NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 MNHT COMP NIGHT&DAY (OL BACN X)-M, 240 2ND AVENUE, MANHATTAN, NY, 10010 School: InspectionId Inspection Type 12421 ELECTRICAL Time In Last Edited 2015-05-14 11:24AM 2015-06-11 09:53AM Asset Data Question Answer Have any Systems/Major Building Components been upgraded? Systems: Public Address System, Intrusion Alarm System Years: Systems: 1991 HID Lighting Gymnasium, Local Sound System Gymnasium, Interior Incandescent Lighting 1995 Lighting - Security Lights Years: Systems: Years: Systems: 2001 Service Switch, Switchboards, Emergency Generator Set, Partial Molded Case Circuit Breaker Panel Boards, Fire Alarm System, Emergency Light/Exit Light Panel 2003 Interior Fluorescent Lighting, Interior Incandescent Lighting Recessed Mounted 2005 Local Sound System Auditorium Years: Systems: Years: Systems: Years: Systems: 2008 IPDVS/CCTV System, Telephone System, LAN, Projectors in Science Rooms 2009 Projection System Auditorium Years: Systems: Years: 2013 Below Ground Type of Service Does Interactive Whiteboard (IWB) Exist? Yes DEDICATED INTERCOMS IN FIRE RESCUE AREAS Question Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building? Response No Priority Condition Priority Condition Exist Last Year? Priority Category Condition Description Component Affected Location Description Person(s) Notified No Other Hammer Missing Emergency Generator Stop Switch Hammer Missing Basement Mechanical Room Rudy Moore Person(s) Title Handyman PhotoImage No Photo Tak Inspection Question Response Electrical Does not exist ATHLETIC FIELD AUDITORIUM Inspected Instance on 1st Floor House Lighting Inspected Yes Instance on 1st Floor Does a Chandelier Exist? Lighting Fixture - Fluorescent Does not exist Instance on 1st Floor Lighting Fixture - HID Does not exist Instance on 1st Floor Lighting Fixture - Incandescent Inspected Instance on 1st Floor Pendant Mounted Instance on 1st Floor Inspected Instance Condition 3- Fair Mobile Validity Version 2.0 (P) Page 1 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response AUDITORIUM House Lighting Lighting Fixture - Incandescent Pendant Mounted Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on 1st Floor Surface Mounted Instance on 1st Floor Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Lighting Fixture - LED Does not exist Instance on 1st Floor Local Sound System Instance on 1st Floor Inspected Instance Condition Installation Year Source of Installation Year 2- Between Good and Fair Deficiency No deficiencies recorded 2008 Documented Projection System Instance on 1st Floor Inspected Instance Condition Is the projector on a cart or installed on the ceiling? 1- Good Deficiency No deficiencies recorded Ceiling Theater Lighting System Does not exist Instance on 1st Floor Inspected AUXILIARY SIGNAL/BELL SYSTEM 5- Poor Condition Deficiency Deficiency Location/Instance Deficiency Quantity BELL TRANSFORMER PANEL NOT OPERATIONAL Basement Mechanical Room 1 EACH REPLACE PANEL PRIORITY 3 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations CAFETERIA Instance on 5th Floor Inspected Instance on 5th Floor Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on 5th Floor Pendant Mounted Instance on 5th Floor Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on 5th Floor Surface Mounted Does not exist Instance on 5th Floor Lighting Fixture - HID Does not exist Instance on 5th Floor Lighting Fixture - Incandescent Does not exist Instance on 5th Floor Lighting Fixture - LED Mobile Validity Version 2.0 (P) Page 2 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response CAFETERIA Lighting Lighting Fixture - LED Instance on 5th Floor Does not exist Local Sound System Does not exist Instance on 5th Floor Projection System Does not exist Instance on 5th Floor Theater Lighting System Does not exist Instance on 5th Floor Inspected CITY FIRE ALARM SYSTEM 3- Fair Condition Deficiency No deficiencies recorded Inspected CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Inspected Lighting Does a Chandelier Exist? No Inspected Lighting Fixture - Fluorescent Inspected Pendant Mounted 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Recessed Mounted 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Surface Mounted 2- Between Good and Fair Condition Deficiency No deficiencies recorded Lighting Fixture - HID Does not exist Lighting Fixture - Incandescent Inspected Inspected Pendant Mounted 3- Fair Condition Deficiency No deficiencies recorded Inspected Recessed Mounted 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Surface Mounted 3- Fair Condition Deficiency No deficiencies recorded Does not exist Lighting Fixture - LED COMPUTER LAB Does not exist EMERGENCY DC STANDBY BATTERY POWER Does not exist EMERGENCY GENERATOR SET Inspected Automatic Transfer Switch (ATS) Inspected Instance Basement Mechanical Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year ASCO ATS-1 400 Amps Nameplate 2003 Documented Deficiency No deficiencies recorded Instance Basement Mechanical Room Mobile Validity Version 2.0 (P) Page 3 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response EMERGENCY GENERATOR SET Automatic Transfer Switch (ATS) Instance Condition 2- Between Good and Fair Instance Quantity 1 EACH Instance Quantity Uom Installation Year Source of Installation Year ASCO ATS-2 100 Amps Nameplate 2003 Documented Deficiency No deficiencies recorded Instance Basement Mechanical Room 2- Between Good and Fair Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year ASCO ATS-FA 30 Amps Nameplate 2003 Documented Deficiency No deficiencies recorded Instance Fire Pump Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year Firetrol ATS Fire Pump 60 HP Nameplate 2003 Documented Deficiency No deficiencies recorded Inspected Battery Charger Instance Emergency Generator Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Capacity/Size 2 Quantity Capacity/Size 2 UOM Source of Capacity/Size Installation Year Source of Installation Year SENS Battery Charger 10 AmpsDC 24 VDC Nameplate 2003 Documented Deficiency No deficiencies recorded Inspected Diesel Instance Emergency Generator Room 2- Between Good and Fair Instance Condition Instance Quantity 1 EACH Instance Quantity Uom Mobile Validity Version 2.0 (P) Page 4 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response EMERGENCY GENERATOR SET Diesel Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Capacity/Size 2 Quantity Capacity/Size 2 UOM Capacity/Size 3 Quantity Capacity/Size 3 UOM Source of Capacity/Size Installation Year Source of Installation Year Caterpillar Emergency Generator 312 kVA 250 kW 866 Amps Nameplate 2003 Documented Deficiency No deficiencies recorded Does not exist Natural Gas Inspected EMERGENCY LIGHT/EXIT LIGHT PANEL 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected EMERGENCY LIGHTING Inspected Battery Pack 3- Fair Condition Deficiency No deficiencies recorded Inspected Non Battery Pack 3- Fair Condition Deficiency No deficiencies recorded Inspected EXIT LIGHT Inspected Battery Pack 3- Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity FIXTURE NOT OPERATIONAL Basement Corridor Stairway A 1 EACH REPLACE PRIORITY 5 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Does not exist Non Battery Pack EXIT/EMERGENCY LIGHT Does not exist FIRE ALARM SYSTEM Inspected Area Smoke Detector Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Bell/Horn 2- Between Good and Fair Condition Deficiency No deficiencies recorded Duct Smoke Detector Does not exist Elevator Recall Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Fan Shutdown Control 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Fire Alarm Digital Communicator Instance Basement Mechanical Room 2- Between Good and Fair Instance Condition Mobile Validity Version 2.0 (P) Page 5 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response FIRE ALARM SYSTEM Fire Alarm Digital Communicator Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year Silent Knight Digital Communicator 5 Zones Inspector Estimate 2003 Documented Deficiency No deficiencies recorded Inspected Fused Cutout Panel 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Heat Detector 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Magnetic Door Holder/Contactor 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Main Panel Inspected Bell At Panel Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Fire Alarm Control Panel (Electronic) Instance Main Lobby Security Closet 2- Between Good and Fair Instance Condition Instance Quantity 1 EACH Instance Quantity Uom EquipmentId Capacity/Size Quantity Capacity/Size UOM Capacity/Size 2 Quantity Capacity/Size 2 UOM Source of Capacity/Size Installation Year Source of Installation Year Edwards System Technology EST 2 Fire Alarm Control Panel 18 Zones 1 Section(s) Diagram 2003 Documented Deficiency No deficiencies recorded Manufacturer Model Does not exist Fire Alarm Control Panel (Standard) Inspected Manual Pull Station 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Remote Annunciator Display Monitor Does not exist Panel Inspected Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Printer Condition 2- Between Good and Fair Deficiency No deficiencies recorded Does not exist Punch Register Inspected Sprinkler Flow/Air Pressure Switch 2- Between Good and Fair Condition Mobile Validity Version 2.0 (P) Page 6 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response FIRE ALARM SYSTEM Sprinkler Flow/Air Pressure Switch Deficiency No deficiencies recorded Inspected Strobe 2- Between Good and Fair Condition Deficiency No deficiencies recorded Sub-Panel Does not exist Tamper Flow Switch/Chain Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected GROUNDING SYSTEM 3- Fair Condition Deficiency No deficiencies recorded GYMNASIUM Instance on 4th Floor Inspected Instance on 4th Floor Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on 4th Floor Pendant Mounted Does not exist Instance on 4th Floor Recessed Mounted Does not exist Instance on 4th Floor Surface Mounted Instance on 4th Floor Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Lighting Fixture - HID Inspected Instance on 4th Floor Pendant Mounted Instance on 4th Floor Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on 4th Floor Surface Mounted Does not exist Instance on 4th Floor Lighting Fixture - Incandescent Does not exist Instance on 4th Floor Lighting Fixture - LED Does not exist Instance on 4th Floor Local Sound System Instance on 4th Floor Inspected Instance Condition Installation Year Source of Installation Year 3- Fair Deficiency No deficiencies recorded 1995 Documented Projection System Does not exist Instance on 4th Floor Scoreboard Does not exist Instance on 4th Floor Theater Lighting System Does not exist Instance on 4th Floor Inspected INTERCOM SYSTEM Mobile Validity Version 2.0 (P) Page 7 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response INTERCOM SYSTEM Inspected Elevator 3- Fair Condition Deficiency No deficiencies recorded Does not exist Holding Area KITCHEN/WARMING PANTRY Instance on 5th Floor Inspected Instance on 5th Floor Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on 5th Floor Pendant Mounted Instance on 5th Floor Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on 5th Floor Surface Mounted Does not exist Instance on 5th Floor Lighting Fixture - HID Does not exist Instance on 5th Floor Lighting Fixture - Incandescent Does not exist Instance on 5th Floor Lighting Fixture - LED Does not exist Instance on 5th Floor Inspected LAN Inspected Local Distribution Frame (I/LDF) 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inaccessible Main Equipment Rack (MDF) LIBRARY Instance on 1st Floor Inspected Has LAN/Modem access Yes Instance on 1st Floor Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on 1st Floor Pendant Mounted Does not exist Instance on 1st Floor Recessed Mounted Does not exist Instance on 1st Floor Surface Mounted Instance on 1st Floor Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Lighting Fixture - HID Does not exist Instance on 1st Floor Lighting Fixture - Incandescent Inspected Instance on 1st Floor Pendant Mounted Instance on 1st Floor Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Recessed Mounted Mobile Validity Version 2.0 (P) Page 8 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response LIBRARY Lighting Lighting Fixture - Incandescent Recessed Mounted Instance on 1st Floor Does not exist Surface Mounted Does not exist Instance on 1st Floor Lighting Fixture - LED Does not exist Instance on 1st Floor Projection System Does not exist Instance on 1st Floor Raceway With Receptacles Instance on 1st Floor Does not exist LIGHTNING PROTECTION Does not exist LOCKER ROOM Does not exist MOTOR CONTROL CENTER Does not exist MOTOR STARTER/CONTACTOR Inspected 3- Fair Condition Deficiency No deficiencies recorded MULTIPURPOSE ROOM Does not exist PANEL BOARD Inspected Inspected Fused Disconnect Switch Type 3- Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity PANEL BOARD BEYOND USEFUL LIFE Basement Mechanical Room 1 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Fused Knife Switch Type Does not exist Fused Toggle Switch Type Inspected 3- Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity PANEL BOARD BEYOND USEFUL LIFE Mechanical Room 1 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Inspected Molded Case Circuit Breaker Type 3- Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity PANEL BOARD BEYOND USEFUL LIFE Auditorium Backstage, Corridors, Gymnasium 7 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Deficiency Deficiency Location/Instance Deficiency Quantity CIRCUIT BREAKER NOT OPERATIONAL 3rd Floor Corridor Near Room 309, 6th Floor Electrical Closet 2 EACH Quantity Uom Mobile Validity Version 2.0 (P) Page 9 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response PANEL BOARD Molded Case Circuit Breaker Type Potential Action Urgency of Action Purpose of Action Violations REPLACE CIRCUIT BREAKER PRIORITY 3 LEVEL 2 No violations recorded Inspected PUBLIC ADDRESS SYSTEM Instance Room 103 3- Fair Instance Condition Instance Quantity 1 EACH Instance Quantity Uom Model Installation Year Source of Installation Year Dukane MACS 1991 Documented Deficiency No deficiencies recorded SCIENCE DEMO ROOM Instance on Room 404 Inspected Has LAN/Modem access Yes Power Panel? No Alternative Use No Emergency Gas Shut-Off Valve Does not exist Instance on Room 404 Emergency Shut-Off Power Instance on Room 404 Does not exist Instance on Room 404 Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on Room 404 Pendant Mounted Instance on Room 404 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on Room 404 Surface Mounted Does not exist Instance on Room 404 Lighting Fixture - HID Does not exist Instance on Room 404 Lighting Fixture - Incandescent Does not exist Instance on Room 404 Lighting Fixture - LED Does not exist Instance on Room 404 Power Supply Does not exist Instance on Room 404 Projection System Instance on Room 404 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded SCIENCE LAB Instance on Rooms 602, 605 Inspected Has LAN/Modem access Yes Power Panel? No Alternative Use No Emergency Gas Shut-Off Valve Mobile Validity Version 2.0 (P) Page 10 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response SCIENCE LAB Emergency Gas Shut-Off Valve Instance on Rooms 602, 605 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Emergency Shut-Off Power Instance on Rooms 602, 605 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Instance on Rooms 602, 605 Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on Rooms 602, 605 Pendant Mounted Instance on Rooms 602, 605 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on Rooms 602, 605 Surface Mounted Does not exist Instance on Rooms 602, 605 Lighting Fixture - HID Does not exist Instance on Rooms 602, 605 Lighting Fixture - Incandescent Inspected Instance on Rooms 602, 605 Pendant Mounted Does not exist Instance on Rooms 602, 605 Recessed Mounted Does not exist Instance on Rooms 602, 605 Surface Mounted Instance on Rooms 602, 605 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Lighting Fixture - LED Does not exist Instance on Rooms 602, 605 Power Supply Inspected Instance on Rooms 602, 605 Instructor Unit Instance on Rooms 602, 605 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Meter Demonstration Unit Instance on Rooms 602, 605 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Student Unit Instance on Rooms 602, 605 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Projection System Instance on Rooms 602, 605 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded SCIENCE PREP ROOM Mobile Validity Version 2.0 (P) Page 11 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response SCIENCE PREP ROOM Instance on Room 603 Inspected Has LAN/Modem access Yes Power Panel? No Alternative Use No Emergency Gas Shut-Off Valve Instance on Room 603 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Emergency Shut-Off Power Instance on Room 603 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Instance on Room 603 Inspected Lighting Lighting Fixture - Fluorescent Inspected Instance on Room 603 Pendant Mounted Instance on Room 603 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Recessed Mounted Does not exist Instance on Room 603 Surface Mounted Instance on Room 603 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Lighting Fixture - HID Does not exist Instance on Room 603 Lighting Fixture - Incandescent Does not exist Instance on Room 603 Lighting Fixture - LED Does not exist Instance on Room 603 Power Supply Inspected Instance on Room 603 Instructor Unit Instance on Room 603 Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Inspected SECURITY Intrusion Alarm System Inspected Central Control Panel Inspected Instance Custodian's Office 3- Fair Instance Condition Instance Quantity 1 EACH Instance Quantity Uom Model Vista - 50P 1991 Documented Installation Year Source of Installation Year Deficiency Deficiency Location/Instance Deficiency Quantity PANEL NOT CONNECTED TO DOE CENTRAL STATION Custodian's Office 1 EACH REWIRE PRIORITY 4 Quantity Uom Potential Action Urgency of Action Mobile Validity Version 2.0 (P) Page 12 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response SECURITY Intrusion Alarm System Central Control Panel Purpose of Action Violations LEVEL 3 No violations recorded Inspected Infrared Sensor Condition 3- Fair Deficiency No deficiencies recorded Inspected Panic Switch Condition 3- Fair Deficiency No deficiencies recorded Inspected Remote Annunciator Condition 3- Fair Deficiency No deficiencies recorded Inspected Siren/Strobe Condition 3- Fair Deficiency No deficiencies recorded Does not exist Ultrasonic Sensor Inspected IPDVS/CCTV System 2- Between Good and Fair Condition Installation Year Source of Installation Year 2009 Documented Deficiency No deficiencies recorded Inspected Lighting - Security Condition 2- Between Good and Fair Replacement Quantity Replacement Uom 11 EACH Deficiency Deficiency Location/Instance Deficiency Quantity LIGHTING FIXTURE BALLAST DEFECTIVE Exterior Wall Near Fire Escape 1 EACH REPLACE BALLAST PRIORITY 4 LEVEL 3 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Inspected SERVICE SWITCH Instance Electrical Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year Siemens Service Switch 1600 Amps Nameplate 2003 Documented Deficiency No deficiencies recorded SWIMMING POOL Does not exist SWITCHBOARD Water Penetration In Electrical Room? Number of Spares Inspected Air Circuit Breaker Type No 0 Does not exist Fused Disconnect Switch Type Inspected Instance Mobile Validity Version 2.0 (P) Electrical Room Page 13 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response SWITCHBOARD Fused Disconnect Switch Type Instance Condition 2- Between Good and Fair Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Capacity/Size 2 Quantity Capacity/Size 2 UOM Source of Capacity/Size Installation Year Source of Installation Year Siemens Switchboard MS-B 1600 Amps Total 2 Section(s) Nameplate 2003 Documented Deficiency No deficiencies recorded Fused Knife Switch Type Does not exist Molded Case Circuit Breaker Type Inspected Instance Basement Mechanical Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Capacity/Size 2 Quantity Capacity/Size 2 UOM Source of Capacity/Size Installation Year Source of Installation Year Cutler Hammer DP-EM 400 Amps Total 1 Section(s) Nameplate 2003 Documented Deficiency No deficiencies recorded Inspected TELEPHONE SYSTEM Inspected PBX/Intercom 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Standard 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected TOILET ROOM - STAFF Inspected Lighting Inspected Lighting Fixture - Fluorescent Inspected Pendant Mounted 2- Between Good and Fair Condition Deficiency No deficiencies recorded Recessed Mounted Does not exist Surface Mounted Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Lighting Fixture - HID Does not exist Lighting Fixture - Incandescent Does not exist Lighting Fixture - LED Does not exist Inspected TOILET ROOM - STUDENT Inspected Lighting Inspected Lighting Fixture - Fluorescent Inspected Pendant Mounted 2- Between Good and Fair Condition Mobile Validity Version 2.0 (P) Page 14 of 15 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Electrical Inspection M661 Question Response TOILET ROOM - STUDENT Lighting Lighting Fixture - Fluorescent Pendant Mounted Deficiency No deficiencies recorded Recessed Mounted Does not exist Surface Mounted Does not exist Lighting Fixture - HID Does not exist Lighting Fixture - Incandescent Inspected Pendant Mounted Does not exist Recessed Mounted Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Does not exist Surface Mounted Does not exist Lighting Fixture - LED TRANSFORMER Does not exist TV SYSTEM Cable System Exist? Operational? Inspected Yes Yes Does not exist Main Equipment Rack Mobile Validity Version 2.0 (P) Page 15 of 15 Print Date: 6/18/2015