INSTALLATION GUIDE
CURRENT MONITORING
TM
H280, H280NC
TM
280, 280NC
Load Status Switch
Installer’s Specifications
Sensor Power
Operating Temperature
Operating Humidity
LED Status
Frequency
Wire Specifications:
Lead Length
Gauge
Agency Approvals
Line powered
-15° to 60°C (5° to 140°F)
10-90% RH, non-condensing
GREEN LED=status normal; RED LED=status alarm
50/60 Hz
14”(356mm) min.
UL1015; Neutral: 18AWG; Line: 12AWG; Status: 16AWG
UL 508, E150462
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
2. Secure with the conduit nut provided.
3. Connect load in series:
• C hoose one orange wire and connect to load side of switch.
• Choose the other orange wire and connect to load.
4. Connect status output:
• C onnect the grey wires (or brown wires for H280NC) to controller digital
input. Not polarity sensitive.
NOTICE
•
•
•
•
1. Using the threaded nipple, connect the switch to the desired enclosure through a
knock out hole.
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
5. Secure the enclosure and reconnect power.
Wires that are not terminated must be isolated or insulated, i.e. wire nut.
DIMENSIONS
2.9"
(74 mm)
1.6"
(41 mm)
2.8"
(71 mm)
1.7"
(43 mm)
1.8"
(46 mm)
1/2" NPT Nipple
Z203739-0A
PAGE 1
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
H280, H280NC
TM
OPERATION
WIRING EXAMPLE
WIRING COLOR CODES
Line Connections
POWER
SOURCE
VOLTAGE
Current
Switch
Output
ORANGE
110-277VAC
w
llo
ye
w
llo
ye
White
Orange
Neutral
Orange
Wht/Yellow
NOTE: Incidental loads as small as 30 mA AC connected in parallel to the sensed load (e.g. pilot
lamps or control circuits) might draw enough current to give a false load presence signal, even
though the true load has been interrupted.
ORANGE
To Load
Line
STATUS OUTPUT
From Line
Current Flow
Status Output
(H280: Grey;
H280NC: Brown)
Sw
itc
h
The H280 and H280NC load status switches monitor both voltage and current on
manually switched loads (e.g., lights/fans in bathrooms). This device provides status
monitoring for loads that are not, or cannot be, controlled by a building control
system. The H280 has a normally open (N.O.) output switch, while the H280NC is
normally closed (N.C.). Dual colored LEDs provide easy indication of output, with
green for normal output and red for alarm status. The H280 and H280NC require no
external power to generate the output.
Voltage
Switch
CURRENT
H280
H280NC
LED
ON
ON
OPEN
CLOSED
GREEN
ON
OFF
CLOSED
OPEN
RED
OFF
OFF
OPEN
CLOSED
OFF
Neutral
Status Output Connections
H280 (N.O.)
BROWN
COMMON
COMMON
GREY
BROWN
N.O.
Z203739-0A
H280NC (N.C.)
GREY
PAGE 2
N.C.
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com