Sounders

advertisement
Yodalarm
12
Sounders
• Y03
• Y04/YL4
• Y05/YL5
• Y08/YL8/Y08 SUPER/
YL8 SUPER
• V4
• V6/Y06/YL6
• Carillon
Pg
185
186
187
188
189
190
191
Sounders
Yodalarm
S2YA/
Y03
Code
Approval Specification
1YA030207
1YA030203
1YA030205
UL464
C22.2 No. M1983
BS EN54-3:2001
incorporates amendment
A1:2002
YL03012/24
YL030110/230
Two fixing holes FØ
DIMENSIONS:
Dim A
Dim B
Dim C
Dim D
Dim E
(mm):
118(4.7")
102(4.0")
89(3.5")
85(3.4")
18(0.7")
12
Mounting:
The Y03 series alarm should be mounted to a reasonably flat wall or bulkhead of suitable material using the
lugs projecting from the side of the case. The lugs are bored 6mm clearance on 102mm centres. The minimum
recommended length of fixing screws is 25mm. To maintain the integrity of the weather seal, the cable must be
fitted using a suitable sealed gland.
Line monitoring (DC only) excludes additional voltage options
- 3-wire 2-stage or 2-wire single-stage, monitor via reverse polarity
- 2-wire 2-stage i.e. bi-polar inputs, monitor via threshold (applied voltage<1V)
End of line resistor
Minimum 3K3 ohm 0.5 watts, wire-wound or metal film type.
Technical Specification
Main Features
- Operating temperature: -25 to + 55° C
- Operating voltage: 24Vdc, 48Vdc, 115Vac, 230Vac
- Relative humidity: 90% @ 40° C
- Sound output: 100dB(A) @ 1 meter
- IP54 rated standard
- Volume control allowing 18dB(A) adjustment
- Minimum current consumption 20mA
- Optional independent 2nd stage via second DIL switch
- IP65 available on request
- 2-stage alarm
- 3-wire polarised DC (Not additional voltage option)
& AC, or 2-wire bi-polar for DC only
- 3-wire AC second stage control
- Complies with BS 5839
- Flame retardant ABS plastic enclosure
- Stainless steel fixings
- Continuously rated
- 32 selectable tones meeting international regulations
- Sound selection via 5 way DIL switch
Industrial Electrical Distributor
185
POWER PRODUCTS
Sounders
Yodalarm
S2YA/
Y04/YL4
Code
Approval Specification
1YA040217
YL04012/24
UL1638, UL464
C22.2 NO. 205-M1983
CAN/ULC-5526-M87 BS EN54-3:2001
incorporates amendment A1:2002
Mounting:
The Y04/YL4 series alarm should be mounted to a reasonably flat wall or bulkhead of suitable material
using the internal fixing holes. The recommended fixing screws are 4.5mm (dia) max x 20mm long.
To maintain the integrity of the weather seal, the cable must be fitted using a suitable sealed gland.
Line monitoring (DC only) excludes additional voltage options
- 3-wire 2-stage or 2-wire single-stage, monitor via reverse polarity
- 2-wire 2-stage i.e. bi-polar inputs, monitor via threshold (applied voltage<1V)
End of line resistor
Minimum 3K3 ohm 0.5 watts, wire-wound or metal film type
Technical Specification
- Operating temperature: -25 to + 55° C
- Operating voltage: 24Vdc, 48Vdc,115Vac, 230Vac
- Additional voltage options (Sounders only): 24Vdc
& 48Vdc (BT), 110Vdc (12Vdc versions will produce
approx. 6dB less output)
- Relative humidity: 90% @ 40° C
- Sound output: 106dB(A) @ 1 meter
- IP54 rated standard
- Volume control allowing 18dB(A) adjustment
- Minimum current consumption 20mA.
- Optional independent 2nd stage via second DIL
switch (DC only)
- IP65 available on request
Industrial Electrical Distributor
Main Features
- 2-stage alarm
- High sound output
- 3-wire polarised DC (Not additional voltage option) &
AC, or 2-wire bi-polar for DC only
- 3-wire AC second stage control
- Complies with BS 5839
- Strobe 2.5 and 5 joule
- Choice of 6 lens colours: Amber (A), Red ( R),Green (G),
Opal (O), Blue (B) and Clear (C) made from flame
retardant polycarbonate plastic
- Red/white flame retardant ABS plastic enclosure
- Continuously rated
- Flush mounting base available
- 32 selectable tones meeting international regulations
- Sound selection via 5 way DIL switch
186
POWER PRODUCTS
12
Sounders
Yodalarm
S2YA/
Y05/YL5
Code
Approval Specification
1YA050207
1YA050203
1YA050205
YL05012/24
YL050110/230
UL1638, UL484
C22.2 No. 205-M1983 CAN/ULC-5526-M87
BS EN54-3:2001 incorporate amendment
A1:2002
Two fixing holes FØ
DIMENSIONS:
Dim A
Dim B
Dim C
Dim D
Dim E
Dim F
(mm):
169(6.7")
153(6.0")
134(5.3")
128(5.0")
23(0.9")
8(0.3")
12
Mounting:
The Y05/YL5 series alarm units should be mounted to a reasonably flat wall or bulkhead of suitable material using the
lugs projecting from the side of the case. The lugs are bored 8mm on 153mm centers. The minimum recommended
length of fixing screws is 25mm. To maintain the integrity of the weather seal, the cable entry must be fitted using a
suitable sealed gland.
Line monitoring (DC only) excludes additional voltage options
- 3-wire 2-stage or 2-wire single-stage, monitor via reverse polarity
- 2-wire 2-stage i.e. bi-polar inputs, monitor via threshold (applied voltage<1V)
End of line resistor. Minimum 3K3 ohm 0.5 watts, wire-wound or metal film type
Technical Specification
Main Features
- Operating temperature: -25 to + 55° C
- Operating voltage: 24Vdc, 48Vdc, 115Vac,
(12Vdc versions will produce approx. 6dB less
output)
- Relative humidity: 90% @ 40° C
- Sound output: 110dB(A) @ 1 meter
- IP54 rated standard
- Volume control allowing 18dB(A) adjustment
- Minimum current consumption 20mA
- Optional independent 2nd stage via second DIL
switch (DC only)
- IP65 available on request
- 2-stage alarm
- 3-wire polarised DC (Not additional voltage option) & AC, or
2-wire bi-polar for DC only
- Choice of 6 lens colours: Amber (A), Red ( R),Green (G), Opal (O),
Blue (B) and Clear (C) made from flame retardant polycarbonate
plastic
- High sound output
- Complies with BS 5839
- Low current consumption
- Continuously rated
- Robust, reliable and simple to install
- Flame retardant ABS plastic enclosure
- Strobe 2.5 and 5.0 joule
- 32 selectable tones meeting international regulations
- Sound selection via 5 way DIL switch
- Stainless steel fixings
Industrial Electrical Distributor
187
POWER PRODUCTS
Sounders
Yodalarm
S2YA/
Y08/YL8 & Y08 SUPER/YL8 SUPER
Code
Approval Specification
1YA080207
1YA080203
1YA080205
1YA080217
1YA080213
YL0801224
YL080110/230
YL08S012/024
YL08S110/230
UL1638, UL484
C22.2 No. 205-M1983 CAN/ULC-5526-M87
BS EN54-3:2001 incorporate amendment
A1:2002
Two fixing holes FØ
DIMENSIONS:
Dim A
269(10.6")
Dim B
250(9.8")
Dim C
216(8.5")
Dim D
153(6.0")
Dim E
24(0.9")
12
Mounting:
The YL8/YL8 SUPER series alarm units should be mounted to a reasonably flat wall or bulkhead of suitable material
using the lugs projecting from the side of the case. The lugs are bored 10mm on 250mm centres. The minimum
recommended length of fixing screws is 30mm. To maintain the integrity of the weather seal, the cable entry must be
fitted using a suitable sealed gland.
Line monitoring (DC only)
- 3-wire 2-stage or 2-wire single stage, monitor via reverse polarity
- 2-wire 2-stage i.e. bi-polar inputs, monitor via threshold (applied voltage<1V)
End of line resistor. Minimum 3K3 ohm 0.5 watts, wire-wound or metal film type.
Main Features
Technical Specification
- Operating temperature: -25 to + 55° C
- Operating voltage: 24Vdc, 48Vdc, 115Vac,230Vac +- 10%
- DC second stage alarm signal is via polarised or 2-wire
bi-polar connection
- IP54 rated as standard
- Seperate input and output terminals on Y08, optional on YL8
- Relative humidity: 90% @ 40° C
- Sound output: 116dB(A) @ 1 meter
- Sound output: 120dB(A) @ 1 meter (SUPER units)
- Minimum current consumption 300mA
- IP65 available on request
Industrial Electrical Distributor
188
- 2-stage alarm
- 3-wire polarised DC and AC, or 2-wire bi-polar for
DC only
- Independently selectable second stage
- Complies with BS 5839
- Choice of 6 lens colours: Amber (A), Red (R), Green (G),
Opal (O), Blue (B) and Clear (C) made from flame
retardant polycarbonate plastic
- Continuously rated
- Flame retardant ABS plastic enclosure
- Strobe 2.5 and 5.0 joule
- 32 selectable tones meeting international regulations
- Sound selection via DIL switch
- Stainless steel fixings
POWER PRODUCTS
Xenon Flashers
Yodalarm
S2YA/
V4
V4
12
Code
Approval Specification
1FL040195
1FL040422
1FL040421
ATEX DIRECTIVE -9/94/EC EN50014:1997
+ Amendments 1& 2 EN50020:2002 &
EN50284:1999 BASEEFA Certificate No.
BAS05ATEX0075
Mounting:
All units are supplied seperate from the back box for ease of installation. The back box must be mounted
with the two cable entries at the top or bottom. The back box should be mounted to a reasonably flat
surface or to a standard wiring box using any of the internal mounting holes. A gasket is supplied, should
the surface be uneven, or if the unit is to be installed in wet conditions. The installation is completed by
fitting the beacon onto the back box by means of the supplied screws.
Line monitoring
Monitoring via reverse polarity
End of line resistor minimum 3K3 ohms 0.5 watts wire-wound or metal film type
Ordering information
Base colours:
RF=Red Flame
WN=White
Technical Specification
Main Features
- Operating temperature range: -25 to +40 deg C
- Storage temperature range: -40 to +70 deg C
- Relative humidity: 90% @ 40 deg C
- IP65 Rated
- Weight: DC types 0.24kg
- Weight: AC types 0.22kg
- Operating Voltage: 12Vdc or 24Vdc or 48Vdc
115Vac or 230Vac
- Flash rate 1 per second
- Continuously rated
- Strobe 2.5 and 5 joule
- High flash intensity
- 360° visibility
- Reliable and simple to install
- Complements audible alarm system
- Flush mounting base available
- Red/white flame retardant ABS plastic enclosure
- Lens colours, Red (R), Amber (A), Green (G), Opal (O),
Blue (B) and Clear (C) made from flame retardant
polycarbonate plastic
- Steady lamp version available upon request
Industrial Electrical Distributor
189
POWER PRODUCTS
Explosion Proof Sounders
Yodalarm
S2YA/
V6 / Y06 / YL6
V4
Approval Specification
UL STANDARDS:
UL464, UL1203, UL1638. Control No. 8N30
(Sounder Y06 and combined unit YL6) Control No. 13JM (Strobe only V6)
UL CLASSIFICATIONS:
Class I division 1 & 2, Gas group BCD. Class II division 1 & 2, Gas group EFG (Strobe only V6).
CUL CANADA:
CSA C22.2 No. 25-M1966, CSA C22.2 No. 30-M1986.
EUROPEAN STANDARDS:
EN.50014:1997 + Amendments 1 & 2 EN.50018:2000 EN50281-1-1:1998 BASEEFA 02ATEX 0212X (IIB).
BASEEFA 02ATEX 2222X (IIB+H2) ATEX Directive 94/9/EC.
Mounting:
Mounting bracket provided. Holes 9mm (dia).
Pitch 75mm.
Technical Specification
Main Features
- IP66 NEMA 4X
- Sounder: 24Vdc (Y06) 110dB @1 meter 350mA
- Strobe: 24Vdc (V6) 5 Joule 220mA
- Sounder/Strobe: 24Vdc (YL 6) 570mA
- Operating temperature:
- 35° C to + 60° C
- 20° C to + 60° C
- Omni directional high output sounder
- 2-Stage alarm
- Independently selectable 2nd stage
- All units share a common explosion proof housing
- Reduced installation costs
- Meets universal approval
- Low current consumption
- Dual cable entry, cable in-cable out
- LM 6 aluminium enclosure
- Stainless steel fasteners
- Borosilicate glass dome for strength and protection
- Lens guard provided as standard
- Weather proof flame retardant ABS horn
- 7 Lens colours in flame retardant poly-carbonate, Clear,
Opal, Yellow, Red, Amber, Blue, Green
- 32 Selectable tones meeting international regulations
Industrial Electrical Distributor
190
POWER PRODUCTS
12
Sounders
Yodalarm
S2YA/
CARILLON - Electronic Sounder
Approval Specification
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
12
Mounting:
The Carillon alarm units should be mounted to a reasonably flat wall or bulkhead of suitable material using
the internal fixing holes (mounting gasket supplied).
The recommended fixing screws are dia. 4.5max x 20m long. To maintain the integrity of the weather seal,
the cable must be fitted using a suitable sealed gland.
Technical Specification
Main Features
- Operating temperature range: -25 to +40 deg C
- Storage temperature range: -40 to +70 deg C
- Relative humidity: 95% @ 40 deg C
- IP65 Rated
- Cable gland entry must be suitably sealed
- Weight: 0.25kg
- Operating Voltage: 24Vdc +/- 10%
- Volume control giving 18dB(A) adjustment
- Minimum current consumption 20mA
- Versatile compact sounder
- Low current consumption
- High sound output
- 2 stage alarm by 2 wire bi-polar and 3 wire polarised
control
- Continuously rated
- Complies with BS 5839
- Easy installation
- For 3 wire alarm system, line integrity may be monitored
via reverse polarity
- 32 selectable tones meeting international regulations
- Sound selection via 5 way DIL switch
- Red flame retardant ABS plastic enclosures
Industrial Electrical Distributor
191
POWER PRODUCTS