Supersafe TM Range

advertisement
PRODUCT
INFORMATION
SUPERSAFE
TM
•
•
•
•
•
•
•
•
Fully insulated connectors – increased
personnel safety.
Modular steel structure – providing compact,
simple flexible assembly, minimising on site
installation time.
Excellent vibration resistance – to Seismic
Zone 4.
Low self discharge rate – 0.5~1.0% per week
@ 25º C.
Design life – up to 20 years in floating service
@ 25º C.
Capacity range – single cells from 100Ah to
1500Ah C10 to 1.80vpc @ 25º C.
Testing - 100% of cells proven to 100% rated
C10 capacity prior to despatch.
Manufactured by Hawker - in one of our many
ISO9001 accredited facilities.
CONSTRUCTION
•
•
STANDBY POWER APPLICATIONS
•
•
•
•
•
•
•
Telecommunications
Power generation plants
Electrical switchgear
Uninterruptible power supplies
Emergency lighting
FEATURES
•
•
Valve regulated sealed lead-acid – proven
in service V.R.L.A.(AGM type) technology
providing a gas recombination efficiency of
99%, ensuring minimal gassing in normal
operation and requiring NO addition of
water throughout operating life.
AGM separators – completely absorb the
electrolyte into their structure.
•
•
•
•
•
•
•
Positive plate – extra thick lead-calcium-tin
grids to resist corrosion and prolong life.
Negative plate – balanced lead-calcium grids
to optimize recombination efficiency.
AGM separator – mechanically strong, low
resistance microporous glass fibre.
Casing material – polypropylene container and
heat sealed lid housed in steel modules.
Connectors – bolted flexible copper connectors
fully insulated with flame retardant PVC
materials.
Main battery terminal plates – pre-drilled solid
copper.
Front panel – and main battery terminal plate
isolating shields made from V0 rated ABS.
Electrolyte – dilute sulphuric acid.
Cell terminal – lead casting with threaded
copper insert to provide maximum conductivity.
Terminal seal – ring burn with secondary
epoxy resin seal, 100% water bath tested in
factory and proven in service.
Regulating valve - operates @ 15-20 Kpa and
is complete with integral flame arrestor.
RANGE SUMMARY
Model
12TM-100
12TM-200
12TM-300
6TM-400
12TM-500
12TM-580
6TM-830
6TM-1000
6TM-1080
6TM-12004
4TM-1500
6TM-1500
Voltage
(V)
12
12
12
6
12
12
6
6
6
6
4
6
Nominal Capacity@25ºC (Ah)
1 hr rate to
1.75vpc
60
120
180
240
300
350
485
585
635
720
900
900
10hr rate to
1.80vpc
100
200
300
400
500
580
830
1000
1080
1200
1500
1500
Dimensions (mm)
Weight (kg)
Height
Length
Depth
218
218
218
218
218
218
218
218
218
277
277
277
437
665
893
623
957
1071
801
915
972
1027
793
1147
330
330
330
330
516
516
516
516
516
465
465
465
65
107
155
105
236
276
201
232
252
246
216
322
Note: 1. The depth excludes 86mm to the front panel.
2. Weight of the module excludes the front panel, connector, terminal plate/connector and base.
3. Supersafe TM are designed for horizontal installation.
4. Availability – end 2000.
H
D
L
Hawker Worldwide Marketing
Rake Lane, Clifton Junction
Swinton, Manchester M27 8LR
United Kingdom
Tel: +44 (0)161 794 4611
Fax:+44 (0)161 727 3809
www.hawker.invensys.com
An Invensys company
For further information, please contact your local Hawker company:
Download