Chemistry Building Generator Auburn University Engineer Project No.: 11028 Auburn Project No.: 06-140 16450 GROUNDING SYSTEM 1.0 GENERAL 1.01 SUMMARY A. The General Provisions, Supplemental General Provisions, section 16010, and Special Provisions apply to all Work specified in this Section. B. This Section describes the materials and methods required to provide a complete grounding system. Comply with other Division 16 Sections and Drawings as applicable. C. Furnish and install all equipment, materials, tools, and labor to provide a complete grounding system. D. Ground all metallic parts of the electrical system which are not intended to carry current such as conduit, panelboards, cabinets and enclosures, etc., in accordance with the NEC and applicable codes. E. In non-metallic conduits, maintain continuity of equipment grounding by installing an insulated grounding conductor and connected by an acceptable method. 2.0 PRODUCTS 2.01 GENERAL A. All equipment and materials provided under this Section of the Specifications shall be new; UL listed, and bear the UL label. B. All panel boards, etc. shall be provided with a copper equipment ground bar bolted, brazed, or riveted to the associated enclosure or cabinet. C. All conduit, raceways, junction boxes, pull boxes, etc. shall be made electrically continuous by means of grounding conductors, bonding jumpers, grounding bushings, etc. as required by the NEC and the authorities having jurisdiction. D. Refer to other Sections for additional grounding requirements. 2.02 GROUNDING CONDUCTORS A. All grounding electrode conductors shall be bare or green insulated copper conductors sized per the NEC, unless noted on the Drawings. Where the authorities having jurisdiction or local code requires grounding electrode GROUNDING SYSTEM 16450 - 1 Chemistry Building Generator Auburn University Engineer Project No.: 11028 Auburn Project No.: 06-140 conductor sizing in excess of that shown on the Drawings or specified herein, the larger size conductor shall be installed. B. All equipment grounding conductors shall be green insulated copper conductors sized as indicated on the Drawings. Where the authorities having jurisdiction or local code requires equipment grounding conductor sizing in excess of that shown on the Drawings or specified herein, the larger size conductor shall be installed. C. All bonding conductors shall be flexible copper bonding jumpers sized in accordance with the NEC for grounding electrode conductors. 2.03 GROUND RODS A. All ground rods shall be a minimum of ¾” x 10’-0” copper clad steel unless otherwise indicated on the Drawings. 3.0 EXECUTION 3.01 INSTALLATION A. Bonding and grounding conductors shall be sized, shall be run in conduit, and shall be connected to various services in accordance with the requirements of the authorities having jurisdiction and the NEC. B. Provide grounding system for the generator as a separately derived system per the NEC. See the drawings for more information. C. Provide exothermic type chemical welded type connectors (Cadweld or approved equal) for the joining of conductors to ground rods, grounding plates, external ground bars and splicing. Provide compression and bolted type connectors for the joining of grounding electrode conductors to the ground bars. D. Provide a separate green-insulated equipment grounding conductor, with insulation of the same rating as the phase conductors, for all feeders and branch circuits. Install the grounding conductors in the raceway with related phase and neutral conductors. Where parallel conductors in separate raceways occur, provide a grounding conductor in each raceway. Connect all grounding conductors to ground terminals at each end of the run so that there will be no uninterrupted grounding circuit from the point of ground fault back to a point of connection of the equipment ground and system neutral. E. Provide grounding bushings on all raceways terminating within all electrical enclosures. Provide grounding conductors from such bushings to the frame of the enclosure, ground bus and equipment grounding strap where one occurs. F. Assure the electrical continuity of all metallic raceway systems, pulling up all conduits and/or locknuts wrench-tight. Where expansion joints or telescoping GROUNDING SYSTEM 16450 - 2 Chemistry Building Generator Auburn University Engineer Project No.: 11028 Auburn Project No.: 06-140 joints occur, provide bonding jumpers. Wherever flexible metallic conduit is employed, provide a green insulated ground jumper installed in the flexible conduit. 3.02 TESTS A. Provide ground continuity tests at all panel boards, distribution panels, transfer switch equipment. END OF SECTION GROUNDING SYSTEM 16450 - 3