OPSS 2323
MARCH 1998
MATERIAL SPECIFICATION FOR
CATHODIC PROTECTION AC POWER DISTRIBUTION ASSEMBLY
TABLE OF CONTENTS
2323.01
SCOPE
2323.02
REFERENCES
2323.03
DEFINITIONS
2323.04
SUBMISSION AND DESIGN REQUIREMENTS
2323.04.01
Submissions
2323.04.01.01
.02
Submission of Shop Drawings
Notification of Production
2323.04.02
Design Requirements
2323.05
MATERIALS
2323.05.01
Cathodic Protection AC Power Distribution Assembly
2323.05.01.01
Enclosure
2323.05.02
.03
.04
.05
.06
.07
Circuit Breakers
Lightning and Surge Protection
Wire Connectors
Grounding and Bonding Equipment
Thermoset Wires and Cables
Marking
2323.06
Not Used
2323.07
PRODUCTION
2323.07.01
.02
.03
General
Marking
Packaging and Shipping
2323.08
QUALITY ASSURANCE
2323.09
OWNER PURCHASE OF MATERIAL
2323.10
Not Used
Page 1
Rev. Date: 03/1998 OPSS 2323
2323.01
SCOPE
This specification covers the requirements for the Cathodic Protection AC Power Distribution Assembly.
2323.02
REFERENCES
This specification refers to the following standards, specifications or publications.
Canadian Standards Association Standards:
CSA C22.2 No. 0.4-M1982 (R1993) - Bonding and Grounding of Electrical Equipment, Protective
Grounding
C22.2 No. 0.12-M1985 (R1992) - Wiring Space and Wire Bending Space in Enclosures for Equipment
Rated 750 V or Less
C22.2 No. 5.1-M91 - Moulded Case Circuit Breakers
C22.2 No. 29-M1989 (R1995) - Panelboards and Enclosed Panelboards
C22.2 No. 38-95 - Thermoset Insulated Wires and Cables
C22.2 No. 41-M1987 (R1993) - Grounding and Bonding Equipment
C22.2 No. 65-93 Wire Connectors
CAN/CSA - C22.2 No. 94-M91 Special Purpose Enclosures
CAN/CSA - C233.1-87 (R1995) - Gapless Metal Oxide Surge Arresters for Alternating Current Systems
2323.03
DEFINITIONS
Stamped: means "Reviewed, Permission to Construct Granted" has been stamped on the drawings by
the Owner.
2323.04
SUBMISSION AND DESIGN REQUIREMENTS
2323.04.01
Submissions
2323.04.01.01
Submission of Shop Drawings
Four copies of the shop drawings containing at least the following information shall be submitted to the
purchaser on request.
a. dimensioned layout drawings including sections and details for enclosure, equipment layout and
mounting arrangement;
b. detailed bill of materials, including their source;
c. wiring diagrams;
d. equipment nameplates, and manufacturers label when available;
e. weight.
Page 2
Rev. Date: 03/1998 OPSS 2323
Shop drawings submitted for review will be "stamped" if acceptable or marked with required changes.
One copy of drawings will be returned to the supplier when changes are required and also when
"stamped".
The above submission procedure shall be repeated if changes are required.
Materials and dimensions shown on the "stamped" shop drawings shall not be changed.
2323.04.01.02
Notification of Production
The purchaser shall be given at least one week prior notice of the date of commencement of fabrication of
the assembly and the date of completion.
2323.04.02
Design Requirements
The assembly shall be designed as specified.
The enclosure for the assembly shall be so constructed that exposure to the weather, to the effects of
condensation, or to external splashing will not impair the effectiveness of the enclosed electrical
equipment.
The enclosure shall have:
a. A rack mounting bracket according to the details specified;
b. A removable internal equipment panelboard consisting of a combination backboard and drip shield.
The drip shield shall be formed such that the electrical components mounted on the backboard shall
not be affected by moisture condensing on the interior of the enclosure.
The panelboard shall be according to the combination service, entrance panel requirements of CSA
C22.2 No. 29 and shall accept bus bar bolt-on breakers.
c.
Internal Dead-Front Panels, Front and Back
i
The dead-front panel for the main breaker section shall be formed so as to prevent contact, by
service personnel, with live circuits from all sides in the main breaker section;
ii
The branch breaker section shall protect all secondary circuits from contact, by service personnel,
with live circuits.
The dead-front panels shall be formed so that the branch breaker panel has to be removed before the
main breaker panel can be removed. Both panels shall be supplied with quarter-turn screw latches
welded to the dead-front panels.
2323.05
MATERIALS
2323.05.01
Cathodic Protection AC Power Distribution Assembly
2323.05.01.01
Enclosure
The enclosure and the internal equipment panel shall be manufactured from 14 gauge galvanized steel.
All bus work shall be copper. All interconnecting wire and cables shall be at least 19 strand copper
according to CSA C22.2 No. 0.12 for bending radii.
Page 3
Rev. Date: 03/1998 OPSS 2323
The panelboard shall meet service entrance requirements of the subsection "Combination
Service/Entrance Panelboard" CSA C22.2 No. 29.
Cable shields shall be fabricated from 14 gauge galvanized steel.
The dead-front panels shall be manufactured of 14 gauge galvanized steel.
The assembly shall be inspected and approved by an organization accredited by the Standard Council of
Canada or an organization otherwise approved to Canadian Standards by Ontario Hydro. Their label of
approval shall be issued prior to the unit being shipped.
2323.05.02
Circuit Breakers
Circuit breakers shall be according to CAN/CSA C22.2 No. 5.1.
2323.05.03
Lightning and Surge Protection
Lightning arresters shall be according to CAN/CSA-C233.1. The protection device shall be rated at a
minimum of 650 V.
2323.05.04
Wire Connectors
Wire connectors shall be according to CSA C22.2 No. 65.
2323.05.05
Grounding and Bonding Equipment
Equipment used for grounding and bonding shall be according to CAN/CSA C22.2 No. 0.4, and C22.2
No. 41.
2323.05.06
Thermoset Wires and Cables
Interconnecting cables shall be according to CSA C22.2 No. 38 and shall be at least 19 strand copper,
Type RWU 90 cross link -40°C.
2323.05.07
Marking
The marking shall be weather resistant on a corrosion resistant metal plate.
2323.07
PRODUCTION
2323.07.01
General
The assembly shall be manufactured and wired as specified.
The enclosure shall be manufactured according to CSA C22.2 No. 94 Type 3 and as specified. All
welding shall be according to Type 4.
The panelboard layout and manufacture shall be according to CSA C22.2 No. 29.
The shields shall be formed according to CSA C22.2 No. 29.
Page 4
Rev. Date: 03/1998 OPSS 2323
2323.07.02
Marking
Each completed assembly shall have identification marking showing the manufacturer's name or
trademark, the OPSS specification number OPSS 2323 and the date of manufacture permanently
attached with adhesive to the inside of the door, in a highly visible location.
2323.07.03
Packaging and Shipping
The equipment completely factory assembled, wired and tested for continuity, shall have suitable
protection provided for shipping and handling.
The purchaser, shall be provided with notice of intent to deliver three days prior to the shipping date.
2323.08
QUALITY ASSURANCE
All work is subject to an inspection by the purchaser's representative prior to shipment.
The purchaser's representative shall have free access to the place of manufacture of the assembly while
work on the unit is being performed, for the purpose of inspecting the work and examining plant records
and certificates, materials being used, process of fabrication and to make any test as may be considered
necessary.
2323.09
OWNER PURCHASE OF MATERIAL
2323.09.01
Basis of Payment
Payment at the price specified in the purchasing order for each of the Cathodic Protection AC Power
Distribution Assembly shall be full compensation for the supply and delivery of each of the assemblies to
the destinations and at the times specified.
The cost of testing, except that performed in the Owner's laboratory shall be included in the price.