Untitled - Pacific Construction Services

advertisement
ADDENDA NO. 1
AUGUST 26, 2008
USPS FACILITY
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
COMM. NO. 1597-104
WHEREAS THIS ADDENDA CONFLICTS WITH THE INFORMATION CONTAINED IN THE
DRAWINGS AND/OR SPECIFICATIONS, THIS ADDENDA SHALL GOVERN.
Drawings:
S.1 – General Structural Notes. Amend the first paragraph, the first sentence, titled
“Testing Laboratory Services” to read as follows: The Contractor shall employ…..
Specifications: Delete Section 16510 – Interior Lighting and Section 16520 – Exterior Lighting dated
9/17/2007 and replace same with Section 16510 – Interior Lighting, pages 1 thru 17, and
Section 16520 – Exterior Lighting, pages 1 thru 7, dated 2/12/2008. Specification Section
00010 – Table of Contents, revised and attached.
Drawings:
T1.1 – Title Sheet, Schedule of Drawings, Delete Drawings E1.0, E1.1, E1.2 and E1.4.
Add Drawings E001, E101, E201 and E301 identified as Revision 1 and dated 9/5/2008.
Drawings/
Specifications: A1.1 – The pre-engineered canopy shall be all inclusive including the required foundation
system. Refer to attached Specification Section 13600 – Pre-Engineered Canopy.
Specification:
Refer to attached Spectification Section 09710 – Epoxy Flooring and Wall Coatings.
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
DOCUMENT 00010 - TABLE OF CONTENTS
INTRODUCTORY INFORMATION
Document
Document
Document
Document
00001
00002
00007
00010
Project Title Page
Project Directory
Seals Page
Table of Contents
SCHEDULE, CLAUSES AND ATTACHMENTS, AND SOLICITATION REQUIREMENTS
Issued separately by U.S. Postal Service.
SPECIFICATIONS
DIVISION 1 - GENERAL REQUIREMENTS
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
01110
Summary of Work
01110_A Summary of Work – Attachment A
01120
Contract Documents
01150
Environmental Procedures
01150_A Environmental Procedures – Attachment A
01150_B Environmental Procedures – Attachment B
01320
Construction Progress Documentation
01330
Submittal Procedures
01330f
Schedule of Values
01450
Quality Control
01500
Temporary Facilities and Controls
01600
Product Requirements
01700
Execution Requirements
01780
Closeout Submittals and Training
DIVISION 2 - SITEWORK
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
02220
02230
02300
02315
02370
02510
02530
02554
02630
02634
02743
02753
02765
02810
02917
02920
02930
02935
Site Demolition
Site Clearing
Earthwork
Excavation and Fill
Erosion and Sedimentation Control
Water Distribution
Sanitary Sewerage
Gas Distribution
Storm Drainage
Storm Drainage Manholes
Bituminous Concrete Pavement
Plain Cement Concrete Pavement
Pavement Markings
Irrigation Systems
Soil Preparation
Lawns and Grasses
Exterior Plants
Plant Maintenance
DIVISION 3 - CONCRETE
Section
Section
Section
03100
03200
03300
Concrete Forms and Accessories
Concrete Reinforcement
Cast-In-Place Concrete
00010 - 1
USPS SSBD SPECIFICATION
Issued Date: 9/17/2007
TABLE OF CONTENTS
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
DIVISION 4 - MASONRY
Section
Section
Section
04100
04210
04220
Masonry Mortar and Grout
Clay Unit Masonry
Concrete Unit Masonry
DIVISION 5 - METALS
Section
Section
Section
05120
05500
05520
Structural Steel
Metal Fabrications
Handrails and Railings
DIVISION 6 - WOOD AND PLASTICS
Section
Section
Section
Section
06100
06170
06175
06200
Rough Carpentry
Wall Protection
Wood Trusses
Finish Carpentry
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
Section
Section
Section
Section
Section
Section
07190
07210
07310
07620
07840
07900
Water Repellents
Building Insulation
Shingles
Sheet Metal Flashing and Trim
Firestopping
Joint Sealers
DIVISION 8 - DOORS AND WINDOWS
Section
Section
Section
Section
Section
Section
Section
Section
08100
08210
08310
08360
08380
08410
08710
08800
Metal Doors and Frames
Wood Doors
Access Doors and Panels
Sectional Overhead Doors
Impact Traffic Doors
Aluminum Windows, Entrances and Storefronts
Door Hardware
Glazing
DIVISION 9 - FINISHES
Section
Section
Section
Section
Section
Section
Section
Section
09110
09250
09300
09510
09650
09680
09710
09900
Non-Load Bearing Wall Framing
Gypsum Board
Tile
Acoustical Ceilings
Resilient Flooring
Carpet
Epoxy Flooring and Wall Coatings
Painting
DIVISION 10 - SPECIALTIES
Section
Section
Section
Section
Section
Section
Section
Section
Section
10125
10170
10200
10260
10350
10435
10436
10520
10810
Bulletin Boards
Plastic Toilet Compartments
Louvers and Vents
Corner Guards
Flagpoles
Exterior Signage
Miscellaneous Signage
Fire Protection Specialties
Toilet Accessories
00010 - 2
USPS SSBD SPECIFICATION
Issued Date: 9/17/2007
TABLE OF CONTENTS
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
DIVISION 11 - EQUIPMENT
Section
11160
Loading Dock Equipment
DIVISION 12 - FURNISHINGS
Section
Section
12358
12490
Miscellaneous Casework
Window Treatments
DIVISION 13 - SPECIAL CONSTRUCTION
Section
Section
Section
Section
13600
13702
13851
13900
Pre-Engineered Canopy
Intrusion Detection System
Fire Alarm
Fire Suppression
DIVISION 14 - CONVEYING SYSTEMS
Not Used.
DIVISION 15 - MECHANICAL
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
15050
15080
15100
15410
15480
15736
15767
15769
15810
15830
15833
15850
15900
15950
Basic Mechanical Materials and Methods
Mechanical Insulation
Building Services Piping
Plumbing Fixtures
Water Heaters
Split-System Air Conditioning Units
Unit Heaters
Electric Heating
Ducts
Ceiling Fans
Centrifugal Fans
Air Outlets and Inlets
HVAC Instrumentation and Controls
Testing, Adjusting, and Balancing
DIVISION 16 - ELECTRICAL
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Section
Appendix A
16050
16120
16130
16140
16210
16274
16410
16441
16510
16520
16582
16705
16720
Basic Electrical Materials and Methods
Conductors and Cables
Raceway and Boxes
Wiring Devices
Electrical Utility Services
Power Transformers
Enclosed Switches
Panelboards
Interior Luminaires
Exterior Luminaires
Lighting Controls
Communications Cable and Equipment
Intercommunication System
Geotechnical Subsurface Investigation
END OF DOCUMENT
USPS SSBD Specifications issued: 9/17/2007
Last revised: 9/17/2007
00010 - 3
USPS SSBD SPECIFICATION
Issued Date: 9/17/2007
TABLE OF CONTENTS
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
SECTION 09710 - EPOXY FLOORING AND WALL COATINGS
A.
SUMMARY
1.
B.
SUBMITTALS
1.
2.
3.
C.
Product Data: Required
Samples: Required
Color: Per USPS Non-Retail Standard Finishes schedule
QUALITY ASSURANCE
1.
2.
D.
Epoxy flooring and wall coating in Toilet Rooms and Kitchens.
Applicator to be certified and licensed by the flooring manufacturer.
Field samples to be approved and serve as minimum acceptable standards for finished work.
MANUFACTURERS
1.
Stonhard:
a.
b.
E.
Floor Product: Stonclad GS
Wall Product: Stonglaze VSC
2.
Crossfield Products, Dex-O-Tex
3.
General Polymers
4.
Florock
5.
Dur-A-Flex Inc.
INSTALLATION
1.
Apply coating systems in accordance with manufacturer instructions for material and
substrate involved.
2.
Provide ample ventilation during application.
END OF SECTION
USPS Major Facilities Master Outline Specification issued: 1/17/2007
Last revised: 3/22/2007
09710 - 1
USPS MMOS
Issued Date: 1/17/2007
EPOXY FLOORING AND WALL COATINGS
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
SECTION 13600 – PRE-ENGINEERED CANOPY
PART 1 - GENERAL
1.1
SUMMARY
A.
Section includes prefabricated steel or aluminum canopies.
B.
ADA-ABA Accessibility Guidelines: U.S. Architectural & Transportation Barriers Compliance
Board's "Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and
Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines."
1.2
A.
PERFORMANCE REQUIREMENTS
Structural Performance: Canopy shall withstand the effects of gravity loads and the following
loads and stresses within limits and under conditions indicated according to ASCE/SEI 7:
1.
2.
B.
Thermal Movements: Allow for thermal movements from ambient and surface temperature
changes. Base calculations on surface temperatures of materials due to both solar heat gain and
nighttime-sky heat loss.
1.
1.3
Snow Loads: 25 psf.
Wind Loads: 20 psf.
Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 deg C),
material surfaces.
SUBMITTALS
A.
Product Data: For each type of product indicated. Include construction details, material
descriptions, dimensions of individual components and profiles, and finishes for canopy.
B.
Shop Drawings: For canopy. Include plans, elevations, sections, details, and attachments to other
work.
C.
Samples for Initial Selection: For canopy with factory-applied color finishes.
D.
Samples for Verification: For exposed finishes, in manufacturer's standard sizes.
E.
Delegated-Design Submittal: Canopy indicated to comply with performance requirements and
design criteria, including analysis data signed and sealed by the qualified professional engineer
responsible for their preparation.
F.
Welding certificates.
G.
Maintenance Data.
H.
Warranty: Sample of special warranty.
1.4
A.
QUALITY ASSURANCE
Welding Qualifications: Qualify procedures and personnel according to the following:
1.
2.
AWS D1.1/D1.1M, "Structural Welding Code - Steel."
AWS D1.2/D1.2M, "Structural Welding Code - Aluminum."
PRE-ENGINEERED CANOPY
13600 - 1
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
3.
B.
1.5
A.
1.6
A.
USPS NO. J80967
COMM. NO. 1597-104
AWS D1.3, "Structural Welding Code - Sheet Steel."
Regulatory Requirements: Comply with applicable provisions in the International Building Code
2006 Edition.
COORDINATION
Coordinate installation of anchorages. Furnish setting drawings, templates, and directions for
installing anchorages, including sleeves, concrete inserts, anchor bolts, and items with integral
anchors that are to be embedded in concrete or masonry. Deliver such items to Project site in
time for installation.
WARRANTY
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair finish
that fail in materials or workmanship within specified warranty period.
1.
Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1
A.
MATERIALS
Aluminum: Alloy and temper recommended by aluminum producer and manufacturer for type of
use and finish indicated, and as follows:
1.
2.
3.
Sheet: ASTM B 209 (ASTM B 209M).
Extruded Shapes: ASTM B 221 (ASTM B 221M).
Rolled Tread Plate: ASTM B 632/B 632M, Alloy 6061-T4 or Alloy 6061-T6.
B.
Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, commercial quality, G90 (Z275)
coating designation; mill phosphatized.
C.
Galvanized, Rolled Steel Tread Plate: ASTM A 786/A 786M, rolled from steel plate complying
with ASTM A 572/A 572M, Grade 55 (380); hot-dip galvanized according to ASTM A 123/A 123M.
D.
Steel Structural Tubing: ASTM A 500, Grade B.
E.
Steel Plates, Shapes, and Bars: ASTM A 36/A 36M.
F.
Steel Mechanical Tubing: ASTM A 513, welded steel mechanical tubing.
G.
Zinc-Coated (Galvanized) Steel: Hot-dip galvanized according to ASTM A 123/A 123M.
H.
Anchorages: Anchor bolts; hot-dip galvanized according to ASTM A 153/A 153M or ASTM F 2329.
2.2
A.
PREFABRICATED CANOPYS, GENERAL
General: Provide a complete, integrated set of mutually dependent components that form a
completely assembled, prefabricated canopy, ready for installation on Project site.
1.
Building Style: As indicated on Drawings.
PRE-ENGINEERED CANOPY
13600 - 2
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
2.3
USPS NO. J80967
COMM. NO. 1597-104
GENERAL FINISH REQUIREMENTS
A.
Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for
recommendations for applying and designating finishes.
B.
Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of
approved Samples and are assembled or installed to minimize contrast.
2.4
A.
FINISHES
Steel and Galvanized-Steel Factory Finish: Immediately after cleaning and pretreating, apply
manufacturer's standard two-coat, baked-on finish consisting of prime coat and thermosetting
topcoat.
1.
2.5
A.
Color and Gloss: As selected by Architect from manufacturer's full range.
ALUMINUM FINISHES
Color Anodic Finish: AAMA 611, AA-M12C22A42/A44, Class I, 0.018 mm or thicker.
1.
Color: As selected by Architect from full range of industry colors and color densities.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
B.
Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the
Work.
C.
Proceed with installation only after unsatisfactory conditions have been corrected.
END OF SECTION 13600
PRE-ENGINEERED CANOPY
13600 - 3
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
SECTION 16510 - INTERIOR LIGHTING
PART 1 - GENERAL
1.1
A.
SUMMARY
Section Includes:
1.
2.
3.
4.
5.
6.
Interior luminaires and accessories.
Emergency lighting units.
Exit signs.
Ballasts.
Lamps.
Luminaire accessories.
B.
Related Documents: The Contract Documents, as defined in Section 01110 - Summary of Work,
apply to the Work of this Section. Additional requirements and information necessary to
complete the Work of this Section may be found in other Documents.
C.
Related Sections:
1.
1.2
A.
B.
REFERENCES
American National Standards Institute (ANSI):
1.
ANSI C78.379 - Electric Lamps - Incandescent and High-Intensity Discharge Reflector
Lamps - Classification of Beam Patterns.
2.
ANSI C82.1 - Ballasts for Fluorescent Lamps - Specifications.
3.
ANSI C82.4 - Ballasts for High-Intensity Discharge and Low Pressure Sodium Lamps
(Multiple Supply Type).
National Electrical Manufacturers Association (NEMA):
1.
C.
A.
NEMA WD 6 - Wiring Devices-Dimensional Requirements.
National Fire Protection Association (NFPA):
1.
2.
1.3
Section 16050 - Basic Electrical Materials and Methods: Basic electrical methods.
NFPA 70 - National Electrical Code.
NFPA 101 - Life Safety Code.
SUBMITTALS
Section 01330 - Submittals Procedures: Procedures for submittals.
1.
Product Data: Provide dimensions, ratings, and performance data for each fixture specified.
2.
Assurance/Control Submittals:
16510-1
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
a.
B.
Manufacturer's Instructions: Indicate application conditions and limitations of use
stipulated by Product testing agency. Include instructions for storage, handling,
protection, examination, preparation, and installation of Product.
Section 01780 - Closeout Submittals: Procedures for closeout submittals:
1.
1.4
USPS NO. J80967
COMM. NO. 1597-104
Operation and Maintenance Data: Submit manufacturer's operation and maintenance
instructions for each type of fixture.
QUALITY ASSURANCE
A.
Manufacturer Qualifications: Company specializing in manufacturing the Products specified in
this section with minimum five years documented experience.
B.
Regulatory Requirements:
1.
2.
3.
1.5
Conform to requirements of NFPA 70.
Conform to requirements of NFPA 101.
Products: Listed and classified by Underwriters Laboratories Incorporated as suitable for
the purpose specified and indicated.
MAINTENANCE
A.
Section 01780 - Closeout Submittals: Procedures for closeout submittals.
B.
Extra Products: At completion of installation, deliver to Contracting Officer.
1.
2.
Two of each plastic lens type.
Each ballast type: Provide quantity equal to 10 percent of fixture total, but not less than two
of each type.
PART 2 - PRODUCTS
2.1
A.
LUMINAIRE MANUFACTURERS
Subject to compliance with project requirements, manufacturers offering Products which may be
incorporated in the Work include the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Cooper Lighting (Halo, Invue, Lumark, McGraw-Edison, Metalux, Sure-Lites), Peachtree
City, GA (770)486-4800.
Cooper Crouse-Hinds, Syracuse, NY (315) 477-5531.
Hubbell Lighting, Inc., (Columbia, Spaulding, Sterner) Spartanburg, SC (864) 599-6000.
Indy Lighting, Fishers, IN (317) 849-1233.
Kurt Versen Company, Westwood, NJ (201) 664-8200.
Lightolier, Fall River, MA (508) 679-8131.
Lithonia Lighting, Conyers, GA (770) 922-9000.
Omega Lighting, Tupelo, MS (800) 234-1890.
Phoenix Products Company, Inc., Milwaukee, WI (800) 973-3300.
Prescolite Lighting, Spartanburg, SC (864) 599-6000.
Day-Brite, Tupelo, MS (662) 842-7212.
Holophane, Newark, OH (740) 345-9631.
D.L. Manufacturing, North Syracuse, NY (315) 463-7348.
Chloride Systems, Burgaw, NC (910) 259-1000.
Day-O-Lite Manufacturing, Warwick, RI (401) 467-8232.
Dual-Lite, Cheshire, CT (203) 699-2000.
16510-2
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
B.
4.
5.
6.
7.
8.
Description: Recessed, 2’W x 4’L x 4”D gasketed fluorescent grid troffer with acrylic lens.
Lens: Prismatic acrylic, A-12 pattern, 0.125 inches thick.
Housing:Cold rolled steel body, door is aluminum with mitered corners. Frame and housing
finished with baked white enamel.
Ballast: Two lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Two F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia 4PS24-232G-RAA12 E U
b.
Metalux 2GCRA-232A125 UNV EB8
Type A2Lithonia 2SP8-F-232RW-A12125 [277][120].GEB10IS:
1.
2.
3.
4.
5.
6.
7.
8.
D.
Edison-Price Lighting, Long Island City, NY (718) 685-0700.
Gardco Lighting, San Leandro, CA (800) 227-0758.
Gotham Lighting, Conyrs, GA (800) 315-4982.
Guth Lighting, St. Louis, MO (314) 533-3200.
H.E.Williams, Carthage, MO (417) 358-4065.
Kenall Manufacturing, Gurnee, IL (847) 360-8200.
Lumux Lighting, Los Angeles, CA (877) 895-5552.
Pheonix Products, Milwaukee, WI (414) 438-1200.
Selux Corporation, Highland, NY (845) 691-7723.
LightAlarms (Thomas & Betts) Montreal, ON (888) 552-6467.
Belfer Group, Farmingdale, NJ (732) 493-2666.
Zumtobel Staff, Highland, NY (800) 448-4131.
Kirlin Lighting, Detroit, MI (313) 259-6400.
Kramer Lighting, Sturtevant, WI (800) 236-6800.
Canlet Oak Lawn, IL (800) 441 1771
AEI, Meza,AZ (480)-733-6594
Optimum , Henderson,NC (800)541-9082
Lighting Alternatives, Cherry Hill, NJ (877)847-1102
Fostoria, Fostoria,OH (800)495-4525
Infinity, Carthage,MO (417)-359-3333
Widelite, San Marcos,TX (512)392-5821
GE Lighting Systems, Charlotte,NC (803)462-2016
Vista Simi Valley,CA, (805)527-0987
Nite-Brites, Tupelo,MS (800)234-1890
Type A1Lithonia 2WRT-G-232-A12125[277][120].GEB10IS:
1.
2.
3.
C.
USPS NO. J80967
COMM. NO. 1597-104
Description: Recessed, 2’W x 4’L x 4”D fluorescent flanged troffer with acrylic lens.
Lens: Prismatic acrylic, A-12 pattern, 0.125 inches thick.
Housing: Cold rolled steel body, door is aluminum with mitered corners. Frame and housing
finished with baked white enamel.
Ballast: Two lamp electronic ballast.
Mounting: Recessed in a GWB ceiling.
Voltage: [277] [120].
Lamps: Two F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia 4PS24-232F-RAA12125 EU
b.
Metalux 2FRAC-232A125 UNV EB8
Type A3Lithonia 2SP8-G-332RW-A12125 [277][120]. ].GEB10IS:
16510-3
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
1.
2.
3.
4.
5.
6.
7.
8.
E.
4.
5.
6.
7.
8.
9.
Description: Recessed, 2’W x 4’L x 4”D fluorescent grid troffer with acrylic lens.
Lens: Prismatic acrylic, A-12 pattern, 0.125 inches thick.
Housing: Cold rolled steel body, door is aluminum with mitered corners. Frame and
housing finished with baked white enamel.
Ballast: Four lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Four F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia 4PS24-432G-RAA12125 EU
b.
Metalux 2GRAC-432A125 UNV EB8
Switching: See electrical drawings for dual level workroom lighting requirements.
Type A7Lithonia 2PM3N-G-A-232-16LS MVOLT GEB10 IS:
1.
2.
3.
4.
5.
6.
7.
8.
G.
Description: Recessed, 2’W x 4’L x 4”D fluorescent grid troffer with acrylic lens.
Lens: Prismatic acrylic, A-12 pattern, 0.125 inches thick.
Housing: Cold rolled steel body, door is aluminum with mitered corners. Frame and housing
finished with baked white enamel.
Ballast: Three lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Three F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia 4PS24-332G-RAA12.125 3EU
b.
Metalux 2GRAC-332A125 UNV EB8
Type A5Lithonia 2SP8- G-432RW-A12.125 [277] [120]. ].GEB10 IS:
1.
2.
3.
F.
USPS NO. J80967
COMM. NO. 1597-104
Description: Recessed, 2’W x 4’L x 6”D fluorescent parabolic troffer for grid ceiling.
Louver: 3” deep low iridescent, vertical grain anodized aluminum precision parabolic
louvers. 2 by 8 cells.
Housing: die-formed prime cold-rolled steel, with contoured ballast/wireway cover.
Ballast: Two lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Two F F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia P4D24-232G-LS28- E U
b.
MetaLux 2EP3GAX232S28I UNV EB8
Type B1Lithonia DMS-2-32-AR [277] [120].GEB10 IS:
1.
2.
3.
4.
5.
6.
7.
8.
Description: Enclosed and gasketed industrial fluorescent fixture. UL listed for damp location.
Lens: High impact acrylic diffuser.
Housing: Steel housing
Ballast: Two lamp electronic ballast.
Mounting: Surface.
Voltage: [277] [120].
Lamps: Two F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia LU4-232-E-DMR (Aluminum housing)
b.
Pheonix LFS232A (Aluminum housing)
16510-4
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
H.
Type CL1Lithonia C232-WGCSMR[277][120] GEB10 IS:
1.
2.
3.
4.
5.
6.
7.
8.
I.
Description; 4'-0" long, dual row, two fluorescent lamp strip luminaire with protective wire
mesh with reflector around lamps.
Lens: None
Housing: Die-formed cold rolled steel housing with punched knockouts for mounting. End
plates shall be die-formed heavy gauge rolled steel with punched knockouts for through
wiring. White baked enamel with a minimum 85 percent reflectance.
Ballast: Two lamp electronic ballast.
Mounting: Surface mounted to the underside of the ceiling. Attach luminaire to ceiling grid
by means of a gripper hanger which attaches to any standard ceiling grid system. For
spaces without ceiling, suspend from structure with all-thread rods to required height.
Electrical Contractor to determine quantity of hangers required for either method.
Voltage: [277] [120].
Lamps: Two F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia CS4-232 EU-CSWG4-CSR4
b.
Metalux SS-232-232I/GRP-SS-U-WG/SS-4FT-EB8
Type CV1Lithonia S132-GEB10 IS[277][120]:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
J.
USPS NO. J80967
COMM. NO. 1597-104
Description: Cove mounted; single lamp 4 feet long fluorescent strip luminaire.
Louver: Lay-in chrome parabolic cube louver for illuminated cove, manufactured by
American Louver Company, Skokie, Illinois (800) 323-4250, or approved substitution. Cell
size- 1 1/2 inch x 1 1/2 inch x 1 inch. Width and Length - Refer to plans.
Louver to be shipped to the site and installed with the protective film. Once the final
inspection has been conducted the film is to be removed.
Housing: Die-formed cold rolled steel with a painted exterior surface. Interlocked housing
corners with positive locking and rigid construction. Housing to be finished in white baked
enamel finish with a minimum reflectivity of 85 percent.
Ballast: One or two lamp electronic ballast. Ballast to operate this fixture and an adjacent
CV2 fixture where applicable.
Note:Individual lead lengths shall not exceed 18 feet.
Mounting: Surface mounted to the underside of the cove on a 2 inch spacer.
Louver lays into constructed cove on wall angles (furnished and installed by general
contractor). Louver shall be made into lengths and configurations shown on plans and fill
the cove end to end.
Voltage: [277] [120].
Lamp:
F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Metalux SN-132-UNV EB81
b.
Columbia CS4-132-E U
Type CV2Lithonia S117 [277] [120]GEB10 IS:
1.
2.
3.
4.
Description: Cove mounted; single lamp 2 feet long fluorescent strip luminaire.
Louver: Lay-in chrome parabolic cube louver for illuminated cove, manufactured by
American Louver Company, Skokie, Illinois (800) 323-4250, or approved substitution
paracube II. Cell size- 1 1/2 inch x 1 1/2 inch x 1 inch. Width and Length - Refer to plans.
Louver to be shipped to the site and installed with the protective film. Once the final
inspection has been conducted the film is to be removed.
Housing: Die-formed cold rolled steel with a painted exterior surface. Interlocked housing
corners with positive locking and rigid construction. Housing to be finished in white baked
enamel finish with a minimum reflectivity of 85 percent.
16510-5
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
5.
6.
7.
8.
9.
10.
K.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Description: Cove mounted; single lamp 3 feet long fluorescent strip fixture.
Louver: Lay-in chrome parabolic cube louver for illuminated cove, manufactured by
American Louver Company, Skokie, Illinois (800) 323-4250, or approved substitution
paracude II. Cell size- 1 1/2 inch x 1 1/2 inch x 1 inch. Width and Length - Refer to plans.
Louver to be shipped to the site and installed with the protective film. Once the final
inspection has been conducted the film is to be removed.
Housing: Die-formed cold rolled steel with a painted exterior surface. Interlocked housing
corners with positive locking and rigid construction. Housing to be finished in white baked
enamel finish with a minimum reflectivity of 85 percent.
Ballast: One or two lamp electronic ballast. Ballast to operate this fixture and an adjacent
CV2 fixture where applicable.
Note: Individual lead lengths shall not exceed 18 feet.
Mounting: Surface mounted to the underside of the cove on a 2 inch spacer.
Louver lays into constructed cove on wall angles (furnished and installed by general
contractor). Louver shall be made into lengths and configurations shown on plans and fill
the cove end to end.
Voltage: [277] [120].
Lamp: F25T8/SP41/ECO
Alternate Manufacturers:
a.
Columbia CS3-125-E U
b.
Metalux SN-125-EB8-(T1LW)
Type EM1Lithonia ELSQMN-LEX/ELA-FRK :
1.
2.
3.
4.
5.
6.
7.
M.
Ballast: This unit shall come complete, less ballast. Electrical contractor shall wire the
lamp sockets to an adjacent CV1 or CV3 fixture.
Mounting: Surface mounted to the underside of the cove on a 2 inch spacer.
Louver lays into constructed cove on wall angles (furnished and installed by general
contractor). Louver shall be made into lengths and configurations shown on plans and fill
the cove end to end.
Voltage: [277] [120].
Lamp: F17T8/SP41/ECO
Alternate Manufacturers:
a.
Columbia CS2-117-E U
b.
Metalux SN-117-EB8
Type CV3Lithonia S125 [277] [120].GEB10 IS:
1.
2.
L.
USPS NO. J80967
COMM. NO. 1597-104
Description: Recessed 10.5 inch square decorative Nickel-Cadmium battery type
emergency light unit. Provide with line latching, solid-state voltage limiting charger, solidstate switching, low voltage disconnect, brownout circuit, overload, short-circuit protection
test switch and power indicator light.
Lens: Lexan lens.
Housing: Black thermoplastic body, UL924 listed, all components meet the UL 94-0.5VA
flame retardant standard.
Mounting: Provide with manufacturer rough-in kit for fully recessed installation.
Voltage: [277] [120]
Lamps: 10W Tungsten Halogen (included)
Alternate Manufacturers:
a.
Chloride SPU30M-FR-PC (Polycarbonate Lens, 9” Square)
b.
Sure-Lites P4C7-PCL-FRK1/29-40 (9” Square)
Type EM2Lithonia ELM627-B-N:
16510-6
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
1.
2.
3.
4.
5.
6.
7.
N.
2.
3.
4.
5.
6.
7.
Description: Industrial design emergency lighting unit with adjustable heads. Provide with
line latching, solid-state voltage limiting charger, solid-state switching, low voltage
disconnect, brownout circuit, overload, short-circuit protection test switch and power
indicator light.
Battery: Sealed, maintenance free Nickel-Cadmium, 6 volt, with 24 Watt capacity.
Housing: 18-guage steel housing finished in instrument tan color, with hinged faceplate for
ease of maintenance. UL924 listed, all components meet the UL 94-0.5VA flame retardant
standard.
Mounting: Wall mounted.
Voltage: [277] [120].
Lamps: 8W Halogen (included)
Alternate Manufacturers:
a.
Chloride CCL675DY2A-V (8W Sealed Par36 heads))
b.
Dual-lite LM30N-V(7.2W halogen lamps)
Type EM4(interior & exterior)Lithonia INDX12100W-ULT-H1212:
1.
2.
3.
4.
5.
6.
7.
8.
P.
Description: Compact contemporary design emergency lighting unit with adjustable heads.
Provide with line latching, solid-state voltage limiting charger, solid-state switching, low
voltage disconnect, brownout circuit, overload, short-circuit protection test switch and
power indicator light.
Battery: Sealed, maintenance free Nickel-Cadmium, 6 volt, with 27 Watt capacity.
Housing: Black thermoplastic body, UL924 listed, all components meet the UL 94-0.5VA
flame retardant standard.
Mounting: Wall mounted.
Voltage: [277] [120]
Lamps: 9W krypton. (included)
Alternate Manufacturers:
a.
Chloride S50N-T9-B-AM (50Watt cap., 9W Tungsten lamps)
b.
Dual-lite LZB20N (20Watt Cap., 5W halogen lamps)
Type EM3Lithonia ELT24-N-AM-VM-H:
1.
O.
USPS NO. J80967
COMM. NO. 1597-104
Description: Surface Mounted UL wet location (NEMA 4X) listed emergency lighting unit
Lamping: Sealed Beam PAR 36
Housing: Heavy-duty polycarbonate sealed, gasketed, and corrosion resisitant.
Battery: Lead-Calcium, with self-diagnostics. Listed for cold weather (-40 degrees to 55
degrees C), damp and wet locations.
Mounting: Surface wall.
Voltage: Dual-voltage input capability (120/277).
Lamps: Two 12W, 12V par36 composite halogen
Alternate Manufacturers:
a.
Chloride: SV16L-W-HR (5.5W MR16 Lamps)
b.
Sure-Lites: UEL1WHSDAV (12W MR16 Lamps)
Type MH1Kirlin HRR-08072/ED-17/MED100-43-40 [277][120]:
1.
2.
3.
4.
5.
6.
Description: Recess mounted 8” aperture wet location downlight with horizontal lamp,
tempered prismatic lens, regressed white door.
Reflector: Upper reflector is highly reflective.
Housing: Entire housing serviceable through removable trim assembly.
Ballast: Constant wattage autotransformer encased and potted for qquiet operation.
Voltage: [277] [120]
Lamps: MP100/U/MED
16510-7
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
7.
Q.
2.
3.
4.
5.
6.
7.
8.
Description: Surface Mounted 18” diameter half cylinder wall mounted full cut-off luminaire
with 12V emergency lighting. Lens door is fully gasketed with one-piece solid silicone.
Reflector: Segmented reflector with wide throw optics.
Housing: Die-cast single piece aluminum housing with 1/8” thick tempered glass lens.
Ballast: Constant wattage autotransformer encased and potted for quiet operation.
Mounting: Surface wall.
Voltage: [277] [120]
Lamps:MP100/U/MED & 100Q/CL/DC
Alternate Manufacturers:
a.
Gardco: 104EMWT100MHBRP-FQ12v B84CG EMERGENCY
b.
Lumark: MH-IPC-100W-F-EM/SC/12V
Type P1Phoenix DL-INC-IR-GG1:
1.
2.
3.
4.
5.
6.
7.
T.
Description: Surface mounted 17.5” square luminaire, overall height of 11.25”
Housing: Die cast aluminum mounted directly to outlet box.
Lens: Drop Polycarbonate refractor providing a square distribution.
Ballast: Constant wattage autotransformer encased and potted for quiet operation.
Voltage: [277] [120]
Lamps: MP150/U/MED
Alternative Manufacturers:
a.
Nite Brites DSS150MEPDPM-BLACK (25” SQ, 10” D)
b.
Lumark MHCL150BLK (21” SQ, 12” D)
Type MH3LithoniaWSR100MWT (120)(277)-DC2012:
1.
S.
Alternative Manufacturers:
a.
Gotham LGHZ100M8RWT73
b.
Kramer KL8100MHLHPLWSPYWFF
Type MH2(interior)Lithonia KACM150MDPPDBL [277][120]:
1.
2.
3.
4.
5.
6.
7.
R.
USPS NO. J80967
COMM. NO. 1597-104
Description: Ceiling Mounted Dock Light with spring suspension swivel mounting, provide
light head with glare guard and timer control switch.
Light Head: Incandescent/Halogen.
Housing: Fixture head of 18 gauge steel.
Mounting: Swivel hanger for direct mounting to standard 4 inch junction box. Pendant to
be 1/2 inch conduit with flexible spring for impact resistance and sufficient length to
suspend center of light at 8’-6” AFF.
Voltage: 120.
Lamps: CF23EL/PAR38/BL/2/12 Sylvania
Alternate Manufacturers:
a.
Fostoria DKL-25-FLX + INC + GS-1
Type PL1(interior & exterior) Infinity MHRL 13 175 ED28/MOG-H0RZ-FF:
1.
2.
3.
4.
5.
6.
7.
Description: 12” Diameter Recessed shallow plenum, regressed lensed Metal Halide
downlight compatible with metal slat ceiling systems. White smooth splay with prismatic lens.
Reflector: Low brightness clear specular alzak finish reflector.
Housing: Diecast aluminum lamp holder assembly.
Ballast: Encased and potted constant wattage auto-transformer type, high power factor.
Mounting: Mounting pan assembly with adjustable brackets.
Voltage: [277] [120].
Lamps: M175/C/U.
16510-8
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
8.
U.
4.
5.
6.
7.
8.
Description: Pendant 10 inch diameter aperture compact fluorescent downlight.
Reflector: Low brightness clear specular alzak finish reflector.
Housing: Heavy gauge aluminum cylinder, finished white. Pendant hung on a 24” stem with
a swivel canopy.
Ballast: Two type 1, Class P, high power factor universal voltage electronic compact
fluorescent ballasts, 1 or 2 lamp operation.
Mounting: Pendant mounted, height as indicated by architectural elevations.
Voltage: [277] [120].
Lamps: 3 – F32TBX/SPX35/A/4P
Alternate Manufacturers:
a.
Infinity PHC13/12-PM
Type R1 Gotham AF2/26DTT-8AR-[MVOLT]GEB10:
1.
2.
3.
4.
5.
6.
7.
8.
9.
W.
Alternate Manufacturers:
a.
KIRLIN HRR-11073-ED28-MOG175-43-40
b.
Kramer KL11175MHLWSPYWFF (11”)
Type PL2 Omega OM103H32PLTPCSPLPL-U (Univ:120/277):
1.
2.
3.
V.
USPS NO. J80967
COMM. NO. 1597-104
Description: Recessed compact fluorescent downlight with a nominal 8 1/4 inch diameter
reflector opening.
Baffle: specular clear alzak cone.
Ballast: Type 1, Class P, high power factor universal voltage electronic compact
fluorescent ballast
Mounting Frame: Frame to be 16 gauge galvanized steel ring. Mounting ring shall be
secured to grid ceiling bar hangers (supplied with fixture). NOTE: Luminaire frame to be
supported from the structure by at least two opposing corners.
Junction Box: Junction box to be code approved for through wiring. Junction box to be
secured to the mounting ring and accessible from two sides. Junction box to be pre-wired
and accessible per code through the ceiling trim opening.
Mounting: 24 inch grid ceiling bar hangers shall be supplied by manufacturer and securely
fastened to grid or 28 inch 'C' channel mounting bars for drywall ceilings.
Voltage: [277] [120].
Lamp(s): Two (2) NEMA CFQ26W/G24d/835.
Alternate Manufacturers:
a.
Kramer Lighting KL82X-26QPL-CFF
b.
Zumtobel/Staff S5D8204-U-8203RC
Type R2 Gotham AFW2/26DTT-8AR MVOLT GEB10.
1.
2.
3.
4.
5.
6.
7.
Description: Recessed compact fluorescent wallwasher.
Baffle: Specular clear alzak cone.
Ballast: Type 1, Class P, high power factor universal voltage electronic compact fluorescent
ballast
Mounting Frame: Frame to be 16 gauge galvanized steel ring. Mounting ring shall be
secured to ceiling bar hangers (supplied with fixture). NOTE: Luminaire frame to be
supported from the structure by at least two opposing corners.
Junction Box: Junction box to be code approved for through wiring. Junction box to be
secured to the mounting ring and accessible from two sides. Junction box to be pre-wired
and accessible per code through the ceiling trim opening.
Mounting: 24 inch grid ceiling bar hangers shall be supplied by manufacturer and securely
fastened to grid or 28 inch "C" channel mounting bars for drywall ceiling.
Voltage: [277] [120].
16510-9
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
8.
9.
X.
3.
4.
5.
6.
7.
8.
Description: Recessed 2 feet x 2 feet, two lamp, nine cell parabolic fluorescent troffer.
Louver: Post-anodized, highly specular, 3” deep, 9 cell parabolic louver constructed of high
purity aluminum. Louver shall have a smooth, crack free, brilliant surface without
iridescence. Louver shall be held by internal spring catches and center itself in the housing
when it is snapped-in.
Housing: Die-formed 20 gauge sheet with a baked white acrylic enamel finish. Housing
shall be prepared in a three step process of cleaning, degreasing and washing prior to
painting.
Ballast: two lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Two FB032/841XP/6/SS/ECO
Alternate Manufacturers:
a.
Metalux 2EP3GX-2U6T8S33MI-EB81
b.
Columbia P4D22-232U6G-LS33-S-EB8LH
Type R4 Lithonia 2PM3X33218LDGEB10RS:
1.
2.
3.
4.
5.
6.
7.
8.
Z.
Lamp(s): Two (2) CFQ26W/G24d/835.
Alternate Manufacturers:
a.
Kramer Lighting KL82X-26QPLWW-CFF
b.
Zumtobel/Staff S5D8204-U-8203WC
Type R3 Lithonia Lighting 2PM3NGB2U3169LS MVOLT GEB10RS
1.
2.
Y.
USPS NO. J80967
COMM. NO. 1597-104
Description: Surface mounted 2 feet x 4 feet, three lamp, eighteen cell parabolic
fluorescent troffer.
Louver: Post-anodized, highly specular eighteen cell parabolic louver constructed of high
purity aluminum. Louver shall have a smooth, crack free, brilliant surface without
iridescence. Louver shall be held by internal spring catches and center itself in the housing
when it is snapped-in.
Housing: Die-formed 20 gauge sheet with a baked white acrylic enamel finish. Housing
shall be prepared in a three step process of cleaning, degreasing and washing prior to
painting.
Ballast: Three lamp electronic ballast.
Mounting: Surface to ceiling.
Voltage: [277] [120].
Lamps: F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Metalux 2EP3GX-332S36MI-277-ER81
b.
Columbia P4D24-332G-LS36-S-3E
Type R5 Lithonia 2SP-GB232-A12125-GEB10RS.
1.
2.
3.
4.
5.
6.
7.
8.
Description: Recessed 2 feet x 4 feet, two lamp, lensed troffer.
Louver: clear prismatic acrylic lens, 0.125 inch thick.
Housing: Die-formed 20 gauge sheet with a baked white acrylic enamel finish. Housing
shall be prepared in a three step process of cleaning, degreasing and washing prior to
painting.
Ballast: two lamp electronic ballast.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: Two F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
16510-10
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
a.
b.
AA.
Metalux 2GC232-A125ER81
Columbia 4PS24-232-G-FS-A12125-EP
Type R6 Lithonia 2SP-G-432-A12125-GEB10RS.
1.
2.
3.
4.
5.
6.
7.
8.
BB.
USPS NO. J80967
COMM. NO. 1597-104
Description: Recessed 2 feet x 4 feet, four lamp, lensed troffer.
Louver: clear prismatic acrylic lens.
Housing: Die-formed 20 gauge sheet with a baked white acrylic enamel finish. Housing
shall be prepared in a three step process of cleaning, degreasing and washing prior to
painting.
Ballast: two lamp electronic ballasts.
Mounting: Recessed in Inverted T suspended ceiling.
Voltage: [277] [120].
Lamps: F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Metalux 2GC432-A125ER8
b.
Columbia 4PS24-432-G-FS-A12125EB
Type SP5(exterior) Lithonia KSF1175M R2 SF DBB [277] [208]:
1.
2.
3.
4.
5.
6.
7.
8.
Description: Rectilinear architectural arm-mounted full cut-off.
Reflector: Anodized segmented reflectors. Type II distribution.
Housing: Rugged aluminum rectilinear housing with all seams continuously welded for
integrity. Corrosion-resistant polyester powder coat
Ballast: Constant wattage auto-transformer type, high power factor.
Mounting: 12 – 15’ Square straight aluminum pole.
Voltage: [277] [208].
Lamps: M175/C/U.
Alternate Manufacturers:
a.
McGraw Edison CAL175MHMT2SF BZ
b.
Hubbell RCS-A-H17-H3-F-Q-DBW4
CC. Type T3:
1.
Track: Lytespan 6001NWH.
2.
3.
Fixture: Lightolier 8279ENWH.
Description: 4 feet long single circuit track with recessed feed-end connector and t-bar
attachment clips.
Features: White track light wall wash fixture.
Mounting: T-bar ceiling clip.
Voltage: 120.
Lamps: (2) FT40W/DL/2G11/RS/835.
Alternate Manufacturers:
a.
Prescolite AKTHLCE240WH and ArchiTrak.
4.
5.
6.
7.
8.
DD. Type UC1 Lithonia N2S-17-120-TW2:
1.
2.
3.
4.
5.
Description: Under cabinet mounted 2 feet long, single fluorescent lamp luminaire, with
solid front.
Housing: Die formed cold rolled steel.
Lens: Clear acrylic prismatic serrated diffuser shall snap into place without tools.
Finish: White polyester powder coat, 92 % overall reflectance.
Ballast: This unit shall come complete, less ballast. Electrical contractor shall wire the
lamp sockets to an adjacent UC 2 fixture.
16510-11
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
6.
7.
8.
EE.
2.
3.
4.
5.
6.
7.
8.
Description: Under cabinet mounted 3'-0" long, single fluorescent lamp luminaire, with solid
front
Housing: Die formed cold rolled steel.
Lens: Clear acrylic prismatic serrated diffuser shall snap into place without tools.
Finish: White polyester powder coat, 92 % overall reflectance.
Ballast: One Magnetek Triad OCTIC T8, one or two lamp ballast. Ballast to operate this
fixture and an adjacent UC 1 fixture where applicable. Individual lead lengths shall not
exceed 18 feet.
Voltage: 120.
Lamp: F25T8/XL/SP41/ECO
Alternate Manufacturers:
a.
H.E.Williams 2SF-24-125-2Lamp ballast-120
b.
Belfer 6316-FO25-1-2Lamp ballast
Type W1 Lithonia TAF10332-Mvolt-GEB10IS-DLAF ME:
1.
2.
3.
4.
5.
6.
7.
8.
GG.
Voltage: 120.
Lamp: F17T8/XL/SP41/ECO
Alternate Manufacturers:
a.
H.E.Williams 2SF-24-117-Tandem-120
b.
Belfer 6316-FO17-1-T8/41K Tandem
Type UC2 Lithonia N2S-25-120-TW2:
1.
FF.
USPS NO. J80967
COMM. NO. 1597-104
Description: Pendant mounted, 8 feet long, fluorescent industrial fixture providing 10
percent uplighting.
Louver: Aluminum cross louver provides 30 degree shielding both crosswise and
lengthwise. Finished in white polyester acrylic paint.
Housing: Channel and end plates of formed steel. Reflector of one piece steel
strengthened by formed apertures, embossed ribs and upturned edge beads. Slots in
reflector provide 10 percent uplighting with 11o crosswise shielding from formed reflector.
Finished with 88 percent minimum reflectance polyester acrylic paint.
Ballast: 2-3 lamp electronic ballasts.
Mounting: Steel pipe pendant (5/8” diameter) and canopy.
Voltage: [277] [120].
Lamps: Six (6) F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Columbia IC-8-332-3E ICVWCB
b.
H.E.Williams 82-8-632-EB3 – LOUVER
Type W2 Lithonia AF10332-Mvolt-GEB10IS-DLAF ME:
1.
2.
3.
4.
5.
6.
7.
Description: Pendant mounted, 4 feet long, fluorescent industrial fixture providing 10
percent uplighting.
Louver: Aluminum cross louver provides 30 degree shielding both crosswise and
lengthwise. Finished in white polyester acrylic paint.
Housing: Channel and end plates of formed steel. Reflector of one piece steel
strengthened by formed apertures, embossed ribs and upturned edge beads. Slots in
reflector provide 10 to15 percent uplighting with 11o crosswise shielding from formed
reflector. Finished with 88 percent minimum reflectance polyester acrylic paint.
Ballast: 3 lamp electronic ballast.
Mounting: Steel pipe pendant stem (5/8 inch diameter) and canopy.
Voltage: [277] [120]
Lamps: Three (3) F32T8/SP41/IS/WM/ECO
16510-12
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
8.
USPS NO. J80967
COMM. NO. 1597-104
Alternate Manufacturers:
a.
Columbia IC-4-332-3E ICVWCB
b.
H.E.Williams 82-4-332-EB3 – LOUVER
HH. Type W3 Holophane HBT4DSNNNO46-EP-2:
1.
2.
3.
4.
5.
6.
II.
Type W6 LIGHTING ALTERNATIVES FWHB24/T8848-RFW-MB4-WG-FH-2X432T8PSUNV:
1.
2.
3.
4.
5.
6.
7.
8.
JJ.
Description: Pendant mounted industrial fluorescent high bay with wide beam distribution
and (2) programmed start ballasts with a ballast factor of at least 0.88.
Features: Single stem pendant mount, wire guard.
Housing: Cold rolled steel painted before fabrication with 92% reflectance white reflector.
Mounting: Ceiling, 20’ and above.
Voltage: [277] [120]
Lamps: Eight (8) F32T8/SP41/IS/WM/ECO
Warranty for combination Lamp and ballast systems shall be utilized, similar to Quick 60+
by Sylvania for a system consisting of Quicktronic PSX T8 ballast with Octron XP lamps.
Alternate Manufacturers:
a.
OPTIMUM LIGHTING G21832UV2PSWPSWG
b.
AEI LIGHTING T8CLS 832 UNI41 PSWH SP
Type XF1Canlet 68-02-01-0G-11:
1.
2.
3.
4.
5.
6.
7.
KK.
Description: Pendant mounted industrial fluorescent high bay with wide beam distribution
and (2) programmed start T8 ballasts for 2-level switching.
Housing: Cold rolled steel painted before fabrication with 92% reflectance white reflector.
Mounting: Ceiling, above 15’ and below 20’
Voltage: [277] [120]
Lamps: Six (6) F32T8/SP41/IS/WM/ECO
Alternate Manufacturers:
a.
Lighting Alternatives FWHB24/T8/6/48/RFW/FH/ 2/2X332T8/IS INV
b.
Day-Brite FBF632T8-2/3EBH-U
Description: Vaportight incandescent listed and labeled for Class I, Div. 2, Groups C,D,
hazardous locations in accordance with article 501 of the National Electrical Code.
Lens: Heat and impact resistant glass globe.
Housing: Body and guard of lexan polycarbonate.
Mounting: Surface ceiling mounted.
Voltage: 120
Lamps: 135W/A19/130V
Alternate Manufacturer:
a.
Hubbell NVX15GHG
Type X1Sure-Lites CCX-71-70-R-WH-SD :
1.
2.
3.
4.
5.
6.
7.
Description: Ceiling mount, single face exit sign with canopy.
Features: Red Letters, White Stencil, White Housing (verify colors with local jurisdiction).
Injection molded UL94-5V rated polycarbonate frame and canopy.
Mounting: Ceiling or end-mount.
Battery: Maintenance free sealed Nickel Cadmium with long life, full recharge time of 24
hours max.
Voltage: 120.
Lamps: LED lamp module.
Alternate Manufacturers:
16510-13
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
a.
b.
LL.
USPS NO. J80967
COMM. NO. 1597-104
Chloride SLN1RW-AD
Lightalarms XQ-U-ELR-D
Type X2Sure-Lites CCX-72-70-R-WH-SD :
1.
2.
3.
4.
5.
6.
Description: Ceiling mount, double face exit sign with canopy.
Features: Red Letters, White Stencil, White Housing (verify colors with local jurisdiction).
Injection molded UL94-5V rated polycarbonate frame and canopy. Two bottom apertures
snap out to emit downlight as required.
Mounting: Ceiling or end-mount.
Voltage: 120.
Lamps: LED lamp module.
Alternate Manufacturers:
a.
Chloride SLN2RW-AD
b.
Lightalarms XQ-U-ELR-D
MM. Type CI02Vista AGVSP-LED-DC-HL-C-ZN-WT-UNV-MW:
1.
2.
3.
4.
5.
6.
7.
8.
2.2
A.
Description: Recessed 9.25”w x 3.3”h x 4.3”d step light with L.E.D. source
Features: Die cast aluminum step light with louver face.
Housing: Back box constructed of die-cast aluminum alloy.
Louvers: Die-cast aluminum alloy.
Mounting: Recessed wall mounting.
Voltage: Universal (both120 & 277)
Lamp:
White LED’s included
Alternate Manufacturers:
a.
Kenall MSLS)DBCPWLL [120] [277] (9.25”w x 3.75”h x 3.5”d)
b.
Lumux SL630/LED/BRONZE [120] [277] (10.25”w x 4”h x 3.25”d) ok
ELECTRONIC FLUORESCENT LAMP BALLASTS
Manufacturers:
1.
2.
3.
4.
5.
Advance Transformer Company, Rosemont, IL (847) 390-5000.
Motorola, Lake Zurich, IL (800) 654-0089.
Universal Lighting Technologies, Nashville, TN (615) 316-5100.
Osram/Sylvania, Danvers, MA (800) 544-4828.
Hatch Transformers, Tampa, FL (813)288-8006
B.
Description: High frequency, energy efficient, electronic fluorescent lamp ballasts operating
lamps at a frequency above 42 kHz with power factor of 0.98 for primary lamp. Ballast shall be
compatible for operating the lamps indicated. Ballast shall have a minimum ballast factor for
primary lamp of 0.85. Ballast shall provide independent lamp operation for instant start allowing
remaining lamp(s) to maintain full light output when one or more lamps fail. The lamp crest factor
shall measure 1.7 or less. Ballasts shall have a minimum "Ballast Factor" of 0.87. Ballasts shall
meet or exceed all EMI and RFI standards of the Federal Communications Commission (FCC)
regulations Part 18 (including 15J). Ballasts shall be UL labeled and comply with all local, State
and Federal efficiency standards.
C.
Compact fluorescent ballasts shall be high efficiency, energy efficient, electronic ballasts
operating at a frequency above 50 kHz with a power factor of 0.99. Total harmonic distortion shall
range fro 5 to 13%, depending upon lamp/ballast combination. Compact fluorescent ballasts shall
operate 10 to 32 Watt lamps, either two lamp ballasts, or a single lamp ballast (in three lamp
fixtures). Ballasts shall be factory tested and meet ANSI 15 C62.41, ANSI C82.1 Class P.
16510-14
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
D.
2.3
A.
Voltage 120 and 277 volts to match luminaire voltage.
HIGH INTENSITY DISCHARGE (HID) BALLASTS
Manufacturers:
1.
2.
3.
4.
5.
B.
C.
2.4
A.
USPS NO. J80967
COMM. NO. 1597-104
Advance Transformer Company, Rosemont, IL (847) 390-5000.
General Electric Company, Nela Park, OH (800) 435-2677.
Universal Lighting Technologies, Nashville, TN (615) 316-5100.
Osram/Sylvania, Danvers, MA (800) 544-4828.
Robertson, Blue Island, IL (800) 323-5633
Description:
1.
Metal Halide Electronic Ballast for lamps up to 100 Watt: Power factor of .98 to 1.0, ballast
factor of 1.0, capable of powering two, 400, 350 or 320 watt standard or pulse start lamps
with integral color coded leads. Multi-voltage capable and shall operate from a nominal
voltage range of 208 – 277 volts AC. System efficiency of greater than 93% under full lamp
operation and FCC compliant for EMI/RFI as per parts 18.305 and 18.307. Total harmonic
distortion of less than 5%. Lamp wattage shall not vary more than 0.5% for a 10% change
in input line voltage. A crest factor of 1.5 shall not be exceeded. Where applicable a means
of continuous dimming shall be part of the ballast system. Dimming control is to be of
common 0 – 10 volt DC, two wire IEC protocol. Dimming shall range from 100% down to no
less than 50% of input power. Ballast assembly shall be UL listed for damp locations, 40
degrees C, and comply with all local, state and federal efficiency standards.
2.
Ballast for Metal-Halide Lamps 175 – 400 Watt: Comply with ANSI C82.4 and UL 1029.
Constant-wattage autotransformer or regulating high-power-factor type, with a minimum
starting temperature of Minus 30 deg C for single-lamp ballasts, and a normal operation
temperature of 40 degrees C. Open-circuit operation of ballast shall not reduce average
life. To prevent ballast noise, Manufacturers' standard epoxy-encapsulated models, which
are designed to minimize audible fixture noise shall be utilized.
Voltage: Match luminaire voltage.
LAMPS
Incandescent, Fluorescent and High Intensity Discharge (HID) Lamp Manufacturers:
1.
2.
3.
General Electric Company, Nela Park, OH (800) 435-2677.
Osram/Sylvania, Danvers, MA (800) 544-4828.
Philips Lighting Company, Somerset, NJ (800) 555-0050.
B.
Lamp Types: As specified for luminaire. Refer to Section 01600 for substitutions and product
options.
C.
Reflector Lamp Beam Patterns: ANSI C78.379.
D.
Four foot long T8 and U-bend T8 linear fluorescent lamps shall have a mercury content of less
than 20 ppm.
E.
Linear fluorescent, compact fluorescent and incandescent amps must pass the federal Toxic
Characteristic Leaching Procedure (TCLP) test and be classified non-hazardous waste.
16510-15
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Section 01700 - Execution Requirements: Verification of existing conditions before starting work.
B.
Verification of Conditions: Verify that field measurements, surfaces, substrates and conditions
are as required, and ready to receive Work.
C.
Report in writing to Contracting Officer prevailing conditions that will adversely affect satisfactory
execution of the Work of this Section. Do not proceed with Work until unsatisfactory conditions
have been corrected.
D.
By beginning Work, Contractor accepts conditions and assumes responsibility for correcting
unsuitable conditions encountered at no additional cost to the United States Postal Service.
3.2
INSTALLATION
A.
Install suspended luminaires and exit luminaire signs using pendants supported from swivel
hangers or in accordance with details shown on drawings. Provide pendant length required to
suspend luminaire at indicated height.
B.
Support recessed fluorescent fixtures 2 foot x 2 foot and larger using a minimum of four wire
hangers of same gauge as ceiling suspension system supported from building structure
independent of ceiling framing.
C.
Locate recessed ceiling luminaires as indicated on reflected ceiling plan.
D.
Install surface mounted luminaires and exit luminaire signs plumb and adjust to align with building
lines and with each other. Secure to prevent movement. Mount exit signs to outlet box mounted
flush in wall or ceilings. Outlet box for ceiling mounted exit signs: Connect to rigid conduit
system.
E.
Exposed Grid Ceilings: Support surface mounted luminaires on grid ceiling directly from building
structure.
F.
Install recessed luminaires to permit removal from below.
G.
Install recessed luminaires using accessories and firestopping materials to meet regulatory
requirements for fire rating. In fire rated ceilings recessed luminaires must carry 1 hour UL fire
rating classification.
H.
Install earthquake clips to secure recessed grid-supported luminaires in place.
I.
Install a minimum of four independent wire hangers, one on each corner supported from building
structure.
J.
Install wall mounted luminaires, emergency lighting units and exit luminaire signs at height as
scheduled.
K.
Install accessories furnished with each luminaire.
L.
Connect luminaires, emergency lighting units and exit luminaire signs to separate branch circuits
using minimum 1/2 inch (12 mm) flexible metal conduit whips maximum 5 feet in length.
16510-16
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
M.
Bond products and metal accessories to branch circuit equipment grounding conductor.
N.
Install specified lamps in each emergency lighting unit, exit luminaire sign, and luminaire.
3.3
FIELD QUALITY CONTROL
A.
Section 01450 - Quality Control: Field testing and inspection.
B.
Operate each luminaire after installation and connection. Inspect for proper connection and
operation.
3.4
ADJUSTING
A.
Aim and adjust luminaires as directed by Contracting Officer.
B.
Position exit luminaire sign directional arrows as indicated.
3.5
CLEANING
A.
Section 01700 - Execution Requirements: Cleaning installed work.
B.
Clean electrical parts to remove conductive and deleterious materials.
C.
Remove dirt and debris from enclosures.
D.
Clean photometric control surfaces as recommended by manufacturer.
E.
Clean finishes and touch up damage.
F.
Relamp fixtures with defective or burned out lamps just prior to Final Acceptance.
END OF SECTION
16510-17
USPS INTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
INTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
USPS NO. J80967
COMM. NO. 1597-104
SECTION 16520 - EXTERIOR LIGHTING
PART 1 - GENERAL
1.1
A.
SUMMARY
Section Includes:
1.
2.
Exterior luminaires and accessories.
Poles.
B.
Related Documents: The Contract Documents, as defined in Section 01110 - Summary of Work,
apply to the Work of this Section. Additional requirements and information necessary to
complete the Work of this Section may be found in other Documents.
C.
Related Sections:
1.
2.
1.2
A.
B.
REFERENCES
American National Standards Institute (ANSI):
1.
ANSI C78.379 - Electric Lamps - Incandescent and High-Intensity Discharge Reflector
Lamps - Classification of Beam Patterns.
2.
ANSI C82.4 - Ballasts for High-Intensity-Discharge and Low Pressure Sodium Lamps
(Multiple-Supply Type).
Illuminating Engineering Society (IES):
1.
2.
C.
A.
IES RP-8 - Recommended Practice for Roadway Lighting.
IES RP-20 - Lighting for Parking Facilities.
National Fire Protection Association (NFPA):
1.
1.3
Section 03300 - Cast-in-Place Concrete: Concrete for pole foundation.
Section 16050 - Basic Electrical Materials and Methods: Basic electrical methods.
NFPA 70 - National Electrical Code.
SUBMITTALS
Section 01330 - Submittal Procedures: Procedures for submittals.
1.
Product Data:
a.
b.
2.
Fixture dimensions, ratings, and performance data.
Complete computer data printout of illumination levels based on a grid system of
multiples of spacing to pole height.
Shop Drawings:
a.
Indicate dimensions and components for each luminaire which is not a standard
Product of the manufacturer.
16520-1
USPS EXTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
EXTERIOR LIGHTING
b.
1.4
A.
QUALITY ASSURANCE
Qualifications:
1.
B.
A.
Manufacturer: Company specializing in manufacturing the Products specified in this
section with minimum five years documented experience.
Regulatory requirements:
1.
2.
1.5
Indicate illumination levels in accordance with layout and scheduled luminaires
indicated on Drawings.
Conform to requirements of NFPA 70.
Products: Listed and classified by Underwriters Laboratories, Inc. as suitable for the
purpose specified and indicated.
DELIVERY, STORAGE, AND HANDLING
Section 01600 - Material and Equipment: Transport, handle, store, and protect products.
PART 2 - PRODUCTS
2.1
A.
LUMINAIRE MANUFACTURERS
Subject to compliance with project requirements, manufacturers offering Products which may be
incorporated in the Work include the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
2.2
A.
Cooper Lighting (Halo, Invue, Lumark, McGraw-Edison, Metalux, Sure-Lites), Peachtree
City, GA (770)486-4800.
Cooper Crouse-Hinds, Syracuse, NY (315) 477-5531.
Hubbell Lighting, Inc., (Columbia, Spaulding, Sterner) Spartanburg, SC (864) 599-6000.
Lightolier, Fall River, MA (508) 679-8131.
Lithonia Lighting, Conyers, GA (770) 922-9000.
Holophane, Newark, OH (740) 345-9631.
Gardco Lighting, San Leandro, CA (800) 227-0758.
Gotham Lighting, Conyrs, GA (800) 315-4982.
Guth Lighting, St. Louis, MO (314) 533-3200.
LSI Industries, Inc, Cincinnati, OH (513) 793-3200.
Pheonix Products, Milwaukee, WI (414) 438-1200.
Selux Corporation, Highland, NY (845) 691-7723.
FIXTURE TYPES
Type EM4(interior & exterior)Lithonia INDX12100W-ULT-H1212:
1.
2.
3.
4.
5.
6.
7.
8.
Description: Surface Mounted UL wet location (NEMA 4X) listed emergency lighting unit
Lamping: Sealed Beam PAR 36
Housing: Heavy-duty polycarbonate sealed, gasketed, and corrosion resisitant.
Battery: Lead-Calcium, with self-diagnostics. Listed for cold weather (-40 degrees to 55
degrees C), damp and wet locations.
Mounting: Surface wall.
Voltage: Dual-voltage input capability (120/277).
Lamps: Two 12W, 12V par36 composite halogen
Alternate Manufacturers:
a.
Chloride: SV16L-W-HR (5.5W MR16 Lamps)
b.
Sure-Lites: UEL1WHSDAV (12W MR16 Lamps)
16520-2
USPS MASTER SPECIFICATION
Issue Date: 9/17/2005
EXTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
B.
Type MH2(Exterior)LithoniaWSR100MWT(120)(277)SF:
1.
2.
3.
4.
5.
6.
7.
8.
C.
2.
3.
4.
5.
6.
7.
8.
Description: 12” Diameter Recessed shallow plenum, regressed lensed Metal Halide
downlight compatible with metal slat ceiling systems. White smooth splay with prismatic
lens.
Reflector: Low brightness clear specular alzak finish reflector.
Housing: Diecast aluminum lamp holder assembly.
Ballast: Encased and potted constant wattage auto-transformer type, high power factor.
Mounting: Mounting pan assembly with adjustable brackets.
Voltage: [277] [120].
Lamps: M175/C/U.
Alternate Manufacturers:
a.
KIRLIN HRR-11073-ED28-MOG175-43-40
b.
Kramer KL11175MHLWSPYWFF (11”)
Type SB1(exterior) Lithonia KBA650MR5TBDDB SF:
1.
2.
3.
4.
5.
6.
7.
8.
E.
Description: Surface Mounted 18” diameter half cylinder wall mounted full cut-off luminaire.
Lens door is fully gasketed with one-piece solid silicone.
Reflector: Segmented reflector with wide throw optics.
Housing: Die-cast single piece aluminum housing with 1/8” thick tempered glass lens.
Ballast: Constant wattage autotransformer encased and potted for quiet operation.
Mounting: Surface wall.
Voltage: [277] [120]
Lamps:MP100/U/MED
Alternate Manufacturers:
a.
Gardco: 104WT100MHBRPF
b.
Lumark: MH-IP-C-100W-F1
Type PL1(interior & exterior) Infinity MHRL 13 175 ED28/MOG-H0RZ-FF:
1.
D.
USPS NO. J80967
COMM. NO. 1597-104
Description: 36“ High extruded one piece aluminum domed top round bollard with flared cone.
Reflector: Anodized aluminum upper reflector with spun anodized aluminum flared cone
Housing: extruded, one piece aluminum, 0.156” wall thickness. Top cover is a weldment of
0.125” wall extrusion and 0.25” top plate. Top seals to housing with closed cell EPDM
gasketing.
Ballast: Pulse start electronic, high power factor.
Mounting: Four ½” x 11” anchor bolts with double nuts and washers, 4-1/2” bolt circle
included.
Voltage: [120] [277]
Lamps: MH50W/E17
Alternate Manufacturers:
a.
McGraw-Edison BRC3650MHDARKBRONZE-F
b.
Spaulding FN2P50D0DBFDM36
Type SF1(exterior) InVue VFS-K-70-MH-NS:
1.
2.
3.
4.
5.
6.
7.
8.
Description: Enclosed Micro Floodlight to illuminate a flag pole.
Reflector: Diffuse axial parabolic narrow reflector.
Housing: Die-cast aluminum, 6.25” x 9.75” x 4.75”.
Ballast: High reactance autotransformer.
Mounting: 1/2 inch threaded fitter
Voltage: [277] [208].
Lamps: MH70W/G12
Alternate Manufacturers:
16520-3
USPS EXTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
EXTERIOR LIGHTING
a.
b.
F.
Type SP1(exterior) Lithonia KSF2250M R2 SF DDB [277][208]:
1.
2.
3.
4.
5.
6.
7.
8.
G.
4.
5.
6.
7.
8.
Description: Rectilinear architectural arm-mounted full cut-off.
Reflector: Anodized segmented reflectors. Type III distribution.
Housing: Rugged aluminum rectilinear housing with all seams continuously welded for
integrity. Corrosion-resistant polyester powder coat
Ballast: Constant wattage auto-transformer type, high power factor.
Mounting: 20 – 25’ Square straight aluminum pole.
Voltage: [277] [208].
Lamps: M400/C/U.
Alternate Manufacturers:
a.
McGraw Edison CAL400MHMT3SFDark bronze
b.
Hubbell RCS-A-H40-F-Q-DBW4
Type SP5(exterior) Lithonia KSF1175M R2 SF DBB [277] [208:
1.
2.
3.
4.
5.
6.
7.
8.
I.
Description: Rectilinear architectural arm-mounted sharp cut-off.
Reflector: Anodized segmented reflectors, Type II distribution.
Housing: Rugged aluminum rectilinear housing with all seams continuously welded for
integrity. Corrosion-resistant polyester powder coat
Ballast: Constant wattage auto-transformer type, high power factor.
Mounting: 20 – 25’ Square straight aluminum pole.
Voltage: [277] [208].
Lamps: M250/C/U.
Alternate Manufacturers:
a.
McGraw Edison CAL250MHMT2SFDark bronze OK
b.
Hubbell RCS-A-H25H3-F-Q-DBW4
Type SP2(exterior) Lithonia KSF2400M R3 SF DDB [277][208]:
1.
2.
3.
H.
Sterner CA5D/70MH/RN/SW
Beta Lighting BCQ6407-D[277][208
Description: Rectilinear architectural arm-mounted full cut-off.
Reflector: Anodized segmented reflectors. Type II distribution.
Housing: Rugged aluminum rectilinear housing with all seams continuously welded for
integrity. Corrosion-resistant polyester powder coat
Ballast: Constant wattage auto-transformer type, high power factor.
Mounting: 12 – 15’ Square straight aluminum pole.
Voltage: [277] [208].
Lamps: M175/C/U.
Alternate Manufacturers:
a.
McGraw Edison CAL175MHMT2SF BZ
b.
Hubbell RCS-A-H17-H3-F-Q-DBW4
Type CI02Vista AGVSP-LED-DC-HL-C-ZN-WT-UNV-MW:
1.
2.
3.
4.
5.
6.
7.
8.
Description: Recessed 9.25”w x 3.3”h x 4.3”d step light with L.E.D. source
Features: Die cast aluminum step light with louver face.
Housing: Back box constructed of die-cast aluminum alloy.
Louvers: Die-cast aluminum alloy.
Mounting: Recessed wall mounting.
Voltage: Universal (both120 & 277)
Lamp:
White LED’s included
Alternate Manufacturers:
a.
Kenall MSLS)DBCPWLL [120] [277] (9.25”w x 3.75”h x 3.5”d)
16520-4
USPS MASTER SPECIFICATION
Issue Date: 9/17/2005
EXTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
b.
J.
2.
3.
4.
5.
6.
7.
A.
Lumux SL630/LED/BRONZE [120] [277] (10.25”w x 4”h x 3.25”d) ok
Type XF1Canlet 68-02-01-0G-11:
1.
2.3
USPS NO. J80967
COMM. NO. 1597-104
Description: Vaportight incandescent listed and labeled for Class I, Div. 2, Groups C,D,
hazardous locations in accordance with article 501 of the National Electrical Code.
Lens: Heat and impact resistant glass globe.
Housing: Body and guard of lexan polycarbonate.
Mounting: Surface ceiling mounted.
Voltage: 120
Lamps: 135W/A19/130V
Alternate Manufacturer:
a.
Hubbell NVX15GHG
HIGH INTENSITY DISCHARGE (HID) BALLAST
Manufacturers:
1.
2.
3.
4.
5.
Advance Transformer Company, Rosemont, IL (847) 390-5000.
General Electric Company, Nela Park, OH (800) 435-2677.
Magnetek, Nashville, TN (615) 316-5100.
Osram/Sylvania, Danvers, MA (800) 544-4828.
Section 01600 - Product Requirements: Product options and substitutions. Substitutions:
Permitted.
B.
Description: ANSI C82.4, high pressure sodium lamp ballast.
C.
Provide ballast suitable for lamp specified.
D.
Voltage: [277] 208 ]
2.4
A.
COMPACT FLUORESCENT BALLAST
Manufacturers:
1.
2.
3.
4.
Advance Transformer Company, Rosemont, IL (847) 390-5000.
Motorola, Lake Zurich, IL (800) 654-0089.
Magnetek, Nashville, TN (615) 316-5100.
Osram/Sylvania, Danvers, MA (800) 544-4828.
B.
Description: High frequency, energy efficient, electronic fluorescent lamp ballasts with high
power factor suitable and compatible for operating the lamps indicated. The lamp crest factor
shall measure 1.7 or less. Ballasts shall have a minimum "Ballast Factor" of 0.87. Ballasts shall
meet or exceed all EMI and RFI standards of the Federal Communications Commission (FCC)
regulations Part 18 (including 15J). Ballasts shall be UL labeled and comply with all local, State
and Federal efficiency standards.
C.
Voltage 120 and 277 volts to match luminaire voltage.
2.5
A.
LAMPS
High Intensity Discharge (HID) Lamp Manufacturers:
1.
2.
3.
General Electric Company, Nela Park, OH (800) 435-2677.
Osram/Sylvania, Danvers, MA (800) 544-4828.
Philips Lighting Company, Somerset, NJ (800) 555-0050.
16520-5
USPS EXTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
EXTERIOR LIGHTING
4.
Section 01600 - Product Requirements: Product options and substitutions. Substitutions:
Permitted.
B.
NEMA CFT designated lamps must pass the federal Toxic Characteristic Leaching Procedure
(TCLP) test and be classified non-hazardous waste.
C.
Lamp Types: As specified for luminaire. Refer to Section 01600 for substitutions and product
options.
D.
Reflector Lamp Beam Patterns: ANSI C78.379.
2.6
A.
POLES
Manufacturers:
1.
2.
3.
Lithonia: #SSA25 6G-DM DDB.
McGraw Edison SSA6 M25 Wx.
Hubbell SSA-25-60
B.
Section 01600 - Product Requirements:
Permitted.
C.
Material and Finish: Aluminum with dark bronze finish.
D.
Section Shape and Dimensions: 6 inch (15 cm) Square.
E.
Height: 25 feet, (7.62 m).
F.
Base: Nonbreakaway.
G.
Accessories:
1.
2.
3.
H.
Product options and substitutions.
Substitutions:
Handhole.
Anchor bolts.
Base Cover.
Approximate Loading Capacity Ratings:
1.
2.
3.
Luminaire Weight: 72 pounds.
Luminaire and Bracket Effective Projected Area: 5.6 square feet, 12.68 square meters.
Steady Wind: [70] [ ___ ] miles per hour minimum, with gust factor of [1.3] [ ___ ].
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Provide 3000 PSI minimum concrete bases for lighting poles at locations indicated, in
accordance with Section 03300 and details shown on drawings.
B.
Install poles plumb. Provide double nuts to adjust plumb. Grout around each base.
C.
Install lamps in each luminaire.
16520-6
USPS MASTER SPECIFICATION
Issue Date: 9/17/2005
EXTERIOR LIGHTING
WINNETKA CARRIER ANNEX
NORTHBROOK, ILLINOIS
D.
3.2
USPS NO. J80967
COMM. NO. 1597-104
Bond luminaires, metal accessories and metal poles to branch circuit equipment grounding
conductor. Provide supplementary 5/8 inch x 10 foot copper clad rod grounding electrode at
each pole.
FIELD QUALITY CONTROL
A.
Section 01400 : Field inspection.
B.
Operate each luminaire after installation and connection. Inspect for improper connections and
operation.
C.
Measure illumination levels to verify conformance with layout and performance requirements.
D.
Take measurements during night sky, without moon or with heavy overcast clouds effectively
obscuring moon.
3.3
A.
3.4
ADJUSTING
Aim and adjust luminaires to provide illumination levels and distribution as directed.
CLEANING
A.
Section 01700 - Contract Closeout: Cleaning installed work.
B.
Clean electrical parts to remove conductive and deleterious materials.
C.
Remove dirt and debris from enclosure.
D.
Clean photometric control surfaces as recommended by manufacturer.
E.
Clean finishes and touch up damage.
3.5
PROTECTION OF FINISHED WORK
A.
Section 01700 - Contract Closeout: Protecting installed work.
B.
Relamp all luminaires at Substantial Completion.
END OF SECTION
16520-7
USPS EXTERIOR LIGHTING SPECIFICATION
Issued Date: 2/12/2008
EXTERIOR LIGHTING
Page 1 of 14
General Decision Number: IL080009 08/22/2008
IL9
Superseded General Decision Number: IL20070009
State: Illinois
Construction Types: Building, Heavy, Highway and Residential
County: Cook County in Illinois.
BUILDING, RESIDENTIAL, HEAVY, AND HIGHWAY PROJECTS (does not
include landscape projects).
Modification Number
0
1
2
3
4
5
6
7
Publication Date
02/08/2008
02/22/2008
03/21/2008
04/25/2008
06/06/2008
07/04/2008
07/25/2008
08/22/2008
ASBE0017-001 06/01/2007
Rates
Fringes
HAZARDOUS MATERIAL HANDLER
includes preparation,
wetting, stripping removal
scrapping, vacuuming,
bagging and disposal of
all insulation materials,
whether they contain
asbestos or not, from
mechanical systems..........$ 26.00
15.48
Insulator/asbestos worker
Includes the application
of all insulating
materials, protective
coverings, coatings, and
finishes to all types of
mechanical systems..........$ 37.15
19.18
---------------------------------------------------------------BOIL0001-001 07/01/2004
Rates
Fringes
BOILERMAKER......................$ 35.07
16.26
---------------------------------------------------------------* BRIL0021-001 06/01/2008
Rates
Fringes
BRICKLAYER.......................$ 38.03
18.25
---------------------------------------------------------------* BRIL0021-004 06/01/2008
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 2 of 14
Rates
Fringes
Marble Mason.....................$ 38.03
18.25
---------------------------------------------------------------* BRIL0052-001 06/01/2008
Rates
Fringes
Pointer, cleaner and caulker.....$ 38.20
16.41
---------------------------------------------------------------CARP0555-001 06/01/2004
Rates
Fringes
CARPENTER
CARPENTERS, LATHERS,
MLLWRIGHTS, PILEDRIVER, &
SOFT FLOOR LAYERS...........$ 34.32
10.93
---------------------------------------------------------------CARP0555-002 10/01/2004
Rates
Fringes
CARPENTER (Excluding
structures with elevators and
structures over 3 1/2 stories)...$ 34.32
10.91
---------------------------------------------------------------ELEC0009-003 05/26/2008
Rates
Fringes
Line Construction
Groundman...................$ 30.11
40.66%
Lineman and Equipment
Operator....................$ 38.60
40.66%
---------------------------------------------------------------ELEC0134-001 06/04/2007
Rates
Fringes
ELECTRICIAN
Building....................$ 37.80
18.63
Residential.................$ 37.80
18.23
---------------------------------------------------------------ELEC0134-002 04/01/1998
Rates
Fringes
ELECTRICIAN ((CLASS B)
(Install magnetic or
electronic replacement
ballasts either singly or in
groups including necessary
wiring within fixture;
Install replacement lamp
holders and/or sockets
including necessary wiring
within fixture including
relocating sockets within
fixture; Install replacement
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 3 of 14
lighting circuit breakers
where necessary; Install
replacement lighting switches
where necessary; Repair
lighting fixtures other than
ballast or socket
replacements; Rewire
chandeliers or incandescent
fixtures only within fixtures
themselves.).....................$ 20.71
2.975+a+b
FOOTNOTES:
a-Paid Vacation- Employees who have been employed for one
year but less than three years receive 1 week of paid
vacation; employees who have been employed three years but
less than ten years receive 2 weeks of paid vacation;
Employees who have been employed ten years but less than
twenty years receive 3 weeks of paid vacation; and
employees who have worked twenty or more years receive 4
weeks of paid vacation.
b-Funeral Leave-In the instance of the death of a mother,
other-in-law-; father, father-in-law, sister, brother,
husband, wife, or a child of an employee shall receive up
to three days of paid funeral leave.
---------------------------------------------------------------ELEC0134-003 06/07/2004
Rates
ELECTRICIAN
ELECTRICAL TECHNICIAN.......$ 30.89
Fringes
12.59
The work shall consist of the installation, operation,
inspection, maintenance, repair and service of radio,
television, recording, voice sound vision production and
reproduction, telephone and telephone interconnect,
facsimile, data appatatus, coaxial, fibre optic and
wireless equipment, appliances and systems used for the
transmission and reception of signals of any nature,
business, domestic, commercial, education, entertainment
and residential purposes, including but not limited to
communication and telephone, electronic and sound
equipment, fibre optic and data communication systems, and
the performance of any task directly related to such
installation or service whether at new or existing sites,
such tasks to include the placing of wire and cable and
electrical power conduit or other raceway work within the
equipment room and pulling wire and/or cable through
conduit and the installation of any incidential conduit.
---------------------------------------------------------------ELEV0002-003 01/01/2008
Rates
ELEVATOR MECHANIC................$ 43.93
Fringes
16.285+A+B
FOOTNOTES:
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 4 of 14
A. Eight paid holidays: New Year's Day; Memorial Day;
Independence Day; Labor Day; Thanksgiving Day; Day after
Thanksgiving; Veterans' Day and Christmas Day.
B. Employer contributes 8% of regular basic hourly rate as
vacation pay credit for employees with more than 5 years of
service; and 6% for 6 months to 5 years of service.
---------------------------------------------------------------* ENGI0150-006 06/01/2006
Rates
Power equipment operators:
GROUP 1....................$
GROUP 2....................$
GROUP 3....................$
GROUP 4....................$
41.55
40.25
37.70
35.95
Fringes
15.05
15.05
15.05
15.05
POWER EQUIPMENT OPERATORS CLASSIFICATIONS
GROUP 1: Mechanic; Asphalt Plant*; Asphalt Spreader;
Autograde*; Backhoes with Caisson attachment*:Batch Plant*;
Benoto(Requires two Engineers); Boiler and Throttle Valve;
Caisson Rigs*; Central Redi-Mix Plant*; Combination Backhoe
Front Endloader Machine; Compressor and Throttle Valve;
Concrete Breaker (Truck Mounted)*; Concrete Conveyor;
Concrete Conveyor, Truck Mounted; Concrete Paver over 27E
cu. ft.*; Concrete Paver 27E cu ft and Under*; Concrete
Placer*; Concrete Placing Boom; Concrete Pump (Truck
Mounted); Concrete Tower; Cranes*; Cranes, Hammerhead*;
Cranes, (GCI and similar type Requires two operators only);
Creter Crane; Crusher, Stone, etc; Derricks; Derricks,
Traveling*; Formless Curb and Gutter Machine*; Grader,
Elevating; Grouting Machines; Highlift Shovels or Front
Endloader 2 1/4 yd. and over; Hoists, Elevators, Outside
Type Rack and pinion and similar Machines; Hoists, One,
Two, and Three Drum; Hoists, Two Tugger One Floor;
Hydraulic Backhoes*; Hydraulic Boom Trucks; Hydraulic Vac
(and similar equipment);Locomotives; Motor Patrol*; Pile
Drivers amd Skid Rig*; Post Hole Digger; Pre- Stress
Machine; Pump Cretes Dual Ram(Requiring frequent
Lubrication and Water); Pump Cretes; Squeeze Cretes-Screw
Type Pumps Gypsum Bulker and Pump; Raised and Blind Hole
Drill*; Roto Mill Grinder (36" and Over)*; Roto Mill
Grinder (Less Than 36")*; Scoops-Tractor Drawn; Slip-Form
Paver*; Straddle Buggies; Tournapull; Tractor with Boom,
and Side Boom; and Trenching Machines*.
GROUP 2: Bobcat (over 3/4 cu yd); Boilers; Broom, Power
Propelled; Bulldozers; Concrete Mixer (Two Bag and over);
Conveyor, Portable; Forklift Trucks; Greaser Engineer;
Highlift Shovels or Front End loaders under 2 1/4 cu yd;
Aotomatic Hoists, Hoists, Inside Elevators; Hoists, Sewer
Dragging Machine; Hoists, Tugger Single Drum; Laser Screed;
Rock Drill (Self-Propelled); Rock Drill (Truck Mounted)*;
Rollers; Steam Generators; Tractors; Tractor Drawn
Vibratory Roller (Receives an additional $.50 per hour);
Winch Trucks with "A" Frame.
GROUP 3:
Air Compressor-Small 250 and Under (1 to 5 not to
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 5 of 14
exceed a total of 300 ft); Air Compressor-Large over 250;
Combination-Small Equipment Operator; Generator- Small 50
kw and under; Generator-Large over 50 kw; Heaters,
Mechanical; Hoists, Inside Elevators (Remodeling or
Renovatin work); Hydrualic Power Units (Pile Driving,
Extracting, and Drilling); Low Boys; Pumps Over 3" (1 To 3
not to exceed a total of 300 ft); Pumps, Well Points;
Welding Machines (2 through 5); Winches, 4 Small Electric
Drill Winches; Bobcat (up to and including 3/4 cu yd)
GROUP 4 - Bobcats and/or other Skid Steer Loaders; Brick
Forklifts; Oilers
*-Requires Oiler
---------------------------------------------------------------* ENGI0150-025 06/01/2008
Rates
Power equipment operators:
GROUP 1.....................$
GROUP 2.....................$
GROUP 3.....................$
GROUP 4.....................$
GROUP 5.....................$
42.00
41.45
39.40
38.00
36.80
Fringes
20.30
20.30
20.30
20.30
20.30
POWER EQUIPMENT OPERATOR CLASSIFICATIONS
GROUP 1: Asphalt Plant*; Asphalt Heater and Planer
combination; Asphalt Heater Scarfire*, Asphalt Spreader;
Autograder/ GOMACO or similar; ABG Paver*, Backhoes with
Caisson attachment*, Ballast Regulator, Belt Loader*;
Caisson Rigs*Car Dumper, Central Redi-Mix Plant*,
Combination Backhoe; Front End Loader Machine (1 cu yd or
over Backhoe bucket or with attachments); Concrete Breaker
(truck mounted); Concrete Conveyor; Concrete Paver over 27E
cu ft*; Concrete Placer*; Concrete Tube Float; Cranes, all
attachments*; Cranes, Hammerhead, Linden, Peco and machines
of a like nature*; Creter Crane; Crusher, stone; All
Derricks; Derrick Boats; Derricks, traveling*; Dowell
Machine with Air Compressor ($1.00 above Class 1);
Dredges*; Field Mechanic Welder; Formless Curb and Gutter
Machine*; Gradall and machines of a like nature*; Grader,
Elevating; Grader, Motor Grader, Motor Patrol, Auto Patrol,
Form Grader, Pull Grader, Subgrader; Guard Rail Post Driver
mounted*; Hoists, one, two, and three Drum; Hydraulic
Backhoes*; Backhoes with Shear attachments*; Mucking
Machine; Pile Drivers and Skid Rig*; Pre-Stress Machine;
Pump Cretes Dual Ram (requires frequent lubrication and
water)*; Rock Drill- Crawler or Skid Rig*; Rock Drill truck
mounted*; Rock/ Track Tamper; Roto Mill Grinder, (36" and
over)*; Slip-Form Paver*; Soil Test Drill Rig, truck
mounted*; Straddle Buggies; Hydraulic Telescoping Form
(tunnel); Tractor Drawn Belt Loader*; Tractor Drawn Belt
Loader with attached Pusher (two engineers); Tractor with
boom; Tractaire with attachment; Traffic Barrier Transfer
Machine*; Trenching Machine; Truck Mounted Concrete Pump
with boom*; Underground Boring and/or Mining Machines 5 ft
in diameter and over tunnel, etc.*; Wheel Excavator* &
Widener (Apsco); Raised or Blind Hoe Drill, Tunnel & Shaft*
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 6 of 14
GROUP 2: Batch Plant*; Bituminous Mixer; Boiler and Throttle
Valve; Bulldozer; Car Loader Trailing Conveyors;
Combination Backkhoe Front End Loader Machine, (less than 1
cu yd Backhoe Bucket with attachments); Compressor and
Throttle Valve; Compressor, common receiver (3); Concrete
Breaker or Hydro Hammer; Concrete Grinding Machine;
Concrete Mixer or Paver 7S series to and including 27 cu
ft; Concrete Spreader; Concrete Curing Machine; Burlap
Machine; Belting Machine and Sealing Machine; Concrete
Wheel Saw; Conveyor Muck Cars (Haglund or similar type);
Drills (all); Finishing Machine-Concrete; Greaser Engineer;
Highlift Shovels or Front End Loader; Hoist- Sewer Dragging
Machine; Hydraulic Boom Trucks, all attachments;
Hydro-Blaster (requires two operators); Laser Screed*;
Locomotives, Dinky; Off-Road Hauling Units (including
articulating); Pump Cretes; Squeeze Cretes-Screw Type
pumps, Gypsum Bulker and Pump; Roller Asphalt; Rotary Snow
Plows; Rototiller, Seaman, self-Propelled; Scoops-Tractor
Drawn; Self- propelled Compactor; Spreader-Chip-Stone;
Scraper; Scraper-Prime Mover in Tandem regardless of size
(add $1.00 to Group 2 hourly rate for each hour and for
each machine attached thereto add $1.00 to Group 2 hourly
rate for each hour); Tank Car Heater; Tractors, Push,
pulling Sheeps Foot, Disc, or Compactor, etc; Tug Boats
GROUP 3: Boilers; Brooms, all power propelled; Cement Supply
Tender; Compressor, Common Receiver (2); Concrete Mixer,
two bag and over; Conveyor, Portable; Farm type Tractors
used for mowing, seeding, etc; Fireman on Boilers; Forklift
Trucks; Grouting Machines; Hoists, Automatic; Hoists, all
Elevators; Hoists, Tugger single Drum; Jeep Diggers; Low
Boys; Pipe Jacking Machines; Post-hole Digger; Power Saw,
Concrete, Power Driven; Pug Mills; Rollers, other than
asphalt; Seed and Straw Blower; Steam Generators; Stump
Machine; Winch Trucks with A-Frame; Work Boats; Tamper-Form
motor driven
GROUP 4: Air compressor - Small 250 and under (1 to 5 not to
exceed a total of 300 ft); Air Compressor - Large over 250;
Combination - Small Equipment Operator; Directional Boring
Machine; Generators - Small 50 kw and under; Generators Large , over 50 kw; Heaters, Mechanical; Hydraulic power
unit (Pile Driving, Extracting or Drilling); Light Plants
(1 to 5); Pumps, over 3" (1 to 3, not to exceed a total of
300 ft); Pumps, Well Points; Tractaire; Welding Machines (2
through 5); Winches, 4 small electric drill winches;
GROUP 5: Bobcats (All); Brick Forklifts; Oilers; Directional
Boring
*Requires Oiler
---------------------------------------------------------------IRON0001-026 06/01/2008
Rates
Fringes
IRONWORKER (Structural and
Reinforcing).....................$ 40.25
24.99
----------------------------------------------------------------
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 7 of 14
IRON0063-001 06/01/2008
Rates
Fringes
IRONWORKER, ORNAMENTAL...........$ 39.05
19.64
---------------------------------------------------------------IRON0063-002 06/01/2007
Rates
Fringes
IRONWORKER
Fence Erector...............$ 28.64
12.75
Metal Fence Erector.........$ 22.54
12.04
---------------------------------------------------------------IRON0136-001 07/01/2006
Rates
Fringes
IRONWORKER
Machinery Movers & Riggers..$ 30.24
19.87
Master Riggers..............$ 32.74
19.87
---------------------------------------------------------------LABO0002-006 06/01/2007
Rates
Laborers:
GROUP 1....................$ 33.15
GROUP 2....................$ 33.15
GROUP 3....................$ 33.225
GROUP 4....................$ 33.25
GROUP 5....................$ 33.30
GROUP 6....................$ 33.35
GROUP 7....................$ 33.375
GROUP 8....................$ 33.375
GROUP 9....................$ 33.475
GROUP 10....................$ 33.60
GROUP 11....................$ 33.425
GROUP 12....................$ 34.15
Fringes
13.87
13.87
13.87
13.87
13.87
13.87
13.87
13.87
13.87
13.87
13.87
13.87
LABORER CLASSIFICATIONS
GROUP 1: Building Laborers; Plasterer Tenders; Pumps for
Dewatering; and other unclassified laborers.
GROUP 2:
Fireproofing and Fire Shop laborers.
GROUP 3:
Cement Gun.
GROUP 4:
Chimney over 40 ft.; Scaffold Laborers.
GROUP 5: Cement Gun Nozzle Laborers (Gunite); Windlass and
capstan person.
GROUP 6:
Stone Derrickmen & Handlers.
GROUP 7: Jackhammermen; Power driven concrete saws; and
other power tools.
GROUP 8:
Firebrick & Boiler Laborers.
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 8 of 14
GROUP 9: Chimney on fire brick; Caisson diggers; & Well
Point System men.
GROUP 10:
Boiler Setter Plastic Laborers.
GROUP 11:
Jackhammermen on fire brick work only.
GROUP 12: Dosimeter use (any device) monitoring nuclear
exposure); Asbestos Abatement Laborer; Toxic and Hazardous
Waste Removal Laborers.
---------------------------------------------------------------LABO0002-007 06/01/2007
Rates
Laborers:
GROUP
GROUP
GROUP
GROUP
GROUP
1.....................$
2.....................$
3.....................$
4.....................$
5.....................$
33.15
33.425
33.30
33.425
34.15
Fringes
13.87
13.87
13.87
13.87
13.87
LABORER CLASSIFICATIONS
GROUP 1: Common laborer; Tenders; Material expeditor
(asphalt plant); Street paving, Grade separation, sidewalk,
curb & gutter, strippers & All laborers not otherwise
mentioned
GROUP 2: Ashpalt tampers & smoothers; Cement gun laborers
GROUP 3: Cement Gun Nozzle (laborers), Gunite
GROUP 4: Rakers, Lutemen; Machine-Screwmen; Kettlemen;
Mixermen; Drun-men; Jackhammermen (asphalt); Paintmen;
Mitre box spreaders; Laborers on birch, overman and similar
spreader equipment; Laborers on APSCO; Laborers on air
compressor; Paving Form Setter; Jackhammermen (concrete);
Power drive concrete saws; other power tools.
GROUP 5: Asbestos Abatement Laborers; Toxic and Hazardous
Waste Removal Laborers, Dosimeter (any device) monitoring
nuclear exposure
---------------------------------------------------------------LABO0002-008 06/01/2007
Rates
Laborers: (Compressed Air)
0 - 15 POUNDS...............$
16 - 20 POUNDS..............$
21 - 26 POUNDS..............$
27 - 33 POUNDS..............$
34 - AND OVER...............$
Laborers: (Tunnel and Sewer)
GROUP 1.....................$
GROUP 2.....................$
GROUP 3.....................$
GROUP 4.....................$
Fringes
34.15
34.65
35.15
36.15
37.15
13.87
13.87
13.87
13.87
13.87
33.15
33.275
33.375
33.50
13.87
13.87
13.87
13.87
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 9 of 14
GROUP 5.....................$ 34.15
13.87
LABORER CLASSIFICATIONS (TUNNEL)
GROUP 1: Cage tenders; Dumpmen; Flagmen; Signalmen; Top
laborers
GROUP 2: Air hoist operator; Key board operator; concrete
laborer; Grout; Lock tenders (Free Air Side); Steel
setters; Tuggers; Switchmen; Car pusher
GROUP 3: Concrete repairmen; Lock tenders (pressure side);
Mortar men; Muckers; Grout machine operators; Track layers
GROUP 4: Air trac drill operator; Miner; Bricklayer tenders;
Concrete blower operator; Drillers; Dynamiters; Erector
operator; Form men; Jackhammermen; Powerpac; Mining machine
operators; Mucking machine operator; Laser beam operator;
Liner plate and ring setters; Shield drivers; Power knife
operator; Welder- burners; Pipe jacking machine operator;
skinners; Maintenance technician
GROUP 5: Asbestos abatement laborer; Toxic and hazardous
waste removal laborer; Dosimeter (any device) monitoring
nuclear exposure
LABORER CLASSIFICATIONS (SEWER)
GROUP 1:
Signalmen; Top laborers and All other laborers
GROUP 2:
Concrete laborers and Steel setters
GROUP 3: Cement carriers; Cement mixers; Concrete repairmen;
Mortar men; Scaffold men; Second Bottom men
GROUP 4: Air trac drill operator; Bottom men;
Bracers-bracing; Bricklayer tenders; Catch basin diggers;
Drainlayers; dynamiters; Form men; Jackhammermen; Powerpac;
Pipelayers; Rodders; Welder-burners; Well point systems men
GROUP 5: Asbestos abatement laborer, Toxic and hazardous
waste removal laborer; Dosimeter (any device) monitoring
nuclear exposure
---------------------------------------------------------------LABO0225-001 06/01/2007
Rates
Laborers:
(DEMOLITION/WRECKING)
Group 1.....................$ 26.85
Group 2.....................$ 32.40
Group 3.....................$ 33.15
Fringes
13.87
13.87
13.87
LABORER CLASSIFICATIONS
GROUP 1 - Complete Demolition
GROUP 2 - Interior Wrecking and Strip Out Work
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 10 of 14
GROUP 3 - Asbestos Work with Complete Demolition/Wrecking or
Strip Out Work
---------------------------------------------------------------* MARB0067-001 06/01/2008
Rates
Fringes
TERRAZZO WORKER/SETTER...........$ 37.39
17.38
TILE FINISHER....................$ 32.15
13.62
TILE SETTER......................$ 38.63
15.34
---------------------------------------------------------------* MARB0087-001 06/01/2008
Rates
Fringes
MARBLE FINISHER..................$ 28.65
18.17
---------------------------------------------------------------PAIN0014-001 06/01/2008
Rates
Fringes
PAINTER
Including Taper.............$ 36.90
16.32
---------------------------------------------------------------PAIN0027-001 06/01/2008
Rates
Fringes
GLAZIER..........................$ 37.00
20.13
---------------------------------------------------------------PLAS0005-002 07/01/2008
Rates
Fringes
PLASTERER........................$ 38.10
16.35
---------------------------------------------------------------PLAS0502-001 06/01/2008
Rates
Fringes
CEMENT MASON/CONCRETE FINISHER...$ 41.85
15.43
---------------------------------------------------------------PLUM0130-001 06/01/2007
Rates
Fringes
PLUMBER..........................$ 41.00
16.93
---------------------------------------------------------------* PLUM0597-002 06/01/2008
Rates
Fringes
PIPEFITTER.......................$ 42.05
17.58
---------------------------------------------------------------ROOF0011-001 12/01/2007
Rates
Fringes
ROOFER...........................$ 35.00
11.00
----------------------------------------------------------------
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 11 of 14
SFIL0281-001 01/01/2008
Rates
Fringes
SPRINKLER FITTER.................$ 40.50
16.00
---------------------------------------------------------------SHEE0073-001 01/01/2007
Rates
Fringes
Sheet Metal Worker...............$ 36.96
17.42
---------------------------------------------------------------SHEE0073-002 01/01/2007
Rates
Fringes
Sheet Metal Worker
ALUMINUM GUTTER WORK........$ 24.03
17.42
---------------------------------------------------------------TEAM0731-001 06/01/2008
Rates
TRUCK DRIVER
2 & 3 Axles.................$
4 Axles.....................$
5 Axles.....................$
6 Axles.....................$
Fringes
30.70
30.95
31.15
31.35
12.20
12.20
12.20
12.20
FOOTNOTES FOR TRUCK DRIVERS:
A. Paid Holidays: New Year's Day, Memorial Day,
Independence Day, Labor Day, Thanksgiving Day, and
Christmas Day.
B. 900 straight time hours or more in 1 calendar year for
the same employer shall receive 1 week paid vacation; 3
years - 2 weeks paid vacation; 10 years - 3 weeks paid
vacation; 20 years - 4 weeks paid vacation.
---------------------------------------------------------------TEAM0731-002 06/01/2008
Rates
Fringes
TRUCK DRIVER (DEMOLITION)
2 OR 3 Axles................$ 30.70
12.20
4 Axles.....................$ 30.95
12.20
5 Axles.....................$ 31.15
12.20
6 Axles.....................$ 31.35
12.20
---------------------------------------------------------------TEAM0731-003 05/01/1997
Rates
Fringes
Traffic Control Device Monitor
TRAFFIC SAFETY WORKERS:
Traffic Safety Worker
primary duties include but
are not limited to the
delivery, maintenance and
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 12 of 14
pick-up of traffic control
devices, the set-up and
installation of traffic
signs, pavement markings,
barricades, crash barrels
and glare screens, and
traffic control
surveillance, the repair
and maintenance of the
company's trucks, cars,
arrow boards, message
signs, barricade and sign
fabrication equipment......$ 16.15
108.75/wk+a
FOOTNOTE a:
1. The following paid holidays: New Year's Day; Memorial Day;
Independence Day; Labor Day; Thanksgiving Day; and
Christmas Day provided the employee has earned a vacation
the previous year or have worked thirty-one days in the
current year before the holiday, or have seniority as
stated herein; work the scheduled work day before and the
scheduled day after the holiday; work one day in the
holiday week; and work one scheduled work day after the
holiday.
2. Paid vacation is earned the first year of employment, but
may not be taken until after their first anniversary date.
One and two years of employment receive 40 hours of paid
vacation; Three thru nine years of employment receive 80
hours of paid vacation; Ten thru nineteen years of
employment receive 120 hours of paid vacation; and Twenty
years and over receive 160 hours of paid vacation.
3. Personal time (floating holidays) will be earned on a per
hour worked basis. New employees will earn personal time
during the first year of employment, but may not be take
personal time until after their first anniversary date.
Personal time is earned in the following way: One and two
years receive 8 hours of personal time; Three thru nine
years receive sixteen hours of personal time; and ten years
and over receive twenty-four hours of personal time.
---------------------------------------------------------------TEAM0786-001 06/01/2004
Rates
TRUCK DRIVER
2 & 3 Axles.................$
4 Axles.....................$
5 Axles.....................$
6 Axles.....................$
Fringes
27.625
27.875
28.075
28.625
d,e,f
d,e,f
d,e,f
d,e,f
FOOTNOTES FOR TRUCK DRIVERS (BUILDING & RESIDENTIAL):
d.
$327.00 per week.
e. Paid Holidays: New Year's Day, Memorial Day,
Independence Day, Labor Day, Thanksgiving Day, and
Christmas Day.
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 13 of 14
f. 900 straight time hours or more in 1 calendar year for
the same employer shall receive 1 week paid vacation; 3
years - 2 weeks paid vacation; 10 years - 3 weeks paid
vacation; 20 years - 4 weeks paid vacation.
---------------------------------------------------------------WELDERS - Receive rate prescribed for craft performing
operation to which welding is incidental.
================================================================
Unlisted classifications needed for work not included within
the scope of the classifications listed may be added after
award only as provided in the labor standards contract clauses
(29CFR 5.5 (a) (1) (ii)).
---------------------------------------------------------------In the listing above, the "SU" designation means that rates
listed under the identifier do not reflect collectively
bargained wage and fringe benefit rates. Other designations
indicate unions whose rates have been determined to be
prevailing.
---------------------------------------------------------------WAGE DETERMINATION APPEALS PROCESS
1.) Has there been an initial decision in the matter? This can
be:
*
*
*
*
an existing published wage determination
a survey underlying a wage determination
a Wage and Hour Division letter setting forth a position on
a wage determination matter
a conformance (additional classification and rate) ruling
On survey related matters, initial contact, including requests
for summaries of surveys, should be with the Wage and Hour
Regional Office for the area in which the survey was conducted
because those Regional Offices have responsibility for the
Davis-Bacon survey program. If the response from this initial
contact is not satisfactory, then the process described in 2.)
and 3.) should be followed.
With regard to any other matter not yet ripe for the formal
process described here, initial contact should be with the
Branch of Construction Wage Determinations. Write to:
Branch of Construction Wage Determinations
Wage and Hour Division
U.S. Department of Labor
200 Constitution Avenue, N.W.
Washington, DC 20210
2.) If the answer to the question in 1.) is yes, then an
interested party (those affected by the action) can request
review and reconsideration from the Wage and Hour Administrator
(See 29 CFR Part 1.8 and 29 CFR Part 7). Write to:
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Page 14 of 14
Wage and Hour Administrator
U.S. Department of Labor
200 Constitution Avenue, N.W.
Washington, DC 20210
The request should be accompanied by a full statement of the
interested party's position and by any information (wage
payment data, project description, area practice material,
etc.) that the requestor considers relevant to the issue.
3.) If the decision of the Administrator is not favorable, an
interested party may appeal directly to the Administrative
Review Board (formerly the Wage Appeals Board). Write to:
Administrative Review Board
U.S. Department of Labor
200 Constitution Avenue, N.W.
Washington, DC 20210
4.) All decisions by the Administrative Review Board are final.
================================================================
END OF GENERAL DECISION
http://www.wdol.gov/wdol/scafiles/davisbacon/IL9.dvb
9/4/2008
Download