ELECTRONICON KONDENSATOREN GMBH GERA GERMANY Introduction The following technical note provide planners and users with an overview of fundamentals and practice, as well as a description of our products and services related to reactive power compensation and power quality - two topics that are closely linked; because problem optimised reactive power compensation achieves an improvement of mains and power network quality. We have attempted to make your choice of the correct solution for your problem as simple as possible. The hurried, well versed expert will find the information he needs quickly with the help of the list of contents or the problem oriented index selection scheme. Those who require more comprehensive information should take the time to read on. Many electrical devices, e.g. single-phase and three-phase motors, require inductive reactive power Q for the build-up and decay of their magnetic fields, in addition to the active power that is transformed into mechanical work. These inductive loads draw a current I from the power network that lags behind the voltage U. Voltage and current at an inductive load voltage U current I 0 90 180 270 360 450 540 630 We have taken care to include in this folder all that you need from the planning phase to placing your order. This does not however release you from conscientiously clarifying each case, taking local conditions and the applicable regulations into account. If you are in doubt, we will gladly provide you with advice and practical support and, if you wish, even during your preliminary planning. Basics of reactive power compensation Electricity is the most important and cleanest form of energy and its application is virtually unlimited due to its convenient transmission. The transmission of active energy is uppermost. It is released by electrical consumers, e.g. as mechanical work, heat or light. Consumers that draw only active power P from the power system are referred to as resistive loads. These include filament lamps and electrical heaters. The current I drawn by them from the power network has no phase displacement relative to the network voltage U. Voltage and current at a resistive load voltage U current I All transmission devices must also be designed to accommodate the additional reactive current component - this costs a lot of money. Reactive work is normally measured by the energy supplier and billed to commercial users due to the additional losses and loading. reactive power Q Chapter 1 In contrast to active energy, reactive energy is not drawn continuously from the power network, but swings between the load and the power station generator. It loads the transmission equipment and leads to undesirable additional losses and thus to considerable pollution by CO². active power P In this note MKP capacitors means Metalliziert Kunstoff Polypropylene which is the same as MPP Metallised Polypropylene, the term popularly used in India. M This can constitute a significant part of the electricity bill. 0 90 180 270 360 450 540 630 The useless reactive energy component of the transmitted energy should be kept as small as possible to minimise pollution as well as equipment and energy costs. Since reactive power is however indispensable for the consumer, an attempt must be made to provide it from sources other than the power network. In contrast to inductive loads, capacitors possess the ability to draw a current I from the power network that leads the network voltage U. They require capacitive reactive energy to build up their electric field. 1 Voltage and current at an inductive load voltage U current I 0 90 180 270 360 450 540 In the case of an unknown phase angle j , the apparent power can also be calculated from the root sum of squares of active and reactive power: S= P²+ Q² 630 Sinusoidal voltage and non-sinusoidal current M reactive power Q active power P An inductive reactive current and an equally large capacitive reactive current cancel each other. The inductive reactive current, e.g. from motors, can therefore be compensated by the capacitive reactive current from capacitors. This process is known as reactive current or reactive power compensation. Equations and relationships Sinusoidal voltage and sinusoidal current The apparent power S for sinusoidal voltage and sinusoidal current is calculated as the product of voltage U and current I: The current in most power networks has serious harmonic distortion, i.e. non-sinusoidal, due to increasing use of equipment with a non-linear currentvoltage characteristic. The voltage normally has a lower distortion, which can be neglected in power calculations. The active power can be generated only between voltages and currents of the same frequency. The harmonic currents can generate only the reactive power component D with the fundamental component of the voltage. This reactive power caused by the harmonically distorted current is referred to as harmonic reactive power. In contrast to this, the reactive power Q1 caused by the phase displacement j 1 is known as the displacement reactive power. Cosj 1 is therefore also known as the displacement factor. The apparent power is therefore: S= P²+ Q 1 ²+ D² Active power is transported only in the fundamental wave: P= U× I1 × cosj 1 The ratio between active power and apparent power is known as the power factor l : S = U·I P P l = = S P²+ Q1 ²+ D² For any phase anglej , the active power P is: The displacement factor cosj 1 results from: P = U · I · cosj = S · cosj Cosj is a measure for the ratio of active to apparent power: cos j = The reactive power Q for a sine waveform is calculated from: Q = S · sinj P P cosj = 1 = S1 P²+ Q1 ² It is also known as the power factor of the fundamental in the special case of sinusoidal voltage and non-sinusoidal current. The form of all quantities (power factor, displacement factor, apparent power, active power, reactive power and harmonic reactive power) can be comprehended easily with the aid of a diagram with a right-angled coordinate system. 2 The following relationship applies between the powers: Individual compensation with automatic capacitor banks can be beneficial for large loads with widely varying reactive power needs. S² = P² + Q² + D² Group power factor correction In the case of group compensation, several, mostly neighbouring, simultaneously operating inductive loads e.g. in one sub-distribution, are grouped together and compensated there by one fixed capacitor. The load group These comments should give a feeling for the relationships. A deeper consideration of the complex topic of harmonic reactive power would go beyond the aims of this document and is unnecessary for its terms of reference. Chapter 2 Types of compensation Individual power factor compensation Individual power factor compensation is typical for the operation of individual asynchronous motors, generators, transformers, welding devices, discharge lamps and as a harmonic absorber at larger harmonic sources. Individual compensation compensates inductive reactive power immediately at the place of origin. A corresponding capacitor is allocated to each inductive load. Benefits of individual compensation: can consist, for example, of motors or lighting with discharge lamps. If the load and the capacitor are connected jointly to the power network by means of one contractor or switch, then separate switches are also unnecessary for group compensation. If the loads are switched separately, then the capacitor must be equipped with a separate switch device, which is closed only when all loads are in operation. In contrast to individual compensation, the load on the feeder lines to the individual loads is not removed, but only the feeder to the load group. Larger lighting systems are often compensated in groups for economic reasons. Benefits of group compensation: Fewer separate components than with individual compensation l Unloading of the feeder to the group distribution l Central compensation with automatic capacitor banks Consumer installations usually possess a varying reactive power requirement. Unregulated fixed compensation is not possible in such cases, since an uneconomical under-compensation or a dangerous overcompensation can occur. One must therefore continuously adjust the capacitor power to the required reactive power requirement. Reduction of burden on the feeder to the load l Additional switchgear normally unnecessary l Individual compensation is economical for loads with: Higher powers (> 20 kW) l One achieves this by means of automatic capacitor banks, which are directly assigned to a switchgear unit, distribution, and sub-distribution or to a large load with fluctuating reactive power requirements. Constant power l Mainly continuous operation l 3 Apart from the power section with fuses, switches, reactors and capacitors, automatic capacitor banks contain a reactive power regulator, which measures the reactive power present at the supply point. If power consumption is measured on the high-voltage side, then it is sensible to use individual compensation (no-load reactive power) of the feeder transformer using a fixed stage. If deviations from the applied setpoint occur, it switches capacitors on or off in stages. A base load can be programmed in automatic capacitor banks to compensate series-connected transformers. Benefits of central compensation: Automatic adjustment of the compensation power to the momentarily required active power. Chapter 3 Exploitation of the simultaneity factor of the loads; thus less capacitor power necessary. Characteristics and functionality of compensation equipments Important for planners and practitioners More economic, since minimised use of separate components, especially in the case of reactor protected systems. Power capacitors l l l Adaptation to changing conditions by simple extensibility. l Light, simple, economic monitoring due to centralised layout. l Selection of the most beneficial compensation type Economic and technical system aspects must be considered when deciding whether the individual loads can be compensated most beneficially with fixed capacitors or with central automatic capacitor banks. One can assume that central compensation is 1.3 - 1.5 times more expensive than individual compensation for the same power. If one however takes into account that in most companies, it is rare that all loads are in operation simultaneously, lower capacitor power is sufficient for central compensation. Both types of compensation are already equally priced at a simultaneity factor of approx. 0.70. Central compensation offers a further advantage particularly in the case of reactor protected capacitors, since the high protection classes often needed for fixed capacitors can be achieved only at extremely high extra cost in the case of reactor protection. A combination of different types of compensation can be worthwhile under certain technical system conditions, e.g. to compensate large loads running for long periods individually, in order to reduce the loading on transmission lines, and the remaining reactive current of the other loads centrally at the main distribution board. Several automatic capacitor banks, e.g. at main distribution and sub-distribution boards or at controlled large consumers, are also conceivable for similar reasons. One speaks of mixed compensation in such cases. Power capacitors should be employed wherever technically possible for reactive power compensation and for the reduction of harmonics, due to a higher price-performance ratio than achieved by other solutions. They distinguish themselves by: l Simple, low-priced technology l Long service life and low maintenance cost l High operational security l Low losses l See Chapter 4 – “Capacitor technology” for more details. Connections and protection equipment Connection lines in and to compensation systems and their protection equipment should be designed to continuously carry 1.5 times the capacitor nominal current. This also applies to fuses, which should also have a time-lag characteristic. The ambient temperature and applicable regulations should also be observed. Switching of capacitors Connecting a single capacitor normally causes no problems, since the inrush current is limited by the impedance of series-connected transformers and cables (assuming satisfactory discharge before re-switching). Switching a capacitor in parallel to capacitors that are already switched on is significantly more critical. These supply a high inrush current, which is limited only by the small impedance of the connection cables. Care must be taken when switching capacitors in compensation systems to ensure that the impedance between the capacitors is sufficiently high to reduce the inrush current to reasonable values. 4 This is achieved in non-reactor protected systems by using special capacitor switching contractors. These are equipped with precharging resistors as a permanent component of the contractors. The capacitor is first connected to the network via these resistors by means of early closing contacts, before the main contacts close. The inrush current is then only approx. 5% of the nonattenuated value. Capacitors with a series-connected reactor can be connected to the network without this precaution, since sufficient attenuation is normally achieved by the reactor inductance. The inrush current surge lies between 10 and 20% of the non-attenuated value. Power-up is performed in dynamic automatic capacitor banks with thyristor switches with the aid of a special control system. Thyristor switches switch almost without interaction when the voltage is equal between input and output. See Chapter 9 – “Compensation in mains with quick load changes” for more details. Operational reliability of compensation systems is largely dependent upon the quality and load reserves of the employed switchgear. Discharge devices Discharge devices are necessary to discharge capacitors to an uncritical residual voltage after disconnection from the network voltage and before reconnection. They must be suitable to absorb and allow the energy stored in the capacitor We = ½ CU² to decay within a period of seconds. One achieves this with corresponding resistor combinations, special discharge modules or discharge reactors. Discharge reactors allow rapid discharge with low losses. To comply with IEC60831-1, every capacitor unit must be capable of reliable discharge within three minutes to a residual voltage of <= 75 V. As a basic rule: The residual capacitor voltage when reconnected must be no higher than 10% of the capacitor rated voltage. This must be taken into account especially for switched capacitors for individual compensation and for automatic capacitor banks. The controller reconnection time should be at least 10% longer than the capacitor discharge time. Connection to the supply network with phase opposition to the insufficiently discharged capacitor must be avoided under all circumstances. Achievable reconnection times using different techniques: A reactive power controller detects the momentary reactive power requirement by means of voltage and current measurements in the feeder to the consumer's installation (distribution or sub-distribution). The capacitor power is adjusted by connection or disconnection in such a manner that a target cos programmed at the regulator is reached. To avoid the reconnection of capacitors that have not yet been discharged, certain switching or lock-out times are specified or preselectable in the reactive power regulator, which are to be taken into account when choosing discharge devices. The distribution of the total power among the switched regulator control taps (control outputs) is specified with the control series. It contains the number of steps and their power ratings as a factor of the power of the first step, which is defined as 1. The cross-sum of the control series gives the number of combination steps of the compensation system. For example: Control series with four control steps of the same power: 1:1:1:1, the compensation system is regulated in 1+1+1+1 = 4 combination steps. Or: All steps are provided with double the power of the previous step: 1:2:4:8, the compensation system is regulated in 1+2+4+8 = 15 combination steps. In this manner, it is possible to implement reactive power compensation systems, with which the number of steps is significantly higher than the number of control outputs at the reactive power controller. Reactive power compensation systems are normally provided with 6 to 20 combination steps. The graduation is too coarse with smaller numbers of steps, while more steps do not offer a significant improvement of cos . In practice, one should choose control series up to 1:2:4:4:4 ... . In this manner, a controller achieves with 4 control steps and a control series 1:2:4:4 = 11 combination steps and a controller achieves with eight control steps and a control series 1:2:4:4:4:4:4:4 = 27 combination steps. Steeper control series (e.g. 1:2:4:8:16...) should remain an exception. Controllers with 8 control steps fulfil all practical requirements. If one wishes to utilise the wear optimisation facility (loading back method) in modern controllers, then each partial power should be provided at least twice in the control series to allow a change between capacitor taps. A relatively fine grading for 250 kVAR total power could, for example, be arranged as follows: 1 : 1 : 2 : 2 : 2 : 4 : 4 : 4 = 20 combination steps An increasing number of applications require significantly shorter reconnection times. See Chapter 9 – “Compensation in networks with quick load changes” for more details. Regulation, number of steps and control series Most consumer installations are compensated using automatic capacitor banks due to the recognised benefits. The compensation power is designed with switched steps to match the employed capacitor power to the fluctuating load situation in the consumer's system. 12.5 : 12.5 : 25 : 25 : 25 : 50 : 50 : 50 = 250 kVAR or a little cheaper with one free tap but fewer change possibilities: 1 : 1 : 2 : 4 : 4 : 4 : 4 : 0 = 20 combination steps 12.5 : 12.5 : 25 : 50 : 50 : 50 : 50 : 0 = 250 kVAR Systems with such graduated control series can be set up more economically than systems with control series 1:1:1:1… and they function more effectively with modern controllers. 6 Several capacitor contractors can, of course, be controlled from one control output. l High quality controllers and automatic capacitor banks should: l Be connectable without attention to phase, phase relation and current direction l Should calibrate themselves and become operational immediately with minimal adjustment l Safely prevent that capacitors are reconnected before they have been discharged to an uncritical value l Have a load dependent control characteristic and correct reactive power load fluctuations as quickly as possible, while protecting the installation and network, by direct switching l Use the installed capacitor power optimally by separately adjustable target and alarm cos Possess a facility (in the case of high voltage measurement) to program a base load for the compensation of the seriesconnected power network transformer l Be simple to operate and possess clear display logic, which shows all important network and installation data l Evaluate all relevant network and installation data and generate an alarm if a danger of overload occurs and, if necessary, disconnect endangered capacitor taps or the whole system l Store critical maximum values such as power network voltage and harmonic loading (3rd, 5th, 7th, 11th harmonics) l There is no alternative: Quality pays for itself, not only for the controller, but for all components in the automatic capacitor bank. Reactor protection Most automatic capacitor banks employed today are provided with reactor protection as a result of the increasing harmonic loading of the consumer installation and the power networks. Every capacitor or capacitor tap is connected in series to an inductance (reactor), in contrast to "normal" unprotected compensation. If the resonant frequency of the series resonant circuit formed in this way deviates by more than 10% from the frequency of the nearest harmonic, then one speaks of a detuned resonator circuit. Reactor protected compensation systems are designed as detuned resonator circuits and the series resonant frequency f0 is normally chosen to be below the frequency of the 5th harmonic (250 Hz). The capacitor and reactor system is therefore inductive for all harmonic frequencies >= 250 Hz and dangerous resonance between the capacitor and network inductance (e.g. transformer) is therefore avoided. Consumer installations with high 3rd harmonic (150 Hz) components are an exception but it can become necessary to set the series resonant frequency to 134 Hz in such cases. If the series resonant frequency is less than 10% below or above a harmonic frequency, then it is described as a tuned resonator circuit. Tuned resonator circuits are normally employed as wave traps for the deliberate reduction of individual harmonics. Tariff switching Some supply networks require that cos be limited to a certain maximum Reactor protection-factor p The reactor-protection factor p [%] specifies the ratio of the reactor reactance to the capacitor reactance at network frequency. value, e.g. 0.85 or 0.9 during low-load periods. A controller with tariff switchover is necessary in such cases, which allows separate target cos to The resonant frequency of the series resonant circuit can also be calculated from p using the following equation: be specified for high-load and low-load periods. This is activated by an external signal. 1 fR = f1 × p For example: p=7 %, f1 = 50 Hz Control quality Increasing harmonic load, more sensitive manufacturing processes and economic considerations in consumer systems designed only for the active component pose ever increasing demands on the reliability and safety of automatic capacitor banks. Besides this, their network interaction should be as low as possible: l If the automatic capacitor bank fails, the main switch could trip and production be interrupted. Claims for compensation due to excessively high reactive power costs are also becoming more frequent. l If the automatic capacitor bank does not switch back due to a controller defect or incorrect wiring, a dangerous capacitive overload can occur during low-load periods. l Serious damage can occur if the automatic capacitor bank is overloaded by harmonics, for example, and it does not switch off. The safety standards demanded today cannot be offered by a 100 € controller and the 100 € saving is quickly swallowed by the first maintenance trip to the customer - without mentioning the loss of confidence. f R 1 = 50 Hz × = 189 Hz 0.07 One of the often-tried standard values is normally used for the choice of a suitable reactor-protection factor for the application: The selection of the correct reactor protection prevents inadmissible influences from the compensation system on any existing audio-frequency ripple control system and reduces existing harmonics. See Chapter 7 – “Compensation in mains with harmonics” and Chapter 8 – “Compensation in mains with audio-frequency ripple control systems” for more details. 7 Capacitor rated voltage with reactor protection A voltage increase arises at the capacitor from the serial connection of the reactor and capacitor. It can be calculated from the reactor-protection factor p: 1 UC = UNet × 1p The controller manufacturer's correction factors should be observed at other voltages. If a capacitor is requested for fixed compensation of the feeder transformer, then it is to be installed in front of the current transformer. The correct installation position for the current transformer For example: p = 7%, UNet = 400 V 1 430 V UC = 400 V × = 1 - 0.07 The capacitors employed for p = 7% must therefore be suitable for a continuous rated voltage of at least 430 V. Retrospective reactor protection The voltage increase at the capacitor is a reason why old unprotected automatic capacitor banks cannot be protected by reactors retrospectively. The higher current associated with retrospective reactor protection would often also exceed the switching capability of the contractors. Unprotected capacitors that have been installed in networks for a long period normally show considerable capacitance losses. The capacitance for reactor protection should not deviate from the nominal capacitance by more than ± 5%. Voltage and current measurement The reactive power controller requires both voltage and current measurements to determine the load conditions. An approximately symmetrical network is normally assumed and a single-phase measurement system employed. This is not normally a restriction, since the capacitor power is usually provided only with three-phase switching. The voltage can be measured at the compensation system power terminals. A current transformer (secondary current preferably 5 A) must be inserted in the feeder line of the distribution / consumer installation to measure the current. Modern reactive power compensation systems permit the installation of the current transformer in any phase, without taking the current direction into consideration, with the help of an automatic calibration phase. Only the installation position of the current transformer must be correct. It is installed in such a manner that, as seen from the supply network, it is located in front of all loads and also in front of the compensation system terminals. The rating of the current transformer is chosen to suit the maximum current in the feeder to the consumer installation to be compensated. Excessively rated current transformers impair the control accuracy. If the phases are loaded unequally, the current transformer should be installed in the phase with the medium loading. If other measuring instruments are to be connected to the same current transformer, then the current paths of both devices are to be connected in series (observe maximum loading VA). The cross-section of the measuring leads should be 2.5 mm² for lengths up to 10 m, and 4 mm² for longer lengths. The power ratio of the smallest capacitor step in kVAR, divided by the CT transformation ratio should be >= 0.05 at 400 V. controller The most frequent errors can be quickly determined, since modern controllers provide corresponding error signals. If the current transformer is installed in the feeder to the loads, the reactive power controller cannot measure the load current change and an error signal is output. The reactive power controller cannot detect a load current change and outputs a signal when the current transformer is installed in the feeder to the compensation system. Summation current transformers In the case of consumer installations with two or more feeders to one busbar system or several busbar sections with continuously closed bus coupler switches, the current in each feeder is to be measured using current transformers. The secondary currents of the individual current transformers are evaluated by means of a corresponding summation current transformer, which can be installed in the compensation system, and passed on to the reactive power controller. An unused primary circuit of a summation current transformer must remain open. 8 One can normally do without the significantly more expensive high-voltage measurement. Compensation of the transformer using a fixed step or the base-load facility integrated into the compensation system, in conjunction with optimal lowvoltage compensation, is sufficient to achieve a very good result in most cases. If several busbar sections can be operated with both closed and also open bus coupler switches and with one or several transformers, a compensation system could be necessary for each busbar section. A differential measurement is sensible in such cases, e.g. with three main current transformers and two summation current transformers. Chapter 4 Capacitor technology - a comparison In the past, one could assume a service life of at least ten years for power capacitors. Today, capacitor failures are often observed after significantly shorter operation periods. According to our experience, there are three causes for this: Increased ambient temperatures due to increased packing density in switchgear and equipment rooms. l Load increases due to harmonics, higher network voltages and higher switching frequencies. l Use of low-priced capacitors, in which unacceptable compromises with respect to materials, technology and field strength are frequently accepted. l This circuit guarantees an optimal reactive power compensation for all circuit or load configurations. High voltage measurement It is sometimes requested in consumer installations with high-voltage current measurement that the measurement point for the reactive power compensation also be located on the high-voltage side. In these cases, both the voltage measurement and the current measurement must be made at the high voltage current transformers. The power ratio of the smallest capacitor step in kVAR, divided by the CT transformation ratio and the transformer transformation ratio should be >= 0.05 at a secondary voltage of 400 V. The controller manufacturer's correction factors should also in this case be observed at other voltages. One of the most important factors affecting capacitor service life is the ambient temperature. If it is increased by 7°C, for example, then the service life is shortened to approximately half. Self-healing The vast majority of capacitors employed today for reactive power compensation are self-healing, low-loss capacitors. The following comparison is therefore deliberately restricted to this technology. An evaporation layer of a special mixture of aluminum and zinc, or of pure aluminum, is applied under high vacuum to a base material (Bi-axially oriented polypropylene) for use in self-healing capacitors. Self healing Power capacitors do not require series-connected fuses to protect against short-circuits. If breakdown occurs in the capacitor following voltage surges, the metallic coating around the puncture point evaporates as a result of the temperature of the arc that forms between the electrodes. The metal vapour is pressed away from the centre of the puncture within several microseconds by the pressure formed by the breakdown. A coating free zone is formed around the puncture point, which is completely insulated. The capacitor remains fully functional during the self - healing process. The capacitance reduction is negligible. 9 Capacitor winding, enclosure, safety The metal-coated base materials are then wound, around a tubular core, with or without a further film (dielectric), depending on the technology employed, and then contacted at the butt ends by metal spray techniques (Schoop process). This is a highly complicated process done on state of the art machines in our factory. The completed windings are then wired up, dried in a complex process with vacuum and heat and inserted into an aluminum, steel or plastic enclosure under vacuum. This capacitor can is provided with a filler material in a further manufacturing process to protect the contents against environmental influences (oxygen and moisture). The enclosure is then hermetically sealed. Long-tested safety system Every capacitor eventually reaches the end of its useful life. Every capacitor can be overloaded by unforeseen events or it can have defects in exceptional cases. Only an effective pressure relief device can then help. The lid arches, interrupts the power supply to the winding at the rupture joint. Only the combined function of pressure release and disconnection from the power network guarantees the necessary safety. Safety system Rupture joint Lid arch Characteristics of a high-quality power capacitor: A design that dissipates dangerous internal pressure and reliably disconnects the capacitor winding from the power network after a fault. Rupture joint A large number of the described self-healing events can occur during long overloads or at the end of the capacitor's service life. Since self-healing actions are always accompanied by gas formation and increases in internal pressure, reliable safety precautions are necessary to avoid explosion of the enclosure. l Gaseous or fluid, ecologically compatible, filler material with long-term stability. l Three individual windings for three-phase capacitors to separate the different potentials safely and to dissipate heat in an optimal manner. MKP capacitors The winding consists of a low-loss bi-axially oriented polypropylene film, coated on one side with an aluminium and zinc, which serves simultaneously as the base material for the coating and also as dielectric. l Reliable sealing system with long-term stability to protect the wrapping against oxygen and moisture. Contacting Large number of switching cycles by means of optimal butt-end contacting and reliable internal connections. l Winding of an MKP capacitor Metallized polypropylene film Metallized polypropylene film l High capacitance constancy over the whole service life to avoid dangerous drifting of the series resonant frequency in reactor protected compensation systems. l Shock-hazard protected connection and discharge techniques with high contact stability l Design of an MKP capacitor Advantages: Small dimensions, high specific capacity l Lower price than Metallised Paper or MKV technology l High voltage load capability l High impulse capability l Low dissipation losses l MKP capacitors are divided into three groups ac¬cording to the filler material: Solid encapsulated MKP capacitors l 1. Case crimped seam l 2. Clamping l 3. Wire 4. Break-off release (Rupture joint) 5. Wrapping Liquid filled MKP capacitors Gas filled MKP capacitors Solid encapsulated MKP capacitors The wrappings are normally inserted into plastic tanks after drying and encapsulated with resin, which hardens completely. Advantages: Especially economic due to simple technology l Operation possible in any position l No escape of liquid filler after a fault l Relatively low disposal cost l 10 Disadvantages No effective pressure release possible, therefore additional burst protection is necessary, e.g. by steel sheet enclosure. l Normally no effective long term protection of the wrapping against oxygen or moisture since penetration possible through connecting wires and hairline cracks in the resin. Disadvantages Very high demands on sealing and production quality l Greater care necessary during further installation work l l The harmful influence of oxygen during the manufacturing process not totally avoidable. l Liquid filled MKP capacitors The wrappings are normally inserted in aluminium cans and vacuum dried by a special process. The cans are immediately filled with a non-hardening resin or a specially treated vegetable oil and then sealed. It is possible to fill the can with vegetable oil (flooding) directly in the vacuum system, which offers the highest degree of protection. Advantages Reliable pressure release l Additional burst protection unnecessary l Very good permanent protection against oxygen and moisture l Very good heat dissipation l Influence by oxygen or moisture not possible with optimal manufacturing process l Disadvantages Operation recommended only in vertical position l Escape of liquid filler possible after a fault l Separation of solid and liquid components necessary for disposal l Gas filled MKP capacitors The wrappings are normally inserted into aluminium cans, vacuum dried by a special process and flood¬ed with a protective gas, e.g. non-toxic and physiologically safe nitrogen, while still in the drying container and then sealed immediately. This technology places very high demands on the quality of the employed materials and the manufacturing process to achieve the necessary long term stability. Advantages Reliable pressure release l Additional burst protection unnecessary Summary Disputes over the advantages and disadvantages of the different technologies always arise in practice. We master all described technologies and can therefore make recommendations free of constraints caused by material interests. Most importantly: All of our three-phase capacitors are equipped with three separated wrappings and pressure release features. We employ MKP capacitors with gas or vegetable oil filler, preferably for unprotected and reactor protected compensation systems under standard conditions. We have come to the conclusion after careful consideration that the gas filled, reinforced MKP capacitor, without mounting restrictions, with reliable pressure release features and completely harmless filler material offers the best priceperformance ratio for applications ranging from standard to difficult conditions. We recommend high-quality 276 series or MKP UHD capacitors for reactor protected compensation systems employed under difficult to extreme operating conditions, such as high ambient temperature, very high switching frequency and large voltage spikes, since they achieve long service lives under such conditions. Both technologies have advantages and disadvantages. Design and material quality, monitoring and control of the whole manufacturing process, from coating to final test, are crucial for long and reliable operation. We adopt a conservative position on further size reduction and the associated increase of field strengths - for your safety. In spite of this, new coating techniques and structures, in association with further process improvements will make even higher field strengths possible in future. One aspect always applies: The user must pay attention to the technical parameters. Capacitors for higher voltage levels The design of capacitors for a higher voltage than the network voltage does not protect against harmonics. Only reactor protection will help. High-quality capacitors are designed generously with respect to voltage stability as a matter of course. Even the highest voltage stability cannot protect against resonance. l Good permanent protection against oxygen and moisture l Low weight l Operation possible in all mounting positions l Escape of liquid filling material impossible l Simple disposal l 11 Chapter 5 Planning of compensation equipment Important for planners and practitioners Guidance values for the reactive power demand of motors and the recommended capacitor power for individual compensation: Individual compensation of transformers Rated- Only the no-load power should be compensated for feeder transformers. The compensation power necessary for normal three-phase transformers is approx. 3 - 8% of the rated power. It should be compensated only when the power utility requires it or in the case of consumption measurement on the high voltage side. Guidance values for the reactive power demand of transformers and the recommended capacitor power : Individual compensation of welding equipment Reactor protected fixed capacitors should, if possible, always be equipped with a fuse and contactor to be able to use the reactor temperature sensors for shut-down at overload. Features of reactive power compensation for in-plant generation equipment Compensation of synchronous generators The capacitor power is dimensioned for welding transformers at approx. 40 - 50% of the apparent transformer power. Welding rectifiers require a capacitor power of approx. 10% of the apparent device power. The same conditions apply to welding converters as to motors. Individual compensation of motors The reactive power of the capacitor should not be greater than the no-load reactive power of the motor, unless the capacitor is switched by its own contactor (pay attention to discharge times). An excessive compensation power can lead to impermissibly high voltages due to self-excitation during deceleration. Fixed capacitors for motors with a star-delta switch and reverse operation, with speed switchover, in lifts, hoists and brakes should always be controlled by their own contactor to ensure clean isolation from the motor. An automatically controlled system instead of a fixed capacitor can be beneficial for large motors with considerable reactive load fluctuations. The measures are restricted to the compensation of the consumer installation. Precautions are necessary under certain circumstances to prevent voltage increases due to capacitive operation (controller with high-speed disconnection or voltage path via overvoltage relay). Compensation of asynchronous generators The capacitor power for fixed compensation should be approx. 35 - 50% of the generator rated power. Asynchronous generators may be operated in the network only in the unexcited state. The connect command for any fixed capacitors must therefore be given by an auxiliary contact on the bus coupler switch. Disconnection must be initiated simultaneously with the opening of the coupler switch. Capacitors with high voltage stability must always be used with contactor and fuse. Automatic capacitor banks should be used with fluctuating power (water or wind dependent). They should always be connected in front of the generator switch (network side) in such a manner that the system can also be used to compensate any loads during pure network operation. One can use 75 - 80% of the generator power plus consumer component as a guidance value for the capacitor power (measurement necessary). The current transformer is always to be installed in the network feeder as already described. All loads, the asynchronous generator and the compensation system must lie behind the current transformer. 12 In the case of changing energy directions - import or export - the target cos must always be set to 1, to guarantee a symmetrical control characteristic in both directions. A target cos setting of 0.9 inductive would become a target Metal-halide lamps cos of 0.9 capacitive after a reverse of the energy direction and thus cause a dangerous over-compensation. This precaution is not necessary for controllers that work on the four-quadrant principle. Compensation of power inverters, wind-power systems, photovoltaic In-plant generation systems that are connected to the power network via power inverters, e.g. photovoltaic systems and wind power systems, operate with a cos between 0.5 and 0.7 (line-commutated inverters). They are normally considerable sources of harmonics and are subject to large power fluctuations due to clouds or wind variations. These special characteristics are to be considered for the reactive power compensation; automatic control is necessary. Capacitors and reactors are to be designed so that they can cope with high voltage spikes and harmonic levels without capacitance losses over the whole service life of this generating equipment. One should not accept compromises with respect to voltage stability, especially for capacitors. Faults in compensation systems for wind power plant can be very expensive. We recommend series 275 or series 276 capacitors. Sodium vapour lamps Low-pressure sodium vapour lamps Compensation is not necessary for self-commutated inverters, since their cos is close to 1.0 . Compensation of discharge lamps Uncompensated discharge lamps with reactors operate with a cos of 0.3 - 0.6. The following table gives guidance values for the capacitor power required for discharge lamps with inductive ballast. The table restricts itself intentionally to parallel compensation, since the series compensation loses significance due to newer regulations. A cos > 0.9 is achieved after compensation. Discharge lamps Warning: Even lamp capacitors can be overloaded by harmonics, which can lead to considerable consequential damage with unprotected capacitors. Only protected capacitors should therefore be used in networks subjected to harmonics. Guidance values for average cos load-dependent High pressure mercury vapour lamps 13 Guidance values for average cos - the power utility and values of 33%, 50% or 62% (corresponding to cos installation-dependent 0.95, 0.9 or 0.85) are usual. One extracts the values for active and reactive work from the electricity bill for the calculation of the necessary compensation power. Tan is calculated from them. Example: Active work: 17,500 kWh Reactive work: 21,000 kVARh Target cos 1: 0.9 21,000 kVARh = 1.2 tanj 1 = 17,500 kWh Reduction of current and ohmic losses by installation of capacitors, offers additional savings and safety The corresponding cos = 0.64 is determined from the following table. The row with the value 0.64 is selected from the cos 1 column. The column with the target cos 2 = 0.9 is sought in this row and factor f = 0.72 is found at the intersection. The average active power at an assumed average monthly working period of 170 hours is: P= 17,500 kWh = 103 kW 170 h The necessary capacitor power results from: Q= P× f = 103 kW × 0.72 = 74 kVAR Guide values for average cos - Including reasonable reserves, a compensation power of 100 kVAR should be selected. Load-dependent Power tariff The highest active power peak determined over, for example, 15 minutes is used as the basis for the bill. An average cos is determined from the active and Estimate of the compensation power using the transformer output An approximate estimate of the necessary compensation power is possible on the basis of the transformer output power at a new installation or if a calculation basis is lacking. Target -cos reactive work measured over the month. An (assumed) apparent power peak is calculated from these values, which is then billed. We recommend therefore that a target cos = 1 is striven for. The values for the peak active power and the average cos are taken from the electricity bill. Example: Peak active power: 175 kW Average cos : 0.7 A factor of f = 1.02 for the compensation of cos 1 = 0.7 to cos 2 = 1 is found in the table Conversion factor f from cos 1 to cos 2 (Page 17). Determination of the compensation power based on the electricity bill The necessary compensation power is calculated as follows: Determination of the compensation power with the help of the electricity bill is the best solution, since the consumption situation over several months can be taken into consideration. If extensions can be foreseen, these should also be taken into account (guidance values can be found in the above tables). Q= P× f = 175 kW × 1.02 = 179 kVAR With a reasonable reserve capacity, a compensation power of 200 kVAR is recommended. Kilowatt-hour tariff The monthly active and reactive work is billed separately. For this, the calculated reactive work is reduced by a free component of, for example, 50% of the calculated active work. This free component is dependent upon Determination of the compensation power by measurement If an electricity bill is not available, a network ana¬lysis over a representative month is recommended. It can also clarify any network problems. We would gladly perform this work for you, please contact us. 14 Calculation table for the determination of the capacitor power Conversion-factor f from cos1 to cos2 15 Fuses and incoming cables Fuses and incoming cables for power capacitors at +30°C max. Fuses and incoming cables for automatic capacitor banks at +30°C max. Fuses and incoming cables for wave traps and wave trap equipment at +30°C max. ** The currents quoted are the maximum permissible harmonic currents. The rating of fuses and incoming cables will include the 50 Hz fundamental current plus the harmonic current. For intermediate sizes always use the next higher power step. Disclaimer: The values mentioned above are for guidance only and non-binding. Regional regulations must be observed. Electronicon Kondensatoren GmbH is not resposible for any error or ommission. Selectivity – fuse When the cos value is very poor, it can happen that the necessary fuse for the compensation equipment equals or exceeds the rating of the distribution or main fuse. In order to avoid the selectivity problem in such cases, the compensation equipment can be spread over multiple cabinets with separate back-up fuses and feeders. Another alternative would be to work with separate compensation units in the sub - or main distribution systems. 16