FD Series
Inverter Packaged Air Conditioners
Proudly supporting
2
FD Series
Inverter Packaged Air Conditioners
change
setting by
button taps
only
Run / Stop
High power operation
Energy-saving operation
Maximum capacity operation (Max 15 minutes)
• Increased compressor speed
• Increased air flow
• Changes set temperature at 28ºC in
cooling mode and 22ºC in heating mode, 25ºC in auto mode.
• Operation correction by outdoor temperature
Main functions
Energy management
Peak cut timer • Automatic temperature set back • Weekly timer • Set ON/OFF timer by hour
• Set ON/OFF timer by clock • Fan only operation • Sleep timer
Comfort
Individual flap control • High power operation • External ventilation ON/OFF
• Warm up operation • Automatic fan speed • Temperature increment setting by 0.5ºC
Convenience
LCD contrast setting • Back light setting • Filter clean sign • Control sound • Outdoor silent
mode • Summer time setting • Home leave mode • Indoor & outdoor temperature display
• Heating standby display • Defrosting operation display • Auto cooling/heating display
• ºC/ºF display • Administrator settings • Room name setting
Service
Error code display • Operation data display • Next service data display
• Contact company display • USB connection (mini-B)
Operation mode
Cooling
Dry
FD series Inverter Packaged Air Conditioners 2015
Auto
Fan
Heating
Advanced touch screen panel with full dot Liquid Crystal Display
PRODUCTS
Basic operation
All settings are changed by tapping the touch screen panel
Operation mode setting screen
Temperature setting screen
The operation mode can
be selected by simply
tapping this button.
You can select
the desired
temperature by
tapping the ▲▼
button.
NEW
IntesisHome
Your
our home in the cloud
Intesis Wifi Adaptors
RAC Model: IS-IR-WIFI-1
PAC Model: MH-RC-WIFI-1
3
FD Series
4
Hyperinverter
Our advanced technology has allowed us to achieve high efficiency, powerful heating and
long distance refrigerant piping specifications. This feature permits installation of the units
when a heating in operation under temperature conditions down to -20˚C is required.
Design flexibility has been improved by an extension
of the refrigerant piping length to 100m
(12.5 & 14.0kW).
Micro
SRC50ZMXA-S
SRC60ZMXA-S
FDCA71VNX
FDC90VNP
FDCA125VNX
FDCA140VSX
FDCA100VN
FDCA160VSA
FDCA200VSA
Blue Fin 7.1-20.0kW
Base heater kit (option)
Due to application of blue coated fins (KS101) for the heat
exchanger of the new outdoor unit, corrosion resistance
has been improved compared to previous models.
This kit is recommended for use in areas where the
temperature drops below 0˚C.
Blue
Fin
Blue
Fin
CW-H-E applied for
FDCA100VN
FDCA125~140VNX
Micro Inverter
Installation workability
ø133mm
diameter of shell& 14.0kW
Long pipingOutside12.5
ø185mm
Former
compressor
Height at 342mm
Height at 440 mm
Enhanced installation workability
Compact design of outdoor
thanks to the extended pipe
units
length – one of the longest levels
* Vector control:
FDCA100VN
To convert the current
in the industry. Units are prewave to a smooth
Reduction in height by 22.3%
sinusoidal
waveform. 10.0kW condenser
Our
single
fan micro
charged with refrigerant. Reduction in volume by
44.1%
is one of the most compact in the
industry only 845(h)x970(w)x370(d)
New model
DC rotary compressor
Height difference
Height difference
(Outdoor higher
(Outdoor
than Indoor)
higher than Indoor)
Piping
length
Piping
length
Refrigerant
precharged piping
MicroMicro
Inverter
Inverter
length extending to
Height difference
Height difference30m
(Outdoor higher
(Outdoor
than Indoor)
higher than Indoor)
Piping
length
Piping
Height
Piping
length
length
kW difference
Height
difference
5~6
30m5~6 20m30m
20m
7.1
50m 7.1 30m50m
30m
12.5~14
100m
100m
12.5~1430m
30m
kW
FD series Inverter Packaged Air Conditioners 2015
Piping
length
Precharged refrigerant piping
length extends up to 30m. (5.0 &
6.0kW up to 15m)
This eliminates the need to
Former model
model
Piping
Height
Piping
Height
add refrigerantCurrent
on site,
which
length
length difference
kW
kW difference
20msets it free from the trouble of
30m 9 20m30m
9
excessive or insufficient charging
30m
50m 10 30m50m
10
of refrigerant, and allows smooth
30m
70m*
70m*
16,20
16,20 30m
installation.
* Refer technical
* Refer
manual
technical manual
Size reduction and high efficiency
performance of the DC twin rotary
compressor
* Vector control:
To convert the current
wave to a smooth
sinusoidal waveform.
Protection
Improved operation of the electronic expansion valve allows
for more reliable oil return and this assists to protect the
compressor.
Height at 342mm
Height at 440 mm
Reduction in height by 22.3%
Reduction in volume by 44.1%
Re-designing the fins to a straight shape has reduced the
pressure loss of the air flow in the heat exchanger. A new
surface treatment on the fins has enhanced the frost resistance
capacity. A high speed fan motor has increased the airflow
which allows cooling capacity to be maintained even at high
outdoor air temperatures.
FEATURES
The DC twin rotary compressor can operate at
speeds as high as 120 rps. Vector control provides
perfect compressor control. Starting current
has reduced significantly and vibration has been
minimized.
Improved efficiency of the heat exchanger
Outside diameter of shell
ø185mm
ø133mm
Former
compressor
New model
DC rotary compressor
Former model
Current model
High efficiency
Reduction of air flow pressure loss
common
XR5 of the
Heat transfer efficiency has improved by using high efficiency piping and by the redesign
XR5
from 2 to 1 piece.
XR1~5 : approx. DC12v
Convenience
XR1
XR2
XR4
XR3
XR4
A dry contact is fitted to each indoor unit which is used
when a signal output is required.
XR2
CnT
CnT
XR1
CnT terminal
output3 (comp on)
output4 (alarm)
in put
heat
exchanger
XR1
XR3 XR2
XR3
XR5 XR4
XR1~5 : approx. DC12v
XR5
commoncommon
XR1
output1 (run)
output1
XR2 (run)
output2 (heat)
XR3 (heat)
output3 (comp on)
output2
XR4 output4 (alarm)
output3
(comp
on)
in put
XR5
output4 (alarm)
in put
source
XR3
XR4
Power
source
Power
XR3
XR4
Power
source
Increase of heat transfer efficiency
CnT
Pressure caused by air flow in the indoor unit is reduced by making the air outlet larger. The reduction of pressure
XR1 output1 (run)
XR1
reduces the load on the fan motor so increasing efficiency.
XR2 output2 (heat)
XR2
XR5
XR1~5 : approx. DC12v
Monitoring Function
Condensers are fitted with RS232C so you can connect
directly to your PC for monitoring. MHI’s service software
(Mente PC) makes service simpler. PAC converter
necessary required to connect to PC directly
Remote control RC-E5
The new remote control for all indoor units. Non-polar 2
core wiring is used. Installation is easier.
Previous
3-core
Current
2-core
Previous
3-core
Current
2-core
All models employ R410A with RoHS* directive
Previous
Employment of lead free solder
3-core
Current
2-core
Adapt to RoHS
Pressure caused by air flow in the indoor unit is reduced
by making the air outlet larger. The reduction of pressure
reduces the load on the fan motor so efficiency increases.
*”RoHS” is the abbreviation of the European standard,
which means Restriction of Hazardous Substances.
Employment of R410A refrigerant
All models of the FD inverter series use refrigerant
R410A characterized by an ozone depletion
coefficient of 0.
5
6
FDT-FDTC
Ceiling Cassette - 4way - Indoor units
Individual flap control system
Individual flap control is possible even after
installation. This means that the installation
area has become wider than before.
The outlet design has been perfected to
allow flow that can reach a long distance
from the indoor unit.
Previous
Previous
Upper
position
Flap control system
The design of the heat exchanger has
changed from 2 parts to a single piece.
The height of the indoor unit has been
reduced significantly.
*RCH-E3 is not applicable to the Individual flap control
system and the Flap control system.
Previous
Upper
position
Current
Current
Movable
range
Movable Lower
range
position
Upper
position
Lower
position
For person who is far
Movable
range
For person
whoindoor
is far unit
from the
from the indoor unit
Lower
position
The thinnest design
DC fan motors are used to increase
efficiency. Weight has been reduced
and as a result the unit has become
one of the most compact in the
industry.
Current
FDT125~140
FDT125~140
18%
18%
reduction!!
For person who is far
from the indoor unit
reduction!!
365mm
365mm
FDT125~140
18%
reduction!!
298298
mm
mm
For both persons who are
For both persons who are
feeling
or cold
feeling
hot orhot
cold
365mm
FDT71
FDT71
Shape
of heat
heatexchanger
exchanger
Shape of
For both persons who are
9%9%
298
reduction!!
reduction!!
feeling hot or cold
mm
270mm
270mm
Previous
Previous
Current
Current
FDT71
246
9% 246
mmmm
reduction!!
Shape of heat exchanger
Can Can
cool cool
both both
the kitchen
the kitchen
and the
andguests
the guests
270mm
Previous
Current
FD series Inverter Packaged Air Conditioners 2015
246
mm
Can cool both the kitchen
and the guests
FDUA Indoor Unit
Duct Connected - High Static Pressure
PRODUCTS
External static pressure (E.S.P.) control
Selecting the external static pressure setting the optimum air flow volume can be achieved.
The indoor unit will recognize the external static pressure setting and keep rated air volume.
New
FDUA
Duct
Duct
Longer Duct
Ceiling
Keep the same
air flow volume
Setting No.
1
E.S.P. (Pa)
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 200
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19
E.S.P. button
External static pressure
can be set by E.S.P.
button.
Improved servicing
Improved servicing
Fan unit (impeller and motor) can be pulled out from the right side of the unit. Maintenance access is available
from both the right side and below the unit.
Pipe
Unit
Fan unit
Maintenance
hole
Service
space
7
FDUA Indoor Unit
Duct Connected - High Static Pressure
MODELS: FDUA71VF, FDUA100VF, FDUA125VF, FDUA140VF
Remote control (Options)
Wired
Wireless
DRED enabled model
RC-E5
RCH-E3
RCN-KIT3-E
200 Duct dimension
Dimension
H 398
(1) Indoor units
Model FDUA71VF
65
Unit:mm
740 Duct dimension
Symbol
A
Gas piping
B Liquid piping
C1 Drain piping
Drain piping
C2
Gravity drainage
D Hole for wiring
E Suspension bolts
F
Inspection hole
185
41
RC-EX1A
39
FDUA100/125/140/160VF
Return air duct
H 280
Drain hose piece
Accessory
Content
15.88 5 8"
Flare
9.52 3 8"
Flare
VP25 I.D.25,O.D.32
VP20 I.D.20,O.D.26
M10
450X450
Installed on site
FD series Inverter Packaged Air Conditioners 2015
55
880 Duct dimension
55
100
1300
C2
635
510
471
413
175
105
Max. drain lift
76
D
600 or less
295 325
15
Under 60
less than
600mm
30
280
250
472
Suspension bolts pitch
135
Air supply duct
43
Flexible hose
E
620
Note 1 The model name label
is attached on the lid
of the control box.
B
A
58
67
Duct dimension
Drain can be discharged upwards by 600mm
from the ceiling surface. It allows a piping layout
with a high degree of freedom depending on the
installation location.
C1
69
600
Inspection
hole
Control box
600mm Drain Pump
From bottom of unit
or more
Case 2
18
284
82
28
FDUA71VF
18
or more
Hanger plate for
suspension bolt
986 Suspension bolts pitch
950
170
8
467
30
FDUA
FDUA71AVNXVF
Set
FDUA100AVNVF
FDUA100AVNXVF
Indoor
FDUA71VF
FDUA100VF
FDUA100VF
FDUA125VF
FDUA140VF
FDCA71VNX
FDCA100VN
FDCA100VNX
FDCA125VNX
FDCA140VNX
7.1 (3.2-8.0)
10.0 (4.0-11.2)
10.0 (4.0-11.2)
12.5 (5.0-14.0)
14.0 (5.0-14.5)
8.0 (3.6-9.0)
11.2 (4.0-12.5)
11.2 (4.0-12.5)
14.0 (4.0-17.0)
16.0 (4.0-18.0)
2.22
3.05
2.85
3.83
4.44
Outdoor Unit
1 Phase 220-240V 50Hz
Cooling T1
kW
Heating H1
Cooling T1
Input
kW
Heating H1
2.22
2.87
2.74
3.68
4.41
3.20
3.28
3.51
3.26
3.15
EER
Cooling T1
COP
Heating H1
3.60
3.90
4.09
3.80
3.63
Indoor
P-Hi:38 Hi:33
Me:29 Lo:25
P-Hi:43 Hi:42
Me:40 Lo:37
P-Hi:43 Hi:42
Me:40 Lo:37
P-Hi:45 Hi:43
Me:41 Lo:37
P-Hi:47 Hi:46
Me:43 Lo:40
51
49
48
48
Sound pressure level
(JIS C9612)
dB(A)
Outdoor
Sound power level (JIS C9612)
Outdoor
Airflow
66
Indoor
External static pressure
External dimensions
(HXWXD)
Indoor
Net weight
Refrigerant piping
398x1150x650
750x880(+88)x340
845x970x370
1300x970x370
34
52
60
81
105
Ø9.52
mm
Gas line
Ø15.88
Connection method
Refrigerant R410A
Flare Connection
Quantity
kg
Pre charged to pipe
length
m
Maximum pipe length
2.95
3.8
4.5
30
m
50
Supply air connection
mm
170x880
Return air connection
mm
200x740
100
348x898
RC-E5, RC-EX1A or RCN-KIT3-E
Controller
UA-SP1-E (Optional)
UA-SP2-E (Optional)
348
898 Duct dimension
181
472
Inspection
hole
C1
69
B
A
150
506
Case 2
17.5
284
86
VP25 I.D.25,O.D.32
VP25 I.D.25,O.D.32
M10
450X450
12.7 1 2"
22.22 7 8"
From bottom of unit
40
295 325
G
Under 60
or less
15
215
Air supply duct
111
898 Duct dimension
182
181 192
C2
650
Notes 1) The model name label is attached on the lid
of the control box.
(2) Connect the piping with local pipe by using the pipe of the
attachment. Liquid side and Gas side
61
74
E
Flare
Brazing
100
1150
C2
111
Drain piping
Drain piping
Gravity drainage
Hole for wiring
Suspension bolts
Inspection hole
Connecting position of the local pipe. liquid side
Connecting position of the local pipe. gas side
Control box
24
Duct dimension
40
348
or less
215
650
531
498
458
398
370
248
172
15
Under 60
D
600
Air supply duct
Max. drain lift
40
295 325
Suspension bolts pitch
Hanger plate for
suspension bolt
61
74
Flare
600
100
1500
650
B
A
E
17.5
600
Inspection
hole
C1
69
150
Suspension bolts pitch
472
Control box
9.52 3 8"
D
E
F
G
H
Drain hose piece
Accessory
28
From bottom of unit
or more
Case 2
17.5
284
82
28
1150
Flare
Connecting position of the attached
connecting pipe liquid side
or more
Return air duct
1185
Suspension bolts pitch
Suspension bolts pitch
15.88 5 8"
B
C2
Installed on site
or more
1185
Connecting position of the attached
connecting pipe gas side
or more
M10
450X450
A
C1
VP25 I.D.25,O.D.32
Installed on site
17.5
181
1500
898 Duct dimension
Max. drain lift
Drain hose piece
Accessory
15.88 5 8"
Flare
9.52 3 8"
Flare
VP25 I.D.25,O.D.32
111
Content
H
D
650
531
498
458
40
398
370
248
172
24
Return air duct
Content
Symbol
26
Symbol
A
Gas piping
B
Liquid piping
C1
Drain piping
Drain
piping
C2
Gravity drainage
D
Hole for wiring
E
Suspension bolts
F
Inspection hole
Duct dimension
Unit:mm
181
Unit:mm
Model FDUA160VF
24
898 Duct dimension
26
111
348
Duct dimension
Models FDUA100VF, 125VF, 140VF
600
Safety pan
24
P-Hi:850 Hi:800
Me:700 Lo:600
200
kg
Outdoor
Liquid line
Hanger plate for
suspension bolt
P-Hi:717 Hi:650
Me:600 Lo:500
280x950x635
mm
Outdoor
72
P-Hi:650 Hi:600
Me:550 Lo:483
Pa
Indoor
49
70
P-Hi: 400 Hi: 317
Me: 250 Lo: 167
l/s
Products
Capacity
Duct dimension
FDUA140AVNXVF
Outdoor
Power supply
348
FDUA125AVNXVF
506
Note 1 The model name label is attached
on the lid of the control box.
Outline drawing (Unit:mm)
9
Model FDUM50VF
Models FDUM60,71VF
FDUA Indoor Unit
10
Duct Connected - High Static Pressure
MODELS: FDUA140VF, FDUA160VF
MODEL: FDUA200VG
Remote control (Options)
Wired
Wireless
DRED enabled model
RC-EX1A
RC-E5
RCH-E3
Compact design
RCN-KIT3-E
Drain pump standard enabled. Gravity drainage selectable.
600mm
drain
pump
379mm
Flexible hose
less than
600mm
■SW8-4 : ON (Range of use limitation : Setting 10Pa-200Pa)
Model FDUA160VF
Characteristic FAN (1)
Model FDUA160VF
Symbol
181
348
Flare
180
Connecting position of the attached
connecting pipe liquid side
9.52 3 8"
Flare
160
D
E
F
G
H
Drain hose piece
Accessory
1150
Case 2
17.5
284
86
VP25 I.D.25,O.D.32
M10
450X450
12.7 1 2"
22.22 7 8"
150
215
898 Duct dimension
C2
H
D
600
or less
15
G
Me
P-Hi
120
Hi
100
Lo
Me
80
Setting 60Pa
60
0
30
P-Hi
Hi
Lo
Me
Setting 10Pa
Lo
Lo
Me
35
40
1500
Max. drain lift
40
Under 60
111
Setting 120Pa
140
40
45
Hi
55
60
or more
600
Characteristic FAN (2)
Range of approvable air flow
200
650
531
498
458
40
200P
a
180
180P
160
140
120
Pa
100
120
80
100
Pa
Pa
60
80P
40
60P
a
a
20
506
a
160P
a
140
0
46
10P
a
47 48
49 50
51
20P
a
52 53
Air flow (m3/min)
FD series Inverter Packaged Air Conditioners 2015
P-Hi
50 51
Air flow (m3/min)
Notes 1) The model name label is attached on the lid
of the control box.
(2) Connect the piping with local pipe by using the pipe of the
attachment. Liquid side and Gas side
61
74
182
181 192
Hi
220
B
A
295 325
650
398
370
248
172
472
C1
69
Air supply duct
24
Inspection
hole
P-Hi
Setting 200Pa
20
Control box
E
Flare
Brazing
From bottom of unit
28
17.5
Suspension bolts pitch
VP25 I.D.25,O.D.32
100
1185
Suspension bolts pitch
Drain piping
Drain piping
Gravity drainage
Hole for wiring
Suspension bolts
Inspection hole
Connecting position of the local pipe. liquid side
Connecting position of the local pipe. gas side
or more
24
Return air duct
Hanger plate for
suspension bolt
Duct dimension
15.88 5 8"
B
C2
In case actual E.S.P. correspond setting of E.S.P.
200
Connecting position of the attached
connecting pipe gas side
C1
Installed on site
348
Content
A
External static pressure (Pa)
898 Duct dimension
26
111
220
External static pressure (Pa)
Duct dimension
Unit:mm
40P
a
54 55
56
FDUA
FDUA140AVSXVF
Set
FDUA160AVSAVF
FDUA200AVSAVG
Indoor
FDUA140VF
FDUA160VF
FDUA200VG
Outdoor
FDCA140VSX
FDCA160VSA
FDCA200VSA
Power supply
Outdoor Unit
3 Phase 415V 50Hz
Cooling T1
kW
Heating H1
Cooling T1
Input
16.0 (6.9-20.0)
20.0 (6.9-28.0)
16.0 (4.0-18.0)
18.0 (5.5-22.4)
22.4(5.5-31.5)
4.44
4.83
6.03
4.44
4.66
5.5
3.15
3.31
3.32
kW
Heating H1
EER
Cooling T1
COP
Heating H1
3.6
3.86
4.07
Indoor
P-Hi:47 Hi:46 Me:43 Lo:40
P-Hi:49 Hi:48 Me:45 Lo:42
P-Hi:52 Hi:50 Me:47 Lo:45
49
59
Outdoor
Sound power level (JIS C9612)
dB(A)
Outdoor
Airflow
Indoor
l/s
External static pressure
73
P-Hi:850 Hi:800 Me:700 Lo:600
P-Hi:850 Hi:800 Me:700 Lo:600
Pa
Indoor
External dimensions (HXWXD)
Indoor
Outdoor
Refrigerant piping
200
Quantity
89
■SW8-4 : ON (Range of use limitation : Setting 10Pa-200Pa)
105
Characteristic143
FAN (1)
In case actual E.S.P. correcpond setting of E.S.P.
Ø9.52
Connection method
Refrigerant R410A
1505x970x370
52
mm
Gas line
379x1600x893
1300x970x370
kg
Liquid line
Ø12.7*
240
Ø15.88
Ø22.22
, Ø25.4 or Ø28.58*
220
Flare Connection
Setting 200Pa
200
Liquid:
Flare / Gas:
Brazing*
kg
4.5
utomatic
external static pressure
(E.S.P.)
control
Maximum pipe length
m
100
Pre charged to pipe length
m
Supply air connection
P-Hi:1333 Hi:1200 Me:1067 Lo:933
398x1150x650
mm
Outdoor
Net weight
59
70
mm
30
External static pressure (Pa)
Sound pressure level (JIS C9612)
180
7.2
Setting 120Pa
140
Me
P-Hi
70*
120
100
Hi
Lo
Me
80
60
Model
FDUA200VG
*Refer
to technical manual
Model FDUA200VG
S.P.
FDUM
Duct
0
50
■SW8-4 : ON (Range of use limitation : Setting 10Pa-200Pa)
Me
10Pa
20Pa
30Pa
40Pa
No.5
50Pa
No.6
60Pa
No.7
70Pa
Setting 120Pa
140
Me
P-Hi
120
60
40
80Pa
20
0
50
90
No.9
Me
No.10
Lo
Hi
Me
90Pa 100Pa
Lo
Hi
Me
Lo
60
180
200P
160
180P
140
160P
120
140
a
a
a
Pa
E.S.P.
button
100
Hi
Lo
Setting 60Pa
P-Hi
Setting 10Pa
P-Hi
70
Air flow
proved servicing
80
90
120
Pa
80
100
Pa
External static pressure
can be set by E.S.P.
button.
60
80P
40
60P
a
10P
20
0
72
a
76
a
a
80
a
40P
20P
84
88
Air flow (m3/min)
(m3/min)
Characteristic FAN (2)
Range of approvable air flow
240
220
200
External static pressure (Pa)
unit (impeller and motor) can be pulled
from the right side of the unit.
ntenance is available from the right side
rom beneath.
Hi
160
80
No.8
80
200
P-Hi
External static pressure (Pa)
No.4
External static pressure (Pa)
No.3
P-Hi
70
220
Setting 200Pa
Keep the
180 same
air flow volume
No.2
60
240
220
200
No.1
Setting 10Pa
Hi
Me
Range of approvable air flow
240
100
Lo
Lo
Characteristic FAN (2)
In case actual E.S.P. correcpond setting of E.S.P.
Ceiling
P-Hi
Hi
Air flow (m3/min)
LongerCharacteristic
Duct FAN (1)
Duct
Setting 60Pa
250x1450
Lo
40
20
P-Hi
Hi
160
using a DC motor, the optimum air flow volume can be achieved by
this automatic control.
348x898
Return air connection
mm
indoor unit will recognize external static pressure automatically
and keep rated
RC-E5, RC-EX1A or RCN-KIT3-E
Controller
flow volume.
Safety pan
UA-SP2-E (Optional)
tting No.
Products
Capacity
14.0 (5.0-14.5)
180
160
140
120
100
80
60
The fan unit (impeller
and motor) can be
Unitaccessed
easily
200P
a
Maintenanceand pulled
out from
180P
a
hole
the right
side of the
160P
a
unit. Maintenance
is
140
Pa
accessible from both
120
Service
Pa
the right
side and
100
space
Pa
underneath the unit
Fan unit
80P
a
40
60P
10P
20
0
72
Pipe
a
76
a
a
80
Air flow (m3/min)
a
40P
20P
84
88
11
FDUM Indoor Unit
12
Duct Connected - Medium Static Pressure
MODELS: FDUM50VF, FDUM60VF, FDUM71VF1, FDUM90VNPVF1, FDUM100VF1, FDUM125VF, FDUM140VF
Remote control (Options)
Wired
Wireless
DRED enabled model
RC-EX1A
RC-E5
RCH-E3
RCN-KIT3-E
600mm Drain Pump
Thin design
Drain can be discharged upwards
by 600mm from the ceiling surface.
It allows a piping layout with a high
degree of freedom depending on
the installation location.
The height of all FDUM models is only 280mm.
less than
600mm
FDUM50/60/71VF
C2
31
986
18
Hanger plate for
suspension bolt
Suspension bolts pitch
950
18
284
81
Control box
4
4
Holes for
tapping screws
635
510
471
413
30
M
Air supply duct
FD series Inverter Packaged Air Conditioners 2015
295 325
D
55
467
4
4
Holes for
tapping screws
139
E
880 Duct dimension
55
F
G
View M
30
Max. drain lift
30
58
67
or less
90
262
170
Hole
76
G
152
124
B
A
135
Suspension bolts pitch
113
F
170
C1
69
G
600
472
F
2" Flare
6.35 1 4" Flare
VP20 standard:I.D.20, O.D.26 or VP25 Used
with attached socket:I.D.25, O.D.34 Note 2
Drain piping
VP20 standard:I.D.20, O.D.26 or VP25
C2
Gravity drainage Used with attached socket:I.D.25, O.D.34
D
Hole for wiring
E
M10
Suspension bolts
Outside air opening
F
150 Knock out
for ducting
Air outlet opening
125 Knock out
G for ducting
H
450X450
Inspection hole
Notes 1 The model name label is attached on the lid of the control box.
2 Prepare the connecting socket VP20 or VP25 on site.
4
4
Holes for
tapping screws
15
262
Drain piping
113
450X450
C1
105
39
Return air duct
14
4
Holes for
tapping screw
Liquid piping
90
635
510
471
413
170
30
175
31
170
Installed on site
Content
12.7 1
B
280
250
Duct dimension
41
200
Drain hose piece
Accessory
50
Max. drain lift
76
Symbol
A
Gas piping
65
46
28
152
Hole
15
50
55
860 Duct dimension
4 200=800
200
125 Knock out
View M
D
680 Duct dimension
150 Knock out
170
295 325
65
46
M10
139
B
A
135
Air supply duct
4
4
Holes for
tapping screws
124
C1
600 or less
472
Hole for wiring
Suspension bolts
Outside air opening
for ducting
Air outlet opening
for ducting
Inspection hole
H
69
E
43
D
E
Notes 1 The model name label is attached on the lid of
the control box.
2 Prepare the connecting socket VP20 or VP25 on site.
18
284
81
28
750
58
67
170
Drain piping
Gravity drainage
F
Suspension bolts pitch
G
Duct dimension
Suspension bolts pitch
C2
G
Control box
55
Drain piping
12.7 1 2" Flare
6.35 1 4" Flare
VP20 standard:I.D.20, O.D.26
or VP25 Used with attached
socket:I.D.25, O.D.34 Note 2
VP20 standard:I.D.20, O.D.26
or VP25 Used with attached
socket:I.D.25, O.D.34
43
Return air duct
12
4
Holes for
tapping screw
C1
105
39
31
Installed on site
Gas piping
Liquid piping
Duct dimension
170
Drain hose piece
Accessory
F
M
H 280
Content
A
B
170
31
65
46
280
250
175
Duct dimension
41
200
660 Duct dimension
200 200 200
786
H 280
FDUM60VF
Symbol
18
H 299
Model FDUM60VF
Model FDUM50VF
Hanger plate for
suspension bolt
19mm less
H 350
FDUM100/125/140VF
FDUM50VF
65
46
70mm less
Flexible hose
C2
467
Outline drawing (Unit:mm)
Model FDUM50VF
FDUM
Set
FDUM50ZMXAVF FDUM60ZMXAVF
FDUM71AVNXVF1
FDUM90VNPVF1
FDUM50VF
FDUM60VF
FDUM71VF1
FDUM100VF1
FDUM100VF1
FDUM125VF
FDUM140VF
SRC50ZMXA-S
SRC60ZMXA-S
FDCA71VNX
FDC90VNP
FDCA100VN
FDCA125VNX
FDCA140VNX
Indoor
Outdoor
Power supply
Outdoor Unit
1 Phase 220-240V 50Hz
Cooling T1
Heating H1
Input
kW
FDUM140VF
FDCA140VSX
3 Phase 415V 50Hz
5.0 (2.2-5.6)
5.6 (2.8-6.3)
7.1 (3.2-8.0)
9.0 (1.9-9.0)
10.0 (4.0-11.2)
12.5 (5.0-14.0)
14.0 (5.0-14.5)
14.0 (5.0-14.5)
5.4 (0.6-6.3)
6.7 (0.6-7.1)
8.0 (3.6-9.0)
9.0 (1.9-9.0)
11.2 (4.0-12.5)
14.0 (4.0-17.0)
16.0 (4.0-18.0)
16.0 (4.0-16.5)
Heating H2
4.3
4.9
7.0
N/A
11.4
13.7
14.3
Cooling T1
1.56
1.75
2.20
2.65
2.92
3.60
4.40
1.70
2.00
2.20
2.25
3.20
3.90
4.54
kW
Heating H1
FDUM140AVSXVF
PRODUCTS
Capacity
FDUM100AVNVF1 FDUM125AVNXVF FDUM140AVNXVF
N/A
4.40
4.54
EER
Cooling T1
3.21
3.20
3.23
3.40
3.42
3.47
3.18
COP
Heating H1
3.18
3.35
3.64
4.00
3.50
3.59
3.52
3.52
Indoor
P-Hi:37 Hi:32
Me:29 Lo:26
P-Hi:36 Hi:31
Me:28 Lo:25
P-Hi:38 Hi:33
Me:29 Lo:25
P-Hi:44 Hi:38
Me:36 Lo:30
P-Hi:44 Hi:38
Me:36 Lo:30
P-Hi:45 Hi:40
Me:34 Lo:29
P-Hi:47 Hi:40
Me:35 Lo:30
P-Hi:47 Hi:40
Me:35 Lo:30
50
54
51
55
49
50
49
49
63
64
66
69
72
70
P-Hi: 217 Hi: 167
Me: 150 Lo: 133
P-Hi:333 Hi:250
Me:217 Lo:167
P-Hi: 400 Hi: 316
Me: 250 Lo: 166
P-Hi: 600 Hi: 467
Me: 417 Lo: 317
P-Hi:800 Hi:583
Me:467 Lo:367
P-Hi:800 Hi:583
Me:467 Lo:367
Sound pressure level
(JIS C9612)
Outdoor
Sound power level
(JIS C9612)
dB(A)
Outdoor
Airflow
Indoor
l/s
External static pressure
70
Pa
Indoor
External dimensions
(HXWXD)
Indoor
Net weight
Liquid line
280x950x635
640x800(+71)x290
29
280x1370x740
750x880(+88)x340
34
mm
Gas line
Refrigerant piping
280x750x635
kg
Outdoor
P-Hi:650 Hi:533
Me:433 Lo:333
100
mm
Outdoor
P-Hi: 600 Hi: 467
Me: 417 Lo: 317
750x880(+88)x340
845x970x370
1300x970x370
34
54
45
60
57
Ø6.35
Ø9.52
Ø9.52/Ø6.35/Ø6.35
81
105
Ø9.52
Ø12.7
Ø15.88
Connection
method
Flare Connection
Quantity
kg
1.5
2.95
2.1
Pre charged to
pipe length
m
15
30
15
Maximum pipe length
m
30
50
30
Supply air connection
mm
170x680
170x1200
mm
200x660
235x1280
Return air connection
2 wire or
infrared
Controller
55
18
284
81
124
B
A
G
71
170
C1
Hole
180
295 325
104
D
1200 Duct dimension
104
C2
92
45
15
Air supply duct
Max. drain lift
E
43
467
Hole for wiring
Suspension bolts
M10
Outside air opening
150 Knock out
for ducting
Air outlet opening
G
125 Knock out
for ducting
450X450
H Inspection hole
Notes 1 The model name label is attached on the lid of
the control box.
4
4 2 Prepare the connecting socket VP20 or VP25 on site.
4
4
Holes for
Holes for
tapping screws
152 285
tapping screws
Control box
59
69
M
C2
F
Suspension bolts pitch
30
Duct dimension
635
510
471
413
170
Drain piping
Drain piping
Gravity drainage
D
E
Return air duct
1368
C1
15.88 5 8" Flare
9.52 3 8" Flare
VP20 standard:I.D.20, O.D.26
or VP25 Used with attached
socket:I.D.25, O.D.34 Note 2
VP20 standard:I.D.20, O.D.26
or VP25 Used with attached
socket:I.D.25, O.D.34
139
21.5
24.5
14
4
Holes for
tapping screw
Content
Gas piping
Liquid piping
113
24.5
235
205
Installed on site
F
530
113
G
View M
90
Drain hose piece
Accessory
1404
139
or less
880 Duct dimension
C2
76
50
D
F
30
Max. drain lift
295 325
15
Air supply duct
Hole
600
472
E
43
262
170
B
A
135
Suspension bolts pitch
C1
69
58
67
Duct dimension
152
124
4
4
Holes for
tapping screws
A
B
64
100
28
4
4
Holes for
tapping screws
1280 Duct dimension
4 280=1120
280
18
Hanger plate for
suspension bolt
Suspension bolts pitch
18
284
81
28
950
170
Suspension bolts pitch
G
170
D
E
Air outlet opening
125 Knock out
for ducting
H
450X450
Inspection hole
Notes 1 The model name label is attached on the lid of the control box.
2 Prepare the connecting socket VP20 or VP25 on site.
Control box
55
100
Symbol
64
100
G
F
M
C1
C2
F
Return air duct
14
4
Holes for
tapping screw
9.52 3 8" Flare
VP20 standard:I.D.20, O.D.26 or VP25 Used
Drain piping
with attached socket:I.D.25, O.D.34 Note 2
Drain piping
VP20 standard:I.D.20, O.D.26 or VP25
Gravity drainage Used with attached socket:I.D.25, O.D.34
Hole for wiring
M10
Suspension bolts
Outside air opening
150 Knock out
for ducting
105
39
31
170
Installed on site
Flare
Liquid piping
175
31
Drain hose piece
Accessory
Duct dimension
B
Content
15.88 5 8"
23.5
Symbol
A
Gas piping
65
46
280
250
Duct dimension
41
200
860 Duct dimension
4 200=800
986
50
FDUM100VF, 125VF, 140VF
200
18
30
Models FDUM100VF, 125VF, 140VF
FDUM71VF
Hanger plate for
suspension bolt
4.5
RC-E5, RC-EX1A or RCN-KIT3-E
Model FDUM71VF
65
46
3.8
30
600 or less
280
250
184.5
134.5
Refrigerant R410A
3.18
F
G
View M
90
738
635
468
405
170
30
467
13
EX1A
FDTC - Indoor Unit
14
Ceiling Cassette-4way Compact 600x600mm
MODELS: FDTC50VF
Remote control (Option)
Wireless
Wired
FDTC50VF
Remote control (Options)
Wired
RCH-E3
RC-E5
Wireless
RCN-TC-24W-ER
DRED enabled model
RC-EX1A
RC-E5
RCH-E3
RCN-TC-24W-ER
Outline drawing (Unit:mm)
G
G
G
D
A B
C F
G
FD series Inverter Packaged Air Conditioners 2015
FDTC
Set
FDTC50ZMXAVF
Indoor
FDTC50VF
Outdoor
SRC50ZMXA-S
Outdoor Unit
1 Phase 220-240V 50Hz
Cooling T1
Capacity
5.0(1.1-5.6)
Heating H1
Input
kW
5.4 (0.6-6.3)
Heating H2
5.10
Cooling T1
1.56
kW
Heating H1
1.45
EER
Cooling T1
COP
Heating H1
3.72
Indoor
P-Hi:47 Hi:42 Me:36 Lo:30
Sound pressure level (JIS C9612)
3.20
Outdoor
Sound power level (JIS C9612)
dB(A)
54
P-Hi: 225 Hi: 191 Me: 150 Lo: 133
Outdoor
63
Airflow
Indoor
l/s
Panel
TC-PSA-25W-E
mm
Indoor
External dimensions (HXWXD)
Indoor
640x800(+71)x290
Unit 15 Panel 3.5
kg
Outdoor
Liquid line
Refrigerant piping
35x700x700
248x570x570
mm
Outdoor
Net weight
45
Ø6.35
mm
Gas line
Ø12.7
Connection method
Flare connection
Quantity
Refrigerant R410A
Products
Power supply
kg
Pre charged to pipe length
Maximum pipe length
1.5
m
15
m
30
Controller
RC-E5, RC-EX1A or RCN-TC-24W-ER
Quiet operation
Taking OA (Outside air intake) into inside
Sound Pressure
level in the Lo mode
(dB)
OA Spacer TC-OAS-E (option)
(dB)
36
3dB
35dB
36
3dB
Joint Duct TC-OAD-E (option)
35
35dB
Down
35
Down
(dB)
34
Utilizing OA spacer which
36
3dB
35dB34
(dB)
33 (dB)
32dB
comes as optional equipment,
35
Indoor Unit FDTC
Down
33
36
36
3dB
3dB
32dB
Indoor Unit FDTC
35dB
35dB
32
34
32
35
35
Down
Down
outside air can be taken
31
33
30dB
34
31
34
32dB
Indoor Unit FDTC
30dB
into inside.
30 33
32
33
30
32dB
32dB
Indoor Unit FDTC 31
Indoor Unit FDTC
29
Using 1 joint duct:
32
32
30dB 5dB
29
5dB
300mm 300mm
30
OA
28
3
31
31
28
OA comes up to 1.3m /min.OA
30dBDown Down 30dB
29
Spacer Spacer
30
300mm
27 5dB 27 30
Using 2 joint ducts: OA
28
29
29
Down
26
5dB
26 5dB
Spacer
300mm
300mm OA
OA
27
Ceiling Ceiling
OA
OA
OA 2.6m3/min.
28
28
OA
OA comes from 1.3 to
Down
25Down 25
surface surface Spacer
Spacer
Panel
Ceiling OA
surface
Ceiling OA
surface
OA
Panel
Panel
Panel
Joint Duct Joint Duct
Duct OA
Ceiling
OA Joint
surface
Joint Duct
OA
Panel
26
27
25
26
27
Previous
Joint Duct (Cooling/Heating)
Previous
(Cooling/Heating)
25
Previous New
Previous
26
(Cooling/Heating)
25(Cooling/Heating)
New
New(Cooling)
(Cooling)
(Heating)
Previous
New
New
(Cooling) (Cooling/Heating)
(Heating)
New
New
(Cooling)
(Heating)
New
(Cooling)
New
(Heating)
New
(Heating)
Compact and Convenient
“CLEARER”Air Flow
New shape & angled louver redirects the
air current away from the ceiling, to reduce
ceiling stains
Installation Workability
For wireless control simply insert the infrared
receiver kit onwireless
a corner of the panel
wireless
248mm
remote
wirelesscontrol
wirelesswireless 248mm
remote control
RCN-TC-24W-ER
remote control
remote remote
controlcontrol
RCN-TC-24W-ER
RCN-TC-24W-ER
RCN-TC-24W-ER
• 600mm Drain Pump
Drain can be discharged upward by 600 mm from the
ceiling surface close to the indoor unit.
It allows a piping layout with a high degree of freedom
depending on the installation location.
• 600 x 600 ceiling
Indoor unit size (W:570 x D:570) brings easy installation
for 600 x 600 ceiling and Panel size (700 x 700) is
suitable for 600 x 600 ceiling. Height is one of the
industry’s lowest level at 248mm and weight is only
16.5kg.
Flexible hose
Flexible hose
Flexible hose
248mm
600mm
600mm
248mm
248mm
Flexible
Flexiblehose
hose
600mm
600mm
600mm
RCN-TC-24W-ER
15
FDT - Indoor Unit
16
Ceiling Cassette-4way
MODELS: FDT60VF, FDT71VF1, FDT90VNPVF1, FDT100VF1, FDT125VF, FDT140VF
ol (Option)
Wired
RC-E5
Wireless
Remote control (Options)
Wired
Wireless
RCH-E3 RCN-T-36W-E
DRED enabled model
RC-EX1A
RC-E5
RCH-E3
RCN-T-36W-E
Outline drawing (Unit:mm)
Model FDT 60,71VF
Model 100,125,140VF
H
G
H
G
H
H
H
H
H
H
C
B A
C
F
F
B A
H
H
D
D
G
G
FD series Inverter Packaged Air Conditioners 2015
FDT
Set
FDT60ZMXAVF
Indoor
Outdoor
Power supply
FDT100AVNVF1
FDT125AVNXVF
FDT140AVNXVF
FDT60VF
FDT71VF1
FDT100VF1
FDT100VF1
FDT125VF
FDT140VF
FDT140VF
SRC60ZMXA-S
FDCA71VNX
FDC90VNP
FDCA100VN
FDCA125VNX
FDCA140VNX
FDCA140VSX
5.6 (1.1-6.3)
7.1 (3.2-8.0)
9.0 (1.9-9.0)
10.0 (4.0-11.2)
12.5 (5.0-14.0)
14.0 (5.0-16.0)
14.0 (5.0-16.0)
6.7 (0.6-7.1)
8.0 (3.6-9.0)
9.0 (1.5-9.0)
11.2 (4.0-12.5)
14.0 (4.0-17.0)
16.0 (4.0-18.0)
16.0 (4.0-20.0)
1 Phase 220-240V 50Hz
kW
FDT140AVSXVF
3 Phase 415V 50Hz
Heating H2
5.29
7.2
N/A
N/A
15.6
13.8
N/A
Cooling T1
1.52
2.04
2.67
2.76
3.28
4.19
4.19
Heating H1
kW
1.70
1.94
2.19
2.74
3.43
4.2
4.20
EER
Cooling T1
3.68
3.48
3.37
3.62
3.81
3.34
3.34
COP
Heating H1
3.94
4.12
4.11
4.09
4.08
3.81
3.81
Indoor
P-Hi:46 Hi:33
Me:31 Lo:30
P-Hi:46 Hi:35
Me:33 Lo:31
P-Hi:51 Hi:40
Me:37 Lo:35
P-Hi:51 Hi:40
Me:37 Lo:35
P-Hi:51 Hi:42
Me:40 Lo:37
P-Hi:51 Hi:43
Me:41 Lo:38
P-Hi:51 Hi:43
Me:41 Lo:38
dB(A)
54
51
55
49
50
52
49
Outdoor
65
66
69
70
70
72
72
Indoor
l/s
P-Hi: 466 Hi: 300
Me: 266 Lo: 233
P-Hi: 466 Hi: 350
Me: 316 Lo: 283
P-Hi: 617 Hi: 450
Me: 400 Lo: 333
P-Hi: 616 Hi: 450
Me: 400 Lo: 333
P-Hi: 616 Hi: 500
Me: 450 Lo: 383
P-Hi: 616 Hi: 500
Me: 450 Lo: 383
P-Hi: 617 Hi: 500
Me: 683 Lo: 383
Sound pressure level
(JIS C9612)
Sound power level
(JIS C9612)
Airflow
Outdoor
Panel
mm
External dimensions
(HXWXD)
Indoor
Outdoor
Indoor
Net weight
Outdoor
Liquid line
Refrigerant piping
Gas line
mm
kg
mm
T-PSA-3BW-E (35x950x950)
246x840x840
640x800(+71)x290
298x840x840
750x880(+88)x340
Unit 24 Panel 5.5
45
1300x970x370
60
57
Unit 27 Panel 5.5
81
105
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Flare connection
Quantity
kg
1.5
2.95
2.1
Pre charged to pipe
length
m
15
30
15
m
30
50
30
Maximum pipe length
845x970x370
Unit 27 Panel 5.5
Connection method
Refrigerant R410A
Products
Heating H1
Input
FDT90VNPVF1
Indoor Unit
Cooling T1
Capacity
FDT71AVNXVF1
Controller
3.8
4.5
30
50
100
RC-E5, RC-EX1A or RCN-T-36W-E
Installation
Infrared control option
Detachable covers at each corner allows
for easy alignment and balance.
The panel does not need to
be removed. Installation time
is reduced.
For wireless control simply insert the infrared receiver
kit on the corner.
wireless
remote
control
wireless
remote
control
RCN-T-36W-E
RCN-T-36W-E
wireless remote
remote control
control
wireless
RCN-T-36W-E
RCN-T-36W-E
Easy checking of drain pan
700mm Drain Pump
To check the drain pan simply remove the corner lid.
Drain can be discharged upwards by Flexible
700mm
from
Flexible
hose the
hose
ceiling surface. The 260mm flexible hose is supplied as
standard equipment.
thanthan
Flexiblehose
hoselessless
Flexible
700mm
700mm
lessthan
than
less
700mm
700mm
17
FDEN - Indoor Unit
Ceiling Suspended
MODELS: FDEN100VF1, FDEN125VF
FDEN 100/125VF
Remote control (Options)
Wired
Wireless
DRED enabled model
Remote control (Option)
RC-EX1A
Wired
RC-E5
RCH-E3
Wireless
RCN-E1R
Outline drawing (Unit:mm)
RC-EX1A
b
40
40
c
52
68
Air outlet
690
195
235
271
75 Liquid piping
Gas piping
Air inlet grille
110
Drain hole
connection(1)
(VP20(I.D.20))
135
Dimension Table
model
FDEN100~125
a
b
c
d
e
1572
1540
1620
255
250
FD series Inverter Packaged Air Conditioners 2015
53
Note(1) The slope of drain piping
inside the unit is able
to take incline of 10mm.
10
Drain hole
connection(1)
(VP20(I.D.20))
76
100
or more
150
or more
RCH-E3 RCN-E1R
RC-E5
Indication board
Space for installation and service
Liquid piping
Gas piping
e
d
173
5
135
Holes for suspension bolts
(M8 to M10x4pcs.Not included)
410
145
300 or more
290(Suspension bolts pitch)
24
53
109
a (Suspension bolts pitch)
24
308
18
Obstacles
Drain hole
connection(1)
(VP20 (I.D.20))
5
or more
FDEN
Set
Indoor
Outdoor
FDEN100VNVF1
FDEN125AVNXVF
FDEN100VF1
FDEN125VF
FDCA100VN
FDCA125VNX
Outdoor Unit
1 Phase 220-240V 50Hz
Cooling T1
Capacity
10.0 (4.0-11.2)
12.5 (5.0-14.0)
11.2 (4.0-12.5)
14.0 (4.0-17.0)
Heating H2
8.7
15.0
Cooling T1
2.85
3.86
2.97
3.77
3.51
3.23
Heating H1
Input
Heating H1
kW
kW
EER
Cooling T1
COP
Heating H1
3.77
3.71
Indoor
P-Hi:46 Hi:44 Me:41 Lo:39
P-Hi:50 Hi:46 Me:44 Lo:43
Sound pressure level (JIS C9612)
Outdoor
Sound power level (JIS C9612)
dB(A)
49
50
Outdoor
Airflow
Indoor
Indoor
External dimensions (HXWXD)
Outdoor
Indoor
Net weight
Outdoor
Liquid line
Refrigerant piping
Gas line
70
l/s
mm
kg
P-Hi:466 Hi:433 Me:383 Lo:350
845x970x370
1300x970x370
49
81
105
Ø9.52
mm
Ø15.88
Flare Connection
Quantity
kg
Pre charged to pipe length
m
Maximum pipe length
P-Hi:533 Hi:483 Me:433 Lo:383
250x1620x690
Connection method
Refrigerant R410A
Products
Power supply
m
3.8
4.5
30
50
100
Controller
RC-E5, RC-EX1A or RCN-E-E
Improved installation workability
Increased freedom of a piping layout
Up
Right
Rear
The refrigerant pipe from the unit can be arranged in three directions, rear, right and up. The drain pipe can be arranged in two
directions, left and right. This will allow a free layout of piping for various installation conditions. The unit can only be serviced
from below.
Compact and modern design
Height
250mm
ht
All models fit compactly on ceiling. (Height-210mm or 250mm).
Plain, modern design featuring rounded edges gives room a comfortable atmosphere.
19
20
SUPERLINK-
Control System
KX6 series
SC-SL1N-E
RAC series
(SRK/SRF-ZMA-S)
SC-BIKN-E
SC-ADNA-E
SC-SL4AE
SC-ADNA-E
SC-ADNA-E
Central Control
SC-SL1N-E
SC-SL2NA-E
SC-SL4-AE/BE
Start/stop control of up to 16 indoor units is
possible either individually or collectively. With
simple operations, you can effect centralised
control.
Centralised control of up to 64 indoor units.
Allows connection with a weekly timer without
using any interface.
Easy operation through the large color LCD
and touch panel. Up to 128 indoor units can be
controlled, when three SUPERLINK-II systems
are connected.
PC windows central control
SC-WGWNA-A/B
(SC-WGWNA-B has electric power calculation function)
BMS interface unit
SC-BGWNA-A/B
(LonWorks gateway)
Up to 96 cells (some cells can have two or
more indoor units and total number of indoor
units can be up to 128 units) are controlled
centrally from a BMS.
Up to 96 indoor units (48 indoor unit x 2) are
linked as an open network. Centrally
controlled through LonWorks.
(SC-WGWN-B has electric power calculation function)
Up to 96 cells (some cells can have two or
more indoor units and total number of
indoor units can be up to 128 units) are
controlled from the Internet.
Additional engineering service, in the case of
SCWGWNB256-A/B up to 256 cells cost is required.
Please consult your dealer when using this central
control.
FD series Inverter Packaged Air Conditioners 2015
SC-LGWNA-A
(BACnet gateway)
Additional engineering service, in the case of
SCWGWNB256-A/B up to 256 cells cost cost is
required. In case of SC-BGWN-B, communication test
by qualified person regarding electric cost calculation
function is required before commissioning. Please
Additional engineering service cost is required.
Please consult your dealer when using this gateway.
SUPERLINK E BOARD (SC-ADNA-E)
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
Blue
A
Run
Abnormal
SL E board
A
Blue
B
LED3
LED2
X
White
Y
Y
ON
SW3
OFF
SW2
SW1
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm2
B
Black
X
Connected to the remote controller terminals (no
polarity) (the length should be 600 m or shorter)
200 m or shorter
0.5 mm2 x 2 cores
300 m or shorter
0.75 mm2 x 2 cores
400 m or shorter
1.25 mm2 x 2 cores
600 m or shorter
2.0 mm2 x 2 cores
Network address setting switches
[000]-(127)
Master/Sub
address
Basic Connections
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
Internal/external Crossing
Indoor unit
X Y
SL E Board
X Y
A B
Inside Inside Inside Inside
Remote control
X Y
SL E
Board
Network
options
Network A B
options
R
R
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
R
Inside Inside Inside
SL E
Board
R
Network
options
Without Remote Control
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
SL E
Board
CONTROL SYSTEM
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a
network option (SC-SL1N-E, SC-SL2NA-E, etc).
R
R
Set up “000” to “127” using address switch on the SL E board.
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Set the SL E board dip SW
to “Master” SW3-1 ON.
The network option
SLA-1-E, SL1N-E is not
allowed (This will disturb
switching of the operation
mode)
Wireless Kit
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
(3) Metal box dimension
85
35
30
70
90
5
22.5
100
40
2-ø6
21
22
Control System
Individual Control
Remote Control line up
indoor unit
wired
remote control
RC-E5
RCH-E3
RC-EX1A
all models
wireless
indoor unit
FDT
FDTC
FDUM, FDU
FDEN
remote control
RCN-T-36W-E
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E-E
Wired remote control with weekly timer (option)
RC-E5
Run hour metres to facilitate maintenance checking
RC-E5 stores operation data when an anomaly occurs and indicates the error on
the LCD. It also displays cumulative operation hours of the air conditioner and
compressor since commissioning.
The RC-E5 controller enables
extensive access to service
and maintenance technical
data combined with easy to
use functions and a clear
LCD display.
Weekly timer function as standard
RC-E5 provides (as a standard feature) a weekly timer, which allows
one-week operation schedules to be registered. A user can specify up to
four times a day to start/stop the air conditioner. (Temperature setting is also
possible with the timer).
Timer operation
Room temperature controlled
by the remote control sensor
The temperature sensor is housed in the top
section of the remote control unit. This
arrangement has improved the sensitivity of the
remote control unit’s sensor, which permits more
finely controlled air conditioning.
Changeable set temperature ranges
RC-E5 allows the upper and lower limits of a set temperature range to be
specified separately.
By adjusting a set temperature range, you can ensure energy saving air
conditioning by avoiding excessive cooling or heating.
Changeable range
Upper limit
20~30C(effective for heating operation)
Lower limit
18~26C(effective for non-heating operation)
Simple remote control (option)
RCH-E3 (wired)
Considering specialised usage in hotel rooms,
control buttons are limited only to minimum
required functions such as ON/OFF, mode,
temperature setting and fan speed. It is really
simple and easy to use.
RCH-E3 is not applicable to the Individual flap control
system and the Flap control system.
When RCH-E3 is used, the fan has 3 speed settings
(Hi-Me-Lo) only.
Up to 16 units
It can control up to 16 units individually, by pressing the AIR CON No. button.
AUTO restart
This function allows starting the air conditioner automatically when power supply
is restored after power failure or by turning on the power switch.
Wireless remote control (option)
Thermistor (option)
SC-THB-E3
For wireless control simply insert the infrared
receiver kit on a corner of the panel.
RCN-T-36W-E,
RCN-TC-24W-ER
RCN-KIT3-E
When wireless remote control is used, the fan has 3 speed settings (Hi-Me-Lo) only.
FD series Inverter Packaged Air Conditioners 2015
RCN-E-E
This sensor is used when individual remote control is
not required in each room and the system is under
central control. By installing sensors in strategic
locations through out the structure greater comfort
control is achieved. In many instances one additional
sensor is all that is required.
KXZ-KXR
Industry leading energy efficiency and
reliability from our advanced technology
PRODUCTS
Mitsubishi Heavy Industries offers one of the largest ranges of VRF multi inverter
products in the industry. The compact M series (11.2 to 15.5kW) is a single fan, single
phase outdoor that is providing air conditioning solutions all over Australia and New
Zealand. The larger side blow (22.4 to 33.5kW) and top discharge (40 to 68kW) units
can be used singularly or in combination to deliver up to 136kW of heat pump or heat
recovery technology and energy saving in high rise and mid rise structures. With 16
types of indoor units and 78 different capacities available designs are only limited by
imagination. Our eSolution software makes selection simple.
The SuperlinkII network can control up to 128 indoor units via a central control or
BMS interface such as Web or BACnet gateways. Mente PC can be connected for
fault finding and recording test run reports.
VRF inverter multi-system
Air-Conditioners
SR
Residential Air Conditioner
Mitsubishi Heavy Industries wall mounted and floor standing
inverter split systems are the ideal choice to control comfort in
any residential situation.
Mitsubishi Heavy Industries residential air conditioners have
received great reviews in consumer magazines here and
overseas when tested and compared to the competitions
similar products. Energy efficiency, quite operation and ease of
use were the standout differences.
SCM
Residential Air Conditioner
These residential use inverter multi systems can condition
2 to 6 rooms using either wall mounted, floor standing,
low static bulkhead or compact cassette type indoor units.
The SCM series offers a total of 7 outdoor units and many
indoor units making hundreds of different comfort
combinations possible. Perfect for homes and apartments.
23
Before starting use
Heating performance
Refrigerant leakage
The heating performance values (kW) described in catalog are the values
obtained by operating at an outdoor temperature of 7C and indoor temperature
of 20C as set forth in the ISO Standards. As the heating performance decreases
as the outdoor temperature drops, if the outdoor temperature is too low and the
heating performance is insufficient, use other heating appliances as well.
The refrigerant (R410A) used for Air conditioner is non-toxic and nonflammable
in its original state.
However, in consideration of a state where the refrigerant leaks into the room,
measures against refrigerant leaks must be taken in small rooms where the
tolerable level could be exceeded. Take measures by installing ventilation
devices, etc.
Indication of sound values
The sound values are the values (A scale) measured in a chamber such as an
anechoic chamber following the ISO Standards. In the actual installation state,
the value is normally larger than the values given in the catalog due to the effect
of surrounding noise and echo. Take this into consideration when installing.
Use in oil atmosphere
Avoid installing this unit in as atmosphere where oil scatters or builds up, such
as in a kitchen or machine factory.
If the oil adheres to the heat exchanger, the heat exchanging performance will
drop, mist may be generated, and the synthetic resin parts may deform and
break.
Use in snowy areas
Take the following measures when installing the outdoor unit in snowy areas.
Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake
port or enter and freeze in the outdoor unit.
Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In
this case, a frame that is 50cm or higher than the estimated snow fall must be
installed underneath the outdoor unit.
Automatic defrosting device
Use in acidic or alkaline atmosphere
If this unit is used in acidic atmosphere such as hot spring areas having high
level of sulfuric gases or in alkaline atmosphere including ammonia or calcium
chloride, places where the exhaust of the heat exchanger is sucked in, or at
coastal areas where the unit is subject to salt breezes, the outer plate or heat
exchanger, etc., will corrode. Please ask a dealer or specialist when you use an
air conditioner in places differing from a general atmosphere.
If the temperature is low, and the humidity is high, frost will stick to the heat
exchanger of the outdoor unit. If use is continued, the heating performance will
drop.
The “Automatic defrosting device” will function to remove this frost.
After heating for approx, three to ten minutes, it will stop, and the frost will be
removed. After defrosting, hot air will be blown again.
Use in places with high ceilings
Servicing the air-conditioner
If the ceiling is high, install a circulator to improve the heat and air flow
distribution when heating.
After the air-conditioner is used for several seasons, dirt will build up in the
air-conditioner causing the performance to drop. In addition to regular servicing,
we recommend the maintenance contract (charged for) by a specialist.
Safety Precautions
Air-conditioner usage target
Installation
The air-conditioner described in this catalog is a dedicated cooling/heating
device for human use.
Do not use it for special applications such as the storage of foodstuffs, animals
or plants, computer server rooms, precision devices or valuable art, etc.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current leaks
could occur.
Always commission the installation to a dealer or specialist. Improper
installation will lead to water leakage, electric shocks and fires.
Make sure that the outdoor unit is stable in installation. Fix the unit to stable
base.
Before use
Always read the “User's Manual” thoroughly before starting use.
Usage place
Do not install in places where combustible gas could leak or where there are
sparks.
Installation in a place where combustible gas could be generated, flow or
accumulate, or places containing carbon fibers could lead to fires.
Only persons that are qualified and licensed are permitted to install and service products that contain refrigerants in Australia, go to www.arctick.org.
Suitable access for service must be provided in compliance with industry standards and local regulations.
Proudly supporting
Australia:
New Zealand:
ABN 92 133 980 275
G.S.T. 105-673-620
Phone: 1300 138 007 Fax: 1800 644 329
Phone: 0800 138 007 Fax: 09 442 5346
NSW & Head Office
Victoria
Brisbane
Townsville
Western Australia
Auckland
9C Commercial Road
Kingsgrove NSW 2208
PO Box 318 Kingsgrove
NSW 1480
2/24 Lakeside Drive
Burwood East
VIC 3151
5/26 Flinders Parade
North Lakes
QLD 4509
12/31 Fleming Street
Aitkenvale
QLD 4812
PO Box 1386 Aitkenvale
QLD 4814
Unit 3A 2 Mulgul Rd
Malaga WA 6090
PO Box 2089 Malaga
WA 6944
Unit 2 100 Bush Road
Albany 0632
PO Box 300552
Albany 0632
www.mhiaa.com.au
MRE SPARE PARTS
www.mrespareparts.com.au Tel: +61 (0) 2 9600 7444 Fax: +61 (0) 2 9600 8044
ISO9001
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certified ISO 9001
Certificate number : JQA-0709
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD.
Certified ISO 9001
Certificate Number : 04100 1998 0813
ISO 14001
Certificate 04104 1998 0813 E5
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certified ISO 14001
Certificate number : JQA-EM0256
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO.,LTD.
Certificate Number : 04104 1998 0813 E5
P
Our Air Conditioning &
Refrigeration Systems
Headquarters has been
assessed and found to
comply with the
requirements of
ISO14001.
nd Lab
ou
ts a
ar
5
Ye
a
r Wa r r a n
ty
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. E&OE.
MHIAA446_PAC Series 2015_08