Document

advertisement
SOMALI ENERGY TRANSFORMATION (SET) PROJECT
Solar PV installation BOQ
MARCH 2016
LOT 1
Health Centers
1. Godmo Biyo Cas MCH- Sanaag Region
2. Kalabyth Health Center- Sool Region.
3. Deg Agabar MCH- Maroji Jeex Region.
4. Garadag MCH- Sanaag Region.
5. Suuqsade Health Center- Sahil Region
1. Godmo Biyo Cas MCH- Sanaag Region
Equipment Details
Description
Units
125W multicrystalline solar panel,12VDC
No
800W, 12V Effecto inverter,transformer based
No
200Ah,12V Sealed maintenance-free solar batteries
No
50Amp PWM charge controller, 12/24VDC
No
Solar mounting structure
No
Battery cabinet
No
18W energy saving bulbs
No
Accessories & BOS
Lot
1.5sqmm TFE Cable
Mtrs
2.5sqmm TFE Cable
Mtrs
Internal wiring sundries
Lot
Installation labour
Lot
Total
Qty
Unit
Cost
Total
Cost
4
1
2
1
1
1
24
1
200
50
1
1
2. Kalabyth Health Center- Sool Region.
Equipment Details
Description
Units
250W multicrystalline solar panel, 24VDC
No
1600W, 24V Effecto inverter
No
200Ah,12V Sealed maintenance-free solar battery
No
50Amp OPTI MPPT charge controller, 12/24VDC
No
Solar mounting structure
No
18W energy saving bulbs
No
Accessories & BOS
Lot
Qty
Unit
Cost
Total
Cost
10
1
10
1
1
90
1
1
1.5sqmm TFE Cable
2.5sqmm TFE Cable
2.5sqmm 2-core armored Cable
Internal wiring sundries
Installation labour
Total
Mtrs
Mtrs
Mtrs
Lot
Lot
800
400
300
1
1
3. Deg Agabar MCH- Maroji Jeex Region.
Equipment Details
Description
Units
125W multicrystalline solar panel,12VDC
No
800W, 12V Effecto inverter Transformer based
No
200Ah,12V Sealed maintenance-free solar battery
No
45Amp Steca charge controller, 12/24VDC
No
Solar mounting structure
No
Battery cabinet
No
18W energy saving bulbs
No
Accessories & Balance of system
Lot
1.5sqmm TFE Cable
Mtrs
2.5sqmm TFE Cable
Mtrs
Internal wiring sundries
Lot
Installation labour
Total
Qty
Unit
Cost
Total
Cost
Unit
Cost
Total
Cost
4
1
2
1
1
1
24
1
200
50
1
1
4. Garadag MCH- Sanaag Region.
Equipment Details
Description
Units
125W multicrystalline solar panel,12VDC
No
800W, 12V Effecto inverter, transformer based
No
200Ah,12V Sealed maintenance-free solar battery
No
45Amp Steca charge controller, 12/24VDC
No
Solar mounting structure
No
Battery cabinet
No
18W energy saving bulbs
No
Accessories & Balance of system
Lot
1.5sqmm TFE Cable
Mtrs
2.5sqmm TFE Cable
Mtrs
Internal wiring sundries
Lot
Installation labour
Total
Qty
4
1
2
1
1
1
24
1
200
50
1
1
2
5. Suuqsade Health Center- Sahil Region
Equipment Details for Suuqsade Health Centre
Description
125W multicrystalline solar panel,12VDC
200Ah,12V Sealed maintenance-free solar
battery
45Amp Steca charge controller, 12/24VDC
Solar mounting structure
Battery cabinet
18W energy saving bulbs
Accessories & Balance of system
1.5sqmm TFE Cable
2.5sqmm TFE Cable
Internal wiring sundries
Installation labour
Total
Units
No
No
No
No
No
No
Lot
Mtrs
Mtrs
Lot
Lot
Qty
Unit
Cost
Total
Cost
4
4
2
1
1
1
24
1
200
50
1
3
1. EQUIPMENT TECHNICAL SPECIFICATIONS
1.1 Schools and MCHs Inverter/Charger
(i.e. Inverters with Built-in AC Battery Chargers)
Rated Continuous Output power
- specify
Surge Power Capability
- 200% of rated continuous
Power
Peak Efficiency (Minimum)
- 85%
Frequency
- 50Hz
Nominal Input voltage Output
specify
Voltage Range Output
- 220 - 240V AC (RMS)
Voltage Regulation
- +/- 5%
Output wave form
- Pure Sine wave
Battery low shut down voltage Protection
- specify
(electrical)
Power factor capability Charging algorithm of
- Overload and short circuit
charger
Charger input voltage range
- Low battery disconnect
Minimum rated Charging Current
specify
Guarantee
- 3 years minimum
a) High Frequency Transformer-less Inverter is NOT acceptable.
b) Only Pure Sine-wave output is acceptable. Modified sine wave output wave form is
NOT acceptable
1.1 Solar Charger Controller
Main features
Series or Shunt type, constant-voltage, pulse width
modulation (PWM) charging, with battery type
(sealed/gel and flooded lead acid) selection provision
and temperature compensation. MPPT acceptable
Nominal Voltage
- specify
Rated solar charging current
- specify
Earthing
- Negative earth
Metering
- Digital metering for currents and voltages
Operating temperature
- -40 to + 60o C
Protection
- Reversed polarity protection
- Overload and short circuit protection
- Lightning and transients surge protection
- Night reverse current protection (blocking diode or
equivalent.)
Self- Consumption
- 0.5% (Maximum) of rated current
Status Indicators (minimum)
Charging and low battery visual indicators
Guarantee
- 3 years minimum
1.2 Solar Batteries
Rated capacity
- minimum capacity of 100Ah.
Battery Type
- specify.
Plate type
- Flat plate or Tubular acceptable.
4
Electrolyte
Nominal Voltage
Casing material
Warranty
1.3 Solar Photovoltaic Modules
Module Type:
- specify.
- specify.
-Supply may be in 12V or 24V mono blocks.
Self-discharge per month - 6%
maximum Cycle Life - 1,500 cycles at 20% daily depth
of discharge
- Polypropylene or similar translucent/transparent case or
equivalent
- 3 years
- High efficiency crystalline silicon modules (mono
or Poly crystalline) or equivalent
- please specify
- specify
- specify
Voltage at maximum
Open circuit Voltage (Minimum
power minimum Power rating:)
Warranted
- specify
Number of cells per module
Maximum system voltage:
Guarantee:
- 20 Years minimum
1.4 Electrical Fittings, Switchgear and Accessories
Electrical switchgear (such as switches, sockets, consumer units, fuses etc.) must be high
quality certified to the relevant Kenyan (KS), IEC, British (BS) or equivalent standard. Proof
of such certification and origin may be requested.
1.5 Installation Hardware
a) Mounting structure: The solar modules shall be mounted on structures fabricated
using Iron or Aluminum, strong enough to withstand windstorms of 100km/hr. and
be painted to reduce corrosion. Fasteners and other installation accessories (screws,
bolts, etc.) should be galvanized or stainless steel. The structures when mounted shall
have the modules tilted at an appropriate angle from the horizontal plane and the space
between them and the roof/ground shall be at least 6 inches.
b) Battery box/rack: The solar batteries (Accumulators) shall be placed in wooden boxes
and stacked on racks fabricated from steel and painted to reduce corrosion.
c) Cabling: The works shall be carried out in cable routes and therefore the wiring shall
be as per standards of existing cable routing or better. Cables and wires shall be of
the correct size and quality to carry the minimum requisite current and appropriate
voltage drop, laid neatly, adequately fixed, and appropriately terminated.
d) Earthing: The array structure of the PhotoVoltaic yard shall be grounded using
adequate number of earthing kits. All metal casing / shielding shall be thoroughly
grounded to ensure safety of the Solar Photovoltaic power system. Earth resistance
readings must be measured by a qualified person and submitted. Resistance values
shall conform to IEE regulations.
e) Lightning: The system shall be provided with lightning & over voltage protection.
The main aim in this protection shall be to reduce the over voltage to a tolerable value
before it reaches the PV or other sub system components. The source of over voltage
5
can be lightning, atmosphere disturbances etc. Metal oxide variastors shall be
provided inside the Array Junction Boxes. In addition suitable MOV‟s (Metal Oxide
Varistors) also shall be provided in the Inverter to protect the inverter from over
voltage.
f) Installation: The installation will be done in conformity with relevant Kenyan (KS),
IEC, British (BS) or equivalent.
g) Testing and Commissioning: After the completion of the works, the vendor will
perform all necessary tests to ensure the Works comply with the client’s requirements
and proceed to the systems‟ commissioning and handing over to the client.
h) Preferred origin of equipment should be EU and ACP countries
System outline
Solar Panels
Solar Inverter
Battery bank
Charge Controller
Loads/Consumer units
6
Download