QUICKTRONIC® Emergency Ballasts 300, 550, 650, and 1400

advertisement
www.sylvania.com
QUICKTRONIC® Emergency Ballasts
300, 550, 650, and 1400 Lumens
QuickSwap™ Wiring Harness
1 or 2 Lamp Emergency Operation
Low Profile Series
Lamp/Emergency Ballast Guide
T5
FP14, FP21, FPC22, FP24/HO, FP28,
FP35, FP39/HO, FPC40, FP54/HO
T8
FO17, FBO16, FBO24, FO25, FO28/SS,
FBO29/SS, FO30/SS, FBO30/SS, FBO31,
FO32, FBO32, FO40, FO96, FO96/SS,
FO96HO
T9 Circline
FC6T9, FC8T9, FC12T9, FC16T9
T12
F24, F25, F30, F34, FB34, F40, FB40,
F48, F64, F72, F84, F96
T5 Long Compact (4-pin)
CF18DF, CF24DF, CF36DF, FT18DL, FT24DL,
FT36DL, FT40DL, FT50DL, FT55DL
T4 Compact (4-pin)
CF9S/E, CF13DD/E, CF13DT/E,
CF18DD/E, CF18DT/E, CF21/2D,
CF26DD/E, CF26DT/E, CF28/2D,
CF32DT/E, CF38/2D, CF42DT/E
SYLVANIA QUICKTRONIC EMERGENCY
BALLASTS enable an existing fluorescent
fixture to operate as both an emergency
egress lighting fixture as well as a normal
lighting fixture. During a power loss, the
emergency ballast automatically switches
the fixture to emergency mode and
continues to operate one or two lamp(s)
at reduced lumen output for at least
90 minutes.
The innovative QuickSwap™ wiring
harness allows for one-time wiring,
greatly simplifying subsequent field
maintenance and lumen upgrades.
These Emergency Ballasts can be installed
as part of a fixture by an OEM or added to
an existing fixture during a retrofit.
This series has dual input voltage (120 or
277V) and it supports many lamp types
and wattages.
Each SYLVANIA QUICKTRONIC Emergency
Ballast comes with the SYLVANIA Total
System Solution that includes primary
lamp ballast and emergency ballast
compatibility.
The optional End-of-Life Adapter (QTEB
EOLA TSI) is for T5 and T4 ballasts that
incorporate lamp end-of-life sensing.
A single pole test switch/charge indicator
accessory kit is supplied with each unit.
Key System Features
•
•
•
•
•
•
•
•
•
•
•
90 minute emergency operation
QuickSwap™ wiring harness
Integrated test switch/charge indicator
Automatic battery recharge
Dual Input Voltage (120/277V)
Small size and lightweight
Sealed, maintenance-free, hightemperature nickel cadmium battery
UL Listed as “Emergency Lighting
and Power Equipment”
Meets or exceeds all National
Electric Code (NEC) requirements
Meets or exceeds NFPA 101/Life Safety
Code (LSC) requirements for Emergency
Lighting
3 or 5 year warranty
Application Information
SYLVANIA QUICKTRONIC
EMERGENCY BALLASTS
are ideally suited for:
• Commercial
• Retail
• Offices
• Wherever emergency illumination
is required
ECS100 – 8/2009
QTEB
1L300-LP
System Information
• Highly efficient DC/AC power conversion
techniques achieve the optimum
balance of maximum light output,
battery life, and reliability.
• The unit’s low profile allows it to be
discreetly mounted within the existing
fixture’s wireway, reducing its visibility
and protecting it from being vandalized.
If desired, two additional 1⁄2" holes in the
fixture channel can permit mounting of
test switch/charge indicator behind
fixture lens. The mounting centers are
the same as those of a standard ballast.
Low Profile
1.18
2.19
Typical
2.40
QTEB
2L650-LP
QTEB
2L1400-LP
Lamp Type
Wattage
24"-48" T5
14-28
T5 HO
24-54
1
1
U-Lamp T8
16-31
1
1
1, 2
1, 2
24"-48" T8
17-32
1
1
1, 2
1, 2
60"-96" T8
40-59
1
1
96" T8 HO
86
1
1
Circline T9
20-40
1
1
Number of Lamps Supported
1
1
U-Lamp T12
34-40
1
1
1, 2
1, 2
24"-48" T12
20-40
1
1
1, 2
1, 2
60"-96" T12
50-75
1
1
24"-48" T12 HO
35-60
1
1
60"-96" T12
70-110
1
1
24"-48" T12 HO
74-115
1
1
60"-96" T12
135-215
1
T4 Compact (4-pin)
T4 Compact (4-pin)
1.50
QTEB
1L550-LP
9-32
42
T5 Long Compact (4-pin)
18-40
T5 Long Compact (4-pin)
50-55
1
1, 2 (13-32W)
1
1
1
1
1
1
1
QUICKTRONIC® EMERGENCY BALLASTS
Application Example
Fluorescent fixture:
Lensed troffer
1 FC average
Lamp type:
FO32T8
0.1 FC minimum
Ceiling Height:
9'
Corridor Size:
8' x 100'
Egress Path Width:
3'
CORRIDOR
43'
Emergency Ballast:
QTEB2L650-LP-120/277
Emergency Ballast Spacing:
43'
Recommended Center-to-Center Spacing Chart
One Footcandle Average Spacing Guidelines – Corridor
T8 lensed troffer
T8 direct/indirect
T8 parabolic
QTEB1L300-LP
24'
18'
21'
QTEB1L550-LP
35'
28'
32'
QTEB2L650-LP
43'
34'
40'
QTEB2L1400-LP
57'
59'
53'
Note: Meets Life Safety Code standard minimum illuminance of 0.1FC and average illuminance of
1.0 FC. Assumes 3 T8 lamps in each fixture, 8'W x 100'L corridor, ceiling height of 9' and
reflectances of 80/50/20.
1 FC average
Fluorescent fixture:
2 x 4 T8 parabolic
0.1 FC minimum
Lamp type:
FO32T8
Ceiling Height:
9'
Office Size:
100' x 100'
Egress Path Width:
3'
Emergency Ballast:
QTEB2L1400-LP-120/277
OPEN OFFICE
Emergency Ballast Spacing: 45'
Recommended Center-to-Center Spacing Chart
45'
One Footcandle Average Spacing Guidelines – Open Office
T8 lensed troffer
T8 direct/indirect
T8 parabolic
QTEB1L300-LP
16'
13'
17'
QTEB1L550-LP
29'
21'
27'
QTEB2L650-LP
35'
26'
34'
QTEB2L1400-LP
47'
47'
45'
Note: Meets Life Safety Code standard minimum illuminance of 0.1FC and average illuminance of
1.0 FC. Assumes 3 T8 lamps in each fixture, 100'W x 100'L open office, ceiling height of 9' and
reflectances of 80/50/20.
Accessories
QuickSwap™ connector and wiring harness:
Black, Orange, White = 21"
Red/White = 33"
Blue, Yellow, Yellow/Black, Blue/White = 45"
Red = 57"
Test switch/charge indicator harness:
Black/White = 36"
End-of-Life Adapter (optional):
Black/White = 5.5"
Blue, Yellow, Grey, Violet = 5.25"
QUICKTRONIC® EMERGENCY BALLASTS
Example Wiring Diagrams
THREE LAMP INSTANT START BALLAST
TWO LAMP OSRAM SYLVANIA PROGRAM START / DIMMING BALLAST WITH T5 LAMPS
BLACK
CONNECT 120 OR 277 VOLT AC
SWITCHED OR UNSWITCHED
NOTE: VERIFY VOLTAGE RATING ON AC BALLASTS
WHITE/RED
WHITE
RED
BLUE
BLACK
RED
BLU/WHT
2 LAMP
YELLOW
PROGRAM START/DIMMING
BALLAST
YELLOW
YEL/BLK
BLUE
YELLOW
BLUE
RED
B
NORMAL / EMERGENCY LAMP
NORMAL / EMERGENCY LAMP
RED
RED
UNSWITCHED BATTERY
PACK INPUT ONLY
USE PORPER VOLTAGE TAP
AND CAP UNUSED LEAD
NEUTRAL
WHITE
120 VAC
BLACK
277 VAC
ORANGE
EMERGENCY BALLAST
A
CONNECT TO POINT “A” FOR ONE LAMP OR
“B” FOR TWO LAMP EMERGENCY OPERATION.
TEST SWITCH/
PILOT LIGHT
LAMP SELECTOR (QTEB2L1400 ONLY)
TWO LAMP OSRAM SYLVANIA PROGRAM START / DIMMING BALLAST WITH T8 LAMPS
Specifications subject to change without notice.
Emergency Ballast
SPECIFICATION DATA
Catalog #
Date
Type
Project
Prepared by
Comments
Low Profile Series
QUICKTRONIC® Emergency Ballasts
Input
Voltage
(VAC)
Max.
Input
Current
(Amps)
Average
Initial Lumens
During
Emergency
Operation (lm)
No. of
Lamps
Warranty
Input
Power
(Watts)
45102
QTEB1L300-LP-120/277
120 / 277
0.27 / 0.29
300
1
3 year
2.5
45108
QTEB1L550-LP-120/277
120 / 277
0.27 / 0.29
550
1
3 year
3.2
45104
QTEB2L650-LP-120/277
120 / 277
0.29 / 0.29
550 - 650
1 or 2
5 year
3.0
0.27 / 0.29
1100 - 1400
1 or 2
5 year
2.5
Description
45100
QTEB2L1400-LP-120/277
120 / 277
45116
QTEB-EOLA-TSI
End Of Life Adapter - Test switch interface - Suitable for T5 and T4 Systems with EOL circuits
COMPETITIVE CROSS REFERENCE
SYLVANIA
ALP
ATLITE
BIG BEAM
BODINE
CARPENTER
CHLORIDE
DAYBRITE
DUALITE
EMERGILITE
ENCORE
EXITRONIX
HIGHLITES
HUBBELL
IOTA
LIGHTALARMS
LIGHTGUARD
LITHONIA
MULE
PATHWAY
PRESCOLITE
SIDELITE
SILTRON
SURELITES
QTEB1L300-LP
EFPSL32
QTEB1L550-LP
FEB-1
FP700
Specifications
QTEB2L650-LP
EFP-48
FP700-8
EFB40
EFB80
B100
B90
B60/B70A
FB-1
FB-2/FB-3A
C450
CFP60
CFP45
DEB7
UFO-3A
UFO-4
UFO-5/UFO-2X
FPSI-32
FPSU-28
EP500
EP700-8
XEB-55
XEB-7
200A
201
202
E-100
E-48
E-48A/E-60
I-32
I-40
I-48
AM32
AM7
L450
L700
PS300QD
PSQ500QD
PS600QD
MF40-100
MF40-60/70
F40
F40S
F40P
EFP-1-500
EFP1-500
EFP3/EFP4
S40F
S66F
UP40
UP80
FBP-1-40X
FBP-2-40U
FBP-2-40M
**Cross Reference is for reference only. Please check datasheets before installation.**
QTEB2L1400-LP
EFB40-2
B50
C1400
UFO-6
FPSI/U
EP1350
XEB-13/XEB-14
204
E-96
I-320/I-80
AM12
L1400
PS1400QD
MF40-50
2F40P
EFP-5
UP80-2
FBP-2-40H
Circuit Type: 1 or 2 Lamp Emergency
Operation, see chart
AC Input:
Input Voltage: 120V or 277V
Max. Input Current: see chart
Fed from the same branch circuit
as primary ballast
Battery:
Optimum Temp:1 32-100°F
Shelf Life:2 3 years
Expected Battery Life:2 7-9 years
Standards:
UL listed
For sealed and gasketed fixtures
UL924, NFPA 101, NEC and OSHA
illumination standards
Housing:
Engineering-grade plastic housing
UL94V-O flame rating
1
2
Dimensions
Size
LxWxH
Mounting
Length (ML)
QTEB1L300-LP-120/277
9.5" x 2.19" x 1.19"
9"
12
1.4
QTEB1L550-LP-120/277
9.5" x 2.19" x 1.19"
9"
12
1.4
QTEB2L650-LP-120/277
9.4" x 2.19" x 1.19"
9"
12
1.4
QTEB2L1400-LP-120/277
13.31" x 2.19" x 1.19"
12.9"
8
2
Model
Qty
Weight
(per case) each (lbs)
Optimum ambient temperature range
where unit will provide capacity for 90
minutes. Higher and lower temperatures
affect life and capacity.
At 77°F. Emergency Ballast must be fully
charged within 3 years of manufacture
date in order to ensure battery functionality.
System Life / Warranty
Height
(H)
Mounting
Length
(ML) Length
(L)
OSRAM SYLVANIA Low Profile
Emergency Ballasts are covered
by a full three or five year customer
satisfaction warranty.
Width
(W)
Item Number
45102 QTEB 1L 300 - LP - 120/277
Input Voltage
QUICKTRONIC® Emergency Ballast
Form Factor
Number of Lamps Supported
(2L = 1 or 2 lamps)
Average Initial Lumens
(Emergency Operation)
SYLVANIA ,The System Solution and See the World in a New Light are registered trademarks of OSRAM SYLVANIA INC. QuickSwap is a trademark of OSRAM SYLVANIA INC. QUICKTRONIC
is a registered trademark of OSRAM GmbH. Information subject to change without notice.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
©2009 OSRAM SYLVANIA
Item
Number
Download