INSTALLATION INSTRUCTIONS FOR EMERGENCY EXIT SIGN IMPORTANT: When relamping, only use lamps (or LEDs) specified in the exit sign. Using other lamp types may result in transformer damage or unsafe conditions. Battery in this unit may not be fully charged. After electricity is hooked up to unit, let the battery charge up for at least 24 hours. The normal operation of this unit should then take effect. Important safeguards When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. Do not use outdoors. 2. Do not mount near gas or electric heaters. 3. Use caution when handing batteries. Avoid possible shorting. 4. Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel. 5. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 6. Do not use this equipment for other than its intended use. 7. Before wiring to power supply, turn off electricity at fuse or circuit breaker. 8. Consult local building code for approved wiring and installation. 9. Installation and servicing should be performed by qualified personnel. SAVE THESE INSTRUCTIONS INSTALLATION: CEILING & END MOUNTING (FIG 1) & FIG2) - (FIG. 1) 1. Connect input as shown in wiring diagram below and fasten canopy to J-box bracket. 2. Snap housing to canopy. 3. Secure faceplate to housing and remove the proper arrow as required. Wiring diagram - (FIG. 2) WARNING: Unused wires must be capped using enclosed wire nuts. SELF-DIAGNOSTICS TESTING: 1) NORMAL OPERATION When unit is functioning properly with A.C. power supplied, the status indicator will be green and the exit lamp will be on. 2) TESTING The exit performs two types of tests, Contingency and Non-Contingency. The contingency testing includes “Battery Disconnected Mode” and “LED Failure Mode”. When the Battery is disconnected, the indicator would indicate as Red (Steady). When a LED fails, the indicator would indicate as Red (Blinking - three times). The Non-Contingency test is for testing the Battery for its “discharging” and “recharging” capacity. A 15-minute battery discharge test is performed every 30 days to check for the normal operation of the battery and the unit. Also a full 90-minute discharge test is performed once a year to confirm the same. When the battery is in discharging mode, the LED indicator would be flashing Green (Three/ Four Pulses). Upon completion of the test and after 24 hours battery charging (Indicator on Red and Green flashing), the status indicator will return to either Green (Steady) indicating a properly functioning unit or Red (Double Pulse) to show a battery failure. The following table shows the status indication. FUNCTION LED INDICATION Exit is in Emergency Mode Off Exit is in Normal Mode Green (Steady) Battery Disconnected Red (Steady) LED Failure Red (Flashing 3 times) Battery Charging Red and Green (Flashing Alternately) * Battery Failure Red (Flashing 2 times) 30 Second Battery Discharging Mode Green (Flashing 1 time) ** Green (Flashing 2 times) *** Green (Flashing 3 times) 15 Minute Battery Discharging Mode 90 Minute Battery Discharging Mode * = Happens only after battery discharges once in every 30 days or 1 year. ** = Occurs once in every 30 days. *** = Occurs once in a Year. MANUAL TESTING: TESTING Battery and ‘LED strip’ test may be manually initiated by pressing the test switch. Once the test switch is pressed, the unit would be reset and the date of battery self-testing would start counting again. ACTION REACTION AND LED INDICATION Press test button once (within 2 seconds) 30-second test; Green light - Single blinking Press test button 2 times (within 2 seconds) 15-minute test; Green light - Double blinking Press test button 3 times (within 2 seconds) 90-minute test; Green light - Triple blinking OPERATION: OPERATION: During an electrical power failure, the LED strip will automatically come ON for a minimum of 90 minutes. To test this unit, the battery needs to be charged initially for 2 hours before depressing the test switch (to do manual test). On pressing the test switch, the LED strip will illuminate. The LEDs will turn OFF after 30 sec/15 min/90 min depending on the number of times the switch has been pressed.