Property Services Design Standard Volume Three: Electrical

advertisement
Property Services
Design Standard
Volume Three: Electrical Systems
Issue 7 2015
August 2015
RMIT University
Design Standards – Volume Three Electrical Systems
August 2015
Version Control
This document will be updated and re-issues to reflect approved change to content, and is
subject to version control. The version record and status is documented below
Document Change History 1 :
Version
Date
Author
Comments
7.0
31/07/2015
Property Services
Complete review of standards
Owner
The overall responsibility for these standards resides with RMIT University Property Services
Review
This Document is reviewed every two years
1
Printed copies of this document are considered uncontrolled and may not reflect the most recent revision
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 2 of 17
Table of Contents
Introduction
2.
4
1.1
Background
4
1.2
Purpose
4
1.3
Demonstrating Compliance with the Standards
4
Electrical Design Standards
5
2.1
General
5
2.2
Power Supply
6
2.3
Mains, Submains and Sub-circuit Reticulation
7
2.4
Main Switchboards
8
2.5
Mechanical & Electrical Distribution Switchboards
9
2.6
General Purpose Power Wiring, Accessories and Outlets
2.7
Lighting
10
2.8
Emergency Lighting and EXIT Signs
12
2.9
UPS
13
2.10 Preferred Manufacturers
13
3.
Appendix A - Asset Numbering
14
4.
Appendix B - Letter Code Identification
16
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
9
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 3 of 17
1.
Introduction
1.1
Background
This document details the minimum RMIT design requirements for electrical systems. It forms part
of the suite of RMIT Design Standards set out below. All volumes of the standards are available on
the RMIT Property Services Design Standards web page.

Volume One
Introduction

Volume Two
Architecture and Planning

Volume Three
Electrical Systems

Volume Four
Fire Protection Systems

Volume Five
Hydraulic Systems

Volume Six
Mechanical HVAC Systems

Volume Seven
Vertical Transportation Systems

Volume Eight
Building Management Systems

Volume Nine
Electronic Security

Volume Ten
Communications

Volume Eleven
Audio Visual

Volume Twelve
Landscape

Design Standards Checklist
This document should be read in conjunction with Volume One - Introduction, which provides
context on the organisational and governance arrangements that apply to the design and
construction of new facilities and describes the key principles that underpin the requirements of the
Standards:
 Safety
 Reliability
 Accessibility
 Compatibility
 Innovation
 Sustainability
 Student Experience
 Heritage
 Maintainability and
 Life Cycle
Serviceability
 Precinct Wide Solutions
 Modularity and
Standardisation
1.2
Purpose
The purpose of this brief is to set out the minimum requirements for the design of electrical
services. The aim is to achieve the maximum possible consistency and standardisation across the
electrical services systems on the RMIT University campuses.
Any design aspects not specifically addressed by this brief shall be identified by the consultant
during the design process and shall be brought to RMIT University’s attention for resolution.
1.3
Demonstrating Compliance with the Standards
Designers are required to confirm compliance and justify any proposed deviations by completing
the Design Standards Checklist.
All deviations must be approved by RMIT prior to commencing design. Unless a robust justification
is provided for deviations from the Standards, it is unlikely that approval will be given. Design
Standards compliance is achieved through completion of the Design Standards Checklist and
endorsement by RMIT of any proposed non- compliances.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 4 of 17
2.
Electrical Design Standards
2.1
General
2.1.1
2.1.2
2.1.3
2.1.4
2.1.5
2.1.6
2.1.7
2.1.8
2.1.9
2.1.10
2.1.11
2.1.12
2.1.13
2.1.14
2.1.15
2.1.16
2.1.17
2.1.18
2.1.19
2.1.20
An electrical load study is to be conducted and the adequacy of network
infrastructure to provide peak load shall be confirmed with the electrical retailer and
power distributor.
The electrical specification requires high frequency ballasts in fluorescent
luminaires in at least 95% of the useable floor area.
Fluorescent luminaires to be fitted with high frequency ballasts over at least 95% of
the useable floor area
Lighting levels to provide a maintenance illuminance of no greater than 25% above
the recommended values in Table E1 of AS1680.2.3 for 95% of the useable area at
the working plane.
Energy sub metering is connected to the BMS for all mechanical switch boards,
main cooling source, main heating source, air systems and water systems.
Shared or precinct wide energy systems have been adopted.
The electrical supply originates from Supply Authority sub-stations distributed
around the campus.
Substations should be located on grade as opposed to basement or elevated
locations.
RMIT requires that an arc flash study be carried out for each switchboard in every
system.
Provide PPE guidance information and notices at each switchboard location.
Main Switchboards are located on grade as opposed to basement or elevated
locations.
Main Switchboards are located in dedicated air conditioned plant rooms separate
from other plant and equipment. Equipment such as power factor correction can
occupy the same space.
Ancillary equipment such as UPS and generators are housed separately from Main
Switchboards.
Dust entry to Main Switchboards is minimised.
The design shall incorporate adequate enclosed space for:
 Supply Authority metering equipment
 University BAS connections
 Termination of incoming and outgoing circuits University kWh check metering
and for nominated outgoing sub-mains
 Future extensions or additions
 Surge protection devices
 Connection of power factor correction equipment
 Challenger security and access control equipment
 CCTV equipment
Switchboards are located in dedicated lockable ventilated rooms or closets
separate from other plant and equipment. Equipment such as lighting controllers
can occupy the same space. Access is provided from a public corridor or similar
accessible space, not an office or teaching space.
Switchboards supplying a particular floor/level are located on that floor/level.
Switchboards supplying a particular building or substructure shall be located in that
building or substructure.
Mechanical switchboards are located in plant rooms (refer also to HVAC section).
Generators are located in dedicated lockable ventilated rooms separate from other
plant and equipment. Equipment such as bulk fuel tanks must not occupy the same
space.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 5 of 17
2.1.21
2.1.22
2.1.23
2.1.24
2.1.25
2.1.26
2.1.27
2.1.28
2.1.29
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.2.7
2.2.8
2.2.9
2.2.10
Generators are located on grade.
Fuel tanks shall be above ground types and shall be suitably bunded.
Exhaust and ventilation cooling complete with sound attenuation, with due regard to
AS 1668, shall be provided.
UPS units greater than 30 kVA shall be located in dedicated lockable conditioned
rooms separate from other plant and equipment. Equipment such as battery banks
must not occupy the same space.
UPS equipment shall be hardwired and not connected via a standard GPO.
Power factor correction equipment shall generally be located as close as possible
to the main switchboard.
Heat dissipation to Power factor correction equipment shall be provided.
An LED luminaire and power point shall be provided in every switchboard, riser,
data, telephone and AV cupboard.
No shunt trip on power emergency shut off. Button key re- set only.
Power Supply
Substation installed transformer capacity shall be designed to accommodate at
least 125% of the anticipated building maximum demand.
Substation space: shall be designed to accommodate one additional transformer
and associated switchgear.
Spare capacity shall be included in the Main Switchboard and cable design as
follows:
 Electrical load spare capacity 25%
 Minimum physical space spare capacity 25% on both sides
 Equipped Spares: 2 x 100 A
 Equipped Spares: 1 x 200 A.
Note: Spare circuit space: minimum 20% number of circuits on every busbar
section.
Note that at the City campus and Bundoora campus, connection to and interaction
with the local cogeneration and tri-generation systems must be taken into account
in the design of new projects.
Main switchboards shall have the capacity to withstand the prospective fault level at
the point of supply when the corresponding substations are fitted out with
transformers at their possible maximum capacity, or as advised by the Supply
Authority.
Spare capacity shall be included in the Distribution Switchboard design as follows:
 Electrical load spare capacity;
 Base building 50%
 Tenancy fit outs 25%
 Minimum physical space spare capacity 25%
Generators shall be gas fired.
Generators shall be installed with at least 30% spare capacity.
Generator controllers shall be equipped with a high level interface connected to the
RMIT BAS system and be fully compliant with the published RMIT Standard.
Acoustic attenuation shall be fitted to generators.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 6 of 17
2.2.11
2.3
2.3.1
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7
2.3.8
2.3.9
2.3.10
2.3.11
2.3.12
2.3.13
2.3.14
2.3.15
2.3.16
2.3.17
Provide for the following using multifunction meters with TCP/IP communications
port:
 Separate metering for all mains and sub-mains circuits, and loads > 50 kVA.
 Separate metering for mechanical plant, lifts, power, and lighting circuits.
 Removable busbar links for all CT’s.
 Test links for all CT secondary terminals
 A set of fused potential terminals is to be provided for the connection of portable
test and recording equipment.
 Meters and BAS software shall be set up for presentation of time/consumption
graphs and ongoing storage of data as part of each project. Refer to BMS
Standard for details.
Mains, Submains and Sub-circuit Reticulation
Consumer mains shall be designed to accommodate 125% of the anticipated
maximum demand as determined in consultation with RMIT and the Supply
Authority.
Computation of the anticipated voltage drop shall be based on the 125% of the
anticipated maximum demand for each circuit.
Circuit breakers are preferred to fuse switches and motor start fuses.
All cables shall be stranded copper conductor types.
General power circuits shall be wired in not less than 2.5 mm2 TPS cable (black
colour).
General light circuits shall be wired in not less than 2.5 mm2 TPS cable (white
colour).
Cables shall be concealed.
Cables installed as surface wiring shall be enclosed in PVC mini ducting in lieu of
PVC conduit subject to approval. The duct shall be fixed to the wall with suitable
fixings, not double sided adhesive tape.
Cables chased into masonry shall be installed in suitable PVC conduit.
Busducts may be used for horizontal runs only.
Vertical main or submain busduct runs are not included.
Busbar Tee-off boxes shall be provided with circuit breakers or links. Tee-off boxes
shall be of an RMIT approved type.
Construction of busbar tee off boxes shall be arranged for access of all equipment
from the front.
Mains sensing relays and contacts shall be provided and connected to the BAS.
Design shall allow for no more than ten computers on a single circuit.
Design shall allow for no more than twelve double T5 fittings on a single circuit.
Design shall allow for a dedicated circuit for AV equipment in teaching spaces.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 7 of 17
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
2.4.6
2.4.7
2.4.8
2.4.9
2.4.10
2.4.11
2.4.12
2.4.13
2.4.14
2.4.15
2.4.16
2.4.17
2.4.18
Main Switchboards
As a minimum main switchboard shall be provided with a degree of protection of
IP44, as per AS1939 and shall be of smoke proof construction.
Main switchboards shall be:
 800A or more back connected, free standing
 Less than 800A front connected, may be wall mounted
 No less than Form 3(b)
Mechanical services are to be separated from the other light and power supplies.
Power supplies for equipment of sensitive nature, such as Computers and audiovisual equipment shall be provided with dedicated supplies separated from
mechanical services supplies.
Protection equipment shall be of CB, MCCB or ACB type, to be selected as
appropriate for the magnitude of the corresponding power supply.
Supply Authority metering shall be integrated with the main switchboard.
Provide Infra-Red transparent clear shrouds and barriers to permit thermo graphic
scanning without the need to remove shrouds and barriers.
The main switchboard shall incorporate separate check metering and for selected
major power supplies, lighting and power circuits.
The design of the main switchboard shall provide for the RMIT BAS system to be
safely integrated in the board in a separate enclosure to monitor and control
designated supplies and status signals.
The main switchboard shall be provided with surge protection with local
operation/health indication and replaceable cartridges.
ACB’s and any approved CFS units shall be withdrawable.
Engraved Traffolyte labels shall be installed on the front door of protection devices
enclosures and shall indicate the capacity of the unit and the protection settings or
rating of installed fuse cartridges.
Labels shall also be installed adjacent to the load terminals.
Lift-off panels shall be labelled to identify their location on the main switchboard.
Labels shall be provided for Essential Supplies, which are:
 Fire protection equipment
 Fire indicating panel
 Passenger elevators
 Circuits supplying computer LAN, WAN or computer equipment
 Circuits controlling emergency luminaires
 Circuits controlling security and building access control equipment
A separate, wall-mounted, steel, lockable cabinet, keyed to a CL001 key shall be
provided in a suitable location in each main switchboard room.
The cabinet shall be labelled “SPARE FUSES AND EQUIPMENT” and shall contain
spare parts, tools, and a full set of spare HRC fuse cartridges for all CFS units
installed on the main switchboard.
A laminated and framed copy of the schematic wiring drawing, shall be prominently
displayed in a suitable enclosure inside the main switch room.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 8 of 17
2.4.19
2.4.20
2.4.21
2.4.22
2.4.23
2.5
2.5.1
2.5.2
2.5.3
2.5.4
2.5.5
2.5.6
2.5.7
2.5.8
2.6
2.6.1
2.6.2
2.6.3
A schematic wiring diagram of the complete as-constructed switchboard shall be
supplied. The wiring diagram shall include, but shall not be limited to:
 Circuit breaker capacities and trip settings
 Fuse sizes
 Capacity of protection units installed
 Size and capacity of installed busbar
 Capacity of incoming supply
 Capacity of outgoing circuits
 Destination of sub-main supplies
 Size of main earth conductor and location of main earth electrode
 Type test rating of the main switchboard.
Supply both design and workshop soft copies (pdf and CAD) of the switchboard
drawings.
Where required, control equipment shall:
 Be located and mounted in dedicated control cubicles / panels
 Generally be located in the vicinity of corresponding switchboards on the same
level as the equipment being controlled.
Control panels shall be sized as required for 100% spare capacity (panel should be
50% full).
For switchboards with multiple supplies a bus tie arrangement is to be included.
Mechanical & Electrical Distribution Switchboards
Mechanical and electrical distribution switchboards shall be provided with a main
switch mounted separate to the distribution and controls chassis.
Switchboards shall be easily expandable to permit another chassis to be added.
Escutcheon panels on switchboards shall be hinged.
Switchboard doors shall be fitted with dust and smoke proof seals.
Switchboard enclosures shall be a minimum width of 580mm.
The protective device for electrical distribution switchboards (and load centres)
serving final sub-circuits, shall be, as a minimum, rated at 63A. All upstream and
downstream devices shall discriminate with these protective devices.
Excluding the main switch, there shall be no less than 12No poles in electrical
distribution switchboards.
Mechanical switchboards shall form part of the overall electrical design including
arc flash and fault level studies.
General Purpose Power Wiring, Accessories and Outlets
General purpose power circuits shall be protected by 20A RCD and shall be loaded
to no more than:
 Base building 20%
 Tenancy fit out 80%
 The maximum number of double GPOs per circuit shall be 5 double GPOs for
air-conditioned spaces.
GPO’s to be installed, as a minimum, as follows:
 Office spaces- 1No duo GPO for every 5m²;
 Lecture theatres- 1No double GPO per student chair plus 1No double GPO
every 20 m²;
 Study spaces- 1No double GPO per student chair
 Internal circulation spaces- 1No double GPO every 10 linear meters.
Double power outlet combinations are required: no single power outlets.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 9 of 17
2.6.4
2.6.5
2.6.6
2.6.7
2.6.8
2.6.9
2.6.10
2.6.11
2.6.12
2.6.13
2.6.14
2.6.15
2.6.16
2.6.17
2.6.18
2.6.19
2.6.20
2.7
2.7.1
2.7.2
2.7.3
2.7.4
2.7.5
All outdoor plant area shall be equipped with at least two weather proof GPO’s, one
at the plant and one adjacent to each switchboard.
Lighting sub-circuits shall be protected by RCD and:
 Shall have a rating of 20 Amps
 Shall be limited to a maximum of 2,000 W connected load or 25 lighting points
per 2.5mm² circuit
 Shall retain facility to add further lights to each circuit up to 80% of the capacity
of the circuit breaker controlling each final sub-circuit
 Circuits shall be no less than 2.5 mm² black TPS.
Provide dedicated power sub-circuits for:
 Each item of permanently connected equipment.
 Each 15 A switched socket outlet.
 Circuits shall be no less than 2.5 mm2 white TPS
Combined lighting and power loads in a single circuit are not permitted.
Provide USB charging points based on one per 10 m2 in general foyer and lounge
spaces and as called for on room data sheets. Label “Charging Only”.
USB charging points shall be flush mounted and with cover plates matching the
local GPO’s.
Emergency stop buttons shall be installed for safety control for laboratory power
outlets.
Label emergency stop buttons: “For Emergency Use Only”
Emergency stop buttons shall be latching large Red Mushroom Head types.
RCD’s and ELCB’s shall be installed in the local switchboard and not in the field.
Power to automatic sliding doors at entrance(s) to a building shall be key switch
operated.
Sliding door(s) must remain in an open position during normal hours when Fire
Indicator Panel (FIP) is in alarm mode.
An approved electronic lock and mounting position is required where security
access control systems are installed.
At each light switch, fan switch, equipment power isolator switch and all GPOs
provide identification labels.
Labels shall be installed either at the top of fixing screws or on the face plate of
removable front plates.
Labels shall be engraved with the DB number and the circuit number of the circuit
relating to the switch and/or GPO. UPS/generator connections shall be identified.
The base colour of the identification labels shall match the colour of the switch
and/or GPO.
Lighting
The design of the lighting zone allows for all individual and enclosed places to be
individually switched. Each switched zone does not exceed 100m2 for 95% of
useable floor area.
100% of outdoor spaces meet or exceed the minimum requirements of AS1158 for
illuminance levels. All externally lit spaces use a light source with efficacy of at least
50 lumens/watt and are connected to a daylight sensor.
Daylight shall maximise in internal spaces to reduce the required lighting load and
to assist in the achievement of Green Star points.
RMIT requires all project lighting system to achieve an overall building or project
lighting energy density of 8 watts / m² or 20% less than the requirements of Part J
of the current NCC whichever is the lesser.
All luminaires shall have photometric and thermal performance testing to be done
by a NATA registered laboratory or other approved laboratory.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 10 of 17
2.7.6
2.7.7
2.7.8
2.7.9
2.7.10
2.7.11
2.7.12
2.7.13
2.7.14
2.7.15
2.7.16
2.7.17
2.7.18
2.7.19
2.7.20
2.7.21
2.7.22
2.7.23
2.7.24
2.7.25
2.7.26
Solid state lighting is preferred. Metal halide and T5 fluorescent lamps will be
considered.
Incandescent, compact fluorescent, mercury vapour and high pressure sodium
lamps are not permitted.
All control gear shall be internally corrected to better than 0.9 power factor.
Galvanised Loxins, dynabolts or approved metal expansion devices shall be used
for securing light fittings to concrete ceilings. Wooden or plastic plugs will not be
accepted.
The minimum number of fixings per light fitting shall be:
 0 to 300 mm wide linear LED or fluorescent light fitting — 2 fixings
 300 mm wide linear LED or fluorescent light fitting — 4 fixings.
Luminaires selected for computer laboratories or office areas shall be the low
brightness type.
All luminaires shall be installed using the plug in method.
Provide uniform lighting levels, measured at a task height of 720mm, with the ratio
of minimum to average being 0.7 or more.
Lighting in toilet areas shall be controlled only by ultrasonic movement sensors
located at strategic locations.
Stair wells shall be provided with two lighting circuits.
One of the stair lighting circuits shall be arranged to operate as a 24 hour circuit (or
as a circuit switched OFF by a movement sensor or a PE cell only where adequate
natural lighting is available.
The other stair lighting circuit shall be controlled by either motion sensors or PE
cell.
All stair lighting shall be readily accessible by maintenance staff without requiring
scaffolding or similar access equipment.
External security lighting shall be provided at all doors, entrances and exits.
Security lighting shall be PE Cell controlled. External lighting shall:
 Provide safe circulation space around the building.
 Have a manual override switch installed in switchboard
 External lighting designs shall comply with the obtrusive light spill standard AS
4282
 Cables shall be suspended from catenary cables and not ceilings.
Lighting control systems shall be Dynalite or the installed BAS linked existing
system either:
 Option 1 - Dali ballasts fitted to all light fittings; lighting control system for full
monitoring of fitting status for maintenance; daylight harvesting and light
depreciation compensation; ultrasonic movement sensors for presence
detection.
 Option 2 - Dali ballasts without connection to a lighting control system; daylight
harvesting and light depreciation compensation; ultrasonic movement sensors
for presence detection.
 Option 3 - Controls to provide daylight and light depreciation compensation.
Movement sensors also to be connected.
 Option 4 - 240 Volt controls wiring with sensors in fittings for daylight
compensation only. Acoustic / movement sensors also to be connected.
The designer shall investigate and propose the lighting control system most
appropriate for the project.
Group Light fittings located near windows onto a separately switched circuit.
In all other areas, control shall be circuited to alternate luminaires for 50/100%
switching.
Provide Security lighting at corridors and intersections.
Security lights shall be spaced at least every 25 m.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 11 of 17
2.7.27
2.7.28
2.7.29
2.7.30
2.7.31
2.7.32
2.7.33
2.7.34
2.7.35
2.7.36
2.7.37
2.7.38
2.7.39
2.7.40
2.7.41
2.7.42
2.8
2.8.1
2.8.2
2.8.3
2.8.4
2.8.5
2.8.6
2.8.7
2.8.8
2.8.9
The number of light fittings on security lighting shall be no more than 5% of the total
number of light fittings.
Plant rooms, corridors, foyers, lobbies and other service areas control shall be
circuited to alternate luminaires.
Stair lighting: provide separate circuits for luminaires located on each main landing
and luminaires located on each intermediate landing.
Provide time switching, manual switching and occupant sensor switching for office
areas, lecture theatres, libraries and classrooms.
In single offices, meeting rooms and related areas arrange lighting controls so that
lighting is manually switched ON, but automatically switched OFF.
Rooms and areas anticipated to be occupied infrequently; lighting shall be
controlled by lighting motion sensors.
Where four or more switches are located adjacent to each other, they shall be
ganged under a common stainless steel plate.
Lighting motion sensors shall be provided with an isolator/lighting switch located
next to the main entry door to the room.
Ceiling pull cord switches are not acceptable.
All external security and street lighting shall be controlled by individual photo cell
switching.
By-pass switches shall be provided on all PE controlled external and street light
circuits.
Each street light pole shall be separately protected with local means of isolation.
Light switches in tunnels shall be fitted with continuously operating amber coloured
indicators.
Light switches in tunnels and all service areas shall be the splash proof protected
type.
Where trunking with multiple lights are specified Dynabolts or similar must be used
to fix to concrete slabs.
Light switches to be stainless steel push button control type.
Emergency Lighting and EXIT Signs
Where only part of a floor area is affected by the project works, the design of the
emergency lighting system shall include the entire floor area for compliance.
Particular emphasis shall be the path of escape to fire escape stairs, within the
stairs and to the final building exit.
Cabled versions are preferred.
The system shall be integrated into the campus wide network and set up for remote
automatic monitoring and statutory testing and reporting.
Malfunction both in normal and emergency modes of operation shall be reported
automatically.
This system shall be set up to display and print faults, test results, malfunctions,
with reference to dates, time and address of the relevant luminaires.
System shall be adjustable when new luminaires are added or deleted.
The system controller shall be interfaced with the Lantronics monitoring system.
Computerised monitoring shall be carried out via a Lantronix system controller back
to the centralized monitoring office located in:
 City Campus Building 14, Level 3
 Bundoora Campus Building 202, Level 1, Room 20
 Brunswick Campus Building 512, Level 1, Room 101
A datapoint and double power point is to be installed in the main electrical
switchboard of the building.
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 12 of 17
2.8.10
2.8.11
2.8.12
2.8.13
2.8.14
2.8.15
2.8.16
2.9
2.9.1
2.9.2
2.9.3
2.9.4
2.10
2.10.1
2.10.2
2.10.3
2.10.4
2.10.5
Multi-level buildings shall have a communications cable run as a backbone spine to
one centralized Lantronix unit with an individual area controller located on each
level.
The Lantronix system shall incorporate its own battery on mains failure.
Emergency exit signs shall be of the pictograph type and illuminated by an LED
light source for both emergency and 240 V operation.
Emergency luminaires shall not be used for normal lighting.
All exit signs shall be installed at a minimum of 2200 mm above floor level to the
bottom of the luminaires.
Exit sign luminaires shall be circuited separately from the local distribution board. A
lockable 20A switch on the distribution switchboard shall be provided for the normal
control of these exit signs.
Protected type emergency luminaires shall be provided in all toilets.
UPS
UPS equipment shall only be installed when specifically required by RMIT in
writing.
Prepare and issue for approval a design report outlining:
 Number and size of the UPS
 Location of each UPS unit
 Location of each battery unit
 UPS reticulation system
 Testing strategy proposed
 Proposed Equipment type and list of manufacturers suitable for the project.
All BAS equipment, remote Input/Output panels and field controllers shall be
connected to a UPS.
Each UPS > 30 kVA shall be equipped with a high level interface connected to the
BAS.
Preferred Manufacturers
ACB’s and any approved CFS units shall be Nilsen (ACB’s D-PRO series).
Emergency luminaires and exit signs shall be the LEGRAND Minitronics Monitored
Commander or Axiom System type.
Major equipment items shall be of one of the following preferred manufacturers:
 Schneider
 Terasaki
 Sprecher and Schuh
 Siemens
The Preferred manufacturer of Automatic doors is Dorma Automatics Pty Ltd.
Cables shall be of one of the preferred manufacturers:
 Olex
 Prismium
 Pirelli
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 13 of 17
Appendix A - Asset Numbering
3.
ANT
ACC
ACR
ACU
ADR
AHU
ALC
ARY
BCC
BPD
BWU
CAR
CCP
CON
CTR
CWP
CWV
DHP
DHU
EAF
ECO
EFH
FAD
FCB
FCH
FCU
FCW
FCX
FHD
FHR
FIP
FRB
FRD
FSP
FXT
GDX
HCU
HEE
HEX
HUM
HWB
Acid Neutralising Tank
Air Cooled Refrigeration Condensing Unit
Air Compressor
Self- contained packaged air conditioned unit,
window units with or without condenser
Aid Drier
Air Handling Unit, including duct connected fan
coil units
Air Cool Liquid Chiller
Automatic Water Refill Unit
BAS Control Cubicle
Backflow Prevention Device
Boiling Water Unit
Compressed Air Receiver
Condenser Water Pump
Evaporative, air or water cooled refrigeration
Condenser
Cooling Tower
Chilled Water Pump
Open or closed Chilled Water expansion tank
or vessel
Domestic Hot Water Pump
Domestic Hot Water Unit, gas, oil or electric
fired storage or instantaneous Unit
Exhaust Fan
Evaporative Cooler
Electric Fan Heater
Fire Damper
Fume Cupboard
Fan Convector
Fan Coli Unit- Non duct connected
Indoor wall, floor, or ceiling mounted
component, refrigeration provided by chilled
water
Indoor wall, floor, or ceiling mounted
component, refrigeration provided by direct
expansion
Fire Hydrant
Fire Hose Reel
Fire Indicator Panel
Fire Blanket
Fire Rated Door
Fire Services Pump
Fire Extinguisher
Gas Detecting System
Heating and Cooling Unit
Heating Element
Heat Exchanger
Duct or Space Humidifier
Heating, Hot Water, gas or electric fired boiler
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 14 of 17
HWP
HWV
MCD
MCH
MSS
OAF
RAF
RCR
SAF
SCD
VPP
WAF
WCCC
WLC
WMU
Heating Hot Water Pump
Heating Hot Water open or closed expansion
tank or vessel
Motorised Control Damper (Only if not a BAS
field device)
Modular Chiller
Mechanical Services Switchboard
Outdoor Air Fan
Return Air Fan
Refrigeration Compressor
Supply Air Fan
Smoke Control Damper
Vacuum Pump
Warm Air Furnace (ducted or non- ducted)
Water Cooled Condensing Unit
Water Cooled Liquid Chiller
Water Make up Unit
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Property Services
Document: Design Standards – Volume Three
Electrical Systems
Author: Property Services
Approved :EDPS
Page 15 of 17
Appendix B - Letter Code Identification
4.
LETTER CODE FOR IDENTIFICATION OF INSTRUMENT FUNCTION
1
2
3
4
5
Letter
First letter or initiated variable
Modifier
User’s Choice (final modifier)
A
Analysis
Succeeding letter (display or output
function)
Alarm
B
Burner, Flame
State or Status Display
C
Control
D
Density
E
All electrical variables
F
Flow Rate
G
Gauging position or length
Glass
H
Manually initiated (hand) operated
High (alarm)
Difference
Sensing Element
Ratio
I
Indicating
J
Power
K
Time or time program
Barrier
L
Level
Low (alarm)
M
Moisture or humidity
User’s choice
N
User’s choice
choice
O
User’s choice
User’s choice
P
Pressure or vacuum
Q
R
Scan
User’s choice
Test point connection
Integrating or
totalise
Radiation
Cooling
Integrating or summating
Recording
Heating
LETTER CODE FOR IDENTIFICATION OF INSTRUMENT FUNCTION
1
2
3
4
5
Letter
First letter or initiated variable
Modifier
User’s Choice (final modifier)
S
Speed or frequency
Succeeding letter (display or output
function)
Switching and/ or status
T
Temperature
Transmitting
U
Multivariable
Multifunctional unit
V
Vibration
Valve, damper, louver, acting
element, unspecified connecting or
final control element.
W
Weight or force
Well temperature sensor
X
Cathode ray tube etc.
Y
Unclassified variables e.g. TV
camera
User’s choice
Computing relay, relay
Z
Position
Emergency or safety acting
Defined User’s Choice
i.e.
C
Chiller
N
Pump or fan
Y
Fire
NC- Fan control start/ stop command
NB- Fan status
FV- Air flow valve/ damper
OC- Packaged Unit
TVH- temperature control valve (heating)
TVC- temperature control valve (cooling)
Status: FINAL
Issue: 7.0
Save Date: 18/08/2015
Resources/Property
Services
Document: RMIT Design Standard Vol 3
Electrical Systems Issue 7.docx
Author: Property Services
Approved :EDPS
Page 17 of 17
Download