NORMAL OPERATION / MANUAL TESTS
CTXR Series
INSTRUCTION MANUAL
OP – PANEL INDICATORS / OPERATION:
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
P/N 787625774
06112004
GREEN - Status: Solid indicates system normal and AC power is on.
NOTE: To reset/cancel a test, simply press the green button once during any test.
1 Press: perform a 5/sec brief test, AC power is disabled and all lamps are operating from battery only.
2 Presses: perform a 1/min test, AC power is disabled and all lamps are operating from battery only.
3 Presses: perform a 30/min test, AC power is disabled and all lamps are operating from battery only. The
system allows only one 30/min test each 24/hr period.
CONTINUOUS MONITORING: The system monitors the following
1. Battery
2. Lamps
3. Charger
4. Transfer function
OPTIONAL FACTORY EQUIPPED ITEMS:
Re-strike Time Delay: After a power failure and power is restored, the lamp will remain on for a 15/min period.
TROUBLE INDICATIONS / TROUBLESHOOTING
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
OP – PANEL INDICATORS
TEST
Button
REMOTE SENSOR
(IF EQUIPPED)
Ø
GREEN - Status: solid indicates system normal and AC power is on and flashes
during any manual/auto test cycle.
Ø
RED – CHARGER FLASHING: a charger failure requires the power supply board to
be replaced.
Ø
RED – BATTERY FLASHING: battery may be disconnected or if it is connected a
replacement is needed.
Ø
RED - LAMP FLASHING 2X/SEC: indicates that a lamp(s) has failed
Ø
RED - LAMP FLASHING 4X/SEC: indicates the transfer function has failed and the
charger board needs to be replaced.
WIRING INFORMATION
Warning: Electrical Shock Potential!! Do not attempt to install, maintain or re-lamp without
disconnecting all power. Failure to disconnect power can result in electrocution, shock or severe burns.
§
§
§
§
LAMP
Cables
BATTERY
Cable
REMOTE
Lamp Load
L1
§
§
Do not use this equipment outdoors.
Do not mount near gas or electrical heater.
Equipment should be mounted in locations and at heights where it will not be readily subjected to
tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
Do not let power supply cords touch hot surfaces.
Do not use this equipment for other than intended use.
CAUTION: Halogen cycle lamp(s) are used in this equipment.
To avoid shattering: Do not operate lamp in excess of rated voltage, protect lamp against abrasion
and scratches and against liquids when lamp is operating, dispose of lamp with care.
L2
Transformer Inputs:
BLACK – 120V
WHITE – Common
RED – 277V
TRANSFORMER
Cables
POWER SUPPLY BOARD
776 S. Green Street – Tupelo, MS 38804 – ph. 662.842.7212 –fax. 662.680.6619
§
§
§
§
Halogen cycle lamps operate at high temperature.
Do not store or place flammable materials near lamp.
Use caution when servicing batteries.
Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in eyes, flush eyes with
fresh water and contact a physician immediately.
SAVE THESE INSTRUCTIONS
INSTALLATION
INSTRUCTIONS WALL (BACK) MOUNT
Ø
Ø
Ø
Ø
Ø
Ø
NORMAL POWER-UP SEQUENCE
SLIDING TABS
Open front cover; slide the four tabs on side up and down; see Fig. 1.
Remove knockout hole in back plate located behind the battery - loosen screws holding
battery in place, see Fig. 2 and remove battery.
Route AC service wires through knockout hole in back plate, mount back plate to outlet box
using screws. See Fig. 3.
Make AC service connection at this time. See OPERATING INSTRUCTIONS.
Reconnect/verify at this time that the battery is connected to the BAT location on the main
PCB.
Replace the cover and secure with 4 tabs, see Fig. 1.
1.
2.
3.
4.
Make AC service connection at this time. Observe wire colors:
§
Black wire – 120 volt input,
§
White wire – common for 120 or 277 volt inputs,
§
Red wire – 277 volt input,
Make supply connections and then push connections into outlet box.
Plug the battery connector to power supply board.
Energize AC power to equipment and check the unit using the POWER-UP SEQUENCE as a
guide.
Leave AC connected for a minimum of 168 hours before performing any extended testing.
It is necessary to reset the unit after battery
replacement.
To reset the unit: hold the green indicator light
down for 6/sec.
~0/sec
FIGURE 1
OPERATING INSTRUCTIONS
IMPORTANT NOTE
APPLY
INPUT
POWER
BATTERY
SCREWS
IF ALL
RED DIAG
LEDS ARE
FLASHING
IF THE
BATTERY
INDICATOR
IS FLASHING
~7/sec
Y
IT IS IMPORTANT, THEN SOME ERRORS MAY OCCUR. THE CONFIGURATION MUST
MATCH WHAT YOU HAVE CONNECTED EXACTLY.
UNIT
MAY BE RECONFIGURED
REMOTE LAMP HEAD HOOKUP INSTRUCTIONS
FIGURE 3
1.
2.
3.
The total watts on L1 or L2 may not exceed 12W for all CTXR units.
The remote lamp connection (L3) may not exceed the output rated maximum minus the
output on L1 & L2.
Do not short the lamp leads to ground.
Failure to properly follow conditions stated above may result in
damage to the unit.
VERIFY
BATTERY
CONNECTED
TO REMEMBER THAT THIS CONFIGURING ONLY AFFECTS WHAT IS CHECKED BY THE
DIAGNOSTICS, NOT WHAT IS ACTIVATED. IF YOU POPULATE LAMPS THAT YOU HAVE NOT
CONFIGURED TO BE CHECKED FIELD CONFIGURABLE REMOTES:
UNUSED PRIMARY WIRES MUST BE CAPPED TO PREVENT SHORTING OR
ELECTRICAL SHOCK.
NOTE: Observe output rating and do not exceed maximum load
combining all lamp connections.
FIELD CONFIGURABLE REMOTES:
Presses
Description of Configuration
Internal Lamps only DEFAULT
Ø 5
Ø 6
Internal and Remote
Ø 7
Remote Lamps only
N
WITHIN - 7/sec
GREEN STATUS - ON
KNOCKOUT
REMOVE
INPUT POWER
IMMEDIATELY
N
BATTERY
FIGURE 2
Y
~25/sec
Ø
Press/hold the green test button for 6/sec until the green light goes out.
Ø
As soon as the green indicator comes back on, start pressing the number of times for the
desired configuration. You must be completed pressing before it starts flashing/Green auto
test within ~10/sec or it may not have read your presses correctly.
Y
N
WITHIN – 20/sec
GREEN LED - FLASH
IT PERFORMS 5/sec
AUTO-DIAG TEST
AUTO-DIAG TESTING:
Ø
Ø
Ø
TO
NORMAL
OPERATION
The unit automatically performs diag testing at each power-up and initializes itself.
The system is capable of detecting the following failures: Lamps, Battery, Charger and
Transfer function.
The unit’s monthly 30/min discharge testing is randomized. Within each 30/day period
thereafter the unit shall perform the 30/min test.