NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
MNHT COMP NIGHT&DAY (OL BACN X)-M, 240 2ND AVENUE, MANHATTAN, NY, 10010
School:
InspectionId
Inspection Type
12421 ELECTRICAL
Time In
Last Edited
2015-05-14 11:24AM
2015-06-11 09:53AM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Public Address System, Intrusion Alarm System
Years:
Systems:
1991
HID Lighting Gymnasium, Local Sound System
Gymnasium, Interior Incandescent Lighting
1995
Lighting - Security Lights
Years:
Systems:
Years:
Systems:
2001
Service Switch, Switchboards, Emergency Generator
Set, Partial Molded Case Circuit Breaker Panel Boards,
Fire Alarm System, Emergency Light/Exit Light Panel
2003
Interior Fluorescent Lighting, Interior Incandescent
Lighting Recessed Mounted
2005
Local Sound System Auditorium
Years:
Systems:
Years:
Systems:
Years:
Systems:
2008
IPDVS/CCTV System, Telephone System, LAN,
Projectors in Science Rooms
2009
Projection System Auditorium
Years:
Systems:
Years:
2013
Below Ground
Type of Service
Does Interactive Whiteboard (IWB) Exist?
Yes
DEDICATED INTERCOMS IN FIRE RESCUE AREAS
Question
Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms
in your building?
Response
No
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
No
Other
Hammer
Missing
Emergency
Generator Stop
Switch Hammer
Missing
Basement
Mechanical
Room
Rudy Moore
Person(s) Title
Handyman
PhotoImage
No Photo Tak
Inspection
Question
Response
Electrical
Does not exist
ATHLETIC FIELD
AUDITORIUM
Inspected
Instance on 1st Floor
House Lighting
Inspected
Yes
Instance on 1st Floor
Does a Chandelier Exist?
Lighting Fixture - Fluorescent
Does not exist
Instance on 1st Floor
Lighting Fixture - HID
Does not exist
Instance on 1st Floor
Lighting Fixture - Incandescent
Inspected
Instance on 1st Floor
Pendant Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Mobile Validity Version 2.0 (P)
Page 1 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
AUDITORIUM
House Lighting
Lighting Fixture - Incandescent
Pendant Mounted
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on 1st Floor
Surface Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Lighting Fixture - LED
Does not exist
Instance on 1st Floor
Local Sound System
Instance on 1st Floor
Inspected
Instance Condition
Installation Year
Source of Installation Year
2- Between Good and Fair
Deficiency
No deficiencies recorded
2008
Documented
Projection System
Instance on 1st Floor
Inspected
Instance Condition
Is the projector on a cart or installed on the ceiling?
1- Good
Deficiency
No deficiencies recorded
Ceiling
Theater Lighting System
Does not exist
Instance on 1st Floor
Inspected
AUXILIARY SIGNAL/BELL SYSTEM
5- Poor
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
BELL TRANSFORMER PANEL NOT OPERATIONAL
Basement Mechanical Room
1
EACH
REPLACE PANEL
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
CAFETERIA
Instance on 5th Floor
Inspected
Instance on 5th Floor
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on 5th Floor
Pendant Mounted
Instance on 5th Floor
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on 5th Floor
Surface Mounted
Does not exist
Instance on 5th Floor
Lighting Fixture - HID
Does not exist
Instance on 5th Floor
Lighting Fixture - Incandescent
Does not exist
Instance on 5th Floor
Lighting Fixture - LED
Mobile Validity Version 2.0 (P)
Page 2 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
CAFETERIA
Lighting
Lighting Fixture - LED
Instance on 5th Floor
Does not exist
Local Sound System
Does not exist
Instance on 5th Floor
Projection System
Does not exist
Instance on 5th Floor
Theater Lighting System
Does not exist
Instance on 5th Floor
Inspected
CITY FIRE ALARM SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE
Inspected
Lighting
Does a Chandelier Exist?
No
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Recessed Mounted
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Surface Mounted
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Lighting Fixture - Incandescent
Inspected
Inspected
Pendant Mounted
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Recessed Mounted
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Surface Mounted
3- Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Lighting Fixture - LED
COMPUTER LAB
Does not exist
EMERGENCY DC STANDBY BATTERY POWER
Does not exist
EMERGENCY GENERATOR SET
Inspected
Automatic Transfer Switch (ATS)
Inspected
Instance
Basement Mechanical Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
ASCO
ATS-1
400
Amps
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Instance
Basement Mechanical Room
Mobile Validity Version 2.0 (P)
Page 3 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
EMERGENCY GENERATOR SET
Automatic Transfer Switch (ATS)
Instance Condition
2- Between Good and Fair
Instance Quantity
1
EACH
Instance Quantity Uom
Installation Year
Source of Installation Year
ASCO
ATS-2
100
Amps
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Instance
Basement Mechanical Room
2- Between Good and Fair
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
ASCO
ATS-FA
30
Amps
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Instance
Fire Pump Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Firetrol
ATS Fire Pump
60
HP
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Inspected
Battery Charger
Instance
Emergency Generator Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
SENS
Battery Charger
10
AmpsDC
24
VDC
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Inspected
Diesel
Instance
Emergency Generator Room
2- Between Good and Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Mobile Validity Version 2.0 (P)
Page 4 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
EMERGENCY GENERATOR SET
Diesel
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Capacity/Size 3 Quantity
Capacity/Size 3 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Caterpillar
Emergency Generator
312
kVA
250
kW
866
Amps
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Does not exist
Natural Gas
Inspected
EMERGENCY LIGHT/EXIT LIGHT PANEL
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
EMERGENCY LIGHTING
Inspected
Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Non Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
EXIT LIGHT
Inspected
Battery Pack
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
FIXTURE NOT OPERATIONAL
Basement Corridor Stairway A
1
EACH
REPLACE
PRIORITY 5
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Does not exist
Non Battery Pack
EXIT/EMERGENCY LIGHT
Does not exist
FIRE ALARM SYSTEM
Inspected
Area Smoke Detector
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Bell/Horn
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Duct Smoke Detector
Does not exist
Elevator Recall
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Fan Shutdown Control
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Fire Alarm Digital Communicator
Instance
Basement Mechanical Room
2- Between Good and Fair
Instance Condition
Mobile Validity Version 2.0 (P)
Page 5 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
FIRE ALARM SYSTEM
Fire Alarm Digital Communicator
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Silent Knight
Digital Communicator
5
Zones
Inspector Estimate
2003
Documented
Deficiency
No deficiencies recorded
Inspected
Fused Cutout Panel
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Heat Detector
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Magnetic Door Holder/Contactor
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Main Panel
Inspected
Bell At Panel
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Fire Alarm Control Panel (Electronic)
Instance
Main Lobby Security Closet
2- Between Good and Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Edwards System Technology
EST 2
Fire Alarm Control Panel
18
Zones
1
Section(s)
Diagram
2003
Documented
Deficiency
No deficiencies recorded
Manufacturer
Model
Does not exist
Fire Alarm Control Panel (Standard)
Inspected
Manual Pull Station
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Remote Annunciator
Display Monitor
Does not exist
Panel
Inspected
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Printer
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
Punch Register
Inspected
Sprinkler Flow/Air Pressure Switch
2- Between Good and Fair
Condition
Mobile Validity Version 2.0 (P)
Page 6 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
FIRE ALARM SYSTEM
Sprinkler Flow/Air Pressure Switch
Deficiency
No deficiencies recorded
Inspected
Strobe
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Sub-Panel
Does not exist
Tamper Flow Switch/Chain
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
GROUNDING SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
GYMNASIUM
Instance on 4th Floor
Inspected
Instance on 4th Floor
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on 4th Floor
Pendant Mounted
Does not exist
Instance on 4th Floor
Recessed Mounted
Does not exist
Instance on 4th Floor
Surface Mounted
Instance on 4th Floor
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Inspected
Instance on 4th Floor
Pendant Mounted
Instance on 4th Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on 4th Floor
Surface Mounted
Does not exist
Instance on 4th Floor
Lighting Fixture - Incandescent
Does not exist
Instance on 4th Floor
Lighting Fixture - LED
Does not exist
Instance on 4th Floor
Local Sound System
Instance on 4th Floor
Inspected
Instance Condition
Installation Year
Source of Installation Year
3- Fair
Deficiency
No deficiencies recorded
1995
Documented
Projection System
Does not exist
Instance on 4th Floor
Scoreboard
Does not exist
Instance on 4th Floor
Theater Lighting System
Does not exist
Instance on 4th Floor
Inspected
INTERCOM SYSTEM
Mobile Validity Version 2.0 (P)
Page 7 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
INTERCOM SYSTEM
Inspected
Elevator
3- Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Holding Area
KITCHEN/WARMING PANTRY
Instance on 5th Floor
Inspected
Instance on 5th Floor
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on 5th Floor
Pendant Mounted
Instance on 5th Floor
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on 5th Floor
Surface Mounted
Does not exist
Instance on 5th Floor
Lighting Fixture - HID
Does not exist
Instance on 5th Floor
Lighting Fixture - Incandescent
Does not exist
Instance on 5th Floor
Lighting Fixture - LED
Does not exist
Instance on 5th Floor
Inspected
LAN
Inspected
Local Distribution Frame (I/LDF)
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inaccessible
Main Equipment Rack (MDF)
LIBRARY
Instance on 1st Floor
Inspected
Has LAN/Modem access
Yes
Instance on 1st Floor
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on 1st Floor
Pendant Mounted
Does not exist
Instance on 1st Floor
Recessed Mounted
Does not exist
Instance on 1st Floor
Surface Mounted
Instance on 1st Floor
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Instance on 1st Floor
Lighting Fixture - Incandescent
Inspected
Instance on 1st Floor
Pendant Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Mobile Validity Version 2.0 (P)
Page 8 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
LIBRARY
Lighting
Lighting Fixture - Incandescent
Recessed Mounted
Instance on 1st Floor
Does not exist
Surface Mounted
Does not exist
Instance on 1st Floor
Lighting Fixture - LED
Does not exist
Instance on 1st Floor
Projection System
Does not exist
Instance on 1st Floor
Raceway With Receptacles
Instance on 1st Floor
Does not exist
LIGHTNING PROTECTION
Does not exist
LOCKER ROOM
Does not exist
MOTOR CONTROL CENTER
Does not exist
MOTOR STARTER/CONTACTOR
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
MULTIPURPOSE ROOM
Does not exist
PANEL BOARD
Inspected
Inspected
Fused Disconnect Switch Type
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Basement Mechanical Room
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Fused Knife Switch Type
Does not exist
Fused Toggle Switch Type
Inspected
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Mechanical Room
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Molded Case Circuit Breaker Type
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Auditorium Backstage, Corridors, Gymnasium
7
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CIRCUIT BREAKER NOT OPERATIONAL
3rd Floor Corridor Near Room 309, 6th Floor Electrical Closet
2
EACH
Quantity Uom
Mobile Validity Version 2.0 (P)
Page 9 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
PANEL BOARD
Molded Case Circuit Breaker Type
Potential Action
Urgency of Action
Purpose of Action
Violations
REPLACE CIRCUIT BREAKER
PRIORITY 3
LEVEL 2
No violations recorded
Inspected
PUBLIC ADDRESS SYSTEM
Instance
Room 103
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Model
Installation Year
Source of Installation Year
Dukane MACS
1991
Documented
Deficiency
No deficiencies recorded
SCIENCE DEMO ROOM
Instance on Room 404
Inspected
Has LAN/Modem access
Yes
Power Panel?
No
Alternative Use
No
Emergency Gas Shut-Off Valve
Does not exist
Instance on Room 404
Emergency Shut-Off Power
Instance on Room 404
Does not exist
Instance on Room 404
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on Room 404
Pendant Mounted
Instance on Room 404
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on Room 404
Surface Mounted
Does not exist
Instance on Room 404
Lighting Fixture - HID
Does not exist
Instance on Room 404
Lighting Fixture - Incandescent
Does not exist
Instance on Room 404
Lighting Fixture - LED
Does not exist
Instance on Room 404
Power Supply
Does not exist
Instance on Room 404
Projection System
Instance on Room 404
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
SCIENCE LAB
Instance on Rooms 602, 605
Inspected
Has LAN/Modem access
Yes
Power Panel?
No
Alternative Use
No
Emergency Gas Shut-Off Valve
Mobile Validity Version 2.0 (P)
Page 10 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
SCIENCE LAB
Emergency Gas Shut-Off Valve
Instance on Rooms 602, 605
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Emergency Shut-Off Power
Instance on Rooms 602, 605
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Instance on Rooms 602, 605
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on Rooms 602, 605
Pendant Mounted
Instance on Rooms 602, 605
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on Rooms 602, 605
Surface Mounted
Does not exist
Instance on Rooms 602, 605
Lighting Fixture - HID
Does not exist
Instance on Rooms 602, 605
Lighting Fixture - Incandescent
Inspected
Instance on Rooms 602, 605
Pendant Mounted
Does not exist
Instance on Rooms 602, 605
Recessed Mounted
Does not exist
Instance on Rooms 602, 605
Surface Mounted
Instance on Rooms 602, 605
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Lighting Fixture - LED
Does not exist
Instance on Rooms 602, 605
Power Supply
Inspected
Instance on Rooms 602, 605
Instructor Unit
Instance on Rooms 602, 605
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Meter Demonstration Unit
Instance on Rooms 602, 605
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Student Unit
Instance on Rooms 602, 605
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Projection System
Instance on Rooms 602, 605
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
SCIENCE PREP ROOM
Mobile Validity Version 2.0 (P)
Page 11 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
SCIENCE PREP ROOM
Instance on Room 603
Inspected
Has LAN/Modem access
Yes
Power Panel?
No
Alternative Use
No
Emergency Gas Shut-Off Valve
Instance on Room 603
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Emergency Shut-Off Power
Instance on Room 603
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Instance on Room 603
Inspected
Lighting
Lighting Fixture - Fluorescent
Inspected
Instance on Room 603
Pendant Mounted
Instance on Room 603
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on Room 603
Surface Mounted
Instance on Room 603
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Instance on Room 603
Lighting Fixture - Incandescent
Does not exist
Instance on Room 603
Lighting Fixture - LED
Does not exist
Instance on Room 603
Power Supply
Inspected
Instance on Room 603
Instructor Unit
Instance on Room 603
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
SECURITY
Intrusion Alarm System
Inspected
Central Control Panel
Inspected
Instance
Custodian's Office
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Model
Vista - 50P
1991
Documented
Installation Year
Source of Installation Year
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL NOT CONNECTED TO DOE CENTRAL STATION
Custodian's Office
1
EACH
REWIRE
PRIORITY 4
Quantity Uom
Potential Action
Urgency of Action
Mobile Validity Version 2.0 (P)
Page 12 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
SECURITY
Intrusion Alarm System
Central Control Panel
Purpose of Action
Violations
LEVEL 3
No violations recorded
Inspected
Infrared Sensor
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Panic Switch
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Remote Annunciator
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Siren/Strobe
Condition
3- Fair
Deficiency
No deficiencies recorded
Does not exist
Ultrasonic Sensor
Inspected
IPDVS/CCTV System
2- Between Good and Fair
Condition
Installation Year
Source of Installation Year
2009
Documented
Deficiency
No deficiencies recorded
Inspected
Lighting - Security
Condition
2- Between Good and Fair
Replacement Quantity
Replacement Uom
11
EACH
Deficiency
Deficiency Location/Instance
Deficiency Quantity
LIGHTING FIXTURE BALLAST DEFECTIVE
Exterior Wall Near Fire Escape
1
EACH
REPLACE BALLAST
PRIORITY 4
LEVEL 3
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
SERVICE SWITCH
Instance
Electrical Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Siemens
Service Switch
1600
Amps
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
SWIMMING POOL
Does not exist
SWITCHBOARD
Water Penetration In Electrical Room?
Number of Spares
Inspected
Air Circuit Breaker Type
No
0
Does not exist
Fused Disconnect Switch Type
Inspected
Instance
Mobile Validity Version 2.0 (P)
Electrical Room
Page 13 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
SWITCHBOARD
Fused Disconnect Switch Type
Instance Condition
2- Between Good and Fair
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Siemens
Switchboard MS-B
1600
Amps Total
2
Section(s)
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Fused Knife Switch Type
Does not exist
Molded Case Circuit Breaker Type
Inspected
Instance
Basement Mechanical Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Cutler Hammer
DP-EM
400
Amps Total
1
Section(s)
Nameplate
2003
Documented
Deficiency
No deficiencies recorded
Inspected
TELEPHONE SYSTEM
Inspected
PBX/Intercom
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Standard
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
TOILET ROOM - STAFF
Inspected
Lighting
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Surface Mounted
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Lighting Fixture - Incandescent
Does not exist
Lighting Fixture - LED
Does not exist
Inspected
TOILET ROOM - STUDENT
Inspected
Lighting
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
2- Between Good and Fair
Condition
Mobile Validity Version 2.0 (P)
Page 14 of 15
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M661
Question
Response
TOILET ROOM - STUDENT
Lighting
Lighting Fixture - Fluorescent
Pendant Mounted
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Surface Mounted
Does not exist
Lighting Fixture - HID
Does not exist
Lighting Fixture - Incandescent
Inspected
Pendant Mounted
Does not exist
Recessed Mounted
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Surface Mounted
Does not exist
Lighting Fixture - LED
TRANSFORMER
Does not exist
TV SYSTEM
Cable System Exist?
Operational?
Inspected
Yes
Yes
Does not exist
Main Equipment Rack
Mobile Validity Version 2.0 (P)
Page 15 of 15
Print Date: 6/18/2015