5 4 3 2 0 1/2" 1" 2" GENERAL NOTES D Proposed New Jones HS NIC ALL VISUAL FIRE ALARM DEVICES TO BE FURNISHED WITH FIELD ADJUSTABLE SETTINGS, INITIALLY SET AT VALUES AS INDICATED ADJUST SETTINGS BASED ON FIELD TESTING AS REQUIRED. 2. ALL ELEVATOR POWER, COMMUNICATIONS, AND MISCELLANEOUS. SYSTEMS REQUIREMENTS SHALL BE COORDINATION WITH ELEVATOR SHOP DRAWINGS. AT&T SERVICE ENTRANCE: (2) 4"C's FOR SERVICE ENTRANCE CABLES. FURNISHED AND INSTALLED BY SERVICE PROVIDER. PROVIDE INNER DUCT AND PULL STRING. CABLES SHALL BE ROUTED TO DEMARCATION POINT LOCATED IN 3RD FLOOR MDF ROOM. (1) SPARE CONDUIT SHALL BE STUBBED INTO TELCO ROOM AND CAPPED FOR FUTURE. 16 PROVIDE (2) #12AWG-3/4"C FROM E-ATS-ELEV-B TO ELEVATOR CONTROLLER. - UTILIZE 2-HOUR RATED CI CABLE IN CONDUIT, WHEN INSTALLED OUTSIDE 2HOUR RATED ENCLOSURE. 2 COMCAST SERVICE ENTRANCE: PROVIDE (1) 3"C. FOR SERVICE ENTRANCE CABLES TO BE INSTALLED BY SERVICE PROVIDER. PROVIDE PULL STRING. CABLE SHALL BE ROUTED IN CONDUIT TO DEMARCATION POINT LOCATED IN 3RD FLOOR MDF ROOM. 18 IT SHAFT #1: LOCATION OF CONDUIT SLEEVES STUB UP TO FIRST FLOOR FOR AT&T AND COMCAST SERVICE ENTRANCE CABLES, AND MISCELLANEOUS LOW VOLTAGE SYSTEMS CABLING SERVING BASEMENT. REFER TO DRAWING E2.11A FOR ROUTING CONTINUATION. ALL CABLING TO BE INSTALLED IN CONDUIT. 3 SMOKE AND HEAT DETECTORS TO BE INSTALLED IN EVERY BEAM POCKET. TYPICAL FOR ALL AREAS WITH OPEN CEILING. 1 3. ALL GENERAL RECEPTACLE AND 120V/1ø, 208V/1ø EQUIPMENT CIRCUITS WITH NO ALPHABETICAL PREFIX EMANATE FROM PANEL 'RPGP-B', U.N.O. 4. ALL 480/3ø AND 277/1ø MECHANICAL EQUIPMENT CIRCUITS DENOTED "MXX" EMANATE FROM PANEL 'PPH-M-B', U.N.O. 5. ALL EMERGENCY EQUIPMENT CIRCUITS DENOTED "EXX" EMANATE FROM PANEL 'E-LP-B', U.N.O. (1)3" AND (1)4" C'S FOR IT(AT&T) AND CATV (COMCAST) SERVICES UP TO THIRD FLOOR MDF ROOM. INSTALL TIGHT TO CEILING BEAMS. 5 MOUNT HEAT DETECTOR WITHIN 2' OF SPRINKLER HEAD. WALL MOUNT WHEN POSSIBLE. 6 LOCATION OF WATER METERS. SEE DETAIL 4 ON SHEET E5.01 FOR GROUNDING REQUIREMENTS. 7 FUSED ELEVATOR DISCONNECT SWITCH WITH AUXILIARY CONTACTS AS MANUFACTURED BY BUSSMANN OR APPROVED EQUAL. FINAL LOCATION SHALL BE COORDINATED WITH ELEVATOR SHOP DRAWINGS PRIOR TO INSTALLATION AND FEEDER CONDUIT ROUTING. ALL 120V/1ø STANDBY POWER EQUIPMENT CIRCUITS DENOTED "S2-XX" EMANATE FROM PANEL 'E-RP-SB-B', U.N.O. ALL COMPUTER CIRCUITS DENOTED "CXX" EMANATE FROM PANEL 'RP-CP-B'. 8. ALL SECURITY CCTV CAMERAS SHALL BE SUSPENDED 1" HIGHER THAN THE BOTTOM OF THE LOWEST STRUCTURAL BEAM LOCATED WITHIN 35FT OF EACH DEVICE. ADJUST EXACT LOCATION AND FIELD OF VIEW FOR EACH CAMERA BASED ON ACTUAL OBSTRUCTIONS IN FIELD SO CAMERAS FIELD OF VIEW IS NOT OBSTRUCTED. 9. 17 FIRE ALARM RETURN RISERS FROM ABOVE. 19 2-HOURS FIRE RATED SOFFIT BY OTHERS FOR EMERGENCY POWER FEEDERS, FIRE ALARM AND MISCELLANEOUS SYSTEMS CONDUIT ROUTING. VERIFY EXACT LOCATION AND ELEVATION WITH ARCHITECTURAL DRAWINGS. 4 ALL 480V/3ø AND 277V/1ø STANDBY POWER EQUIPMENT CIRCUITS DENOTED "S1-XX" EMANATE FROM PANEL 'E-PPH-SBH-B', U.N.O. 7. KEYED NOTES KEYED NOTES 1. 6. 1 21 ALL ELECTRICAL DEVICES, DISCONNECT SWITCHES, JUNCTION AND PULL BOXES LOCATED IN THIS ROOM, RESPECTIVE CONDUIT AND WIRING INSTALLATION SHALL COMPLY WITH CEC REQUIREMENTS FOR INSTALLATION IN AIR HANDLING SPACES. VERIFY EXACT EXTENT OF PLENUM RATED SPACES WITH DIV. 15 DRAWINGS. 8 ELEVATOR CONTROLLER FINAL LOCATION SHALL BE COORDINATED WITH ELEVATOR SHOP DRAWINGS. 9 PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL TO ELEVATOR CAB LIGHT AND FAN. PROVIDE 20A/1P LOCAL DISCONNECT SWITCH. 23 GENERATOR BATTERY CHARGER. ARCHITECT 24 FUEL TANK CONNECTION. 10 25 FIRE ALARM SPEAKER CONNECTION. PROVIDE NOTIFICATION CIRCUIT FROM NEAREST POWER SUPPLY. PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL FOR ELEVATOR INTERCOM SYSTEM. PROVIDE 20A/1P PANEL DISCONNECT SWITCH. 11 12. LOCATE INTERCOM PAGING SPEAKERS IN STAIRWELLS ON EVERY LANDING. 700 South State Street Chicago, IL 60605 D 22 UNDERGROUND CONCRETE-ENCASED FEEDER. REFER TO RISER DIAGRAM DRAWING. E4.04. 10. IN FINISHED AREAS CAMERAS SHALL BE CEILING MOUNTED. 11. SEE ENLARGED ELECTRICAL PLANS SHEET E7.00 FOR ELECTRICAL EQUIPMENT (PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) LOCATED IN ELECTRICAL ROOMS. William Jones College Preparatory High School 20 ADMINISTRATIVE CONCENTRATOR ENCLOSURE TO BE FED FROM PANEL RP-CP-B. ACE TO SERVE ALL DATA/VOICE OUTLETS IN BASEMENT LEVEL. 26 PROVIDE "PLAIN OLD TELEPHONE SERVICE" (POTS) LINE CONNECTION TO PHONE, INSTALLED BY OTHER, IN ELEVATOR CAB. PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL FOR ELEVATOR SECURITY SYSTEM. PROVIDE 20A/1P PANEL DISCONNECT SWITCH. 12 PROVIDE (3) ADDRESSABLE RELAY MODULES FOR INTERFACE WITH FIRE ALARM SYSTEM FOR THE FOLLOWING FUNCTIONS: - PRIMARY RECALL -ALTERNATE RECALL(SPARE) -NOTIFICATION ON FACP AND FAA (FIREMAN HAT) 28 PROVIDE (1)1"C. WITH WIRING AS REQUIRED BY MANUFACTURER FOR LOW LEVEL FUEL ALARM. TERMINATE CONDUIT IN REMOTE LOW LEVEL FUEL ALARM PANEL LOCATED IN ENGINEER'S OFFICE, ROOM #174. 13 POWER FOR GENERATOR JACKET HEATER AND CONTROL PANEL. 30 PROVIDE (1)1"C. FROM ACU-0-1 TO ACCU-0-2 FOR CONTROL WIRING. 14 FINAL BAS LOCATIONS AND QUANTITY TO BE COORDINATED WITH BAS INSTALLER. 31 HEAT TRACE CONTROL PANEL AND CONNECTION - EQUIPMENT AND CABLE FURNISHED BY DIV. 15. PROVIDE ALL POWER, CONTROLS CONDUIT AND WIRING, INSTALL HEATING CABLES, AND MAKES FINAL CONNECTIONS FOR COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH DIV. 15 CONTRACTOR. PROVIDE INTERFACE TO BMS. 29 120V/1ø CONTROL CIRCUIT FOR FIRE ALARM BELLS. JUNCTION BOX TO MOUNT SENSORS FOR AUTOMATIC DOOR OPENER. REFER TO DRAWING E2.11A FOR CONTROL PANEL LOCATION. DIV. 16 CONTRACTOR TO PROVIDE ALL CONDUIT, WIRING, AUXILIARY DEVICES ARE REQUIRED BY MANUFACTURER INSTALLATION INSTRUCTIONS FOR COMPLETE AND OPERATIONAL SYSTEM. REFER TO KEYED NOTE 10, DRAWING E2.11A. 15 9 330 North Wabash Ave. Suite 3600 Chicago, IL 60611 t 312.755.0770 f 312.755.0775 www.perkinswill.com 27 FOR ELEVATOR PIT. 8.7 32 ASSOCIATE ARCHITECT The Architects Enterprise, Ltd. 230 West Monroe St. Suite 2205 Chicago, IL 60606 t 312.424.0330 f 312.424.0111 www.taeltd.com FIRE ALARM, SPRINKLER SUPERVISORY TROUBLE BELLS. LOCATE ABOVE FIRE ALARM PANELS. 8 STRUCTURAL ENGINEER Halvorson and Partners 14 13 12 11.6 11 10.7 10 9.8 7 AC 2 REFER TO DRAWING ES1.1 FOR CONTINUATION (2)WATER METERS 6 2 HH SD FIRE PUMP 3 M M 1 CCTV UH 0-13 T 16 JP 1 RAMP UH 0-12 S 8 P 29 PB M T T GFI 2 GFI IG C6 TELCO 008 PB 30cd W V SD 30cd PB V SD S M GFI 2 BP 1 CP PDPH-M-B-2 RA SV GFI 75cd 3 FIRE PUMP 6 METERS M M 14 IG GFI S S2-12 C6 18 W SV FPC J M 75cd RA GFI WP S2 5 135° D PDPH-M-B-2 27 S6 J SV 26 GFI 4 EUH 0-1 SV E7 E9 12 10 11 9 E5 D GFI EF-0-2 M 16 7 MACHINE ROOM MECH 011 21 EF 0-3 D 3 8 30cd S 14 J SC RA MD V M GFI 4 SV 75cd GFI 3 M PLUMBING EQUIPMENT P 75cd EUH-0-1 T S V S P GFI C4 S GFI 6 S SV 75cd D D RA S6 31 CONDUITS UP TO FIRST FLOOR CP S1-25,27,29 M EF 0-6 M M D MCC-M-B GFI M 6 CP SV 0ST5 RA T S S SE 1 P WP GFI RA S SV RA GFI 30cd 6 17 S5 CIVIL ENGINEER Terra Engineering C GFI S2-7 Chicago, IL D.8 LANDSCAPE ARCHITECT S5 Jenkins & Huntington, Inc. FOOD SERVICE CONSULTANT CP ESP 3 M S1-31,33,35 IG IG C2 C3 RA Chicago, IL VERTICAL TRANSPORTATION CONSULTANT Willowbrook, IL 19 Cini-Little International, Inc. Naperville, IL . TB Schuler Shook Chicago, IL E21 TB 32 3 THEATER DESIGN CONSULTANT D.1 TB IG SD C4 RA 20 P SV 75cd S W D ELEC ACOUSTIC / AUDIO-VISUAL CONSULTANT Talaske 004 Oak Park, IL C.9 NATATORIUM CONSULTANT Bill Robertson Pool Design/Build, Inc. Northville, MI EL-METER S1-1,3,5 75cd (5) 2" C.'S FROM FIRST FLOOR 1 E7.00 WF AMM VSS AMM 1 E7.00 STAIR 01 C CT V C.8 SV S2-7 GFI WF AMM S VSS AMM P STAIR 02 C.7 IG C4 A CC TV C SC B.8 PB B S P S P S P S CCTV P (1) 2" C.'S FROM FIRST FLOOR S P (2) 2" C.'S S P PARKING S P (7) 2" C.'S 000 (1) 2" C.'S FROM FIRST FLOOR CCTV CCTV S 27 135° WF AMM AMM WF D 5 VSS AMM AMM VSS SV 30cd SD RA 27 W S2-9 SC SC GFI SV 1 75cd 5 Chicago, IL 30 22,24 WF AMM VSS AMM P D S S5 EF 0-7 M MCC-M-B S ATS SD S2-9 001 P 75cd 18 M2,4,6 ESP 2 3 19 MCC-M-B GFI SV S2-9 M 75cd RA RA 75cd PB STAIRS 05 D MECHANICAL ENGINEER Primera Engineers E 135° 3 135° 5 D 014 EF 0-5 S D GFI 3 SD 3 SD T 6 D IT SHAFT #1 4 SD B D WP GFI SV 75cd ACU 0-1 RA GFI 3 D ATS SV CP S1-19,21,23 GFI CP PB GFI 3 S GFI S2-9 PB GFI 4 ESP 1 D 75cd UH 0-14 003 Naperville, IL Site Design Group, Ltd. 5 J P SV MD 15 M J E19 E CP M7,9,11 22 EF-0-3 CP RCP M1,3,5 EF 0-2 13 M14,16,18 15 017 S 2 SC 14 J M 75cd 75cd WP GFI Drucker Zajdel Structural Engineers S 016 30-32 M13,15,17 J J J J J J 010 SD J M WF AMM 25 S4 S VSS AMM SV 30cd 3 SD SD 30 RA W GFI M ACCU S4 26,28 0-1 PB FIRE PUMP CONTROLLER POWER FROM COMED VAULT GFI CP M 3 007 T 31 PIT ACCESS E18 SD EQUIP ELEV 5 D J 34 EF 0-4 M GD 2 V S2-9 3 MCC-M-B D 012 ELEVATOR PIT EF 0-1 MCC-M-B GENERATOR MD HT 0-1 P S 20 S5 D 5 135° 75cd 23 1 GFI 18 S P PIT ACCESS WP GFI UH 0-15 E T D P 013 22 009 S J J D D 1 E7.00 E-PDPH-SB-B 14,16,18 GFI SD 18 SD S11 T ACE CRE FP M CC TV GFI 18 CP M SV 75cd 28 24 S1-14,16,18 CP C JPC (1) WF AMM (13) VSS AMM (2) PS AMM STRUCTURAL ENGINEER SEE 14.4 MATCHLINE 15 1 / E2.10B Chicago, IL REFER TO FP DRAWINGS FOR EXACT QUANTITY AND LOCATIONS CCTV CCTV Revisions CCTV 7 P B.2 MD GFI GFI SC 1 GFI 1 GFI 1 1 SC FOR REFERENCE ONLY B UH 0-11 M T M 8 T 75cd SV UH M 0-9 25 T UH 0-10 25 75cd SV T 75cd SV 21 A.4 75cd SV BULLETIN NO 52 ISSUED FOR PERMIT ISSUED FOR GC BID ISSUED FOR 90% CD ISSUED FOR 60% CD ISSUED FOR DESIGN DEVELOPMENT 1 ISSUED FOR SCHEMATIC DESIGN NO ISSUE UH 0-8 M 75cd 7 6 5 4 3 2 SV SV 04/17/13 05/25/11 05/25/11 04/01/11 01/11/11 10/26/10 08/24/10 DATE Sheet Information Date A 03/06/13 PBC Project Wm Jones College Prep H S PBC Contract No. Perkins+Will Job No. C:\Users\jlefeu\Documents\PEL_JCP_R11_ELEC-CENTRAL_jlefeu.rvt 4/17/2013 4:47:24 PM Drawn 05265 022093.00 DWM Checked DNT Approved RGL Title A A BASEMENT FLOOR POWER AND SYSTEMS PLAN AREA A Sheet 1 BASEMENT FLOOR POWER AND SYSTEMS PLAN - AREA A NORTH 1/8" = 1'-0" E2.10A Copyright © 2010 Perkins+Will 5 4 3 2 1 5 4 3 2 0 1/2" 1" 2" GENERAL NOTES D 1. Proposed New Jones HS NIC KEYED NOTES ALL VISUAL FIRE ALARM DEVICES TO BE FURNISHED WITH FIELD ADJUSTABLE SETTINGS, INITIALLY SET AT VALUES AS INDICATED. ADJUST SETTINGS BASED ON FIELD TESTING AS REQUIRED. 2. 1 ALL ELEVATOR POWER, COMMUNICATIONS, AND MISCELLANEOUS. SYSTEMS REQUIREMENTS SHALL BE COORDINATION WITH ELEVATOR SHOP DRAWINGS. 3. ALL GENERAL RECEPTACLE AND 120V/1ø, 208V/1ø EQUIPMENT CIRCUITS WITH NO ALPHABETICAL PREFIX EMANATE FROM PANEL 'RPGP-B', U.N.O. 4. ALL 480/3ø AND 277/1ø MECHANICAL EQUIPMENT CIRCUITS DENOTED "MXX" EMANATE FROM PANEL 'PPH-M-B', U.N.O. 5. KEYED NOTES 1 SMOKE AND HEAT DETECTORS TO BE INSTALLED IN EVERY BEAM POCKET. 2 MOUNT HEAT DETECTOR WITHIN 2' OF SPRINKLER HEAD. WALL MOUNT WHEN POSSIBLE. 3 PROVIDE (3) ADDRESSABLE RELAY MODULES PER ELEVATOR FOR INTERFACE WITH FIRE ALARM SYSTEM FOR THE FOLLOWING FUNCTIONS: - PRIMARY RECALL - ALTERNATE RECALL(SPARE) - NOTIFICATION ON FACP AND FAA (FIREMAN HAT) 4 PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL TO ELEVATOR CONTROL PANEL FOR ELEVATOR CAB LIGHTS AND FAN. PROVIDE 20A/1P LOCAL DISCONNECT SWITCH. ALL EMERGENCY EQUIPMENT CIRCUITS DENOTED "EXX" EMANATE FROM PANEL 'E-LP-B', U.N.O. 5 PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL FOR ELEVATOR INTERCOM SYSTEM. PROVIDE 20A/1P LOCAL DISCONNECT SWITCH. 6. ALL 480/3ø AND 277/1ø STANDBY POWER EQUIPMENT CIRCUITS DENOTED "S1-XX" EMANATE FROM PANEL 'E-PDPH-SB-B', U.N.O. 6 PROVIDE 120V, 1P, 20A CIRCUIT FROM LIFE SAFETY PANEL FOR ELEVATOR SECURITY SYSTEM. PROVIDE 20A/1P LOCAL DISCONNECT SWITCH. 7. ALL 120/1ø AND 208V/1ø STANDBY POWER EQUIPMENT CIRCUITS DENOTED "S2-XX" EMANATE FROM PANEL 'E-RP-SB-B', U.N.O. 7 FUSED ELEVATOR DISCONNECT SWITCH WITH AUXILIARY CONTACTS AS MANUFACTURED BY BUSSMANN OR APPROVED EQUAL. FINAL LOCATION SHALL BE COORDINATED WITH ELEVATOR SHOP DRAWINGS PRIOR TO INSTALLATION AND FEEDER CONDUIT ROUTING. ALL SECURITY CCTV CAMERAS SHALL BE SUSPENDED 1" HIGHER THAN THE BOTTOM OF THE LOWEST STRUCTURAL BEAM LOCATED WITHIN 35FT OF EACH DEVICE. ADJUST EXACT LOCATION AND FIELD OF VIEW FOR EACH CAMERA BASED ON ACTUAL OBSTRUCTIONS IN FIELD SO CAMERA FIELD OF VIEW IS NOT OBSTRUCTED. 8. 10. ALL INTERIOR CCTV CAMERAS IN FINISHED AREAS SHALL BE CEILING MOUNTED WHERE POSSIBLE. REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. 11. SEE ENLARGED ELECTRICAL PLANS SHEET E7.00 FOR ELECTRICAL EQUIPMENT (PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) LOCATED IN ELECTRICAL ROOMS. 12. LOCATE INTERCOM PAGING SPEAKERS IN STAIRWELLS ON EVERY LANDING. COMBINATION DUPLEX 15 AMP, 125V/2ø, 3W, NEMA L5-15R/5-15R GROUNDING TYPE RECEPTACLE (HUBBELL CAT. NO 4792 OR EQUIVALENT) LOCATED 3'-9" ABOVE FLOOR. 12 PROVIDE "PLAIN OLD TELEPHONE SERVICE" (POTS) LINE CONNECTION TO PHONE, INSTALLED BY OTHER, IN ELEVATOR CAB. 13 SECONDARY SERVICE CONDUITS SHALL BE EXTENDED 3" MINIMUM INTO COMED VAULT. TERMINATE WITH GROUNDING TYPE INSULATION BUSHINGS (OZ TYPE BUSHINGS OR EQUIVALENT). CONCRETE ENVELOPE IS NOT REQUIRED INSIDE COMED VAULT. SPARE CONDUITS TO BE THREADED AND CAPPED. USE 4' LONG RADIUS BEND WITH MAXIMUM TOTAL OF 250 DEGREES OF BENDS IN ONE CONDUIT RUN. PULL PROPER SIZE WIRE BRUSH THRU ALL DUCTS. LEAVE #8 GALVANIZED PULLING WIRE, NYLON CORD OR POLYPROPYLENE ROPE IN DESIGNATED BY COMED DUCTS. SEAL DUCTS TEMPORARILY. 14 ALL SECONDARY SERVICE ENTRANCE CABLE AND/OR SECONDARY LUGS TO BE PROVIDED BY DIV. 16 CONTRACTOR. COORDINATE WITH COMED EXACT REQUIREMENTS. 15 COMED VAULT GROUNDING: COORDINATE ALL WORK WITH COMED GROUNDING RODS FURNISHED BY COMED ARE TO BE INSTALLED BY THE DIV. 16 CONTRACTOR. CONNECT WITH 1#4/0 - 1/C BARE COPPER CABLE IN 1-1/2"C. GROUND MUST MEET COMED REQUIREMENTS. 16 8 ELEVATOR CONTROLLER FINAL LOCATION SHALL BE COORDINATED WITH ELEVATOR SHOP DRAWINGS. 9 FIRE ALARM SPEAKER CONNECTION. PROVIDE NOTIFICATION CIRCUIT FROM NEAREST POWER SUPPLY. 10 COMED VAULT FITOUT IS PROVIDED BY COMED. INCLUDING DISTRIBUTION EQUIPMENT TRANSFORMER AND ALL INTERCONNECTIONS. DIV. 16 CONTRACTOR SHALL COORDINATE INSTALLATION OF SMOKE DETECTORS, OTHER DEVICES WITH COMED EQUIPMENT LOCATIONS - DO NOT INSTALL ANY DEVICES DIRECTLY ABOVE OR BEHIND COMED EQUIPMENT. ALL LOCATIONS SHALL BE ACCESSIBLE FOR FUTURE MAINTENANCE. ALL ISOLATED GROUND COMPUTER CIRCUITS INDICATED AS "CXX" EMANATE FROM PANEL 'RP-CP-B'. 9. 11 William Jones College Preparatory High School 700 South State Street Chicago, IL 60605 D 4/0 - 1/C BARE COPPER CABLE IN 1-1/4" GALVANIZED STEEL CONDUIT WITH BUSHING TO BUILDING GROUND BUS FOR COMED GROUNDING PURPOSES. CONDUIT MUST BE BONDED TO CABLE AS SHOWN ON COMED STANDARDS C0725 OR C0726. CABLE SHALL EXTEND 3' INTO VAULT. ALL GROUND RODS SHALL BE INTERCONNECTED TO THE GROUND CABLE. 17 ARCHITECT PROVIDE (1)1"C. FOR CONTROL WIRING FROM ACU-0-2 TO ACCU-0-2. 330 North Wabash Ave. Suite 3600 Chicago, IL 60611 t 312.755.0770 f 312.755.0775 www.perkinswill.com ASSOCIATE ARCHITECT 1 / E2.10A 230 West Monroe St. Suite 2205 Chicago, IL 60606 t 312.424.0330 f 312.424.0111 www.taeltd.com SEE MATCHLINE The Architects Enterprise, Ltd. 6.2 6 5 4.3 4 3.5 3 2.7 2 1.4 STRUCTURAL ENGINEER 1 Halvorson and Partners Chicago, IL STRUCTURAL ENGINEER Drucker Zajdel Structural Engineers EUH 0-2 16 CP 15 GFI S2-7 EL-METER 15 75cd Chicago, IL 18 14 COM ED 1 M19,21,23 RA GFI 10 GFI 12 UH 0-1 M 10 13 005 UH 0-2 M WF AMM VSS AMM S2-7 15 GFI S2-7 M M SV CRE RA LINE VOLTAGE THERMOSTAT S SV P S P S SV GFI 10 SC Jenkins & Huntington, Inc. Willowbrook, IL FOOD SERVICE CONSULTANT Cini-Little International, Inc. Naperville, IL FOR STAIR 03 & 07 THEATER DESIGN CONSULTANT B.8 Schuler Shook Chicago, IL STAIR 07 ACOUSTIC / AUDIO-VISUAL CONSULTANT Talaske Oak Park, IL 0ST7 C.8 NATATORIUM CONSULTANT Bill Robertson Pool Design/Build, Inc. SC GFI 10 C.7 M19,21,23 S Northville, MI P UH 0-4 CCTV 75cd C AMM WF AMM VSS WP 75cd RA RA MD C.9 S1-2,4,6 M M P VERTICAL TRANSPORTATION CONSULTANT D SE STAGE #2 CCTV IG C5 75cd SV S1-7,9,11 P D.1 WP 2 11 75cd GFI W 11 SV J 5 EF 0-8 M SP 1 WF AMM VSS AMM STAGE #1 SD MCC-M-B CP 75cd SD W UP CCTV CCTV E-PDPH-SB-B: 7,9,11 M Chicago, IL S M31,33,35 CP P M Site Design Group, Ltd. 13 S UH 0-3 M31,33,35 15 EL-METER SP 2 LANDSCAPE ARCHITECT T GFI 11 SD SD GFI 10 Terra Engineering C P 1 IG C4 Chicago, IL 15 1 E7.00 S 1.4 Primera Engineers CIVIL ENGINEER CP S 2 D.8 M8,10,12 C MECHANICAL ENGINEER 75cd SV E Naperville, IL E SV CC TV M B E-PDPH-ELEV-B SC WF AMM VSS AMM ELEVATOR MACHINE ROOM S 75cd SV MACHINESD 30cd ROOM C UP S STAIR 07 PB PARKING S 000 P 4 E5.00 7 S P 17 S P S P (7) 2" C.'S S P ACCU 0-2 CCTV B 0ST7 S CP SC M SC UH 0-6 M T 21 UH 0-5 T 23 75cd 75cd SV SV 3'-4 1/2" MACHINE ROOM S1 015 B.2 WF AMM VSS AMM B B.2 B B 9 Revisions SV 75cd KP FOR REFERENCE ONLY PP PP SD J 15 RCP GFI 12 M 23 T J J WP GFI 135° D 2 SD MD MD CC TV M UH 0-7 17 ACU 0-2 S17,19 SC GFI 12 75cd SV S CONCRETE ENCASED COMED DUCT BANK INSTALLED AT THE TOP OF LOWER LEVEL TIGHT BELOW STRUCTURAL BEAMS, APPROXIMATELY 56"(W) x 12"(H). (6) 5" CONDUITS FROM STUBBED FROM PROPERTY LINE. COORDINATE EXACT LOCATION WITH COMED. 12 E8 E10 5 6 M CCTV FOR ELEVATOR PIT 9 4 E6 8 S21,23 GFI 12 GFI S3 CP 2 E2.10B M 1 7 W B.8 J J J J J SD 015 SV RA 3 ELEV 6 CC TV DRESSING ROOMS 128 & 131 GFI S3 S P PB A.4 7 6 5 4 3 2 BULLETIN NO 52 ISSUED FOR PERMIT ISSUED FOR GC BID ISSUED FOR 90% CD ISSUED FOR 60% CD ISSUED FOR DESIGN DEVELOPMENT 1 ISSUED FOR SCHEMATIC DESIGN NO ISSUE W 7 GFI REFER TO DRAWING ES1.10, E11.1B, AND CIVIL DRAWINGS FOR CONTINUATION. 13 (7) 2" C.'S FOR LOW VOLTAGE SYSTEMS UP TO FIRST FLOOR SHAFT A.4 7 A Wm Jones College Prep H S PBC Contract No. Perkins+Will Job No. C:\Users\jlefeu\Documents\PEL_JCP_R11_ELEC-CENTRAL_jlefeu.rvt 4/17/2013 4:47:24 PM 2 1/8" = 1'-0" DATE 03/06/13 PBC Project 1 08/24/10 Sheet Information Date BASEMENT FLOOR POWER AND SYSTEMS PLAN - AREA B 04/17/13 05/25/11 05/25/11 04/01/11 01/11/11 10/26/10 ENLARGED BASEMENT FLOOR NORTH Drawn 1/4" = 1'-0" 05265 022093.00 DWM Checked DNT Approved RGL Title A A BASEMENT FLOOR POWER AND SYSTEMS PLAN AREA B Sheet NORTH E2.10B Copyright © 2010 Perkins+Will 5 4 3 2 1 4 2" 5 3 0 1/2" 1" GENERAL NOTES D Proposed New Jones HS NIC 1. 2. ALL VISUAL FIRE ALARM DEVICES TO BE FURNISHED WITH FIELD ADJUSTABLE SETTINGS, INITIALLY SET AT VALUES AS INDICATED. ADJUST SETTINGS BASED ON FIELD TESTING AS REQUIRED. 1 FIRE ALARM SPEAKER TO BE INSTALLED IN ELEVATOR CAB. 2 HEAD END INTERCOM SYSTEM EQUIPMENT. PROVIDE 120/1ø CIRCUIT FROM STANDBY POWER PANEL. SMOKE DETECTORS FOR DOOR HOLDERS RELEASE SHALL BE INSTALLED WITHIN 5' FROM THE CENTERLINE OF THE DOOR OPENING. 3 SPRINKLER SYSTEM ALARM BELL - PROVIDE 120V, 1ø, CIRCUIT FROM LIFE SAFETY PANEL. VERIFY EXACT LOCATION AND MOUNTING HEIGHT WITH FIRE PROTECTION AND ARCHITECTURAL ELEVATIONS. PROVIDE INTERFACE TO FIRE ALARM CONTROL PANEL. 4 ALL 480V/3ø AND 277/1ø MECHANICAL EQUIPMENT CIRCUITS DENOTED "M1-XX" EMANATE FROM PANEL 'PPH-M-1-1', U.N.O. 4. CONCENTRATOR TO SERVE ROOMS 134, 135, 136, 137, 138, 164, 166, 167, 168, 169, 170, 174, 175, 181, 185, AND SECURITY DESK. ALL 480V/3ø MECHANICAL EQUIPMENT CIRCUITS DEMOTED "M2-XX" EMANATE FROM PANEL 'PPH-M-1-2',U.N.O. 5. 6 CONCENTRATOR TO SERVE ROOMS 139, 141, 142, 143, 144, 146, 147, 148, 150, 153, 154, 156, 157, 158, 159. ALL 120V/3ø STAND BY RECEPTACLES CIRCUITS DENOTED "SXX" EMANATE FROM PANEL 'E-RP-SB-1', U.N.O. 6. 7 ALL EXTERIOR CCTV CAMERAS SHALL BE SURFACE MOUNTED UNDER THE CANOPY OR WALL BRACKET MOUNTED AT 15' MINIMUM ABOVE FINISHED GRADE WHEN NO CANOPY EXISTS, U.N.O. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS. REFER TO TYPICAL CCTV DETAILS DRAWING E5.07. 7. 10. 11. SEE ENLARGED ELECTRICAL PLANS SHEET E7.00 FOR ELECTRICAL EQUIPMENT (PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) LOCATED IN ELECTRICAL ROOMS. UPON ACTIVATION OF FIRE ALARM DOOR REMAINS LOCKED - "FAIL SECURE". 18 PROVIDE (1) UL LISTED "120V TO 24V AC" CCTV POWER SUPPLY FOR UP TO 3 OUTDOOR FIXED CAMERAS AND (1) POWER SUPPLY FOR EACH PTZ OUTDOOR CAMERA. EACH POWER SUPPLY OUTPUT SHALL BE RATED FOR 3.5 AMPS MINIMUM. POWER SUPPLY SHALL BE AS MANUFACTURED BY ALTRONIX ALTV24 SERIES OR APPROVED EQUAL. DISTANCE FROM POWER SUPPLY TO CAMERA SHALL NOT EXCEED 75 FT. INSTALL IN FINISHED SPACES IN ACCESSIBLE LOCATION ABOVE CEILING. COORDINATE EXACT LOCATIONS IN FIELD WITH ARCHITECT. WHEN POWER SUPPLY IS LOCATED ABOVE PLENUM RATED CEILINGS, PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. - TYPICAL FOR ALL OUTDOOR CAMERAS. 9 SMOKE OR HEAT DETECTOR TO BE LOCATED IN EACH BEAM POCKET. 10 MOTORIZED PARKING GARAGE DOOR AND ELECTRICAL SENSORS FOR ACCESS CONTROL. INSTALL PER MANUFACTURERS SPECIFICATIONS. CONNECT TO CONTROL PANEL LOCATED IN VAULT ROOM 158 FOR A COMPLETE AND OPERATIONAL SYSTEM. 23 DOCK LEVELER AND VEHICLE RESTRAINT SYSTEM. PROVIDE POWER, AND CONTROL WIRING AS REQUIRED BY MANUFACTURER'S INSTALLATION INSTRUCTIONS. MAKE ALL FINAL CONNECTIONS FOR COMPLETE AND OPERATIONAL SYSTEM. 36 LOCATE DOOR POWER SUPPLIES FOR VESTIBULE DOORS IN RECEPTION AREA ABOVE ACCESSIBLE CEILING. COORDINATE EXACT LOCATION AND CONDUIT ROUTING WITH ARCHITECT. 24 FIRE ALARM RISERS. 25 (1)3" AND (1)4" CONDUITS FOR AT&T AND COMCAST SERVICES FROM BASEMENT LEVEL UP TO THIRD FLOOR MDF ROOM. PROVIDE PULL BOXES AS REQUIRED TO MAINTAIN MINIMUM CABLE BENDS AT (6) DIAMETERS, NOT FURTHER THAN EACH 100'. PROVIDE (1)"C TO COOLER AND FREEZER CONTROL PANELS FOR CONTROLS WIRING. PROVIDE WIRING AND MAKE FINAL CONNECTIONS BETWEEN CONDENSING UNITS AND COOLER/FREEZER EVAPORATIVE UNITS PER MANUFACTURER INSTALLATION INSTRUCTIONS. 12 LOCATE DOOR POWER SUPPLY IN VESTIBULE 177 IN ACCESSIBLE LOCATION. 13 PROVIDE COMPLETE POWER AND DATA SYSTEMS WITHIN CASEWORK OR FURNITURE - INCLUDING POWER/DATA OUTLETS, BACKBOXES, CONDUIT, AND WIRING. MAKE ALL FINAL CONNECTIONS, ALL DEVICES TYPE, LOCATION, CONDUIT, AND ROUTING SHALL BE COORDINATED WITH RESPECTIVE SUPPLIER. 35 LOCATE RECEPTACLES +24" AFF - RECYCLING ONLY. 37 PROVIDE (1)1"C. FOR CONTROL WIRING FROM ACU-2-1 TO ACCU-1-1 AND FROM ACU-3-1 TO ACCU 1-2. REFER TO DRAWINGS E2.12A AND E7.01 FOR LOCATIONS. 38 FUEL FILL SPILL BOX CONTROLLER. William Jones College Preparatory High School 39 DOOR TO BE UNLOCKED FROM REMOTE LOCATION. REFER TO KEYED NOTE 34. ALL ELECTRICAL DEVICES, DISCONNECT SWITCHES, JUNCTION AND PULL BOXES LOCATED ABOVE THE SUSPENDED CEILING RESPECTIVE CONDUIT AND WIRING INSTALLATION SHALL COMPLY WITH CEC REQUIREMENTS FOR INSTALLATION IN AIR HANDLING SPACES. VERIFY EXACT EXTENT OF SUCH SPACES WITH DIV. 15 DRAWINGS. 40 ZONE ABOVE ACCESSIBLE CEILING FOR POWER AND LOW VOLTAGE SYSTEMS PULL BOXES TO ENTER/EXIT IT SHAFT AND ELECTRICAL ROOM. 27 PROVIDE (1)2"C. FROM MDF ROOM. 41 SHAFT FOR LOW VOLTAGE CONDUIT ROUTING TO 2ND FLOOR CEILING. 28 CIRCUIT SHALL EMANATE FROM PANEL RP-GP-1-1. 42 CIRCUIT SHALL EMANATE FROM PANEL RP-GP-2-2. 29 CAMERAS SHALL BE SURFACE MOUNTED TO THE UNDERSIDE OF CANOPY. REFER TO DETAIL 10 DRAWING E5.07. 43 CIRCUIT SHALL EMANATE FROM PANEL RP-GP-2-1. PROVIDE (2) JUNCTION BOXES AND 3/4" SLEEVES FOR POWER AND DATA CONNECTIONS TO CCTV CAMERAS FROM CCTV POWER SUPPLY (PS) AND CCTV REMOTE ENCLOSURE (CRE). REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. WHEN CEILING DRYWALL SOFFIT DOES NOT ALLOW MOUNTING OF BOXES RIGHT AT THE PERIMETER - LOCATED THEM AWAY FROM EXTERIOR WALL IN ACCESSIBLE CEILING SPACE. - TYPICAL FOR ALL OUTDOOR CAMERAS. 30 CAMERA TO BE WALL MOUNTED AT ELEVATION 15' TO 20' AFG. 31 CAMERA TO BE SURFACE MOUNTED AT ROOF SPANDREL. 32 REMOTE LOW FUEL LEVEL ALARM PANEL. CONNECT TO FUEL TANK IN GENERATOR ROOM. PROVIDE 1"C. AND WIRING AS REQUIRED BY MANUFACTURER. 20 POWER SUPPLY BY DOOR HARDWARE MANUFACTURER, TYPICAL. COORDINATE WITH DOOR HARDWARE SUPPLIER. 33 21 DOOR ENTRY IS ALLOWED BY PRESENTING VALID ACCESS CARD OR BY UNLOCKING FROM THE OFFICE AREA. REFER TO VIDEO-ENTRY SYSTEM RISER DIAGRAM. COORDINATE INTERFACE REQUIREMENTS WITH DOOR HARDWARE SUPPLIER. 19 11 LOCATE INTERCOM PAGING SPEAKERS IN STAIRWELLS ON EVERY LANDING. 34 REMOTE DOOR SWITCH CONTROL PANEL: SWITCHES TO UNLOCK/LOCK DESIGNATED DOORS. ALL FUNCTIONS OF THIS SYSTEM SHALL BE OVERRIDDEN BY FIRE ALARM DOOR RELEASE SYSTEM OR BY MANUAL SWITCH FROM FIRE COMMAND CENTER. 26 PROVIDE WALL MOUNTED BOXES FOR POWER AND DATA CONNECTIONS TO CASEWORK OR POWERED FURNITURE. INSTALL CONDUITS IN THE FLOOR SLAB TO THE NEAREST WALL AND STUB IN ACCESSIBLE CEILING SPACE. INSTALL BOXES AT 12" AFF. COORDINATE IN FIELD EXACT LOCATIONS OF BOXES AND WHIPS INTO FURNITURE OR CASEWORK WITH LAYOUT. PROVIDE SEPARATE JUNCTION BOXES FOR NORMAL POWER AND ISOLATED GROUND COMPUTER GRADE POWER. 8 DIV. 16 CONTRACTOR SHALL PROVIDE STEP-DOWN TRANSFORMER 120V-240V FOR DOOR HARDWARE WHEN NOT FURNISHED BY DOOR HARDWARE MANUFACTURER. PROVIDE TRANSFORMER IN ENCLOSURE WITH REMOVABLE COVER AND SAFETY DISCONNECT SWITCH. INSTALL TRANSFORMER IN ACCESSIBLE LOCATION ABOVE THE CEILING. WHEN TRANSFORMER IN INSTALLED IN PLENUM RATED CEILING - PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. 9. 17 PARKING GARAGE ENTRY CONTROL PANEL. PROVIDE 120/1ø CIRCUIT FROM STANDBY POWER PANEL. ALL INTERIOR CCTV CAMERAS SHALL BE CEILING MOUNTED WHERE POSSIBLE. REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. 8. ALL EXTERIOR RECEPTACLES SHALL BE GFI, WEATHERPROOF WHILE IN USE, WITH LOCKABLE COVER. 16 KEYED NOTES PROVIDE INTERFACE BETWEEN CARD READER AND DOOR OPERATOR TO UNLOCK AND OPEN THE DOORS WHEN VALID ACCESS CARD IS PRESENTED. BOTH, EXTERIOR AND INTERIOR DOORS SHALL OPEN SIMULTANEOUSLY WITH TIME DELAY - REFER TO "DOOR HARDWARE" SPECIFICATION SECTION 08710. REFER TO TYPICAL DOOR DETAIL, DRAWING E5.03, DETAIL 3 AND 4. 22 IT SHAFT #1: LOCATION OF CONDUIT SLEEVES STUBS UP TO SECOND FLOOR IN LOW VOLTAGE SHAFT FOR ROUTING OF MISCELLANEOUS LOW VOLTAGE SYSTEMS CABLING IN CONDUIT TO THIRD FLOOR MDF ROOM. 15 LOW VOLTAGE SHAFT FOR VERTICAL ROUTING OF MISCELLANEOUS LOW VOLTAGE SYSTEMS CABLING IN CONDUIT FROM MDF ROOM TO FIRST, SECOND FLOORS NORTH, SIXTH, SEVENTH, EIGHTH FLOORS NORTH AND SOUTH. 5 AUTOMATIC PLUMBING FIXTURES, INCLUDING FAUCET OR FLUSH VALVE: INSTALL AND WIRE 120/24V TRANSFORMERS FURNISHED BY DIV. 15 CONTRACTOR AS PART OF PLUMBING FIXTURE PACKAGE. PROVIDE SAFETY DISCONNECT SWITCHES. INSTALL TRANSFORMERS IN AN ENCLOSED JUNCTION BOXES IN ACCESSIBLE LOCATION ABOVE THE CEILING ACCESS PANELS. VERIFY EXACT LOCATION IN FIELD. PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR COMPLETE AND OPERATIONAL SYSTEM. COORDINATE ACCESS PANEL WITH ARCHITECT AND GENERAL CONTRACTOR. 14 1 KEYED NOTES KEYED NOTES KEYED NOTES ALL EMERGENCY RECEPTACLE CIRCUITS DENOTED "EXX" EMANATE FROM PANEL 'E-LP-1-2', U.N.O. 3. 2 700 South State Street Chicago, IL 60605 D ARCHITECT 44 (1) 2" C. DOWN TO BASEMENT LEVEL FOR INTERCOM AND FA SYSTEM INTERFACE TO EXISTING JONES HS. 45 (5) 2" C. FOR LOW VOLTAGE SYSTEMS FROM MDF ROOM 347 DOWN TO BASEMENT. 330 North Wabash Ave. Suite 3600 Chicago, IL 60611 t 312.755.0770 f 312.755.0775 www.perkinswill.com 9 HEAT TRACE CONTROL PANEL AND CONNECTION - EQUIPMENT AND CABLE FURNISHED BY DIV. 15. PROVIDE ALL POWER, CONTROLS CONDUIT AND WIRING, INSTALL HEATING CABLES, AND MAKES FINAL CONNECTIONS FOR COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH DIV. 15 CONTRACTOR. PROVIDE INTERFACE TO BMS. ASSOCIATE ARCHITECT The Architects Enterprise, Ltd. 230 West Monroe St. Suite 2205 Chicago, IL 60606 t 312.424.0330 f 312.424.0111 www.taeltd.com STRUCTURAL ENGINEER 15 14.4 14 13 12 11.6 11 10.7 10 9 9.8 8.7 Halvorson and Partners 8 Chicago, IL 7 STRUCTURAL ENGINEER Drucker Zajdel Structural Engineers 181 10 C M C C TV WP CC 6 TV GD 1 10 RAMPRAMP 012 S24,S26 012 33 33 HT 1-1 WP GFI 12 19 T T 43 PT RE DC IG P C1 6 D CP S22 J S26 33 J S24 33 IG C5 J IG C5 IG C5 CP PS J J WP GFI P D PTZ 35 WP 20 29 18 10 RECYCLING GFI CCTV 10 RA CP M2-12,14,16 180 GD 9 GFI M 3 10 VRS SD SD CP WP M2-2,4,6 1 FCU M M M2-8,10,12 UH WP M 1-5 CP M LV CP 1-4 S WP 23 SV M1-2 MD 1 M M2-19,21,23 WP 75cd 11 GFI LOADING/ P M2-12,14,16 S S 10 P J WP 75cd RECEIVING CP 18 T 173 WP SV M HT CP UH K45B 1-2 1-3 M 29,31,33 RA WP M2-19,21,23 S22 33 K09B GFI TV 18 C 10 28,30,32 C CP GFI IG C2 19 J TYPICAL WP GFI 25 GD 4 M2-7,9,11 CM 1 TEF1-1 EF1-4 M GFI 25 PS 18 J GFI 25 WG SD M T UH 1-2 18 27 EF1-3 WP AP WP CR DC TV CMT GFI 12 RCP UH 1-1 27 M J S J J P 4 SV D STAIR 01 75cd RA P EF 1-4 S M HD J 8 J GFI 7 J J HD J 10 T S J J J J J J J 20 T J J J 30cd J J J V CMT 1 S M1-8 FCU 1-18 J S P J J 22 T 30cd V FCU 1-17.2 5 M1-25,27,29 SD FCU 1-17.1 M1-19,21,23 M1-1 FCU S1-2 M1-1 FCU S1-1 GFI 25 T J HD 14 GFI 7 1 HD 16 M 30cd S J 14 H GFI 7 SD S20 7 SV 30cd IG C7 A 1-1 SD VEST 1 / E2.11B E Chicago, IL LANDSCAPE ARCHITECT Site Design Group, Ltd. D.8 Chicago, IL VERTICAL TRANSPORTATION CONSULTANT Jenkins & Huntington, Inc. Willowbrook, IL SD ELEV P LOBBY Cini-Little International, Inc. S 1 2 E7.00 33 J FCU 1-22 THEATER DESIGN CONSULTANT Schuler Shook 1ST2 107 M NATATORIUM CONSULTANT Bill Robertson Pool Design/Build, Inc. Northville, MI C.9 RA H CCTV Talaske D V ELEC ACOUSTIC / AUDIO-VISUAL CONSULTANT Oak Park, IL FCU S2-1 W Chicago, IL D.1 M1-12 S 18 J PS 30 Naperville, IL STAIR 02 C.8 A S CR SV 1 75cd S C.7 P 40 C TV B.8 FSP EPS RAP FOR REFERENCE ONLY B.2 CR 1 MD SV B 9 8 7 6 5 4 3 2 BULLETIN NO 52 BULLETIN NO. 1 ADDENDUM 3 ISSUED FOR PERMIT ISSUED FOR GC BID ISSUED FOR 90% CD ISSUED FOR 60% CD ISSUED FOR DESIGN DEVELOPMENT 1 ISSUED FOR SCHEMATIC DESIGN NO ISSUE 75cd A.4 CC TV TV FAA SAA EPS 08/24/10 DATE 03/06/13 PBC Project Wm Jones College Prep H S PBC Contract No. A TV C:\Users\jlefeu\Documents\PEL_JCP_R11_ELEC-CENTRAL_jlefeu.rvt Date C C 4/17/2013 4:47:31 PM 04/17/13 09/14/11 06/22/11 05/25/11 05/25/11 04/01/11 01/11/11 10/26/10 Sheet Information CC TV CC TV B Revisions ESP FAA SAA ACE CC TV ICC CRE C C 29 WP PTZ 26 Terra Engineering C CC TV C C ACE CCTV CCTV TV 3 WP E2 B CIVIL ENGINEER 1 H CCTV 19 Chicago, IL S SD 1 EF SV V P M KRONOS SYSTEM S T T 106 RP-GP-1-2 1-1 M H M M +42" AFF M2-25,27,29 SD TLT 15cd 30cd MD 1 1 1 S TEF M RA MENS WP 22 TB WOMENS M S E-PDPH-SBH-B 18 23 P J D 5 S 22 J J VEST 3 J C M1-8 P M ACCU E4,E6 23 E8 1 S C S S T P 20 M 1-1 SD SD TV 20 8,10,12 105 R DD RA TLT SD PS P SD SD RA P PS MD T S P TB J TLT FAA S AC 1-1 CCTV 172 WP S 30 S M FOR BAS M2-13,15,17 25 PB 102 ACCU MD T 1 18 6 26 RA SAA GFI 18 S RA 42 1-1 1 101 M 75cd SV ERU-1,2 1 P TB CONTROL 75cd 75cd M 5 M P EPS 10 MD 1-2 22 8 42 T PB SD CCTV MD S M 30cd SV GFI SV SV 15 WG 23 J IT SHAFT #2 34,36 37 J H H T 37 H CUH VAULT H 30cd 25 23 S18 IG S1 S IG GFI 1-7 IG CRE IG IG PB IG 156 1 SV C28 3 21 C9 M 3 M1-13 KP IG S S CR 45 24 19 19 C9 COT C28 GFI SV C9 MD EF 10 22 13 C5 MD 15 17 PB IG IG SD IG ENGINEER C9 5 15 21 CR COPIER FCU S GFI 22 CNSLR 1-2 SV TJAN C7 RM C22 75cd C3 17 GFI CNSLR IT SHAFT #1 5 1 174 CNSLR 1-4 SV 30cd 9 IG 168 17 SD 179 22 75cd 3 M K 159 15 S IG 19 170 IG S C9 13 21 S 2 169 C2 S GFI S AMM VSS VSS C7 P SD 30cd 30cd 30cd GFI 30cd 30cd S 26 8 13 1 IG IG 2 IG .RCP J 20 39 42 PS AMM 3 AMM VEST J 2 4 V STAIR V V V V STAIR 13 IG C7 WORKROOM C2 C3 RA E7.00 C1 AMM PS PT PT PS AP IG IG 177 MD MD MD IG 0505 154 2 CCTV 40 CR PD RA SV MS C13 LOBBY C2 25 32 V P C16 GFI T P EWC S LS LS P CORRIDOR 7 STAIR S GFI P S 1ST5 0ST5 C 7 MD S SD P S J 20 75cd DF LAUNDRY 100 TV C S M 3 4 75cd SV RE RE FCU FILE 162 EXAMS2 PS 23 04 R-DRYER REF IG IG 161 1-8 TV 20 PS P V 4 4 OPEN TO TYPICAL C STOR 8 13 S P 21 EF-1-2 RM 5 C8 C6 C 23 1ST4 GFI 30cd 4 J J FLOOR ABOVE M1-17 FOR 2 SV 75cd MD IG STARTER SD 5 167 IG 6 K 7 158 IG J J 23 22,24,26 C27 75cd 8 WAITING MD J J J P 8CONF FCUTOILET ELEC C11 18 MD P 11 T J IG V J D P J 4 J T SV S S 1-3 RM T 27 171 75cd WF AMM TV S 3 REF 41 P R-WASHER 163 178 C C7 14 NURSE MD IG SV CR C 14 153 M M1-7 S3 RA VSS AMM 2 24 IG K COPIER 9 8 T 4 IG 14 C24 7 WORK P S4 EXAM 30cd P P 166 P S 75cd S C30 24 ELEC S J S S S C2 T MD MD IG 15cd T FCU CR WP V J S RCP T CRE KRONOS 44 IG P SD RM S 8 RM DC TV S C31 S6 185 23 PTOILET GFI 1-7 30cd V DS 21 TB TB TB V GFI SYSTEM C6 P AP 19 GFI S7 7 4 J S IG,C4 9 GFI 164 24 15 E14,E16,E18 PT RE 157 TOILET M FCU +42" AFF S MS 6 J J 151 7 7 75cd M1-13 34 MD 6 CR GFI GFI E13,E17 CR 11 S4-1 PT RE DC SV IG GFI 152 15cd V SD M V SV FA IG 9 9 44 43 7 9 IG SECURITY 11 SD C11 15cd S2 PPH-M-2 M1-5 J S C16 20 J C16 IG MS ADM IG CR 31 IG OFFICE AP FIRE COMMAND SV CCTV FCU 75cd SV 1 CR EWC 7 C11 AP TV C16 4 C8 7 CENTER C 75cd FCU FCU SV 9 1 E5.06 20 DF 1-2 IG 137 75cd ATTEND C WP P FCU CORRIDOR S S5 IG S P P 1-11 1-1 P C15 26 26 P FCU 8 13 S S S 1-10 M MD 136 13 FCU 75cd MD C12 TV M M 149 M1-5 7 P IG M1-7 DJ 7 M S 7 TV M 1-9 S M M M1-3 1-6 30cd C CCTV SV C13 FCU C IG IG CR CR M1-3 P J M1-11 SV 1-15 C22 C13 1 3 J V V V V V V V SV 30cd IG IG M1-15 RCP IG MD 17 C22 18 IG C19 SV 30cd 30cd 30cd 30cd 30cd 30cd 30cd TV 75cd C20 IG MD TV FCU C4 P C SV IG TV 75cd SV VC C24 CR PP MD C 18 19 MD MD 75cd 12 PS MD 1-14 MD IG K C31 12 IG V 7 IG CNSLR J P TV 30cd IG S S IG 26 FCU IG M1-11 IG C18 18 16 M 21 C6 17 IG M C13 18 FCU 17 IG J D IG 150 C12 J C6 IG 1-12 M TV C15 TV IG 8 C14 TV 18 C6 IG C10 1-16 CUH C21 KRONOS TV TV TV FCU TV PP T TV TV M1-9 C19 19 19 16 15 C21 IG 16 C P MD SYSTEM 18 1-1 C MD M 1-13 M1-15 S P CONF 10 14 S P P P P 14 5 P 16 15 P VC DJ S C4 S S S S VC +42" AFF VC S 17 VESTIBULE P KP P S P ASST OPEN WAITING M D RM M1-16 AP 21 3 BUS. SV 75cd T 23 S S P P ADM VC ASST IG CNSLR RECEPTION VC VC VC P J S 17 PRCPL MD MS +68" AFF VC 111 IG 18 19 135 SV CNSLR PRCPL CNSLR OFFICE IG P IG IG MGR CUH IG IG M RE IG 148 S 147 142 134 RE 30cd C14 PS RE RE RE PRCPL C10 IG C8 8 2 C24 14 10 C18 5 C12 IG C13 141 C15 1-2 144 139 138 8 13 18 143 16 17 DC ADM IG 15 DC DC DC DC 19 17 C6 16 146 C31 ADM DJ PS 25 ADM K C19 23 ADM P P PS D PT PT PT PT J P 28 PT J IG ADM 28 IG P 1 IG J J J J J J 18 19 18 IG IG IG IG IG IG ED ED ED ED ED RCP J D C24 C23 C15 J PS D C10 C14 P C8 C12 C13 C4 V IG T 4 25 6 WP C 36 C KRONOS WP J J PTZ DC 8 13 29 S P B E11 18 19 SYSTEM PTZ 25 25 28 28 36 PT WP TYPICAL 16 TYPICAL +42" AFF 28 3 PTZ E10, 6 WP,GFI S ED WP WP 29 WP V 19 29 IG IG GFI E12 RP-GP-1-1 19 4 CCT RP-GP-1-1 P J PS GFI C17 C17 WP 3 19 PTZ WP E7 WP 29 AP TYPICAL 19 2 20 CR WP GENERAL RECEPTACLES EMANATE GENERAL RECEPTACLES EMANATE TB TB TB E9 FROM 'RP-GP-1-1', U.N.O. FROM 'RP-GP-1-4', U.N.O. IG TYPICAL CIRCUITS DENOTED "CXX" EMANATE CIRCUITS DENOTED "CXX" EMANATE 21 22 C25 PP FROM PANEL 'RP-CP-1-1', U.N.O. FROM PANEL 'RP-CP-1-2', U.N.O. 10 GENERAL RECEPTACLES EMANATE GENERAL RECEPTACLES EMANATE FROM 'RP-GP-1-4', U.N.O. FROM 'RP-GP-1-3', U.N.O. J 20 C C B P J J 30 D 1 103 33 J J J 19 TYPICAL MECHANICAL ENGINEER Primera Engineers FOOD SERVICE CONSULTANT SV S J J 30 P 30 J J D K T 22 22 P 1ST1 M2-26,28,30 TV C C 20 T 20 GFI 18 J J GFI T GFI 20 22 7 7 J J J J T 20 T J J J J K J 13 DCES DC GFI M W 25 M2-20,22,24 SV GFI SD YARD S 25 175 S TYPICAL 14 14 TYPICAL WP EF 1-3 STORAGE S C C P MD 12 PT RE WP 9 S GFI WP WP S 17 WP GFI 12 DC J S22 WP TV PTZ CC 4 JP 4 D CP WP GFI HT 1-1 CP 16 W GFI SD PS 16 CP J CC TV J M2-1,3,5 GFI 10 38 29 PT PT RE RE DC DC WP PTZ 30 16 TYPICAL TV PTZ 30 WP 30 WP CP RCP PT RE DC C C WP GFI 29 DC 31 19 PTZ WP 16 Naperville, IL SEE GAS TV GFI WP 12 25 J MATCHLINE 12 GENERAL RECEPTACLES EMANATE FROM 'RP-GP-1-3', U.N.O. C C GENERAL RECEPTACLES EMANATE FROM 'RP-GP-1-2' , U.N.O. CIRCUITS DENOTED "CXX" EMANATE FROM PANEL RP-CP-1-2, U.N.O. TV CC GENERAL RECEPTACLES EMANATE FROM 'RP-GP-1-1' , U.N.O. CIRCUITS DENOTED "CXX" EMANATE FROM PANEL RP-CP-1-1, U.N.O. GENERAL RECEPTACLES EMANATE FROM 'RP-GP-1-2', U.N.O. CCTV 42 Perkins+Will Job No. Drawn 05265 022093.00 DWM Checked DNT Approved RGL Title A A GROUND FLOOR POWER AND SYSTEMS PLAN AREA A Sheet 1 GROUND FLOOR POWER AND SYSTEMS PLAN - AREA A 1/8" = 1'-0" NORTH E2.11A Copyright © 2010 Perkins+Will 5 4 3 2 1 4 3 2 1 2" 5 GENERAL NOTES SMOKE DETECTORS FOR DOOR HOLDERS RELEASE SHALL BE INSTALLED WITHIN 5' FROM THE CENTERLINE OF THE DOOR OPENING. 3. REFER TO EAX.XX SERIES DRAWINGS FOR LOCATIONS OF ALL AUDIOVIDEO DEVICES. PROVIDE ALL CONDUIT AND BACKBOXES SHOWN ON THESE DRAWINGS. 0 1/2" 2. 15. DIV. 16 CONTRACTOR SHALL PROVIDE STEP DOWN TRANSFORMER 120V24V FOR DOOR HARDWARE WHEN NOT FURNISHED BY DOOR HARDWARE MANUFACTURER. PROVIDE TRANSFORMER IN ENCLOSURE WITH REMOVABLE COVER AND SAFETY DISCONNECT SWITCH. INSTALL TRANSFORMER IN ACCESSIBLE LOCATION ABOVE THE CEILING. WHEN TRANSFORMER IS INSTALLED IN PLENUM RATED CEILING - PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. LOCATE INTERCOM PAGING SPEAKERS IN STAIRWELLS ON EVERY LANDING. SPEAKER TO BE INSTALLED IN ELEVATOR CAB. 2 REEL CORD CEILING MOUNTED WITH NEMA 5-15R TWIST LOCK RECEPTACLE. 3 PROVIDE IG/AV GRADE RECEPTACLE AND DATA OUTLETS, CIRCUIT NUMBER AS INDICATED. COORDINATE EXACT LOCATION WITH THEATER CONSULTANT DRAWINGS. OUTLETS TO BE LOCATED IN FLOOR POCKET NEXT TO POWER AND CONTROLS CONNECTIONS FOR REHEARSAL PANEL 'RHP-1'. 5 6 ALL CIRCUITS INDICATED AS "AVXX" EMANATE FROM PANEL 'RP-AV-21'. REFER TO DRAWINGS E2.12B FOR PANEL LOCATION. SEE NOTE 4 FOR IDENTIFICATION REQUIREMENTS. 5. 7 6. ALL CIRCUITS INDICATED AS "E1-XX" EMANATE FROM EMERGENCY POWER PANEL 'E-LP-AD-1-1', U.N.O. 7. ALL GENERAL POWER CIRCUITS ON THIS DRAWING EMANATE FROM PANEL 'RP-GP-1-3', UNLESS NOTED OTHERWISE. CIRCUIT NUMBERS ARE DESIGNATED WITH NO ALPHABETICAL PREFIX. 8 9 ALL ISOLATED GROUND COMPUTER GRADE CIRCUITS INDICATED ON DRAWING AS "CXX" EMANATE FROM PANEL 'RP-CP-1-2'. 8. ALL 480V/3ø AND 277/1ø MECHANICAL EQUIPMENT CIRCUITS DENOTED "M1-XX" EMANATE FROM PANEL 'PPH-M-1-1', U.N.O. 9. 11. ALL CIRCUITS INDICATED AS "E2-XX" EMANATE FROM PANEL 'E-LP-1-2', U.N.O. 12. ALL EXTERIOR CCTV CAMERAS SHALL BE SURFACE MOUNTED UNDER THE CANOPY OR ARM MOUNTED AT 15' MINIMUM ABOVE FINISHED GRADE WHEN NO CANOPY EXISTS, U.N.O. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS. REFER TO TYPICAL CCTV DETAILS. 24 ADMINISTRATIVE CONCENTRATOR (ACE) TO SERVE ROOMS 100, 107, 113, 115, 116, 122, 126, 128, 131, AND ORCHESTRA PIT. 25 RECESSED WEATHERPROOF SPEAKER MOUNTED UNDERSIDE OF CANOPY. 26 CAMERA TO BE WALL MOUNTED AT ELEVATION 15'-20' AFG, U.N.O. 27 CAMERA TO BE SURFACE MOUNTED TO THE UNDERSIDE OF THE CANOPY, REFER TO DETAIL 10, DRAWING E5.07. 28 CAMERA TO BE MOUNTED ON LIGHTING POLE AT 15' AFG. PROVIDE (2) 1"C. POWER AND DATA CONNECTIONS. POWER FEED SHALL NOT EXCEED 75' TOTAL ROUTING LENGTH. REFER TO DRAWING ES1.10 FOR POLE LOCATION AND CONDUIT ROUTING. 30A, 208V, 1Ø, 3W TWIST LOCK OUTLET FOR SHOP EQUIPMENT, INSTALL 36" AFF. PROVIDE IDENTIFICATION LABEL, "FUTURE". 14 100A, 208V, 1Ø, 4W SAFETY DISCONNECT SWITCH IN NEMA 12 ENCLOSURE FOR FUTURE SHOP EQUIPMENT. 15 SPRINKLER SYSTEM BELL. VERIFY EXACT LOCATION AND MOUNTING HEIGHT WITH FIRE PROTECTION DRAWINGS AND ARCHITECTURAL ELEVATIONS. PROVIDE 120V, 1Ø POWER FROM LIFE SAFETY PANEL. PROVIDE INTERFACE TO FIRE ALARM CONTROL PANEL AND ANNUNCIATOR. 16 30A, 208V, 3Ø, 4W TWIST LOCK OUTLET FOR SHOP EQUIPMENT, INSTALL 36" AFF. 29 LOCATE DOOR POWER SUPPLY IN ORCHESTRA ROOM 116 IN ACCESSIBLE LOCATION. 17 PROVIDE POWER CONNECTION FOR FUTURE EQUIPMENT JUNCTION BOX TO BE MOUNTED 60" AFF. TERMINATE CONDUCTORS IN 20A/1P SAFETY DISCONNECT SWITCH IN NEMA 12 ENCLOSURE. PROVIDE BLANK COVER WITH IDENTIFICATION LABEL "VENT HOOD". 30 LOCATE DOOR POWER SUPPLY IN SCENE SHOP ROOM 113 IN ACCESSIBLE LOCATION. PROVIDE CONTACTORS TO CONTROL LIGHTING CIRCUITS FOR SX-1 TAGGED FIXTURES IN SCENE SHOP AND RECEPTACLE CIRCUITS IN RACEWAY ABOVE THE COUNTER IN GREEN ROOM. REFER TO DETAIL 8 DRAWING E5.03 AND DRAWINGS E7.07 AND E7.09. POWER SUPPLY BY DOOR HARDWARE MANUFACTURER - TYPICAL. COORDINATE WITH DOOR HARDWARE SUPPLIER. ALL EXTERIOR RECEPTACLE SHALL BE GFI, WITH WEATHERPROOF, WHILE IN USE. PROVIDE LOCKABLE COVER. PROVIDE 30AS/20AF,3Ø DISCONNECT SWITCH IN NEMA 12 ENCLOSURE FOR FUTURE DUST COLLECTION EQUIPMENT. PROVIDE IDENTIFICATION LABEL "DUST COLLECTION SYSTEM". 18 HEAT DETECTORS TO BE LOCATED IN EVERY BEAM POCKET. FIRE RATED DOOR. PROVIDE INTERFACE TO FIRE ALARM SYSTEM TO CLOSE THE DOOR IN CASE OF FIRE. SMOKE DETECTORS TO BE LOCATED WITHIN 5' FROM THE CENTERLINE OF DOOR OPENING. 19 NOT USED. 20 PROVIDE (1) UL LISTED; "120V TO 24V AC" CCTV POWER SUPPLY FOR UP TO 4 OUTDOOR FIXED CAMERAS AND (1) POWER SUPPLY FOR EACH PTZ OUTDOOR CAMERA. EACH POWER SUPPLY OUTPUT SHALL BE RATED FOR 3.5 AMPS MINIMUM. POWER SUPPLY SHALL BE AS MANUFACTURED BY ALTRONIX ALTV24 SERIES OR APPROVED EQUAL. DISTANCE FROM POWER SUPPLY TO CAMERA SHALL NOT EXCEED 75 FT IN FINISHED SPACES INSTALL IN ACCESSIBLE LOCATION ABOVE CEILING. COORDINATE EXACT LOCATIONS IN FIELD WITH ARCHITECT. WHEN POWER SUPPLY IS LOCATED ABOVE PLENUM RATED CEILINGS, PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. 11 PROVIDE INTERFACE BETWEEN CARD READER AND DOOR LOCK TO UNLOCK DOORS WHEN VALID ACCESS CARD IS PRESENTED. REFER TO "DOOR HARDWARE" SPECIFICATION SECTION 08710. 31 DOOR TO BE UNLOCKED FROM REMOTE LOCATION. REFER TO DRAWING E2.11A, KEYED NOTE 34. 32 COORDINATE LOCATION OF DEVICES WITH ORCHESTRA SHELL. 33 DELIVER TO AV DEVICE - SEE DRAWING EA1.11B. 34 CIRCUIT SHALL EMANATE FROM PANEL RP-GP-2-2. 35 CIRCUIT #9 EMANATE FROM PANEL RP-GP-1-3. 36 (7) 2" C.'S FOR LOW VOLTAGE SYSTEMS FROM BASEMENT LEVEL. STUB CONDUITS 1' FROM BUILDING TO UNDER THE CANOPY. PROVIDE WATERPROOFING AS REQUIRED. COORDINATE WITH ARCHITECT. WIRING WILL BE PULLED BY OTHERS. THIS CONTRACTOR TO MAKE FINAL CONNECTIONS. 12 100A, 208/120V, 3Ø, 5W AUDIO/VIDEO COMPANY SWITCH AND 400A, 208/120V, 3Ø,5W STAGE LIGHTING COMPANY SWITCH. REFER TO RISER DIAGRAM DRAWING E4.00 FOR SPECIFICATION. COORDINATE EXACT LOCATION PER DRAWING E7.09. William Jones College Preparatory High School 700 South State Street Chicago, IL 60605 D ARCHITECT 330 North Wabash Ave. Suite 3600 Chicago, IL 60611 t 312.755.0770 f 312.755.0775 www.perkinswill.com 9 PROVIDE (2) JUNCTION BOXES AND 3/4" SLEEVES FOR POWER AND DATA CONNECTIONS TO CCTV CAMERAS FROM CCTV POWER SUPPLY (PS) AND CCTV REMOTE ENCLOSURE (CRE). REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. WHEN CEILING DRYWALL SOFFIT DOES NOT ALLOW MOUNTING OF BOXES RIGHT AT THE PERIMETER - LOCATED THEM AWAY FROM EXTERIOR WALL IN ACCESSIBLE CEILING SPACE. 21 ALL INTERIOR CCTV CAMERAS SHALL BE CEILING MOUNTED WHERE POSSIBLE. REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. 13. KEYED NOTES AUTOMATIC PLUMBING FIXTURES, INCLUDING FAUCET OR FLUSH VALVE: INSTALL AND WIRE 120/24V TRANSFORMERS FURNISHED BY DIV. 15 CONTRACTOR AS PART OF PLUMBING FIXTURE PACKAGE. PROVIDE SAFETY DISCONNECT SWITCHES. INSTALL TRANSFORMERS IN AN ENCLOSED JUNCTION BOXES IN ACCESSIBLE LOCATION ABOVE THE CEILING ACCESS PANELS. VERIFY EXACT LOCATION IN FIELD. PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR COMPLETE AND OPERATIONAL SYSTEM. COORDINATE ACCESS PANEL WITH ARCHITECT AND GENERAL CONTRACTOR. 10 DOOR ENTRY IS ALLOWED BY PRESENTING VALID ACCESS CARD OR BY UNLOCKING FROM THE OFFICE AREA. REFER TO VIDEO-ENTRY SYSTEM RISER DIAGRAM. COORDINATE INTERFACE REQUIREMENTS WITH DOOR HARDWARE SUPPLIER REFER TO ENLARGED PARTIAL PLANS DRAWING E7.00 FOR ELECTRICAL ROOM LAYOUT AND PANELS LOCATIONS. 10. 13 1 4 ALL POWER FOR A/V EQUIPMENT SHALL BE ISOLATED GROUND, COMPUTER GRADE, WITH PERMANENT ENGRAVING ON THE COVER "AV ONLY". RECEPTACLES ARE DESIGNATED ON FLOOR PLAN WITH SUBSCRIPT "AV". 4. D 14. ALL VISUAL FIRE ALARM DEVICES TO BE FURNISHED WITH FIELD ADJUSTABLE SETTINGS, INITIALLY SET AT VALUES AS INDICATED. ADJUST SETTINGS BASED ON FIELD TESTING AS REQUIRED. 1" 1. KEYED NOTES KEYED NOTES GENERAL NOTES ASSOCIATE ARCHITECT The Architects Enterprise, Ltd. 22 INSTALL SAFETY DISCONNECT SWITCHES IN ACCESSIBLE LOCATION IN DIRECT VIEW OF FAN MOTORS. PROVIDE PLENUM RATED ENCLOSURES. REFER TO DRAWING E7.00 FOR STARTER'S LOCATIONS. 23 ALL ELECTRICAL DEVICES, DISCONNECT SWITCHES, JUNCTION AND PULL BOXES LOCATED ABOVE THE SUSPENDED CEILING RESPECTIVE CONDUIT AND WIRING INSTALLATION SHALL COMPLY WITH CEC REQUIREMENTS FOR INSTALLATION IN AIR HANDLING SPACES. VERIFY EXACT EXTENT OF SUCH SPACES WITH DIV. 15 DRAWINGS. 230 West Monroe St. Suite 2205 Chicago, IL 60606 t 312.424.0330 f 312.424.0111 www.taeltd.com STRUCTURAL ENGINEER 5 4.3 4 3.5 3 2.7 2 1.4 15 EF 1-6 MCC-M-B P M 22 23 J PS 23 STAIR 02 16 7 1ST2 M ELEC 112 S P SD SD H H 27 J 34 FCU S2-2 S C C 14 TEF 1-2 CLG J MTD 4 27,29,31 4 5,7 12 6 M T SV 30cd 3 132 S SV J T 5 13 9 1 GFI 3 11 15cd IG AV AV26 SV T 5 3 J J GFI 3 J 6 S S 6 6 IG C19 CR 13 TV 127 IG C30 W VEST SV 110cd SD 124 MD 9 SV 110cd S J CR 3 9 CR 13 IG AV AV-19 33 CR 13 S M CCTV GFI WP 15 SV SV T S WP GFI S S WP 15 15 TYPICAL SV M1-6 28 2 S MD SV 75cd S CCT V NATATORIUM CONSULTANT Bill Robertson Pool Design/Build, Inc. Northville, MI ELEV LOBBY DC WP 11 14 PS E26 J DC WP ES WP CR WP A.4 S P P 14 11 10 PT ED J PS 31 109 CUH 1-3 T D 21 P D 21 P RP-GP-1-3 32 VEST M1-14 S P M MD P A.4 26 SV 75cd Date WP RCP PT ED DCRE 24 GFI WP 15 36 9 Perkins+Will Job No. Drawn J PS 31 21 J 21 A PP TV PP 75cd CR SV S 10 RCP PT ED DCRE 22 J 31 A CR WP 10 11 A 11 TV 2 1/8" = 1'-0" WP AP 14 PP C C GROUND FLOOR POWER AND SYSTEMS PLAN - AREA B 05265 022093.00 DWM Checked DNT Approved RGL Title J 26 1 DATE Wm Jones College Prep H S PBC Contract No. RCP RCP 08/24/10 03/06/13 PBC Project CC TV 04/17/13 09/14/11 06/22/11 05/25/11 05/25/11 04/01/11 01/11/11 10/26/10 Sheet Information COORDINATE WITH GENERAL CONTRACTOR FOR ACCESS PANEL PB 24 14 S 110 (7)2" C.'S FOR LOW VOLTAGE SYSTEMS FROM BASEMENT LEVEL PP J J J J 109 B 6 WP E-LP-1-1 E1 ELEV LOBBY PP 35 J RCP S M VEST DF MD CR KP +68" AFF 2 E2.11B BULLETIN NO 52 BULLETIN NO. 1 ADDENDUM 3 ISSUED FOR PERMIT ISSUED FOR GC BID ISSUED FOR 90% CD ISSUED FOR 60% CD ISSUED FOR DESIGN DEVELOPMENT 1 ISSUED FOR SCHEMATIC DESIGN NO ISSUE FCU 1-21 . 75cd SV 13 9 8 7 6 5 4 3 2 13 SD SD ED RCP PT RCP J WP E-RP-SB-1 21 29 .RCP J PT PS 31 9 LS M 1.4 C C C:\Users\jlefeu\Documents\PEL_JCP_R11_ELEC-CENTRAL_jlefeu.rvt Talaske Oak Park, IL 10 B A 4/17/2013 4:47:32 PM ACOUSTIC / AUDIO-VISUAL CONSULTANT B.2 1 110 LOBBY S Chicago, IL FOR REFERENCE ONLY WP D J 75cd 110cd WP PTZ 27 S V FCU 1-17.4 CCT V Schuler Shook Revisions CCTV P THEATER DESIGN CONSULTANT 34 LIGHT POLE H CR 13 29 DCRE PT 110cd CR 13 108 Naperville, IL B J 31 T CUH 34 1-4 35 16 J SD 75cd P FOOD SERVICE CONSULTANT Cini-Little International, Inc. B.8 P SD CCTV J D 21 J P 29 Willowbrook, IL B 130 MD SV Jenkins & Huntington, Inc. C P M VEST S 110cd M1-4 S MD S 30cd IG C32 P FCU 1-17.3 OPEN TO FLOOR ABOVE 13 3 RHP-1 Chicago, IL VERTICAL TRANSPORTATION CONSULTANT P RP-GP-1-3 1ST3 27DN PS J SV S STAIR RP-GP-1-3 07 26 PS J W SV WP 27 PTZ 29 10'-0" AFF 20 122 122 Site Design Group, Ltd. C.8 RP-GP-1-3 24 PS J CC TV AUDITORIUM H LANDSCAPE ARCHITECT TV H 29 .RCP J PT PT PS 31 LS LS 9 P IG C27 RP-AD-1-2: 28,30,32 RA Chicago, IL 116 AUDITORIUM RA Terra Engineering C M 7'-6" AFF OHD 3 C TV CTV CIVIL ENGINEER ORCHERSTA 6 ROOM 110cd C C Chicago, IL 25 C C CR SV 13 JAN 75cd P 20 123 S PS S 29 J VC MECHANICAL ENGINEER Primera Engineers 6 P IG C17 Naperville, IL C.9 P WP S Drucker Zajdel Structural Engineers C.7 TV S 6 7'-6" AFF SV IG C23 D Proposed New Jones HS NIC STRUCTURAL ENGINEER 30cd C C CCT V 9 IG C19 S 9 IG C17 V J CCT 35 9 MD TV IG C21 PT RE DC SV VC CR 13 9 15cdTOILET 3 125 PT RE DC D.1 P M MD S FCU 13 S3-1 T STAIR PPH-M-2 03 30 1ST3 IG AV AV9 5 8' - 6" IG AV AV8 34 DC +18" AFF GREEN ROOM 126 W S V TV 1ST6 P 5 C C CONVENIENCE +7'-0" STAIR AFF 06 S T S IG C28 V IG AV AV27 +7'-0" AFF S SV MD IG C19 110cd 30cd 110cd 2 J CRE 5 J J 13 IG C26 29 J 31 5 8' - 6" CATWALK ACCESS 30cd V P DRESSING RM 128 IG C17 CR 11 SV 30cd WP J D 28 TV WP CC PTZ 28 WP GFI 15 VC 115 D.8 LIGHT POLE S P WP CP RCP S M SV 3 P FCU 1-20 P S STAGE IG,AV AV10 18"AFF IG AV AV7 18"AFF 110cd W MD S SV S E WP RP-GP-1-3 28 +18" AFF IG,AV AV18 48"AFF 24 M1-18 15cd OHD 2 12 TOILET T TV +5'-0" AFF 3 3 131 C C B AV AV25 IG DRESSING RM S MD IG C29 IG C30 SV 9 WP REFER TO DRAWINGS E7.08 AND E7.09 FOR ADDITIONAL POWER, DATA AND CONTROL REQUIREMENTS FOR STAGE AND AUDITORIUM LIGHTING SCOPE 115 M 21,23,25 10 IG C18 SV 75cd ACE S MD AFF 133 P 1,3 4 12 1 CORRIDOR +7'-0" 32 ES WP DC DC PS P J P CCTV PS J DJ MD 4 Chicago, IL WP E-RP-SB-1 J 21 RCP CR WP WP PTZ 25 TV CC STAGE SD SD CLG MTD IG C25 8 J 2 17 TV 26 J +18" AFF D CLG MTD IG C29 114 2 S 18 WG 10 15cd 30cd SCENE SHOP 2 16 9,11,13 11 IG C30 6 J 113 75cd SV 11 TYPICAL FOR 2 P S TV D DC CUH RP-AD-1-2 S M 1-6 33 SV T +18" AFF IG 75cd 4 AV AV14 IG SV 110cd AV 2 AV11 2 +18" AFF 32 IG C19 CROSS OVER SV TV CC MD TV CCTV 19 34 10 P S H 2 J 2 CLG MTD M1-10 FCU 1-19 M 29 .RCP J PT PT PS 31 LS LS 29 34 23 C C M1-12 H 27 J SD T 8 2 18 114 IG AV AV12 S 16 4 TYPICAL 15 26 RP-GP-1-3 25 20 21 TV CC IG C18 S 110cd SV SV 75cd P S IG 75cd AV SV AV13 CCTV M CUH RP-AD-1-2 1-5 33 T 75cd 4 CROSS +18" AFF OVER MD TYP. D C3 S 18 14 C2 P MD C17 IG S C1 DC EF 1-5 M 3 E7.00 WP,GFI 15 1 GFI WP 15 CC TV WP V PTZ T 23 CC FUTURE EQUIPMENT 5 20,22,24 OHD CRE PT PT WP GFI RE RE DC DC S 30 J 34 PT ED M DC MCC-M-B CC TV 26 RCP CP J CC TV 20 ALL GENERAL POWER CIRCUITS EMANATE FROM PANEL 'RP-AD-1-1', U.N.O. CIRCUITS ARE DESIGNATED WITH NO ALPHABETICAL PREFIX. 15,17,19 CRE MD S 30 CP 1 / E2.11A 29 PT RE DC SEE C MATCHLINE ALL GENERAL POWER CIRCUITS IN SCENE SHOP EMANATE FROM PANEL 'RP-AD-1-2', U.N.O. CIRCUITS ARE DESIGNATED WITH NO ALPHABETICAL PREFIX 34 Halvorson and Partners 1 CC TV 6 CCTV 6.2 GROUND FLOOR POWER AND SYSTEMS PLAN AREA B WP PTZ 26 18'-0" AFG ENLARGED GROUND FLOOR NORTH ENTRY Sheet 1/4" = 1'-0" E2.11B NORTH Copyright © 2010 Perkins+Will 5 4 3 2 1 4 3 2 1 2" 5 KEYED NOTES GENERAL NOTES 1" 1/2" 0 D 16 ALL VISUAL FIRE ALARM DEVICES TO BE FURNISHED WITH FIELD ADJUSTABLE SETTINGS, INITIALLY SET AT VALUES AS INDICATED. ADJUST SETTINGS BASED ON FIELD TESTING AS REQUIRED. 1 IT CONCENTRATOR TO SERVE ROOM 341. 2 IT CONCENTRATOR TO SERVE ROOMS 343, 344, 346 AND CIRCULATION DESK. 2. SMOKE DETECTORS FOR DOOR HOLDERS RELEASE SHALL BE INSTALLED WITHIN 5' FROM THE CENTERLINE OF THE DOOR OPENING. 3 CABLING FOR ALL VOICE/DATA OUTLETS IN ROOM 336 (NORTH) TO BE ROUTED TO MDF DIRECTLY. NO CONCENTRATOR REQUIRED. 4 3. ALL GENERAL POWER CIRCUITS ON THIS DRAWING DESIGNATED WITH NO ALPHABETICAL PREFIX, EMANATE FROM PANEL 'RP-GP-3-1' OR 'RP-GP-3-2' AS INDICATED BY DEMARCATION LINES. MLC - MOTORIZED SHADES CONTROLLER. PROVIDE (1) 120V, 1 PHASE CIRCUIT. CONNECT TO PUSHBUTTON SWITCHES LOCATED BEHIND LIBRARIAN DESK IN MEDIA CENTER OR FOR OTHER ROOM LOCATIONS AS INDICATED ON FLOOR PLAN. 1. Proposed New Jones HS NIC KEYED NOTES 4. INSTRUCTORS STATION POWER AND DATA DEVICE TO BE MOUNTED APPROXIMATELY 5'0" FROM WALL. REFER TO DETAIL 1 ON SHEET E5.03 FOR EXACT LOCATION. TYPICAL OF ALL CLASSROOMS, WORLD LANGUAGE LABS AND ART CLASSROOMS. 6 REFER TO DETAIL 1 AND 2 ON SHEET E5.03 FOR ELEVATIONS OF TYPICAL FRONT AND REAR WALL, DEVICE LOCATIONS FOR ALL CLASSROOMS AND COMPUTER/WORLD LANGUAGE LABS. ALL COMPUTER CIRCUITS DEVOTED "CXX" EMANATE FROM PANELS 'RP-CP-3-2' OR 'RP-LP-C-3-3' AS INDICATED ON DRAWING BY DEMARCATION LINES. 5. ALL EMERGENCY POWER DENOTED AS "EXX" EMANATE FROM PANEL 'E-LP-3'. 6. 7 ALL EXTERIOR CCTV CAMERAS SHALL BE SURFACE MOUNTED UNDER THE CANOPY. REFER TO TYPICAL CCTV DETAILS. 7. ALL INTERIOR CCTV CAMERAS SHALL BE CEILING MOUNTED WHERE POSSIBLE. REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. 8. SEE ENLARGED ELECTRICAL PLANS SHEET E7.01 FOR ELECTRICAL EQUIPMENT (PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) LOCATED IN ELECTRICAL ROOMS. 9. DIV. 16 CONTRACTOR SHALL PROVIDE STEP-DOWN TRANSFORMER 120V-240V FOR DOOR HARDWARE WHEN NOT FURNISHED BY DOOR HARDWARE MANUFACTURER. PROVIDE TRANSFORMER IN ENCLOSURE WITH REMOVABLE COVER AND SAFETY DISCONNECT SWITCH. INSTALL TRANSFORMER IN ACCESSIBLE LOCATION ABOVE THE CEILING. WHEN TRANSFORMER IN INSTALLED IN PLENUM RATED CEILING - PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. 10. ALL CCTV CAMERAS LOCATED IN LIBRARY/MEDIA CENTER ARE CONNECTED DIRECTLY TO DVS RACKS IN MDF ROOM, NO CRE REQUIRED. 11. ALL 480/3ø OR 277/1ø CIRCUITS DESIGNATED WITH CIRCUIT NUMBER "MXX" EMANATE FROM PPH-M-3. 9 PROVIDE FLUSH WITH FINISHED FLOOR BOXES FOR POWER AND DATA CONNECTIONS TO POWERED FURNITURE. INSTALL CONDUITS IN THE FLOOR SLAB TO THE NEAREST WALL AND STUB IN ACCESSIBLE CEILING SPACE. COORDINATE EXACT LOCATIONS OF THE BOXES WITH FURNITURE LAYOUT. WHEN FURNITURE IS LOCATED ADJACENT TO THE WALL, WALL MOUNTED BOXES LOCATED 12" AFF WITH WHIP INSIDE THE FURNITURE SHALL BE PROVIDED. PROVIDE SEPARATE COMPARTMENTS FOR DATA, NORMAL POWER, AND ISOLATED GROUND POWER. PROVIDE COMPLETE POWER AND DATA SYSTEMS WITHIN FURNITURE - INCLUDING POWER/DATA OUTLETS, BACKBOXES, CONDUIT, AND WIRING. MAKE ALL FINAL CONNECTIONS ALL DEVICES TYPE, LOCATION, CONDUIT, AND ROUTING SHALL BE COORDINATED WITH FURNITURE SUPPLIER. 11 ALL ELECTRICAL DEVICES, DISCONNECT SWITCHES, JUNCTION AND PULL BOXES LOCATED ABOVE THE CEILING. RESPECTIVE CONDUIT AND WIRING INSTALLATION SHALL COMPLY WITH CEC REQUIREMENTS FOR INSTALLATION IN AIR HANDLING PLENUM SPACES. VERIFY EXACT EXTENT OF SUCH SPACES WITH DIVISION 15 DRAWINGS AND CONTRACTOR. LOCATE INTERCOM PAGING SPEAKERS IN STAIRWELLS ON EVERY LANDING. 12. REFER TO EA-XXX SERIES DRAWINGS FOR EXACT LOCATIONS OF A/V DEVICES. PROVIDE ALL CONDUIT AND BACKBOXES AS SHOWN ON THESE DRAWINGS. 13. 12 RECEPTACLE CIRCUIT IN STAIRWELL EMANATE FROM PANEL RP-GP-4-3 LOCATED ON 4TH FLOOR. 13 RECEPTACLE CIRCUIT IN STAIRWELL EMANATE FROM PANEL RP-GP-1-2 LOCATED IN GROUND LEVEL. 14 IT CONCENTRATOR TO SERVE ROOMS 336 (SOUTH) AND 339. 15 RECEPTACLE CIRCUIT IN STAIRWELL EMANATE FROM PANEL RP-GP-1-3 LOCATED IN GROUND LEVEL. 32 (5) 2" C.'S FOR LOW VOLTAGE SYSTEMS. INTERFACE WITH EXISTING JONES HIGH SCHOOL DOWN TO BASEMENT. UTILIZE EXISTING SHAFT. 33 MDF ROOM - HEADEND FOR IT,SECURITY, CCTV, TV. 9 William Jones College Preparatory High School FIRE ALARM RETURN RISERS. 20 BOOK DETECTION SYSTEM CONNECTION. PROVIDE ADDRESSABLE RELAY MODULE WITHIN 3' FROM SHUTTER CONTROLLER. PROVIDE INTERFACE TO BUILDING FIRE ALARM CONTROL PANEL TO RELEASE SHUTTERS IN CASE OF FIRE ALARM. UPDATE HARDWARE, SOFTWARE, AND ANNUNCIATOR AS REQUIRED. POWER SUPPLY BY DOOR HARDWARE MANUFACTURER - TYPICAL. COORDINATE WITH DOOR HARDWARE SUPPLIER. 19 8 31 PROVIDE (2) JUNCTION BOXES AND 3/4" SLEEVES FOR POWER AND DATA CONNECTIONS TO CCTV CAMERAS FROM CCTV POWER SUPPLY (PS) AND CCTV REMOTE ENCLOSURE (CRE). REFER TO TYPICAL CCTV DETAILS, DRAWING E5.07. WHEN CEILING DRYWALL SOFFIT DOES NOT ALLOW MOUNTING OF BOXES RIGHT AT THE PERIMETER - LOCATED THEM AWAY FROM EXTERIOR WALL IN ACCESSIBLE CEILING SPACE. 18 AUTOMATIC PLUMBING FIXTURES, INCLUDING FAUCET OR FLUSH VALVE: INSTALL AND WIRE 120/24V TRANSFORMERS FURNISHED BY DIV. 15 CONTRACTOR AS PART OF PLUMBING FIXTURE PACKAGE. PROVIDE SAFETY DISCONNECT SWITCHES. INSTALL TRANSFORMERS IN AN ENCLOSED JUNCTION BOXES IN ACCESSIBLE LOCATION ABOVE THE CEILING ACCESS PANELS. VERIFY EXACT LOCATION IN FIELD. PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR COMPLETE AND OPERATIONAL SYSTEM. COORDINATE ACCESS PANEL WITH ARCHITECT AND GENERAL CONTRACTOR. 10 PROVIDE (1) UL LISTED "120V TO 24V AC" CCTV POWER SUPPLY FOR UP TO 3 OUTDOOR FIXED CAMERAS AND (1) POWER SUPPLY FOR EACH PTZ OUTDOOR CAMERA. EACH OUTPUT SHALL BE RATED FOR 3.5 AMPS. POWER SUPPLY SHALL BE AS MANUFACTURED BY ALTRONIX ALTV24 SERIES OR APPROVED EQUAL. DISTANCE FROM POWER SUPPLY TO CAMERA SHALL NOT EXCEED 75 FT. COORDINATE EXACT LOCATIONS IN FIELD WITH ARCHITECT. WHEN POWER SUPPLY IS LOCATED ABOVE PLENUM RATED CEILINGS, PROVIDE CEC COMPLIANT PLENUM RATED ENCLOSURE. 17 5 KEYED NOTES LOW VOLTAGE SHAFT UP TO FOURTH AND FIFTH FLOOR FOR CONDUIT ROUTING TO SERVE FOURTH AND FIFTH SOUTH MISCELLANEOUS LOW VOLTAGE SYSTEMS. 700 South State Street Chicago, IL 60605 D 21 LOW VOLTAGE SHAFT FOR VERTICAL ROUTING OF MISCELLANEOUS LOW VOLTAGE SYSTEMS CABLING IN CONDUIT FROM MDF ROOM TO 1, 2 FLOORS NORTH, AND 6,7,8 FLOORS NORTH AND SOUTH. 22 SMOKE DETECTORS TO BE LOCATED IN EVERY BEAM POCKET. ARCHITECT 23 DOOR TO BE UNLOCKED FROM REMOTE LOCATION. REFER TO DRAWING E2.11A, KEYED NOTE 34. 24 RECEPTACLES TO BE MOUNTED HORIZONTALLY IN CURB. 25 ZONE ABOVE ACCESSIBLE CEILING FOR POWER AND LOW VOLTAGE SYSTEMS PULL BOXES TO ENTER/EXIT IT SHAFT AND ELECTRICAL ROOM. 26 120V 1 PHASE CONNECTION TO FIRE ALARM POWER SUPPLY. 27 TWO COMPARTMENT BOX: PROVIDE AT LOCATION OF EXISTING STUB UPS FLUSH WITH FLOOR BOX WITH REGULAR, AND ISOLATED GROUND (IG) POWER OUTLETS FOR LIBRARY DESK EQUIPMENT. COORDINATE COVER TRIM/FINISH WITH ARCHITECTURAL FLOOR FINISHES IN THIS AREA. 28 CIRCUIT SHALL EMANATE FROM PANEL RP-GP-2-1. 29 MOTORIZED PROJECTION SCREEN AND CONTROL SWITCH. PROVIDE CONDUIT AND WIRING BETWEEN SCREEN CONTROLLER AND CONTROL SYSTEM AS REQUIRED BY MANUFACTURER FOR COMPLETE AND OPERATIONAL SYSTEM. REFER TO EAX.XX SERIES DRAWINGS. PROVIDE CONDUIT SIZE AS INDICATED. FOR CABLING TO A/V EQUIPMENT RACK. PROVIDE ISOLATION BUSHINGS FOR CONDUIT ENTERING TO THE RACK. 330 North Wabash Ave. Suite 3600 Chicago, IL 60611 t 312.755.0770 f 312.755.0775 www.perkinswill.com ASSOCIATE ARCHITECT 30 The Architects Enterprise, Ltd. 230 West Monroe St. Suite 2205 Chicago, IL 60606 t 312.424.0330 f 312.424.0111 www.taeltd.com FIRE-RATED POKE DEVICE WITH VOICE/DATA OUTLETS FOR LIBRARY DESK EQUIPMENT. COORDINATE COVER TRIM/FINISH WITH ARCHITECTURAL FLOOR FINISHES IN THIS AREA. INSTALL 1"C. VOICE/DATA CONDUIT IN CEILING SPACE BELOW. COORDINATE LOCATION OF THE FLOOR PENETRATION WITH STRUCTURAL ENGINEER. STRUCTURAL ENGINEER Halvorson and Partners 9 8.7 8 Chicago, IL STRUCTURAL ENGINEER Drucker Zajdel Structural Engineers 14 13 12 11.6 11 10.7 10 7 9.8 C P GFI K T 12 12 T 12 T J GENERAL POWER CIRCUITS EMANATE FROM PANEL 'RP-GP-3-1' HD 18 GFI 24 STAIR 01 GENERAL POWER CIRCUITS EMANATE FROM PANEL 'RP-GP-3-2' S P IG C7 D TV P 29 3ST4 SCREEN CLG. MOUNTED J J D T 23 P D IG C11 T IG IG C7 C11 IG C9 1 IG C5 CLG MTD IG C24 PR IG C9 1 IG IG 75cd 1 C3 1 C25 SV LCE LCE 9 P 28 B PPH-M-2 31 FCU S4-3 M 11 23 S CC TV 18 11 M 4 M 25 T TYPICAL D P IG C21 M D 3 S IG 1 P IG C23 75cd SV 4 339 25 MLC C2 IG C6 IG C13 IG C19 COMPUTER LAB S 16 75cd SV FCU 3-1.2 M M3 IG IG C7 C9 IG C8 D IG IG C10 D IG C10 C12 P D GFI 9 IG C12 P 6 PS J 18 SD 23 MLC 15 IG C4 CCTV IG C4 WORKROOM S 5 P MD 341A 3 4 11 J 4 29 3 E7.01 C C TV 2 IG C18 5 DF IG C11 S MD M P IG C15 IG C11 P 11 IG D C13 IG C15 P IG D C17 IG C17 IG C13 IG C21 P D IG C21 M T 18 CLG MTD IG IG C23 C28 PR IG C19 P 9 D IG TYP. C25 IG C19 16 WP GFI M T 16 C C SV WP 110cd EF3-1 STARTER TV S LIBRARY/MEDIA CENTER P IG C23 S 336 IG C2 IG C25 4 M M 16 WP PTZ 18 16 T WP GFI 75cd TYPICAL T D IG C29 P 9 P IG C29 13 SV D IG C4 FCU 3-5.2 M7 M IG C2 IG C27 MD 75cd SV S S 24 TYP IG C31 M IG C6 T 14 IG C6 WP S P SV WP 110cd T 14 337 IG C14 P S P IG C14 S 12 M T 12 Naperville, IL SD 28 J HD 20 J J J 7 14 T TLTT 305 P 306 SD SV 11 17 IT SHAFT #2 17 H 19 P S 9 10 3 S TYPICAL (5) 2" C.'S CORRIDOR 300 9 MD D 22 ELEC SD 307 15 26 SV 75cd 27 T Bill Robertson Pool Design/Build, Inc. Northville, MI C.9 19 RA C.8 A S C.7 MD 25 S S P P 25 11 SV 31 Revisions P FOR REFERENCE ONLY 11 RCP B.2 75cd 75cd M M9 P IG C18 TYP. IG C18 P IG C20 M T 10 T 31 13 S IG C20 IG C22 8 A.4 M M T BULLETIN NO 52 BULLETIN NO. 1 ADDENDUM 3 ISSUED FOR PERMIT ISSUED FOR GC BID ISSUED FOR 90% CD ISSUED FOR 60% CD ISSUED FOR DESIGN DEVELOPMENT 1 ISSUED FOR SCHEMATIC DESIGN NO ISSUE RCP M 10 9 8 7 6 5 4 3 2 FCU 3-5.3 MD 9 S B SV SV IG C10 M 10 NATATORIUM CONSULTANT 13 IG C16 T Talaske Oak Park, IL B.8 31 MD TYPICAL ACOUSTIC / AUDIO-VISUAL CONSULTANT B IG C10 IG C12 J Chicago, IL 17 S SD W 30cd E7 J FCU 3-16 M13 RA Schuler Shook D.1 V M THEATER DESIGN CONSULTANT 3ST2 28 J VEST 15cd 30cd 32 21 H GFI V 14 S 24 STAIR 02 1 E7.01 M13 RCP IG C8 SCREEN CLG. MOUNTED 4 30cd P FCU 3-7 TV MD IG C22 IG C12 IG C16 M HD 22 GFI 24 M Cini-Little International, Inc. 27 TV T TV S SV 75cd C C C C 12 C C FOOD SERVICE CONSULTANT RA R DD S P ERU-1,2 TV CC 8 M Willowbrook, IL 13 M S P Jenkins & Huntington, Inc. C CLG MTD IG C26 PR 29 EXTERIOR TERRACE 18 .RCP J PT PT PS 23 LS LS 25 DF DF IG C31 MD 8 P IG C8 75cd WP GFI 17 17 TYPICAL FOR 2 VERTICAL TRANSPORTATION CONSULTANT SD 302 P Chicago, IL D.8 MD SV DC SD MD M11 J 30cd V MENS J LANDSCAPE ARCHITECT Site Design Group, Ltd. 10 TYP. IG C4 J J Chicago, IL 17 DF SV CR 75cd 17 29 P IG C27 9 TYP. DC C24 IG 30 MD J J S 13 S M J S S J J T 14 30cd V P T T Date T 8 GENERAL POWER CIRCUITS EMANATE FROM PANEL 'RP-GP-3-2' 08/24/10 DATE 03/06/13 PBC Project Wm Jones College Prep H S PBC Contract No. Perkins+Will Job No. A C:\Users\jlefeu\Documents\PEL_JCP_R11_ELEC-CENTRAL_jlefeu.rvt 04/17/13 09/14/11 06/22/11 05/25/11 05/25/11 04/01/11 01/11/11 10/26/10 Sheet Information M GENERAL POWER CIRCUITS EMANATE FROM PANEL 'RP-GP-3-1' 4/17/2013 4:47:33 PM Terra Engineering C 303 J J J J 33 13 MD WP S P P IG C22 11 J J D P T 18 17 25 V/D MD 10 TYP. S 29 12 14 S CIVIL ENGINEER ELEV LOBBY 14 T T J J 301 IG C22 29 CCTV 13 SCREEN 9 9 J J J J T T 14 J J WOMENS TLT 13 1 RA SD P J J 9 M MLC MLC 14,16 TV DF M3 M 5 IT SHAFT #3 75cd 8,10,12 SV 4 S PPH-M-3 23,25,27 EF 3-1 FCU 3-5.5 IG C26 SV 75cd M 4 M11 7 FCU 3-2 SD CCTS. 8,10,12,14,16 FCU 3-3 SD 347 COPIER IG C16 344 M AV/MDF S 20 SV 75cd T V 30cd 6 P 346 P FCU S1-5 5 J J CMT GFI 26 K TLT PPH-M-2 28 FCU S P S1-6 M PPH-M-2 24 STORAGE 9 9 GFI 7 4 E7.01 IG C14 IG C4 IG C8 P S P IG C14 343 RA C9 C7 COLLEGE C3RESOURCE CTR MD IG C19 6 D IG C2 MD IG C5 IG C6 P CIRCUITS DENOTED "CXX" EMANATE FROM PANEL 'RP-CP-3-2' GFI 5 6 TV IG C23 ELEC CC TV 11 M 25 IG C13 S 75cd IG C21 IG C20 9 3 T 1 FCU M7 3-5.1 M1 V IG C17 IG IG FCU 3-4 8 IG C1 IG C1 13 IG C15 341 IG C5 IG C3 11 PROF LIBRARY T 25 P IG C17 14 M M1 SV 75cd P MD IG C5 FCU 3-1.1 PT SD RCP TV RA ED PT C C 20 ED J PS S SD D 1-1/4" C. TYPICAL 12 VSS AMM WF AMM P IG C15 C2 3 4 S IG M 2 MD MOTORIZED SCREEN SWITCH 23 CIRCUITS DENOTED "CXX" EMANATE FROM PANEL 'RP-CP-3-1' 10 J GFI 24 24 J CCTV IG C1 M T 23 1 S 9 CCTV IG 10 CCTV 5 C1 STAIR 04 M 4 9 TYPICAL ACE CIRCUITS DENOTED "CXX" EMANATE FROM PANEL 'RP-CP-3-1' CCTV CIRCUITS DENOTED "CXX" EMANATE FROM PANEL 'RP-CP-3-2' S J J HD 16 J 3ST1 J J J J Chicago, IL E CCTV S CMT GFI 10 TYPICAL 7 CCTV TYPICAL 7 MECHANICAL ENGINEER Primera Engineers SEE 14.4 MATCHLINE 15 1 / E2.13B Naperville, IL Drawn 05265 022093.00 DWM Checked DNT Approved RGL Title A A THIRD FLOOR POWER AND SYSTEMS PLAN AREA A Sheet 1 THIRD FLOOR POWER AND SYSTEMS PLAN - AREA A NORTH E2.13A 1/8" = 1'-0" Copyright © 2010 Perkins+Will 5 4 3 2 1