CEAG History of self-contained emergency lighting. Month Day, Year CEAG History of self-contained emergency lighting. ¾ In 1971: CEAG produced the worlds first explosion protected emergency light fitting based on eLLK 70 design. ¾ eLLK 70 series is still in use today. ¾ That represents a 34 years in operation . ¾ No spare parts or batteries available Replaced by eLLK 92 series, see page 7 2 1. Maintenance Practice 1.1 Production period: 1982 - 1993 eLLK 81 020/20 N and eLLK 81 040/40 N Emergency light fittings types: eLLK 81020/20 N (2 x 20 W T12-Fa6) eLLK 81040/40 N (2 x 40 W T12-Fa6) No spare parts or batteries available Replaced by eLLK 92 series, see page 7 1. Maintenance Practice 1.1 Production period: 1982 - 1993 eLLK 81 020/20 N and eLLK 81 040/40 N Replacement type: CEAG eLLK 92018/18 NIB Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal) CEAG eLLK 92036/36 NIB. Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal) 1.2 Production period: 1993 - 1995 eLLK 92018/18 N and eLLK 92036/36 N Red lampholder = emergency lamp Red LED at the lampholder Emergency light fittings types: eLLK 92018/18 N (2 x 18 W T8-Fa6/G13) eLLK 92036/36 N (2 x 36 W T8-Fa6/G13) For direct replacement and batteries available see page 7. 1. Maintenance Practice 1.2 Production period: 1993 - 1995 eLLK 92018/18 N and eLLK 92036/36 N Installed Battery: 6 V 7 Ah emergency duration time: 1.5 h or 3.0 h Charging duration: 24 h/ >90 % of rated capacity Fault indicators: FIRST CHECK LAMPS ARE WORKING No red LED Failure in the change inverter/ charging circuit ballast unit No emergency Battery or inverter change battery/ light fault change inverter No mains light/ emerg. light o.k. Ballast faulty change ballast 1. Maintenance Practice 1.2 Production period: 1993 - 1995 eLLK 92 018/18 N and eLLK 92 036/36 N Replacement type: CEAG eLLK 92018/18 NIB Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal) CEAG eLLK 92036/36 NIB. Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal) Fitting replacement type: Battery replacement: type 2710-2 (Ni) Order no. 2 2710 902 000 1. Maintenance Practice Production period: 1995 - 2002 1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni 1 red LED 5 green LEDs grey battery box Emergency light fittings types: eLLK 92018/18 Ni (2 x 18 W T8-Fa6/G13) eLLK 92036/36 Ni (2 x 36 W T8-Fa6/G13) For direct replacement and spare batteries available see page 12. 1. Maintenance Practice Production period: 1995 - 2002 1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni Installed Battery: 6 V 7 Ah emergency duration time: 1.5 h or 3.0 h Circuit diagram see page 10/11 Charging duration: 14 h/>90 % capacity Fault indicators: FIRST CHECK LAMPS ARE WORKING Red LED flashing Last duration test > 6 month or Emerg. duration < 30 min. No mains light/ Ballast fault emerg. light o.k. no green LED no charging start duration test for > 30 min. fully charge (cycle!) start test again change ballast faulty battery/inverter change battery/inverter 1. Maintenance Practice Production period: 1995 - 2002 1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni Wiring diagram eLLK 92018/18 Ni 1. Maintenance Practice Production period: 1995 - 2002 1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni Wiring diagram eLLK 92036/36 Ni 1. Maintenance Production period: 1995 - 2002 1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni Replacement type: CEAG eLLK 92018/18 NIB Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal) CEAG eLLK 92036/36 NIB. Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic) Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal) Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal) Fitting replacement type: Battery replacement: type 2710-2 (Ni) Order no. 2 2710 902 000 Practice 1. Maintenance Practice Production period: 2002 - now 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB 1 red LED 5 green LEDs black battery box Emergency light fittings types: eLLK 92018/18 NIB (2 x 18 W T8-Fa6/G13) eLLK 92036/36 NIB (2 x 36 W T8-Fa6/G13) Spare parts and batteries available See page 14 1. Maintenance Practice Production period: 2002 - now 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB Replacement fitting type: eLLK 92018/18 NIB CEAG. Bi-pin lamp Order No.: 1 2260 879 101 (2 x M25 plastic) Order No.: 1 2260 879 103 (4 x M25 plastic) Order No.: 1 2260 879 111 (4 x M20 metal) single pin lamp 1 2210 879 111 eLLK 92036/36 NIB CEAG. Bi-pin lamp single pin lamp Order No.: 1 2261 879 101 (2 x M25 plastic) Order No.: 1 2261 879 103 (4 x M25 plastic) Order No.: 1 2261 879 111 (4 x M20 metal) 1 2211 879 111 Replacement battery type: type 2710-3 (NIB), Order no. 2 2710 904 000 1. Maintenance Practice Production period: 2002 - Current 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB Installed Battery: 6 V 7 Ah optional emergency duration time: 1.5 h or 3.0 h Charging duration: 14 h/>90 % capacity Automatic function test every week (< 5 minutes) Automatic duration test every 3 months Automatic battery monitoring 5 green LEDs for capacity monitoring Circuit Diagram see page 18/19 1. Maintenance Practice Production period: 2002 - Current 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB L L L1 L1 L2 L2 L3 L3 N N PE PE 0 L1 N LL LL Wiring diagram eLLK 92036/36 NIB LL FS LL1 LL2 EVG..236 L N +B LL -B FS B1 Not B2 LL1 B5 B4 B6 B3 + VE97236 1 2 3 Ersatzbruecke fuer Fernschalter muss beim Anschluss eines Schalters entfernt werden Netzlampe/Mains lamp Remote Switch, to be removed for connection of inhibit switch Notlampe/Emergency lamp eBK 02 1. Maintenance Practice Production period: 2002 - Current 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB 0 + Wiring diagram eLLK 92018/18 NIB 1 2 3 1. Maintenance Practice Production period: 2002 - now 1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB Fault indicators: FIRST ACTION CHECK LAMPS ARE WORKING LED indication possible reason action Red LED flashing Last duration test start duration test for > 3 month or > 30 min. Emerg. duration fully charge (cycle!) < 30 min. start test again Red LED cont. on Battery failure replace battery No mains light/ Ballast fault change ballast emerg. light o.k. No green LED not charging faulty battery/inverter change battery/inverter less than 2 LEDs ageing of the cycle battery, start full on after fully battery; duration test, if not charged capacity loss more LED on, change 1.5 Visual capacity of the battery. Automatic display of the remaining capacity The eLLK 92 NIB series will continuously show the actual capacity of the installed battery: With steps of 20 % displayed by 5 green LEDs, the residual capacity can be monitored at the battery enclosure. 100 % rated capacity 80 % rated capacity 60 % rated capacity 40 % rated capacity 20 % rated capacity a flashing LED indicates charging to the next step Automatic display of fault conditions The red LED shows a fault indication: • continuously on. Red LED continuously on: Battery fault Battery must be replaced Red LED flashing: Function test/duration test not passed Last duration test more than 3 month passed (Inhibit switch off?) Charge battery at least 24h Repeat function test manually (cut off line) If red LED is still flashing Battery capacity too low - Change battery - 2. Installation 2.1 Setting of emergency duration To select the rated emergency duration (1.5 or 3 h) the wire at terminal 1 is used. 2.1.1 1.5 h rated emergency duration both wires have to be connected on terminal 1 2.1.2 3.0 h rated emergency duration the wires have to be disconnected: one to terminal 1 one to terminal 0 0 + 1 2 3 Ersatzbruecke fuer Fernschalter muss beim Anschluss eines Schalters entfernt werden Remote Switch, to be removed for connection of inhibit switch eBK 02 2. Installation 2.2 Connecting inhibit switch 0 + 1 Connect up to 10 eLLK92… NIB to one central inhibit switch (Ex-e circuit). This switch will block the emergency operation during a power failure. Do not use it for maintenance work! Note: An open inhibit switch does not allow an automatic function- or duration test. This will cause a flashing red LED at the battery box. 2 3 Ersatzbruecke fuer Fernschalter muss beim Anschluss eines Schalters entfernt werden Remote Switch, to be removed for connection of inhibit switch ELLK92NIB ELLK92NIB ELLK92NIB ELLK92NIB 3. Calculation of emergency duration 3.1 Display of the NIB-Battery The 5 green LEDs shows the actual charging state of the NiCd-battery. A new battery with nominal 7 Ah capacity will be the equivalent to 5 green LEDs. Each LED indicates approx. 20 % of the nominal capacity (= 1.4 Ah) By ageing of the battery the nominal capacity will be reduced over the years. The speed of deterioration is dependant of the operation- and ambient conditions. Even a unused battery will deteriorate. An average working time of 9 - 10 years can be expected under normal conditions. (25 °C ambient, duration test every 6 month, no deep discharge periods) 2. Calculation of emergency duration 3.2 Capacity of battery by LED-indication The inverter of the eLLK 92 series needs an operating current of approx. 3.4 A (1.5 h setting) or 1.7 A (3 h setting). A calculation of 1.5 h x 3.4 A results 5.1 Ah. This is the reason, why a new nominal 7.0 Ah battery will last more then 1.5 h emergency operation. Based on the 1.4 Ah/per LED this results a theoretical time of 24 minutes/LED. When 3 LEDs are on, 1 h emergency duration can be expected.