Bulletin 550-126 dated 2015 15 kV Wall

advertisement
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Elliott air-insulated bushings
accept IEEE Standard
inserts and elbows
Kinked roof prevents
standing moisture
Removable lift
provisions with
blind holes for
tamper resistance
Glass reinforced
barriers meet
NEMA GPO-3
Standards
550-126
Page 1
2015
Tamper-Resistant Enclosure
meets National and Regional
Enclosure Integrity Standards and
virtually eliminates the entrance of
airborne contamination to reduce
maintenance
Superlife Finish
Includes phosphatizing,
rust-inhibiting epoxy primer
and Pad-Mount Green
(Munsell 7GY 3.29/1.5)
polyurethane top coat over 5 mils dry
Clear polycarbonate door
safety barrier.
Safety latches on the door
safety barrier are insulating
and require a positive
action to remove the
safety barrier. Barrier lift
handles are insulating and
keyed to prevent rotation
0.625" diameter
copper ground bar
Stainless steel hinges are
welded to the door and the
enclosure – 0.375” pins
are standard
Coordinated padlock and
penta-head or optional
hex-head (top and bottom)
provides bolted door security
with visual confirmation by
supervisory personnel.
Security bolt is made captive
with a stainless steel washer
compressed to an oval shape
to severely discourage removal.
Overlapping door and
enclosure flanges - with
other features - provide
tamper resistance to meet
national and regional
standards
Corrosion proof nameplate
is located to provide easy
access for the operator
Heavy duty 11-gauge steel
enclosure is all welded
construction for long life
“In-Air” Insulation
eliminates leaking or
contamination of
insulating medium for
long trouble-free
operation
“In-Air” Visibility
allows visual inspection
of all components without
the inconvenience or
expense associated with
equipment which must be
de-energized for inspection
Bulletin
Ground lugs accept
#6 - #2/0 ground cable
"Danger - Bushings
May Be Energized"
Door-holder rods are stainless
steel and hold the door open
100 degrees or 140 degrees
Ground lugs accept
#6 - #2/0 ground cable
Parking stands are unpainted stainless
steel and provide space and grounding
for feed-thru and other portable devices
ENCLOSURE OPTIONS:
1) 0.125” #5052H32 Aluminum
2) 12-gauge #304L Stainless Steel
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 2
2015
Three-Phase - Two Ways Per Phase
600 Amp 15 kV S&C #255222-S5 Mini-Rupter® Switch
8.3/14.4 kV Grounded Wye Max Design
95 kV BIL
600 Amp 15-kV S&C #255222-G3-S5
Mini-Rupter® Switch with non-removable
handle located on right side, padlockable
handle in "Open" or "Close" position, provisions for key interlock are standard
Standard Paint: "Pad-Mount Green"
Munsell #7GY3.29/1.5
Optional Paint: "Grey"
Munsell #5BG7.0/0.4
Option G1: Ground studs at main
contact of switch
Option G2: Ground studs at hinge
end of switch
Option K: Key interlock
11-Gauge Steel Enclosure
Stainless Steel Hinges
Provisions for padlock and stainless steel
penta-head (or hex-head) bolt
Clear polycarbonate door safety barrier standard
6" Min. Strike Distance to Ground
8" Min. Strike Distance Phase-to-Phase
Catalog Number
Top View Bushings
Operating Handle
EWMRG-15-311S-E2TB-RHMR
200 Amp Bushing Wells
Top and Bottom
Right Side (Shown Above)
EWMRG-15-311S-E2TB-LHMR
200 Amp Bushing Wells
Top and Bottom
Left Side (Opposite Hand)
EWMRG-15-311S-E6T/E2B-RHMR
600 Amp Bushings - Top
200 Amp Bushing Wells - Bottom
Right Side (Shown Above)
EWMRG-15-311S-E6T/E2B-LHMR
600 Amp Bushings - Top
200 Amp Bushing Wells - Bottom
Left Side (Opposite Hand)
EWMRG-15-311S-E6TB-RHMR
600 Amp Bushings
Top and Bottom
Right Side (Shown Above)
EWMRG-15-311S-E6TB-LHMR
600 Amp Bushings
Top and Bottom
Left Side (Opposite Hand)
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 3
2015
Three-Phase - Two Ways Per Phase
600 Amp 15 kV S&C #255222-S5 Mini-Rupter® Switch
8.3/14.4 kV Grounded Wye Max Design
95 kV BIL
600 Amp 15-kV S&C #255222-G3-S5
Mini-Rupter® Switch with non-removable
handle located on right side, padlockable
handle in "Open" or "Close" position,
provisions for key interlock are standard
Standard Paint: "Pad-Mount Green"
Munsell #7GY3.29/1.5
Optional Paint: "Grey"
Munsell #5BG7.0/0.4
Option G1: Ground studs at main
contact of switch
Option G2: Ground studs at hinge
end of switch
Option K: Key interlock
11-Gauge Steel Enclosure
Stainless Steel Hinges
Provisions for padlock and stainless steel
penta-head (or hex-head) bolt
Clear polycarbonate door safety barrier standard
6" Min. Strike Distance to Ground
8" Min. Strike Distance Phase-to-Phase
Catalog Number
Top View
Bushings
Operating Handle
EWMRG-15-311S-E2FB-RHMR
200 Amp Bushing Wells
Front and Bottom
Right Side (Shown Above)
EWMRG-15-311S-E2FB-LHMR
200 Amp Bushing Wells
Front and Bottom
Left Side (Opposite Hand)
EWMRG-15-311S-E6F/E2B-RHMR
600 Amp Bushings - Front
200 Amp Bushing Wells - Bottom
Right Side (Shown Above)
EWMRG-15-311S-E6F/E2B-LHMR
600 Amp Bushings - Front
200 Amp Bushing Wells - Bottom
Left Side (Opposite Hand)
EWMRG-15-311S-E6FB-RHMR
600 Amp Bushings
Front and Bottom
Right Side (Shown Above)
EWMRG-15-311S-E6FB-LHMR
600 Amp Bushings
Front and Bottom
Left Side (Opposite Hand)
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Bulletin
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
550-126
Page 4
600 Amp S&C Mini-Rupter Switch
®
2015
Three-Phase - Two Ways Per Phase
600 Amp 15 kV S&C #255222-S5 Mini-Rupter® Switch
8.3/14.4 kV Grounded Wye Max Design
95 kV BIL
600 Amp 15-kV S&C #255222-G3-S5
Mini-Rupter® Switch with non-removable
handle located on right side, padlockable
handle in "Open" or "Close" position, provisions for key interlock are standard
Standard Paint: "Pad-Mount Green"
Munsell #7GY3.29/1.5
Optional Paint: "Grey"
Munsell #5BG7.0/0.4
Option G1: Ground studs at main
contact of switch
Option G2: Ground studs at hinge
end of switch
Option K: Key interlock
11-Gauge Steel Enclosure
Stainless Steel Hinges
Provisions for padlock and stainless steel
penta-head (or hex-head) bolt
Clear polycarbonate door safety barrier standard
6" Min. Strike Distance to Ground
8" Min. Strike Distance Phase-to-Phase
Catalog Number
Bushings
Operating Handle
EWMRG-15-311S-EL6T/E2B-RHMR
600 Amp Live Terminal Thru-Bushings - Top
200 Amp Bushing Wells - Bottom
Right Side (Shown Above)
EWMRG-15-311S-EL6T/E2B-LHMR
600 Amp Live Terminal Thru-Bushings - Top
200 Amp Bushing Wells - Bottom
Left Side (Opposite Hand)
EWMRG-15-311S-EL6T/E2B-RHMR
600 Amp Live Terminal Thru-Bushings - Top
600 Amp Bushing Wells - Bottom
Right Side (Shown Above)
EWMRG-15-311S-EL6T/E2B-LHMR
600 Amp Live Terminal Thru-Bushings - Top
600 Amp Bushing Wells - Bottom
Left Side (Opposite Hand)
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 5
2015
Elliott Floor Support Frame For Wall-Mount Enclosure
Provides Additional Support When Wall Structure
Is Inadequate or Questionable
11-Gauge Steel
Standard Paint: "Pad-Mount Green"
Munsell #GY3.29/1.5
Option Paint: "Grey"
Munsell #5BG7.0/0.4
Catalog Number
Dimension “A”
EFSF-18-3905-33.5
EFSF-24-3905-33.5
EFSF-30-3905-33.5
EFSF-36-3905-33.5
EFSF-42-3905-33.5
18”
24”
30”
36”
42”
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 6
2015
Typical Specification - Page 1 of 3
General
The switchgear shall be 15 kV Class, 95 kV BIL, 600
ampere continuous current, suitable for use on 8.3/14.4 kV
grounded wye max design systems. The enclosure shall be
designed for wall mounting and shall include provisions to
accept a floor support frame that may be specified when a
wall structure is questionable or inadequate to support the
switchgear. The switchgear shall be constructed for
connection to the utility system with noninsulated two-hole
NEMA Standard connectors and/or separable insulated
connectors as described in IEEE Standard 386—latest revision
(separable insulated connectors [and loadbreak inserts when
required] shall be supplied by the user). The switchgear shall
be designed for and contain a three-pole, group-operated
interrupter switch that includes an external nonremovable
side-mounted operating handle. The operating handle shall
be padlockable in the open or the closed position and shall
include provisions for key interlocks. A door safety barrier
shall be provided inside the door on the switch compartment
as recommended in IEEE Standard C2 (National Electrical
Safety Code) Rule 381G. Tamper resistance shall meet the
Enclosure Security requirements of IEEE Standard C57.12.28
(Pad-Mounted Equipment—Enclosure Integrity). Together,
the tamper resistance and the door safety barrier shall resist
unauthorized entry, protect authorized and unauthorized
persons, and provide positive safety features when installed
in areas accessible to the general public. The switchgear shall
be constructed for indoor/outdoor installation in areas subject
to precipitation and in areas with windblown contamination.
The equipment shall be “air-insulated” and completely
assembled prior to shipment.
Enclosure Construction
The enclosure shall be tamper-resistant, all-welded
construction utilizing 11-gauge minimum sheet steel. Single
and double 90-degree bends shall be used as necessary
to assure strength and rigidity. The enclosure top shall be
cross-kinked to provide watershed and rigidity. The switch
compartment access door shall be furnished with a stainless
steel door holder that will latch the door open 100 degrees
and 140 degrees and resist accidental closing. The door
shall be provided with provisions for padlocking and a
recessed penta-head (or hex-head) security bolt to prevent
unauthorized entry (coordinated to prevent installation of
the padlock until the security bolt is tightened when closing
the door(s) and to prevent a wrench from operating the
security bolt until the padlock is removed when opening
the door(s)). The security bolt shall be made captive with
a stainless steel washer compressed to an oval shape to
severely discourage removal. Hinges shall be stainless steel
(with stainless steel pins not less than 0.3125-inch diameter)
and shall be welded to both the enclosure and the door to
maintain door alignment for the life of the equipment. The
enclosure shall be nonventilated to minimize the entrance
of airborne contamination, insects, rodents or reptiles. The
protective finish shall include necessary grinding, cleaning
and phosphatizing, two-component rust-inhibiting epoxy
primer and a Pad-Mount Green two-component polyurethane
top coat finish—Munsell color 7GY 3.29/1.5 (or Optional
Grey—Munsell color 5BG 7.0/0.4). The primer and top
coat shall be electronically monitored during application to
insure proper ratio and mixing of each component. Total
average thickness of paint (after curing) shall be not less
than 5 mils. The protective coating shall meet the Enclosure
Coating System requirements of IEEE Standard C57.12.28
(Pad-Mounted Equipment—Enclosure Integrity). Removable
lift provisions, adequate to withstand handling with normal
utility equipment, shall be provided on the outside of the
enclosure. Threaded openings for lift provision bolts shall be
blind holes to prevent the entrance of wire or other foreign
objects into the enclosure when lift provisions are removed.
Four threaded openings for attachment of a floor
support frame (to provide additional support when a wall
structure is questionable or inadequate) shall be provided
on the bottom of the enclosure. The threaded openings
shall be blind holes and shall be unpainted internally to
provide a ground for the floor support frame that may be
installed. When specified, an 18-inch (alternate 24-inch,
30-inch, 36-inch or 42-inch) high floor support frame shall
be supplied bolted in place with stainless steel hardware.
The floor support frame shall be all-welded construction
utilizing 11-gauge minimum sheet steel formed to assure
strength and rigidity. The two ground lugs specified for the
bottom of the enclosure shall be installed on the floor support
frame not more than 6 inches from the original location. The
protective coating of the floor support frame shall meet or
exceed the coating requirements specified above for the
enclosure.
Bushings and Terminals
Alternate 1: Bushings shall be 200 ampere Elliott
#1101-225B, 25 kV class (15.2 kV to ground) Air-Insulated
Bushing Wells, 125 kV BIL, per IEEE Standard 386 Fig. 3
(200 A Bushing Well Interface, 8.3 kV, 15.2 kV and 21.1 kV)
for use with either 8.3/14.4 kV or 15.2/26.3 kV separable
insulated connectors (Elastimold®, Eaton's Cooper Power
Systems or other approved equal). The bushing wells shall
be pressure-molded cycloaliphatic epoxy with a 0.75-inch
diameter copper conductor on the “air-insulated” side
that is drilled and tapped 0.375-inch – 16UNC x 1-inch deep
to provide direct connection of the bus and/or live parts.
Leakage distance from the apparatus connection end of the
bushing well to ground shall be not less than 30 inches to
assure trouble-free operation in a wet and/or contaminated
environment. Integral shielding shall be provided to
eliminate partial discharge caused by off-center mounting
and mounting holes that may have sharp edges or burrs.
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 7
2015
Typical Specification - Page 2 of 3
Bushing wells shall mount in a 3.125-inch diameter opening
and bolt in place to allow field replacement with standard
tools. The bushing well mounting bolts shall be self-locking
stainless steel serrated-flange hex-head bolts that “cut”
through the enclosure protective finish to ground the integral
shielding of each bushing well. The head of one or more
of the mounting bolts for each bushing well shall include a
0.156-inch diameter hole to provide a connection to ground for
the loadbreak insert shielding ground wire as recommended
by separable insulated connector manufacturers. To assure
adequate strength for apparatus support, the bushing well
shall withstand a minimum cantilever loading of 600 pounds
for five minutes without damage. The bushing well interface
shall be free of all voids, holes and heat sinks to assure
proper mating with separable insulated connectors. Each
bushing well shall be tested in free air, mounted in a grounded
steel plate not less than 10 inches x 10 inches, with a bushing
well plug (Eaton's Cooper Power Systems #IBWP225 or
equal) installed in the well interface to accurately simulate
operating conditions (gas or liquid dielectric in the interface
shall not be acceptable for this test). Each bushing well shall
meet the requirements for 25 kV devices in accordance with
IEEE Standard 386 (latest revision), including 100 percent
production testing.
Alternate 2: Bushings shall be 600 ampere Elliott
#1201-625B2, 25 kV class (15.2 kV to ground) Air-Insulated
Bushings, 125 kV BIL, per IEEE Standard 386 Fig. 11 (600 A
Deadbreak Interface No. 1, 8.3 kV and 15.2 kV) for use with
either 8.3/14.4 kV or 15.2/26.3 kV separable insulated
connectors (Elastimold®, Eaton's Cooper Power Systems or
other approved equal). The bushings shall be pressure-molded
cycloaliphatic epoxy with a 1.25-inch diameter tin-plated
aluminum conductor on the “air-insulated” side that is drilled
and tapped 0.625-inch – 11UNC x 1-inch deep to provide
direct connection of the bus and/or live parts. Leakage
distance from the apparatus connection end of the bushing
to ground shall be not less than 30 inches to assure troublefree operation in a wet and/or contaminated environment.
Integral shielding shall be provided to eliminate partial
discharge caused by off-center mounting and mounting holes
that may have sharp edges or burrs. Bushings shall mount
in a 3.125-inch diameter opening and bolt in place to allow
field replacement with standard tools. The bushing mounting
bolts shall be self-locking stainless steel serrated-flange
hex-head bolts that “cut” through the enclosure protective
finish to ground the integral shielding of each bushing. To
assure adequate strength for apparatus support, the bushing
shall withstand a minimum cantilever loading of 600 pounds
for five minutes without damage. The bushing interface shall
be free of all voids, holes and heat sinks to assure proper
mating with separable insulated connectors. Each bushing
shall be tested in free air, mounted in a grounded steel
plate not less than 10 inches x 10 inches, with an insulated
protective cap (Eaton's Cooper Power Systems #DPC625
or equal) installed on the interface to accurately simulate
operating conditions (gas or liquid dielectric on the interface
shall not be acceptable for this test). Each bushing shall meet
the requirements for 25 kV devices in accordance with the
test values of IEEE Standard 386 (latest revision), including
100 percent production testing.
Alternate 3: Bushings shall be 600 ampere Elliott
#1351-615TB, 15 kV class (8.3 kV to ground) Air-Insulated
Live-Terminal Thru-Bushings, 95 kV BIL, for use with
8.3/14.4 kV systems. The bushings shall be pressure-molded
cycloaliphatic epoxy with a 1.25-inch diameter tin-plated
aluminum conductor that is drilled and tapped 0.625-inch –
11UNC x 1-inch deep on both ends to provide for connection
of the bus and/or live parts. The end of the bushing that
is external to the enclosure shall be provided with a copper
two-hole NEMA Standard terminal for connection to the
utility electrical system. Integral shielding shall be provided
to eliminate partial discharge caused by off-center mounting
and mounting holes that may have sharp edges or burrs.
Bushings shall mount in a 3.125-inch diameter opening and
bolt in place to allow field replacement with standard tools.
The bushing mounting bolts shall be self-locking stainless
steel serrated-flange hex-head bolts that “cut” through the
enclosure protective finish to ground the integral shielding of
each bushing. To assure adequate strength for apparatus
support, the bushing shall withstand a minimum cantilever
loading of 500 pounds for five minutes without damage. Each
bushing shall be tested in free air, mounted in a grounded
steel plate not less than 10 inches x 10 inches and shall meet
the requirements for 15 kV devices in accordance with the
test values of IEEE Standard 386 (latest revision), including
100 percent production testing.
Interrupter Switch
The three-pole, group-operated interrupter switch shall
be S&C 15 kV class, 95 kV BIL, 600 amp Mini-Rupter®
that includes an external nonremovable side-mounted (or
front-mounted) operating handle. The interrupter switch
shall include a quick-make quick-break mechanism that
will quickly and positively open and close the switch
blades independent of the switch-operating hub speed. An
arc-chute shall be provided for each switched pole and circuit
interruption shall take place within the arc-chute. Any exhaust
from the arc-chute shall be vented in a controlled manner.
The interrupter switch and other electrical components shall be
“air-insulated” and positioned to allow visual inspection of the
switch position and all internal connections and components
without removing the clear-polycarbonate door safety barrier,
de-energizing or removing the equipment from service.
The operating handle shall be padlockable in the open or the
close position. When Option G1 is specified, ground studs
shall be provided for each terminal at the main contact end
of the interrupter switch. When Option G2 is specified,
ground studs shall be provided for each terminal at the hinge
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
15-kV Wall-Mount Switchgear
Three-Phase Indoor/Outdoor
600 Amp S&C Mini-Rupter Switch
®
Bulletin
550-126
Page 8
2015
Typical Specification - Page 3 of 3
end of the interrupter switch. When Option K is specified,
key interlocks shall be provided that require operations in a
given sequence.
Bus
Bus shall be copper with all burrs and sharp corners
removed prior to installation. Positive pressure shall be
assured by use of stainless steel fasteners and lock washers
at all connection points. All connections shall provide direct
contact of current-carrying parts and shall not depend on
current transfer through fastener thread-to-thread contact.
Electrical components shall be “air-insulated” and positioned
to allow visual inspection of all internal connections and
components without removing the clear-polycarbonate door
safety barrier, de-energizing or removing the equipment from
service.
Barriers
Phase and ground barriers shall be provided to assure
correct phase-to-phase and phase-to-ground clearances for
proper operation at rated voltage. These barriers shall be
glass-reinforced polyester (NEMA GPO-3 class material)
not less than 0.1875-inch thick.
A removable insulating barrier with a “DANGER – Keep
Out! – Hazardous voltage” sign, Elliott #7203-D2003-309,
shall be located inside the door(s) on the fuse compartment
as recommended in Rule 381G of IEEE Standard C2
(National Electrical Safety Code). This door safety barrier
shall be constructed of 0.25-inch clear-polycarbonate
(Lexan or equal) and shall completely close the door opening
and be provided with a nonconductive safety latch requiring
a positive action to remove the barrier. Handles and other
hardware extending through this door safety barrier shall be
nonconductive material. Handles shall be keyed to prevent
rotation for secure handling. Complete visual inspection of
the internal components shall be possible without removing
the door safety barrier.
Grounding Provisions
Four high-conductivity bronze eyebolt-type ground
lugs, which accept #6 through #2/0 copper conductor, shall
be installed on the enclosure (two on the exterior of the top
and two on the exterior of the bottom). One 0.625-inch
diameter copper grounding bar that bolts to both walls inside
the enclosure shall be provided near the bottom of the door
opening in a position easily accessible for attachment of
grounding clamps. When grounding clamps are installed it
shall be possible to close and lock the door.
Accessory Equipment
Stainless steel parking stands shall be provided in the
quantity required to allow use of feed-thru bushings, parking
bushings and grounding bushings. The parking stands shall
be welded in place, in a position to allow the use of hot-line
tools for installation of feed-thru bushings, etc. The parking
stands shall be unpainted (except welds shall be painted) to
provide a ground for feed-thru bushings and other devices
that may be placed into the parking stands.
A corrosion proof nameplate with permanent thermal
transfer printing shall be installed inside the compartment door.
It shall be located at the top corner farthest from the enclosure
when the door is open. The nameplate will provide Type of
Equipment, Model Number, Amps Continuous, kV Maximum,
BIL, Serial Number, Job Number, Date Manufactured and
Weight of Equipment.
The enclosure shall be labeled in near proximity of the
locking provisions with a pressure-sensitive vinyl label using
letters not less than 0.375-inch nor more than 0.625-inch
high. The label shall indicate the type of equipment behind
the access (switch, fuses, bus, etc.).
Packaging
Each switchgear shall be bolted to a solid-top wood pallet
to prevent hidden damage. The equipment shall be wrapped
with 0.125-inch thick polyethylene foam or other suitable
material to minimize damage to the finish during shipment.
Drawings
When specified, drawings shall be furnished for each
switchgear that include:
1) enclosure dimensions and location of components.
2) proposed labels and location of labels.
If you do not find the design you need
PLEASE CONTACT
our REPRESENTATIVE or the FACTORY
Mini-Rupter® is a registered trademark of S&C Electric Company.
Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com