Hard Rock Lobby Renovation Drawings

advertisement
PLC
HARD ROCK LOBBY RENOVATION
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
4"
N
EST C
I R CL
E
2"
400' - 0"
1"
200' - 0"
HWY 412
3"
600' - 0"
PROJECT LOCATION ON SITE
800' - 0"
REVISIONS
TI M B
E RC R
1" = 200'
0'
0"
Consultants
DOOR CLEARANCES - REF. 2010 ADA STANDARDS 404.2.4.1
ARCHITECTURE
A101
FLOOR PLAN & DEMOLITION PLAN
A102
DIMENSION PLAN & ENLARGED PLANS
A130
REFLECTED CEILING PLAN
AI601
INTERIOR FLR PLAN, DOORS & WINDOWS
INTERIORS
AI600
SCHEDULES & DETAILS
AI610
INTERIOR ELEVATIONS
PLUMBING
FP100
FIRE PROTECTION PLAN
PD100
PLUMBING DEMO PLAN
MECHANICAL
M000
MECHANICAL NOTES, SCHEDULES, DETAILS & LEGEND
MD100 MECHANICAL DEMO PLAN
M100
MECHANICAL HVAC PLAN
ELECTRICAL
E000
ELECTRICAL NOTES, SCHEDULES AND LEGEND
E101
POWER PLANS
E102
TEMPORARY ELECTRICAL PLANS
E201
LIGHTING PLANS
E301
SYSTEMS PLAN
E401
ELECTRICAL SCHEDULES
E402
ELECTRICAL SCHEDULES AND DETAILS
Grand total: 20
D
AB
A/C
ACP
AT
AD
ADH
ADJ
AFF
AL
ALT
AMB
ANSI
ANCHOR BOLT
AIR CONDITIONING
ACOUSTICAL PANEL
ACOUSTICAL TILE
AREA DRAIN
ADHESIVE
ADJUSTABLE
ABOVE FINISH FLOOR
ALUMINUM
ALTERNATE
AMBULATORY
AMERICAN NATIONAL
STANDARDS INSTITUTE
AP
ACCESS PANEL
APPROX APPROXIMATE
ARCH
ARCHITECT(URAL)
ASPH
ASPHALT
AUTO
AUTOMATIC
D
DBL
DEG
DEMO
DF
DH
DIA
DIAG
DIM
DIV
DL
DN
DP
DR
DS
DWG
DWR
B
E
BBD
BD
BIT
BLDG
BLKG
BM
BRG
BTB
BUR
BULLETIN BOARDS
BOARD
BITUMINOUS
BUILDING
BLOCKING
BENCH MARK, BEAM
BEARING
BACK TO BACK
BUILT-UP ROOFING
C
CA
CAB
CB
CBB
CF
CFM
CG
CHBD
CI
CIP
CJ
CL
CLG
CLR
CM
CMU
COL
CONC
CONF
CONST
CONT
CORR
CSMT
CT
CY
CARPET/ CARPETING
CABINET
CATCH BASIN
CEMENTITIOUS BACKING BOARD
CUBIC FEET
CUBIC FEET PER MINUTE
CORNER GUARD
CHALKBOARD
CAST IRON
CAST IN PLACE
CONTROL JOINT
CENTERLINE
CEILING
CLEAR(ANCE)
CONSTRUCTION MANAGER
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONFERENCE
CONSTRUCTION
CONTINUOUS
CORRIDOR
CASEMENT
CERAMIC TILE
CUBIC YARD
E
EB
EHD
EIFS
EJ
EL
ELEC
ELEV
ENGR
EQ
EQUIP
ES
EW
EWC
EXH
EXP
EXT
EXIST
DRAIN
DOUBLE
DEGREES
DEMOLISH, DEMOLITION
DRINKING FOUNTAIN
DOUBLE HUNG
DIAMETER
DIAGONAL
DIMENSION
DIVISION
DEAD LOAD
DOWN
DAMPPROOFING
DOOR
DOWNSPOUT
DRAWING
DRAWER
EAST
EXPANSION BOLT
ELECTRIC HAIR DRYER
EXTERIOR INSULATION
FINISH SYSTEM
EXPANSION JOINT
ELEVATION
ELECTRIC(AL)
ELEVATOR
ENGINEER
EQUAL
EQUIPMENT
EACH SIDE
EACH WAY
ELECTRIC WATER COOLER
EXHAUST
EXPOSED
EXTERIOR
EXISTING
F
FA
FBO
FB
FD
FE
FEC
FF
FFE
FFL
FHC
FL
FOC
FOF
FOM
FOS
FP
FRGWB
FIRE ALARM
FURNISHED BY OWNER
FACE BRICK
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FACTORY FINISH
FINISH FLOOR ELEVATION
FINISH FLOOR LINE
FIRE HOSE CABINET
FLOOR/ FLOORING
FACE OF CONCRETE
FACE OF FINISH
FACE OF MASONRY
FACE OF STUDS
FIREPROOF
FIRE RATED GYPSUM WALL BOARD
FRT
FSR
FT
FTG
FUR
FIRE RETARDANT TREATED
FLEXIBLE SHEET ROOFING
FOOT/ FEET
FOOTING
FURRING
G
GA
GALV
GB
GCMU
GD
GL
GST
GRNBD
GWB
GYP
GAUGE
GALVANIZED
GRAB BAR
GLAZED CONCRETE MASONRY UNIT
GRADE
GLASS
GLAZED STRUCTURAL UNIT
GREEN BOARD
GYPSUM WALL BOARD
GYPSUM
H
HB
H/C
HC
HD
HDR
HDW
HK
HM
HORZ
HP
HR
HT
HVAC
HOSE BIBB
HANDICAPPED
HOLLOW CORE
HEAVY DUTY
HEADER
HARDWARE
HOOK
HOLLOW METAL
HORIZONTAL
HORSEPOWER
HOUR
HEIGHT
HEATING, VENTILATING,
AIR CONDITIONING
I
INSUL
INT
INSULATION
INTERIOR
J
JAN
JB
JOH
JOW
JANITOR'S CLOSET
JUNCTION BOX
JAMB OPENING HEIGHT
JAMB OPENING WIDTH
K
KD
KG
KIT
KO
KVA
KW
KNOCKDOWN
KILOGRAM
KITCHEN
KNOCKOUT
KILOVOLT AMPERES
KILOWATTS
L
L
LAM
LAV
LBS
LL
LENGTH
LAMINATE(D)
LAVATORY
POUNDS
LIVE LOAD
LLH
LLV
LVR
L/W
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LOUVER
LIGHTWEIGHT
M
M
MAINT
MAX
MBR
MC
MECH
MEZZ
MFR
MH
MIN
MI
MISC
MKBD
MLDG
MM
MO
MPU
MR
MTG
MTL
MULL
N
N
NE
NIC
NOM
NTS
NW
NPS
NORTH
NORTHEAST
NOT IN CONTRACT
NOMINAL
NOT TO SCALE
NORTHWEST
NOMINAL PIPE SIZE
O
OC
OD
OH
OTO
OZ
ON CENTER
OUTSIDE DIAMETER
OVERHEAD
OUT TO OUT
OUNCE
P
PBD
P/C
PCF
PE
PEJ
PFB
PL
PLAM
PLBG
PNL
PR
PSF
PSI
PT
PART
PVC
PVG
PWD
PARTITION
POLYVINYL CHLORIDE
PAVING
PLYWOOD
R
METER
MAINTENANCE
MAXIMUM
MEMBRANE
MEDICINE CABINET
MECHANICAL
MEZZANINE
MANUFACTURER
MANHOLE
MINIMUM
MIRROR
MISCELLANEOUS
MARKER BOARD
MOULDING
MILLIMETER
MASONRY OPENING
MULTIPURPOSE UNIT
MOP RACK
MOUNTING
MATERIAL
MULLION
PARTICLEBOARD
PRECAST (CONCRETE)
POUNDS PER CUBIC FOOT
PORCELAIN ENAMEL
PREFORMED EXPANSION JOINT
PREFABRICATED
PLATE, PROPERTY LINE
PLASTIC LAMINATE
PLUMBING
PANEL(S)
PAIR
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PAINT, POINT
54" IF CLOSER
IF CLOSER
48"
SYMBOLS LEGEND
ABBREVIATIONS
A
LATCH APPROACH, PUSH SIDE
R
RA
RB
RD
REF
REFR
REINF
REQ
RES
REV
RFG
RLG
RM
RO
ROW
RPM
RTU
RV
RADIUS
RETURN AIR
RUBBER BASE
ROOF DRAIN
REFERENCE
REFRIGERATOR
REINFORCING/ REINFORCEMENT
REQUIRED
RESILIENT
REVISION
ROOFING
RAIL(ING)
ROOM
ROUGH OPENING
RIGHT-OF-WAY
REVOLUTIONS PER MINUTE
ROOF TOP UNIT (HVAC)
ROOF VENT PENETRATION
S
S
SATB
SC
SCH
SD
SE
SECT
SF
SGL
SIM
SNR
SNV
SP
SPECS
SPK
SQ
SR
SS
SOUTH
SOUND ATTENUATION BLANKET
SOLID CORE
SCHEDULE
SOAP DISPENSER, STORM DRAIN
SOUTHEAST
SECTION
SQUARE FOOT
SAFETY GLASS
SIMILAR
SANITARY NAPKIN RECEPTACLE
SANITARY NAPKIN VENDOR
SOUNDPROOF
SPECIFICATIONS
SPEAKER
SQUARE
SHOWER ROD
SERVICE SINK/
STAINLESS STEEL
ST
STREET
STD
STANDARD
STG
SEATING
STL
STEEL
STOR STORAGE
STP
STANDPIPE
STRUC STRUCTURAL
SW
SOUTHWEST
SYM
SYMMETRICAL
SYS
SYSTEM
T
TB
T/C
TD
TDW
TEL
TEMP
TGL
TH
THK
THR
TKBD
TLT
TOPO
T/P
TTD
TRT
T/SL
T/STL
TV
T/W
TYP
TZ
T&B
T&G
TOWEL DISPENSER
TOWEL DISPENSER & WASTE
TELEPHONE
TEMPERATURE
TEMPERED GLASS
TOWEL HOOK
THICK(NESS)
THRESHOLD
TACK BOARD
TOILET
TOPOGRAPHY MAP
TOP OF PARAPET
TOILET TISSUE DISPENSER
TREATED (PRESERVATIVE)
TOP OF SLAB
TOP OF STEEL
TELEVISION
TOP OF WALL
TYPICAL
TERRAZZO
TOP AND BOTTOM
TONGUE AND GROVE
U
UC
UH
UNFIN
UR
US
UTIL
UNDERCUT
UNIT HEATER
UNFINISHED
URINAL
UTILITY SHELF
UTILITY
1
?
A
FIRST FLOOR
View Identification
1/8" = 1'-0"
View Scale
Column Grid Lines
Interior Elevation Identification
4
?
A
Window Type
101
?
Door Number
View Identification
7 A611
V
VB
VCT
VERT
VIN
VJ
VOL
VT
VWC
VENT
VAPOR BARRIER
VINYL COMPOSITION TILE
VERTICAL
VINYL (SHEET)
V-JOINTED(ED)
VOLUME
VINYL TILE
VINYL WALLCOVERING
Sheet on which Interior Elevation
is drawn
Room Number and Name
101
Name of Level
Elevation of Level
Elevation Height in Section View
or Elevation View
A101
W
W/
WC
WD
WGL
WH
WM
W/O
WP
WR
WSCT
WT
WWF
YD
?
ABC
M
WEST, WIDTH
WITH
WATER CLOSET
WOOD
WIRE GLASS
WATER HEATER
WIRE MESH
WITHOUT
WATERPROOFING
WASTE RECEPTACLE
WAINSCOT
WEIGHT
WELDED WIRE FABRIC
YARD
Sheet Number
Elevation in Plan View
Drawing Category:
1=Plan, 2=Elev., etc.
Wall Type
Discipline,
A=Architectural
AI=Interiors
F.E.C.
Fire Extinguisher in Cabinet
Fire Separation Wall
2 hr. Rated
Fire Separation Wall
1 hr. Rated
Section Identification
W
5
6
CORRIDOR
V
Y
TOWEL BAR
TOP OF CURB
?
A
SIM
1
A101
8
A200
View Identification
1
MEP ENGINEER:
TriArch
www.tri-arch.com
618 E 3rd St.
Tulsa OK 74120
PHONE (918) 743-2724
HP Engineering, Inc.
www.hpengineeringinc.com
1836 S Baltimore Ave, Suite B
Tulsa, OK 74119
PHONE (539) 664-4618
Name
Contact
Kory Zehr (Mechanical)
kzehr@hpengineeringinc.com
Brandon Pinkerton (Electrical)
brandon@hpengineeringinc.com
HOTEL LOBBY
AREA OF WORK
OVERALL CASINO
No. of Revision
N
Revision Cloud
Sheet on which Exterior Elevation
is drawn
Key Plan
PROJECT TEAM
ARCHITECT:
12/03/2014
Smoke Barrier
1 hr. Rated
Non Rated Smoke Partition
Indicates drawing is Similar
Drawing Number on Sheet
Sheet on which Section is drawn
Exterior Elevation Identification
Seal
SPECIFICATIONS
WRITER:
Bill Stoskopf
1803 S. Carson Ave.
Tulsa, OK 74119
PHONE: (918) 747-3900
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
COVER SHEET
Author
Checker
12/03/2014
G000
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
GENERAL
G000
COVER SHEET
G100
CODE REVIEW & PHASING
FRONT APPROACH, PUSH SIDE
IF CLOSER
100% CONSTRUCTION
DOCUMENTS
INDEX OF DRAWINGS
24"
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
HINGE APPROACH, PUSH SIDE
IF CLOSER
24"
HARD ROCK LOBBY
RENOVATION
ABOVE IMAGE IS CONCEPTUAL - REFER CONSTRUCTION DRAWINGS FOR ACTUAL REQUIREMENTS
12"
48"
42"
22"
48"
42" IF Y<60"
18"
48" IF CLOSER
36"
LATCH APPROACH, PULL SIDE
60"
FRONT APPROACH, PULL SIDE
Y= 60" 0R 54"
HINGE APPROACH, PULL SIDE
DN
EX. DATA
EX. ELEV
86 SF
ELV-1
130
EX. MECH
EX. FIRE
52 SF
67 SF
123
124
ELECTRICAL
349 SF
Occupants 4
MEN
121
FUTURE SPA LOBBY
360 SF
WOMEN
120
119
61 SF
59 SF
EXISTING JEWELRY
STORE
FUTURE SPA
142
144
143
472 SF
Occupants 2
1478 SF
Occupants 5
1119 SF
Occupants 12
43 SF
NEW OFFICE
TEMP COPIER
136
117
127
463 SF
Occupants 5
EX. ELEV
126
128
ELV-2
290 SF
Occupants 3
438 SF
53 SF
125
EX. ELEV
220 SF
Occupants 3
ELV-3
NO CHANGE TO
SHADED AREAS
EX. STRS
134
129
133
81 SF
189 SF
Occupants 1
210 SF
EX. STOR.
EX LOBBY
135
53 SF
125 SF
Occupants 2
CORR
1451 SF
Occupants 29
EX. ELEV. LOBBY
1504 SF
MAX TRAVEL DISTANCE = 94'
EXPANDED FITNESS
36 SF
ALLOWABLE AREA PER 503 - NO CHANGE
EX. VEST.
NEW WORK RM.
CORR
146
3541 SF
REQUIRED PLUMBING FIXTURES - NO CHANGE
•
TOTAL OCCUPANT LOAD: 76
•
12 OCCUPANTS x 0.2 = 2.4" MIN
118
BUILDING CODE - NO CHANGE
IBC 2009 (USED IBC 2009)
•
OCCUPANCY CLASSIFICATION = R-1, TRANSIENT HOTEL LOBBY RENOVATION
•
OCCUPANT LOAD = 76
•
CONSTRUCTION TYPE = II-B
EX. ELEC.
122
SUPPORT
FIRE RESISTANCE RATING - NO CHANGE
•
STRUCTURAL FRAME
0
•
BEARING WALLS
EXTERIOR
0
INTERIOR
0
•
NON BEARING
0
•
FLOOR
0
•
ROOF
0
FROM TB. 601 READ: II-B
FIRE EXTINGUISHING SYSTEM - NO CHANGE
•
EXISTING CONSTRUCTION: FULLY SPRINKLERED, TYPE II-B
•
FIRE WALL SEPARATION PER TB. 705.4:
3-HR FIRE WALL SEPARATION REQUIRED PER TABLE NOTE 'A'
•
FEMALES: 38
TOILETS 1:50 = (1) FIXTURES MIN
LAVATORIES 1:50 = (1) FIXTURES MIN
•
•
•
DRINKING FOUNTAINS: 76 / 100 = (1) MIN.
SHOWERS: NONE REQUIRED
SERVICE SINKS: (1) REQUIRED
LEGAL DESCRIPTION - NO CHANGE
EGRESS - ADD 2 ADDITIONAL EXITS
REQUIRED EXITS TB 1021.1 = OCCUPANTS < 500 = (2) EXITS
ALLOWABLE TRAVEL DISTANCE TB. 1016.1
WITH SPRINKLER
= 250 FEET
COMMON PATH OF EGRESS TRAVEL 1014.3
= 75 FEET
•
MINIMUM REQUIRED FIXTURES
MALES: 38
NOTE: URINALS MAY BE SUBSTITUTED
FOR 67% OF REQUIRED MALE TOILET
FIXTURES
TOILETS 1:50 = (1) FIXTURES MIN,
(0) URINALS, (1) WATER CLOSETS
LAVATORIES 1:50 = (1) FIXTURES MIN
ZONING - NO CHANGE
REQUIRED EGRESS WIDTH PER TB. 1005.1,
RESIDENTIAL - 1
COPIER ROOM
141
104 SF
Occupants 2
1
LIFE SAFETY PLAN
1/16" = 1'-0"
VIP CHECKIN
MECH
EXIST. MECH
140
137
139
139 SF
Occupants 2
28 SF
49 SF
FRONT DESK
EX. STOR.
138
145
437 SF
Occupants 5
34 SF
Occupants 1
0"
1"
2"
3"
RM.
NO.
RM. NAME
AREA
OCCUPANTS
PER SF.
FROM
T1004.1.1
TOT. OCC
OCCUPANCY CALCULATION
DESIGN
OCCUPANT
LOAD
RM.
NO.
ELV-3
119
120
121
122
123
124
128
130
133
134
134.1
134.2
135
137
139
146
147
ELV-1
ELV-2
WOMEN
MEN
ELECTRICAL
EX. DATA
EX. MECH
EX. FIRE
EX. ELEV. LOBBY
EX. ELEC.
EX. STRS
EX. VEST.
EX. VEST
EX. VEST
EX LOBBY
MECH
EXIST. MECH
CORR
TEMP DESK
EX. ELEV
EX. ELEV
59 SF
61 SF
360 SF
86 SF
43 SF
36 SF
438 SF
67 SF
210 SF
81 SF
66 SF
111 SF
1504 SF
28 SF
49 SF
3541 SF
374 SF
52 SF
53 SF
16' - 0"
32' - 0"
48' - 0"
AREA
EX. ELEV
53 SF
7273 SF
Accessory storage
129
EX. STOR.
142
FUTURE SPA LOBBY
144
FUTURE SPA
145
EX. STOR.
Business Areas
118
SUPPORT
125
NEW OFFICE
126
NEW WORK RM.
127
CORR
136
TEMP COPIER
138
FRONT DESK
140
VIP CHECKIN
141
COPIER ROOM
143
EXISTING JEWELRY STORE
4"
1/16" = 1'
0'
RM. NAME
Rink and pool
117
EXPANDED FITNESS
64' - 0"
OCCUPANTS
PER SF.
FROM
T1004.1.1
TOT. OCC
PLC
OCCUPANCY CALCULATION
CODE REVIEW INFORMATION
NO CHANGE TO
SHADED AREAS
ARCHITECTURE
DESIGN
OCCUPANT
LOAD
0.0
0
189 SF
1478 SF
472 SF
34 SF
2173 SF
300 SF
300 SF
300 SF
300 SF
0.6
4.9
1.6
0.1
7.2
1
5
2
1
9
349 SF
220 SF
290 SF
463 SF
125 SF
437 SF
139 SF
104 SF
1119 SF
3248 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
3.5
2.2
2.9
4.6
1.3
4.4
1.4
1.0
11.2
32.5
4
3
3
5
2
5
2
2
12
38
1451 SF
1451 SF
14144 SF
50 SF
29.0
29.0
68.7
29
29
76
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
•
•
PHASE 3B
After new permanent check-in desk is open, demo temp desk and
renovate floors and ceilings
Renovate columns and previous path to elevators
•
•
PHASE 4A
Demo and renovate floor and ceiling area shown
•
•
•
•
PHASE 3A
New permanent desk is open
Demo temp desk and renovate floors and ceilings
Demo column wraps and previous path to elevators
•
Seal
12/03/2014
HOTEL LOBBY
AREA OF WORK
OVERALL CASINO
N
•
•
PHASE 2B
After renovating floors & ceiling in front of new
permanent check-in desk, minimize construction
area for construction of new permanent desks &
offices
•
•
•
PHASE 2A
Temp check-in desk is open
Demo existing check-in desk
Key Plan
PHASING REQUIREMENTS:
TEMPORARY CONSTRUCTION REQUIREMENTS:
1.
PHASING PLANS ARE A SUGGESTED METHOD OF PHASING TO
COMPLY WITH OWNERS OPERATIONAL NEEDS DURING
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR CREATING
AND COORDINATING A FEASIBLE PHASING PLAN ACCORDING
TO THE CONTRACTOR'S OWN MEANS AND METHODS PROPOSED
IN BID.
1.
2.
CONTRACTOR SUBMIT THE FOLLOWING
DOCUMENTATION WITH BID:
A.
PROPOSED PHASING SCHEME WITH
CONTRACT TIME TO COMPLETE EACH PHASE
AND TOTAL TIME TO COMPLETE ENTIRE
PROJECT.
2.
B.
PHASING DIAGRAMS CORRESPONDING TO
THE SCHEDULE SHOWING INTENT OF
PHASING AND LOCATION OF TEMPORARY
WALLS.
C.
•
•
•
•
•
•
PHASE 1B
Construct New check-in desk
Construct temp walls for laydown area
Open area previously occupied by C-Note for traffic
Construct new office area and outside access by elevator lobby
Renovate partial elevator lobby (1 elevator closed)
•
•
•
•
•
PHASE 1 A
Demo existing walls where construction laydown area is to take place
Demo C-Note bar area and renovate
Demo partial elevator lobby
Cut new doors to allow construction traffic
1.
6'-0" MIN. WIDTH CONTINUOUS PATH
BETWEEN NORTH AND SOUTH ENDS
OF PROJECT AREA
2.
8'-0" CLEAR ON PUBLIC SIDE (FRONT) OF
CHECK-IN COUNTER
3.
4'-0" CLEAR ON PRIVATE SIDE (BACK) OF
CHECK-IN COUNTER
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
0"
2
CONTRACTOR TO MAINTAIN THE FOLLOWING
CLEARANCES AT ALL TIMES:
PRIOR TO THE START OF ANY DEMOLITION,
CONTRACTOR TO BUILD TEMPORARY PARTITIONS TO
VISIBLY SEPARATE ALL CONSTRUCTION ACTIVITIES
FROM OPERATING PORTIONS OF THE BUILDING.
TEMPORARY WALLS SHALL BE BUILT AS WALL TYPE
"3AH," REF. INTERIOR PARTITION LEGEND ON SHEET
A102. PAINT COLOR INDICATED IN FINISH NOTES ON
THE AI DRAWINGS AND PROVIDE AND INSTALL
RUBBER BASE, COLOR TBD FROM STANDARD
RANGE. REFER SPECIFICATIONS FOR SEALING AND
DUST CONTAINMENT MEASURES REQUIRED ABOVE
CEILING AND FOR DUCTWORK AND OTHER
COMPONENTS TO PREVENT CONSTRUCTION DUST
AND DEBRIS FROM ENTERING OCCUPIED SPACE.
THERE ARE THREE CHECK-IN COUNTERS INDICATED
IN THE PLANS; THE EXISTING, THE TEMPORARY, AND
THE NEW. ONE OF THE THREE MUST BE IN SERVICE
AND ACCESSIBLE AT ALL TIMES DURING
CONSTRUCTION ACTIVITIES. REFER PHASING
REQUIREMENTS FOR CLEARANCES. CONTRACTOR
MUST COORDINATE WITH OWNER FOR OWNER
INSTALLATION OF SECURITY CAMERAS AND DATA
CONNECTIONS NECESSARY TO PUT COUNTERS INTO
SERVICE FOR EACH PHASE.
100% CONSTRUCTION
DOCUMENTS
PHASING NOTES
1"
2"
3"
4"
1" = 20'
SUGGESTED PHASING PLANS
1" = 20'-0"
DRAWN BY:
0'
20' - 0"
40' - 0"
60' - 0"
80' - 0"
CHECKED BY:
ISSUE DATE:
CODE REVIEW &
PHASING
Author
Checker
12/03/2014
G100
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
PHASE 4B
Demo and renovate floor and ceiling area shown (lose 1 elevator)
HARD ROCK LOBBY
RENOVATION
•
•
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
Consultants
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
DN
No.
Description
Date
REVISIONS
DN
GENERAL DEMOLITION NOTES
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DEMOLITION PLANS ARE GENERAL AND DIAGRAMMATIC IN NATURE. THE PLANS ARE NOT INTENDED TO
REPRESENT THE TOTAL SCOPE OF WORK. THESE PLANS DO NOT SHOW EACH ITEM THAT IS REQUIRED TO BE
REMOVED. EACH CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL CONDITIONS AS THEY EXIST IN
THE FIELD THROUGH SITE INSPECTION AND REVIEW OF THESE DOCUMENTS. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO DETERMINE AND COORDINATE THE REMOVAL AND DEMOLITION WORK AS REQUIRED TO
ACHIEVE FINAL PRODUCT AS INDICATED IN THESE DOCUMENTS.
REFER SUGGESTED PHASING PLANS, PHASING REQUIREMENTS, AND TEMPORARY CONSTRUCTION REQUIREMENTS
AND PLAN ALL WORK ACCORDINGLY
THE CONTRACTOR HAS DISCRETION OF MEANS AND METHODS TO REMOVE MORE MATERIAL THAN IS SHOWN
ON THIS DEMOLITION PLAN AND RESTORE THOSE PORTIONS DURING NEW CONSTRUCTION IN ORDER TO SIMPLIFY
ARRIVING AT THE FINISHED PRODUCT SHOWN.
REMOVE ALL EXISTING FLOOR FINISHES WHERE NEW FINISHES ARE SCHEDULED. PREPARE EXISTING FLOOR SURFACE
AS NECESSARY FOR NEWLY SCHEDULED FINISHES.
WHERE NEW FINISH MATERIALS ARE SPECIFIED TO BE INSTALLED ON EXISTING SURFACES, PREPARE EXISTING
SURFACE AS INDICATED BY FINISH MATERIAL MANUFACTURER TO RESULT IN AN APPROPRIATE, UNIFORM BASE
SURFACE ON WHICH TO PLACE THE NEW FINISH MATERIAL.
THE OWNER AND HIS DESIGNATED REPRESENTATIVES HAVE FIRST RIGHT OF REFUSAL REGARDING SALVAGEABLE
ITEMS. CONTRACTOR SHALL COORDINATE WITH OWNER.
PRIOR TO START OF DEMOLITION, OBTAIN DIRECTION FROM OWNER FOR BUILDING COMPONENTS TO BE KEPT
AND STORED BY OWNER.
EXISTING BUILDING PLANS IF AVAILABLE MAY BE REVIEWED UPON REQUEST. THESE PLANS SHALL NOT BE
CONSIDERED ACCURATE AND COMPLETE AS TO THE CONDITIONS AS THEY EXIST IN THE FIELD.
EXISTING STRUCTURAL SYSTEM SHALL NOT BE REMOVED OR MODIFIED UNLESS APPROVED IN ADVANCE BY THE
ARCHITECT OR AS SPECIFICALLY OTHERWISE INDICATED.
REMOVE EXISTING ITEMS AS REQUIRED FOR REUSE IN THE NEW PLAN OR NEW FINISH. catalog AND STORE ITEMS IN
A SAFE STORAGE AREA SUBJECT TO THE OWNER'S APPROVAL UNTIL THE TIME OF REINSTALLATION. LOST ITEMS
SHALL BE REPLACED WITH COMPARABLE NEW ITEM AT NO COST TO THE OWNER.
PRIOR TO INITIATING DEMOLITION ACTIVITIES INDICATED, ENSURE THAT NO JURISDICTIONALLY REGULATED
HAZARDOUS SUBSTANCE IS PRESENT WITHIN THE CONSTRUCTION AREA. IF A HAZARDOUS SUBSTANCE IS FOUND,
NOTIFY THE ARCHITECT AND OWNER, AND OBTAIN THE OWNER'S DIRECTION CONCERNING DISPOSITION OF THE
SUBSTANCE PRIOR TO PROCEEDING WITH THE WORK. ALL DEMOLITION ACTIVITIES SHALL COMPLY WITH
APPLICABLE PROVISIONS OF FEDERAL, STATE, COUNTY AND LOCAL JURISDICTIONAL REGULATORY
REQUIREMENTS.
UNLESS INDICATED OTHERWISE, ALL DEMOLISHED MATERIAL EQUIPMENT AND RELATED ITEMS SHALL UPON
REMOVAL BECOME THE PROPERTY OF THE CONTRACTOR AND BE DISPOSED OF IN STRICT ACCORDANCE WITH
REGULATORY REQUIREMENTS.
PRIOR TO INITIATING DEMOLITION ACTIVITIES, FIELD VERIFY EXISTING SPACE CONFIGURATION AND
COMPONENTS INDICATED ON THE DRAWINGS. SHALL DISCREPANCIES EXIST, NOTIFY THE ARCHITECT AND
OBTAIN THE ARCHITECT'S DIRECTION CONCERNING DISPOSITION OF THE DISCREPANCY PRIOR TO PROCEEDING
WITH THE WORK.
PROTECT EXISTING CONSTRUCTION TO REMAIN WITHIN CONSTRUCTION AREA AND BUILDING COMPONENTS
OUTSIDE THE CONSTRUCTION AREA FROM DAMAGE DURING DEMOLITION ACTIVITIES. SHALL DAMAGE OCCUR,
REPAIR DAMAGE AS REQUIRED TO RETURN THE DAMAGED COMPONENT TO ITS CONDITION PRIOR TO
INITIATION OF THE WORK. SHALL REPAIR NOT BE FEASIBLE, CONSULT THE ARCHITECT FOR DISPOSITION OF THE
DAMAGED COMPONENT.
WHERE REQUIRED TO PROTECT EXISTING SPACES FROM DAMAGE AND/OR DUST NOISE AND CONSTRUCTION
DEBRIS, PROVIDE TEMPORARY ENCLOSURES, BARRIERS, FILTERS AND OTHER TEMPORARY MEASURES REQUIRED TO
PROVIDE PROTECTION.
SHALL DEMOLITION ACTIVITIES REQUIRE ACCESS TO OR THROUGH EXISTING OCCUPIED PUBLIC OR PRIVATE
SPACES, CONSULT THE OWNER FOR SPECIFIC ACCESS REQUIREMENTS, AND ADHERE STRICTLY TO THE OWNER'S
REQUIREMENTS.
MAINTAIN REQUIRED EXIT ACCESS CORRIDORS AND EXITS FREE AND CLEAR AT ALL TIMES UNLESS TEMPORARY
OBSTRUCTION IS APPROVED BY JURISDICTIONAL REGULATORY AGENCIES.
IF INDICATED IN THE DRAWINGS, VERIFY THAT FIRE RESISTANCE RATING INDICATED ON EXISTING WALLS
ABUTTING CONSTRUCTION AREA COMPLIES WITH RATING INDICATED, INCLUDING OPENING PROTECTIVES.
SHALL ANY PORTION OF THE ASSEMBLY NOT COMPLY WITH FIRE RESISTANCE RATING, CONSULT THE ARCHITECT
TO DETERMINE CORRECTIVE MEASURES REQUIRED. IF MODIFICATIONS ARE MADE TO EXISTING FIRE PROTECTION
AND FIRE RESISTIVE WALL OR FLOOR SYSTEMS RESTORE TO MAINTAIN THE REQUIRED RATING AND CONTINUITY.
DN
NOTE: REFER MEP, PHASING
PLANS FINISH PLANS AND
NOTES AND DEMOLITION
NOTES FOR OTHER
DEMOLITION REQUIREMENTS
D
DASHED LINES INDICATE
ELEMENTS DO BE DEMOLISHED
RELOCATE DOOR ACCESS
HARDWARE TO CORRESPONDING
NEW DOOR, REF. DOOR
SCHEDULE
Consultants
B
C
A
DN
DN
2
HARD ROCK LOBBY
RENOVATION
DN
DEMOLITION PLAN
1/8" = 1'-0"
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
1.
DN
AI601
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
EX.
ELEV
NEW
WORK
RM.
124
NEW
OFFICE
125
ELV-2
126
EX.
STOR.
EX.
VEST.
EX.
VEST
134
134.1
129
4
A102
125
Seal
129
142B
OFOI COPIER
136
OVERALL CASINO
N
Key Plan
EX
LOBBY
5
A102
TEMP
DESK
135
7
PROVIDE PERFORATED METAL
AT SIDES AS SHOWN IN
SECTION DETAILS-TYPICAL
CORR
147
146
5
AI610
1
TEMPORARY RECEPTION DESK
2
A102
4
17
AI600
141B
138
XFER
140
RECESS LIGHTING FLUSH WITH GYPSUM
BOARD IN WALLS AND CEILING REFER
ELECTRICAL DRAWINGS VERIFY EXACT
PLACEMENT WITH ARCHITECT DURING
CONSTRUCTION
VIP
CHECKIN
3' - 0"
DISC PANEL
140
HP
FRONT
DESK
COPIER
ROOM
HP
HP
141
141A
137
3
A102
DN
HOTEL LOBBY
AREA OF WORK
ELV-3
126
136
144
12/03/2014
DN
EX.
ELEV
TEMP
COPIER
24' - 0"
128
16' - 0"
134.2
EXIST.
MECH MECH
139
137
OFOI COPIER
EX.
STOR.
AI610
138
145
6
145
DN
DN
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
1
FLOOR PLAN
1/8" = 1'-0"
DRAWN BY:
CHECKED BY:
ISSUE DATE:
FLOOR PLAN &
DEMOLITION PLAN
Author
Checker
12/03/2014
A101
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
11.
144
133
100% CONSTRUCTION
DOCUMENTS
10.
143
130
EX.
VEST
8' - 0"
8.
9.
FUTURE
SPA
142
123
EX.
FIRE
ELV-1
DN
0'
7.
EXISTING
JEWELRY
STORE
EX.
MECH
EX.
STRS
1/8" = 1'
6.
FUTURE
SPA
LOBBY
EX.
ELEC.
3"
5.
EX.
ELEV.
LOBBY
122
EX.
ELEV
2"
4.
EX.
DATA
1"
3.
128
2' - 1"
2.
UNLESS INDICATED OTHERWISE, FLOOR PLAN DIMENSIONS ARE TO THE CENTER LINE OF NEW
METAL STUD WALL CONSTRUCTION AND TO THE FINISHED FACE OF EXISTING CONSTRUCTION.
WHERE REQUIRED TO ENSURE WALL STABILITY, DIAGONALLY BRACE TOP OF WALL ABOVE
CEILING AT 4'-0" ON CENTER AND EACH SIDE DOOR SECURED TO STRUCTURE ABOVE.
UNLESS INDICATED OTHERWISE, LOCATE HINGE SIDE OF DOOR OPENINGS 4" FROM FINISH
FACE OF ADJACENT WALL.
FIELD VERIFY FINISHED CASEWORK OPENINGS PRIOR TO FABRICATION OF CASEWORK.
NOTIFY THE ARCHITECT AND OBTAIN THE ARCHITECT'S DIRECTION SHALL VERIFIED CASEWORK
OPENING REQUIRE DIMENSIONAL RECONFIGURATION OF THE CASEWORK INDICATED.
UNLESS INDICATED OTHERWISE, REFER TO REFLECTED CEILING PLANS FOR CEILING HEIGHT
DESIGNATIONS.
PROVIDE AND INSTALL BLOCKING, FRAMING AND / OR BRACING AS REQUIRED TO SECURELY
INSTALL ALL OWNER AND CONTRACTOR FURNISHED EQUIPMENT OR WALL PROTECTION
ASSEMBLIES OR GRAB BARS OR TOILET ACCESSORIES. VERIFY BLOCKING IS INSTALLED IN
EXISTING WALLS TO RECEIVE OWNER OR CONTRACTOR FURNISHED EQUIPMENT OR WALL
PROTECTION ASSEMBLIES.
INSTALL PLUMBING AND ELECTRICAL FIXTURES AND DEVICES, MAKE CONNECTIONS TO
EXISTING SYSTEM PER CODE REQUIREMENTS.
REFER 'AI' DRAWINGS FOR INTERIOR ELEVATIONS AND ADDITIONAL INFORMATION.
THE DRAWINGS AND SPECIFICATIONS, AND ALL COPIES THEREOF, ARE LEGAL INSTRUMENTS OF
SERVICE FOR THE USE OF THE OWNER AND AUTHORIZED REPRESENTATIVES ON THE
DESIGNATED PROPERTY ONLY. OTHER USE, WITHOUT THE EXPRESSED WRITTEN PERMISSION OF
THE ARCHITECT OF RECORD, IS PROHIBITED
SPECIFICATIONS, DETAILS AND SCHEDULES WHICH MAY BE BOUND SEPARATELY ARE PART OF
THESE CONTRACT DOCUMENTS. DRAWINGS BY CONSULTING PROFESSIONALS, SUCH AS
STRUCTURAL, LANDSCAPE, ETC. ARE SUPPLEMENTARY TO THE ARCHITECTURAL DRAWINGS AND
ARE PART OF THESE CONTRACT DOCUMENTS
THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY OF ANY OMISSIONS OR
DISCREPANCIES BETWEEN THE ARCHITECTURAL DRAWINGS, CONSULTING PROFESSIONAL'S
DRAWINGS, SPECIFICATIONS OR EXISTING CONDITIONS. SHOULD THERE BE AN OMISSION OR
DISCREPANCY BETWEEN SAID DRAWINGS, SPECIFICATIONS OR CONDITIONS, IT SHALL BE
BROUGHT TO THE ARCHITECT'S ATTENTION IN WRITING FOR CLARIFICATION PRIOR TO
INSTALLATION OF SAID WORK
THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY IF INFORMATION IS NOT
SHOWN OR UNCLEAR
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING CONDITIONS
PRIOR TO STARTING WORK AND REPORT ANY DISCREPANCIES IN WRITING TO THE ARCHITECT.
ANY WORK INSTALLED IN CONFLICT WITH THE ARCHITECTURAL DRAWINGS SHALL BE
CORRECTED BY THE CONTRACTOR AT HIS EXPENSE
THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVALS FOR ALL WORK
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SCHEDULING AND COORDINATING THE WORK
FOR ALL UTILITIES AND SERVICES
ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. QUESTIONS REGARDING THE SAME, OR THEIR EXACT MEANING,
SHOULD BE DIRECTED TO THE ARCHITECT
WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE. DO NOT SCALE DRAWINGS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT AND
CONFIGURATION OF THE BUILDING ON THE SITE
ALL EXISTING WALL DIMENSIONS ARE TO INSIDE FACE OF STUD, FACE OF CONCRETE OR
MASONRY UNLESS NOTED OTHERWISE. INTERIOR WALL DIMENSIONS ARE TO CENTER LINE OF
WALL UNLESS NOTED OTHERWISE
FLOOR ELEVATIONS ARE TO TOP OF CONCRETE SLAB, UNLESS NOTED
CONTRACTOR SHALL PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BLOCKING, BACKING,
HANGERS, BACK-UP PLATES, AND SUPPORTING BRACKETS REQUIRED FOR THE INSTALLATION
OF ALL CASEWORK, TOILET ROOM ACCESSORIES, FIXTURES, PARTITIONS AND ALL WALLMOUNTED OR SUSPENDED MECHANICAL, KITCHEN, ELECTRICAL OR MISCELLANEOUS
EQUIPMENT AND FURNISHINGS
CONTRACTOR SHALL VERIFY EXACT SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT
PADS, BASE STRUCTURES, ROOF OPENINGS, AS WELL AS POWER, WATER, DRAIN INSTALLATIONS
AND STRUCTURAL STEEL SUPPORT LOCATIONS WITH EQUIPMENT MANUFACTURERS BEFORE
PROCEEDING WITH THE WORK. CHANGES TO ACCOMMODATE FIELD CONDITIONS OR
APPROVED SUBSTITUTIONS SHALL BE MADE WITHOUT ADDITIONAL CHARGE TO THE OWNER
0"
142A
1.
4"
S1
GENERAL PLAN NOTES
32' - 0"
AI601
S2
0' - 3 1/4"
0' - 2 7/8"
WALLCOVERING OVER 5/8" HIGH IMPACT GYP.
ON 1 5/8" LGMF AT 1'-4" O.C.-TYPICAL
7' -
1 5/8" BRACING WITH CLIP
ANGLE BACK TO
STRUCTURAL COLUMN AS
NEEDED. START AT 6" ABOVE
BASE OF COLUMN
3' -
5/8" GYP. BOARD
CLAD IN WALLCOVERING
0"
AI610
1' 0"
153°
"
0' - 1 1/2"
0"
'-1
34
8
8' - 6"
EXISTING STRUCTURAL
COLUMN - PAINT BRIGHT
WHITE FOR REFLECTION OF
LIGHTING
TEMPORARY RECEPTION DESK
REFER ELEVATIONS AND DETAILS
5
Date
REVISIONS
REMOVABLE ACCESS PANEL
WRAP VWC INTO JOINT
AND TO COVER 1" OF BACK
OF PANEL
GYP CEILING INFILL AT
1" ABOVE HIGHEST
ADJACENT CEILING
REFER CEILING PLAN
PLAN SECTION
COLUMN PLAN DETAIL
3" = 1'-0"
Description
CONTINUOUS LED STRIP LIGHTING
FULL HEIGHT OF COLUMN COVER
ADHERED TO LGMF - REFER
ELECTRICAL
0' - 10 1/2"
2' -
AI610
No.
1/4" ROUND NEODYMIUM
MAGNET RETAINERS AT 1'-0" OC
VERTICAL RECESS AND ADHERE TO
SUBSTRATE WITH 3M SCOTCH-WELD
OR APPROVED EQUAL
AT BASE OF COLUMN - 6" HIGH 20
GAUGE STAINLESS STEEL BASE
ADHERED TO 6" HIGH PLYWOOD
FASTENED TO COLUMN WITH LGMF
CLIP ANGLES
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
FRY REGLET 'Z' REVEAL GYP
CORNER AND MAGNET MOUNT
5
A102
9
DESIGN
REMOVABLE RESIN PANEL FABRICATED IN (2)
SECTIONS BOTTOM OF PANEL AT 4" AFF AND
BREAK AT 16" AFF RP1 - REFER TO FINISH LEGEND,
SHEET AI600
0' - 3 3/4"
6"
GROMMETS-GR1CENTER 1 OVER EACH
COMPUTER STATION
AND 1 OVER EACH PRINTER STATION
ARCHITECTURE
FRY REGLET 5/8"X1/2" 'F' TRIM TO
RETAIN PANEL AND FINISH GYP
CORNER - WRAP BOTTOM WITH
LGMF AND RIVET TO REGLET TO
PROVIDE CLOSURE THAT WILL
HOLD UP ACRYLIC
0' - 3"
0' - 1 1/2"
1' - 0"
SUSPEND COLUMN WRAP
ASSEMBLY FROM STRUCTURE
ABOVE OR FRAME BACK TO
AND SUSPEND FROM
COLUMNS
PROVIDE CORNER GUARD-CG1 AT ALL OUTSIDE
CORNERS-TYPICAL
1' - 0 3/8"
PLC
1' - 6 5/8"
REFLECTED CEILING DETAIL
9' - 6"
GROMMETS-GR1CENTER 1 OVER COMPUTER
STATION AND 1 OVER
PRINTER STATION, TYPICAL
1' - 0"
2' - 6"
4' - 0"
GROMMETS GR1 EVERY
3'-0" O.C. OR AS DIRECTED
BY OWNER-TYPICAL
2' - 7"
-8
4' - 0"
4' - 0"
4' - 0"
4' - 0"
4' - 0"
4' - 0"
4' - 0"
4' - 0"
1' - 0"
10
12
2' - 6"
AI610
4' - 0"
AI610
5' - 10"
4' - 0"
2
"
10
GROMMETS-GR 11 CENTERED AT EACH COMPUTER
STATION AND 1 AT EACH
PRINTER STATION
AI610
AI610
AI600
5/8" GYP BD ONE SIDE 3 5/8"
LGMF INFILL WALL
ALIGN
6
17
AI610
4' - 0"
Consultants
7' - 0"
2'
°
90
4' - 0"
2' - 0"
SUPPORT BRACKET BR1 EVERY
3'-0" O.C.-TYPICAL
225
°
4' - 0"
3' - 0"
3' - 6"
6
ENLARGED TEMPORARY DESK
1/4" = 1'-0"
STORAGE FILES TO
CREATE ADDITIONAL
STRUCTURAL SUPPORT
FOR COUNTERTOPS
13
-8
"
PONY WALL AT
3'-6" HIGH
3
VIP CHECK IN 140
1/4" = 1'-0"
VIDEO WALL
2
CHECK-IN DESK
1/4" = 1'-0"
1' - 6"
2'
43' - 10"
ON CHASE SIDE INSTALL
TRANSLUCENT GLAZING FILM OVER
PORTION OF GLAZING LOOKING
INTO MECHANICAL CHASE
3' - 3"
2' - 0"
AI610
16
AI610
14
°
233
82
°
3
5
6
6.7
8
8.3
9.5
10 11
12 13
14
WORK ROOM 126
1/4" = 1'-0"
W
DN
V
U
T
3A1
98
°
3A0
11' - 3"
HOTEL LOBBY
AREA OF WORK
2N0
2N0
155°
3A0
3A0
3A0
4' - 5"
3A0
3A0
3A0
3A0
3A0
2N0
N
133°
Key Plan
3' - 0"
1' - 0"
3' - 0"
1' - 0"
3' - 0"
1' - 0"
3' - 0"
3' - 0"
3A0
169°
6' - 0"
3' - 0"
3A0
3A1
B. INSULATION TYPE
A. ACOUSTICAL
T. THERMAL
N. NONE
C . WALL HEIGHT
L. LOW WALL - DOES NOT REACH CEILING, REF. ELEVATIONS FOR WALL HEIGHT
H. HIGH WALL - WALL STUDS AND GYP SEAL TIGHT TO BOTTOM OF CEILING
0. WALL STUDS AND GYP END 6" ABOVE CEILING
1. WALL STUDS AND ONE SIDE GYP EXTEND TO DECK
2. WALL STUDS AND BOTH SIDES GYP EXTEND TO DECK
3°
3' - 10" 3' - 1"
M
3A0
8°
!. CODE RATING
°
93
11' - 2"
3A0
3NL
N
DN
ALIGN
3A1
ALIGN
DN
XZX
2"
8' - 0"
1"
4' - 0"
15
100% CONSTRUCTION
DOCUMENTS
1' - 0"
3' - 0"
1' - 0"
4"
7°
7' - 0"
3A0
8' - 5"
6' - 5"
14' - 3"
2' - 2"
INTERIOR PARTITION LEGEND
DN
GENERAL NOTES
1. INSTALL 5/8" GYPSUM BD UltraLight FIRECODE PANELS AT ALL
EXPOSED SIDES OF STUDS.
2. INSTALL MOLD & MOISTURE RESISTANT GYP BD NO LESS THAN 4' 0" FROM ALL PLUMBING FIXTURES.
3. INSTALL CEMENTITIOUS TILE BACKER BOARD BEHIND ALL TILE.
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DIMENSION PLAN &
ENLARGED PLANS
0'
DIMENSION PLAN
1/8" = 1'-0"
1/4" = 1'
1
0"
ABC
°
65
10' - 0"
3A0
3A0
4' - 7"
3A0
OVERALL CASINO
3' - 0"
153°
3A1
R
2N0
7' - 0"
6A0
2N0
3' - 10" 2' - 0"
3A1
3A0
A. WALL CORE WIDTH
0. 7/8" HAT CHANNELS
1. 1 5/8" METAL STUDS
2. 2 1/2" METAL STUDS
3. 3 5/8" METAL STUDS
4. 4" METAL STUDS
6. 6" METAL STUDS
T. TWO 3 5/8" METAL STUDS
WITH 1 3/4" AIR SPACE
2N0
3A0
3A0
25°
1' - 5" CL COL - FOW
2N0
2N0
27°
P
3A1
2N0
82
°
ALIGN
8°
Q
3A1
ALIGN
2N0
3NL
7' - 6"
2N0
3A0
12/03/2014
14' - 4"
16' - 0"
13' - 5"
12' - 0"
15' - 5"
3"
3A0
Seal
DN
DRAWN BY:
CHECKED BY:
ISSUE DATE:
Author
Checker
12/03/2014
A102
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
DN
11
4
4
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
2' - 7"
4" BACKSPLASH
HARD ROCK LOBBY
RENOVATION
225
°
15
CEILING NOTES
2
3
4
TEMPORARY SECURITY CAMERAS BY OWNER FOR TEMPORARY CHECKIN PATCH AND REPAIR ALL CEILLINGS AFTER REMOVAL OF
CAMERAS
COORDINATE WITH OWNER ALL OWNER PROVIDED AND INSTALLED CAMERAS, SPEAKERS, WIRELESS ACCESS POINTS, AND
OTHER PERMANENT DEVICES
AT CAMERAS IN MIRROR CEILING DRILL 3" DIAMETER HOLE THROUGH CENTER OF PANEL CONFIRM LOCATIONS WITH OWNER
LED BACKLIT FROSTED ACRYLIC 3/8" THICK X 4 1/2" WIDE TYPICAL - ROUTE JOINTS TO CREATE 1/4" SHIPLAP ALL PANEL JOINTS
AND ALLOW NO LINE OF SITE TO PLENUM - FABRICATE INTERSECTIONS FROM A SINGLE PIECE SUCH THAT NO JOINTS ARE IN THE
INTERSECTION - INSTALL AS WITHIN SUSPENDED GRID IN A MANNER THAT IS REMOVABLE
5
CP2 - PREFABRICATED FINISHED PANELS DRILLED AND SCREWED TO 3 5/8" LIGHT GAGE METAL FRAMING @ 2'-0" ON CENTER
SUSPENDED FROM STRUCTURE ABOVE - PROVIDE CONTINUITY OF PATTER AMONT PANELS IN CONTIGUOUS SECTIONS - RECESS
SCREW HEADS FILL HOLES AND TOUCH UP PAINT TO MATCH PREFINISHED PANEL
6
CP1 - FULLY ADHERE CHROME MIRROR TO 3/8" PLYWOOD AND LAY INTO 2'X2' X 9/16" SUSPENDED GRID SYSTEM - REFER FINISH
NOTES
PLC
1
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
CEILING LEGEND
REVISIONS
1.
2.
3.
ACT 1
24"x48" ACOUSTICAL
CEILING TILE
ACT 2
24"x24" ACOUSTICAL
CEILING TILE
ACT 3
CLEANABLE TYPE 24"x24"
ACOUSTICAL CEILING TILE
GYP
GYPSUM BOARD
CEILING
CP1
24"X24" MIRROR CEILNG
CP2
ACRYLIC PANEL CEILING
INSULATION ABOVE
CEILING-TYPICAL.
SEE NOTE 2. ABOVE
REFER TO ELECTRICAL DRAWINGS FOR LIGHTING AND SWITCHING LAYOUT
LAY ACOUSTICAL BATT INSULATION ATOP ACOUSTICAL TILE WITHIN 4' OF PERIMETER IN ALL OFFICES. USE
CARPET TAPE PER SPECIFICATIONS.
ADJUST GRID AS NECESSARY SUCH THAT NO TILES ARE LESS THAN 6" IN WIDTH AND GRID IS AS CENTERED AS
POSSIBLE IN ROOM.
Consultants
SHEET METAL SCREWS TYPICAL
REFER PLAN
1' - 11"
STRUCTURE ABOVE
LED STRIP LIGHT
ADHERED TO GYPSUM
BOARD
STRUCTURE ABOVE
0' - 2"
0' - 2"
1/2" GYP BD ON SOFFIT FRAMING 3 5/8"
(MIN.) MTL. STUDS@ 24" O.C. ATTACH TO
STRUCTURE AS REQ'D
4 1/2" X 3/8" FROSTED
TRANSLUCENT ACRYLIC
SECURITY CAMERAS BY OWNER
POLISHED CHROME MIRROR
LAMINATED TO 3/8" MDF PANEL
IN 9/16" 2X2 SUSPENDED GRID
0' - 8"
POLISHED CHROME MIRROR
LAMINATED TO 3/8" MDF PANEL
IN 9/16" 2X2 SUSPENDED GRID
2' - 5"
1/2" GYP. BOARD ON METAL
STUD FRAMING SUSPEND FROM
STRUCTURE ABOVE PAINT
POLISHED CHROME MIRROR
LAMINATED TO 3/8" MDF PANEL
IN 9/16" 2X2 SUSPENDED GRID
1/2" GYP BD ON SOFFIT FRAMING
3 5/8" (MIN.) MTL. STUDS
@ 24" O.C. ATTACH TO
STRUCTURE AS REQ'D
FLOWBAR BORDER 22 SLOT DIFFUSER WITH
1" VISIBLE OPENING REFER MECHANICAL
LAY-IN 4" X 3/8" FROSTED
TRANSLUCENT ACRYLIC
WHERE INDICATED ON PLAN
8' - 0"
1' - 4"
2
DTL-CLG-COVE SOFFIT
1 1/2" = 1'-0"
4"
NEW
OFFICE
FUTURE
SPA
125
°
55
144
ACT1 9' - 0"
4' - 10"
42' - 10" R
PERMANENT CAMERAS
BY OWNER
A130
AI600
78
°
140
CP1 9' - 3"
EXIST.
MECH
COPIER
ROOM
139
141
6
FRONT
DESK
CP2 9' - 6"
155°
6"
CP1 9' - 3"
EX.
STOR.
5
145
138
EX. CLG
ACT1 9' - 0"
MECH
137
ACT1 8' - 0"
EX. CLG
2
SLOT DIFFUSER REFER MECHANICAL
°
93
7' - 10"
ACT1 9' - 0"
VIP
CHECKIN
CP2 9' - 6"
GYP 9' - 0"
3
TING
EXIS
GYP. 9' - 0"
2' - 0"
63
°
CP1 9' - 3"
CP1 9' - 3"
EXISTING CEILING TO BE
REPAINTED P3
LED LIGHTING
SLOT DIFFUSER
CP2 9' - 6"
FROM THIS CIRCLE IN, CURVED
CEILING-EXIST. TO REMAIN
4
CP2 9' - 6"
17
LED BACKLIT FROSTED
ACRYLIC 3/8" THICK X 4
1/2" WIDE TYPICAL ROUTE
AND SHIPLAP ALL JOINTS
REFER NOTES
3' - 9"
GYP./LED 9' - 9"
GYP 9' - 0"
INFILL EXIST. CLG TO LEVEL OF
ADJACENT SOFFIT TO REMAIN
AND PAINT P3
20' - 10"
146
SLOT DIFFUSER
4
Seal
12/03/2014
HOTEL LOBBY
AREA OF WORK
OVERALL CASINO
EX. CLG-NEW CEILING
DESIGN TO DIE INTO
EXISTING LOWER SOFFIT
CP1 9' - 3"
CP2 9' - 6"
CP1 9' - 3"
134.1
CH
MAT
3' - 8"
6' - 0"
2
27' - 3"
134.2
"
42' - 10
CORR
RADIUS
GYP. 8' - 0"
SLOT DIFFUSER
28' - 9"
GYP. BOARD TRIM
@ 9'-2"
134
CP1 9' - 0"
5"
27' - 3"
EX.
VEST
EX. CLG
2' -
22' - 2"
EX.
VEST
EX. CLG
A130
GYP./LED 9' - 9"
40' - 6" R
CP2 9' - 6"
GYP 9' - 0"
EX.
VEST.
ELV-3
A130
CP1 9' - 3"
CP1 9' - 3"
147
5' - 5"
3
TEMP
COPIER
TEMP
DESK
1.
129
136
42' - 10" R
NO CLG
ELV-2
EX. CLG
EX.
ELEV
1' - 4"
ACT1 9' - 0"
EX.
STOR.
EX. CLG
8' - 4"
143
ACT1 9' - 0"
40' - 6"
EXISTING
JEWELRY
STORE
24' - 0"
CP2 9' - 6"
NO CLG
NO CLG
16' - 0"
126
EX.
ELEV
0'
-
142
NO CLG - SHELL SPACE
128
8' - 0"
124
EX. CLG
FUR OUT GYP. BOARD
AT EXISTING CLG. 2.5" HIGH, PAINT P3
N
0'
123
EXIST. CLG
133
130
1/8" = 1'
EX.
FIRE
ELV-1
1"
EX.
MECH
NEW
WORK
RM.
EX.
STRS
EX.
ELEC. EX. CLG
3"
EX.
ELEV.
LOBBY
122
FUTURE
SPA
LOBBY
EX.
ELEV
9' - 0"
2"
EXIST. CLG
0"
EX.
DATA
Key Plan
EX
LOBBY
135
100% CONSTRUCTION
DOCUMENTS
DTL-CLG-HEADER
1 1/2" = 1'-0"
32' - 0"
3
0' - 8"
4
DTL-CLG-CEILING TRANSITION
1 1/2" = 1'-0"
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
N
1
REFLECTED CEILING PLAN
1/8" = 1'-0"
DRAWN BY:
CHECKED BY:
ISSUE DATE:
REFLECTED CEILING
PLAN
Author
Checker
12/03/2014
A130
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
9' - 3"
CEILING PERIMETER ANGLE
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
9/16" PERIMETER ANGLE
FASTENED TO 6" FASCIA TRIM
SUSPENDED CEILING SYSTEM
NOTE: REFER REFLECTED CEILING
PLAN FOR CEILING HEIGHTS
HARD ROCK LOBBY
RENOVATION
9' - 3"
3FORM PANEL MOUNTED
WITH CONCEALED CLIPS
FINISH EXPOSED EDGES
0' - 6"
9' - 0"
0' - 3"
3FORM PANEL SCREWED TO 3 5/8" METAL FRAMING AT
2'-0" OC - RECESS SCREW HEADS FILL HOLES AND TOUCH
UP PAINT TO MATCH PREFINISHED PANEL SUSPEND FROM
STRUCTURE WITH FRAMING AND OR WIRE
1/2" GYP.
BOARD PAINTED
0' - 6"
9' - 6"
0' - 5"
0' - 3"
STRUCTURE ABOVE
0' - 3"
9' - 6"
LINEAR LED FIXTURE ON
ANGLED MOUNT
3' - 0"
PLC
0' - 9"
ROOM FINISH LEGEND
SPECIALTIES SCHEDULE
ARCHITECTURE
MARK
DESCRIPTION
MFGR.
DIVISION 6 - ARCHITECTURAL WOODWORK
BR1
METAL COUNTER SUPPORT BRACKET
GR1
3" GROMMET
DIVISION 10-FIRE PROTECTION SPECIALTIES
FE
FIRE EXTIGUISHER
FEC
FIRE EXTIGUISHER CABINET- SEMI RECESSED
DIVISION 10-SHEETWALL PROTECTION
CG1
EXTRUDED CORNER GUARD
DIVISION 12- WINDOW TREATMENTS
WB1
1" ALUMINUM MINI BLINDS
MFGR. #
DIMENSIONS
FINISH
RESPONSIBILITY
TMI SYSTEMS
DOUG MOCKETT
A7453
MM5-21
3"W x AS REQUIRED
3"
BLACK
BLACK METALLIC
CP & I
CP&I
LARSEN'S
LARSEN'S VERTICAL DUO
RE: SPECS
RE: SPECS
RE: SPECS
RE:SPECS
STAINLESS STEEL
CP & I
CP & I
KOROGARD
G825
3/4" WING
MULTIPLE-TO MATCH ADJACENT WALLS
CP&I
LEVOLOR
RIVIERA
AS REQUIRED
BRUSHED ALUMINUM
CP&I
REMARKS
PROVIDE BLOCKING
ROOM FINISH SCHEDULE
#
125
126
128
134
134.1
134.2
135
136
137
138
140
141
146
147
Name
Floor Finish
NEW OFFICE
NEW WORK RM.
EX. ELEV. LOBBY
EX. VEST.
EX. VEST
EX. VEST
EX LOBBY
TEMP COPIER
MECH
FRONT DESK
VIP CHECKIN
COPIER ROOM
CORR
TEMP DESK
CA1
CA1
STF1/STF2
STF2
STF2
STF2
ETR/STF1/STF2
CA1
SC
STF1/STF2/STF3/CA1
CA1
CA1
STF1/STF2/STF3
ST1/STF2/STF3
Base Finish
RB1
RB1
STF2
STF2
STF2
STF2
STF2
RB1
RB1
RB1/STF2
RB1
RB1
STF2
RB1/STF2
North Wall
P1
P1
WC1/WC8
ETR
WC1
WC1
WC1/WC8
P1
P1
WC1
WC1
P1
WC1/WC8
P2
East Wall
P1
P1
WC1/WC8
ETR
WC1
WC1
WC1/WC8
P1
P1
WC2/WC7
WC1
P1
WC1/WC7/WC8
P2
South Wall
P1
P1
WC1/WC8
ETR
WC1
WC1
WC1/WC8
P1
P1
WC7
WC1
P1
WC1
P2
West Wall
Ceiling Finish
P1
P1
WC6/WC8
ETR
WC1
WC1
WC1/WC8
P1
P1
NA
WC1
P1
P2/MF1/M1/M2/WC1/WC8
P2
ACT1
ACT1
CP1/CP2/FROST. ACR./GYP.
ETR
ETR
ETR
ETR
ACT1
ACT1
CP1/CP2/FROST. ACR/GYP.
ACT1
ACT1
CP1/CP2/FROST. ACR/GYP.
CP1/CP2/FROST. ACRYLIC
Comments
2
2
FLOORING
STF1
MANUFACTURER: AS REQUIRED
STYLE: GRANITE
COLOR: MATCH EXISTING BLUE PEARL-OWNER TO
APPROVE RUN
SIZE: 12"X12"
GROUT: MATCH EXISTING
STF2
MANUFACTURER: AS REQUIRED
STYLE: GRANITE
COLOR: MATCH EXISTING CREAM COLORED GRANITEOWNER TO APPROVE RUN
SIZE: 12"X12"
GROUT: MATCH EXISTING
STF3
MANUFACTURER: AS REQUIRED
STYLE: GRANITE
COLOR: MATCH EXISTING RED GRANITE (INDIAN RED
MULTI)-OWNER TO APPROVE RUN
SIZE: 12"X12"
GROUT: MATCH EXISTING
CA1
MANUFACTURER: MASLAND CONTRACT
STYLE: LINGO MODULAR
COLOR: T508-50807 SCUTTLEBUTT
SIZE: 24"X24"
INSTALLATION: QUARTERTURN
SC
SEALED CONCRETE
BASE
RB1
MANUFACTURER: ROPPE
STYLE: 4" RUBBER COVE BASE
COLOR: P100 BLACK
STF2
MANUFACTURER: AS REQUIRED
STYLE: GRANITE
COLOR: MATCH EXISTING CREAM COLORED GRANITEOWNER TO APPROVE RUN
SIZE: 4"H x AS NEEDED
CEILINGS
GYP.
GYPSUM WALL BOARD
CP1
MANUFACTURER: CHEMETAL
STYLE: POLISHED CHROME 801
SIZE: 24"X24 MOUNTED ON 3/8" PLYWOOD
GRID SYSTEM: ARMSTRONG 9/16"
COLOR: PROVIDE PLATINUM AND SILVER
SATIN SAMPLES FOR SELECTION
CP2
MANUFACTURER: 3 FORM
STYLE: RAY
COLOR: PEWTER
SIZE: 4'X8'
*MATCH PATTERN REPEAT
CP3
3/8" FROSTED ACRYLIC
ACT1
MANUFACTURER: USG CEILING SYSTEMS
STYLE: ASTRO CLIMAPLUS CEILINGS
SIZE: 24"X48"
COLOR: WHITE
GRID SYSTEM: ANGLED TEGULAR
SIZE: 15/16"
COLOR: WHITE
3
1,2,3
1,2,3
WALLS
PAINT
P1
MANUFACTURER: SHERWIN WILLIAMS
COLOR: SW7050 USEFUL GRAY
P2
MANUFACTURER: SHERWIN WILLIAMS
COLOR: 7003 TOQUE WHITE
P3
MANUFACTURER: MODERN MASTERS
STYLE: METALLIC PAINT COLLECTION
COLOR: BLACKENED BRONZE ME238 TINT
WALL FINISHES
WC1
MANUFACTURER: SOURCE ONE
STYLE: TOKAGE
COLOR: SGG-07 NEUTRA
WC2
MANUFACTURER: LANARK
STYLE: MOD
COLOR: L2-MO-10
WC3
MANUFACTURER: SOURCE ONE
STYLE: LUSTROUS
COLOR: LLU-02 SKI LIFT
WC4
NOT USED
WC5
NOT USED
WC6
MANUFACTURER: SOURCE ONE
STYLE: PRESTON
COLOR: 2VPS-03 TAUPE
WC7
MANUFACTURER: SOURCE ONE
STYLE: MEMENTO
COLOR: NME-01 PEPPER
MF1
MANUFACTURER: ADVANCED TECHNOLOGIES INC.
STYLE: MIRROFLEX, RANDOM LINES
COLOR: CROSSHATCH SILVER
SIZE: 4'X8'
*PROVIDE COORDINATING TRIM PIECES AT ALL
CORNERS, OUTSIDE/EXPOSED EDGES
M1
1/4" TEMPERED GLASS MIRROR
20 GAUGE STAINLESS STEEL FINISHED TO NO. 8
ARCHITECTURAL BRIGHT FINISH
SIZE: CUSTOM
M2
MANUFACTURER: TWO WAY MIRRORS
STYLE: GLASS 2-WAY MIRROR,
1/4" TEMPERED GLASS
SIZE: CUSTOM
METAL STUD BRACING
BACK TO STRAIGHT WALL
MILLWORK
QZ1
MANUFACTURER: DUPONT
STYLE: ZODIAQ
COLOR: LICORICE
SIZE: 3CM
PL1
MANUFACTURER: WILSONART
STYLE: 4968-38 URBAN IRON
PL2
MANUFACTURER: WILSONART
STYLE: 8826-58 NEUTRAL TWILL
MISCELLANEOUS
BO
BY OTHERS
ETR
EXISTING TO REMAIN
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
FINISHED CEILING
No.
Description
Date
INFILL AT ENDS PERFORATED METALMCNICHOLS 1433312238
FINISH: STAINLESS STEEL
KEYED FINISH REMARKS:
1.
TEMPORARY WALLS TO BE PAINTED P2 AND RECEIVE RUBBER
BASE RB1.
2.
PROVIDE WAINSCOTT W/ PATTERN CLAD IN MF1 AS SHOWN IN
ELEVATION 6, SHEET AI610 AT ALL WALLS
3.
APPROVED VENDORS FOR WATER JET CUTTING:
CRIMSON CUTTING SOLUTIONS: 918-852-4954
WATER JET WORKS: 972-991-0972
18
AI600
REVISIONS
5/8" GYP. BOARD ON
3 5/8" METAL STUD
FRAMING @ 1'-4" OC
TYP
GENERAL NOTES:
1.
ALL HOLLOW METAL DOORS, DOOR FRAMES, AND
WINDOW FRAMES TO BE PAINTED P1
2.
ALL WINDOW SILLS AND APRONS TO HAVE GYP. BOARD
RETURNS
3.
PROVIDE APPROPRIATE RUBBER TRANSITION STRIPS AT
FLOORING CHANGES
4.
MILLWORK DETAILS ARE PROVIDED AS AN OVERALL BASIS OF
DESIGN. PROVIDE MILLWORK DETAILS COMPLIANT WITH
SPECIFICATIONS AND TYPICAL CONSTRUCTION STANDARDS TO
BE APPROVED THROUGH SHOP DRAWINGS AND SUBMITTAL
PROCESS.
5.
CEILING DETAILS ARE PROVIDED AS AN OVERALL BASIS OF
DESIGN. PROVIDE CEILING DETAILS COMPLIANT WITH
SPECIFICATIONS AND TYPICAL CONSTRUCTION STANDARDS
FOR CEILINGS.
6.
PROVIDE CORNER GUARDS(CG1-REFER TO SPECIATLIES
SCHEDULE) AT ALL INTERIOR OUTSIDE CORNERS.
7.
ALL STAINED WOOD DOORS TO BE STAINED TO MATCH
EXISTING ADJACENT.
METAL STUD BRACING
BACK TO STRAIGHT WALL
SYMMETRICAL AT
OTHER END
INFILL BOTH ENDS
PERFORATED METALMCNICHOLS 1433312238
FINISH: STAINLESS STEEL
LINE OF METAL FRAMING BELOW - CUT
OUT AT GYP. BOARD FOR AIR RETURN
ONLY AT CHASE LOCATION. CUTOUT
6'-0" HIGH X 2'-0" WIDE. SET 1'-0" AFF
1/2"X1/4" GLAZING
CHANNEL BOTH SIDES TO
RETAIN INFILL PANEL
90
°
METAL STUD BRACING
BACK TO STRAIGHT WALL
0' - 4"
WRAP WALL COVERING
AROUND BACK EDGE TYPICAL
Consultants
0' - 1"
18
17
DTL-ANGLE WALL PLAN SECTION
1 1/2" = 1'-0"
1/4" MIRRORED GLASS
REF. FINISH SCHED
DTL-ANGLE WALL SECTION
3/4" = 1'-0"
1/4" MIRRORED GLASS
REF. FINISH SCHED
WAINSCOTT MAT'L
REF. FINISH SCHED.
1/4" MIRRORED GLASS
REF. FINISH SCHED
5/8" GYP BD ON MTL STUD
PROVIDE FRY REGLET 1/2",
"J" MOLD AT TOP AND BOTTOM.
FINISH: ANNODIZED
PROVIDE FRY REGLET 1/2",
"J" MOLD AT TOP AND BOTTOM.
FINISH: ANNODIZED
4" HIGH GRANITE BASE
WAINSCOT MAT'L
REF. FINISH SCHED.
5/8" GYP BD ON MTL STUD
2 LAYERS 3/4" PLYWOOD
1/4" 2-WAY MIRRORED GLASS
REF. FINISH SCHED
4" HIGH GRANITE BASE
5/8" GYP BD ON MTL STUD
0' - 0 1/4"
16
DTL PLAN - WINDOW / MIRROR TRANSITION
6" = 1'-0"
15
DTL PLAN - MIRROR / MIRROR TRANSITION
6" = 1'-0"
14
DTL SECTION - BASE / MIRROR TRANSITION
6" = 1'-0"
13
DTL SECTION - BASE / WAINSCOTT TRANSITION
6" = 1'-0"
M
1' - 1"
2' - 0"
BRACE FRAMING 4'-0" OC
ADJUSTABLE SHELVING
5/8" GYP. BOARD SUBSTRATE
0' - 5 7/8"
0' - 1"
SERVICE VALANCE ON HINGE - PERFORATED
METAL (REFER FINISH LEGEND) ADHERED TO
BLACK MELAMINE CLAD 1/2" MDF ON BLUM
FULL OVERLAY CABINET HINGES 2'-0" OC
ATTACHED TO CONTINUOUS 2X4 NAILER
PUNCH DRYWALL TO ALLOW FOR
2 WAY MIRROR. PROVIDE 1' OF
DRYWALL AT TOP AND BOTTOM AND
4" OF DRYWALL AT SIDES TO ADHERE MIRROR
TO WALL
PLANAR VIDEO SCREEN AND MOUNT BY OWNER
DIMENSIONS 43.81' W X 4.49' H X 3.32" D - VERIFY
WITH OWNER BEFORE FRAMING
2' - 1"
7' - 0"
BOX BOX FILE
1" = 1'-0"
CONTINUOUS 3/4"
PLYWOOD BACKING ON
3 5/8" METAL FRAMING
PAINT MATTE BLACK
2' - 0"
PLAM CLAD 3/4" MDF
COUNTERTOP, SPLASH,
AND NOSING
2-WAY MIRROR-M2
5/8" GYP. BOARD SUBSTRATE
5/8" GYP. BOARD SUBSTRATE
0' - 1"
PLAM CLAD 3/4" MDF
COUNTERTOP,AND NOSING
PROVIDE GYP. BOARD RETURN AT
OFFICE SIDE OF WINDOW-TOP, BOTTOM,
AND SIDES
2X6 METAL STUD FRAMING
PLAM CLAD FILE DRAWER
SCHEDULED
HARDWARE
Seal
2X6 METAL STUD FRAMING
0' - 10"
1/2" PLYWOOD
CLAD IN 1/8" MF1
PROVIDE FRY REGLET
"J" MOLD AT TOP, BOTTOM, AND SIDES.
FINISH: ANNODIZED
EXISTING WALL
PLAM CLAD FILE DRAWER
SCHEDULED BASE
1"X4" WOOD BASE
SCHEDULED BASE
PROVIDE FRY REGLET
"J" MOLD AT TOP AND BOTTOM.
FINISH: ANODIZED
10
OVERALL CASINO
9
SCREEN WALL SECTION
1 1/2" = 1'-0"
PROVIDE FRY REGLET
"J" MOLD AT TOP AND BOTTOM.
FINISH: ANNODIZED
4" HIGH GRANITE BASE
8
DTL-MLW-DECORATIVE MIRROR WALL
3/4" = 1'-0"
PLAM CLAD CABINET
DOORS
1"X4" WOOD BASE
4" HIGH GRANITE BASE
FILE FILE
1" = 1'-0"
HOTEL LOBBY
AREA OF WORK
PLAM CLAD 3/4" MDF
ADJUSTABLE SHELVING
3 5/8" METAL FRAMING WITH STUDS
AT 1'-4" OC FASTEN WALLS TOGETHER
1' - 0"
1' - 0"
1LAYER 1/2" PLYWOOD
CLAD IN MIRROR-M1
DTL-MLW-2-WAY MIRROR
3/4" = 1'-0"
SCHEDULED BASE
4" HIGH GRANITE BASE
7
N
6
DTL-MLW-DECORATIVE WALL
3/4" = 1'-0"
Key Plan
STANDARD MILLWORK-UPPER AND LOWER CABINET
1" = 1'-0"
3' - 5"
2' - 6"
3/4" PLYWOOD
TRANSACTION COUNTER
CLAD IN PLASTIC LAMINATE
3' - 6"
3MM QUARTZ
TRANSACTION COUNTER
1' - 0"
4"
1' - 0"
3' - 5"
1' - 0"
4' - 0"
3' - 6"
3/4" PLYWOOD
TRANSACTION COUNTER
CLAD IN PLASTIC LAMINATE
1' - 0"
2' - 6"
QUARTZ TRANSACTION
COUNTER
2X4 STUD FRAMING
1x4 WOOD BRACING
4" RUBBER COVE BASE
PULL OUT PRINTER TRAY ON
HEAVY DUTY FULL EXTENSION
SLIDES
4" RUBBER COVE BASE
BRUSHED 2" STAINLESS STEEL
PIPING SPLIT AND MOUNTED
TO FACE OF DESK
3' - 0"
3"
2' - 0"
LED BACK LIGHTING LOCATION
PROVIDE REMOVEABLE
MILLWORK ACCESS PANELS
FOR BACK LIGHTING
1' - 0"
SCHEDULED HARDWARE
2"
BRUSHED 2" STAINLESS STEEL
PIPING SPLIT AND MOUNTED
TO FACE OF DESK
2X4 STUD FRAMING
PLAM CLAD 3/4" PLYWOOD
FIXED SHELVING
1/4" FROSTED ACRYLIC PANEL
GT METAL AIR VENT GRILLEDOUG MOCKETT, MESH 1
SIZE: 8W"X6H"
COLOR: GRAY
2X4 STUD FRAMING
4" RUBBER COVE BASE
4
DTL-MLW-TEMP. DESK PRINTER STORAGE
1" = 1'-0"
3
DTL-MLW-TEMP. DESK COMPUTER STATION
1" = 1'-0"
4" RUBBER COVE BASE
2
DTL-MLW-CHECK-IN DESK PRINTER STORAGE
1" = 1'-0"
v.1.4_noSeal
SHEET TITLE:
1
DTL-MLW-CHECK-IN DESK COMPUTER STATION
1" = 1'-0"
SCHEDULES &
DETAILS
0'
1" = 1'
5
DTL-MLW-WAINSCOTT
3/4" = 1'-0"
PROJECT NO. 01-1305
1x4 WOOD BRACING
0"
4" HIGH GRANITE BASE
3MM GRANITE DESIGN AT
FACE OF DESK
PROVIDE ACCESS PANEL
FOR BACK LIGHTING
0' - 2"
PLAM CLAD 3/4" PLYWOOD
FIXED SHELVING
PULL OUT PRINTER TRAY ON
HEAVY DUTY FULL EXTENSION
SLIDES
PROVIDE FRY REGLET 1/2",
"J" MOLD AT TOP AND BOTTOM.
FINISH: ANNODIZED
2' - 10"
2X4 STUD FRAMING
SCHEDULED HARDWARE
PULL OUT KEYBOARD TRAY
3/4" PLYWOOD CLAD IN
PLASTIC LAMINATE
2' - 10"
1/2" PLYWOOD
CLAD IN 1/8" MF1
3/4" PLYWOOD
CLAD IN PLASTIC
LAMINATE
2' - 10"
3' - 2"
2X6 METAL STUD FRAMING
3' - 6"
LED BACK LIGHTING LOCATION
LED LIGHTING
0' - 3"
3M GRANITE DESIGN
AT FACE OF DESK
3MM QUARTZ COUNTERTOP,
SPLASH, AND NOSING
0' - 5"
LED LIGHTING
0' - 6"
1"
QUARTZ COUNTERTOP,
SPLASH, AND NOSING
2' - 10"
PULL OUT KEYBOARD TRAY
0' - 8"
0' - 6"
3/4" PLYWOOD COUNTERTOP,
NOSING, AND SPLASH CLAD
IN PLASTIC LAMINATE
SCHEDULED HARDWARE
PROVIDE FRY REGLET "T" MOLD 1/2"X1/2"
2' - 6"
3' - 6"
5/8" GYP. BOARD SUBSTRATE-CLAD IN
WALLVOVERING ABOVE WAINSCOTT
0' - 8"
0' - 8"
0' - 8"
2' - 6"
PLAM CLAD 3/4"
PLYWOOD COUNTERTOP,
SPLASH, AND NOSING
12/03/2014
2' - 10"
2' - 6"
2X6 METAL STUD FRAMING
PLAM CLAD FILE CABINET FRONTS
11
DRAWER
LINE OF JAMB BEYOND
3' - 9"
0' - 10"
1' - 0"
SCHEDULED HARDWARE
PLAM CLAD CABINET DOORS
ALIGN AND LEAVE 3/16" GAP
WRAPVWC INTO OPENING ON
ALL GYP RETURNS
4' - 6"
5' - 3 1/2"
12
CLEAR OPEN
0' - 5"
PLAM CLAD FILE DRAWER
SCHEDULED BASE
3/4" MDF SHELVING
PROVIDE GYP. BOARD RETURN AT
OFFICE SIDE OF WINDOW-TOP, BOTTOM,
AND SIDES
PLAM CLAD FILE CABINET FRONTS
1"X4" WOOD BASE
BOX HEADER TYPICAL ALL
FRAMED OPENINGS
100% CONSTRUCTION
DOCUMENTS
2' - 6"
SCHEDULED HARDWARE
NEW CEILING REFER
CEILING PLAN
2' - 6"
DRAWER
1' - 8"
1' - 0 1/4" +/-
SCHEDULED HARDWARE
DRAWN BY:
CHECKED BY:
ISSUE DATE:
Author
Checker
12/03/2014
AI600
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
PLAM CLAD 3/4" MDF
COUNTERTOP,AND NOSING
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
PROVIDE FRY REGLET 1/2",
"H" MOLD AT TOP AND BOTTOM.
FINISH: ANNODIZED
HARD ROCK LOBBY
RENOVATION
PROVIDE FRY REGLET 1/4"
OPENING "H" AND
"J" MOLDS AT PERIMETER AND
TRANSITIONS
FINISH: ANODIZED
0' - 4"
0' - 2"
5/8" GYP BD ON MTL STUD
8' - 0"
No.
D
B
3
C
A
4
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
6' - 0"
2
2
2
2
2
2
2
2
2
2
2
2
4' - 0"
3
3
3
3
3
3
3
3
3
3
3
3
NOTES
2' - 0"
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HEAD
3"
1
1
S1
1
1
1
1
1
1
1
S2
2
1
1
JAMB
ARCHITECTURE
0' - 6"
2"
3
2
1
4
4
7
2
5
5
2
1
6
4
5
FRAME
FINISH
0' - 6" 0' - 6"
1"
MATL
0' - 6"
REF. SCHED.
WD
WD
AL
WD
WD
WD
WD
WD
WD
WD
AL
WD
WD
WD
TYPE
EQ
REF. SCHED.
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
HARDWARE
SET NO.
EQ
0' - 6"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
FIRE
RATING
EQ
0' - 6"
REF. SCHED.
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
2' - 6"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
6' - 0"
6' - 0"
3' - 0"
3' - 0"
FINISH
REF. SCHED.
A
C
C
A
A
E
A
A
A
A
CC
AA
A
A
MATL
EQ
0' - 2"
0' - 2"
125
126
128
129
136
137
138
140
141A
141B
142A
142B
144
145
DOOR
THICKNESS
REF. SCHED.
REF. SCHED.
HEIGHT
0' - 2"
WIDTH
0' - 2"
REF. SCHED.
TYPE
0' - 2"
0' - 6"
DOOR SCHEDULE
DOOR
NO.
REF. SCHED.
REF. SCHED.
0' - 6"
0' - 2"
REF. SCHED.
PLC
REF. SCHED.
4"
REF. SCHED.
Description
Date
REVISIONS
D
FRAME ELEVATIONS
1/2" = 1'-0"
DOOR TYPE AA
REF. SCHED. FOR MATERIAL
TYPICAL DOOR
DOOR TYPE CC
REF. SCHED. FOR MATERIAL
TYPICAL DOOR FOR MAX VISUAL
DOOR ELEVATIONS
1/2" = 1'-0"
12' - 2"
0' - 2"
3' - 0"
0' - 2"
6' - 0"
0' - 2"
0' - 2"
REF. SCHED.
0' - 2"
2' - 9"
0' - 2"
2' - 11"
0' - 2"
2' - 9"
0' - 2"
HOLLOW METAL DOOR FRAME
3' - 10"
2' - 10"
0' - 1"
FINISH FLOOR
0' - 2"
INTERIOR
Consultants
SCHED. DOOR
2' - 10"
0' - 2"
EXTERIOR
REF. SCHED.
MTL STUD BOX HEADER
ALUM. STOREFRONT DOOR
SYSTEM
REF. SCHED.
MTL STUD FRAMING
8' - 0"
5/8" GYP. BD.
INSUL. WHERE OCCURS
3' - 10"
TO HINGE SIDE,
UNLESS OTHERWISE
INDICATED
FACE OF GYP, COUNTER, OR
OTHER PERPENDICULAR
OBJECT
0' - 2"
GYP. BD. BOTH SIDES
0'
0"
1/2" = 1'
DOOR TYPE C
REF. SCHED. FOR MATERIAL
TYPICAL DOOR
0' - 8"
0' - 2"
F
DOOR TYPE A
REF. SCHED. FOR MATERIAL
TYPICAL DOOR
FRAME TYPE 2
HOLLOW METAL FRAME
TYPICAL FOR DOUBLE LEAF DOOR
0' - 2" 0' - 2"
FRAME TYPE 1
HOLLOW METAL FRAME
TYPICAL FOR SINGLE LEAF DOOR
0' - 8"
1.
2.
3.
4.
REFERENCE THE STOREFRONT ELEVATIONS (THIS SHEET) FOR PROPER STOREFRONT SYSTEM FRAME
RELOCATE & INSTALL EXISTING HARDWARE FROM INDICATED REMOVED DOORS ON THE DEMILTION PLAN FOR DOORS
NOTED A,B,C,&D
USE ¼” TEMPERED CLEAR GLASS ALL INTERIOR LITES.
USE 1" INSULATED CLEAR TEMPERED LOW EMISSIVITY GLAZING ON ALL EXTERIOR LITES.
PANIC HARDWARE
TEMPORARILY INSTALL HOLLOW METAL DOORS FOR THE MAJORITY OF CONSTRUCTION, INSTALL SCHEDULED DOOR AT END OF
PROJECT
1' - 0"
S
0.
1' - 0"
DOOR SCHEDULE NOTES
5/8" GYP. BD.
2
INT DOOR HEAD JAMB
3" = 1'-0"
S2
INT DOOR HEAD
3" = 1'-0"
S1
STOREFRONT 2
1/2" = 1'-0"
STOREFRONT 1
1/2" = 1'-0"
1.
2.
3.
8' - 8"
WINDOW SCHEDULE NOTES
USE ¼” TEMPERED CLEAR GLASS ALL INTERIOR LITES.
USE 1" INSULATED CLEAR TEMPERED LOW EMISSIVITY
GLAZING ON ALL EXTERIOR LITES.
USE MIRRORED GLASS REF. INTERIORS.
0' - 9"
STF2
STF3
EXIST. TO
REMAIN
2' - 1"
0' - 9"
WINDOW TYPE A
ALUMINUM FRAME
2-WAY GLASS
WINDOW TYPE B
ALUMINUM FRAME
2-WAY GLASS
WINDOW ELEVATIONS
1/2" = 1'-0"
4"
W
2' - 1"
32' - 0"
STF1
CA1
0' - 4"
0' - 4"
FLOORING LEGEND
EXIST. FLOOR
TO REMAIN
3"
24' - 0"
16' - 0"
WC1/WC8
2"
EXIST. FLOOR
TO REMAIN
WC1/WC8
12' - 4"
EXIST. FLOOR
TO REMAIN
EXIST. FLOOR
TO REMAIN
WC1/WC8
EXIST. FLOOR
TO REMAIN
EXIST. FLOOR
TO REMAIN
STF1
5°
11
STF3-WATER JET CUT
0"
42' 10"
STF1
40' - 6"
5' - 6"
WITHIN THIS PERIMETER
CIRCLE-EXISTING FLOOR
TO REMAIN
STF2
WC1/WC8
40' - 6"
"
2' - 4
27' - 3"
9' - 9"
22' - 4"
28' - 10"
26' - 11"
31' - 3"
STF2
STF1
STF1
3' - 8"
STF2
STF2
EXISTING FLOOR
TO REMAIN
MF1 TO CLG
BASE-STF2
7' - 11"
STF2
STF1
3°
MF1 TO CLG
BASE-STF2
MF1 TO CLG
BASE-STF2
STF1
27°
STF2
8°
12°
6' - 3"
MF1 TO CLG
CA1
SC
CA1
CA1
MF1 TO CEILING
BASE-STF2
MF1 TO CLGCONTINUE TO
END OF RAMP WALL, BOTH SIDES
AND ENDS
BASE-STF2
100% CONSTRUCTION
DOCUMENTS
STF3-WATER JET CUT
STF2
2' - 9"
Key Plan
EXISTING FLOOR TO REMAIN
STF3-WATER JET CUT
5' - 3"
N
STF3-WATER
JET CUT
2' - 0"
6"
40' -
10' - 4"
MF1 TO CEILING
BASE-STF2
WC1/WC8
STF1
OVERALL CASINO
0'
STF1
STF2
STF2
WC1/WC8
HOTEL LOBBY
AREA OF WORK
8' - 0"
STF2
STF1
82
°
CA1
EXIST. FLOOR
TO REMAIN
STF1
1/8" = 1'
CA1
°
55
STF2
1"
CA1
9' - 2"
EXIST. FLOOR
TO REMAIN
1' - 5"
STF2
12/03/2014
1' - 3"
Seal
PROJECT NO. 01-1305
v.1.4_noSeal
1
INTERIOR FINISH FLOOR PLAN
1/8" = 1'-0"
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
INTERIOR FLR PLAN,
DOORS & WINDOWS
Author
Checker
12/03/2014
AI601
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
3
EXT STOREFRONT DOOR SILL
3" = 1'-0"
REF. SCHED.
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
HOLLOW METAL DOOR
FRAME
HARD ROCK LOBBY
RENOVATION
3 5/8" MTL STUD FRAMING @ 16"
O.C.
128
0' - 2"
CONCRETE SLAB
142A
8' - 8"
SCHED. DOOR
0' - 2"
INSUL. WHERE OCCURS
2' - 0"
4
BACKER ROD &
SEALANT
PLC
Sim
8
ARCHITECTURE
AI600
No.
GYP. BOARD PONY WALL
Sim
12
COUNTER, SPLASH, NOSING-PL1
1' - 3"
SCHEDULED BASE
3' - 3"
SUPPORT BRACKET
BR1, 3'-0" O.C.-TYPICAL
1' - 2"1' - 4"
3' - 6"
SCHEDULED BASE
SUPPORT BRACKET
BR1, 3'-0" O.C.-TYPICAL
AI600
Sim
2
COUNTER, NOSING,
AND SPLASH-QZ1
2' - 10" 0' - 8"
CABINETS-PL2
INSIDE OF OPEN CABINETS/
PULL OUT DRAWERS/ADJUSTATBLE
SHELVING-PL2
2" BRUSHED STAINLESS
STEEL TUBING SPLIT
IN HALF AND ADHERED
TO ACRYLIC W/ CONSTRUCTION
ADHESIVE
12
2' - 6"
1' - 6"
1
11
AI610
1' - 0"
SCHEDULED BASE
1' - 6"
COUNTER-QZ1
Sim
2' - 1"
11
WORK ROOM 126 NORTH
1/4" = 1'-0"
PRINTER STATIONCENTER GR1-TYPICAL
Sim
3
4
AI600
COMPUTER STATIONCENTER GR1-TYPICAL
AI600
TRANSACTION TOP AND
WORK COUNTER-PL2
SPLASH-PL1
CABINETS-PL2
INSIDE OF OPEN CABINETS/
PULL OUT DRAWERS-PL2
BACKLIT 1/4" FROSTED ACRYLIC
PANEL
Sim
1' - 0"
10
CHECK-IN DESK DETAILS
1/2" = 1'-0"
9
CHECK-IN 140 NORTH
1/4" = 1'-0"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
AI600
CABINETS-PL2
Sim
7
2' - 5"
1' - 6"
2' - 10"
AI600
3' - 2"
2' - 6"
SCHEDULED BASE
1' - 6"
TEMP. CHECK-IN DESK EAST
1/4" = 1'-0"
1/2", "SNAP IN REVEALS"
FROM FRYE REGLET-TYPICAL
AI600
FRYE REGLET "J" MOLD
AT EDGE OF WALL-PATTERN
CONTINUE TO END OF WALL
2-WAY GLASS-M2
M1
1' - 6"
2-WAY GLASS-M2
Sim
9
Consultants
INSIDE OF OPEN CABINETS/
PULL OUT DRAWERS-PL2
2' - 6"
8
Sim
AI600
COLUMNS-WALL COVERING-WC3, TYPICAL
Sim
3
SPLASH-PL1
1' - 6"
TEMP. CHECK-IN DESK NE
1/4" = 1'-0"
8
FRYE REGLET "J" MOLD
AT EDGE OF WALL-PATTERN
CONTINUE TO END OF WALL
Sim
SCHEDULED BASE
2' - 6"
2" BRUSHED STAINLESS
STEEL TUBING SPLIT IN
HALF
2' - 6"
CHECK-IN 140 SOUTH
1/4" = 1'-0"
13
WORK ROOM 126 NE
1/4" = 1'-0"
Sim
AI600
GRANITE SLAB TO
MATCH STF1. DESIGN TO
BE WATER JET CUT
AI600
AI600
14
WORK ROOM 126 EAST
1/4" = 1'-0"
4
0' - 3"
0' - 3"
PRINTER STATIONCENTER GR1, TYPICAL
1' - 5"
COPMUTER STATIONCENTER GR1, TYPICAL
1' - 3"
1' - 5"
4' - 8"
1' - 6"
1' - 5"
90
°
°
79
WALLS PAINTED P2 FROM HERE
3' - 2"
2' - 10"
2' - 11"
WALL COVERING-WC1
WALL COVERING-WC6
74
°
AI600
0' - 3"
3
REVISIONS
5' - 7"
Sim
BACK LIT 1/4" THICK
FROSTED ACRYLIC
PANEL
Sim
1' - 3"1' - 3"
1' - 10"
2' - 10" 0' - 8"
GRANITE SLAB TO
MATCH STF1-ADHERE
TO ACRYLIC W/ CONSTRUCTION
ADHESIVE
3' - 7"
0' - 4"
1
0' - 3"
0' - 4"
COUNTERTOP-QZ1
15
0' - 3"
16
6' - 5"
17
SUPPORT BRACKET
BR1, 3'-0" O.C.-TYPICAL
FINISHED END PANEL-PL2
3' - 3"
WORK ROOM 126 SOUTH
1/4" = 1'-0"
AI600
SCHEDULED BASE
SCHEDULED BASE
SCHEDULED BASE
WORK ROOM 126 WEST
1/4" = 1'-0"
GYP. BOARD PONY WALL
COUNTER, SPLASH, NOSING-PL1
1' - 0"
SUPPORT BRACKET
BR1, 3'-0" O.C.-TYPICAL
2' - 6"
2' - 6"
SUPPORT BRACKET
BR1, 3'-0" O.C.-TYPICAL
2' - 6"
AI600
Sim
11
3' - 6"
AI600
BOX BOX FILE-PL2
FILE DRAWERS MUST
HOLD STANDARD SIZE
HANGING FILE FOLDER
FRAMES
2' - 10" 0' - 8"
COUNTER, SPLASH, NOSING-PL1
Sim
11
2' - 6"
AI600
BOX BOX FILE-PL2
FILE DRAWERS MUST
HOLD STANDARD SIZE
HANGING FILE FOLDER
FRAMES
AI600
BOX BOX FILE/FILE FILE-PL2
FILE DRAWERS MUST
HOLD STANDARD SIZE
HANGING FILE FOLDER
FRAMES
Date
COUNTER, SPLASH, NOSING-PL1
FILE FILE-PL2
FILE DRAWERS MUST
HOLD STANDARD SIZE
HANGING FILE FOLDER
FRAMES
2' - 6"
Sim
Description
2-WAY GLASS-M2
8' - 8"
12
99
°
Sim
12
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
3' - 3"
COUNTER, SPLASH, NOSING-PL1
DESIGN
8' - 8"
MF1
2' - 1"
1' - 10"
°
81
°
81
4' - 0"
3' - 10"
1' - 10"
4' - 0"
2' - 1"
1' - 10"
5' - 4"
WAINSCOTT(WC8)-MF1.
REFER TO DETAIL 3, SHEET
AI610. CONTINUE AROUND
PERIMETER OF ELEVATOR
LOBBY
BASE-RB1 FROM HERE
BASE-STF2 FROM HERE
SCHEDULED BASE-STF2
CHECK-IN WEST OLD
1/4" = 1'-0"
CEILING BEYOND
SCHEDULED BASE
1" GAP BETWEEN SCREEN
AND WALL OR VALANCE
FINISHED WALL
10
HINGED VALANCE
REFER SECTION
Sim
7
AI600
WALL COVERING-WC7
(22) VIDEO SCREENS
AI600
WALL COVERING AT COLUMN-WC3-TYPICAL
WC1
2' - 3"
DECORATIVE WALL
5
2' - 3"
TEMPORARY CHECKIN
DESK BEYOND
3' - 10"
4' - 6"
WAINSCOTT-MF1
Sim
WB1-MOUNTED INSIDE ROOM 126
AI600
WALL COVERING-WC1
WALLCOVERING-WC2
PL2
WRAP COLUMN
W/ WAINSCOTTWC8
SCHEDULED BASE
BASE-RB1
43' - 10"
6
3' - 7"
5
VIDEO WALL BEHIND CHECK-IN
1/4" = 1'-0"
17
WALL COVERING-WC7,
TYPICAL
WALL COVERING-WC1
CHECK-IN SOUTH
1/4" = 1'-0"
AI600
Sim
17
AI600
Sim
Sim
17
AI600
17
AI600
Sim
17
AI600
Sim
17
Sim
AI600
17
AI600
Sim
WAINSCOTT-(WC8)-MF1.
REFER TO DETAIL 3, SHEET AI610.
EXISTING STOREFRONT
GLASS WINDOWS
SLANTED WALLS
WALL COVERINGWC1-TYPICAL
Seal
12/03/2014
HOTEL LOBBY
AREA OF WORK
WALL COVERING-WC2
OVERALL CASINO
1
Sim
AI600
RECESSED FLAT SCREEN TELEVISIONS-OWNER PROVIDED,
CONTRACTOR INSTALLED. VERIFY DEPTH OF RECESS W/ OWNER
N
Key Plan
SCHEDULED BASE
SCHEDULED BASE
NEW CHECK-IN DESK
32' - 0"
CHECK-IN EAST
1/4" = 1'-0"
4"
4
COMPUTER STATIONCENTER GR1OVER EACH, TYPICAL
6' - 7"
3
WAINSCOTT-WC8
1/2" = 1'-0"
2' - 3"
1' - 0"
3' - 6"
DOOR TO EXISTING
STORAGE 145
WAINSCOTT(WC8)-MF1.
REFER TO DETAIL 3, SHEET AI610
SPLASH-PL2
CABINETS-PL2
EXISTING ELEVATORS
INSIDE OF OPEN CABINETS/
PULL OUT DRAWERS-PL2
NEW CHECK-IN DESK
SCHEDULED BASE
0' - 4"
0' - 9"
°
90
°
80
1' - 8"
WALL COVERING-WC1
TRANSACTION TOP AND
WORK COUNTER-QZ1
16' - 0"
PRINTER STATIONCENTER GR1OVER EACH, TYPICAL
3' - 2"
°
80
0' - 7"
0°
11
WALL COVERING-WC1
NEW BACKLIT COLUMN WRAP AT EXISTING
STRUCTURAL COLUMNS.
WALL COVERING-WC3-TYPICAL
8' - 0"
0°
11
°
90
24' - 0"
3"
1' - 0"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
2' - 6"
1' - 6"
CONTINUE WAINSCOTT WC8 AT COLUMN
SCHEDULED BASE
SCHEDULED BASE
PROJECT NO. 01-1305
v.1.4_noSeal
SCHEDULED BASE
SHEET TITLE:
BASE-STF2
REPETITIVE
PATTERN EVERY
6'-7"
2
CHECK-IN DESK WEST
1/4" = 1'-0"
1
CHECK-IN NORTH
1/4" = 1'-0"
INTERIOR
ELEVATIONS
0'
1' - 1"
1/8" = 1'
1' - 11"
2"
1' - 1"
2' - 10" 0' - 8"
1' - 2"
AI600
1"
PANEL MATERIAL-MF1
Sim
0"
5
100% CONSTRUCTION
DOCUMENTS
11
AI610
DRAWN BY:
CHECKED BY:
ISSUE DATE:
Author
Checker
12/03/2014
AI610
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
7
AI600
FRYE REGLET "J" MOLD
AT EDGE OF WAINSCOTT-PATTERN
CONTINUE TO END OF WALL
0' - 8"
SCHEDULED BASE-RB1
Sim
HARD ROCK LOBBY
RENOVATION
5
CHEROKEE NATION ENTERTAINMENT, LLC
777 W. CHEROKEE ST. CATOOSA, OK 74015
WALL COVERING-WC1
PLC
FIRE SPRINKLER PLAN NOTES
GENERAL: THERE IS AN EXISTING WET-PIPE SPRINKLER SYSTEM SERVING THE PROJECT
AREA. REVISE, REMOVE, REPLACE, AND/OR PROVIDE ADDITIONAL SPRINKLER HEADS AS
NOTED BELOW, AND MODIFY PIPING AS REQUIRED TO PROVIDE CODE REQUIRED COVERAGE
IN ACCORDANCE WITH NFPA-13. REFER TO ARCHITECT'S REFLECTED CEILING PLANS FOR
CEILING TYPES, MATERIAL, ELEVATION, AND OTHER FEATURES AND COMPONENTS.
A.
REMOVE EXISTING SPRINKLER HEADS AND PROVIDE UPRIGHT SPRINKLER HEADS FOR
OPEN CEILING SHELL SPACE AREAS.
B.
REMOVE EXISTING SPRINKLER HEADS AND PROVIDE SEMI-RECESSED CHROME
SPRINKLER HEADS WITH CHROME ESCUTHEONS.
C.
REMOVE EXISTING SPRINKLER HEADS AND PROVIDE FULLY CONCEALED SPRINKLER
HEADS. PROVIDE CHROME COVERPLATES FOR "MIRROR" FINISH CEILING AREAS.
PROVIDE FACTORY APPLIED CUSTOM COLOR COVERPLATES (COLOR SELECTED BY
ARCHITECT) FOR GYPSUM BOARD CEILINGS, ACRYLIC CEILINGS, AND OTHER
ARCHITECTURAL CEILING MATERIALS.
1.
RUN ALL PIPING PARALLEL OR PERPENDICULAR TO STRUCTURE IN ALL AREAS.
SPRINKLER CONTRACTOR SHALL COORDINATE LOCATION OF HORIZONTAL SPRINKLER
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
PIPING WITH OTHER TRADES TO MISS ALL LIGHT FIXTURES, DUCTS, VAV BOXES, AIR
DIFFUSERS AND ALL OTHER ITEMS WHERE CEILING CLEARANCES ARE CLOSE.
2.
DESIGN, FABRICATE, INSTALL THE FIRE PROTECTION AUTOMATIC SPRINKLER SYSTEM IN
AN ACCEPTABLE MANNER TO THE STATE HEALTH DEPARTMENT, LOCAL FIRE MARSHALL
AND THE ARCHITECT/ENGINEER.
3.
D.
ARCHITECTURE
FIRE SPRINKLER GENERAL NOTES
4.
PAY ALL PERMITS, LICENSES, FEES, DEPOSITS AND CHARGES IN CONNECTION WITH THE
WORK, EXCEPT AS NOTED HEREIN. SECURE ALL NECESSARY APPROVALS.
REVISIONS
DESIGN AND INSTALL THE SYSTEM PER THE REQUIREMENTS OF NFPA-13. ALL
DEFICIENCIES SHALL BE THE RESPONSIBILITY OF THE SPRINKLER CONTRACTOR AND
REVISE LOCATION OF EXISTING SPRINKLER HEADS AND/OR PROVIDE ADDITIONAL
HEADS AS REQUIRED TO ACCOMODATE WALL LOCATION REVISION.
ANY DEVIATIONS FROM THE REQUIREMENTS IN NFPA-13 AND/OR THE APPROVED PLANS
SHALL REQUIRE SPECIAL PERMISSION FROM THE ARCHITECT.
5.
COMPLY WITH ALL RULES, REGULATIONS, LAWS AND ORDINANCES OF THE STATE,
LOCAL, CITY OR COUNTY AUTHORITIES AND UTILITY COMPANIES.
6.
THE AUTOMATIC SPRINKLER SYSTEM SHALL BE DESIGNED, FABRICATED, INSTALLED
AND TESTED BY AN EXPERIENCED CONTRACTOR APPROVED BY THE ARCHITECT AND
LICENSED BY THE STATE TO PERFORM SUCH WORK.
7.
SUBMIT SHOP DRAWINGS TO THE ARCHITECT AND THE OWNER'S INSURANCE COMPANY
FOR APPROVAL. BEFORE BEING SENT TO THE ARCHITECT, ALL SHOP DRAWINGS MUST
BEAR THE INSURANCE SERVICE OFFICES (ISO) STAMP OF ACCEPTANCE AND THE LOCAL
AHJ STAMP OF APPROVAL.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
8.
SUBMIT COMPLETE LAYOUT DRAWING OF OVERHEAD SPRINKLER SYSTEM AND RELATED
EQUIPMENT INDICATING RELATIONSHIP OF ALL THE OVERHEAD ITEMS INCLUDING
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
CEILING AIR DIFFUSERS, LIGHTING FIXTURES, BEAMS AND ALL OTHER ITEMS. ALL
SPRINKLER HEADS SHALL BE SPACED PER NFPA.
9.
10.
PROVIDE SPRINKLER HEAD(S) FOR EACH ROOM/SPACE FOR COMPLETE PROTECTION
UNLESS NOTED OTHERWISE ON PLANS.
Consultants
A CORROSIVE-RESISTANT PLACARD SHALL BE PLACED ON THE BASE OF THE RISER
STATING THE DESIGN CRITERIA AND RESULTING DEMAND AT THE BASE OF THE RISER,
INCLUDING HOSE STREAM ALLOWANCES. ALL PIPING, FITTINGS, HANGERS, VALVES, AND
DEVICES ARE TO COMPLY WITH NFPA NO. 13.
B
HOTEL LOBBY
RENOVATION
A
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
11. PROVIDE FULLY RECESSED CONCEALED SPRINKLER HEADS IN ALL GYPSUM BOARD
CEILINGS
D
B
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
EN
KORY M.
ZEHR
G I NE ER
L I C E NS E D
S S I ON A
OFE
L
PR
22834
OK
L A H OM
A
CA5338(PE)
Seal
12/03/2014
AREA OF WORK
N
B
C
1
FIRST FLOOR FIRE PROTECTION
1/8" = 1'-0"
100% CONSTRUCTION
DOCUMENTS
Key Plan
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
FIRE PROTECTION
PLAN
Author
Checker
12/03/2014
FP100
1.
2.
3.
5.
6.
DEMOLISH EXISTING SYSTEMS, EQUIPMENT, ETC. AS NECESSARY TO MAKE WAY FOR
NEW CONSTRUCTION. AVOID DISRUPTION OF SERVICES DURING NORMAL BUSINESS
HOURS. ALL SYSTEM SHUTDOWNS SHALL BE COORDINATED WITH BUILDING OWNER
AND SCHEDULED AFTER NORMAL BUSINESS HOURS OR AS OTHERWISE APPROVED BY
OWNER.
PRIOR TO DEMOLITION, FIELD VERIFY AND IDENTIFY ANY EXISTING EQUIPMENT TO
REMAIN IN SERVICE BY SYSTEMS SHOWN TO BE DEMOLISHED. NOTIFY ENGINEER OF
ANY SUCH CONDITIONS AND REMOVE AND/OR RELOCATE THE SERVICES AS DIRECTED.
PLUMBING GENERAL NOTES
PLUMBING LEGEND
PLUMBING DEMOLITION KEYNOTES
PLC
PLUMBING DEMOLITION GENERAL NOTES
ARCHITECTURE
LINE TYPE / SYMBOL
1 REMOVE DRAIN AND CAP AND SEAL PIPING BELOW SLAB.
2 CAP DOMESTIC WATER PIPING ABOVE CEILING AT MAIN.
DESCRIPTION
SS
SANITARY SEWER
LINE TYPE / SYMBOL
D.F.U
DRAIN FIXTURE UNITS
GW
GREASE WASTE
B.F.F
BELOW FINISHED FLOOR
V
VENT
A.F.F
ABOVE FINISHED FLOOR
3. THE CONTRACTOR SHALL OBTAIN AND PAY ALL FEES RELATED TO PERMITTING, INSPECTION,
TAP-ON FEES, ETC.
DCW
DOMESTIC COLD WATER
GPM
GALLONS PER MINUTE
4. THE CONTRACTOR SHALL COORDINATE ANY PLUMBING OR PIPING SYSTEM SHUTDOWN WITH
THE OWNER A MINIMUM 48 HOURS IN ADVANCE.
DHW
DOMESTIC HOT WATER
F.L
FLOW LINE INVERT
DHWR
DOMESTIC HOT WATER
RETURN
FLOOR DRAIN (FD-1)
G
LOW PRESSURE GAS
FROST PROOF WALL
HYDRANT (FPWH-1)
MPG
MEDIUM PRESSURE GAS
HOSE BIBB (HB-1)
RD
ROOF DRAIN
LINE CAP
ORD
OVERFLOW ROOF DRAIN
FLOOR CLEANOUT (FCO-1)
/ FINISHED GRADE
CLEANOUT (FGCO-1)
FL
FIRE LINE
WALL CLEAN OUT (WCO-1) /
STACK CLEAN OUT (SCO-1
UNION
VALVE
2. THE PIPING INDICATED ON THESE PLANS IS DIAGRAMMATICAL. ALL WORK SHALL BE
COORDINATED WITH ALL OTHER TRADES PRIOR TO INSTALLATION. CONTRACTOR SHALL
COORDINATE ROUTING OF ALL PIPING WITH EXISTING CONDITIONS AND SHALL PROVIDE ANY
NECESSARY OFFSETS, REROUTING, TEES, ELBOWS, ETC. REQUIRED FOR A COMPLETE AND
COORDINATED INSTALLATION.
3 CAP VENT PIPING AT RISER ABOVE CEILING.
4 ABANDON BELOW FLOOR DOMESTIC WATER PIPING. CAP AND SEAL EACH
END BELOW SLAB.
5 REMOVE FLOOR CLEANOUT AND CAP AND SEAL PIPING BELOW SLAB
MEET WITH OWNER PRIOR TO DEMOLITION TO IDENTIFY EXISTING MATERIALS,
SYSTEMS, EQUIPMENT, ETC, ARE CONSIDERED SALVAGE OR DEBRIS. REMOVE DEBRIS
FROM SITE AND DISPOSE OF IN AN APPROVED MANNER AS DIRECTED BY
OWNER/GENERAL CONTRACTOR.
CAP AND SEAL ALL UNUSED PIPING BRANCHES IN AN APPROVED MANNER.
REPLACE ALL DAMAGED PIPE INSULATION. MATCH EXISTING OR AS SPECIFIED IN
SCHEDULE.
REMOVE ALL UNUSED PIPING, TRASH, AND NON-PLENUM RATED MATERIALS FROM
CEILING PLENUM AND CRAWLSPACE AREAS.
DESIGN
1. THE ENTIRE PLUMBING SYSTEM SHALL BE IN ACCORDANCE WITH THE CURRENT
INTERNATIONAL PLUMBING CODE, AND ALL OTHER GOVERNING STATE AND LOCAL CODES,
STATUTES, REGULATIONS, AND REQUIREMENTS OFAUTHORITY HAVING JURISDICTION.
DESCRIPTION
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
5. ALL DOMESTIC WATER, VENT, AND NATURAL GAS PIPING SHOWN IS ABOVE CEILING,
EXPOSED OVERHEAD, OR WITHIN WALLS UNLESS NOTED OTHERWISE.
6. ALL SANITARY SEWER AND OTHER WASTE PIPING SHOWN IS BELOW SLAB, BELOW FLOOR,
OR WITHIN WALLS UNLESS NOTED OTHERWISE.
REVISIONS
7. ALL PIPING PENETRATIONS THROUGH WALLS OR FLOORS SHALL BE SEALED EQUAL TO THE
RATING OF THE WALL OR FLOOR.
8. CLEAN AND DISINFECT THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH
SPECIFICATIONS AND LOCAL CODE AND HEALTH DEPARTMENT REQUIREMENTS.
9. TEST ALL PIPING SYSTEMS IN ACCORDANCE WITH SPECIFICATIONS AND AS REQUIRED BY
LOCAL CODE AND AUTHORITY HAVING JURISDICTION.
10. ANY PVC PIPE PENETRATIONS OF FIRE RATED ASSEMBLIES SHOULD BE EXTERNALLY
SLEEVED WITH STEEL, FERROUS, OR COPPER MATERIALS, SECURELY FASTENED TO THE FIRE
RATED ASSEMBLY, AND ANY SPACE BETWEEN THE SLEEVE AND THE ASSEMBLY PENETRATED
SHALL BE PROTECTED USING MATERIAL THAT CONFORMS TO ASTM E 814 OR UL 1479, SUCH
AS FIRE STOP FS-1900 OR FLAME STOPPER 5000.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
VALVE IN RISER
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
4
5
6
6.7
7
8
8.3 8.5
9
9.5
10
11
12
13
14
W
DN
V
U
1
DN
SS
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
3
HOTEL LOBBY
RENOVATION
SS
1
T
1
S
DN
S S I ON A
OFE
L
PR
R
KORY M.
ZEHR
22834
OK
2
Q.2
G I NE ER
EXISTING HOT AND COLD WATER
ABOVE CEILING TO REMAIN
EN
2
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
2
L I C E NS E D
1.5
L A H OM
A
CA5338(PE)
Seal
12/03/2014
Q
5
P
1
1
SS
1
AREA OF WORK
N.8
2
N
4
DN
Key Plan
3
DN
SS
15
N
DN
M
100% CONSTRUCTION
DOCUMENTS
1
SS
0.1
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
1
FIRST FLOOR PLUMBING DEMO
1/8" = 1'-0"
DRAWN BY:
CHECKED BY:
ISSUE DATE:
PLUMBING DEMO
PLAN
KFR
KMZ
12/03/2014
PD100
A
TAG
B
C
D
MANUFACTURER
TITUS
TITUS
TITUS
TITUS
MODEL NO.
FL-10
63FL
TMS-AA
PAR-AA
SUPPLY
RETURN / EXHAUST
SUPPLY
RETURN
SLOT
GRILLE
GRILLE
GRILLE
REFER TO PLANS
REFER TO PLANS
24"x24"
24"x24"
1/1"
--
--
--
SERVICE
TYPE
FACE SIZE OR SLOT LENGTH - IN.
NUMBER OF SLOTS / SLOT WIDTH- IN.
MOUTING TYPE
FINISH
REMARKS
HVAC GENERAL NOTES
MECHANICAL LEGEND
SURFACE
SURFACE
LAY-IN
LAY-IN
SELECTED BY ARCH
SELECTED BY ARCH
WHITE
WHITE
2
1
EXHAUST GRILLE
(CEILING MOUNTED)
TEMPERATURE SENSOR
(MOUNTED AT 48" A.F.F)
SUPPLY DIFFUSER
(CEILING MOUNTED)
DIFFUSER CALLOUT TAG
RETURN GRILLE
(CEILING MOUNTED)
EQUIPMENT OR DEVICE TAG
DUCT MOUNTED
SMOKE DETECTOR
3. ALL WORK SHALL CONFORM TO STATE AND LOCAL CODES, RULES, REGULATIONS, AND
ORDINANCES, WHICH SHALL TAKE PRECEDENCE OVER THE PLANS IF CONFLICTS EXIST
BETWEEN THEM.
AIR FLOW ARROW
MANUAL BALANCE
DAMPER
4. THE DRAWINGS INDICATE THE GENERAL LAYOUT REQUIREMENTS FOR EQUIPMENT, FIXTURES,
PIPING, DUCTWORK, ETC. FINAL LAYOUT SHALL BE MODIFIED TO FIT ACTUAL SITE CONDITIONS.
C
CONDENSATE PIPE
SIDEWALL AIR DEVICE
R
REFRIGERANT PIPE
B.O.D.
BOTTOM OF DUCT
16"ø
ROUND DUCT
B.O.B.
BOTTOM OF BEAM
16"ø
DOUBLE WALL
ROUND DUCT
A.F.F.
ABOVE FINISHED
FLOOR
CFM
STANDARD CUBIC
FEET PER MINUTE
A.F.G.
ABOVE FINISHED
GRADE
FD
FIRE DAMPER
S
?
?
?
?
?
GENERAL NOTES:
D
A. REFER TO PLANS FOR NECK SIZES.
B. REFER TO ARCHITECT'S REFLECTED CEILING PLANS TO DETERMINE SURFACE OR LAY-IN
24x12
MOUNTING FOR CEILING DIFFUSERS.
REMARKS:
1. SUBMISSION OF PROPOSAL IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER
HAS EXAMINED THE JOB SITE UNDER WHICH HE WILL BE OBLIGATED TO OPERATE SHOULD HE
BE AWARDED THE WORK UNDER THIS CONTRACT. NO EXTRA CHARGE WILL BE ALLOWED FOR
FAILURE OF ANY BIDDER TO EXAMINE THE SITE PRIOR TO BID.
THERMOSTAT
(MOUNTED AT 48" A.F.F)
T
2. ALL RECTANGULAR DUCT SIZES SHOWN ARE THE OUTSIDE METAL DIMENSIONS. DUCT
DIMENSIONS ALREADY HAVE ALLOWANCES FOR THE INSULATION LINER WHERE APPLICABLE IN
THE RECTANGULAR DUCTS. AT DUAL WALL DUCTS, THE DIMENSION SHOWN IS THE OUTSIDE
METAL DUCT SIZE AND ALREADY HAVE ALLOWANCES FOR THE INSULATION THICKNESS.
5. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. CONTRACTOR
SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF MATERIALS.
PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT, AND TRANSFER TO POINT OF
INSTALLATION OF ANY OWNER FURNISHED ITEMS.
RECTANGULAR DUCT
(FIRST DIMENSION,
SIDE SHOWN)
TYPE 66 FLANGED BORDER WITH CONCEALED MOUNTING, TYPE-SXX END CAPS
H
ARCHITECTURE
No.
Description
INSULATION TYPE
REVISIONS
8. USE FLEX DUCTS FOR DUCT RUNOUTS TO CEILING DIFFUSERS, EXCEPT USE RIGID ELBOW FOR
FINAL CONNECTION TO ALL CEILING DIFFUSERS. LIMIT TO 6' MAX. LENGTHS, EXCEPT NO FLEX
DUCT ALLOWED ABOVE GYP. CEILINGS.
HUMIDISTAT
(MOUNTED AT 48" A.F.F)
9. PROVIDE A COMPLETE AND OPERATING MECHANICAL SYSTEM, INCLUDING ALL INCIDENTAL
ITEMS AND CONNECTIONS NECESSARY FOR PROPER OPERATION OR CUSTOMARILY INCLUDED,
EVEN THOUGH EACH AND EVERY ITEM MAY NOT BE INDICATED.
ROUND WRAPPED OR RECTANGULAR LINED, AS
INDICATED ON PLANS.
FIBERGLASS WRAP OR MATTE
FACED FIBERGLASS LINER
2" WRAP OR
1" LINER
ALL RUNOUTS TO SUPPLY DIFFUSERS AND RETURN
GRILLES CONCEALED ABOVE CEILINGS
ROUND WRAPPED OR RECTANGULAR LINED, AS
INDICATED ON PLANS.
FIBERGLASS WRAP OR MATTE
FACED FIBERGLASS LINER
2" WRAP OR
1" LINER
SUPPLY AIR SLOT DIFFUSER PLENUMS
RECTANGULAR LINED
MATTE FACED FIBERGLASS LINER
1" LINER
TRANSFER AIR DUCT
RECTANGULAR LINED
MATTE FACED FIBERGLASS LINER
1" LINER
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
11. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS OR
WALLS, THE SLEEVES SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL
LISTED AND ACCEPTED BY LOCAL AUTHORITIES HAVING JURISDICTION (AHJ) AS BEING
SUITABLE FOR THIS SERVICE SUCH AS DOWN CORNING CORP "SILICONE ELASTOMER, RTV
FOAM, OR SIMILAR MATERIAL TO MAINTAIN FIRE RATING OF THE WALL OR FLOOR.
INSULATION THICKNESS
ALL LOW PRESSURE CONSTANT VOLUME SUPPLY AIR
DUCT FROM AIR HANDLER OR PACKAGED UNIT
Date
7. PROVIDE BALANCE DAMPERS AT ALL SUPPLY AND RETURN DUCT RUNOUTS TO GRILLES AND
DIFFUSERS. LOCATE AS FAR AS POSSIBLE FROM GRILLES IN AN ACCESSIBLE LOCATION.
PROVIDE ACCESS PANELS IN SOLID WALLS AND CEILINGS FOR BALANCING DAMPERS.
MECHANICAL DUCTWORK AND INSULATION SCHEDULE
DUCT TYPE
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
10. REFER TO ARCH. PLANS AND DETAILS FOR EXACT LOCATION OF ALL WALL AND CEILING
MOUNTED DEVICES. ADJUST LOCATION OF SIDEWALL DEVICES AS NECESSARY TO AVOID
INTERFERENCE WITH MOLDING OR OTHER ELECTRICAL DEVICES.
SERVICE
DESIGN
6. IN CASES OF EQUIPMENT SUBSTITUTION, CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT
ALL SYSTEMS AND COMPONENTS WILL FIT PROPERLY PRIOR TO FABRICATION OR ORDERING.
INSTALLED DUCTS MAY BE RESIZED BY THE CONTRACTOR TO FIT FIELD CONDITIONS AS LONG
AS THE INSTALLED DUCTS SHALL HAVE EQUAL FRICTION LOSS TO THOSE SHOWN.
RECTANGULAR DUCTS SHALL NOT BE CHANGED TO ROUND DUCTS. PROVIDE COMPLETE
SHEET METAL SHOP DRAWINGS TO ENGINEER SHOWING ACTUAL DUCT SIZES,
ARRANGEMENTS, AND UNIT LOCATIONS TO BE INSTALLED. THIS SHALL BE DONE PRIOR TO
FABRICATION OR INSTALLATION.
1. PROVIDE ALL ALUMINUM CONSTRUCTION.
2. PROVIDE CONTINUOUS SLOT FACE WITH ACTIVE SUPPLY SECTIONS AS NOTED ON PLANS. HIGH THROW PATTERN CONTROLLER
PLC
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
12. CONTRACTOR SHALL NOT INSTALL ANY MAINTENANCE ITEMS ABOVE HARD CEILINGS.
THIS SHALL INCLUDE VALVES, DAMPERS, OR ANY OTHER ITEMS THAT REQUIRE ACCESS
AFTER CONSTRUCTION IS COMPLETED. IF INSTALLATION ABOVE A HARD CEILING OF
THESE ITEMS CANNOT BE AVOIDED, THEN PROVIDE CEILING ACCESS DOORS EQUAL TO
ACUDOR MODEL FW-505 WHERE REQUIRED. AT FIRE-RATED WALLS, USE EQUIVALENT
OF ACUDOR MODEL FB-5060. MINIMUM SIZE SHALL BE 12"x12". USE 18"x18" WHEN
PERSONNEL ACCESS IS REQUIRED. COORDINATE WITH ARCHITECT PRIOR TO START OF
WORK.
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
13. PROVIDE AN INSULATED BACK ON ALL THERMOSTATS AND TEMPERATURE SENSORS THAT
ARE MOUNTED ON CMU OR HOLLOW WALLS. PROVIDE SHALLOW DEVICE EXTENSION BOX
BEHIND T-STATS AND SENSORS ON MASONRY WALLS.
1.
DEMOLISH EXISTING SYSTEMS, EQUIPMENT, ETC. AS NECESSARY TO MAKE WAY FOR NEW
CONSTRUCTION. AVOID DISRUPTION OF SERVICES DURING NORMAL BUSINESS HOURS. ALL SYSTEM
SHUTDOWNS SHALL BE COORDINATED WITH BUILDING OWNER AND SCHEDULED AFTER NORMAL
BUSINESS HOURS OR AS OTHERWISE APPROVED BY OWNER.
2.
PRIOR TO DEMOLITION, FIELD VERIFY AND IDENTIFY ANY EXISTING EQUIPMENT TO
REMAIN IN SERVICE BY SYSTEMS SHOWN TO BE DEMOLISHED. NOTIFY ENGINEER OF
ANY SUCH CONDITIONS AND REMOVE AND/OR RELOCATE THE SERVICES AS DIRECTED.
3.
MEET WITH OWNER PRIOR TO DEMOLITION TO IDENTIFY EXISTING MATERIALS, SYSTEMS,
EQUIPMENT, ETC, ARE CONSIDERED SALVAGE OR DEBRIS. REMOVE DEBRIS FROM SITE AND
DISPOSE OF IN AN APPROVED MANNER AS DIRECTED BY OWNER/GENERAL CONTRACTOR.
4.
PATCH AND REPAIR ALL UNUSED OPENINGS IN DUCTWORK. SEAL OPENINGS AIRTIGHT AND
PROVIDE A SMOOTH UNOBSTRUCTED SURFACE INSIDE THE DUCT. REPLACE ALL DAMAGED
DUCT INSULATION. MATCH EXISTING OR AS SPECIFIED IN SCHEDULE.
5.
CAP AND SEAL ALL UNUSED PIPING BRANCHES IN AN APPROVED MANNER. REPLACE
ALL DAMAGED PIPE INSULATION. MATCH EXISTING OR AS SPECIFIED IN SCHEDULE.
6.
REMOVE ALL UNUSED DUCTWORK , TRASH, AND NON-PLENUM RATED MATERIALS FROM
CEILING PLENUM.
7.
PROVIDE TEMPORARY FILTER ON RETURN AIR GRILLES AND OPENINGS DURING CONSTRUCTION.
8.
CLEAN SURFACES AND REPAINT AS NECESSARY TO RESTORE FINISH TO NEW ALL DIFFUSERS
AND GRILLES NOTED TO BE REUSED.
45° TAKE-OFF FITTING CAN BE
PURCHASED AS FLEXMASTER
MODEL "STO" OR EQUIVALENT
MAIN L.P. SUPPLY AIR DUCT
MAIN TRUCK
SUPPLY DUCT
G I NE ER
CONICAL SPIN-IN
WITH BALANCE DAMPER
S S I ON A
OFE
L
PR
AIRFLOW
EN
SLOT DIFFUSER/RETURN
GRILLE PLENUM
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
FLEX DUCT, MAX. 6'-0" LENGTH
FLEX DUCT SIZE SHALL MATCH
NECK SIZE OF DIFFUSER
L I C E NS E D
USE RIGID ELBOW TO MAKE
FINAL CONNECTION TO DIFFUSER
HOTEL LOBBY
RENOVATION
HVAC DEMOLITION GENERAL NOTES
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
14. ANY PVC PIPE PENETRATION OF FIRE RATED ASSEMBLY SHOULD BE EXTERNALLY
SLEEVED WITH STEEL, FERROUS, OR COPPER MATERIALS, SECURELY FASTENED TO THE
FIRE RATED ASSEMBLY, AND ANY SPACE BETWEEN THE SLEEVE AND THE ASSEMBLY
PENETRATED SHALL BE PROTECTED USING MATERIAL THAT CONFORMS TO ASTME 814
OR UL 1479, SUCH AS FIRE STOP FS-1900 OR FLAME STOPPER 5000.
KORY M.
ZEHR
22834
OK
45°
PROVIDE MFR.'S SEAL
PLATE/GASKET AT SLOT
PLENUM PENETRATION.
*
L A H OM
A
CA5338(PE)
Seal
12/03/2014
L.P. BRANCH DUCT
HARD CEILING
NOTE: FOR REMOTE DAMPERS SERVING
OTHER THAN SLOT DIFFUSERS, ROUTE
CABLE OPERATOR TO CEILING CUP OR
MOUNTING PLATE ABOVE CEILING IN AN
ACCESSIBLE LOCATION.
DRAW BAND WITH
SILICONE SEALER
HAND VOLUME
DAMPER
MANUAL BALANCE DAMPER AT ALL
DIFFUSER RUNOUTS. DAMPER TO HAVE
NYLON BEARINGS AND DAMPER LEVER
TO EXTEND OUTSIDE OF DUCT WRAP
AREA OF WORK
CEILING
CEILING DIFFUSER
N
CABLE OPERATOR ACCESSIBLE
THRU FACE SLOT. ADJUSTABLE
WITH SCREWDRIVER.
AFIX MFR.'S ANGLE BRACKET
TO INSIDE OF PLENUM.
* - EQUALS WIDTH OF BRANCH DUCT UP TO 12".
12" FOR ALL BRANCH DUCTS LARGER THAN 12".
Key Plan
1
REMOTE CABLE OPERATED DAMPER
N.T.S
2
TYPICAL DIFFUSER CONNECTION
N.T.S
3
TYPICAL SUPPLY AIR BRANCH DUCT TAKE-OFF
N.T.S
100% CONSTRUCTION
DOCUMENTS
ROTO-TWIST
WORM GEAR
ASSEMBLY
ROTO-TWIST CABLE. PROVIDE
LENGTH AS REQUIRED AND
INTERMEDIATE CABLE SUPPORTS/
RETAINERS PER MFR.
RECOMMENDATIONS
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
MECHANICAL
NOTES, SCHEDULES,
DETAILS & LEGEND
MBW
KMZ
12/03/2014
M000
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
HVAC DEMOLITION KEYNOTES
1 EXISTING DIFFUSER TO REMAIN.
2 EXISTING HEAT PUMP AND ASSOCIATED DUCTWORK TO REMAIN UNLESS
NOTED OTHERWISE.
3 REMOVE EXISTING DIFFUSER AND ASSOCIATED BRANCH DUCT. PROPERLEY
CAP AND SEAL DUCT TO REMAIN AIR TIGHT IN AN APPROVED MANNER.
4 REMOVE EXISTING RETURN / TRANSFER GRILLE.
5 REMOVE AND RELOCATE EXISTING THERMOSTAT REFER TO M100.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
6 EXISTING TEMPERATURE SENSOR TO REMAIN.
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
2
3
4
5
6
6.7
7
8
8.3 8.5
9
9.5
10
11
12
13
14
W
DN
V
2
2
2
5
T
4
4
5
DN
T S
2
6
1
4
1
4
4
T
4
3
5
6
1
T
S
2
S
2
DN
4
3
1
1
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
U
HOTEL LOBBY
RENOVATION
4
1
3
5
T
1
T
3
5
3
3
3
3
R
3
3
Q.2
3
3
3
3
3
3
3
3
3
T
S S I ON A
OFE
L
PR
5
3
P
3
3
22834
N.8
3
3
3
KORY M.
ZEHR
OK
3
3
G I NE ER
3
Q
3
EN
3
3
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
1.5
L I C E NS E D
1
L A H OM
A
CA5338(PE)
3
3
3
6
S
T
6
S
T
5
5
6
2
Seal
DN
S
T
12/03/2014
DN
3
3
3
3
3
5
AREA OF WORK
2
15
M
1
FIRST FLOOR HVAC DEMO
1/8" = 1'-0"
N
N
DN
Key Plan
100% CONSTRUCTION
DOCUMENTS
0.1
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
MECHANICAL DEMO
PLAN
Author
Checker
12/03/2014
MD100
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
HVAC KEYNOTES
1 EXISTING DUCTWORK TO REMAIN.
2 EXISTING DIFFUSER AND ASSOCIATED
DUCTWORK TO REMAIN.
3 CONNECT NEW DUCTWORK TO EXISTING DUCTWORK.
REFER TO PLANS FOR SIZES
4 4'-0" LONG ACTIVE SUPPLY SECTION WITH FIELD
FABRICATED PLENUM.
5 3--0" LONG ACTIVE SUPPLY SECTION WITH FIELD
FABRICATED PLENUM.
6 PROVIDE MANUFACTURERS BLANK OFF PANEL ON
INACTIVE SLOT SECTION.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
1
1.5
2
3
4
5
6
6.7
7
8
8.3 8.5
9
9.5
10
11
12
13
14
Consultants
W
DN
V
A
EXISTING HEAT
PUMP TO REMAIN
U
EX. DATA
122
DN
D
1
2
T
175 CFM
4
2
3
3
FUTURE SPA
144
2
D
1
150
8"ø
2
2
C
3
CORR
127
EX. ELEV. LOBBY
128
3
2
EXISTING JEWELRY
STORE
143
EX. STRS
133
3
EX. FIRE
124
1
FUTURE SPA LOBBY
142
WOMEN
119
EX. MECH
123
200
8"ø
2
150
8"ø
20"x14"
NEW OFFICE
125
D
3
TEMP COPIER
136
170 CFM
NEW WORK RM.
126
4
T
12"x14"
EXPANDED FITNESS
117
29'-4"
CONTINUOUS
SLOT
175 CFM
4
CORR
146
4
175 CFM
4
3
Q.2
14"x14"
T
18"x16"
VIP CHECKIN
140
B
P
14"x14"
200 CFM
20"x14"
4
N.8
T
FRONT DESK
138
20"x14"
14"x14"
S S I ON A
OFE
L
PR
DN
210 CFM
4
EX. STOR.
145
G I NE ER
18"x16"
47'-10"
A
210 CFM
CONTINUOUS
SLOT
4
COPIER ROOM
B (2) 16X30
141
EXIST. MECH
139
16"x16"
4' - 0"
EX LOBBY
135
Q
170 CFM
8' - 0"
14"x14"
4
A
T
A
175 CFM
4
170 CFM
5
6
R
EN
175 CFM
4
6
CORR
146 170 CFM
4
12"x14"
T
170 CFM
16"x14"
3
18"x14"
EX. ELEV
ELV-3
29'-0"
CONTINUOUS
SLOT
A
T
TEMP DESK
147
S
DN
A
3
1
T
EX. VEST
134.2
EX. STOR.
129
3
T
A
EX. VEST.
134
EX. ELEV
ELV-2
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
400
CFM
EX. ELEC.
130
EX. ELEV
ELV-1
L I C E NS E D
2
3
59'-0"
CONTINUOUS
SLOT
1
10"ø
ELECTRICAL
121
MEN
120
EXISTING
HEAT PUMP
TO REMAIN
1
KORY M.
ZEHR
22834
DN
OK
14"x14"
L A H OM
A
CA5338(PE)
3
1
1
150
8"ø
A
EXISTING HEAT
PUMP TO REMAIN
DN
15
3
RELOCATE EXISTING
THERMOSTAT (TYPICAL)
Seal
12/03/2014
N
AREA OF WORK
M
N
Key Plan
1
FIRST FLOOR HVAC
1/8" = 1'-0"
100% CONSTRUCTION
DOCUMENTS
SUPPORT
118
1
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
EXISTING HEAT
PUMP TO REMAIN
27'-0"
CONTINUOUS
SLOT
HOTEL LOBBY
RENOVATION
EXISTING HEAT
PUMP TO REMAIN
18"x14"
0.1
PROJECT NO. 01-1305
v.1.4_noSeal
SHEET TITLE:
DRAWN BY:
CHECKED BY:
ISSUE DATE:
MECHANICAL HVAC
PLAN
Author
Checker
12/03/2014
M100
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
HORN AND VISUAL STROBE
FIRE ALARM CONTRACTOR SHALL
SUBMIT FIRE ALARM DRAWINGS TO BE
APPROVED BY ENGINEER. EC SHALL BE
RESPONSIBLE FOR ANY ADDITIONAL
FIRE ALARM DEVICE ROUGH-INS AT THE
DIRECTION OF THE FIRE MARSHALL AT
FINAL INSPECTION AT NO ADDITIONAL
COST TO THE OWNER.
2. OBTAIN A FULL SET OF CONSTRUCTION DRAWINGS TO UNDERSTAND
THE FULL SCOPE OF DEMOLITION IN WALLS AND CEILINGS.
3. WHERE DEMOLITION OF LIGHTING AND DEVICES IS REQUIRED, THE
FIXTURES AND BRANCH CIRCUITS SHALL BE REMOVED IN THEIR ENTIRETY
BACK TO THE SOURCE OF ORIGIN WITHIN THE DEMOLITION AREA. THERE
ARE FIXTURES AND DEVICES OUTSIDE THE DEMO SCOPE OF WORK THAT
MAY BE FED FROM BRANCH CIRCUITS WITHIN THE DEMOLITION AREA. ANY
DEVICES OR EQUIPMENT OUTSIDE THE WORK AREA THAT IS AFFECTED
BY WORK WITHIN THE WORK AREA SHALL BE RESTORED TO FULL
WORKING CONDITION DURING AND AFTER CONSTRUCTION.
ALL EQUIPMENT SHALL BE COMPATIBLE
WITH EXISTING SYSTEM.
PROVIDE COMPLETE SCHEMATIC FIRE
ALARM WIRING DIAGRAM AS PART OF
SHOP DRAWING SUBMITTALS.
4. EXISTING SPEAKERS, AV EQUIPMENT, CARD READERS, AND FIRE
ALARM DEVICES SHALL BE RETAINED AND REUSED DURING NEW
CONSTRUCTION. COORDINATE THE NEW LOCATION OF THE SPEAKERS
AND AV EQUIPMENT WITH THE OWNER. PROVIDE NEW LOW VOLTAGE
WIRING AND ACCESSORIES AS REQUIRED TO RESTORE THESE DEVICES
BACK TO ORIGINAL WORKING ORDER.
FINAL DESIGN LAYOUT OF THE FIRE
ALARM DEVICES SHALL BE PROVIDED BY
THE FIRE ALARM SYSTEM PROVIDER.
5. IF THERE IS ANY EXISTING CONDUIT STUBBED UP THROUGH THE
FLOOR TO BE DEMOLISHED, THE CONDUIT SHALL BE CUT FLUSH WITH THE
FLOOR. COORDINATE ANY FLOOR REPAIR WITH THE FLOOR CONTRACTOR.
FIRE ALARM DEVICES
RATING
OCPD
AMPERAGE
SECONDARY SIDE
SETS OF
CONDUIT
CONDUIT
SIZE
CONDUCTOR
QTY/SIZE
GROUND
QTY/SIZE
OCPD
AMPERAGE
SETS OF
CONDUIT
CONDUIT
SIZE
3. THE CONTRACTOR SHALL SECURE ALL PERMITS OR
APPLICATIONS AND PAY ANY AND ALL FEES AS
REQUIRED.
4. CONTRACTOR TO CONFIRM EXACT LOCATION OF
EXISTING AND NEW EQUIPMENT WITH OWNERS
AGENTS.
5. CONDUIT RUNS ARE DIAGRAMMATICALLY SHOWN ON
THE DRAWINGS. FINAL ROUTING OF THE CONDUITS
SHALL BE DETERMINED BY THE ELECTRICAL
CONTRACTOR.
6. FIELD MOUNTED DEVICES SUCH AS SWITCHES,
MOTOR STARTERS, RECEPTACLES, ETC., ARE SHOWN
IN THEIR APPROXIMATE LOCATION. SWITCH
MOUNTING HEIGHT SHALL BE 48" ABOVE FINISHED
FLOOR AND RECEPTACLE MOUNTING HEIGHT SHALL
BE 18" ABOVE FINISHED FLOOR.
7. POWER WIRING SHALL BE COPPER STRANDED
CONDUCTOR WITH "THW" INSULATION RATED 600
VOLTS. MINIMUM WIRE SIZE OF POWER WIRING
SHALL BE #12 AWG. LIGHTING AND RECEPTACLE
BRANCH CIRCUIT WIRING SHALL BE #12 AWG
UNLESS OTHERWISE NOTED ON DRAWINGS OR
SCHEDULES.
8. HOME RUN CIRCUITS MORE THAN 75 FEET FROM
THE PANEL- BOARD SHALL BE MADE WITH #10
AWG OR LARGER AS REQUIRED TO LIMIT VOLTAGE
DROP TO 2% MINIMUM.
480-208/120V, 3PH, 4W TRANSFORMER FEEDER SCHEDULE
PRIMARY SIDE
2. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK,
MATERIAL, AND LABOR TO SATISFY A COMPLETE
AND WORKING SYSTEM WHETHER SPECIFIED OR
IMPLIED.
CONDUCTOR
QTY/SIZE
GROUND
QTY/SIZE
9. THE TYPE OF CONDUIT SHALL BE AS FOLLOWS FOR
ALL FEEDERS AND DISTRIBUTION CIRCUITS, UNLESS
OTHERWISE SPECIFIED.
APPLICATION
TYPE OF CONDUIT
(1) #6
BURIED IN CONCRETE OR
OUTDOORS
(4) #2/0
(1) #4
SERVICE ENTRANCE
PVC WITH GALV.
RIGID STEEL
ELBOWS
GALV. RIGID STEEL
2"
(4) #1/0
(1) #1/0
EMT
(2)
2 1/2"
(4) #3/0
(1) #1/0
SUPPLY TO DISTRIBUTION
PANELS AND HVAC EQUIPMENT
500A
(2)
3"
(4) #250 KCMIL
(1) #2/0
BRANCH CIRCUITS
EMT OR BOX
800A
(3)
3"
(4) #300 KCMIL
(1) #3/0
15 kVA
25A
(1)
3/4"
(4) #10
(1) #10
60A
(1)
1 1/4"
(4) #4
(1) #8
30 kVA
45A
(1)
1"
(4) #6
(1) #10
100A
(1)
2"
(4) #1
45 kVA
70A
(1)
1 1/4"
(4) #4
(1) #8
175A
(1)
2"
75 kVA
125A
(1)
2"
(4) #1
(1) #6
300A
(2)
112.5 kVA
175A
(1)
2"
(4) #2/0
(1) #6
400A
150 kVA
225A
(1)
2 1/2"
(4) #4/0
(1) #4
225 kVA
350A
(2)
2"
(4) #2/0
(1) #3
TRANSFORMER FEEDER SIZE GENERAL NOTES:
1. CONDUCTOR QUANTITY BASED ON 3-PHASE, 4-WIRE; FOR EQUIPMENT THAT DOES NOT REQUIRE A NEUTRAL OR IS SINGLE PHASE DEDUCT FROM
QUANTITY AS REQUIRED.
10. MC CABLE AND SER CABLE SHALL ONLY BE USED
WITH SPECIFIC PERMISSION FROM THE ENGINEER
AND ONLY WHERE ALLOWED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
11. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL
GROUNDING SYSTEMS (AS REQUIRED) IN
ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.
2. CONDUCTOR SIZES BASED ON NEC TABLE 310.16 - COPPER
60°C UP TO 100AMPS, 75°C GREATER THAN 100AMPS.
3. GROUND SIZES: PRIMARY SIDE BASED ON NEC TABLE 250.122 - COPPER / SECONDARY SIDE BASED ON NEC TABLE 250.66 - COPPER
12. ALL RECEPTACLES SHALL BE GROUNDING TYPE.
4. CONDUIT FILL BASED ON NEC ANNEX C - THW CONDUCTOR INSULATION
13. ALL RECEPTACLES INSTALLED IN BATHROOMS AND
KITCHENS SHALL HAVE GROUND-FAULT CIRCUIT
INTERRUPTER PROTECTION AS REQUIRED BY THE
NATIONAL ELECTRIC CODE.
ELECTRICAL TRANSFORMER FEEDER
SCHEDULE
20. NOT USED.
21. FIELD VERIFY LOCATIONS OF EXISTING ELECTRICAL
EQUIPMENT, INCLUDING POWER POLES, TELEPHONE
PEDESTALS, OVERHEAD AND UNDERGROUND
FEEDERS, METERS, PANELS, DEVICES, ETC. PROVIDE
FOR COORDINATION WITH EXISTING EQUIPMENT.
Consultants
QUADRUPLEX RECEPTACLE
23. PROVIDE CABLE HOOKS ABOVE CEILING ON 6'
CENTERS IN ALL CORRIDORS. MOUNT 6 INCHES
ABOVE CEILING.
SPECIAL RECEPTACLE: VERIFY NEMA TYPE WITH MANUFACTURER
24. COORDINATE MECHANICAL EQUIPMENT CONNECTION
REQUIREMENTS WITH MECHANICAL CONTRACTOR
PRIOR TO ROUGH-IN. LOCATE FEEDERS,
DISCONNECTS AND MAINTENANCE RECEPTACLES SO
THAT THEY WILL NOT INTERFERE WITH OPERATION
OR MAINTENANCE OF MECHANICAL EQUIPMENT.
DUPLEX RECEPTACLE
GFI DUPLEX RECEPTACLE
ABOVE COUNTER GFI DUPLEX RECEPTACLE
25. CONNECT EXIT LIGHTS TO UNSWITCHED PORTION OF
ADJACENT LIGHTING CIRCUIT. DO NOT SWITCH.
CEILING MOUNTED RECEPTACLE
26. EMERGENCY LIGHTS ARE SHOWN HATCHED. PROVIDE
EMERGENCY BALLAST. PROVIDE "HOT" WIRE TO
EMERGENCY BALLAST. SWITCH FIXTURE AS
INDICATED ON PLANS.
DIRECT EQUIPMENT CONNECTION: VERIFY
CONNECTION DETAILS WITH MANUFACTURER
27. COORDINATE ALL CEILING MOUNTED ELECTRICAL
ITEMS WITH OTHER DISCIPLINES AND WITH CEILING
GRID & BAR JOIST. REFER TO ARCHITECTURAL
REFLECTED CEILING PLAN.
WIRING CONCEALED IN CEILING OR WALLS. ALL WIRE IS
NUMBER #12 AWG MINIMUM.
28. WHERE RECESSED LIGHTING FIXTURES ARE
INDICATED IN A FIRE RATED CEILING, PROVIDE A
ONE HOUR RATED "TENT" FOR FIXTURE.
$
29. WHERE SHOWER LIGHT SWITCHES ARE ACCESSIBLE
FROM SHOWER, EC SHALL USE NYLON SCREWS IN
FACEPLATE.
30.
NOT USED
31. FIRE ALARM CONTRACTOR SHALL SUBMIT FIRE ALARM
DRAWINGS TO BE APPROVED BY FIRE MARSHAL. EC
SHALL BE RESPONSIBLE FOR ANY ADDITIONAL FIRE
ALARM DEVICE ROUGH-INS AT THE DIRECTION OF THE
FIRE MARSHALL AT FINAL INSPECTION AT NO ADDITIONAL
COST TO THE OWNER.
32. COORDINATE DEVICE LOCATIONS WITH MILLWORK
AND FURNITURE PLANS PRIOR TO ROUGH-IN.
LOCATIONS OF DEVICES SHOWN ON PLANS ARE
APPROXIMATE. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE DEVICE LOCATIONS
WITH ALL TRADES. DEVICES INSTALLED AT
INACCESSIBLE LOCATIONS BEHIND CABINETS OR MILL
WORK IS NOT ACCEPTABLE. COORDINATE THE
MOUNTING HEIGHT OF ALL DEVICES PRIOR TO ROUGHIN.
occ
FLOOR BOX WITH DATA: HUBBELL 3SFBSS WITH 3SFBC
COVER. EC SHALL ROUTE A 1"C FOR DATA FROM FLOOR BOX
TO NEAREST ACCESSIBLE CEILING SPACE. ON FLOOR
LEVELS WITH ACCESSIBLE SPACE BELOW USE POKE-THRU
STYLE FLOOR BOXES: HUBBELL PT2X2 SERIES.
33. LAY-IN FIXTURES IN GRID CEILINGS SHALL BE
SUPPORTED DIRECTLY FROM STRUCTURE WITH #12
AWG WIRE AT EACH CORNER. THE CEILING GRID SHALL
NOT BE USED AS THE PRIMARY MEANS OF SUPPORTING
A LAY-IN FIXTURE.
J
CONDUCTOR
QTY/SIZE
GROUND
QTY/SIZE
AMPERAGE
SETS OF
CONDUIT
CONDUIT
SIZE
CONDUCTOR
QTY/SIZE
GROUND
QTY/SIZE
15A
(1)
3/4"
(4) #12
(1) #12
225A
(1)
2 1/2"
(4) #4/0
(1) #4
20A
(1)
3/4"
(4) #12
(1) #12
250A
(1)
3"
(4) #250 KCMIL
(1) #4
25A
(1)
3/4"
(4) #10
(1) #10
300A
(2)
2"
(4) #1/0
(1) #4
S S I ON A
O FE
L
PR
D
EQUIPMENT DISCONNECT: SIZE VARIES WITH EQUIPMENT.
(1)
3/4"
(4) #10
(1) #10
400A
(2)
2 1/2"
(4) #3/0
(1) #3
40A
(1)
3/4"
(4) #8
(1) #10
450A
(2)
2 1/2"
(4) #4/0
(1) #2
45A
(1)
1"
(4) #6
(1) #10
500A
(2)
3"
(4) #250 KCMIL
(1) #2
50A
(1)
1"
(4) #6
(1) #10
600A
(2)
3"
(4) #350 KCMIL
(1) #1
60A
(1)
1 1/4"
(4) #4
(1) #10
800A
(3)
3"
(4) #300 KCMIL
(1) #1/0
70A
(1)
1 1/4"
(4) #4
(1) #8
1000A
(3)
3"
(4) #300 KCMIL
(1) #2/0
80A
(1)
1 1/2"
(4) #3
(1) #8
1200A
(3)
3 1/2"
(4) #400 KCMIL
(1) #3/0
90A
(1)
1 1/2"
(4) #2
(1) #8
1600A
(5)
3 1/2"
(4) #400 KCMIL
(1) #4/0
100A
(1)
2"
(4) #1
(1) #8
2000A
(6)
3 1/2"
(4) #400 KCMIL
(1) #250 KCMIL
125A
(1)
2"
(4) #1
(1) #6
2500A
(7)
3 1/2"
(4) #500 KCMIL
(1) #350 KCMIL
150A
(1)
2"
(4) #1/0
(1) #6
3000A
(8)
3 1/2"
(4) #500 KCMIL
(1) #400 KCMIL
175A
(1)
2"
(4) #2/0
(1) #6
3500A
(10)
3 1/2"
(4) #500 KCMIL
(1) #500 KCMIL
200A
(1)
2 1/2"
(4) #3/0
(1) #6
4000A
(10)
4"
(4) #600 KCMIL
(1) #500 KCMIL
TV
S
CEILING MOUNTED 70V SPEAKER: 14 GUAGE WIRE. USE 14/2
SPEAKER CABLE BELDON 6100FE OR EQUIVALENT CABLE IN
THE JUNCTION BOX. CONDUITS TO GO BACK TO THE IDF
(SERVER) ROOM.
TP
A/V CONTROL TOUCH PANEL AMX-MDX-1001-L, USE CAT 6
SHIELDED BLUE BELDON 1352A OR EQUIVALENT CABLE, AMX
CB-MXP10 BOX, 3/4" CONDUIT STUBBED IN JUNCTION HOOK,
CONDUITS TO GO BACK TO THE IDF (SERVER) ROOM. MOUNT
AT 54" AFF.
CR
CARD READER, INSTALLED WITH MAGNETIC LOCKS
1. CONDUCTOR QUANTITY BASED ON 3-PHASE, 4-WIRE; FOR EQUIPMENT THAT DOES NOT REQUIRE A NEUTRAL OR IS SINGLE PHASE DEDUCT FROM
QUANTITY AS REQUIRED.
3. GROUND SIZES BASED ON NEC TABLE 250.122 - COPPER
4. CONDUIT FILL BASED ON NEC ANNEX C - THW CONDUCTOR INSULATION
CA5338(PE)
12/03/2014
VIDEO DISPLAY FACEPLATE: PROVIDE 4X4 JUNCTION BOX WITH
(2) 3/4" CONDUITS (WITH PULL STRINGS) ROUTED TO ACCESSIBLE
CEILING SPACE. PROVIDE SINGLE GANG MUD RING WITH BLANK
COVER. RUN THE WIRES BACK TO THE IDF(SERVER) ROOM.
CONFIRIM HEIGHTS WITH ARCHITECT PRIOR TO ROUGH-IN.
SECURITY CAMERA: PROVIDE ONE(1) CAT6 CABLE DROP FOR
EACH SECURITY CAMERA. CONDUITS TO GO BACK TO THE IDF
(SERVER) ROOM.
FEEDER SIZE GENERAL NOTES:
2. CONDUCTOR SIZES BASED ON NEC TABLE 310.16 - COPPER
60°C UP TO 100AMPS, 75°C GREATER THAN 100AMPS.
A
AREA OF WORK
17.4. NO EQUIPMENT SHALL BE ENERGIZED UNTIL
ALL TESTS AND ADJUSTMENTS HAVE BEEN
MADE. THREE COPIES OF ALL TEST RESULTS
SHALL BE DELIVERED TO THE OWNER.
18. ALL ELECTRICAL WORK SHALL BE COORDINATED
WITH THE MECHANICAL WORK AS CALLED FOR IN
MECHANICAL SPECIFICATIONS.
L A H OM
ABOVE COUNTER PHONE/DATA: PROVIDE 4X4 JUNCTION BOX
ABOVE COUNTER WITH (2) 3/4" CONDUITS (WITH PULL
STRINGS) ROUTED TO ACCESSIBLE CEILING SPACE. PROVIDE
SINGLE GANG MUD RING WITH BLANK COVER.
17.1. THE CONTRACTOR SHALL FURNISH ALL
INSTRUMENTS AND QUALIFIED PERSONNEL OR
FIRM TO PERFORM ALL REQUIRED TESTS.
17.3. ANY CONTRACTOR FURNISHED AND/OR
INSTALLED SPLICE, RECOMMENDED VOLTAGE
AND INSULATION RESISTANCE TESTS, SHALL
BE CONNECTED OR REPLACED BY THE
CONTRACTOR AT HIS EXPENSE.
23042
OK
Seal
17. PERFORMANCE AND WITNESSING OF TESTS
Robert
Brandon
Pinkerton
ELECTRICAL LEGEND
N
30A
PHONE/DATA: PROVIDE 4X4 JUNCTION BOX AT +18" (UNO)
WITH (2) 3/4" CONDUITS (WITH PULL STRINGS) ROUTED TO
ACCESSIBLE CEILING SPACE. PROVIDE SINGLE GANG MUD
RING WITH BLANK COVER.
16. SUBMIT TO THE OWNER CERTIFICATES OF
INSPECTIONS IN DUPLICATE FROM AN APPROVED
INSPECTION AGENCY UPON COMPLETION.
17.2. ALL NEW AND RECONNECTED ELECTRICAL
CIRCUITS SHALL BE TESTED TO INSURE CIRCUIT
CONTINUITY, INSULATION RESISTANCE, PROPER
SPLICING AND GROUNDING IN ACCORDANCE
WITH THE LATEST STANDARDS AS STATED
ABOVE. BEFORE CONNECTING POWER CABLES
TO MOTORS, THE INSULATION RESISTANCE OF
ALL MOTOR WINDINGS SHALL BE TESTED IN
ACCORDANCE WITH THE ABOVE STANDARDS.
4x4 JUNCTION BOX.
G I NEER
CONDUIT
SIZE
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY
SENSOR WITH SPARE DRY CONTACTS. HUBBELL
OMNIDIARP SERIES.
EN
SETS OF
CONDUIT
SWITCH OUTLET MOUNTED AT +48". LOWER CASE LETTER,
WHEN PRESENT, INDICATES FIXTURES CONTROLLED.
ABBREVIATIONS FOR SWITCH OUTLETS
2
DOUBLE POLE SWITCH
3
3-WAY SWITCH
4
4-WAY SWITCH
D
DIMMER SWITCH (1000W MINIMUM)
OS VACANCY SENSOR
V
VOLUME CONTROL SWITCH
K
KEYED SWITCH
F
FAN SWITCH: DUAL OPERATION WITH DIMMER
15. CONTRACTOR TO CONFIRM EXACT LOCATION OF
METERS WITH ELECTRIC UTILITY.
AMPERAGE
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
ABOVE COUNTER RECEPTACLE
22. NOT USED.
14. ALL ELECTRIC MATERIALS AND EQUIPMENT FOR THE
PROJECT SHALL BE NEW AND U.L. OR EQUALLY
APPROVED.
FEEDER SCHEDULE
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
PULL STATION
1. ALL WORK IS TO BE PERFORMED IN STRICT
COMPLIANCE WITH THE NATIONAL ELECTRIC CODE,
STATE LAWS, AND ALL OTHER REGULATIONS
GOVERNING WORK OF THIS NATURE.
ABOVE FINISHED FLOOR
GROUND
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSC.
NOT IN CONTRACT
UNDERGROUND
WEATHERPROOF
ELECTRICAL CONTRACTOR
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
1. THE CONTRACTOR SHALL VERIFY ALL PANELBOARDS AND
EQUIPMENT LOCATIONS IN THE FIELD PRIOR TO START OF
CONSTRUCTION. THE EXISTING CONDITIONS AND ALL EXISTING
PANELBOARDS SHOWN ON THESE DRAWINGS ARE FROM RECORD
DRAWINGS ANS SITE OBSERVATIONS. THESE ITEMS MAY NOT REFLECT
ACTUAL AS-BUILT CONDITIONS. SUBMITTING A BID MEANS THAT YOU HAVE
ACCEPTED AND UNDERSTAND THE EXISTING SITE CONDITIONS.
AFF
GND
NEC
NEMA
NIC
UG
WP
EC
HOTEL LOBBY
RENOVATION
M
SMOKE DETECTOR
ELECTRICAL NOTES
L I C E NS E
SD
ELECTRICAL NOTES
Key Plan
100% CONSTRUCTION
DOCUMENTS
GENERAL DEMO NOTES
VISUAL STROBE
ABBREVIATIONS
ELECTRICAL FEEDER SCHEDULE
PROJECT NO. 01-1305
v.1.4_noSeal
ELECTRICAL NOTES
AND LEGEND
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E000
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
DN
REVISIONS
J
DN
POWER PLAN DEMO NOTES
EXISTING BAR: REMOVE ALL EXISTING POWER AND DATA
ASSOCIATED WITH THE REMOVAL OF THE EXISTING BAR.
EXISTING COOLER: REMOVE ALL EXISTING POWER ASSOCIATED
WITH THE REMOVAL OF THE EXISTING WALK-IN COOLER.
COORDINATE WITH THE OWNER TO RELOCATE THE COOLER AND
RECONNECT TO ELECTRICAL AS REQUIRED.
EXISTING RECEPTION DESK: REMOVE ALL POWER AND DATA
ASSOCIATED WITH REMOVAL THE EXISTING RECEPTION DESK.
DISCONNECT ALL THE CIRCUITS FEEDING THE EXISTING BAR,
LOBBY AND ANY OTHER EQUIPMENT TO BE DEMOLISHED. SAVE
THE SPACES IN THE PANEL THAT BECAME AVAILABLE DURING
DEMOLITION TO CIRCUIT DEVICES DURING THE REMODEL.
COIL EXISTING DATA CONDUITS TO THE CEILING WHERE POSSIBLE
FOR REUSE FOR NEW DATA LOCATIONS.
2.
3.
4.
5.
2
CR
1.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
DN
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
3
J
PE AV
1
AV
DN
4
5
HOTEL LOBBY
RENOVATION
DN
2
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
DN
FIRST FLOOR DEMO POWER PLAN
1/8" = 1'-0"
DN
2.
PROVIDE 6" JUNCTION BOX WITH MULTIPLE KNOCK OUTS FOR
TWO(2) 1" CONDUITS MOUNTED IN WALL. EACH 1"CONDUIT
SHALL HAVE A DC CABLE FOR POWER AND A CAT6 CABLE
FOR DATA FOR THE FLUSH MOUNTED TV IN THE VIDEO WALL.
PROVIDE DOUBLE GANG BOX WITH SINGLE MUD RING FOR 7"
AUX AV TOUCH PANELS AT THIS LOCATION FOR CONTROLLING
THE TV IN THE VIDEO WALL. ROUTE TWO 1"C UPTO
ACCESSIBLE CEILING SPACE
MC CABLE ALLOWED IN MILLWORK.
L I C E NS E
D
ELECTRICAL
EX. MECH EX. FIRE
121
FUTURE SPA
LOBBY
LH1A
123
ELV-1
23042
EX. STRS
EX. ELEC.
OK
133
130
L A H OM
A
CA5338(PE)
Seal
12/03/2014
EX. ELEV
ELV-2
+84" AFF
126
LH1A -19
TXH1
LH1A -39
NEW WORK RM.
EXISTING
JEWELRY STORE
143
128
124
142
LP
EX. ELEV
122
LH1A -15
THX2
EX. ELEV. LOBBY
TV
3.
EX. DATA
EL
EX. STOR.
NEW OFFICE
AREA OF WORK
DN
129
125
FUTURE SPA
EX. ELEV
144
N
ELV-3
TEMP COPIER
136
CORR
Key Plan
127
LH1A -17
CORR
146
COPIER ROOM
LH1A -45
CORR
146
VIP CHECKIN
EXIST. MECH
140
139
LH1A -7
141
LH1A -11
LH1A -23
LH1A -13
LH1A -29
3
EXPANDED
FITNESS
LH1B
117
TXH6
2
2
+54" AFF
+54" AFF
J
LH1A -31
LH1A -21
DN
FRONT DESK
138
DN
J
J
100% CONSTRUCTION
DOCUMENTS
1.
EH
G I NEER
DN
POWER PLAN KEYNOTES
Robert
Brandon
Pinkerton
EN
LH1A -33
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
S S I ON A
O FE
L
PR
1
PROJECT NO. 01-1305
v.1.4_noSeal
POWER PLANS
SHEET TITLE:
1
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E101
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
DN
REVISIONS
DN
TEMPORARY LIGHTING PLAN KEYNOTES
1.
REUSE TRACK LIGHTING AFTER TEMPORARY PHASE FOR
PERMANENT LIGHTING AS SHOWN IN SHEET E201: 1
DN
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
A1
Consultants
TH
TH
TH
TH
TH TH
TH
TH
TH
TH
TH
T1
T1
T1
TH
TH
TH
TH
TH
T1
T1
T1
T1
LH1B -6
LH1B -4
T1
DN
HOTEL LOBBY
RENOVATION
2
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
DN
FIRST FLOOR TEMPORARY LIGHTING PLAN
1/8" = 1'-0"
DN
D
L I C E NS E
23042
REUSE SECURITY CAMERAS AFTER TEMPORARY PHASE FOR
PERMANENT CHECK-IN DESKS AS SHOWN IN SHEET E301: 1
OK
L A H OM
A
CA5338(PE)
Seal
12/03/2014
DN
LH1A -5
AREA OF WORK
N
LH1A -43
Key Plan
LH1A -45
LH1A -41
LH1A -4
DN
DN
100% CONSTRUCTION
DOCUMENTS
1.
G I NEER
TEMPORARY POWER PLAN KEYNOTES
Robert
Brandon
Pinkerton
EN
DN
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
S S I ON A
O FE
L
PR
PROJECT NO. 01-1305
v.1.4_noSeal
1
FIRST FLOOR TEMPORARY POWER PLAN
1/8" = 1'-0"
TEMPORARY
ELECTRICAL PLANS
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E102
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
CR
LIGHTING PLAN DEMO NOTES
1.
REMOVE ALL EXISTING LIGHTING ASSOCIATED WITH THE
REMOVAL OF THE EXISTING BAR, RECEPTION DESK,
DECORATIVE COLUMNS, CEILING AND WALLS IN THE LOBBY
AND RETURN TO OWNER.
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
FIRST FLOOR DEMO LIGHTING PLAN
1/8" = 1'-0"
LIGHTING PLAN GENERAL NOTES
INTERFACE THE PROGRAMMING AND CONTROL OF THE FOLLOWING
LIGHTING ZONES WITH THE EXISTING MODERO X SERIES LIGHTING
CONTROL SYSTEM. PROVIDE ALL PROGRAMMING AND ACCESSORIES AS
REQUIRED FOR A COMPLETE INSTALLATION
a) CEILING LIGHTS - TYPE 'G1' FIXTURES
b) CEILING LIGHTS - TYPE 'H' FIXTURES
c) COLUMN LIGHTING - TYPE 'G1' FIXTURES
d) CHECK-IN DESK LIGHTING(UNDER COUNTER) - TYPE 'G1' FIXTURES
e)CHECK-IN DESK BACK LIGHTING - TYPE 'H4' FIXTURES
X1
WHERE TYPE 'H' FIXTURES ARE SHOWN IN THE DRAWINGS(TYPE
H1/H2/H3/H4), ADJUST THE LENGTHS AND USE CONNECTIONS AS NEEDED
TO FIT PROPERLY IN THE SLOTS AS PER MANUFACTURER'S
RECOMMENDATION. ALL TYPE 'H' FIXTURES ARE NOT TAGGED TO
AVOIDING OVERCROWDING IN THE SHEET.
C1
2.
4.
5.
6.
7.
8.
9.
H4
H4
TH
A1
LH1B -17
B1
B1
TH
H3
H4 H4
H4 H4
TH
H4
T1
TH
H4
H4
TH
H4
T1
TH
H1
H4 H4
H4 H4
H4
H4
B1
B1
A1
LH1B -9
A1
B1
B1
LH1B -7
B1
LH1B -8
TH
TH
LH1B -28
TH
LH1B -30
TH
TH
TH
TH
T1
T1
T1
T1
H1
LH1B -27
H4
H4
X1
H4
H4
C1
H4
H4
H2
C1
C1
9
LH1B -26
C1
H4
H4
H4
H3
H2
H4
LH1B -33
H4
H4
H4
H4
H4
H4
H4
H4
H4
H1
H4
H4
H2
C1
H4
H4
H3
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H1
H4
H1
H4
LH1B -31
H4
LH1B -11
H4
H4
H1
H4
X1
H4
H4
H2
H4
H4
H4
H4
H4
H3
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
C1
C1
LH1B -12
C1
LH1B -29
C1
H4 T1 H4
T1 H4 T1 H4
H4
H4
TH TH TH TH TH
TH
H2
H2
7
R4
D1
D1
C1
H4
LH1B -24
C1
H4
H4 H4
C1
H4
H2
C1
H4
5
H4
H4
C1
H4
H4
R4
D1
D1
H3
H3
H4
C1
H4
H3
T1
T1 H4
T1
TH
THH4
TH TH
H2
TH TH
H2
LH1B
R4
D1
R4
R4
R4
R1 D1
D1
R2
D1
R2
LH1B -15
S1
H4
H3
H4
H4
C1
H4
C1
H4
H4
H2
H4
H4
H4
H4
H2
H4
H4
H4
F1
H4
F1
D1
F1
D1
H3
H1
H4
H4
H4
H4
G1
H4
H4
H4
H4
1
2
H2
H4
H4 H4
H4
D1
H3
H4
H4
H3
H4
H2
H4
H3
H4
LH1B -23
H4
H4
H4
H4
Key Plan
X1
LH1B -3
3
LH1B -14
4
E402
F1
D1
F1
D1
F1
D1
F1
D1
F1
D1
F1
D1
F1
D1
F1
9
F1
D1
D1
3
A1
S1
H4
H2
H4
C1
LH1B -13
H4
H3
H4
LH1B -2
LH1B -25
H4
H4
H4
C1
H4
H4
H2
H3
H2
H4
H4
C1
X1
H4
H4
H4
C1
AREA OF WORK
LH1B -2
TYPE H1
C1
LH1B -2
H2
TH
H4
H4
H4
H4 H4
H2
H4
H4 H4
H4
H4
T1
H4
H4
H4
C1
H3
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
H4
C1
H4
H4
H4
H4
H4
H4
C1
H4
H4
H4
H4
H4
H3
H3
H4
H4 H2
H4
H1
H4
T1
TH
LH1B -22
H4
TH TH 8
TH TH
TH
TH
T1
TH TH TH
T1
TH TH
TH
LH1B -2
T1
TH
TH
T1
T1
T1
T1
D1
A1
4
D1
12/03/2014
LH1B -21
H4
H4
LH1B -10
T1
TH TH
LH1B -1
H4
TH
T1
T1
H4
TH
T1
Seal
H4
H4
C1
LH1B -2
TH TH TH TH TH TH
A1
A1
LH1B -2
A1
TH
A1
B1
H4
T1
N
3.
INSTALL TYPE 'G1' FIXTURE' ALONG THE ENTIRE LENGTH OF THE
CURVED CEILING SOFFIT ON BOTH SIDES. INSTALL 10199 RGB
CONTROLLER, REMOTE ELECTRONIC CLASS 2 TRANSFORMER
AND ANY OTHER COMPONENTS REQUIRED FOR THE PROPER
LIGHTING OF THE FIXTURE. LOCATE THE TRANSFORMER ABOVE
CEILING AND PROVIDE CEILING ACCESS PANEL FOR
MAINTENANCE.
INSTALL CLASS 2 TRANSFORMER 120V AC INPUT, 24V DC OUTPUT
FOR EVERY 20'(MAXIMUM) OF LED TAPE LIGHT TYPE 'G' FIXTURE.
TYPICAL FOR JUNCTION BOXES AT THE SIDES OF THE CURVED
SOFFIT.
UNDER-DESK LIGHTING: INSTALL CLASS 2 TRANSFORMER 120V
AC INPUT, 24V DC OUTPUT FOR EVERY 20'(MAXIMUM) OF LED TAPE
LIGHT(TYPE 'G1' FIXTURE) UNDER THE CHECK IN DESK IN THE
FRONT. TYPICAL FOR THE THREE JUNCTION BOXES UNDER THE
FRONT DESK. REFER TO DETAIL SHEET E402:2, SHEET E402:4 AND
E402: LUMINAIRE SCHEDULE .
REFER TO DETAILS E402: 2 AND E402:3 FOR BACK LIGHTING FOR
CHECK-IN DESKS.
COLUMN LIGHTING TYPICAL FOR JUNCTION BOXES AT THE SIDES
OF THE COLUMN NEAR CEILING: INSTALL TYPE 'G1' FIXTURE ON
THE SIDES OF THE COLUMN PER ARCHITECT'S DETAIL. INSTALL
CLASS 2 TRANSFORMER 120V AC INPUT, 24V DC OUTPUT ON EACH
SIDE OF THE COLUMN. CIRCUIT AND CONTROL ALL COLUMN
LIGHTING TOGETHER(LH1B-2).
THERE SHALL BE TWO SWITCHES AT THIS LOCATION. ONE
SWITCH SHALL CONTROL THE DECORATIVE PENDANT LIGHTS
(TYPE 'F1') AND THE OTHER SWITCH SHALL CONTROL THE
RECESSED DOWNLIGHTS(TYPE 'D1').
THERE SHALL BE TWO SWITCHES IN THIS ROOM. ONE SWITCH
SHALL CONTROL THE LINEAR RECESSED STRIP LIGHTS(TYPE 'R1')
AND THE OTHER SHALL CONTROL THE RECESSED DOWNLIGHTS
(TYPE 'D1'). TYPE 'R1' FIXTURE SHALL BE CONTINUOUS RECESSED
STRIP FIXTURE ALONG THE CEILNG AND EXTENDING DOWN
THROUGH THE WALL TOUCHING THE FLOOR. REFER TO DETAIL
E402: 5 FOR VIP CHECK-IN ROOM LIGHTING.
PROVIDE SWITCHED BREAKERS IN PANEL 'LH1B' AND CIRCUIT
TRACK LIGHTING TO IT. TYPICAL FOR ALL NEW TRACK LIGHTING.
THREE WAY SWITCHES AT THESE TWO LOCATIONS CONTROL THE
CAN LIGHTS(TYPE 'C1') IN THE CORRIDOR
X1
C1
H4
LIGHTING PLAN KEYNOTES
1.
C1
H3
H4 H1
H4 H4 H2
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
B.
X1
D1
D1
D1
D1
D1
6
E402
100% CONSTRUCTION
DOCUMENTS
A.
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
2
HOTEL LOBBY
RENOVATION
Consultants
PROJECT NO. 01-1305
v.1.4_noSeal
1
FIRST FLOOR LIGHTING PLAN
1/8" = 1'-0"
LIGHTING PLANS
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E201
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Description
Date
REVISIONS
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
CR
HOTEL LOBBY
RENOVATION
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
Consultants
M
M
DN
EH
EL
TXH1
SYSTEMS PLAN GENERAL NOTES
S
THX2
B. CONFIRM THE EXACT LOCATIONS OF THE LOW VOLTAGE DEVICES
WITH THE A/V CONTRACTOR PRIOR TO ROUGH-IN.
CR
23042
TV
LP
Robert
Brandon
Pinkerton
OK
DN
CR
C. OWNER TO FURNISH CABLING.
L A H OM
A
CA5338(PE)
CR
D. OWNER TO LOCATE AND FURNISH WIFI ACCESS AND CONNECTION
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
LH1A
G I NEER
L I C E NS E
D
S S I ON A
O FE
L
PR
EN
A. OWNER WILL PROVIDE THE LOW VOLTAGE MATERIALS.
CONTRACTOR SHALL PROVIDE A MATERIAL LIST TO THE OWNER
(QUANTITIES ETC) BASED ON THESE DRAWINGS.
S
Seal
12/03/2014
SYSTEMS PLAN KEYNOTES
AREA OF WORK
S
S
S
S
N
S
S
1
Key Plan
1
S
S
S
S
S
S
S
S
CR
LH1B
1
S
TP
CR
TP
S
S
S
S
DN
SD
CR
M
2
TXH6
DN
2
DN
100% CONSTRUCTION
DOCUMENTS
S
2.
PROVIDE TWO(2) CAT6 CABLE DROPS FOR ACCESS CONTROL
POINTS.
PROVIDE DOUBLE GANG BOX WITH SINGLE MUD RING FOR 7" AUX
AV TOUCH PANELS AT THIS LOCATION FOR CONTROLLING THE TV
IN THE VIDEO WALL. ROUTE TWO 1"C UPTO ACCESSIBLE CEILING
SPACE. MOUNT AT +54" AFF.
S
1.
PROJECT NO. 01-1305
1
FIRST FLOOR SYSTEMS PLAN
1/8" = 1'-0"
v.1.4_noSeal
SYSTEMS PLAN
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E301
PLC
ARCHITECTURE
DESIGN
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
No.
Branch Panel: LH1A
Location: ELECTRICAL 121
Supply From:
Mounting: Surface
Enclosure: Type 1
Volts: 120/208 Wye
Phases: 3
Wires: 4
Description
Date
Branch Panel: LH1B
A.I.C. Rating:
Mains Type:
Mains Rating: 250 A
Location: EXIST. MECH 139
Supply From:
Mounting: Surface
Enclosure: Type 1
Volts: 120/208 Wye
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type:
Mains Rating: 250 A
Notes:
Notes:
REVISIONS
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
Circuit Description
Spare
Spare
Temp copier room power
Copier room 141 power
Spare
Check-in desk power
Check-in desk power
Data room 122 power
Lobby power
New office 125 power
Power video wall
Check-in desk power
Spare
Spare
Check-in desk power
VIP Check in power
Data room 122 power
Spare
Spare
New work room 126 power
Temporary check in desk power
Temporary check in desk power
Temporary check in desk power
Trip
0A
0A
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
0A
0A
20 A
20 A
20 A
0A
0A
20 A
20 A
20 A
20 A
Poles
A
1
0 VA
0 VA
1
1
1
900... 0 VA
-1
1
1080... 0 VA
1
1
1
900... 0 VA
1
1
1
0 VA
0 VA
1
1
1
1080... 0 VA
1
1
1
0 VA
0 VA
1
1
1
1080... 0 VA
1
B
0 VA
C
1080...
900 VA 0 VA
0 VA
0 VA
1260...
360 VA
0 VA
0 VA
900 VA 0 VA
1500...
0 VA
1080...
0 VA
0 VA
1080...
360 VA
0 VA
0 VA
1080...
1260...
0 VA
0 VA
0 VA
540 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
1
1
1
1
1
1
1
1
1
1
1
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
Circuit Description
Spare
Temporary check in desk power
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0A
Trip
-20 A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0 VA
0 VA
Spare
Poles
-1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Total Load:
Total Amps:
5 kVA
42 A
5 kVA
43 A
0 VA
0 VA
6 kVA
53 A
1
1
1
0A
0A
0A
Spare
Spare
Spare
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Circuit Description
Junction box for ceiling(type G) lighting
Junction box for front desk(type G) lighting
Spare
Trac lighting switched breaker
Trac lighting switched breaker
Trac lighting switched breaker
Trac lighting switched breaker
VIP checkin room and other lighting
new Lighting
Check in desk back-type H4 Lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Trip
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Poles
1
1
-1
1
1
1
1
1
1
1
1
1
1
1
1
1
Spare
0A
1
Spare
0A
1
Spare
0A
1
Total Load:
Total Amps:
A
1120... 600 VA
B
C
240 VA 1252...
0 VA
1252...
1511... 1511...
906 VA 906 VA
1209... 906...
1205... 1051...
1405...
0 VA
1627...
0 VA
1680... 1680...
1735... 1797...
1728... 1691...
1814... 1680...
1637... 1701...
1805... 1835...
1779...
0 VA
1798...
0 VA
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
0A
0A
20 A
20 A
20 A
20 A
20 A
20 A
0A
0A
Circuit Description
Junction box for column (type G) lighting
Temp Track lighting
Temp track lighting
Trac lighting switched breaker
Trac lighting switched breaker
Trac lighting switched breaker
check in desk-type F1 lighting
Spare
Spare
Check in desk back - type H4 Lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Type H ceiling lighting
Spare
Spare
0 VA
0 VA
16 kVA
132 A
13 kVA
113 A
0 VA
12 kVA
100 A
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
Legend:
Load Classification
Lighting
Other
Power
Lighting - Dwelling Unit
Connected Load
28859 VA
0 VA
10060 VA
3453 VA
Demand Factor
125.00%
0.00%
100.00%
91.47%
Estimated Demand
36074 VA
0 VA
10060 VA
3159 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
42 kVA
49 kVA
118 A
137 A
Notes:
THERE ARE EXISTING LOADS CIRCUITED TO THIS PANEL, MARKED AS 'SPARE' -THEIR LOADS ARE NOT SHOWN IN THE SCHEDULES.
Connected Load
1500 VA
14940 VA
Demand Factor
100.00%
83.47%
Estimated Demand
1500 VA
12470 VA
HOTEL LOBBY
RENOVATION
Load Classification
Power
Receptacle
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
Legend:
16 kVA
14 kVA
46 A
39 A
Notes:
THERE ARE EXISTING LOADS CIRCUITED TO THIS PANEL, MARKED AS 'SPARE' - THEIR LOADS ARE NOT SHOWN IN THE SCHEDULES.
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
L I C E NS E
G I NEER
Robert
Brandon
Pinkerton
EN
D
S S I ON A
O FE
L
PR
23042
OK
L A H OM
A
CA5338(PE)
Seal
12/03/2014
AREA OF WORK
N
100% CONSTRUCTION
DOCUMENTS
Key Plan
PROJECT NO. 01-1305
v.1.4_noSeal
ELECTRICAL
SCHEDULES
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E401
PLC
ARCHITECTURE
LUMINAIRE SCHEDULE
Type
Mark
Manufacturer
Model
Lamp
COOPER LIGHTING METALUX
COOPER LIGHTING METALUX
COOPER LIGHTING
PORTFOLIO
COOPER RSA LIGHTING,
COMBO LIGHT LV SERIES
TECHLIGHTING
KICHLER LIGHTING
2GC8IC UNV LAMPS
SNF 232 -UNV AYC-CHAIN SET
LD4A 13 D010TE ERM4A13 8 35 LI
(2) 32W T8
(2) 32W T8
LED
56 VA
56 VA
22 VA
LV2010IS WH
PAR20
39 VA
88 VA
80 VA
NOTE B,C
LED
27 VA
NOTE B,C
H2
2' LINEAR LED COLOR CHANGING
10*60 BEAM ANGLE RGB
LED
35 VA
NOTE B,C
H3
3' LINEAR LED COLOR CHANGING
10*60 BEAM ANGLE RGB
LED
53 VA
NOTE B,C
H4
4' LINEAR LED COLOR CHANGING
10*60 BEAM ANGLE RGB
LED
70 VA
NOTE B,C
R1
1' RECESSED LED STRIP
Philips Lighting Color Graze
Powercore
Philips Lighting Color Graze
Powercore
Philips Lighting Color Graze
Powercore
Philips Lighting Color Graze
Powercore
GAMMALUX G-BEAM SERIES
700LSSURG S LED 3000K
24V DC DRY LOCATION RGB-4
WATTS/ FT
10*60 BEAM ANGLE RGB
LED
LED
H1
2x4 LENSED TROFFER
4' NARROW STRIPLIGHT- CHAIN HUNG
4" LED RECESSED MEDIUM BEAM
DOWNLIGHT
RECESSED PAR20 LV TRIMLESS 1 LAMP
LUMINAIRE
ULTRASLIM LED LINEAR SUSPENSION
TASKWORK LED TAPELIGHT COLOR
CHANGING
1' LINEAR LED COLOR CHANGING
LED
10 VA
R2
2' RECESSED LED STRIP
GAMMALUX G-BEAM SERIES
LED
18 VA
R4
4' RECESSED LED STRIP
GAMMALUX G-BEAM SERIES
LED
28 VA
Acuity Brands Lighting
Cooper Industries, Inc.
GB34RC2 1S0LED35 UNIV ZTVL N
REC ASLMD WH
GB34RC2 1S0LED35 UNIV ZTVL N
REC ASLMD WH
GB34RC2 1S0LED35 UNIV ZTVL N
REC ASLMD WH
ZL1N L48 5000LM L/LENS MVOLT 35K
HALO L651 MB
Cooper Industries, Inc.
Acuity Brands Lighting
HALO LA805MED NF 8 30 MB
EDG RED
D1
F1
G1
S1
T1
TH
X1
4' NARROW STRIPLIGHT-SURFACE MOUNT
SINGLE CIRCUIT TRAC- USE ENDFEED
CURRENT LIMITER
TRACHEAD
LED EDGE LIT EXIT
No.
Apparent Load Keynote
LED
42 VA
75 VA
LED
LED
18 VA
5 VA
NO SUBSTITUTIONS WILL BE ALLOWED FOR LIGHTING FIXTURES.
B.
ELECTRICAL CONTRACTOR TO ORDER LENGTHS OF THE FIXTURE BASED ON DRAWINGS AND MANUFACTURER'S INPUT.
C.
ORDER QUANTITY OF DATA ENABLER PRO CONTROLLERS ACCORDING TO MANUFACTURER'S RECOMMENDATION.
Description
Date
REVISIONS
INSTALL CONTINUOUS LED STRIP LIGHTING TYPE
'G1' FIXTURE ON FULL HEIGHT OF COVE IN THE
COLUMN . STRUCTURAL COLUMN TO REFLECT
THE LIGHT OUTSIDE THE COLUMN FROM BOTH
SIDES
CERTIFICATE OF AUTHORIZATION 5338
RENEWAL DATE: 6/30/2015
HP ENGINEERING INC.
1836 SOUTH BALTIMORE AVENUE
SUITE B
TULSA, OKLAHOMA 74119
(539) 664-4618
Consultants
1
A.
PLANNING
618 East 3rd Street
Tulsa, OK 74120
918.743.2724 (o)
918.743.2725 (f)
Type Comments
A1
B1
C1
DESIGN
COLUMN PLAN DETAIL
3" = 1'-0"
3M QUARTZ TRANSACTION
COUNTER
ROOF SPRING
14' - 0"
T.O. STUDS
10' - 0"
CONTINOUS DECORATIVE PENDANTS OF
TYPE 'F1' ABOVE THE CHECK-IN DESKS.
ONE PER COUNTER. DETAIL DOES NOT
REPRESENT THE EXACT SHAPE OF THE
FIXTURE.
LH1B-19
INSTALL FOUR CONTINUOUS LED LIGHTING
STRIPS OF TYPE 'H4' FIXTURE ON ENTIRE
LENGTH OF THE CHECK IN DESKS. PROVIDE
ACCESS PANEL FOR MAINTENANCE.
CHECK IN DESK- BACK VIEW
3/16" = 1'-0"
L I C E NS E
G I NEER
Robert
Brandon
Pinkerton
This document, and the ideas and designs incorporated herein, as an instrument of professional service, is the property of TriArch, and is not to be used, in whole or in part, for any other project, without the written authorization of TriArch.
S S I ON A
O FE
L
PR
D
3
GROUND LEVEL
0' - 0"
EN
2
FRONT DESK SECTION
1 1/2" = 1'-0"
LH1B-20
23042
OK
L A H OM
A
CA5338(PE)
Seal
12/03/2014
AREA OF WORK
N
ROOF SPRING
14' - 0"
RECESSED CAN LIGHTS OF TYPE 'D1' ABOVE THE
CHECK-IN DESKS. ONE PER COUNTER.
COORDINATE THE LOCATION WITH LOCATION OF
SECURITY CAMERA.
T.O. STUDS
10' - 0"
CONTINOUS DECORATIVE PENDANTS OF TYPE
'F1' ABOVE THE CHECK-IN DESKS. ONE PER
COUNTER. DETAIL DOES NOT REPRESENT THE
EXACT SHAPE OF THE FIXTURE.
INSTALL CONTINUOUS LED LIGHTING STRIPS
OF TYPE 'G1' FIXTURE ON ENTIRE LENGTH OF
THE CHECK IN DESKS. PROVIDE ACCESS
PANEL FOR MAINTENANCE.
4
CHECK IN DESK-FRONT VIEW
3/16" = 1'-0"
Key Plan
J
J
100% CONSTRUCTION
DOCUMENTS
LED BACK LIGHTING, TYPE 'H4'
FIXTURE ALONG THE LENGTH OF THE
COUNTER
HOTEL LOBBY
RENOVATION
RECESSED CAN LIGHTS TYPE 'D1' ABOVE THE
CHECK-IN DESKS. ONE PER COUNTER.
COORDINATE THE LOCATION WITH LOCATION
OF SECURITY CAMERA.
HARD ROCK CASINO
777 W. CHEROKEE ST. CATOOSA, OK 74015
LED LIGHTING, TYPE 'G1' FIXTURE
ACROSS THE LENGTH OF THE
COUNTER
J
GROUND LEVEL
0' - 0"
5
VIP CHECK-IN ROOM LIGHTING
PROJECT NO. 01-1305
v.1.4_noSeal
ELECTRICAL
SCHEDULES AND
DETAILS
SHEET TITLE:
DRAWN BY:
RG
BP
12/03/2014
CHECKED BY:
ISSUE DATE:
E402