Programming Manual - iLight Technical Support

advertisement
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Rev3.1 10/2014
Introduction
This manual provides full details about how the EG2 Ethernet Gateway can be configured up for use.
For detailed installation instructions please refer to the EG2 Ethernet Gateway Installation Guide, available to
download from the iLight website:
http://www.ilight.co.uk/downloads/EG2-install-guide-9850-000224-00-rev0---1211.pdf
EG2 Firmware Version
This guide assumes the EG2 is using firmware version 4.04P or above. To check the firmware version
installed connection first has to be made to the EG2 using either IP or iCANnet. See section ‘Establishing
Communications with the EG2’ below.
EG2 Connectors, Indicators and Pushbuttons
iCANnet Connection
iCANnet is connected to the EG2 using the Green connector labelled iCANnet.
NOTE: The EG2 does not supply +12V from this connector.
iCANnet Termination Link
When the link is in the position shown the CAN link is terminated (120Ω). To ‘un-terminate’ the CAN line either
remove the link or move the link to the two pins nearest the iCANnet connector
Eaton’s Cooper Controls Business
Page 1 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Contents
Introduction ......................................................................................................................................................................... 1
EG2 Firmware Version ...................................................................................................................................................... 1
EG2 Connectors, Indicators and Pushbuttons ................................................................................................................. 1
iCANnet Connection .......................................................................................................................................................... 1
iCANnet Termination Link .................................................................................................................................................. 1
Device Identification Pushbutton (Ident) ............................................................................................................................ 4
CAN Status LEDs .............................................................................................................................................................. 4
Power Supply Connector ................................................................................................................................................... 4
Power Supply .................................................................................................................................................................... 4
Ethernet Connection ...................................................................................................................................................... 4
Establishing Communications with the EG2 .................................................................................................................... 4
Ethernet Address ............................................................................................................................................................... 5
Factory Default IP Address ................................................................................................................................................ 5
Changing EG2 IP address ................................................................................................................................................. 5
iCAN Device Number......................................................................................................................................................... 6
iCANnet Connection .......................................................................................................................................................... 6
Ethernet Connection .......................................................................................................................................................... 7
EG2 to Computer (direct connection) ................................................................................................................................ 7
Viewing and Editing EG2 Configuration in Device Editor ................................................................................................. 10
Ethernet Tab .................................................................................................................................................................... 11
Micro SD Card ................................................................................................................................................................. 11
Saving a Device Editor Database to the SD Card............................................................................................................ 14
Reading a stored file back from the SD Card .................................................................................................................. 15
Factory Default Status of EG2 .......................................................................................................................................... 15
Modifying the Default Status of EG2 ................................................................................................................................ 15
SmartPhone Config Tool .................................................................................................................................................. 16
Virtual Information............................................................................................................................................................ 16
Exporting Virtual Information from and iCANsoft (*.ipd) File ............................................................................................ 16
Downloading the Configuration to the EG2...................................................................................................................... 24
Remote Access to EG2 ..................................................................................................................................................... 25
UDP and TCP/IP Connections - Standard ....................................................................................................................... 26
TCP/IP Connection – Special .......................................................................................................................................... 26
Strings and ASCII Messages ........................................................................................................................................... 28
Timeclock........................................................................................................................................................................... 29
‘Timeclock Active’......................................................................................................................................................... 29
Daylight Saving ................................................................................................................................................................ 30
Time/Date ........................................................................................................................................................................ 30
Automatic Time and Date Update .................................................................................................................................... 30
Bridge Mode .................................................................................................................................................................... 31
Eaton’s Cooper Controls Business
Page 2 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Holiday Mode ..................................................................................................................................................................... 33
‘Areas To Include’ ........................................................................................................................................................ 33
Areas to Exclude.............................................................................................................................................................. 34
Playlists ........................................................................................................................................................................... 34
Playlist selection and Playback ........................................................................................................................................ 34
Default Playlist ................................................................................................................................................................. 35
Recorded Playlist ............................................................................................................................................................. 35
Random Minutes.............................................................................................................................................................. 36
The EG2 Webserver ........................................................................................................................................................ 36
Troubleshooting ................................................................................................................................................................ 38
Issue 1: Unable to see IP address of EG2 in iCANsoft when operating in DHCP mode .................................................. 38
Issue 2: Cannot communicate with the EG2 using Ethernet when using DHCP.............................................................. 38
Issue 3: Cannot communicate to EG2 in iCANsoft fully and Smartphone Config will not synchronise. ........................... 38
Eaton’s Cooper Controls Business
Page 3 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Device Identification Pushbutton (Ident)
The Device Identification switch, when pushed, will cause a Device Identification message to be sent onto the
CAN network.
If a computer is connected to the iCANnet, the EG2 will be identified in the Device tree if the device is already
loaded into iCANsoft and a message will show in the watch window and if open, the device will show in the
Advanced Network Search dialog box.
CAN Status LEDs
Behind the iCANnet Termination Link are the Status LED (Green) and Data LED (Red). The Status LED will
flash continually and the Data LED will flash when a CAN message is present on the iCANnet.
Power Supply Connector
Never connect mains power to the EG2!
NOTE: Early versions of the product were fitted with a round DC connector, but this has since changed to a
two part screw terminal of a similar style to the CAN connection terminals.
Power Supply
A regulated DC power supply must be used to provide power to the EG2. The voltage required is minimum
12V and maximum 15V. The power supply should be capable of supplying 500mA.
Ethernet Connection
Ethernet connection is achieved with a standard RJ45 connector. To connect to an Ethernet router or switch,
use a standard RJ45 cable (T-568B).
The pin out is shown above. Both ends of the cable should be wired in the same order.
Establishing Communications with the EG2
Connection the EG2 can either by using the iCANnet port or by using Ethernet via the RJ45 connector.
NOTE: For iCANnet connection to function, the EG2 must be
connected to an iCAN network consisting of at least one
other iCAN device other than the EG2. All configuration of
the EG2 must be done using the Device Editor program that
is currently supplied with the iCANsoft application. Open by
using the Device Editor icon.
Eaton’s Cooper Controls Business
Page 4 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
It is recommended that both Ethernet and CAN connections are in place before power is supplied the EG2.
Ethernet Address
Factory Default IP Address
The factory default address for the EG2 is:
The factory Ethernet default address of the EG-2 is shown above. This can be selected at any time by
deselecting DHCP and then selecting Restore Defaults.
Changing EG2 IP address
The IP address of the EG2 can be changed using Device Editor or by using the built in Webserver.
IMPORTANT
If ‘Restore Defaults’ is selected when communication to the EG2 from the computer is via Ethernet,
communications will we broken to the EG2 if the IP Address 192.168.0.100 is not in the range of the DHCP
server. There is also the chance of potential duplication of addresses. It is recommended that a fixed IP
address is used.
Using Device Editor IP connection
Open Device Editor and load the EG2.
Select the Ethernet Tab
Enter the required IP address, Subnet Mask and Gateway
Select Apply
When a change is made to the IP address the EG2 will go offline and restart. This will take approximately 30
seconds. If connection to the EG2 is by Device Editor using an IP connection then it will be necessary to
modify the IP address of the computer being used to be in the range of the new IP address of the EG2.
During this time the CAN Data and CAN Status LEDs will go off. The EG2 is back on line when these LEDs
are active again.
Using Device Editor iCAN connection
Same as above except there will be no requirement to change any settings of the computer. The EG2 will still
go off line for a short period while the new address is applied.
Eaton’s Cooper Controls Business
Page 5 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
iCAN Device Number
The EG-2 will be supplied with a factory default Device number. This will usually be 255-nnn where nnn is a
number in the range 1-255. It is recommended to renumber the device as part of the programming in order to
move the device away from segment 255.
NOTE: Device Editor will not allow users to renumber devices to segment or node values above 253.
iCANnet Connection
For physical connection details see EG2 Connectors, Indicators and Pushbuttons on page 3.
IMPORTANT
The iCANnet port does not supply +12v so some external source of +12V must be used in order to power a
PC Node or any other device that does not supply DC power to the network. A networked device such as a
Source Controller is required.
•
Connect to the iCANnet using the PC Node.
•
The EG2 can be found on the iCANnet in the same way as any other CAN device. Using the Find
Devices
•
it will appear as Device Type ‘EG2’.
Load into Device Editor by a double click of the EG2 line or if the Device is checked using the
button
•
Once loaded selecting the Gateway from the Devices tree shows the Device properties and allows
configuration.
Eaton’s Cooper Controls Business
Page 6 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Ethernet Connection
The EG-2 is set from the factory with a fixed IP address of 192.168.0.100 and with DHCP not enabled.
EG2 to Computer (direct connection)
This can be done using a standard Ethernet cable. In most cases a crossover cable is not required. If the EG2
is still set with the factory default settings it will be necessary to set the Ethernet port of the computer to an IP
address different to the EG2 but with the same Subnet mask and Gateway. The following values would allow
communication:IP Address
Subnet Mask
Default Gateway
192.168.0.101 (any number in the range 1-255 except 100)
255.255.255.0
192.168.0.1
NOTE: DHCP cannot be used in this type of connection because there is no DHCP server.
In order to communicate with the EG2 using the Ethernet port on a computer, using iCANsoft or Device Editor,
it is necessary to change the method that iCANsoft or Device Editor uses to connect. When using Ethernet,
iCANLink is not used.
Using iCANsoft
•
Open iCANsoft and on the Toolbar select Tools>Options>Network
•
Select Ethernet Gateway and set the Server IP Address to be the same as the IP Address of the EG2;
if using an EG2 straight from the factory this will be as shown above.
•
Select OK to confirm change.
Eaton’s Cooper Controls Business
Page 7 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
•
Once this has been done, iCANsoft will no longer communicate to the network using the PC Node but
using the Ethernet port only. This means that the PC Node can be disconnected
Using Device Editor
•
Open Device Editor and click the bottom right hand corner. If connecting using PC node then
connection type will be Local as shown.
•
Single click the Local and in the Connection Settings make the required changes.
•
Select OK to confirm change.
•
Once this has been done, Device Editor will no longer communicate to the network using the PC
Node but using the Ethernet port only. This means that the PC Node can be disconnected
EG-2 to Computer via Ethernet Switch connection
Eaton’s Cooper Controls Business
Page 8 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
EG-2 to Computer connection with ‘Homeplugs’
EG-2 to Computer via DHCP Router connection
When used in this configuration with a DHCP Router, either a fixed IP address can be used as when directly
connecting from the Computer to EG2 or DHCP allocated IP Address.
DHCP Allocated Address (not recommended)
To enable this both the computer and EG-2 must be set to DHCP.
•
Using Device Editor, which must be connected to the ICANnet network the EG2 is connected to using
the PC Node, reload the EG2 into Device Editor and go to the Ethernet Tab to find out the IP Address
which the DHCP server has allocated to the EG2. Here is an example:
Eaton’s Cooper Controls Business
Page 9 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
•
Change the Connection Settings of Device Editor or iCANsoft so that the IP address in the
Connection settings uses the same IP address. Changing the Connections setting for both iCANsoft
and Device Editor is described the section ‘EG2 to Computer (direct connection)’ above.
Viewing the EG2 in iCANsoft
EG2 is no longer supported in iCANsoft. All configuration should be carried out in Device Editor
Viewing and Editing EG2 Configuration in Device Editor
Device Type
This will always be as shown and cannot be modified
Serial Number
This is embedded in the Device and cannot be modified. A Refresh button is provided but this will always
return the existing number. This does send a request to the EG2 which will cause a response. The request
and response can be seen in the network traffic window in iCANsoft.
Firmware
The current firmware version is displayed here. The Refresh button will send a request to the EG2 which will
trigger a response. The firmware version is not automatically updated when a firmware update has occurred.
Eaton’s Cooper Controls Business
Page 10 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Status
In this section any unloaded or unread parts of the configuration of the EG2 will be listed. Selecting the links
will allow them to be loaded or read again. The IP address of the EG2 will be shown in this window.
Ethernet Tab
Under the Ethernet Tab you will see the following window:
At this tab the IP Details can be viewed and edited. DHCP can also be enabled or disabled..
Micro SD Card
The Micro SD card must be fitted to the EG2. The unit is supplied with a 2GB card. 4GB cards may also be
fitted. Larger cards may not operate. The micro SD card is used to Stores Log Files, Stores Configuration of
the Smart Device App and Files for File Transfer Tool e.g. iCANsoft database
To remove the SD card first power down the EG2. Push the outside edge of the Micro SD card into the socket
and release. The card will move out of the socket slightly and can then be gently removed from the socket.
To insert the card push it into the socket gently as far as it will move and release.
Eaton’s Cooper Controls Business
Page 11 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Saving an iCANsoft Database (*.ipd) to the Micro SD Card
•
First save the database to the computer being used.
•
In iCANSoft move to the Devices tree and right hand
mouse the EG2 it is intended to save the database to.
•
Select the option Save Database to EG2.
•
The following dialog box will pop up to advise saving
the database and warn that changes cannot be made
whilst the database is being uploaded to the EG2.
Selecting OK will automatically open the File Transfer Tool and download the database to the selected EG2
where it will be stored on the Micro SD card.
During the transfer progress information will be displayed in the bottom bar of the window. The window also
shows the IP address of the connected EG2.
After the transfer is completed it is necessary to select ‘Read Directory Info’ to enable the uploaded file to be
shown in the window.
Notes on transfer:
1. A file of the same name will overwrite an existing file without warning.
2. Transfers can use either iCANnet or Ethernet
Eaton’s Cooper Controls Business
Page 12 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Uploading a file to iCANsoft from Micro SD Card
This allows an iCANsoft database file stored on an EG2 to be uploaded to a computer and saved as a
name.ipd file. Once saved to the computer it can then be opened with iCANsoft.
Uploading is achieved using the File Transfer Tool which is embedded into iCANsoft.
Method 1 – Manual Opening of File Transfer Tool
This method allows manual selection of the EG2 and does not require the EG2 to be loaded into iCANsoft.
Open the File Transfer Tool by using the Plug In Tool icon on the Toolbar. It is selected by using the icon
shown circled on the menu toolbar.
Next select the File Transfer Tool from the selection offered.
At the bottom of the dialog box is details of the current connection status of iCANsoft with the iCANnet
network.
In this example it indicates connection is via Ethernet using IP address 192.168.0.195 and that the Password
is Cooper123. More about Password
IMPORTANT: Do not remove the micro SD card when the unit is powered.
A further dialog box opens and automatically
displays a list of the devices on the connected
network.
The list is not limited to EG2 devices only.
If for whatever reason the device required is
not displayed identify the reason for this and
select the Re-search button to find the device.
A Device Count indicates the number of
devices found and shows the current
connection to the iCANnet network.
All devices found can be sorted into
ascending or descending order by clicking in
the header bar above the data column. This facility is available for Device, Device Type, Device Name Serial
Number and Firmware Version.
Eaton’s Cooper Controls Business
Page 13 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Select the EG2 unit that the file is to be uploaded from and click OK
Saving a Device Editor Database to the SD Card
Note – This is only possible if all devices are loaded and configured using Device Editor.
This process is best carried out when connecting to the EG2 using IP.
Save the Database to the computer. Generally, the name to
save the file to will be the same for file saved to the computer
and to the SD Card.
Select the General tab of the EG2 that the database is to be
saved on. Frome the Custom Editors select File Transfer Tools
and then click Edit.
This will open the File Transfer Tool. Any existing files in the ROOT of the SD card will be shown.
Select Write File.
The program will ask for the filename of the file to be copied to the SD card.
Eaton’s Cooper Controls Business
Page 14 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Either leave as the current filename or enter a new
name.
The file will be written to the SD card and will be
shown in the list.
Reading a stored file back from the SD Card
This can only be done if connecting to the EG2 using IP.
Search the network for the EG2 that has the SD card that stores the configuration file stored on it.
Load the EG2 into Device Editor
Open the File Transfer window as described above.
Select the file to load from the SD Card and select Read File(s)
Save the file to a location then open the file the normal way into Device Editor.
Factory Default Status of EG2
Device Number
When new from the factory the Device number is set to Segment 255 and with a Node number in the range 1
to 255.
IP Address
IP address is set 192.168.0.100 and DHCP is turned OFF.
Modifying the Default Status of EG2
Device Number
The Device Number can be changed using iCANsoft. Right click on the EG2 once loaded into iCANsoft and
select Renumber
Users can change the Device Number within the range of ‘1-1’ to ‘253-253’.
IP Address
If the IP address is to be changed from the factory default (192.168.0.100) this can be done by setting the
EG2 to DHCP in which case an IP address will be allocated to the EG2 automatically that is correct for the
network it is connected to or a n umber can be entered manually.
If the IP address is to be entered manually this should be provided by the Network Administrator to avoid the
possibility of duplication.
Eaton’s Cooper Controls Business
Page 15 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
SmartPhone Config Tool
Virtual Information
When a system is configured using iCANsoft, ‘Virtual Information’ is created both automatically and manually.
When a device is uploaded to iCANsoft Virtual information is created from the data uploaded. When a new
Virtual Area is required in iCANsoft this adds to virtual information.
Virtual Information is used to create data for other devices not directly configurable by iCANsoft. This includes
Touchscreens when configured using the Touchscreen Editor and iPhone/Android devices when using the
SmartPhone Config Tool.
Virtual information consists of:
•
•
•
•
Area Numbers and Names
Scene Numbers and Names
Virtual Channel Numbers and Names
Area Scene Levels
This information is all stored in the ipd database of a project. Only in an iCANsoft ipd file is this collective
information stored.
By adding expanding the information within the iCANsoft file to include Area Names, Channel Names and
possibly Scene Names it can then be used in these other applications.
It is therefore worthwhile adding this information once in iCANsoft to prevent having to enter it individually in
these other tools to save time and ensure continuity.
Exporting Virtual Information from and iCANsoft (*.ipd) File
There are two methods of getting the Virtual Information from an iCANsoft file:Method 1 – Directly from iCANsoft *.ipd file.
From within the SmartPhone Config Tool use File>Import>Virtual Info From iCANsoft File.
Select the iCANsoft file that you want to get the Virtual Information from.
Eaton’s Cooper Controls Business
Page 16 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Method 2 – Export Virtual information from iCANsoft ipd file and then Import into SmartPhone Config
Tool
First Export the virtual items from iCANsoft by right hand mouse click on
the Virtual Areas and select Export Virtual Items.
Save the txt file with an appropriate name.
Open the SmartPhone Config Tool. Then File>Import>Virtual Items File to
import the previously saved file.
Method 3 –Starting the SmartPhone Config Tool from Device Editor
(Only applicable if configuration file was created using Device Editor)
From the General Tab of the EG2 select Smart Phone
Config Tool and then click Edit
The Smart Phone Config Tool will open with the Virtual
Information from the Device Editor file.
Which Method Should You Use?
Method 1 is the easiest and quickest to use. Method 2 might be used if you only have the exported Virtual
Information. A Virtual Items text file is much smaller than a *.ipd file. Method 3 is simplest if the configuration
was created using Device Editor.
Eaton’s Cooper Controls Business
Page 17 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Selecting Virtual Data to be Included on the Mobile Device
Once the Virtual Information has been imported into the SmartPhone Config Tool it will be visible on the right
hand side of the screen as shown above.
If necessary, it is possible to change the name of an Area, Scene or Channel at this time. This will not,
however, be reflected back into the iCANsoft file from where the Virtual information was exported from. If the
Smart Phone Configuration Tool was started from within Device Editor changes to area, scene and channel
names will be written back into Device Editor.
To change the name of an area, select the area in the expanded Virtual Items tree. A properties window now
allows the Name to be changed.
In the same manner Scene names can be amended when the Area is expanded.
Channel Names and whether the channel is Dimmed or Switched can also be set
Eaton’s Cooper Controls Business
Page 18 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Selecting the Areas to be Included
Areas to be used can be dragged from the Virtual Items tree to the Sections folder.
Alternatively, right click the Sections folder.
Using the Add Area, select all areas or individual areas to
add.
Changing Area, Scene and Channel Names in the
Configuration Tree
Expanding an Area in the Configuration tree allows the
names of Scenes and Channels to be modified.
Ordering of Areas, Scenes and Channels
The order of the Areas as they will appear in the App will be
as shown in the configuration. The order can be changed by
dragging areas up or down.
Use the same method to change the order of scenes and channels in an area.
Eaton’s Cooper Controls Business
Page 19 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Adding Dividers
Dividers can be inserted into the configuration to provide section on the App screen to indicate different floors
or locations. Dividers can be named and dragged to different positions.
Deleting Areas, Scenes, Channels from a Configuration
An area can be deleted from the configuration by selecting the Area in the configuration tree and selecting
Delete on the keyboard or from a right click.
Eaton’s Cooper Controls Business
Page 20 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Naming the Default Configuration
The default configuration ‘ConfigFile1’ can be renamed (e.g. ‘Home’). Click on the pencil icon and the ‘New
Config Name’ window will appear. Enter the new name for the configuration and click OK.
Adding a New Configuration
To add a configuration, click on the green cross icon next to the configuration drop-down box. The default
name will be ‘ConfigFile(n+1)’ (where n is the last Config number made prior to this). To rename, click on the
pencil icon and the ‘New Config Name’ window will appear. Enter the new name for the configuration and click
OK.
Deleting a Configuration
To delete a configuration select the configuration from the drop-dwn menu and then click on the red cross
icon.
Buttons
Within each Area are found the buttons which are generally used to select scenes
Each Button can have two actions. These two actions operate in a similar to the buttons found on control
panels/control stations. Just as a Press and Release but the Release action occurs a short time after the
button is pressed even if the button is still being pressed.
The Press action, like on the control panel/stations will, with the correct action highlight the button.
Eaton’s Cooper Controls Business
Page 21 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
In the highlighted RED box in the button properties can be seen where the simulated Release action is
configured.
Can Save – allows any channel level changes using the App to be saved.
Can Raise Lower – allows Raise Lower functionality
Passwords
Passwords can be added to all buttons. Different
buttons and actions can be assigned different
passwords.
Passwords are added to Groups which have a
variable name that is used throughout the
configuration.
Right click Passwords to add a Password Group.
Password Groups can be given a name that makes them easier to identify.
Right Click the Group Name in order to add the actual password. A Password Group can have multiple
passwords. This allows multiple users to have different passwords for the same functions but then to be able
to use the same password for functions other users do not have access to.
User 1
Grd Floor
User 2
1st Floor
User 3
2nd Floor
Eaton’s Cooper Controls Business
Page 22 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
This is how the groups and passwords would be arranged in the
configuration tool.
Examples of Password Allocation
An entire area can be protected by passwords for Access to the Area, Area Edit and Saving of modified
scenes.
In addition to this each Scene can be password protected.
Here, all the scenes in the Entry Hall
have been selected together by
selecting the first scene and then with
Shift held down selecting the last.
The required Password Group can
then be allocated for all Scenes.
If however different passwords are
required for different scenes this can
also be achieved.
Eaton’s Cooper Controls Business
Page 23 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
The table below indicates the way passwords can be allocated to the Functions in each Area
Function
Access to Area
Ability to Edit levels
Ability to Save
Buttons
Password Allocation
Single Password Group
Single Password Group
Single Password Group
Individual Single Password Group per Button
Downloading the Configuration to the EG2
Use the red circled button to open the Device Config Manager. This is the
Tool that allows the transfer of the configuration to the EG2.
The configurations will show in the right hand side of the Device File
Manager window.
Drag the required file to the left hand side. This will automatically cause
the configuration to be transferred to the EG2.
Eaton’s Cooper Controls Business
Page 24 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Remote Access to EG2
Using a Computer running iCANsoft
The EG2 allows the possibility of remote accessing a system via the Internet.
Access to the EG2 will require that Port Forwarding is used on a router to allow access through the Firewall.
The method of setting up the router will depend on the router type. Consult the router instructions or system
administrator.
The EG2 is identified in the network by its port number – 30089
Set the Server address in iCANsoft on the remote
computer to the router address and the port number of
the EG2.
Eaton’s Cooper Controls Business
Page 25 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
UDP and TCP/IP Connections - Standard
The EG2 can communicate with other devices on IP utilizing either UDP or TCP/IP. This allows the iLight
standard ASCII strings to be used to communicate bi-directionally with other control systems.
•
The port number for UDP is 30088
•
The port number for TCP/IP is 30087
In both cases the other control system has to initiate communication with the EG2 before the EG2 will send
messages. This is because the EG2 needs to know where the messages have to be sent and it gets this
information from receiving data.
Whilst the Ethernet port can be used simultaneously to connect to a router for purposes of using with
handheld devices only a single external control system can be used since the EG2 will only correspond with
the last control system it communicated with.
Therefore, if the requirement is to communicate with two independent external systems using UDP two EG2
units will be required.
TCP/IP Connection – Special
Example 1
A control system that has an IP address of 192.168.0.18 is required to communicate bi-directionally with the
EG2 using Port 20000 and to use the standard iLight ASCII protocol.
The control system will be for this purpose a TCP server. The EG2 will
need to be configured to make a connection with the control system.
To do this go to the EG2 Settings tab and set the Make Connection to
have the IP address and Port number of the control system.
Set the Send ASCII to either blank or 1.
Click Apply. The EG2 will need to restart. After the restart
communications between the EG2 and control system will be
established.
Example 2
All as above but a two more control systems (IP 192.168.0.19 Port 20000, 192.168.0.34 Port 20001). The
system using 192.168.0.34 does not need to communicate using standard iLight ASCII. Set up the ‘Make
Connection’ and ‘SendASCII’ as below.
Each IP address is separated by a
space.
The number of the IP addresses that
are to receive and send ASCII are
entered separated by a space. In this
example 1 and 2 indicate that the
address 192.168.0.18 and
192.168.0.19 will receive and send
ASCII.
Eaton’s Cooper Controls Business
Page 26 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Remote Access to a Non-Local EG2 (and Connecting to a Local EG2 that Cannot AutoConnect)
If you are connecting to an EG2 from an mobile device on a network that is not directly in the same subnet as
the EG2 IP address, you may need to manually add the EG2 to the iLight Remote Application. The EG2 uses
UDP messages that are broadcast every few seconds so that mobile devices will automatically discover the
EG2.
The UDP broadcast packets are not transmitted beyond the local network, entailing the need to manually add
the EG2 if you are connecting through a router from another network or the internet. In order for this operate,
the network administrator must add port forwarding to the router on port 30089 to map this to the local EG2.
In addition, in some instances, UDP broadcast may not be supported or be turned off by IT administrators. In
this instance, you may need to manually force the connection between the iPad or Android, and the EG2
through port 30089.
Example:
You have an external router with an internal IP of 192.168.0.1 and an external IP of 10.1.2.3. The EG2 IP is
192.168.0.100. Your network administrator has setup port forwarding on Incoming Port 30089(TCP) to
forward this to 192.168.0.100, port 30089.
In the iLumin Remote Application, select the ‘Add’ button on the main Discovery page. Type in the following
info for the application:
Name: Any name you would like for the connection.
Address 10.1.2.3 (external router IP)
Port: 30089
Password: Cooper123 (this is the default password. If it has been changed in the Smartphone Config Tool
‘Device Properties’ window, enter the correct password.)
These same steps can be used to force a manual connection to an EG2 that is not being found via the mobile
device, typing in the IP address of the EG2 and port 30089 with the Cooper123 password.
Eaton’s Cooper Controls Business
Page 27 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Strings and ASCII Messages
The EG2 will send ASCII strings to other devices using either UDP or TCP. Custom strings can be sent to
other devices.
The example here shows four custom outputs strings configured on an EG2.
Strings 2 and 3 will send the Data whenever the a message is received by the EG2 that meets the criteria for
Output Actions 2 and 3. In this case an Area 10 Scene 1 message on the network would result in a ASCII
string 2 being sent and a Start Sequence 1 Action in Device 66-101 would cause the String 3 message to be
sent.
Eaton’s Cooper Controls Business
Page 28 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Timeclock
Access the Timeclock feature using the Timeclock tab in Device Editor – do not use iCANsoft
First set up the Location and Time by selecting the Location/Time icon
‘Timeclock Active’
For the Timeclock to operate the Timeclock Active must be checked as shown in these screenshots.
Location
Use this to set the location of the
EG2. Most major cities of the
world are available from the drop
down lists using the Select From
List option.
However, if there is no close listed
location enter the co-ordinates
manually by selecting Manual
Coordinates.
Timezone
If a city is selected from the list
the timezone will automatically
change to that appropriate for the
city.
If the coordinates are entered
manually then the timezone will
also have to be manually entered
from the list.
Sunrise and Sunset Times
These times are calculated automatically based on the latitude, longitude, date and timezone. The Sunrise
and Sunset times should be the same in both the Location box and Time/Date box after changes have been
applied.
Sunrise is the time when the sun is first visible on the horizon. Sunset is the instant when the sun is no longer
visible on the horizon.
Eaton’s Cooper Controls Business
Page 29 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Daylight Saving
There are 3 options here – Auto, Manual and Disabled.
Auto applies to Europe where there is an international standard relating to daylight saving on fixed dates.
These are the last Sunday in March and last Sunday in October respectively. The clock will automatically
calculate the correct date for this to occur.
Manual allows for a start and end date to be manually entered. This may require the clock to be manually
adjusted each year.
Disabled means that no Daylight Saving will take place.
Time/Date
This section will normally display the current time and date of the clock in the EG2. When the EG2 is loaded
into Device Editor the date will be loaded. To confirm the Time and Date of the EG2 at any time use the
button.
Automatic Time and Date Update
If the EG2 is connected to the internet and has access to the NTP Pool then
the time will be kept accurate. The NTP Pool is a collection of networked
computers that provide highly accurate time via the Network Time Protocol.
These computers form the pool.ntp.org domain.
To disable NTP automatic updating of the time, go to the EG2 Settings tab
and uncheck the NtpHost. Changing the status of the NtpHost requires the
EG2 to restart.
Eaton’s Cooper Controls Business
Page 30 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Bridge Mode
Bridge mode allows an Ethernet network to be used as the spine that joins different networks together.
Each EG2 will have an IP address in order to connect to the Ethernet network.
The Bridge In and Bridge Out have to be set in each EG2.
Imagine that the EG2 are connected in a circle as shown above.
Go to the Ethernet Settings and in the Bridge In and Bridge Out settings put in each EG2 the IP addresses of
the two EG2s that are either side of the device being configured.
If there are only two EG2 connected to the Ethernet.
Example 1 – 2 EG2s connected to an Ethernet Spine
EG2#1 IP address is 192.168.0.100
EG2#2 IP address is 192.168.0.101
In EG2#1 the Bridge In and Bridge Out addresses would both be set to 192.168.0.101.
In EG2#2 the Bridge In and Bridge Out addresses would both be set to 192.168.0.100.
Eaton’s Cooper Controls Business
Page 31 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Example 2 – 4 EG2s connected to an Ethernet Spine
EG2#1 IP address is 192.168.0.100
EG2#2 IP address is 192.168.0.101
EG2#3 IP address is 192.168.0.68
EG2#4 IP address is 192.168.0.77
In EG2#1 the Bridge In address set to 192.168.0.77; Bridge Out address set to 192.168.101.
In EG2#2 the Bridge In address set to 192.168.0.100; Bridge Out address set to 192.168.68.
In EG2#3 the Bridge In address set to 192.168.0.101; Bridge Out address set to 192.168.77.
In EG2#4 the Bridge In address set to 192.168.0.68; Bridge Out address set to 192.168.100.
Any change of the Bridge In and Bridge Out settings will require the EG2 to be reset.
Once done all the local networks attached to each of the EG2s will appear in Device Editor as a single
network.
Eaton’s Cooper Controls Business
Page 32 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Holiday Mode
Holiday Mode can replay 2 weeks of recorded scene selections which could be used to give the impression
that a property is occupied.
When the Holiday Mode is activated, by a Start Playback command, the EG2 will playback over a 2 week
period all the scenes that have either been recorded by the EG2 over the previous two weeks or replay a
manually entered list of scenes.
Access Holiday Mode configuration using the Holiday Mode Tab
‘Areas To Include’
The options here are to select ‘All’ or to enter only the areas that are to be included in the playback of the
‘Recorded’ or ‘Default’ scenes. Use the + and – to add or remove scenes in the list. Areas can be entered in
the following format:Use the + button to add an area. By default the first Area in the Virtual Items list will be added (commonly
Area 1).
Edit the range using the edit field on the right hand side of the screen.
Check the Range enable a range of areas to be
added
Eaton’s Cooper Controls Business
Page 33 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Areas to Exclude
The options here are to select ‘None’ which means that all areas included in the Areas tTo Include will be
played back or to exclude some areas which are listed in the Areas To Include.
All areas in the Areas To Include and Areas To Exclude are scanned before a scene message in the Playback
is actioned.
Example
Areas To Include
Areas To Exclude
2 – 25, 43 – 60
16, 18 – 20, 52
Areas that will be included in Playback will be 2 – 15, 17, 21 – 25, 43 – 51 & 53 – 60
Playlists
Both playlists must include 2 weeks of scenes to be replayed. If only scenes are included for week 1 or 2, then
only that single week will be replayed. Playlists are in week and day order. The Recorded playlist will always
include all the last two weeks of scene
selections.
The scenes to be replayed in the Recorded
Playlist can be viewed by selecting the ‘Get
Latest button’. The list shown in Device Editor
will not be correct unless the ‘Get Latest’
button is pressed.
All scene selections are included in the recording regardless of whether they are excluded from the playback.
Playlist selection and Playback
Three messages are used to control playback of Holiday Mode
Stop Playback
Playback Default
Playback Recorded
The Stop Playback command will stop both Default and Recorded Playback.
All commands must include the device number of the EG2 which contain the playback scenes.
Using Device Editor
In Device Editor the Playback commands are available as a selectable named action
Eaton’s Cooper Controls Business
Page 34 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Timeclock Commands Using CAN Messages
This requires a CAN message to be sent:Hex Version
11 bit ID
DLC
3EE Hex
5
Data 0
Data 1
Device Number
Data 4
Data 2
Data 3
Data 4
0
40
Data 4
Function Name
00 Hex
Stop Playback
01 Hex
Playback Recorded
02 Hex
Playback Default
When entering this as a ‘Send CAN message’ from a device uncheck the ‘Assume hex value’ as this does not
require any data converted to Hex
3EE Hex = 1006
DLC = 5
Data 2 = 0
Data 3 = 64
Data 4 will depend on action
0 = Stop Playback
1 = Playback Recorded
2 = Playback Default
Default Playlist
The Default Playlist can be used in preference to the Recorded Playlist. The entries of the Default Playlist can
be edited as required.
Recorded Playlist
If Recorded Playlist is selected the EG2 will playback the scenes select during the previous two weeks. The
scenes that will be replayed are given week numbers of either Week 1 or Week 2. Week 1 days apply to odd
number weeks of the year and Week 2 days apply to even numbers of the year.
If no scenes are entered for a day the scenes entered in the Default playlist will be used for that day only.
Example
A message to start Recorded Playback is sent at 13:00 on Wednesday of week number 33.
Immediately playback is selected the EG2 will stop recording scenes and start to use the list of
recorded scenes starting from 13:00 of the week 2 Wednesday.
Eaton’s Cooper Controls Business
Page 35 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Random Minutes
This allows for additional minutes to be added to the time that items in the playlist are replayed. It does not
add a fixed value equal to the number entered but adds a value in whole minutes randomly up to the value
entered.
Example
Random Minutes entered = 30min (max value that can be entered. First replayed item could have 16
minutes added, second replayed scene could have 20 minutes added
The EG2 Webserver
The EG2 has built-in Webserver that can be accessed by using a Browser on the Ethernet network the EG2 is
connected to. The Browser must be either IE10 or later or Google Chrome.
There are two levels of access – User Level and Administrator Level. Both levels are protected by different
passwords.
Accessing the EG2 Webserver.
Type the
Type the IP address of the EG2 into the Browser.
Without entering a Username and Password only the About provides any information.
About will typically display the following:-
Eaton’s Cooper Controls Business
Page 36 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Login Level 1
Default User Name – User
Default Password - Password
At this level it is possible to select scenes and change channel levels in areas using the same data as used
for the iPhone and Android applications.
Login Level 2 (Administrator)
Default Admin Name – Admin
Default Admin Password – Cooper123
•
•
•
•
Config – Allows selection of the configuration file to use.
Area – Allows selection Area to be controlled.
Scene – Allows selection of Scene in the Area
Use the Select Scene button to initiate the scene change.
Diagnostics
This screen provides information about the firmware in the EG2.
Administrator level has all the same facilities as the User level but has the addition feature of being able to set
some Configuration data of the EG2.
IMPORTANT: Great care should be used with this feature as it is possible to change settings that can only be
resolved by local intervention and potentially to prevent aspects of a system not to function correctly. The
advice has to be to not access these pages. For this reason the User Name and Password for the
Administrator section are not printed here. Please speak to iLight Technical Support.
Eaton’s Cooper Controls Business
Page 37 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Troubleshooting
Issue 1: Unable to see IP address of EG2 in iCANsoft when operating in DHCP mode
This is likely to be because the EG2 was started before the connection to the Ethernet was established.
Communication with the DHCP server to establish an IP address only occurs at power up. There are 3
methods to resolve this. Choose the most appropriate one for your situation:
1. Press the Reset button next to the Ethernet
connector,
2. Send a Reset message to the EG-2 through the
iCANnet connection or
3. Removing the power to the EG-2 for a few
seconds and then reinstate it.
When using either of the methods allow up to 45 seconds
for the EG-2 to start up before reloading the device into
iCANsoft using CAN connection.
Issue 2: Cannot communicate with the EG2 using Ethernet when using DHCP
This is a similar issue to the previous scenario, possibly occurring after power issues resulting in the EG2
being powered before the DHCP server. Follow the steps from Issue 1 to resolve this issue.
.
If problem persists, consider not using DHCP and use a fixed IP address. Discuss with your network
administrator if you need assistance in setting this up.
Issue 3: Cannot communicate to EG2 in iCANsoft fully and Smartphone Config will not synchronise.
Apart from general CAN based issues such as loose connections or incorrect termination, problems with
getting an EG2 to be fully configurable in iCANsoft and the Smartphone Config Tool could be due to a missing
or corrupt SD card.
If the SD card is present, make sure it is fully inserted into the holder. If it is missing or corrupt then you will
need to get a replacement card which must then be loaded with the necessary files to allow the unit to
operate.
Contact Eaton’s Cooper Controls Technical Support by submitting a support enquiry at www.ilight.info or by
calling +44 (0) 844 324 9100 (9am-5pm GMT) for details of how to resolve this.
Eaton’s Cooper Controls Business
Page 38 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Lighting Controls
EG2 Ethernet Gateway - Programming Manual
Glossary of Terms
DHCP - Dynamic Host Configuration Protocol This is a network configuration protocol that allows IP
addresses to be allocated to connected clients from a DHCP server automatically. The Network Administrator
will assign a range of addresses for use b
Eaton’s Cooper Controls Business
Page 39 of 39
20 Greenhill Crescent, Watford Business Park,
Watford, Hertfordshire, WD18 8JA, UK
T: +44 (0)1923 495495 F: +44 (0)1923 228796
E: enquiries@ilight.co.uk www.ilight.co.uk
Download