CEAG History of self-contained emergency lighting.

advertisement
CEAG History of self-contained
emergency lighting.
Month Day, Year
CEAG History of self-contained
emergency lighting.
¾ In 1971: CEAG produced the worlds first explosion
protected emergency light fitting based on eLLK 70 design.
¾ eLLK 70 series is still in use today.
¾ That represents a 34 years in operation .
¾ No spare parts or batteries available
Replaced by eLLK 92 series, see page 7
2
1. Maintenance
Practice
1.1 Production period: 1982 - 1993
eLLK 81 020/20 N and eLLK 81 040/40 N
Emergency light fittings types:
eLLK 81020/20 N (2 x 20 W T12-Fa6)
eLLK 81040/40 N (2 x 40 W T12-Fa6)
No spare parts or batteries available
Replaced by eLLK 92 series, see page 7
1. Maintenance
Practice
1.1 Production period: 1982 - 1993
eLLK 81 020/20 N and eLLK 81 040/40 N
Replacement type: CEAG eLLK 92018/18 NIB
Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)
CEAG eLLK 92036/36 NIB.
Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)
1.2 Production period: 1993 - 1995
eLLK 92018/18 N and eLLK 92036/36 N
Red lampholder
= emergency lamp
Red LED at the
lampholder
Emergency light fittings types:
eLLK 92018/18 N (2 x 18 W T8-Fa6/G13)
eLLK 92036/36 N (2 x 36 W T8-Fa6/G13)
For direct replacement and batteries
available see page 7.
1. Maintenance
Practice
1.2 Production period: 1993 - 1995
eLLK 92018/18 N and eLLK 92036/36 N
Installed Battery: 6 V 7 Ah
emergency duration time: 1.5 h or 3.0 h
Charging duration: 24 h/ >90 % of rated capacity
Fault indicators: FIRST CHECK LAMPS ARE WORKING
No red LED
Failure in the
change inverter/
charging circuit ballast unit
No emergency Battery or inverter change battery/
light
fault
change inverter
No mains
light/ emerg.
light o.k.
Ballast faulty
change ballast
1. Maintenance
Practice
1.2 Production period: 1993 - 1995
eLLK 92 018/18 N and eLLK 92 036/36 N
Replacement type: CEAG eLLK 92018/18 NIB
Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)
CEAG eLLK 92036/36 NIB.
Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)
Fitting replacement type: Battery replacement:
type 2710-2 (Ni) Order no. 2 2710 902 000
1. Maintenance
Practice
Production period: 1995 - 2002
1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni
1 red LED
5 green LEDs
grey battery box
Emergency light fittings types:
eLLK 92018/18 Ni (2 x 18 W T8-Fa6/G13)
eLLK 92036/36 Ni (2 x 36 W T8-Fa6/G13)
For direct replacement and spare batteries
available see page 12.
1. Maintenance
Practice
Production period: 1995 - 2002
1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni
Installed Battery: 6 V 7 Ah
emergency duration time: 1.5 h or 3.0 h
Circuit diagram see page 10/11
Charging duration: 14 h/>90 % capacity
Fault indicators: FIRST CHECK LAMPS ARE WORKING
Red LED flashing Last duration test
> 6 month or
Emerg. duration
< 30 min.
No mains light/
Ballast fault
emerg. light o.k.
no green LED
no charging
start duration test for
> 30 min.
fully charge (cycle!)
start test again
change ballast
faulty battery/inverter
change battery/inverter
1. Maintenance
Practice
Production period: 1995 - 2002
1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni
Wiring
diagram
eLLK
92018/18 Ni
1. Maintenance
Practice
Production period: 1995 - 2002
1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni
Wiring
diagram
eLLK
92036/36 Ni
1. Maintenance
Production period: 1995 - 2002
1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni
Replacement type: CEAG eLLK 92018/18 NIB
Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)
CEAG eLLK 92036/36 NIB.
Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)
Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)
Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)
Fitting replacement type: Battery replacement:
type 2710-2 (Ni) Order no. 2 2710 902 000
Practice
1. Maintenance
Practice
Production period: 2002 - now
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
1 red LED
5 green LEDs
black battery box
Emergency light fittings types:
eLLK 92018/18 NIB (2 x 18 W T8-Fa6/G13)
eLLK 92036/36 NIB (2 x 36 W T8-Fa6/G13)
Spare parts and batteries available
See page 14
1. Maintenance
Practice
Production period: 2002 - now
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
Replacement fitting type:
eLLK 92018/18 NIB
CEAG.
Bi-pin lamp
Order No.: 1 2260 879 101 (2 x M25 plastic)
Order No.: 1 2260 879 103 (4 x M25 plastic)
Order No.: 1 2260 879 111 (4 x M20 metal)
single pin lamp
1 2210 879 111
eLLK 92036/36 NIB
CEAG.
Bi-pin lamp
single pin lamp
Order No.: 1 2261 879 101 (2 x M25 plastic)
Order No.: 1 2261 879 103 (4 x M25 plastic)
Order No.: 1 2261 879 111 (4 x M20 metal)
1 2211 879 111
Replacement battery type:
type 2710-3 (NIB), Order no. 2 2710 904 000
1. Maintenance
Practice
Production period: 2002 - Current
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
Installed Battery: 6 V 7 Ah
optional emergency duration time:
1.5 h or 3.0 h
Charging duration: 14 h/>90 % capacity
Automatic function test every week (< 5 minutes)
Automatic duration test every 3 months
Automatic battery monitoring
5 green LEDs for capacity monitoring
Circuit Diagram see page 18/19
1. Maintenance
Practice
Production period: 2002 - Current
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
L
L
L1
L1
L2
L2
L3
L3
N
N
PE
PE
0
L1
N
LL
LL
Wiring
diagram
eLLK
92036/36
NIB
LL
FS
LL1
LL2
EVG..236
L
N +B
LL -B
FS B1
Not B2
LL1 B5
B4 B6
B3
+
VE97236
1
2
3
Ersatzbruecke fuer Fernschalter
muss beim Anschluss eines
Schalters entfernt werden
Netzlampe/Mains lamp
Remote Switch,
to be removed for
connection of
inhibit switch
Notlampe/Emergency lamp
eBK 02
1. Maintenance
Practice
Production period: 2002 - Current
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
0
+
Wiring
diagram
eLLK
92018/18
NIB
1
2
3
1. Maintenance
Practice
Production period: 2002 - now
1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB
Fault indicators: FIRST ACTION CHECK LAMPS ARE WORKING
LED indication
possible reason
action
Red LED flashing
Last duration test
start duration test for
> 3 month or
> 30 min.
Emerg. duration
fully charge (cycle!)
< 30 min.
start test again
Red LED cont. on
Battery failure
replace battery
No mains light/
Ballast fault
change ballast
emerg. light o.k.
No green LED
not charging
faulty battery/inverter
change battery/inverter
less than 2 LEDs
ageing of the
cycle battery, start full
on after fully
battery;
duration test, if not
charged
capacity loss
more LED on, change
1.5 Visual capacity of the battery.
Automatic display of the remaining capacity
The eLLK 92 NIB series will continuously show the actual capacity
of the installed battery:
With steps of 20 % displayed by 5 green LEDs, the residual capacity
can be monitored at the battery enclosure.
100 % rated capacity
80 % rated capacity
60 % rated capacity
40 % rated capacity
20 % rated capacity
a flashing LED indicates
charging to the next step
Automatic display of fault conditions
The red LED shows a fault indication:
• continuously on.
Red LED
continuously on:
Battery fault
Battery must be
replaced
Red LED flashing:
Function test/duration test
not passed
Last duration test more
than 3 month passed
(Inhibit switch off?)
Charge battery at least
24h Repeat function test
manually (cut off line)
If red LED is still flashing
Battery capacity too low
- Change battery -
2. Installation
2.1 Setting of emergency duration
To select the rated emergency duration (1.5 or 3 h) the
wire at terminal 1 is used.
2.1.1
1.5 h rated emergency duration
both wires have to be connected on terminal 1
2.1.2
3.0 h rated emergency duration
the wires have to be disconnected:
one to terminal 1
one to terminal 0
0
+
1
2
3
Ersatzbruecke fuer Fernschalter
muss beim Anschluss eines
Schalters entfernt werden
Remote Switch,
to be removed for
connection of
inhibit switch
eBK 02
2. Installation
2.2 Connecting inhibit switch
0
+
1
Connect up to 10 eLLK92… NIB to one central inhibit switch
(Ex-e circuit). This switch will block the emergency operation
during a power failure.
Do not use it for maintenance work!
Note:
An open inhibit switch does not allow an automatic function- or
duration test.
This will cause a flashing red LED at the battery box.
2
3
Ersatzbruecke fuer Fernschalter
muss beim Anschluss eines
Schalters entfernt werden
Remote Switch,
to be removed for
connection of
inhibit switch
ELLK92NIB
ELLK92NIB
ELLK92NIB
ELLK92NIB
3. Calculation of
emergency
duration
3.1 Display of the NIB-Battery
The 5 green LEDs shows the actual charging state of
the NiCd-battery.
A new battery with nominal 7 Ah capacity will be the
equivalent to 5 green LEDs. Each LED indicates approx.
20 % of the nominal capacity (= 1.4 Ah)
By ageing of the battery the nominal capacity will be
reduced over the years. The speed of deterioration is
dependant of the operation- and ambient conditions.
Even a unused battery will deteriorate.
An average working time of 9 - 10 years can be
expected under normal conditions. (25 °C ambient,
duration test every 6 month, no deep discharge periods)
2. Calculation of
emergency
duration
3.2 Capacity of battery by LED-indication
The inverter of the eLLK 92 series needs an operating
current of approx. 3.4 A (1.5 h setting) or 1.7 A (3 h
setting).
A calculation of 1.5 h x 3.4 A results 5.1 Ah. This is the
reason, why a new nominal 7.0 Ah battery will last more
then 1.5 h emergency operation.
Based on the 1.4 Ah/per LED this results a theoretical
time of 24 minutes/LED.
When 3 LEDs are on, 1 h emergency duration can be
expected.