QS Wallbox Closure Interface QSE-CI-WCI Control Interface 369681a 1 12.03.12 QS Wallbox Closure Interface The QSE-CI-WCI (WCI) is a control interface for use with HomeWorks® QS systems, Quantum® systems, and QS standalone applications. The WCI integrates a contact closure keypad with a Lutron® lighting control system. The contact closure keypad must be provided by the customer. The WCI provides up to eight contact closure inputs (CCIs). The CCIs accept maintained or momentary signals. The CCIs are programmable through the HomeWorks® QS and Quantum® system setup software. For QS standalone applications, the CCIs are programmable using the button, DIP switch, and LEDs on the WCI. Shown actual size. Features • Provides 8 contact closure inputs (CCIs), maintained or momentary. • Works with IEC PELV / NEC® Class 2, low-voltage, dry contact closures. • The CCI can be set up to simulate existing Lutron® keypad functionality or custom-configured to meet project-specific requirements. • Place in the wallbox behind a contact closure keypad (See Mounting). • Provides a 1-way interface between the Lutron® lighting system and a contact closure keypad (not supplied). • For use in HomeWorks® QS systems, Quantum® systems, and QS standalone applications. Additional Programming Details • In HomeWorks® QS and Quantum® systems, the 8 CCIs are individually programmable through the appropriate setup software. • For QS standalone applications, the DIP switch allows for selection of CCI control options: - With or without raise/lower controls. - With all momentary or all maintained CCIs. • LEDs provide instant feedback during setup and diagnostics; - Confirmation when programming. ® Job Name: Job Number: S p e c i f i c at i o n S u b m i t ta l Model Numbers: - Verification of which contacts are closed. - Indication of communication miswire/malfunction. • Programming button allows for ease of programming and resetting to factory default. Functionality in QS Standalone Systems •G RAFIK Eye® QS (QSGRx-) - Inputs activate Scenes. - Toggle Zones between a Preset and Off. - Cannot be used as a partion controller. • Energi Savr NodeTM (QSN- or QSNE-) - Inputs activate Scenes. - Toggle Zones between a Preset and Off. - Cannot be used as a partion controller. • Motor Module (QSE-CI-4M) - Window treatment Open/Stop/Close. - Toggle assigned windows treatments between Open and Close. • Contact Closure Interface (QSE-IO) • Sivoia® QS - Window treatment Open/Preset/Close. - Supports venetian window treatments. - Supports 6 default presets (4 presets when applying Raise/Lower). Page 1 QS Wallbox Closure Interface QSE-CI-WCI Control Interface 369681a 2 12.03.12 Specifications Regulatory Approvals • CE marked • Complies with IEC standards 60669-2-1 and 50428:2005 • If UL listing is required, please contact Lutron Input Power • Operating Voltage: 24 V- 20 mA • Low Voltage IEC PELV/NEC® Class 2 wiring provides power, derived from QS link. Consumes one Power Draw Unit (PDU). Contact Closure Input Types • The QSE-CI-WCI (WCI) is compatible with both momentary and maintained contact closure inputs (CCIs). • Contact closure keypad must have a low voltage, dry contact closure rating. • CCIs must have an on-state saturation voltage less than 1 V at 1 mA and an off-state leakage current of less than 100 uA. Contact manufacturer of the contact closure keypad for details. • The signal pulse for the CCI must be greater than 40 ms. Contact manufacturer of the contact closure keypad for details. • The WCI is not designed or rated to work with line/ mains voltage switches. Use with line/mains voltage switches will result in premature failure. ® Job Name: Job Number: S p e c i f i c at i o n S u b m i t ta l Model Numbers: Environment • Ambient Operating Temperature: 0-40 °C (32-104 °F) • Relative Humidity less than 90%, non-condensing • For indoor use only Terminals • Each terminal accepts up to two 1.0 mm2 (18 AWG) wires, one twisted shielded pair 0.5 mm2 (22 AWG) wire or one 4.0 mm2 (12 AWG) wire typical. Mounting • Recommended to be placed in the wallbox behind a contact closure keypad. • Lutron recommends using a wallbox which is 60 mm (2 1⁄2 in) deep x 60 mm (2 1⁄2 in) wide, when installing the WCI. Note: Some applications may require a deeper wallbox. • If alternative mounting is required, do not extend wiring harness more than 45 m (150 ft). QS Link Limits • Please refer to the system spec for details regarding your application. Page 2 QS Wallbox Closure Interface QSE-CI-WCI Control Interface 369681a 3 12.03.12 Mechanical Dimensions Side View mm ) 5 in . 59 340 (2. 52 mm (2.050 in) ® Job Name: Job Number: 47 mm (1.860 in) Front View Back View ® MUX MUX PWR COM 4 3 2 1 21 mm (.834 in) S p e c i f i c at i o n S u b m i t ta l Model Numbers: Page 3 QS Wallbox Closure Interface QSE-CI-WCI Control Interface 369681a 4 12.03.12 Wiring QS Link Wiring QS Wiring ® MUX MUX PWR COM 4 3 2 1 MUX (White) MUX (Purple) PWR (Red) COM (Black) 12345678 White Black 12345678 ON 7 8 COM Grey Blue Purple 3 4 5 6 Green 1 2 Yellow • Connect the contact closures to the contact closure inputs (CCIs) and shared common using supplied wiring harness. • Ensure proper function, and cap all unused CCI wires together, away from other circuitry. Note: All contact closures must share the provided common. (Black) Contact closure wire colors Red Orange Contact Closure Wiring 1 2 LEDs ® QSE-CI-WCI INPUTS ENTRADA ENTRÉES COM 12345678 Contact Closure Contact Closure COM CCI 1 (Red) 12345678 CCI 8 (White) Common (Black) Communication link wiring Contact Closure Inputs Note: Connect CCI wires appropriately Contact closure input 12345678 LEDs 1 (Red) 2 (Orange) 3 (Yellow) 4 (Green) 5 (Blue) 6 (Purple) 7 (Gray) 8 9 (Black) Contact Closure Inputs Wallbox Input Wiring Harness: Approximately 178 mm (7 in) long with 13 mm (1/2 in) pre-stripped end. ® Job Name: Job Number: S p e c i f i c at i o n S u b m i t ta l Model Numbers: Page 4