INSTALLATION GUIDE CURRENT MONITORING TM H280, H280NC TM 280, 280NC Load Status Switch Installer’s Specifications Sensor Power Operating Temperature Operating Humidity LED Status Frequency Wire Specifications: Lead Length Gauge Agency Approvals Line powered -15° to 60°C (5° to 140°F) 10-90% RH, non-condensing GREEN LED=status normal; RED LED=status alarm 50/60 Hz 14”(356mm) min. UL1015; Neutral: 18AWG; Line: 12AWG; Status: 16AWG UL 508, E150462 INSTALLATION Disconnect and lock out all power sources before beginning the installation. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • • • • • Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Turn off all power supplying equipment before working on or inside the equipment. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Failure to follow these instructions will result in death or serious injury. 2. Secure with the conduit nut provided. 3. Connect load in series: • C hoose one orange wire and connect to load side of switch. • Choose the other orange wire and connect to load. 4. Connect status output: • C onnect the grey wires (or brown wires for H280NC) to controller digital input. Not polarity sensitive. NOTICE • • • • 1. Using the threaded nipple, connect the switch to the desired enclosure through a knock out hole. This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure. 5. Secure the enclosure and reconnect power. Wires that are not terminated must be isolated or insulated, i.e. wire nut. DIMENSIONS 2.9" (74 mm) 1.6" (41 mm) 2.8" (71 mm) 1.7" (43 mm) 1.8" (46 mm) 1/2" NPT Nipple Z203739-0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. INSTALLATION GUIDE H280, H280NC TM OPERATION WIRING EXAMPLE WIRING COLOR CODES Line Connections POWER SOURCE VOLTAGE Current Switch Output ORANGE 110-277VAC w llo ye w llo ye White Orange Neutral Orange Wht/Yellow NOTE: Incidental loads as small as 30 mA AC connected in parallel to the sensed load (e.g. pilot lamps or control circuits) might draw enough current to give a false load presence signal, even though the true load has been interrupted. ORANGE To Load Line STATUS OUTPUT From Line Current Flow Status Output (H280: Grey; H280NC: Brown) Sw itc h The H280 and H280NC load status switches monitor both voltage and current on manually switched loads (e.g., lights/fans in bathrooms). This device provides status monitoring for loads that are not, or cannot be, controlled by a building control system. The H280 has a normally open (N.O.) output switch, while the H280NC is normally closed (N.C.). Dual colored LEDs provide easy indication of output, with green for normal output and red for alarm status. The H280 and H280NC require no external power to generate the output. Voltage Switch CURRENT H280 H280NC LED ON ON OPEN CLOSED GREEN ON OFF CLOSED OPEN RED OFF OFF OPEN CLOSED OFF Neutral Status Output Connections H280 (N.O.) BROWN COMMON COMMON GREY BROWN N.O. Z203739-0A H280NC (N.C.) GREY PAGE 2 N.C. ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.