Evaluation of Form Wound Insulation with Motor Circuit Analysis Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC Lombard, IL, USA hpenrose@motordoc.com Abstract—Motor Circuit Analysis techniques involve the use of low voltage, frequency-based and high voltage turn and insulation to ground tests. These methods primarily rely upon circuit inductance, capacitance and impedances as well as insulation to ground capacitive measurements. In this paper the common methods will be outlined as they relate to form wound assembled machines from 4160 Volts to 13.8 kV systems including examples of applications at both voltages. Keywords—Motor Circuit Analysis; MCA; Electric Machine; Inductance; Capacitance; Impedance; Resistance; Surge Comparison; PD Surge; Insulation Resistance; Polarization Index; Insulation Resistance Profile I. INTRODUCTION Low and high voltage Motor Circuit Analysis (MCA) techniques have been commercially available since the 1950s with newer technologies in the low voltage MCA space since the 1980s. Since this time MCA has become more prevalent as a field predictive maintenance (PdM) and testing technology performed on assembled electric machines versus it’s primary use by the machine repair industry and some larger industries, such as utilities, in the past. The description used within the testing industry has commonly been ‘low and high voltage’ testing technologies, giving the incorrect impression that the technologies focus on low and high voltage equipment. Most of the manufacturers of MCA technologies recognized the increased use of these testing methods by maintenance organizations and their applications to fully assembled machines. This required some modifications to existing instruments as the rotating components of the machines had a tendency to impact the test results due to mutual inductance with the stationary component over the airgap. The volume of the airgap, the distance across the airgap between components in particular, the sensitivity of the device being used, and the type of winding style, all have an influence on the balance of readings between phases. The balance and influence of the mutual inductance allows users of MCA technologies to evaluate both the condition of the stator (stationary windings) and rotor (rotating component) when testing can be performed in such a way that the rotor can be moved. However, proper field interpretation requires experience in applications where the rotor cannot be moved due to resulting imbalances in different types of machines. In this paper we will be discussing the application of low and high voltage MCA on form wound machines through 13.8kV including field experience. These machines include industrial machines from induction, wound rotor to synchronous and are applicable to such industries as wind. Each technology will be compared. II. TECHNOLOGIES APPLIED For purposes of this study, three devices were used in the field as part of an evaluation of 42 electric machines ranging from 4160 Vac to 13.8 kV. The devices used in this study included in which all testing methods are outlined in IEEE Std 1415-2006: Amprobe 5kV Insulation Resistance Tester (AMB5): Insulation resistance, polarization index, dielectric absorption, dielectric discharge, and capacitance to ground. ALL-TEST PRO 5: Resistance, inductance, impedance, phase angle, current/frequency response, insulation resistance, capacitance to ground, dissipation factor. All testing but insulation resistance is performed with ~10V output at frequencies through 1200 Hz. Electrom iTIG II D12: Resistance, inductance, impedance, phase angle, capacitance, Q-factor (all low voltage), insulation resistance, polarization index, dielectric absorption, high potential test, surge comparison testing (performed 50-60Hz), and PD Surge. High voltage tests up to 12kV. Each of the above systems is designed to be applied in the field, as well as in the OEM and service industries. It is noted that low voltage equipment is applied across all machine voltages and is generally small and light weight. High voltage test equipment must increase in size in order to provide the output voltage necessary to test machines. ©2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current Sponsors of this including paper are ALL-TEST Pro LLC and Electrom or future media, reprinting/republishing this material for advertising or promotional purposes, creating new collective Instruments. works, for resale or redistribution to servers or lists, or reuse of any copyrighted components of the work in other works. III. CASE STUDIES The following case studies are relatively typical of what is found in the field as part of maintenance testing or PdM. Results are often more severe when troubleshooting, which will be covered in the second case study. Fig. 2. Motor Evaluated in Case Study 1 A. Case Study 1: 4160 Volt Induction Machine Evaluation of an open drip proof 300 horsepower, 885 RPM, 4160 Vac, form wound electric motor as part of a predictive maintenance program. Leads are disconnected at the motor and testing performed using the Electrom iTIG (iTIG) and ALL-TEST Pro 5 (ATP5) with the winding temperatures at room temperature, approximately 20oC. TABLE I. LOW VOLTAGE MCA TEST RESULTS (ATP5) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) I/F (percent) Insulation Resistance (1000V) Capacitance Dissipation Factor Test Frequency TABLE II. T1-T2 1.15 43.7 69.5 81.2 -46.8 T1-T3 T2-T3 1.15 1.15 43.8 43.7 69.7 69.5 81.2 81.1 -46.9 -46.8 >999 MegOhms 35.7 nF 1.13% 100 Hz HIGH AND LOW VOLTAGE MCA TESTS (ITIG) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) Q Factor Partial Discharge (pC) Insulation Resistance (1000V corrected to 40oC) High Potential Test Capacitance Capacitance D Factor T1-T2 T1-T3 T2-T3 1.1530 1.1528 1.1526 369.3 369.0 367.9 58.47 58.43 58.26 84.2 84.3 9.93 9.85 9.93 9.89 114,145 97,839 114,145 8,333 MegOhms, 0.03 uAmps 10,300 V, 1.54 uAmps 0.128 nF 0.437 Fig. 1. Surge Comparison at 8,902 Volts A visual inspection of the windings indicated that there was some level of contamination while test results in both the low and high voltage MCA testing indicated that no serious concern had yet presented itself. The unbalanced partial discharge tests identified in Table II may be an early indicator. However, no other tests performed indicated that there were insulation degradation issues beyond visible contamination. Other than the insulation resistance tests identified in Tables I and II, all other tests are comparative between phases or can be compared to similar machines. Small unbalances between phases are normally due to the rotor being present with specific data patterns identifying faults regardless of the unbalance, such as found in Case Study 2. B. Case Study 2: 13.8 kV Synchronous Machine Evaluation of a 4500 horsepower, 13.8kV, 1800 RPM synchronous machine due to degradation over time was performed using the Amprobe, ATP5 and iTIG systems. Visual inspections had identified degradation of both the stator and rotating fields due to contamination and corona effects. It was determined that the high voltage tests would be performed at the same value as tests performed a year prior. TABLE III. LOW VOLTAGE MCA TEST RESULTS ON STATOR (ATP5) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) I/F (percent) Insulation Resistance (1000V) Capacitance Dissipation Factor Test Frequency T1-T2 0.718 67.8 108 78.2 -46.4 T1-T3 T2-T3 0.771 0.770 62.7 54.2 99.7 86.3 77.7 78.6 -46.6 -47.2 >999 MegOhms 76.9 nF 1.12% 100 Hz ©2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted components of the work in other works. TABLE IV. HIGH AND LOW VOLTAGE MCA TESTS STATOR (ITIG) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) Q Factor Partial Discharge (pC) Insulation Resistance (1000V corrected to 40oC) High Potential Test Capacitance Capacitance D Factor T1-T2 T1-T3 T2-T3 0.7195 0.7186 0.7204 519.2 437.7 437.7 81.23 68.77 76.42 79.4 80.8 79.9 5.35 6.19 5.62 21,742 10,871 8153 25000 MegOhms, 0.01 uAmps 0.62 uAmps at 11,000 V 0.051 -0.701 Fig. 3. Surge Comparison at 11,000 Volts Capacitance 170 nF Dissipation Factor 1.38% Test Frequency 100 Hz This change in results between Tables V and III is indicative of issues with the rotor. As a result, additional rotor tests were performed and compared. The unbalance in PD tests between phases also indicated additional degradation of the stator windings, requiring continued monitoring. TABLE VI. LOW VOLTAGE MCA TEST RESULTS ON ROTOR COMPARISON BETWEEN PRESENT AND 4 MONTHS PRIOR (ATP5) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) I/F (percent) Insulation Resistance (500V) Capacitance Dissipation Factor Test Frequency Present 0.171 42.0 33.4 70.9 -41.2 727 MOhms 9.60 nF 1.12% 100 Hz Prior 0.153 45.8 72.9 63.4 -39.1 >999 MOhms 9.80 nF 1.23% 100 Hz Difference 0.018 3.8 39.5 7.5 2.1 Reduced 0.2 0.11 N/A As found in Table VI, all of the circuit values changed including the insulation to ground test results. A polarization index curve was performed in order to evaluate the condition of the rotor to ground insulation. It was determined, due to contamination, and the significant changes in low voltage MCA results, that high voltage MCA would be dangerous as it could fail the fragile insulation system and eliminate the machine owner’s ability to bring the machine online. The unbalance shown in both of the MCA methods, including the surge test waveforms, was determined to be due to the rotor, even though the rotor circuit was disconnected for testing purposes. Comparison to other machines indicated that when set up this way, the stator windings indicated that they were balanced. The rotor had been tested four months previously with MCA only, allowing a comparison. TABLE V. The insulation resistance profile identified in Fig. 4 indicates contamination and some possible aging of the rotor winding insulation to ground, as there are capacitive discharges across the full time of the test being performed. Fig. 5 identifies that the discharges have become far more severe during the four-month period. This indicates that the rotor insulation system has rapidly degraded during the four-month period. Fig. 4. Insulation Resistance Profile 4 Months Earlier LOW VOLTAGE MCA TEST RESULTS ON STATOR 4 MONTHS PRIOR (ATP5) Resistance (Ohms) Impedance (Ohms) Inductance (mH) Phase Angle (degrees) I/F (percent) Insulation Resistance (1000V) T1-T2 0.726 55.4 88.2 78.7 -47.1 T1-T3 T2-T3 0.727 0.724 54.3 54.7 86.4 87.1 76.8 76.6 -46.2 -46.0 >999 MegOhms ©2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted components of the work in other works. Fig. 5. Present Insulation Resistance Profile potential tests, surge comparison tests, and partial discharge tests, were dramatically dissimilar from the low voltage MCA test regimen. As a result, trending between the technologies is not possible. Trending between the low voltage tests of both machines, from the standpoint of phase to phase comparisons, is possible. However, it was noted that the inductance and impedance readings were dissimilar between machines even though confirmation of the calibration of both machines was sought following the identification of these differences. In order to bring the high voltage MCA device up to the voltage required for 13.8 kV, if the test was performed properly, would have required the addition of a second power supply. No such requirements were needed for low voltage MCA. Both technologies successfully identified the same conditions on all of the machines tested, including those in the case studies. REFERENCES 1. When the results of the stator and rotor tests are reviewed, while there are conditions in the stator, it appears that a developing short and insulation to ground problems in the rotor are the primary issues. The motor was also seeing a vibration issue that appeared to be from misalignment and related causes, but the conditions of the rotor may be contributing to the issues. IV. DISCUSSION In both cases low voltage and high voltage MCA provided similar results. In Case 2, both technologies identified that there was an issue with the machine, including the ability to compare previous to present test results. As the machine had been operating, additional testing was performed on the rotor to see if the issue existed there versus in the stator. The conditions found were significantly different in low voltage MCA such that it was determined that the application of high voltage MCA would most likely put the machine in a condition where it would not operate. 2. 3. 4. 5. IEEE, IEEE Std 43-2013: IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery, Electric Machinery Committee of the IEEE Power Engineering Society, 2013 IEEE, IEEE Std 522-2004: IEEE Guide for Testing Turn Insulation of Form-Wound Stator Coils for Alternating-Current Electric Machines, Electrical Machinery Committee of the IEEE Power Engineering Society, 2004 IEEE, IEEE Std 1415-2006: IEEE Guide for Induction Machinery Maintenance Testing and Failure Analysis, Electrical Machinery Committee of the IEEE Power Engineering Society, 2006 IEEE, IEEE Std 1434-2000: IEEE Guide to the Measurement of Partial Discharges in Rotating Machinery, Electrical Machinery Committee of the IEEE Power Engineering Society, 2000 H. W. Penrose, “Study of Insulation Resistance Profiling Use on Random and Form Wound Machines under 6kV,” Conference Record of the 2012 International Symposium on Electrical Insulation, San Juan, PR, 2012 The study was performed on 42 similar machines at one location with similar results. Both the high voltage and low voltage MCA systems produced similar results with the differences involving the amount of time to perform testing. For the full suite of tests identified with high voltage MCA, the testing took approximately 45 minutes and required a plug in power supply. Low voltage MCA took less than 5 minutes with an internal battery. When coupled with insulation resistance profiling, testing time took approximately 20 minutes total. In both cases, any surge arrestors or power factor correction capacitors had to be removed from the circuit or they would compromise the test results. A majority of the tests were performed at the machines at the request of the machine owner. However, a number of tests were performed from the MCC in which capacitance testing was dropped on both instruments. With the exception of the low voltage tests provided by both instruments, the high voltage tests including the high ©2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted components of the work in other works. ©2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted components of the work in other works.