Electric Cabinet Specifications The following specifications describe the major components that shall be provided in the cabinet. The fabricator shall provide all the required miscellaneous wires, connectors, small components, etc.. In order to provide a functional electrical cabinet. All materials and construction shall meet the standards as stated in the appropriate specification section indicated below. Specifications: Section 16000 General Requirements 1.01 Quality Assurance A. Referenced standards: This Section incorporates by reference the latest revisions of the following documents. They are a part of this Section as specified and modified. Where a referenced document contains references to other standards, those documents are included as references under this Section as if referenced directly. In the event of conflict between the requirements of this Section and those of the listed documents, the requirements of this Section shall prevail. Reference Title AASHTO American Association of State Highway Transportation Officials ANSI A58.1 Minimum Design Loads for Buildings and Other Structures ASTM International (ASTM) FS Federal Specifications ICEA Insulated Cable Engineers Association IEEE Institute of Electrical and Electronics Engineers. Inc. NECA National Electrical Contractor's Association, Inc. NETA International Electric Testing Association NFPA-70 National Electrical Code (NEC) IBC International Building Code UBC Uniform Building Code UL Underwriters Laboratories, Inc. NEMA 250 Enclosures for Electrical Equipment B. Code references: 1. Code references in all Division 16 Sections shall include local amendments. Perform all work and install materials and equipment in full accordance with the latest applicable rules, regulations, requirements, and specifications of the following: a. Local, State and Federal Laws b. Oregon Electrical Specialty Code (OAR Chapter 9.18) c. Electrical Safety Law (ORS Chapter 479) d. National Electrical Code (NEC) e. Life Safety Code (NFPA-101) f. National Electrical Safety Code (NESC) g. American National Standards Institute (ANSI) h. National Electrical Manufacturers Association (NEMA) i. Institute of Electrical and Electronic Engineers (IEEE) j. Insulated Cable Engineers Association (ICEA) k. The Occupational Safety and Health Act (OSHA) l. American Society for Testing and Materials (ASTM) m. Underwriters' Laboratory (UL) n. Local laws, codes, and ordinances 2. In the case of conflicts that may exist between the above items, the more restrictive shall govern. 3. Wherever the requirements of the Specifications or Drawings exceed those of the items above, the requirements of the Specifications or Drawings shall govern. Code compliance is mandatory. Nothing in these Drawings and Specifications permits work not conforming to these codes. 4. Obtain all permits and pay all fees required by any governmental agency having jurisdiction over the work. Arrange all inspections required by these agencies. On completion of the work, furnish satisfactory evidence to the Engineer that the work is acceptable to the regulatory authorities having jurisdiction. C. Shipment, protection, and storage: 1. All equipment shall be shipped to the specified address and shall be protected from damage during shipment. At time of delivery, an approved ODFW representative shall sign off on receipt of the equipment and that is it free from damage. D. Use of listed products: 1. Electrical equipment and materials shall be listed by an independent testing laboratory for the purpose for which they are to be used. Four such organizations are Underwriters Laboratories (UL), Canadian Standards Association (CSA), Factory Mutual (FM), and Electrical Testing Laboratories (ETL). The independent testing laboratory shall be acceptable to the inspecting authority having jurisdiction. 2. When a product is not available with a testing laboratory listing for the purpose for which it is to serve, the product shall be required to undergo a special inspection and field labeling by an acceptable testing laboratory. All costs and expenses incurred for such inspections shall be included in the original contract price. 3. Products shall meet all requirements and be "Certified Electrical Products" per Oregon Electrical Safety Law (ORS 479). E. Factory support: 1. Factory Tests: The assembler or manufacturer of electrical apparatus components, materials and equipment assemblies shall conduct Factory testing. Factory tests shall be performed at the place of fabrication and performed on completion of manufacture or assembly. All system components shall be factory-wired and tested as a system prior to shipment. The costs of factory tests shall be included in the contract price. Testing shall be designed to verify design conformance and system operation and shall include as a minimum: a. Verification of drawings and bill of materials b. Certification of conformance with ANSI/NEMA ICS 1 and ANSI/NEMA ICS. 1.02 SUBMITTALS A. Preconstruction submittals: 1. The following submittal information and product data specified under individual specification sections shall be provided. 2. Manufacturer's equipment and device information. a. Ratings, range, accuracy, etc. b. Catalog cuts shall be edited to show only the items model numbers, and information that apply to the submittal requirements. c. Manufacturer's certification and calculations that the equipment complies with the seismic requirements of this Section. d. Additional specific materials requested by the individual specification sections e. Indication of whether the product is listed or will be labeled to meet Certified Electrical Product requirements 3. Manufacturer's Warranty or when required in the individual specifications, Certified Certificate of Unit Responsibility. 4. Drawings for Vendor or Contractor designed systems: a. Equipment arrangement drawings depicting panel and cabinet locations, dimensions, required clearances, height, width and depth, mounting requirements, support structures. b. Panel drawings shall be comprehensive shop assembly and interconnection drawings. c. Drawing format for circuiting may be as revised one-line diagrams and elementary or schematic diagrams as appropriate. B. Construction and post construction submittals 1. The following submittal information and product data specified under individual specification sections shall be provided. a. Applicable operation and maintenance information on an item-by¬ item basis. Operation and maintenance information shall be provided at the time of equipment, device, or material site delivery, or at a certain stage of project completion, whichever is the earlier. Full-size drawings shall be reduced to 11 x 17 inches. b. Test results for electrical systems shall be maintained by the Contractor. Prior to acceptance of work, the resulting file shall be provided to the Engineer. C. Action submittals: In addition to requirements contained in individual Specification Sections: 1. Panel boards. 2. Control devices, terminal blocks, and relays. 3. Equipment Identification Nameplates and schedule. 4. Conductors, cable, and accessories. 5. Grounding materials. 1.03 DRAWING DEFINITIONS A. Elementary or schematic diagram: A schematic (elementary) diagram shows. By means of graphic symbols, the electrical connections and functions of a specific circuit arrangement. The schematic diagram facilitates tracing the circuit and its functions without regard to the actual physical size, shape, or location of the component devices or parts. B. One-line diagram: Shows by means of single lines and graphical symbols the course of an electrical circuit or system of circuits and the components, devices, or parts used therein. Physical relationships are usually disregarded. C. Block diagram: A diagram of a system, instrument, computer, or program in which selected portions are represented by annotated boxes and interconnecting lines. D. Wiring diagram or connection system: A wiring or connection diagram includes all of the devices in a system and shows their physical relationship to each other including terminals and interconnecting wiring in an assembly. This diagram shall be (a) in a form showing interconnecting wiring only by terminal designation (wireless diagram), or (b) a panel layout diagram showing the physical location of devices plus the elementary diagram. E. Interconnection diagram: 1. Interconnection diagrams shall show all external connections between terminals of equipment and outside points, such as motors and auxiliary devices. References shall be shown to all connection diagrams which interface to the interconnection diagrams. Interconnection diagrams shall be of the continuous line type. Bundled wires shall be shown as a single line with the direction of entry/exit of the individual wires clearly shown. 2. Each wire identification as actually installed shall be shown and the wire identification for each end of the same wire shall be identical. All devices and equipment shall be identified and terminal blocks shall be shown as actually installed and identified in the equipment complete with individual terminal identification. 3. Show all jumpers, shielding and grounding termination details including signal and DC circuit polarities and wire pairs. 4. F. Wireless diagrams and wire lists are not acceptable. Arrangement, layout, or outline drawings: An arrangement, layout, or outline drawing is one which shows the physical space and mounting requirements of a piece of equipment. It may also indicate ventilation requirements and space provided for connections or the location to which connections are to be made. G. Drawings A complete set of Contractor As-Built drawings is to be supplied on 11 X 17 inch paper media and on electronic media. Drawings will be complete with borders and title blocks clearly identifying project name, equipment and the scope of the drawing. Drawing quality and size of presentation shall be such as to permit reduction and reproduction of such drawings for insertion into operation and maintenance manuals. PART 2 – PRODUCTS AND SERVICES 2.01 EQUIPMENT AND MATERIALS A. General: 1. Products shall comply with all applicable provisions of NFPA 70. 2. Equipment and materials shall be new and free from defects. 3. All material and equipment of the same or a similar type shall be of the same manufacturer throughout the work. 4. Standard production materials shall be used wherever possible. B. Equipment finish and color: Unless otherwise indicated, electrical equipment and materials shall be painted by the manufacturer according to their standard paint finish materials and color. C. Enclosure ratings: Unless specified otherwise in other sections, electrical and instrumentation enclosures shall be provided in accordance with the following table. See this section for the location of classified areas: Area Type NEMA 250 rating and material Indoor dry NEMA 12 Mild Steel Indoor wet NEMA 1, Painted Process corrosive Outdoor NEMA 4X, 5052-H32 Aluminum NEMA 3R, Painted Chemical corrosive NEMA 4X, FRP Underground vault, manholes and hand holes Classified NEMA 6P NEMA 7 F. Raceway materials: See Specification Section 16110, 2.01, Table A. 2.02 ELECTRICAL NUMBERING SYSTEMS A. Raceway identification: Raceway Prefix Type of Function C Control or power - 120V or less D Data and Communication H Power above 600V L Lighting - all voltages N Pneumatic tubing P Power 208V to 600V S Signal - data communication or instrumentation X Spare 1. Raceway prefixes shall be followed by a unique number. Add a letter suffix to distinguish the raceways where more than one raceway is routed to a particular piece of equipment. Example: Raceway number = P3109A where: P = conduit contains power 3109 = unique 4-digit (or TAG) number A = letter to distinguish raceways to same equipment 2. Raceways shall be tagged at all terminations. B. Cable and conductor identification: 1. Cables and conductors shall be identified with numbers at both ends. Cable numbers may generally follow conduit designations. Conductor tag numbers shall consist of the Process Area number and equipment TAG number followed by a dash followed by the conductor number specified on the control or one-line diagram. Add a letter suffix to distinguish the cable where more than one cable is routed to a particular piece of equipment. Example: Conductor number =60M3109A-L1 where: 60 = City Pump Station M = Circuit identifier i.e. Motor Circuit 3109 = unique number (or TAG) number A = letter to distinguish parallel cables to same equipment -L I = conductor number Cable circuit identifiers may be any abbreviation shown on the table of General Electrical Abbreviations on Sheet E1. 2. Conductors in parallel or in series between equipment shall have the same conductor number. Neutral conductors shall have the same conductor number. Wherever possible, the conductor number shall be the same as the equipment terminal to which it connects. 3. Where factory-wired equipment has terminal numbers different than the conductor numbers shown on the control diagrams: a. Both shall be shown on the interconnection diagram b. Include a copy of the interconnection diagram inside of the equipment cabinet. 2.03 CONDUCTOR AND CABLE MARKERS A. Each power and control conductor shall be identified at each terminal to which it is connected. Conductors size No. 10 AWG or smaller shall have identification sleeves. Conductors No.8 AWG and larger shall use cable markers of the locking tab type. Tabs shall be white plastic with conductor identification number permanently embossed. Adhesive strips are not acceptable. B. The letters and numbers that identify each wire shall be machine printed on sleeves with permanent black ink with figures 1/8 inch high. Sleeves shall be yellow or white tubing and sized to fit the conductor insulation. Shrink the sleeves with hot air after installation to fit the conductor. C. Conductor and Wire Marker Manufacture: 1. TMS Thermofit Marker System by Raychem Co or IMPACT 2. Sleeve style wire marking system by W. H. Brady Co. 3. Or approved equal. 2.04 INDICATING LAMP COLORS A. Unless otherwise specified, indicator lights shall be fitted with colored lenses in accordance with the following schedule: Color Function Example Amber Abnormal or FAULT Condition Failure of equipment or status abnormal, fault condition Red Ready Ready Green Normal Active Condition pressure of air, water or lubrication Pump Running, Control power on, status OK or clear, Normal White Not Used 2.05 ELECTRICAL EQUIPMENT LABELING A. General 1. All electrical equipment shall have labeling per the requirements specified herein. 2. General requirements for Equipment Identification Labeling are specified in this section. Individual Equipment Identification Label requirements may be modified in the individual specifications section for the associated equipment. 3. Electrical Numbering System requirements for labeling raceway and conductors are specified in Section 16110 and 16000-2.02(A). 4. Equipment Identification Labels for all equipment on this project shall conform to the equipment name standards for equipment as indicated in the project equipment list and on the Drawings in the format shown in paragraph 2.07(D) of this Section. a. Equipment tags shall include the equipment name and numbers exactly as listed in the equipment list and on the Drawings. Contractor shall submit proposed label nomenclature prior to installation on equipment. b. Equipment Identification Labels shall accommodate four lines of up to nineteen characters each. c. All unscheduled equipment shall also be labeled. Contractor shall obtain labeling information direction from the Engineer and shall submit proposed labels prior to installation on equipment. This information shall be transferred to as built documents and drawings by the contractor. B. General signs and labeling Electrical equipment shall have signs and labeling to warn qualified persons of the potential electric arc flash hazards per NEC Article 110.16, Flash Protection. C. Multiple feeder warning: Provide plaques per NEC 690.17 and 70 1.9(A) which identify all multiple source feeders at building disconnect locations identified as SE on the Drawings. D. Equipment identification labels: 1. Equipment Identification Labels shall be affixed to electrical service, distribution and utilization equipment to identify the power source and the load as specified. Nameplates shall be provided on each item of electrical equipment, including individual switches and grouped distribution circuit breakers and shall contain the specified equipment name or approved abbreviation and equipment number. Power Panel boards shall have individual breakers identified on an internal panel schedule 2. Refer to NEC Article 110.22 for Identification of Disconnecting Means installation criteria. Specific information is required such as the equipment tag number and equipment description of both the power source and the load equipment. Equipment with multiple sources will also require Multiple Feeder Identification and Warning Signs as specified in 16000, 2.07(C). 3. Unless modified by specific instruction in individual Sections, indoor Equipment Identification Labels shall be made from laminated phenolic plastic 1-inch high by 2 -1/2 inches long, black background with 1/8-inch machine engraved white letters. Sample Label Format: PANEL 1234 LIFT STATION PUMPS MASTER CONTROL PANEL FEED FROM MCC-11A, UNIT 1A E. Outdoor equipment identification labels: Outdoor equipment identification labels shall be engraved or stamped stainless steel and fastened to the equipment in an immediately visible location with stainless steel screws or drive pins. 2.06 TERMINAL STRIPS, BLOCKS, AND DEVICES A. POWER TERMINAL BLOCKS FOR P-CIRCUITS (POWER 208 TO 600V): Provide back plate mounted terminal strips rated not less than the conductor current rating nor less than 600VAC. Terminals for circuits to 30A shall be pan-head strap screw type, used with wiring terminated with ring type or locking fork terminals. Terminals for circuits above 30A shall be lug type. B. Control terminal blocks for c-circuits (control and/or power 120v or less power) and s-circuits (signal): 1. Terminal blocks shall be cage screw type suitable for direct termination of stranded control wires. a. Rated not less than 20A nor less than 600V for C-circuits unless noted otherwise in the equipment specifications b. Rated not less than 15A nor less than 300V for S-circuits. c. Pull apart terminal blocks: Rated not less than 10A nor less than 300V. C. Terminals shall be provided with integral marking strips. D. Acceptable Manufacturers: 1. Power Terminal Blocks: Marathon Special Products, Ilsco or approved equal. 2. Power Distribution Blocks: Marathon Special Products, Ilsco or approved equal: 3. Control Standard (Switched): Entrelec type M 6/8.SNB 4. Control Fused (BFI): Entrelec type ML 1011 3.SFL 5. DIN rail: Phoenix Contact or Weidmuller Z-Series. 6. Approved equal 2.08 FACTORY TESTING Where specified in the specification section, perform factory tests at the place of fabrication. Perform on completion of manufacture or assembly. 2.09 ELECTRICAL CIRCUITS DESIGNED AND INSTALLED BY THE CONTRACTOR A. Installation requirements not shown on the drawings: There are systems and vendor packages for which it is necessary to install raceways and cables that are not shown on the drawings or schedules. For these cases, circuits shall be installed as required to provide complete and functional systems as described in the specification sections for the associated system or vendor package. No installation of unscheduled circuiting in the scheduled cable trays or raceways for these systems shall proceed without the prior written consent of the Engineer. It shall be the Contractor’s responsibility to provide verification that the raceway fill capacity is not being exceeded. B. Unscheduled raceway: 1. Lighting and receptacle raceway are unscheduled and shall be sized by the Contractor in accordance with the NEC. Minimum size shall be 3/4-inch for exposed and 1-inch for embedded raceway. 2. The number and size of raceways shall be as required for the particular equipment provided and subject to the minimum sizes specified above. The type of raceway and fittings to be used for any given area and application shall conform to the requirements for location/exposure in paragraph 16110-2.0 I, Table A. 3. All unscheduled wiring, cable, conduit, tray and terminal blocks shall be identified and labeled as specified in this Section. Contractor shall obtain labeling information direction from the Engineer and shall submit proposed labels prior to installation on cables or equipment. This information shall be transferred to as built documents and drawings by the Contractor. C. Not used D. All other power circuits: Do not combine power circuits without the authorization of the Engineer. Part 3 Execution 3.01 Final Acceptance Final acceptance of the project is dependent upon completion of all requirements of these specifications and receipt by the Engineer of complete As Built red-line documentation from the contractor. Section 16470 Power Distribution Panelboards PART 1--GENERAL 1.01 DESCRIPTION A. SUMMARY: This Section specifies panelboards for power distribution. 1.02 QUALITY ASSURANCE A. REFERENCED STANDARDS: This Section incorporates by reference the latest revisions of the following documents. They are a part of this Section as specified and modified. Where a referenced document contains references to other standards, those documents are included as references under this Section as if referenced directly. In the event of conflict between the requirements of this Section and those of the listed documents, the requirements of this Section shall prevail. Reference Title IEEE Institute of Electrical and Electronic Engineers NEMA National Electrical Manufacturing Association ANSIII EEE C62.41 Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits ANSI/IEEE C62.45 Circuits Guide on Surge Testing for Equipment Connected to LowVoltage AC Power ANSI 255.1-1967 Gray Finishes For Industrial Apparatus & Equipment NEMA PB I Panelboards NEMA PB 2 Deadfront Switchboards NFPA 70 National Electrical Code (NEC) UL 50 Cabinets and Boxes UL67 Underwriters Laboratories. Electric Panelboards UL489 Molded-Case Circuit Breakers and Circuit Breaker Enclosures UL 1449 Transient Voltage Surge Suppressors 1.03 SUBMITTALS A. Provide for approval prior to equipment purchase. B. Submittal to include the following information: 1. Manufacturer's certification that bus bracing is capable of withstanding the specified short circuit condition. 2. used. Quantity and rating of circuit breakers including short circuit rating for all circuit breaker types 3. Applicable operation and maintenance information. 4. Outline plan and elevation drawings with clearance requirements 5. Test results for all specified testing. 6. Equipment Identification label nomenclature. PART 2--PRODUCTS 2.01 GENERAL Panel boards shall be circuit breaker, dead front type, with bus bar construction of capacity noted on the drawings. Minimum Interrupting Capacity of protective device shall be 42,000 amperes unless specifically approved by the owner or owner’s representative. A. ACCEPTABLE MANUFACTURERS: 1. General Electric, Eaton, Cutler-Hammer, Siemens, Square D The panel board manufacturer's standard models or products may require modification to conform to specified requirements. In this case, notify owner prior to equipment purchase. 2.02 ARRANGEMENT AND CONSTRUCTION The front of the panel shall have concealed trim clamps and hinges. The locks shall be keyedalike and flush with tumbler-type cylinder and spring loaded door pulls. The fronts shall not be removable with doors in the locked position. Gutter space shall be provided on all sides of the breaker assembly to neatly connect and arrange incoming wiring. Individually mounted circuit breakers shall be designed to be removable without disturbing other breakers. A directory holder with clear plastic plate and metal frame shall be mounted on the inside of the door. Enclosure rating to conform with Location/Exposure as shown in Section 16000. 2.03 BUS Bus shall be tin-plated copper and shall have current ratings as shown on the panelboard schedules, sized in accordance with UL 67. Ratings shall be determined by temperature rise test. The minimum bus size shall be 100 amperes. Panel fault withstand rating shall be not less than the interrupting rating of the smallest circuit breaker in the panel. Series rating is prohibited. Panelboards shall be provided with a separate ground bus and, where specified, with a full capacity neutral bus. The neutral bus shall be mounted on insulated stand-offs. 2.04 CIRCUIT BREAKERS Circuit breakers shall be molded-case type provided for the current ratings and pole configurations specified on the panelboard schedule. Circuit breakers shall be bolt-on type. Circuit breakers shall be listed in accordance with UL 489 for the service specified. Load terminals of circuit breakers shall be solderless connectors. Circuit breakers rated 120/208 volt and 120/240 volt alternating current shall have a minimum interrupting current rating of 18,000 amperes symmetrical. Circuit breakers rated 277/480 volt alternating current shall have a minimum interrupting current rating of 25.000 amperes symmetrical at 480 volt or as specified on the panelboard schedule. Provide circuit breakers with special features such as ground fault interrupting (GFI), heating air conditioning and refrigeration (HACR) rating, or locking capability as required by Code or shown on the Drawings or Schedules. 2.05 PANELBOARD FINISH The finish and color shall comply with Section 16000. 2.06 TRANSIENT VOLTAGE SURGE SUPPRESSOR Each Panel board shall have integral TVSS protection on the main bus. 2.07 EQUIPMENT IDENTIFICATION AND PERSONNEL WARNING LABELS A. An Equipment Identification Label shall be provided identifying the Panelboard assembly as specified in Section 16000. B. Provide a typed panel schedule detailing all pane I board circuit assignments and protective device ratings. C. Manufacturer' s nameplate identifying the apparatus and providing ratings and catalog data. D. Manufacturer installed and NEC mandated labels for Personnel Safety. PART 3--EXECUTION 3.01 FIELD TESTING In addition to any testing herein, perform all testing for this product or system consistent with the requirements of the applicable codes and the manufacturers' current quality assurance program. 3.02 PANEL SCHEDULES Panel boards are scheduled on the Schedules in the Project Documents. Type in the circuit description on the circuit directory or panelboard schedule and document changes, deletions and additions in as-built documentation. Section 16480 Service Equipment PART 1--GENERAL 1.01 DESCRIPTION A. SUMMARY: This Section specifies Utility requirements for customer provided and installed equipment for provisions of electrical service and customer owned service entrance equipment for power distribution. 1.02 QUALITY ASSURANCE A. REFERENCED STANDARDS: This Section incorporates by reference the latest revisions of the following documents. They are a part of this Section as specified and modified. Where a referenced document contains references to other standards, those documents are included as references under this Section as if referenced directly. In the event of conflict between the requirements of this Section and those of the listed documents, the requirements of this Section shall prevail. Reference IEEE Title Institute of Electrical and Electronic Engineers NEMA National Electrical Manufacturing Association ANSIII EEE C62.41 Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits ANSI/IEEE C62.45 Circuits Guide on Surge Testing for Equipment Connected to LowVoltage AC Power ANSI 255.1-1967 Gray Finishes For Industrial Apparatus & Equipment NEMA PB I Panelboards NEMA PB 2 Deadfront Switchboards NFPA 70 National Electrical Code (NEC) UL 50 Cabinets and Boxes UL67 Underwriters Laboratories. Electric Panelboards UL489 Molded-Case Circuit Breakers and Circuit Breaker Enclosures UL 1449 Transient Voltage Surge Suppressors 1.03 SUBMITTALS A. Provide for approval prior to equipment purchase. B. Submittal to include the following information: 1. Manufacturer's certification that bus bracing is capable of withstanding the specified short circuit condition. 2. used. Quantity and rating of circuit breakers including short circuit rating for all circuit breaker types 3. Applicable operation and maintenance information. 4. Outline plan and elevation drawings with clearance requirements 5. Test results for all specified testing. 6. Equipment Identification label nomenclature. PART 2--PRODUCTS 2.01 GENERAL Switchboard shall be service rated and of circuit breaker, dead front type, with bus bar construction of capacity noted on the drawings. Minimum Interrupting Capacity of protective device shall be 42,000 amperes unless specifically approved by the owner or owner’s representative. A. ACCEPTABLE MANUFACTURERS: 1. General Electric, Eaton Cutler-Hammer, Siemens, Square D, Approved equal. The switch board manufacturer's standard models or products may require modification to conform to specified requirements. In this case, notify owner prior to equipment purchase. 2.02 ARRANGEMENT AND CONSTRUCTION The front of the panel shall have concealed trim clamps and hinges. The locks shall be keyedalike and flush with tumbler-type cylinder and spring loaded door pulls. The fronts shall not be removable with doors in the locked position. Gutter space shall be provided on all sides of the breaker assembly to neatly connect and arrange incoming wiring. Individually mounted circuit breakers shall be designed to be removable without disturbing other breakers. A directory holder with clear plastic plate and metal frame shall be mounted on the inside of the door. Enclosure rating shall be NEMA 3R for outdoor installation. 2.03 BUS Bus shall be tin-plated copper and shall have current ratings as shown on the drawings, sized in accordance with UL 67. Ratings shall be determined by temperature rise test. The minimum bus size shall be 400 amperes. Panel fault withstand rating shall be not less than the interrupting rating of the smallest circuit breaker in the panel. Series rating is prohibited. Switchboard shall be provided with a separate ground bus and, where specified, with a full capacity neutral bus. The neutral bus shall be mounted on insulated stand-offs. 2.04 CIRCUIT BREAKERS Circuit breakers shall be molded-case type with frame and interchangeable trip unit ratings as specified on the one-line diagram. If a manufacturer offers frame sizes differing from the drawings that may satisfy requirement, submit to engineer for approval prior to purchase. All Circuit breakers shall be bolt-on type. Circuit breakers shall be listed in accordance with UL 489 for the service specified. Load terminals of circuit breakers shall be solderless connectors. Circuit breakers rated 600 volt shall have a minimum interrupting current rating of 42,000 amperes symmetrical. Provide circuit breakers with special features such as ground fault interrupting (GFI), heating air conditioning and refrigeration (HACR) rating, or locking capability as required by Code or shown on the Drawings or Schedules. 2.05 SAFETY DISCONNECT SWITCHES A. Safety disconnect switches shall be non--fused heavy-duty, 30-400-ampere ratings as indicated, stainless steel operator, auxiliary contact kit. safety type rated 600 volts AC. The operating handle shall be a positive, quick-make, quick-break mechanism capable of being padlocked in the "off' position and have a “visible” open capability. B. Enclosure ratings in accordance with Location/Exposure as specified in Section 16000. C. Switches shall be horsepower rated for motors and shall comply with NEMA KS-I. Switches shall be provided with defeatable door interlocks that prevent the door from opening when the operating handle is in the "on" position. Switches shall have line terminal shields. D. ACCEPTABLE MANUFACTURER: 1. Eaton/Cutler-Hammer 2. GE 3. Approved equal. 2.06 EQUIPMENT FINISH The finish and color shall comply with Section 16000. 2.07 TRANSIENT VOLTAGE SURGE SUPPRESSOR The Service Switchboard board shall have factory installed integral TVSS protection on the main bus designed with adequate protective capacity. 2.08 EQUIPMENT IDENTIFICATION AND PERSONNEL WARNING LABELS A. An Equipment Identification Label shall be provided identifying the Panelboard assembly as specified in Section 16000. B. Provide a typed panel schedule detailing all panel board circuit assignments and protective device ratings. C. Manufacturer' s nameplate identifying the apparatus and providing ratings and catalog data. D. Manufacturer installed and NEC mandated labels for Personnel Safety. PART 3--EXECUTION 3.01 FIELD TESTING In addition to any testing herein, perform all testing for this product or system consistent with the requirements of the applicable codes and the manufacturers' current quality assurance program. 3.02 EQUIPMENT SCHEDULES Type in the circuit description on the circuit directory or panelboard schedule and document changes, deletions and additions in as-built documentation.