SECTION 16460 DRY TYPE DISTRIBUTION TRANSFORMERS PART 1 - GENERAL 1.01 DESCRIPTION A. B. 1.02 General: Provide dry type transformers, complete, as shown and specified per Contract Documents. Principal items include: 1. Power transformers. 2. Control transformers. Other Applicable Sections: Requirements of Division 1 and Section 16050 apply to work of this Section. SUBMITTALS A. Procedures: Refer to Division 1. B. Requirements: In addition to the requirements of Section 16050 submittal material shall include copies of descriptive data for all products and materials. C. Shop Drawings: Submit for all work of this Section. PART 2 - PRODUCTS 2.01 POWER TRANSFORMERS A. Dry Type: Integral, self-cooled, enclosed distribution transformers of the two-winding type. B. Capacity and voltage ratings as indicated. C. NEMA Standard Taps: If taps are not standard, equip transformer with two 2-1/2% FCAN and four 2-1/2% FCBN taps. Tap leads shall be terminated on internal block with lugs for connection of incoming conductors. 2.02 D. Where neutral connection is indicated, attach to bolt and lug inside enclosure and extend bolt through enclosure to permit external ground connection. E. Vibration dampers (Korfund Company or equivalent) separating core and coil assembly from the structural members of the enclosures. Sound levels shall be 3 dB lower than NEMA Standard for each particular size. F. Class H insulation, having a 150oC temperature rise above a 40oC ambient, when operating continuously at full load without loss of normal life. Construct enclosures of heavy gauge steel, coated inside and out with zinc chromate or iron oxide rust inhibiting primer. Finish with gray enamel. Use manufacturer's standard gray color unless a particular ASA color is indicated or specified. G. Ventilation openings shall be located to permit placing transformer with two adjacent sides against walls. H. Terminal compartment, shall be located below the level of the transformer winding. Provide access to terminals from front for wall- and floormounted transformers, and from front and bottom for suspended transformers. Support all terminals. I. Manufacturers: General Electric, Westinghouse, or Siemens. CONTROL TRANSFORMERS A. Dry type, integral, self-cooled, two-winding type. Capacity and voltage ratings as indicated, Class H insulation; NEMA I enclosure except where installed in control centers or switchboards. Provide secondary fusing. PART 3 - EXECUTION 3.01 INSTALLATION A. Do not install transformers with ventilation openings closer than 12" from any wall surface. Use flexible conduit for primary and secondary connections, or other approved mechanical isolation method. Provide a separate equipment ground conductor in such flexible connections. Do not attach transformer mounting brackets to walls or structure of other than poured concrete construction unless approved. Provide Korfund or equivalent vibration isolators separating the transformer support points and the supporting structure. **END OF SECTION**