectors.
16. Bus address display.
17. Aux power.
18. Loudspeaker connectors.
19. Outputs.
13
Figure 15 EXP-WCC Wired Expander
1
2
3
1
1
4
1
5
6
7
8
1
14
13
12
9
9
10
11
1. Cable entry (also behind PCB).
2. Antenna.
3. Central keyhole.
4. PCB.
5. Link to enable/disable front/rear
tamper switch.
6. Lid tamper (rear tamper behind PCB).
7. Bus termination jumper.
8. Addressing button.
9. Fixing holes.
10. Engineering keypad connector
11. Bus cable connector.
12. Sounder.
13. Loudspeaker terminals.
14. Bus address display.
Figure 16 EXP-R10/R30 Radio Expander
Page 9
Before You Begin
i-on1000EX
Power Availability
Before connecting any external devices to the
control unit, you must make sure that the control
unit can provide sufficient current to power the
system during a mains failure for the time required
to meet the appropriate standard.
EN50131-1 Grade 3 requires 30 hours, provided
that the control unit is fitted with an ATS4
communicator capable of transmitting a mains fail
signal. PD6662 Grade 3 (UK only) reduces the
standby time requirement to 12 hours.
Note: When calculating the average load during the
standby time period, you must allow for at least two
periods in alarm. To take the worst case, these two
periods of alarm should each be 15 minutes long; the
maximum permitted in EN50131-1 section 8.6.
The amount of current available from the control
unit depends on the capacity of the batteries fitted
and their health. The current taken by the control
unit PCB, communicator and keypads is given in
EN50131-6 Ratings on page 32.
The following calculation shows a simplified
example in an alarm system with an i-on1000EX
control unit, five i-kp01 keypads, three expanders
and 40 wired PIRs, the system takes the following
total quiescent current:
Device
Control unit PCB
40 x PIRs at 15mA each
3 x (wired expanders)
5 x i-kp01 at 30mA each
(backlights off)
Siren (quiescent)
Current
140mA
600mA
60mA
150mA
Total
During an alarm, these figures become:
Device
Control unit PCB
40 x PIRs at 15mA each
3 x (wired expander)
5 x i-kp01 at 60mA each
(backlights off)
Siren (in alarm)
25mA
975mA
Current
220mA
600mA
60mA
300mA
400mA
Total
1580mA
The total amp hours required for EN50131-1
Grade 3 is:
(0.975 A x 29.5h) + (1.58A x 0.5h) = 29.55Ah
Note that this example assumes that the
communicator has its own power supply.
Two new, fully charged, 17Ah batteries can
provide the charge required by the example
system and would meet the EN50131-1 Grade 3
requirements.
Page 10
Note: All current drawn from the Aux terminals
(12V and 14.4V) must be included in the overall
calculation.
CAUTION: Ensure that the system does not
demand more than the maximum current available
from the control unit during an alarm, see page
32.
Bus Cabling Requirements
Cable Type
In general, the control unit requires standard 7/0.2
un-screened four core alarm cable for wiring the
bus.
For maximum performance in harsh
environments, use twisted pair screened cable
with a characteristic impedance of 100-120 Ohms,
such as Belden 8132 or cable designed for
RS485.
Use one pair for data lines A and B. Use the other
pair for 12V and 0V. For optimum performance,
the voltage at the keypads and expanders should
be greater than 12V.
Screened cable may prove necessary if the
installation site has equipment that produces high
levels of R.F. (Radio Frequencies). For example,
welding equipment is known to produce a large
amount of radio interference. If screened cable is
required, you should keep to the following
guidelines:
1. Avoid earth loops by connecting the screen on
the cable to mains earth at the control unit but
not at the keypad or expander.
2. The continuity of the cable screen is most
important and screens MUST be continuous
along the full length of the cable.
3. Where the cable enters any metal enclosure,
ensure the screen is isolated from the case.
Cable Segregation
Segregate the bus cabling from any other wiring,
such as mains supply cables, telephone cables,
computer network cables and R.F. cables. Use
cable ties to keep cables separated.
Keep the bus cable clear of cables supplying
sounders, extension loudspeakers or any other
high-current devices.
Cable Configuration and Length
You can connect up to 25 devices to each bus
cable. You may connect the devices either in
daisy chain (serially), or in star (parallel)
configuration at the control unit connector. For
star configurations, the cable length from control
unit to the most distant bus device should be kept
short, and should not exceed 100m. There should
be no more than four arms in the star.
i-on1000EX
Before You Begin
For a daisy-chain configuration, the total cable
length should not exceed 1,000m.
Note that if there are only two arms in a star
configuration, this is equivalent to a daisy-chain
configuration.
Bus Termination
The i-on1000EX bus uses the RS485 interface.
Because of this, the ends of the line in some
configurations may be terminated to improve
performance in electrically noisy environments or
where there are long cable runs. The control unit
has a termination link for each bus (see Figure 3).
Expanders and keypads have a termination link
on their PCBs (see Figures 7, 11 and 13 for the
keypads). Fitting a jumper to the pins adds a
termination to the cable.
In a daisy-chain configuration, fit the termination
jumpers in the devices at each end of the chain
(see Figure 17).
In a star configuration, terminate at the two
devices on the ends of the longest cables (see
Figure 17).
Voltage Drop
In order for the system to work correctly, the
voltage at each device must NOT drop below
10.5V even when running on the standby battery.
Eaton’s Security Business recommend that the
voltage at each device should stay above 12V.
Standard 7/0.2 alarm cable has a resistance of 8
Ohms per 100m per core. The voltage drop is
calculated using the following formula: V Drop =
Current drawn x cable length x 0.08 x 2.
Table 1 shows the voltage drop against the
current drawn and cable length.
The shaded area shows where the voltage drop
would cause the bus voltage to fall from 13.8V to
below 12.0V when using a single core.
Figure 17 Bus Termination
Page 11
i-on1000EX
Table 1. Voltage Drop
Current
Drawn
60mA
80mA
100mA
120mA
140mA
160mA
180mA
200mA
220mA
240mA
260mA
280mA
300mA
320mA
340mA
360mA
380mA
400mA
Cable Length (Standard 7/0.2 alarm cable)
10m
0.10V
0.13V
0.16V
0.19V
0.22V
0.26V
0.29V
0.32V
0.35V
0.38V
0.42V
0.45V
0.48V
0.51V
0.54V
0.58V
0.61V
0.64V
20m
0.19V
0.26V
0.32V
0.38V
0.45V
0.51V
0.58V
0.64V
0.70V
0.79V
0.83V
0.90V
0.96V
1.02V
1.09V
1.15V
1.22V
1.28V
30m
0.29V
0.38V
0.48V
0.58V
0.67V
0.77V
0.86V
0.96V
1.06V
1.15V
1.25V
1.34V
1.44V
1.55V
1.63V
1.73V
1.82V
1.92V
40m
0.38V
0.51V
0.64V
0.79V
0.90V
1.02V
1.15V
1.28V
1.41V
1.54V
1.66V
1.79V
1.92V
2.05V
2.18V
2.30V
2.43V
2.56V
50m
0.48V
0.64V
0.80V
0.96V
1.12V
1.28V
1.44V
1.60V
1.76V
1.92V
2.08V
2.24V
2.40V
2.56V
2.72V
2.88V
3.04V
3.20V
Reducing Voltage Drop - Method 1:
Double up the supply connections (12V and 0V),
which will halve the resistance on each core and
therefore halve the voltage drop. When using
Table 1 to calculate the expected voltage drop,
simply divide the voltage drop for a single core by
two.
Reducing Voltage Drop - Method 2:
Supply the detection devices from the Aux output
on separate cores. This is the preferred method of
reducing voltage drop as detectors generally
operate at lower voltages (9.5V). When using this
method, the bus cable must have at least two
spare cores.
60m
0.58V
0.79V
0.96V
1.15V
1.34V
1.54V
1.73V
1.92V
2.11V
2.30V
2.50V
2.69V
2.88V
3.07V
3.26V
3.46V
3.65V
3.84V
70m
0.67V
0.90V
1.12V
1.34V
1.57V
1.79V
2.02V
2.24V
2.46V
2.69V
2.91V
3.14V
3.36V
3.58V
3.81V
4.03V
4.26V
4.48V
80m
0.77V
1.02V
1.28V
1.54V
1.79V
2.05V
2.30V
2.56V
2.82V
3.07V
3.33V
3.58V
3.84V
4.10V
4.35V
4.61V
4.86V
5.12V
90m
0.86V
1.15V
1.44V
1.74V
2.02V
2.30V
2.59V
2.88V
3.17V
3.46V
3.74V
4.03V
4.32V
4.61V
4.90V
5.18V
5.47V
5.76V
100m
0.96V
1.28V
1.60V
1.92V
2.24V
2.56V
2.88V
3.20V
3.52V
3.84V
4.16V
4.48V
4.80V
5.12V
5.44V
5.76V
6.08V
6.40V
Remote Power Supplies
When you cannot reduce voltage drops by
method 1 or 2, or the demand on the control unit
power supply exceeds its capacity (see Technical
Specifications –page 32), you should install one or
more remote power supplies. The supply must
have a "floating zero volt rail" if connected to the
bus, otherwise an earth fault will occur. Eaton’s
Security Business recommend the EXP-PSU.
When installing a remote power supply, fit it close
to the equipment it is powering.
Figure 18 shows the recommended method of
connecting a remote power supply.
Device 3
Remote PSU
Control unit
0V
Device 1
12V
Device 2
Device 4
12V
0V
Bus
Figure 18. Connecting Remote Power Supply Units
Page 12
i-on1000EX
3. Installation
Note: The installation steps listed below assume
that you have already decided on the required
number and location for all keypads, expanders
and power supplies.
Caution: Static Electricity
Fitting tamper Shroud
The tamper shroud is intended to prevent an
intruder sliding a tool between case and wall to
interfere with the tamper bracket. When fitted, the
shroud must surround the point where the tamper
bracket touches the wall. see Figure 20. Fit the
tamper shroud at the position where the lid/back
tamper touches the wall, see Figure 20.
Like many other electronic products, the control
unit, keypads and expanders contain components
that are sensitive to static electricity. Try not to
handle their PCBs directly. If you must handle a
PCB, take the standard precautions against
damage by static electricity.
Step 1. Fit the Control Unit
Case
Fitting
To prevent access to the inside of the control unit
through the holes in the rear of the case, you must
mount the control unit on a wall or other flat
surface.
WARNING Ensure that the wall is strong enough
to support the weight of the control unit, its lid and
lead-acid batteries. The total weight of the control
unit plus batteries can be up to 18kg.
The case must be vertical, as shown in Figure 2.
Locate and mark the position of the case. Also,
Mark the position where the lid/back tamper
bracket touches the wall. There must be enough
space around this point to fit the supplied tamper
shroud (see Figure 20).
Fitting Plastic Feet and Tamper Sleeve
The control unit is supplied from the factory with
four plastic feet and one plastic tamper sleeve. Fit
these onto the outside of the case back, as shown
in Figure 19. Fit feet only to the fixing holes that
you intend to use.
Figure 20 Fitting Tamper Shroud.
Fitting Case Back to Wall
Mount the case vertically, as shown in Figure 20.
Use at least three fixing holes. Use No14/M6
screws at least 50mm long, inserted into wall
anchors appropriate for the type of wall. Figure 2
shows the fixing holes and cable entries.
WARNING Ensure that the fixings are strong
enough to support the weight of the control unit,
its lid and two 17Ah lead acid batteries. The total
weight of the control unit plus batteries can be up
to 18kg.
Protect the unit from dust and drilling debris when
drilling the fixing holes.
Installing the Lid/Back Tamper
Fit and connect the combined lid/back tamper
(provided). Ensure that the switch is oriented as
shown in Figure 21.
Figure 19 Fitting Feet and Tamper Sleeve.
Page 13
Installation
Figure 21 Lid/Back Tamper
Item 4 in Figure 3 shows the connector for the
lid/back tamper.
Note that to be approved at Security Grade 3, you
must fit the lid/back tamper.
Step 2. Run Bus Cable
Please read Bus Cabling Requirements on page
10.
i-on1000EX
1. Hold the backplate in place against the wall
and mark the position of the hole in the
tamper block (see Figure 23).
2. Drill and plug the hole, and screw the
backplate to the wall through the tamper block
using the screw provided. Do not tighten the
screw completely home.
3. Make sure the backplate is level and mark,
drill and plug at least three other fixing holes.
Screw the backplate to the wall through the
fixing holes using the M4 screws.
4. For Security Grade 3 installation, cut the
plastic webs connecting the tamper block to
the remainder of the baseplate.
Note: If you do not cut the webs, the tamper
switch will not operate if the complete keypad
is forced off the wall. The keypad will not
comply with Grade 3 requirements.
5. Mount the front of the keypad (containing the
keypad PCB) onto the backplate and make
sure that the tamper switch operates.
Step 3. Fit and Connect the
Keypad(s)
Siting the Keypad(s)
Please refer to page 3 for general guidelines.
Fitting Keypads
Select which cable entry you are going to use and
break out the appropriate plastic sections.
Use 4mm x 25mm countersunk screws with a
thread suitable for the wall material in at least
three fixing holes when mounting the back of the
keypad on the wall.
i-KP01
For i-KP01 keypads on Grade 3 systems, drill out
the hole for the back tamper using a 7mm bit (see
Figure 22).
Figure 23 Screw KEY-K01/KEY-KPZ01 Back Box
to Wall
Connecting Keypads
Figure 24 shows the wiring connections at the
keypad and control unit.
Figure 22 Screw i-KP01 Back Box to Wall
KEY-K01/KP01/KPZ01
For KEY-K01/KP01/KPZ01 Security Grade 3
installation:
Page 14
Figure 24 Connecting a Keypad to the Bus
i-on1000EX
Installation
Keypad Addressing
The control unit assigns addresses to all devices
connected to the bus cable. If you wish, you can
start with one keypad connected to the bus,
address that keypad, and then attach and address
other devices at later times. See “Initial Power Up”
on page 23 for instructions.
Backlight Control for i-KP01
You can control the appearance of the keypad
backlights and set/unset LEDs by fitting links over
the appropriate jumpers on the keypad PCB (see
Figure 7 for the position of the jumpers).
The jumpers have the following functions:
b) Enter a local keypad programming mode (this
replaces the use of jumpers on the keypad
PCB in the i-kp01).
In addition, the local keypad programming mode
allows you to enable or disable the LEDs in the
ABCD keys and the Navigation key.
It is possible to enter the local keypad
programming mode when the keypad is not
connected to a control unit, but simply powered by
12VDC connected to the keypad bus terminal
(see Figure 11, 12 or 13). If the keypad IS
connected to a control unit, make sure that the
control unit is in Installer menu before entering the
keypad’s local programming mode.
ABCD-ON
The set/unset LEDs
are disabled.
M
ABCD-ON
ABCD-ON
ABCD-ON
ABCD-ON
A
1
B
4
ENU
A
g h i
7
p q r s
ENU
*
3
d e f
jk l
6
m
8
t u v
9
wx y z
1
0
A
1
B
4
A
3
d e f
2 ab c
0
3 d ef
#
5
jk l
p q r s
8
t u v M EN
9 Uwx y z
*1
6
m
n o
4 ghi
5 jkl
6 m no
The set/unset LEDs
shows the setting
status of the system.
(Full set is the left
hand LED.) (see Note
below)
7 p q rs
8 t uv
9 w x yz
A
1
*
2 ab c
0
3 d ef
#
B
4 ghi
5 jkl
6 m no
7 p q rs
8 t uv
9 w x yz
0
#
0
#
*
M
A
ENU
1
B
A
B
M
M EN U
2
a b c
3
d e f
4
g h i
5
jk l
6
m
2 ab c
3 d ef
7
p q r s
8
t 4ughi
v
9
w
x y z
5 jkl
6 m no
1
ENU
*
0
#
7 p q rs
A
A
1
B
4
*1
2
a b c
5
jk l
8
t u v 1 9
3
*
0
B
8 t uv
9 w x yz
2 ab c
0
3 d ef
#
d e f
4 ghi
M EN U
g h i
7A p q r s
M
n o
M EN U
6
5 jkl
m
6 m no
n o
8 t uv
w x y 2z ab c
*
0
#
9 w x yz
3 d ef
#
4 ghi
5 jkl
7 p q rs
8 t uv
9 w x yz
*
0
#
6 m no
ENU
M EN U
A
1
2
a b c
3
4
g h i
5
jk l
6
7
p q r s
8
t 7up q
v rs
9
w
8 txuvy z
9 w x yz
#
2 ab c
0
d e f
3 d ef
#
The key backlights are
disabled. They will
glow briefly for five
seconds when a user
presses a key.
A
B
B
M
A
E *N U
1
4 ghi
M EN U
1
*
0
B
A
1
B
4
5 jkl
4 ghi
M EN U
2
a b c
g h i
5
jk l
p q r s
8
t u v
3
7 p q rs
A
1
* 6
B
7
2 ab c
m
m
0
6 m no
8 t uv
9 w x yz
3 d ef
#
6 m no
wx y z
8 t uv
9 w x yz
0
#
M ENU
M
B
M EN U
ENU
M
1
1
2
a 4bghi
c
2 ab c
3 d ef
3
d
e f
5 jkl
6 m no
A
6
8 t uvn o
m
9 w x yz
B
9
wx y z
2 ab c
0
ENU
A
1
B
4
g h i
5
jk 7l p q rs
7
p q r s
8
t u v
2 ab c
1
4 ghi2
M EN U
4
g h i 7 p q rs
5
7
p q r s
M ENU
B
a b 5c jk l
3 d ef
3
jk l 8 tuv 6
The key backlights
glow all the time at
normal intensity.
A
B
1
*
4 ghi
M ENU
*
M
0
ENU
A
1
2
a b c
B
4
g h i
5
jk l
7
p q r s
8
t u v * 9
0
#
*
A
6 m no
B
9 w x yz
3
4 ghi
d e f
7 p6q rs m
2 ab c
0
3 d ef
#
1
*
5 jkl
6 m no
n 8o t uv
w x y 0z
9 w x yz
M
B
B
2 ab c
0
t u v
1
*
2
a b c
4 ghi
m 9 nw xyz
o
3 d ef
#
wx y z
6 m no
#
7 p q rs
1
9
d e6 fm no
5 jk l
0
ENU
A
A
#
8
4 ghi
M EN U
*
1
*
A
B
3 d ef
#
5 jkl
8 t uv
#
7 p q rs
1. Apply 12Vdc to the keypad.
2. Enter Installer menu on the
control unit, if the
keypad is connected to a
system.
3. Open the keypad tamper.
6 m no
#
A
A
Entering Local Programming Mode
3 d ef
2 ab c
n 0o
5 jkl
9
7 p q rs
*
n o
5 jkl
d e f
4 ghi
*
BRIGHT
9 w x yz
g h i
7 p q rs
7 p q rs
BACKLIGHT
ON ON
BL
BRIGHT
BACKLIGHT
BRIGHT ON
BRIGHT
BACKLIGHT
ON ON
BL
BRIGHT
6 m no
8 t uv
a b c
B
ON ON
BL
BACKLIGHT
BRIGHT
BRIGHT
ON
BACKLIGHT
ON
BRIGHT
BL
ON
BACKLIGHT
BRIGHT
BRIGHT
3 d ef
5 jkl
2
B
n o
2 ab c
#
4 ghi
M EN U
*
ABCD-ON
ABCD-ON
ABCD-ON
ABCD-ON
a b c
5
B
7
ABCD-ON
2
M EN U
M
3
8 tuv
9 w xyz
2 ab c
0
3 d ef
#
d e f
5 jk l
6 m no
4
g h i
5
7jkp lq rs
6 8 tuv
m n o
9 w xyz
7
p q r s
8
*t u v
9 0 wx y z
#
*
0
#
4. Press and hold down B and
 together for at
least two seconds.
The keypad is now in local
programming mode,
the display shows the
current status.
MENU
ABCD

M EN U
A
M ENU
1
2 ab c
3 d ef
The keypad backlights
glow all the time, extra
bright.
M
BACKLIGHT ON
ON
BRIGHT
ON
BL
BACKLIGHT
BRIGHT
BRIGHT
ON
BACKLIGHT
BRIGHT
ON
BL
ENU
B
A
1
M
4 ghi
M ENU
1
2
A
B
7 p q rs
a b c
5 jkl
4
g h i
5
jk l
7
p q r s
8
t u v
B
3
M
B
0
ENU
3 d ef
#
m
9
wx y z
A
4 ghi
a b 8c tuv 3
1
*
g h i
7
p q r s
B
5
jk l
4 ghi
M EN U
8
A
9 w x yz
B
2 ab c
0
3 d ef
#
*
M
1
*
1
B
4
2
a b c
5
jk l
3
d e f
6
m
*
g h i
6 m no
2 ab c
0
3 d ef
#
m
9
wx y z
n o
6 m no
8 tuv
0
d e9 fw xyz
6
5 jk l
9 w xyz
#
4 ghi
7 p q rs
A
1
2
B
4
g h i
7
p q r s
5 jk l
6 m no
8 tuv
9 w xyz
a b c
3
d e f
5
jk l
6
m
8
t u v
9
wx y z
6 m no
8 t uv
9 w x yz
0
#
0
#
n o
n o
Note:BRIGHT
To comply with PD6662:2010 for Grade 2
and 3, disable the ABCD LEDs. To comply with
EN50131-1:2006 at Grade 3: disable the ABCD
LEDs.
*
7
*
p q r s
8
0
t u v
9
To Switch ABCD LEDs ON or OFF
3 d ef
#
ENU
*
7 p q rs
A
2 ab c
0
t u v
7 p q rs
6 m no
8 t uv
5 jkl
5 jk l
7 p q rs
2
4
n o
5 jkl
#
1
*
9 w x yz
2 ab c
0
6
4 ghi
M ENU
*
8 t uv
d e f
7 p q rs
A
6 m no
1
B
1
*
4 ghi
M EN U
3 d ef
A
B
A
2 ab c
ENU
0
#
wx y z
#
Backlight Control for KEY-K01/KP01/KPZ01
You can control the brightness of the keypad
backlights by fitting links over the BRIGHT jumper
on the keypad PCB (see Figure 11, 12 or 13).
 Jumper OFF – The keypad backlights glow at
normal intensity.
 Jumper ON – The keypad backlights glow
extra bright.
To program whether the backlights are on or off,
see below.
Programming Backlight, ABCD LEDs and
Navigation Key LEDs
You can set the function of the backlights in either
of two ways:
a) Use the Installer menu – Detectors/Devices –
Wired Keypads – Edit Keypad – (Keypad n) –
Backlight option. See the Engineering Guide
for more details.
MENU
ABCD

2. Press  or  to enable or
disable the ABCD LEDs.
The character at the right of
the display shows “” when
the LEDs are disabled and
“” when the
LEDs are enabled. For
MENU
example:
ABCD

1. Enter local programming
mode (see above).
3. Leave local programming
mode and save your
changes (see page 16).
To Change Backlight Settings
1. Enter Local Programming
mode (see above)
2. Press . The display shows
the current status of the
backlight LEDs, for
example:
MENU
ABCD

MENU
BACKLIGHT

Page 15
Installation
i-on1000EX
disabled, and will not
glow for any fault reports.
3. Press  repeatedly to select
one of the following:
Backlight LEDs ON ().
Backlight timed ().
The backlight will glow for
10 seconds after the last
keypress. The action of
the backlight depends on
the programming of the
control unit.
MENU
BACKLIGHT
MENU
BACKLIGHT


To Leave Local Programming Mode
and Save Changes
EITHER:
Press 
OR
4. Leave local programming
mode and save your
changes (see below).
Close the keypad tamper.
To Disable/Enable the Status OK LED
1. Enter Local Programming
mode.
2. Press  repeatedly until
the display shows:
4. Leave local programming
mode and save your
changes (see below).
MENU
ABCD

MENU
STATUS OK LED 
The keypad saves the changes you have made in
its local memory.
You can now remove 12Vdc power, if required, or
leave Installer menu on the control unit.
KEY-EP External Prox Reader
Figure 25 shows the outside details of the external
prox reader KEY-EP:
3
3. Press  repeatedly to
select one of the
following:
Status OK LED ON ().
Status OK LED OFF ().
The green status LED
under the navigation key
will glow for 20 seconds
after the last press (this
may be useful when the
keypad is placed in
bedrooms that should be
completely dark at night).
MENU
STATUS OK LED 
MENU
STATUS OK LED 
1
2
4. Leave local programming
mode and save your
changes.
1. LED window.
2. Retaining Screw.
3. Removable Fixing Plate.
4. Permanently attached cable.
To Disable/Enable the Status Fault
LED
1. Enter Local Programming
mode.
2. Press  repeatedly until
the display shows:
MENU
ABCD
Figure 25 External Prox Reader KEY-EP

MENU
STATUS FLT LED 
3. Press  repeatedly to
select one of the
following:
Status Fault LED ON ().
Status Fault LED OFF
().
The red Fault LED under
the navigation key is
Page 16
4
MENU
STATUS FLT LED 
MENU
STATUS FLT LED 
Siting the External Prox Reader
Please refer to page 3 for general guidelines.
Note: The external prox reader is fitted with a
length of 2m of the appropriate cable. The cable
can be extended up to 50m by connecting an
additional length of 7/0.2 un-screened alarm
cable.
Opening the External Prox Reader
To open the external prox reader (see Figure 26):
1. Undo the single retaining screw.
i-on1000EX
Installation
2.Tilt the edge of the fixing plate and then slide it a
short distance parallel to the body of the prox
reader.
Figure 28 shows the wiring connections at the
keypad.
3. Slide the fixing plate away from the reader
body, along the cable.
Figure 28 Connecting the External Prox Reader
Tone Volume – All Keypads
Figure 26 Opening External Prox Reader
Figure 27 shows the details of the external prox
reader backplate:
To alter the volume of non-alarm tones from the
keypad, adjust the keypad sounder volume control
(see Figure 7, 11, 12 or 13):
Louder
1
Note: This control changes the
volume of non-alarm tones (for
example Exit/Entry tone). The
volume of alarm tones is fixed.
Softer
2
1
3
1. Fixing hole.
2. Cable entry.
3. Anchor for retaining screw.
Engineering Keypad
An engineering keypad is a modified i-kp01 that
can be plugged into a dedicated connector on the
control unit PCB (item 6 in Figure 3) or any of the
expanders (see Figure 14, 15 or 16). An
engineering keypad does not need to be
addressed, and will always be recognised by the
control unit as an engineering keypad.
Fit External Prox Reader
You can use an Engineering Keypad to program
the system without being tied to any of the
installed keypads. If you wish to move an
Engineering keypad from one connection point to
another, you can do so without removing power
from the system.
Use M4 25mm countersunk screws at both fixing
holes when mounting the back of the keypad on
the wall. Ensure the screw has a thread suitable
for the wall material.
Step 4. Fit and Connect
Expanders
Figure 27 External Prox Reader Fixing Plate
Connecting Remote Prox Reader to
Keypad
Segregate the external prox reader cable from
any other wiring such as mains supply cables,
telephone cables, computer network cables and
R.F. cables. Use cable ties to keep cables
separated.
Keep the prox reader cable clear of cables
supplying sounders or extension loudspeakers.
Both wired and radio expanders are supplied in
the same plastic case. Use M4 25mm
countersunk screws in all three fixing holes when
mounting the back of the case on the wall. Ensure
the screw has a thread suitable for the wall
material. See Figure 14, 15 or 16 for the position
of fixing holes and cable entries.
Note that radio expanders are not approved for
Security Grade 3 systems.
Page 17
Installation
i-on1000EX
Connecting an Expander to the Bus
Both wired and radio expanders provide a
connector for the bus at the bottom of their PCBs.
0V
12V AUX
Z3
Z4
0V +12V A
B
To next device
L
Figure 29 Wiring Expanders
230V ~50Hz 350mA
T500mA 250V
Addressing Expanders
The control unit assigns addresses to all devices
connected to the bus cable. You can start this
process off from the Installer menu during the
initial power up. See “Initial Power Up” on page 23
for instructions. Alternatively, you can add and
address new expanders at a later date.
Expander Loudspeakers
During normal operation, loudspeakers on
expanders repeat setting and entry tones for the
partition that the expander is allocated to. During
an alarm, the loudspeakers repeat alarm tones.
Figure 30 Mains Connection
Step 6. Connect Wired Zones
The wired expander connectors can be used for
either four-wire CCL detectors, two-wire CCL
detectors or two-wire FSL detectors.
Four Wire Closed Circuit Connections
Figure 31 shows the wiring for CCL zones on the
EXP-W10 wired expander. Note that zones 5-9
are not available on the expander.
Alarm Zone 0
Tamper Zone 0
Z0
Alarm Zone 1
Z1
Each loudspeaker draws up to 280mA in
operation. If there is more than one expander
loudspeaker, the bus may not be able to supply
sufficient current during an alarm.
Z2
WARNING: ENSURE THAT THE MAINS
SUPPLY IS DISCONNECTED AND ISOLATED
BEFORE MAKING ANY MAINS CONNECTIONS.
All mains electrical connections must be carried
out by a qualified electrician and must comply with
the current local regulations (e.g. IEE).
Z6
Z5
Alarm Zone 2
Wired Expander
Z4
Step 5. Connect Control Unit
to Mains
Tamper Zone 1
Z3
Note that the volume of the expander
loudspeakers is initially set to zero. You must set
the volume of entry exit tones from the expander
loudspeakers from within the Installer menu;
please see the Engineering Guide.
N
Z9
B
Z8
0V +12V A
Expander
Z7
Control Unit
Tamper Zone 2
Figure 31 Wired Expander CCL Zone Wiring
Figure 32 shows the wiring for CCL zones on the
EXP-WCC wired expander. Note that the EXPWCC provides connectors for a total of ten
separate 4-wire CCL detectors, and that there are
separate terminals for both alarm and tamper.
Alarm Zone 0
Tamper Zone 0
Mains Cabling
Alarm Zone 1
Note: To avoid mains interference, the mains
cable must enter the control unit through its own
cable entry hole (item 10 in Figure 2) and must
not be mixed with other cables.
Tamper Zone 1
Mains Connection
Figure 30 shows the mains connection. Connect
to a suitable supply using a double-pole
disconnect (isolation) device in accordance with
EN60950-1.
Caution: Do not apply power at this point.
Anchor the mains cable with a strain-relief tie.
There is a eye located near the mains cable entry
hole for this purpose.
Page 18
Figure 32 EXP-WCC CCL Zone Wiring
Figure 33 shows the wiring for CCL zones on the
KEY-KPZ01.
i-on1000EX
Installation
Figure 35 shows The wiring connections for FSL
zones on the EXP-WCC.
KEY-KPZ01
Tamper Zone 1
Alarm Zone 1
Figure 33 KEY-KPZ01 CCL Zone Wiring
Two-Wire Closed Circuit Connections
On the EXP-W10, you can connect two-wire CCL
detectors to each pair of zone terminals. To
specify the zone wiring type, use Installer menu –
Detectors Devices – Wired Expanders - Edit Expander.
If required, you can use one pair of zone terminals
as a common tamper, provided you program that
zone with the type “Tamper” from the Installer
menu.
Wired Expander
100 Ohms
4K7
Zone 1
On the control unit, EXP-W10 and EXP-WCC, you
can, if required, use one pair of zone terminals as
a common tamper, provided you program that
zone with the type “Tamper” from the Installer
menu.
The EXP-WCC does not specifically have a 2-wire
CC zone type. However, you can mimic the
setting by using “4k7/2k2/4-wire CC” zone wiring
option, and then connecting the detector to the
alarm terminals and placing a short across the
tamper terminals.
Fully-Supervised Loop Connections
2K2 EOL
4K7
Zone 0
Alarm contacts
2K2 EOL
Tamper contacts
Figure 35 FSL Zone Wiring – EXP-WCC
The allowed values for Alarm Contact/End of Line
are the same as for the EXP-W10.
Figure 36 shows the wiring connections for FSL
zones on a KEY-KPZ01. Note that the resistance
values shown are examples.
100 Ohms
Figure 34 shows the wiring connections for FSL
zones on the EXP-W10 expander.
4K7
KEY-KPZ01
Z0
Alarm contacts
Z1
Zone 1
Zone 0
Z2
Wired Expander
Alarm contacts
Tamper contacts
2K2 EOL
Tamper contacts
4K7
Z3
Alarm contacts
2K2 EOL
Z4
Tamper contacts
Figure 36 Wiring FSL Zones on KEY-KPZ01
100 Ohms
4K7
Alarm contacts
Zone 1
Zone 0
2K2 EOL
Tamper contacts
To select the resistor values for a wired expander,
use Installer menu – Detectors Devices – Wired
Expanders - Edit Expander.
If you wish to connect two or more detectors to a
FSL zone, Figure 37 shows the connections
required.
4K7
Alarm contacts
2K2 EOL
Tamper contacts
Figure 34 FSL Zone Wiring - Expander
The allowed values for Alarm Contact/End of Line
are: 4k7/2k2. 1k0/1k0, 2k2/2k2, or 4k7/4k7.
Note: Use the same pair of values for ALL FSL
wired circuits on an expander.
Figure 37 Wiring Two Detectors per Zone FSL.
Figure 38 shows an example of wiring double
doors with two door contacts to one FSL zone.
Each door contact is a reed switch, connected
Page 19
Installation
between the outer terminals. The inner (shaded)
terminal is not connected, and provides a spare
terminal.
i-on1000EX
Wired External Sounders (Optional)
Wired external sounders differ in their methods of
connection. Figure 41 shows an example of a
general method of using the outputs to connect a
wired sounder.
The connector also provides an input terminal for
a “trouble” signal from the sounder. The control
unit treats this the same as a “Warning Device
Trouble” zone type.
Typical external
siren/strobe
Figure 38 Example: Wiring Two Door Contacts to
One FSL Zone.
Figure 39 shows an example of wiring a
trouble/masking output using the “3-resistor
method”. Note that you must use 2k2 and 4k7
resistors as shown. Other values will not work
(See System Options – Masking in the Engineering
Guide).
12V +
0V
Tamper In
Tamper Out
Strobe +ve
Strobe -ve
Trigger -ve
TRB STB BELL TR 12V 0V 14V4
Figure 41 Connecting External Sounders
Figure 39 Example: Wiring a Trouble/Masking
Zone, 3 Resistor Method.
Step 7. Connect Wired
Outputs
The control unit PCB provides eight connectors
for wired outputs. Outputs 1 to 4 are voltage free
relay outputs. Outputs 5 to 8 are driven by
transistors, and are capable of sinking a maximum
500mA when active. By default outputs 5 to 8 are
0V when active, +12V when inactive. If you wish
to reverse the polarity of these four outputs see
Changing the Polarity of a Wired Output in the
Engineering Guide.
Figure 40 shows an example of using the wired
outputs to drive an indicator LED.
It is possible to program the TR terminal on the
control unit as either CC or FSL. Use Installer
menu – System Options – Panel Tamper Rtn. By
default, the terminal is CC. If you program the TR
terminal as FSL, make sure you connect a 2k2
resistor in series with the wire to the sounder.
Note: If you do not wish to connect a wired
external sounder, leave TR programmed as CC
and make sure you link TR to 0V on the control
unit. This prevents the control unit reporting Bell
Tamper unnecessarily.
Auxiliary Tamper
The control unit provides two “AUX TAMP”
terminals, which you can connect to external
equipment to detect a tamper. The terminals offer
CCL connection only. If you do not intend to use
them, connect the terminals together with a short
wire link.
If you wish to use FSL wiring for an auxiliary
tamper, use a FSL wired zone programmed as
type “Tamper (10)”.
Wired Outputs on Expanders
Each EXP-W10 wired expander provides
connections for up to four transistor-driven
outputs. By default, the outputs are 0V when
active, +12V when inactive. If you wish to reverse
the polarity of these two outputs, see Changing the
Polarity of a Wired Output in the Engineering
Guide. Figure 42 shows an example of using an
expander output to drive an LED.
Figure 40 Connecting Wired Outputs
Page 20
i-on1000EX
Installation
16 Ohm minimum
Typical loudspeake r
for example 09040
Single Wire Tamper Return
If the external sounder provides a single –TR
connection, use the zone type “Tamper Return”
for the zone terminals which receive the
connection at the expander.
1K0 Resistor
LED
(Light
Emitting
Diode)
0V
12V
AUX
Out
1
OUTPUTS
2
3
4 -
LS
+
Figure 42 Using Wired Expander Outputs.
Wired External Sounders on Expanders
Figure 43 shows a general method of using the
outputs on a wired expander to connect a wired
external sounder.
Connect the tamper wiring to an unused zone
connection on the expander. For 4-wire CC
zones, use the alarm contacts only and link the
tamper contacts together with a short length of
wire.
FSL wiring. Connect –TR to the left-hand
terminal of a zone connector (see Figure 44). (The
left-hand terminal is the one next to the “Z” on the
terminal label.) The maximum length of wire is
50m when using 2k2/4k7 or 4k7/4k7 FSL wiring
and a single core of standard 6-core alarm cable.
Fit EITHER a 2k2 resistor if using 2k2/4k7 FSL,
OR a 4k7 resistor if using 4k7/4k7 FSL. Do not
use any other FSL resistor combinations.
CC wiring Eaton’s Security Business does NOT
recommend that you use CC wiring for this
application. The maximum length of wire
allowable is only 6m. Instead Eaton’s Security
Business recommend using FSL wiring, as
described above.
In the Installer menu, program the zone with a
type of “Tamper”. Program the outputs used to
trigger the siren and strobe with the appropriate
output types. See the Engineering Guide for more
details.
Figure 44 Wiring –TR from External Sounder to a
Zone on the Expander.
Remote Loudspeakers (Optional)
If you wish to add a 16 Ohm wired Loudspeaker
unit, then connect it as shown in Figure 45. The
control unit provides connections for two
loudspeakers. If required you can use the
adjacent AUX TAMP terminals to connect a
Figure 43 Wiring External Sounder to Expander
Page 21
Installation
i-on1000EX
Com Connector Cable,
Part number 485210
tamper switch in the loudspeaker to the control
unit.
12V (Red)
Expanders provide connections for only one
loudspeaker. Do not connect another loudspeaker
in parallel. You may connect another loudspeaker
in series, but this will decrease the maximum
volume from the speakers.
Note: Loudspeakers are not warning devices as
described by EN50131-4. Although loudspeakers
may mimic alarm tones, they also give alert tones
and other progress tones when setting and
unsetting the alarm system.
16 Ohm minimum
Typical loudspeaker
for example 09040
0V (Black)
(Not used) (White/Orange)
(Not used) (White/Brown)
O/P 16 (Grey) RF Fault
O/P 15 (White) 24 Hour Alarm
Con 4
O/P 14 (Purple) Ext PSU Fault
O/P 13 (Blue) Ext PSU Low Volt
O/P 12 (Green) Alarm Abort
O/P 11 (Yellow) Technical Alarm
O/P 10 (Orange) Battery Fault
O/P 9 (Brown) AC Fail
+LS
-LS
12V (Red)
0V (Black)
-LS1+ AUXTAMP1
Tell Back input (White/Orange)
Line Fail input (White/Brown)
O/P 8 (Grey) General Fault
Figure 45 Wiring Loudspeakers.
Con 3
O/P 6 (Purple) Tamper
Output on KEY-KPZ01
O/P 5 (Blue) Zone Omit (System)
Figure 46 shows the wiring required to connect an
output the output terminal on the KEY-KPZ01.
0V 12V
A B OP
RS485
LED
(Light Emitting Diode)
O/P 7 (White) Confirmed Alarm
1K0 Ohm Resistor
Figure 46 KEY-KPZ01 Output Wiring
Step 8. Fit a Plug-By
Communicator
The control unit can be connected to a separate
communicator or speech dialler (for example, the
Scantronic 8400, 660 or RedCare STU). Figure 47
shows the connections provided by the
communications wiring harness. Note that the
output types shown in Figure 47 are the Factory
default types. See the Engineering Guide for
details on how to change the defaults.
O/P 4 (Green) Open/Close
O/P 3 (Yellow) Burglar Alarm
O/P 2 (Orange) Hold Up Alarm
O/P1 (Brown) Fire
Figure 47 Plug-By Communicator Wiring
Note: Comms O/P4 will be active when the
system is unset. This is normal.
To fit a communicator, follow the instructions
below.
Caution: Follow the instructions in the order
shown, or you may damage the
control unit and/or communicator.
1. Disconnect mains power from the control unit,
remove the case lid, and disconnect the
battery (if the system has already been
installed).
2. Make any necessary connections from the
communicator to the communication wiring
harness. The default is a 12V positive voltage
when the output is inactive.
Refer to the next section if you are using a
dual-path communicator.
3. Plug the Communication Wiring Harness onto
the communications connector on the main
PCB.
If the system has already been installed:
4. Re-connect the battery.
5. Fit the case lid.
6. Apply mains power.
7. Test communicator operation.
Note: You will need to speak to the ARC in order
to confirm that the communicator has worked
correctly.
Page 22
i-on1000EX
Line Fail Input
This input is designed to allow a plug-by
communicator to indicate to the control unit that
the communications link has failed. The
communicator should have an output capable of
applying +12V to the Line Fail input while a line
fault is present and 0V when the fault is absent.
Installation
Connect the battery leads, red to the positive,
black to the negative terminals of the battery.
Connect the other ends of the leads to either
BATT1 or BATT2 (item 14 in Figure 3).
If you are fitting only one battery, connect it to
BATT1 (the lower set of pins) and disable alerts
on BATT2 (see the Engineering Guide).
Remote Reset (Tell Back) Input
This input (marked “RR”) is designed to allow a
plug-by communicator to indicate to the control
unit that the user can reset the system after a
system tamper. The communicator should have
an output that, when triggered remotely, can apply
+12V for at least 100ms to the input. See “Remote
Reset (Redcare Reset)” in the Engineering Guide
for more information.
Line Monitoring for a Dual-Path Communicator
If a standalone dual-path (landline and mobile)
communication device, such as a RedCARE STU,
is connected to the plug-by connector, you need
to do the following to obtain correct line fault
reporting that complies with BSIA Form No.175,
April 2005 (this is not necessary if you are using a
plug-on module):
1. Reprogram one of the plug by outputs to type
“ATS Test” and wire that output to the ATS
Test input of the communicator.
2. Wire the Line Fault output of the
communicator to the Line Fault input of the
plug-by connector. The communicator must
provide +12Vdc to indicate a line fault (for
example, if the Line Fault output at the
communicator uses a relay, connect the
common terminal of the relay to +12Vdc and
the normally-open terminal to the Line Fault
input of the plug-by connector).
The control unit will generate an "ATE L.F. Single"
alert if only one of the networks is not available, or
"ATE L.F. All" if both networks are not available.
Step 9. Fit and Connect
Battery
Fit either one to two 17Ah lead-acid batteries into
the battery compartment in the bottom of the
control unit (see Figure 48). Use batteries whose
case material has a minimum rating of UL94V-2 in
order to comply with EN60950 (this standard
applies because of the energy content of 17Ah
batteries).
See page 10 for example calculations of battery
requirements.
WARNING 17Ah lead-acid batteries weigh 6kg
each. Do NOT drop. Ensure that the fixings of the
control unit case to the wall, and the wall itself, are
strong enough to support the weight of the control
unit, its lid and up to two 17Ah lead-acid batteries.
The total weight of the control unit plus batteries
can be up to 18kg.
Figure 48 Fitting the Batteries
Note: Connecting the batteries without mains
power will not start the system. (See
“Programming Before Installation” in the
Engineering Guide.)
Step 10. Power-up, Select Main
Settings and Set Addresses
WARNING: During initial power-up all the keypad
sounders, internal loudspeakers and wired sirens
MAY give an alarm tone. If you are working at the
top of a ladder, make sure that the sudden noise
does not startle you and cause a fall.
Note: The following assumes that the control unit,
keypads and expanders are in the factory-default
state. That is, the control unit has not been
previously configured, and the keypads and
expanders have a "null" address (no address
previously allocated).
1. Apply mains power to the control unit.
The keypads and internal sounder may give
an alarm tone. The heartbeat LED on the
control unit PCB and the navigation keys on
keypads start flashing.
Wait until you see:


This message indicates that the keypad has a
"null" address.
2. Go to the keypad you want to use for initial
programming. Obtain an address for this
keypad by pressing and holding A and  keys
simultaneously for at least three seconds
until the display shows the address allocated
by the control unit, such as “b0-d51”(bus 0
device 51).
Page 23
Installation
The address is now stored in the keypad.
Keypads take bus device addresses 51
upwards. Please refer to the Engineering
Guide for details of bus addressing.
3. Follow this step if you see the following (EUR
control units only):

 
a) Press  or  followed by  to select the
language you want.
From this point on, the display operates in
the selected language. If you want to
change the language later, use Installer
menu - System Options - Language.
b) Press  or  followed by  to select the
country:


4. Follow this step if you see the following :


EITHER Press  if there is NO battery
connected to BATT2 (see 14 in Figure 3).
OR press  followed by  if you have
connected a battery to the BATT2 terminals
and wish to enable fault reporting on battery
2.
5. When you see the following, press  or 
followed by  to select the security grade you
require:


6. When you see the following, press  or 
followed by  to select the zone wiring type
you intend to use for wired zones:


Note: This initial choice fixes the wiring type
for the control unit and any attached wired
expanders. If you wish to use a different
wiring type on the expanders, use Installer
menu – Detectors/Devices – Wired Expander
after the initial power up to change the wiring
type for each expander.
7. The display shows:


EITHER: Press  if you do not want to pair
buses (see page 1).
OR: Press  or  to choose Yes or No, and
 or  to display the next pairing option. On
completion, press .
8. You will see one of the following:


If you see the above, press . The
message indicates that the lid is open and
Page 24
i-on1000EX
the "Lid/Back Tamper" link is not fitted.


If you see the above, enter the default
installer access code ("7890" for Grade 2
or "567890" for Grade 3) and, if prompted,
the default user code ("1234" for Grade 2
or "123456" for Grade 3). See page 25 for
further information.
9. Press  when you see the following:


10. Press  when you see the following:


11. Press  when you see the following:


12. Press  if you see the following:


13. The display shows:


When you see this message, the control unit
is ready and waiting to allocate an address to
each additional bus device. The control unit
allocates an address when you press the
relevant button/keys at the device, as
described in steps 14 and 15. The control
unit can allocate an address only if the
address of the device is currently "null".
Note: Get ready to visit each bus device in
turn. You can visit them in any order, but it is
easier if you do it in order of required bus
address, since by default, the control unit
assigns the next free address.
Note: Each device stores its address locally in
non-volatile memory. The control unit also
keeps a record of the allocated address and
device types.
Note: Do not attempt to obtain an address for
two devices at the same time.
14. To obtain an address for a keypad:
Hold down the A and  keys until the display
shows a bus and device number. For
example:


15. To obtain an address for an expander:
a) Open the lid and make sure that the tamper
switch is open. The expander cannot obtain
an address if the "Disable Tamper" link is
fitted.
b) Hold down the addressing button (see
Figure 14, 15 or 16 ) until you hear a double"beep".
i-on1000EX
The control unit assigns the next free address
and displays it on the two-digit LED display.
If you do not want to use the address shown,
press the addressing button again as many
times as necessary to display the required
address.
Refit the lid.
Note: An EXP-R30 expander takes three bus
addresses when you press the button.
16. When you have visited all the connected bus
devices, go back to the keypad and press .
The display shows:


17. If you have finished with the inside of the
control unit, refit its lid, making sure that the
"Lid/Back Tamper" link is not fitted and the
tamper switch closes.
Note: You can set the time and date using
the System Options – Set Time & Date installer
option.
18. Leave the Installer menu as described next.
Leaving the Installer Menu
Important: Leaving the Installer menu causes the
control unit to save the configuration changes into
a permanent store, including the addresses and
types of devices on the bus. If you remove all
power BEFORE you leave the Installer menu, the
control unit will lose your changes.
To leave the Installer menu:
1. Keep pressing  until the display shows:


2. Press  to leave Installer menu (or  if you do
not want to leave the menu).
The display shows:


After a delay of anywhere between a few
seconds to a few tens of seconds (depending
on the number of expanders fitted), the
display shows the time and date:


3. If the control unit finds a bus device missing,
or one with an address that has not been
added using the Installer menu, the display
shows, for example:


The top line of the display shows the number
of new devices found, and the number of
existing devices missing (lost). The bottom
line of the display shows the first in the list of
found and lost devices. Press  to see any
other items in the list.
Installation
4. Either: Press  to go back into Installer menu
(so that you can go and check that all the bus
devices you have installed are connected,
powered up and addressed correctly).
Note: To check an expander address, remove
the lid and briefly press the addressing
button. The two-digit display will show the bus
address for a few seconds.
OR: Press  to make the control unit update
its internal record of devices attached to the
bus. The display shows:


5. Press  to accept the change to the bus.
(You can still press  to return to the Installer
menu if you do not want to change the
number of devices on the bus.)
Note: If you attempt to leave the Installer menu
when a detector/device tamper is active, the
keypad displays a fault message telling you which
detector/device is causing the problem. Press  to
return to the Installer menu. You must either close
the detector/device tamper or delete it from the
system before you can leave the Installer menu.
Re-Entering the Installer Menu
When you enter the Installer menu from a keypad,
the alarm system is effectively disabled. While the
system is in Installer menu:
 Any other user trying to set the system from a
keypad will see the message “Installer on
Site”.
 All HUDs (including radio HUDs), fire alarm
zones, 24-hour zones and tampers are
disabled.
Note that this also applies if you are using the web
browser interface from a PC. If you have logged
into the system from a PC, the alarm system is
inactive.
If you need to re-enter the Installer menu:
1. Make sure the system is unset and showing
the standby screen (time and date).
2. Key in the installer access code ("7890" for
Grade 2 or "567890" for Grade 3). As you
start to key in the code, the display shows:


Note: If you key in an access code
incorrectly, the display shows four “stars”. Key
in the code again. If you key in a total of four
incorrect codes, the system locks you out for
90 seconds.
3. If prompted, key in a user code ("1234" for
Grade 2 or "123456" for Grade 3):


By default, you are prompted for a user code
Page 25
Installation
if you have not been in the Installer menu or
set factory defaults within the last half-hour.
This period of grace is returned to zero if the
control unit is set, or if there is a fire or burglar
alarm.
Note: You can disable the requirement for an
installer to enter a user code after the period
of grace by using the System Options – User
Access – User Code Required installer option.
However, if you set User Code Required to
NO, the control unit no longer complies with
EN50131. This option complies with BS8243
only if the user has given written consent.
4. The display shows:


5. Press  or  display the option you want to
use. The name of the option appears on the
bottom line of the display; for example:


6. Press  to select the option. The option you
selected now appears on the top line. If there
are any sub-options for that selection, the first
of them appears on the bottom line; for
example:


7. Repeat the process until you reach the
required option.
Defaulting Access Codes
If the User 1 and/or Installer codes are lost, you
must restore all user information to its factory
defaults. All prox tags, remotes and radio HUDs
will be deleted.
1. If possible, enter the Installer menu.
Note: If you cannot enter Installer menu, the
control unit will start a tamper alarm when you
open the control unit lid.
2. Remove mains power, then open the case
and disconnect the battery.
Note: This procedure will not work if the
control unit lid tamper remains closed.
3. Identify the Reset Codes pins on the main
PCB (see item 5 in Figure 3).
4. Short the Reset Codes pins together using a
screwdriver or jumper link. (Keep the short on
until step 6.)
5. Apply mains power.
The control unit loads the factory default
access codes:
Grade 2: User 1=1234, Installer=7890.
Grade 3: User 1=123456, Installer=567890
After a short pause, the system starts a
tamper alarm and the display shows the
words “Please wait...”. The red LEDs glow to
show an alert that the control unit lid is open.
Page 26
i-on1000EX
6. Remove the short from the Reset Codes pins.
7. Reconnect the battery.
8. Close the control unit lid (to restore the tamper
switch).
The display shows the time and date; for
example:


9. Key-in the default user 01 code to silence the
sounders.
The display shows:


10. Enter Installer menu and then leave it again.
The LEDs around the navigation key should
now be green. If they glow red, there may be
an alert for a missing battery that needs
acknowledgement. To force the control unit to
check the battery:
11. Press , key in 1234 (or 123456 for Grade 3),
press  again.
The navigation key LEDs should now glow
green.
Note: The log is protected and cannot be erased
by the Installer.
Restoring Factory Defaults at the Control Unit
If you wish to restore all factory default options
without defaulting the user and installer access
codes:
1. From the Installer menu, select System
Options – Restore Defaults – Factory
Defaults.
The display shows:


2. EITHER: Press  to go back to the Installer
menu without changing defaults.
OR: Press  to load defaults.
The display shows:


3. Press  or  to display the desired Security
Grade (“2” or “3”) on the bottom line of the
display, then press  to select it.
The display shows:


4. Press  or  to display the desired wiring
type on the bottom line of the display, then
press  to select it.
The display shows:


i-on1000EX
5. EITHER: Press  if you do not want to pair
buses (see page 1).
OR: Press  or  to choose Yes or No, and
 or  to display the next pairing option. On
completion, press .
The system loads all defaults except for
Access Codes and the Log.
Installation
LEDs On Control Unit PCB
There are several LEDs on the PCB that show the
functioning of various parts of the control unit:
Name
Function
Heartbeat
Flashes once per second
when the processor is
operating normally.
The display briefly shows:
Flashes rapidly when
updating software using the
USB port.


Followed by:


6. Press  until the display shows:


7. Press .
The display shows:


Because you have restored factory defaults,
the control unit has erased its internal list of
bus devices. The control unit scans the bus to
see what devices are attached and powered
up. Providing you have not set the addresses
to "null", the display shows, for example:


The top line of the display shows the number
of devices found. If a device is attached to
the bus but not powered up, the control unit
will not detect it. The bottom line of the display
shows the first in the list of found devices.
Press  to see any other items in the list.
8. Press .
The display shows:


9. Press .
The keypad sounder gives “deed ah”
confirmation tone and the display shows the
time and date, for example:


The control unit has saved all the changes
you have made.
Transferring to Another Keypad
While in the Installer menu, you can transfer to
any other keypad without leaving the Installer
menu. To do this simply go to any other wired
keypad and enter the Installer access code. The
new keypad will pick up your position in the
Installer menu. The keypad you have left will
briefly display the message “Installer session
transferred” for 5 seconds before reverting to the
time and date.
Bus Activity
(Green)
Flashes to show that bus
traffic is operating normally.
Bus Activity (Red)
Glows when the bus 12V
protection device is
operating.
Bus Pair Activity
Glows red to show that two
buses have been paired.
Ethernet activity
Plug-on Comms
Activity
Glows when comms module
has gone off-hook.
See Figure 3 for the location of the LEDs.
LED on Expanders
You may notice the DIAGNOSTIC LED flashing
on an expander PCB. The LED gives one, two,
three or four flashes a second. Each of these
sequences has the following meaning.
No. Flashes
Meaning
One
Communication with control unit
over bus is OK
Two
No communication over the bus
in the last 10 seconds.
Three
No bus address allocated to
expander
Four
No poll request received from
control unit in the last minute.
Step 11. Commission the
System
Install Detectors and Other Peripherals
1. Use the Installer menu to teach the system
the identity of any radio detectors or other
peripherals. (Note that you must have a radio
expander already connected and installed on
the bus to do this.) See the installation
instructions supplied with each detector or
peripheral.
2. Install detectors and peripherals at their
selected locations.
3. Use the Installer menu – Test option to:
a) carry out a walk test of the detectors.
b) test the operation of any other peripherals.
Page 27
Installation
Program the System
Program the system to suit user requirements.
Page 29 contains a summary of the Installer menu
on the i-on1000EX. Please see the Engineering
Guide for a more detailed description.
Note: make sure that you allocate keypads
correctly to partitions. For more information, see
“Assigning Wired Keypads to Partitions” in the
Engineering Guide.
Assemble and close the control unit:
a) Fit the lid of the control unit into the back of
the case (see Figure 49).
b) Fit and tighten the lid fixing screw.
NOTE: It is possible, for convenience, to place
links over tamper contacts to inhibit tamper alarm
during installation. Because of this feature, make
sure you test all lid tampers before completing
installations, to ensure that no links are left fitted.
Figure 49 Replacing the control unit lid.
Leave the Installer menu. The red LEDs should go
out, and the rim of the navigation keys glow
green. The system is now ready to hand over to
the user.
Handover to the User
Instruct the user on how to operate the system.
See the Administrator’s Guide. If necessary, show
them how to set the time and date on the system.
Remember to leave the Administrator’s Guide with
the user.
Page 28
i-on1000EX
i-on1000EX
Installer Menu
1 DETECTORS/ DEVICES
Detectors
1
Add/Del Detectors
Program Zones
Address Bus Device
Wired Expanders
Address Bus Device
Edit Expander
Delete Expander
Enable Expander
Replace Expander
Radio Expanders
Address Bus Device
Edit Expander
Delete Expander
Enable Expander
Replace Expander
Wired Keypads
Address Bus Device
Edit Keypad
Delete Keypad
Enable Keypad
Replace Keypad
Radio Keypads
Add/Del Radio Keypad
Edit Keypads
External Sirens
Radio Sirens
Add/Del Siren
Edit Siren
Wired Sirens
Wired SRN 01..02
Name
WAMs
Add/Del WAM
Edit WAM
2 OUTPUTS
Radio outputs1
Add Outputs
Edit Outputs
Wired outputs
Panel
Siren
Strobe
P0>00>01..8
Exp. x1-nn...
O/P x1>nn>1...4
Name
Type
Polarity
Pulsed
Partitions
Plug-by outputs
Output 01...16
Name
Type
Polarity
Pulsed
Partitions
3 PARTITIONS
Partition 1
Name
Exit mode
Settle time2
3
Exit time
Entry time
Alarm response
HUA response
Siren delay
Siren time
Strobe on Set
Strobe on Unset
Part set exit mode
2
Part set settle time
3
Part set exit time
Part set entry time
Part set alarm resp.
Part set siren delay
Part set siren time
Part set final exit
Part set entry route
Part set strobe set
Part set strobe unset
Partition 2....50
Full Set Link
Partition 2...50
Calendar Set
Add Event
Edit Event
Delete Event
Add Exception
Edit Exception
Delete Exception
4 SYSTEM OPTIONS
Wired Zone type
Panel
All Zones
User Access
HUA keys active
Quick set
Quick omit
User code reqd
2 Way Replies
2w Set Instant
Duress Enable
User reset
Zone alarms4
Zone tampers
System tampers
Confirmation (-UK
version)
Confirmation Mode
Basic
DD243
BS8243
5
Confirmation time
5
After entry
Entry keypad lock5
Sounder on
Siren on
Unconfirmed reset5
5
Confirmed reset
HUA Confirm Time6
6
Tamp as Tamp-Only
Confirmation (-EUR
version)
Sounder on
Siren on
Masking
7
Mask Override
8
Language
Restore defaults
Staged defaults
Factory defaults
Installer name
Installer code
Keypad text
Remote needs Entry
Remote Entry PrtSt
RKP needs Entry
RKP Entry PrtSt
4
Auto Rearm
Panel Loudspeaker
Entry alarm delay
Abort Time
Supervision
Jamming
Force Set
Tamper Omit
CSID Code
Silence Alerts
Mains Fail Delay
Battery 2
Set Date & Time
Panel Tamper Rtn
5 COMMUNICATIONS
ARC Reporting10
Call Mode
Phone book
IP Network10
Account Numbers
Report Type
Fast Format channels11
CID/SIA Events12
Restorals
Burg Comms Rearm 15
11
21CN FF Ack time
12
Send tamper as burg
13
Dynamic Test Call
Static Test Call14
Unset Comms
Speech Dialler10
Call Mode
Messages
Phone Book
Triggers
Destinations
Call Acknowledge
10
SMS
Call Mode
Messages
Phone Book
Triggers
10
PSTN SMS
Line Fail Response9
9
Line Fail Delay
IP Network (Own)
Web Server
Status
Port Number
Downloader
IP Address
Subnet Mask
Gateway Address
GPRS10
10
Ethernet
Downloading
Account
Connection Type
10
Rings to Answer
Answer on 1 ring10
Access Mode10
10
Phone Book
IP Network
10
Secure Callback
Modem Baud Rate10
Remote Servicing17
6 TEST
Sirens & Sounders
Wired Keypad
Radio Keypads
Expanders
Walk Test
Zone Resistances
Signal Strengths
Detectors
Radio Keypads
External Sirens
WAMs
Outputs
Radio Outputs
Wired Outputs
Plug-by Outputs
Expander Outputs
Remotes
User HUAs
Prox Tags
ARC Reporting10
10
Speech Dialler
PSU Current
Battery(s)
Locate Bus Device
7 VIEW LOG
All events
Mandatory events
Non-mandatory events
8 ABOUT
Panel
Bus
Expanders
Keypads
Comms
Module:16
Panel Ethernet
Zone Mapping
Page 29
i-on1000EX
Installer Menu
1
Appears only if a radio expander is available on the bus.
Appears only if Exit Mode is “Final Door”, “Lock Set” or “Exit Terminate”.
3
Appears only if Exit Mode is “Timed Set” or “Silent Set”.
4
Appears only when System Options – Confirmation – Confirmation Mode is “Basic”.
5
Appears only if System Options – Confirmation – Confirmation Mode is either “DD243” or “BS8243”.
6
Appears only if System Options – Confirmation – Confirmation Mode is “BS8243”.
7
Appears only when Masking is ON.
8
Appears only in EUR version.
9
Appears only when communications module fitted.
10
Options visible depend on type of communications module fitted, see Table below.
11
Appears only when Report Type=Fast Format
12
Appears when Report Type=CID or SIA
13
Appears only when Static Test call disabled.
14
Appears only when Dynamic Test call disabled.
15
Appears only when Report Type = Fast Format AND Confirmation Mode = Basic
16
Shows “None” if no module fitted.
17
Must be activated by a Eaton’s Security Business External Support Manager.
2
Table 2. Menu Options Available with Communications Modules
Communications Menu Options:
ARC
With Communications Module
i-dig02 i-gsm02 8750* GPRS*
Yes
Yes
Yes
Yes
ARC – IP Network
No
No
No
Yes
Yes
Speech Dialler
Yes
No
Yes
No
No
SMS
Yes
Yes
Yes
No
No
PSTN SMS
Yes
Yes
No
No
No
Line Fail
Yes
Yes
Yes
Yes
Yes
Line Fail Delay
Yes
Yes
Yes
Yes
Yes
IP Network (Own)
Yes
Yes
Yes
Yes
Yes
GPRS
No
No
No
No
Yes
Ethernet
No
No
No
Yes
No
Downloading - Rings to answer
Yes
Yes
No
No
No
Downloading - Answer on one ring
Yes
Yes
No
No
No
Downloading - Access Mode
Yes
Yes
Yes
No
Yes
Downloading - Phone Book
Yes
Yes
Yes
No
No
Downloading - Secure Callback
Yes
Yes
Yes
No
Yes
Downloading - Modem Baud Rate
Yes
Yes
No
No
No
Downloading - IP address
No
No
No
Yes
Yes
*The
Page 30
i-sd02
Yes
8750 and GPRS are now obsolete.
i-on1000EX
4. Maintenance
The control unit should be inspected once per
year. At each inspection:
Note: If you are replacing a keypad on a singlekeypad system, you will have to re-program the
new keypad with all the functions of the old
keypad, including any non-default ABCD key
functions.

Check the control unit for obvious signs of
damage to the case or its lid.
 Check the action of the back tamper.
 Check the condition of the control unit
standby battery.
 Check the cabling to the keypad(s) and
expander(s) for signs of damage or wear.
 Check the keypads for obvious signs of
damage.
 Test the action of all buttons on all keypads.
 Clean the keypad surface and display. To
clean the keypad, wipe the surface with a
clean soft dry cloth. Do not use water,
solvents or any proprietary cleaning materials.
 Monitor the signal strength and battery
condition of all detectors, radio keypads,
remote controls, radio HUDs and radio
sounders. Test each device. Replace
batteries as recommended by the
manufacturer’s instructions.
 Gently clean the lenses of any PIRs with a
clean, soft dry cloth. Do not use water,
solvents or any proprietary cleaning materials.
 Walk test all detectors.
 Test any external sounders and strobes.
Note that if you wish to find the location of any
keypad or expander, you can employ the Test –
Locate Bus Device option in the Installer menu.
Use this option to make a selected bus device
give a continuous tone from its sounder. Once you
have found the bus device, you can silence the
tone by opening the case and so activating the
device’s tamper.
Replacing or Removing Wired Keypads
If you need to remove or replace a wired keypad
from the system at any point, you must follow the
correct procedure. Before physically
disconnecting the keypad, enter the Installer
menu, then:
To permanently remove a keypad:
 Use the Devices/Detectors-Wired KeypadsDelete Keypad option. This ensures that the
system does not report a missing keypad and
the keypad’s internal address is erased
(allowing it to be used on another system).
To replace a keypad:

Use the Devices/Detectors-Wired KeypadsReplace Keypad option. This ensures that the
replacement keypad will retain the
programming of the old keypad.
See the Engineering Guide for more details.
5. Technical Specification
General
Product name
Product
Description
Manufacturer
Environmental
Operating
temperature
Humidity
Case material
Dimensions:
Control unit
i-KP01
KEYK01/KP01/KPZ01
EXP-W10, EXPR10, EXP-R30
Weight:
Control unit
i-KP01
KEY-K01
KEY-KP01
KEY-KPZ01
EXP-W10,
EXP-R10, EXPR30
i-on1000EX.
1000 zone endstation with
remote keypads.
Eaton’s Security Business.
Class II.
Tested -10 to +55°C.
0 to 93% RH, non-condensing.
Steel.
427 x 400 x 101, mm HxWxD.
115 x 156 x 30, mm HxWxD
128 x 128 x 29, mm HxWxD
230 x 144 x 44, mm HxWxD
6 kg (without stand-by
batteries).
0.26 kg
0.19 kg
0.19 kg
0.19 kg
0.42 kg
0.39 kg
0.39 kg
Capacities
Zones
Outputs
Expanders and
Wired Keypads
Radio Keypads
External Radio
Sirens
WAMs
1000 max (with expanders)
16 plug-by communicator
outputs on control unit, plus
1,000 max for the rest of the
system, comprising:
8 wired on control unit (four
transistor and four relay)
4 transistor based on each wired
expander
8 radio outputs on each 768/769
2 radio outputs on each 762
250 max devices, 25 per bus
max (see note 1).
50 max (two per radio expander)
50 max (two per radio expander)
50 max (two per radio expander,
repeater mode only)
Page 31
Technical Specification
Loudspeakers
Plug-on
communication
modules
Other ports
Partitions
Calendar Set
Timers
Log capacity
Internal Clock
2 on control unit, one per
expander
One
1 x USB, 1 x Ethernet
50
100 max
Up to 6,500 events: 5,000
mandatory events, 1,500 nonmandatory. Stored in EEPROM
memory, available for at least 10
years without power.
±10 minutes over one year
(depending on the accuracy of
the mains supply frequency).
999 (plus installer code)
999 (one per user)
999 (one per user)
999 (one per user)
User Codes
Remote controls
Hold Up Alarms
Proximity tags
Notes:
1. Wired keypads, wired zone expanders, and
radio zone expanders are all bus devices. You
can connect any combination of these devices
to each bus.
The i-on1000EX has a "pair buses" feature (e.g.
to pair buses 0 and 1). This enables a bus to
support double the number of devices, up to a
total system maximum of 250 devices. This
feature is intended for use when replacing an
existing system that supports more than 25
devices per bus. See the Engineering Guide for
further information.
Security
Security Grade
Radio detector
differs
Radio
Supervision
Number of
access codes
Access code
differs
Code blocking
Proximity tag
differs
Grade 2 or 3
16,777,214 (224 -2).
Programmable.
999 plus one installer
10,000 differs with 4-digit
codes.
1,000,000 differs with 6-digit
codes.
All digits may be any number 0
to 9.
Blocked for 90s after four
incorrect codes in series.
4,294,967,296 (232)
Power Supply
This product complies with the requirements of EN50131-6
Type A power supply at Grade 3 and environmental class 2.
Power supply type
Mains power supply
requirements
Page 32
A
230VAC +10%/-15%,
350mA max, 50Hz.
i-on1000EX
Total power supply
capacity:
3.0A (of which 1.5A is used
for battery recharge and
1.5A is available for
powering the system).
850mA max
850mA max
230mA max
400mA max
12V Aux supply*:
12V Bell supply
14.4V output*:
Comms power
supply*:
12V Expander Bus*:
400mA max
LS connectors
280mA in alarm.
*Note: The ratings given here represent the
maximum current that can be drawn before
triggering over-current protection.
EN50131-6 ratings
The i-on1000EX provides space for two 17Ah
batteries, giving a total of 34Ah charge.
Under EN50131-1 for Security Grade 3
installations, the required battery standby time is
30 hours, provided the system is fitted with an
ATS4 communicator capable of transmitting a
mains fail signal .
This means that all the devices powered by those
backup batteries, including the control unit and at
least one keypad, should together draw no more
in total than an average of 1.1A over a 30-hour
standby time. Note that for Security Grade 3, the
i-on1000EX must use a plug-by (“stand alone”)
communicator, which may have its own power
supply.
Under PD6662, battery standby time requirements
for Security Grade 3 drop to 12 hours, provided
the system is fitted with an ATS4 communicator
capable of transmitting a mains fail signal.
For Security Grade 2, the required battery standby
time is 12 hours. However, the total average
current available over 12 hours from the batteries
is limited by the power supply to 1.5A. (The
current is limited to 1.5A because when mains is
present the 3.0A power supply reserves 2x750mA
to recharge batteries, leaving 1.5A available to
supply the system.)
To meet Security Grade 2, the control unit can be
fitted with a plug-on communicator, for example
the i-sd02.
The table below shows the current consumption of
the control unit and each device that can be fitted
to it.
CIE power
requirement:
i-kp01 power
requirement:
KEYKPZ01/KP01/K01
power requirement
140mA min.
220mA max
30mA (normal/idle)
45mA (backlight low)
65mA (backlight high)
35mA backlight OFF,
internal prox reader only.
65mA max backlight ON,
external prox reader
connected
i-on1000EX
Technical Specification
Wired Expander
requirement
Radio Expander
requirement
Battery charging
requirement:
Plug-on
Communicator power
requirement:
Plug-on
Communicator power
requirement
Plug-by
Communicator pins
require:
10 FSL zones
5x4-wire CCL zones
12V Bus output
voltage range :
12V Aux output
voltage range:
12V Bell output
voltage range
14.4V output voltage
range:
Max p-to-p ripple
voltage:
Standby Battery:
‘Low battery’ fault at:
Aux power output fault
at:
Deep discharge
protection at:
Overvoltage protection
trigger voltage
Serviceable
components:
Standby time:
20mA max quiescent.
300mA in alarm if
sounder connected.
40mA max quiescent
320mA in alarm if
sounder connected.
750mA per battery
(recharge within 24 hrs)
i-sd02, i-dig02:
20mA quiescent
50mA max
i-gsm02:
150mA quiescent
and max.
5mA each when active.
20mA
30mA
10±0.5V to 13.8V
Plug-by O/P 116
KEY-KPZ01
Outputs
Open collector transistor,
+12VDC when inactive, 0V
when active, 500mA max.
Sounder Volume Levels (at 1m)
i-kp01 (at max volume)
Expander sounders
Expander 16 Ohm loudspeaker
70dB
70dB
93dB
Fuses
The control unit has a replaceable T500mA mains
fuse.
10±0.5V to 13.8V
Electrical Safety
10±0.5V to 14.7V
Conforms to EN60950-1.
0.5V
Other
12V, 17Ah sealed lead
acid, 2 off (not supplied).
< 12V
< 9V
If you wish to connect the i-on1000EX control unit
to a PC using either the Ethernet or the USB port,
make sure that the cables have the following
specifications:
Ethernet
Cat5e patch cable, straight or
crossed, RJ45 male plugs at
each end, suitable for
10/100Base-T.
USB
Mini-B plug for control unit end,
USB-A for PC end. Max length
3m.
10±0.5V
15.6±1.0V
Mains fuse: 500mA (T)
See “Power Availability”
on page 10.
Conforms to EN50130-4.
Conforms to EN61000-6-3.
Outputs
Panel:
O/P 1 - 4
Panel:
O/P 5 - 8
Expander:
Outputs
Min impedance 16 Ohm per
output, current consumption =
280mA in alarm.
Open collector transistor,
+12VDC when inactive, 0V
when active. 500mA max.
Note: The current is limited by
the amount available from the
power supply driving the
expander.
10±0.5V to 13.8V
Electromagnetic
Compatibility
Immunity
Emissions
LS 1 & 2
(loudspeaker)
Voltage free, single pole relay
contacts rated 24VDC @ 1A.
Open collector transistor,
+12VDC when inactive, 0V
when active. 500mA max.
Open collector transistor
+12VDC when inactive, 0V
when active, 50mA max.
Radio Expander and Keypads
Radio
Transmitter
range
Operating frequency
868.6625MHz Narrowband.
EN 300 220-3.
EN 300 330-2
The range of the transmitters
compatible with this control unit
depends on the environment in
which they are installed. As a
guideline, most transmitters will
work up 200m range in free
space conditions.
Page 33
Technical Specification
Compliance Statements
The i-on1000EX is compliant with EN50130-5
environmental class II.
i-on1000EX
739rEUR-50
DET-RDCS
Sentrol glass break detector
Combined door contact
shock sensor transmitter
Radio PIR
Pet-tolerant radio PIR
Wired PIR
Pet-tolerant wired PIR
The i-on1000EX is suitable for use in systems
designed to comply with PD 6662: 2010 at grade
3.
XCELR
XCELRPT
XCELW
XCELWPT
When installed correctly, the i-on1000EX is
capable of compliance with EN50131 at Grade 3.
Sounders
To maintain Grade 3, the i-on1000EX must be
fitted with a communicator of level ATS4 or above.
760ES
9040UK-00
When fitted with radio devices, the i-on1000EX is
capable of compliance with EN50131 at Grade 2.
Setting / Unsetting – Keypads
The i-sd02 is compliant with EN50136-1 as an
ATS2 communicator.
The i-sd02 may be used as a supplementary
communicator at Grade 3.
At Grade 2, the i-sd02 provides a compliant
communicator for the i-on1000EX provided that:
a) It is installed in accordance with the
installation instructions.
b) The connected PSTN is functioning normally.
When fitted with an i-sd02, this product provides
options A, B and C at Grade 2 as noted in Table
10 of EN50131-1:2006+A1:2009.
If the installer selects a non-compliant
configuration, he/she must remove or adjust
compliance labelling
i-rk01
i-kp01
KEY-EP
KEY-K01
KEY-KP01
KEY-KPZ01
FOB-2W-4B
i-fb01
727rEUR-00
HUD
705rEUR-00
706rEUR-00
710rEUR-00
726rEUR-50
726rEUR-60
Two-button HUD (single
channel, top button is
disabled)
Two-button HUD/tilt switch
transmitter
Two-button HUD
Long-range hand-held HUD
Short-range hand-held HUD
734rEUR-05/06
738rEUR-00/04
Page 34
Pet-tolerant PIR
PIR Transmitter (Small case)
Smoke Detector Transmitter
CC/FSL Door Contact
Transmitter (white)
CC/FSL Door Contact
Transmitter (brown)
Spyder shock sensor
(white/brown)
Two-way keyfob (HUD
function not compatible with
BS8243 or DD243)
Four-button remote control
Four-button remote control
with encrypted code (HUD
function not compatible with
BS8243 or DD243)
Communicators
i-dig02
i-gsm02
i-sd02
Detectors
713rEUR-00
714rEUR-00
720rEUR-00/50
734rEUR-00/01
Radio Keypad
Keypad (with internal prox
reader, but without zones or
external prox reader)
External prox reader for
KEY-KPZ01/KP01
keypad
keypad with internal prox
reader and terminals for
external prox reader
keypad, with internal prox
reader, two zones, one
output and terminals for
external prox reader
Setting / Unsetting - Fobs
Third-party testing carried out by Anpi.
Compatible Equipment
External Wireless sounder
Speaker boxed
PSTN Communication (ARC
only).
GSM communications
module
PSTN Communication
module with speech dialling
Accessories
703rEUR-00
Four-channel (2 zone)
transmitter
762rEUR-00
768rEUR-50
770rEUR-00
i-rc01
Two-channel Receiver
Eight-channel Receiver
Wireless Accessory Module
Relay Card
i-on1000EX
NOTES:
Page 35
i-on1000EX
www.coopersecurity.co.uk
Product Support (UK) Tel: +44 (0) 1594 541978.
Available between:
08:30 to 17:00 Monday to Friday.
Product Support Fax: (01594) 545401
email: techsupport@coopersecurity.co.uk
Part Number 12480675
Page 36
11th November 2014
Download