1 E F G OWNER NAME: EXAMPLE PHONE: 111-000-1111 NAME: EXAMPLE NEW PV SYSTEM: 7.98 kWp EXAMPLE RESIDENCE DESIGN SPECIFICATIONS OCCUPANCY: RESIDENTIAL CONSTRUCTION: SINGLE SPAN RAFTER (WOOD) ZONING: RESIDENTIAL ROOF SNOW LOAD: 30 WIND EXPOSURE: B WIND SPEED: 130 NAME: EXAMPLE PHONE: EXAMPLE AUTHORITIES HAVING JURISDICTION BUILDING: TOWN OF EXAMPLE ZONING: TOWN OF EXAMPLE UTILITY: EXAMPLE H SHEET LIST CONTRACTOR 2 D SHEET NUMBER SHEET TITLE G-1 G-2 A-1 A-2 E-1 E-2 S-1 D-1 D-2 D-3 D-4 D-5 COVER PAGE NOTES SITE PLAN PROJECT PLAN THREE LINE DIAGRAM PLACARDS RACKING DETAILS MODULE DATASHEET INVERTER DATASHEET RACKING DATASHEET RACKING MOUNT DATASHEET POWER OPTIMISER DATASHEET 10 EXAMPLE ST EXAMPLE, NY 11111 ASSESSOR'S #: 00000000 APPLICABLE CODES & STANDARDS BUILDING: 2010 NYSBC ELECTRICAL: NEC 2011 FIRE: 2010 NYSFC 10 EX EXAMPLE PHONE: 111-000-1111 LIC. No.: 000000 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. E ST AMPL EXAMPLE RESIDENCE 3 N AERIAL PHOTO G-1 01 4 G-1 03 SCALE: NTS FRONT PHOTO G-1 02 SCALE: NTS PLAN MAP W E SCALE: NTS S 1.1.1 1.1.2 1.1.3 1.1.4 5 CONTRACTOR 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 PROJECT MANAGER C NEW PV SYSTEM: 7.98 kWp B A 1.1.5 1.1.6 PROJECT NOTES THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES. GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED WITH THE INVERTER IN ACCORDANCE WITH [NEC 690.5(A)] THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 690.64 (B)] ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY [NEC 690.4] & [NEC 690.60] PV MODULES:UL 1703 CERTIFIED, NFPA 70 CLASS C FIRE INVERTER(S):UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(S):UL 1703 OR UL 1741 ACCESSORY ENGINEER OF RECORD 1.2.1 SCOPE OF WORK PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT. 1.2.2 WORK INCLUDES: 1.2.3 PV ROOF ATTACHMENTS 1.2.4 PV RACKING SYSTEM INSTALLATION 1.2.5 PV MODULE AND INVERTER INSTALLATION 1.2.6 PV EQUIPMENT GROUNDING 1.2.7 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX 1.2.8 PV INSTALLING SYSTEM MONITORING EQUIPEMENT 1.2.9 PV LOAD CENTERS (IF NEC.) 1.2.10 PV METERING (IF NEC.) 1.2.11 PV DISCONNECTS 1.2.12 PV GROUNDING ELECTRODE & BONDING TO (E) GEC 1.2.13 PV FINAL COMMISSIONING 1.2.14 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV COVER PAGE DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H G-1 A B C D E F G H 1 2.1.6 2 2.1.7 2.1.9 2.1.10 2.1.11 2.1.12 3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 2.2.10 2.2.11 2.3.1 2.3.2 2.3.3 2.3.4 5 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.4.11 2.4.12 2.2.1 2.2.2 2.2.3 4 2.4.3 2.3.5 2.3.6 SOLAR CONTRACTOR MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730. IF APPLICABLE, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. AS INDICATED BY DESIGN, OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A SUITABLE SEALING COMPOUND. DC WIRING LIMITED TO MODULE FOOTPRINT W/ ENPHASE AC SYSTEM. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT AVAILABLE. ALL INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC MODULES, SOURCE CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. EQUIPMENT LOCATIONS ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY [NEC 110.26]. EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY [NEC 690.31 (A)-(B)] AND [NEC TABLE 310.15 (B)(2)(C)]. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT TO THE UTILITY AC DISCONNECT, OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. 2.4.13 2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 2.5.6 2.5.7 2.5.8 2.6.1 2.6.2 2.6.3 WIRING & CONDUIT NOTES ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE APPLICATIONS ALL PV CABLES AND HOMERUN WIRES BE #10AWG *USE-2, PV WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS REQUIRED ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC 690.8 (A)(1) & (B)(1)], [NEC 240] [NEC 690.7] FOR MULTIPLE CONDUCTORS ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(C)] BLACK ONLY** EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP EDGES PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 600V PER NEC 2008 OR 1000V PER NEC 2011 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 1% FOR AC CIRCUITS NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC POSITIVE- RED (OR MARKED RED) DC NEGATIVE- GREY (OR MARKED GREY) POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: DC POSITIVE- GREY (OR MARKED GREY) DC NEGATIVE- BLACK (OR MARKED BLACK) AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK PHASE B OR L2- RED PHASE C OR L3- BLUE NEUTRAL- WHITE/GRAY *USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE ** USE-2 IS AVAILABLE AS UV WHITE STRUCTURAL NOTES: RACKING SYSTEM & PV ARRAY SHALL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A 1" SPACE BETWEEN MODULES. RAILS MUST ALSO EXTEND A MIN. 3” BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY. ROOFMOUNTED STANDARD RAIL REQUIRES ONE THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL GREATER THAN 40'. ARRAY SHALL BE A MIN. HEIGHT OF 3" ABOVE THE COMPOSITION ROOF. JUNCTION BOX SHALL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. ROOFTOP PENETRATIONS PERTAINING TO SOLAR RACKING WILL BE COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. ALL PV RELATED RACKING ATTACHMENTS WILL BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. O.C. FINAL ATTACHMENT LOCATIONS MAY BE ADJUSTED IN THE FIELD AS NECESSARY. ALL PV RELATED RACKING ATTACHMENTS SHALL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS. GROUNDING NOTES A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690-47] AND [NEC 250-50] THROUGH [NEC 60 250-166] SHALL BE PROVIDED. PER NEC, GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND 2.6.4 2.6.5 2.6.6 2.6.7 2.6.8 2.6.9 2.6.10 2.6.11 2.6.12 2.6.13 2.6.14 2.6.15 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.8.1 2.8.2 2.8.3 2.8.4 NO GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.21], [NEC TABLE 250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO [NEC 690.43]. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC 690.42]. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED, AND BARE WHEN EXPOSED. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO [NEC 690.45] AND BE A MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE (#6AWG SHALL BE USED WHEN EXPOSED TO DAMAGE). GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN (OR MARKED GREEN IF #4 AWG OR LARGER) ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. AC SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED ACCORDING TO [NEC 250.166], MINIMUM #8AWG WHEN INSULATED, #6AWG WHEN EXPOSED TO DAMAGE. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE. INTERCONNECTION NOTES PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED AT THE OPPOSITE END OF THE BUS FROM THE MAIN SERVICE BREAKER OR TRANSFORMER INPUT FEEDER IN ACCORDANCE WITH [NEC 690.64(B)(7)] SUM OF BREAKER RATINGS SUPPLYING THE BUS MAY NOT EXCEED 120% OF THE THE BUSBAR RATING PER [NEC 690.64(B)(2)] AND/OR [NEC 705.12(D)(1). GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC 690.64(A)] AND/OR [NEC 705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 230.42(B)] MICROINVERTER BRANCHES SHALL BE CONNECTED TO A SINGLE BREAKER OCPD IN ACCORDANCE WITH [NEC 110.3(B)]. DISCONNECT NOTES DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH DC CURRENT CONDUCTORS ARE TO REMAIN OUTSIDE OF BUILDING PRIOR TO EITHER A FUSEABLE SOURCE CIRCUIT COMBINER BOX OR A LOAD-BREAK DISCONNECTING DEVICE CONTRACTOR EXAMPLE PHONE: 111-000-1111 LIC. No.: 000000 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 2.1.5 2.4.1 2.4.2 EXAMPLE RESIDENCE 2.1.4 SITE NOTES A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26] ALTERNATE POWER SOURCE PLACARD SHALL BE PLASTIC, ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTACHED USING AN APPROVED METHOD. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE PER NEC 250-64B. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER [NEC 250.64C.] ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. RIGID CONDUIT (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE POLARIS BLOCK OR NEUTRAL BAR) ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERS DISALLOWED ABOVE LIVE PARTS, MEYERS HUBS RECOMMENDED NEW PV SYSTEM: 7.98 kWp 2.1.1 2.1.2 2.1.3 ENGINEER OF RECORD NOTES DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. 2011S REVISIONS 6 A B C D E F G H G-2 B A C D E F G H 1 LEGEND 01 (E) UTILITY METER 02 AC DISCONNECT 03 DC/AC INVERTER E MAIN ENTRANCE DOOR CONTRACTOR EXAMPLE PHONE: 111-000-1111 LIC. No.: 000000 PROPERTY LINE UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. SOLAR MODULE 01 55'-3" 02 NEW PV SYSTEM: 7.98 kWp E EXAMPLE RESIDENCE 03 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 2 17'-10" 21' 4 ENGINEER OF RECORD 39'-8" AREA OF WORK 5 SITE PLAN DATE: N A-1 01 SITE PLAN 6.11.2015 DESIGN BY: J.G. W CHECKED BY: M.M. E SCALE: 1/16" = 1'-0" REVISIONS S 6 0 A B C 10 D 20 32 E F G H A-1 B A 1 C D E F LEGEND M (E) UTILITY METER S AC DISCONNECT 2 MAIN ELECTRICAL PANEL I DC/AC INVERTER DCSW DC DISCONNECT H INTERIOR PV EQUIPMENT [x1] (E) MAIN ELECTRICAL PANEL MEP MEP G EXTERIOR PV EQUIPMENT [x1] (E) UTILITY METER [x1] (N) AC DISCONNECT [x1] (N) DC/AC INVERTER [x1] (N) DC DISCONNECT M S I CONTRACTOR DCSW EXAMPLE PHONE: 111-000-1111 LIC. No.: 000000 JB JUNCTION BOX UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. ROOF RAFTERS 3' FIRE CLEARANCE PER NYFC 2014 FIRE CLEARANCE 2:12 NEW PV SYSTEM: 7.98 kWp JB RAILINGS AND MOUNTS EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 SOLAR MODULE 3' FIRE CLEARANCE PER NYFC 2014 ARRAY 2.28 kW [x8] (N) MODULES 2:12 ARRAY 5.70 kW [x20] (N) MODULES 4 ENGINEER OF RECORD 27'-6" 5 PROJECT PLAN 131.9988 DATE: N A-2 01 PROJECT PLAN DESIGN BY: J.G. W E SCALE: 3/16" = 1'-0" TILT: 10 DEGREES AZIMUTH: 165 DEGREES CHECKED BY: M.M. AZIMUTH: REVISIONS S 0 6 A B C 10 20 D 6.11.2015 32 E F G H A-2 B A C D E F G H 1 PM PO 01 CATEGORY MANUFACTURER MODEL NUMBER COMPONENT REF QUANTITY UNIT QUANTITY PER UNIT DESCRIPTION MODULE SOLAR WORLD SW 285 MONO PM1-28 28 PIECES 1 SOLAR WORLD SW 285 MONO 285W, 60 CELLS, MONOCRYSTALLINE SILICON INVERTER SOLAR EDGE SE7600A-US I1 1 PIECE 1 SOLAR EDGE SE7600A-US 7680W INVERTER POWER OPTIMIZATION SOLAR EDGE P300 PO1-28 28 PIECES 1 SOLAR EDGE P300 OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE) DISCONNECT SQUARE D D222NRB SW1 1 PIECE 1 SQUARE D D222NRB DISCONNECT SWITCH, 2-POLE, 60A, 240VAC, OR EQUIVALENT WIRING GEN-6AWG-BARE-CU HDWR1 98 FEET 1 6 AWG BARE, COPPER (MODULE/RACKING EGC) WIRING GEN-10-AWG-PV-WIRE-CU WR1 80 FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE) WIRING GEN-6-AWG-BARE-CU WR1 40 FEET 1 6 AWG BARE, COPPER (GROUND) WIRING GEN-10-AWG-THWN-2-CU-GR WR2 90 FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND) WIRING GEN-10-AWG-THWN-2-CU-RD WR2 90 FEET 1 10 AWG THWN-2, COPPER, RED (POSITIVE) WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 90 FEET 1 10 AWG THWN-2, COPPER, BLACK (NEGATIVE) WIRING GEN-8-AWG-THWN-2-CU-GR WR3-4 25 FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND) WIRING GEN-8-AWG-THWN-2-CU-BLK WR3-4 25 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 1) WIRING GEN-10-AWG-THWN-2-CU-WH WR3-4 25 FEET 1 10 AWG THWN-2, COPPER, WHITE (NEUTRAL) WIRING GEN-8-AWG-THWN-2-CU-RD WR3-4 25 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 2) WIREWAY GEN-JBOX JB1 1 PIECE 1 JUNCTION BOX WIREWAY GEN-EMT-0_75DIA WW1-3 70 FEET 1 EMT CONDUIT, 0.75 DIA. OCPD GEN-FU-40A-250VAC F1-2 2 PIECES 1 FUSE, 40A, 250VAC CONTRACTOR UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. EXAMPLE RESIDENCE 02 I1 G NEC ELECTRICAL CALCULATIONS FOR CONDUCTORS G L1 L2 N 03 F1-2 4 60A SW1 PHONE: 111-000-1111 LIC. No.: 000000 G 3 EXAMPLE 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 2 BILL OF MATERIALS NEW PV SYSTEM: 7.98 kWp 14 14 IN BRANCH IN BRANCH ID TYPICAL DESCRIPTION CONDUCTOR CONDUIT NO. OF CONDUCTORS IN CONDUIT CONDUIT FILL PERCENT RATED AMPS OCPD 1 2 DC CIRCUIT: SERIES STRING OUTPUT TO JUNCTION BOX 10 AWG PV WIRE, COPPER FREE AIR N/A N/A 15.0A 2 2 DC CIRCUIT (TRANSITIONED): JUNCTION BOX TO INVERTER 10 AWG THWN-2, COPPER 0.75" DIA. EMT 4 23.8% 15.0A 3 1 INVERTER OUTPUT: INVERTER TO UTILITY DISCONNECT 8 AWG THWN-2, COPPER 0.75" DIA. EMT 3 24.6% 4 1 UTILITY DISCONNECT OUTPUT: UTILITY DISCONNECT TO POINT OF CONNECTION 8 AWG THWN-2, COPPER 0.75" DIA. EMT 3 24.6% EGC TEMP. CORR. FACTOR FILL ADJ. FACTOR CONT. CURRENT MAX. CURRENT (125%) BASE AMP. COU AMP. N/A 6 AWG BARE, COPPER 0.58 (66°C) 1.0 15A 18.75A 55A 31.9A N/A 10 AWG THWN-2, COPPER 0.76 (55°C) 0.8 15A 18.75A 40A 24.32A 32.0A N/A 8 AWG THWN-2, COPPER 0.96 (33°C) 1.0 32A 40A 55A 52.8A 32.0A 40A 8 AWG THWN-2, COPPER 0.96 (33°C) 1.0 32A 40A 55A 52.8A ENGINEER OF RECORD G 04 N L2 MAIN 150 A L1 MAIN SERVICE PANEL 240/120 V 1Ø, 3W MAIN BUSS: 200 A UTILITY METER (N) 35 A/2P 5 N N L1 G (E) GROUNDING ELECTRODE 01 E-2 6 A THREE LINE DIAGRAM L2 DATE: TO UTILITY GRID (UG) GROUND ROD 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. (N) ELECTRICAL PLAN REVISIONS NTS B C D E F G H E-1 B A C D E F G H INVERTERS 1 REF. TYP. MAKE AND MODEL AC VOLTAGE MAX OCPD RATING RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1 1 SOLAR EDGE SE7600A-US 240V 40A 7680W 32A 23.5A 500V 97.5% !CAUTION! MODULES REF. TYP. MAKE AND MODEL PMAX PTC ISC IMP VOC VMP FUSE RATING PM1-28 28 SOLARWORLD SW 285 MONO 285W 255.8W 9.84A 9.2A 39.7V 31.3V 25A POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: 2 CONTRACTOR EXAMPLE PHONE: 111-000-1111 LIC. No.: 000000 DISCONNECTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. REF. TYP. MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE SW1 1 SQUARE D D222NRB OR EQUIV. 60A 240VAC REF. TYP. RATED CURRENT MAX VOLTAGE F1-2 2 40A 250VAC REF. TYP. MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX OPERATING VOLTAGE WEIGHTED EFFICIENCY PO1-28 28 SOLAR EDGE P300 300W 15A 12.5A 48V 0.988% EXAMPLE RESIDENCE MAIN DISTRIBUTION UTILITY DISCONNECT 3 POWER OPTIMIZERS PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION LABELING NOTES: OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC 1.1 LABELING REQUIREMENTS BASED ON THE 2011 SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS OF THIS [NEC 690.56(B)] 605.11, OSHA STANDARD 1910.145, ANSI Z535. PHOTOVOLTAIC SYSTEM ARE UNGROUNDED WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AND MAY BE ENERGIZED. OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE AUTHORITY HAVING JURISDICTION. INSTALLED AT EACH DC PV SYSTEM DISCONNECTING MEANS, AT 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO LABEL 1 EACH AC DISCONNECTING MEANS, AND AT THE MAIN SERVICE AT EACH JUNCTION, COMBINER, WITHSTAND THE ENVIRONMENT INVOLVED. DISCONNECTING MEANS SHOWING THE LOCATION OF ALL AC AND 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND DISCONNECT AND DEVICE WHERE ENERGIZED UNGROUNDED CONDUCTORS DC PV SYSTEM DISCONNECTING MEANS IN THE BUILDING. PERMANENTLY AFFIXED. [NEC 690.4(H)] MAY BE EXPOSED DURING SERVICE [NEC 690.35(F)] ! WARNING ! 4 ! WARNING ! OPERATING CURRENT: OPERATING VOLTAGE: MAX SHORT CURRENT: MAX VOLTAGE: ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.17] 11.4 A DC 350 V DC 15 A DC 500 V DC LABEL 3 AT EACH APPLICABLE DC DISCONNECTING MEANS [NEC 690.53] PHOTOVOLTAIC AC DISCONNECT OPERATING CURRENT: OPERATING VOLTAGE: 32 A AC 240 V AC LABEL 4 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] N W E PV ARRAY FRONT S DIRECTORY ! WARNING ! ! CAUTION ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED LABEL 5 LABEL 6 AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(D)(4)] PLAQUE ! WARNING ! LABEL 7 AT UTILITY METER [NEC 690.56(B)] PHOTOVOLTAIC DC DISCONNECT LABEL 8 AT EACH DC DISCONNECTING MEANS [NEC 690.14(C)(2)] 6 A B C D WARNING: PHOTOVOLTAIC POWER SOURCE LABEL 9 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(E)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] E PHOTOVOLTAIC AC DISCONNECT LABEL 10 AT EACH AC DISCONNECTING MEANS [NEC 690.14(C)(2)] F ENGINEER OF RECORD INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED NORTHEAST SIDE OF THE HOUSE 5 INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 BACK NEW PV SYSTEM: 7.98 kWp OCPDS INVERTER OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE DATE: 6.11.2015 DESIGN BY: J.G. LABEL 11 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(D)(7)] G PLACARDS CHECKED BY: M.M. REVISIONS H E-2 B C D SHEET KEYNOTES 3 G H D3 S-1 ROOF MATERIAL: (ASPHALT) SHINGLE ROOF STRUCTURE: TRUSS (WOOD) ATTACHMENT TYPE: L-FOOT WITH FLASHING (STANDARD) MODULE MANUFACTURER: SOLARWORLD MODULE MODEL: SW285 MONO MODULE LENGTH: 65.94" INCHES MODULE WIDTH: 39.41" INCHES MODULE WEIGHT: 39.5 LBS. SEE SHEET A-2 FOR DIMENSION(S) MIN. FIRE OFFSET: 3' OFFSETS FROM RIDGE RAFTER SPACING: 16" O.C. RAFTER SIZE: 2X8 LAG BOLT DIAMETER: 5/16" LAG BOLT EMBEDMENT: 4" TOTAL # OF ATTACHMENTS: 99 TOTAL AREA: 505.30 SQ. FT. TOTAL WEIGHT: 1315.25 LBS. WEIGHT PER ATTACHMENT: 13.29 LBS. DISTRIBUTED LOAD: 2.60 PSF. MAX. HORIZONTAL STANDOFF: 48" MAX. VERTICAL SPACING: 19 STANDOFF STAGGERING: YES RAIL MANUFACTURER: IRONRIDGE RAIL MODEL: XR100 RAIL WEIGHT: 0.68 PLF. MAX RAIL SPAN: USUALLY 48", BUT MAY VARY PER MARKET 4 5 8 20 D6 S-1 3 D7 S-1 D5 S-1 CONTRACTOR EXAMPLE 23 24 25 1 PHONE: 111-000-1111 2 11 D2 S-1 15 18 22 13 14 12 LIC. No.: 000000 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. RACKING DETAIL (LONGITUDINAL) SCALE: NOT TO SCALE RACKING DETAIL (TRANSVERSE) D1 S-1 SCALE: NOT TO SCALE 9 ROOF SLOPE 10 10 6 21 4 D5 S-1 D8 S-1 D9 S-1 7 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 2 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. F EXAMPLE RESIDENCE 1 E NEW PV SYSTEM: 7.98 kWp A DETAIL (LONGITUDINAL) SCALE: NOT TO SCALE ENGINEER OF RECORD (E) DOOR 26 (N)AC FUSED DISCONNECT D3 S-1 DETAIL (TRANSVERSE) D4 S-1 SCALE: NOT TO SCALE RACKING DETAIL (TOP) SCALE: NOT TO SCALE MODULE MODULE 5 (E)METER RACKING DETAILS RAIL END CLAMP NOT TO EXCEED 6' 7" FROM GRADE TO (E)MEP FROM (N) DC/AC INVERTER (GARAGE) TO (E)MEP (GARAGE) MID CLAMP MODULE DATE: DESIGN BY: J.G. (E)GRADE CHECKED BY: M.M. END CLAMP REVISIONS MID CLAMP 6 D6, D7 S-1 A DETAIL (LONGITUDINAL) D8, D9 S-1 SCALE: NOT TO SCALE B C 6.10.2015 D DETAIL (TOP) D10 S-1 SCALE: NOT TO SCALE E F EQUIPMENT ELEVATION SCALE: NOT TO SCALE G H S-1 A B C D E F G H 1 CONTRACTOR EXAMPLE PHONE: 111-000-1111 2 LIC. No.: 000000 EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 NEW PV SYSTEM: 7.98 kWp UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 4 ENGINEER OF RECORD 5 MODULE DATASHEET DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H D-1 A B C D E F G H 1 CONTRACTOR EXAMPLE PHONE: 111-000-1111 2 LIC. No.: 000000 EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 NEW PV SYSTEM: 7.98 kWp UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 4 ENGINEER OF RECORD 5 INVERTER DATASHEET DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H D-2 A B C D E F G H 1 CONTRACTOR EXAMPLE PHONE: 111-000-1111 2 LIC. No.: 000000 EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 NEW PV SYSTEM: 7.98 kWp UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 4 ENGINEER OF RECORD 5 RACKING DATASHEET DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H D-3 A B C D E F G H 1 CONTRACTOR EXAMPLE PHONE: 111-000-1111 2 LIC. No.: 000000 EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 NEW PV SYSTEM: 7.98 kWp UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 4 ENGINEER OF RECORD 5 RACKING MOUNT DATASHEET DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H D-4 A B C D E F G H 1 CONTRACTOR EXAMPLE PHONE: 111-000-1111 2 LIC. No.: 000000 EXAMPLE RESIDENCE 3 10 EXAMPLE ST EXAMPLE, NY 11111 APN# 00000000 NEW PV SYSTEM: 7.98 kWp UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. 4 ENGINEER OF RECORD 5 POWER OPTIMISER DATASHEET DATE: 6.11.2015 DESIGN BY: J.G. CHECKED BY: M.M. REVISIONS 6 A B C D E F G H D-5