International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller M. N. Eskander, M.A.Saleh, Maged N.F.Nashed, S. Amer, Department of Power Electronics & Energy Conversion Electronics Research Institute, Cairo, Egypt eskandermona@yahoo.com, salehmahmoud36@yahoo.com, amersanaa@yahoo.com, magederi@yahoo.com Abstract— The Unified Power Quality Controller (UPQC) device is an integration of a series active filter and a shunt active filter. The main purpose of a UPQC is to compensate for voltage flicker, reactive power, and harmonics. It has the capability of improving power quality at the point of installation on power distribution systems or industrial power systems. This paper utilizes the UPQC to enhance the low-voltage ride-through (LVRT) capability of the doubly fed induction generator (DFIG)-based wind energy conversion system (WECS) according to the grid connection requirement. UPQC is applied to protect the system from ground faults, allows fast restoring of generation system steady state characteristics, improves the system power factor, and prevent the system from rotor over-current and dc-link overvoltage. A comparison between the LVRT results using the UPQC and the results when using STATCOM or DVR is also presented. Index Terms— Unified Power Quality Controller, doubly fed induction generator, low-voltage ride-through, static synchronous compensators, dynamic voltage restorers, MATLAB/Simulink I. INTRODUCTION Wind power generation has been growing rapidly around the world over the past decade and has become one of the most mature renewable generation technologies. This rapid growth has motivated the establishment of grid codes for the interconnection of wind power plants. The performance of the doubly fed induction generator (DFIG) during grid faults is attracting much interest due to the proliferation of wind turbines that employ this technology. International grid codes specify that the generator must exhibit a fault-ride-through (FRT) capability by remaining connected and contributing to network stability during a fault [1]. In wind energy systems employing double fed induction generators (DFIGs), where the stator winding connects to the grid and the rotor windings are connected to the grid via back-to-back converters that control the rotor current and inject current into the grid, the Eskander et. al., system is sensitive to grid disturbances. Therefore, proper protection schemes and FRT techniques are necessary in order to withstand grid faults. Active crowbars are commonly utilized to protect the rotor-side converters (RSCs) against voltage and current transients, which are caused by voltage dips in the stator side [2-3]. When a fault happens and this crowbar is engaged, the DFIG behaves like an induction machine since the rotor winding is short-circuited by shunt resistors and the RSC is disabled. The main drawback of crowbar protection is that the DFIG consumes reactive power when it is activated and this aggravates the grid voltage dip during a fault. In [4], series dynamic resistors are utilized to restrain significant rotor currents so that the RSC and rotor circuits can be effectively protected by way of coordination control of the chopper resistor and the crowbar. However, if the wind farm is connected to a weak power network, the employment of such techniques prevents the DFIG from supplying substantial amounts of reactive power, and thus increases the chance of system instability. Other researches investigated the application of dynamic voltage restorers (DVR) to compensate for voltage sags and swells as given in [5-8]. Therefore, static synchronous compensators (STATCOMs) have been proposed to supply additional reactive power and compensate the DFIG consumption [9-13]. Nevertheless, a STATCOM is inadequate to prevent the system from either rotor over-current or dc-link overvoltage. To achieve full system protection, this scheme is usually combined with other protective elements, such as stator braking resistors and Crowbar, which increase system complexity and additional cost. In this paper protection of a grid-connected wind energy conversion system based on doubly fed induction generator (DFIG) against grid faults is proposed. To achieve full system protection a unified power quality controller UPQC is applied to protect the system from ground faults, allows fast recovery, improve power factor, and prevent the system from rotor over-current and dc-link overvoltage. PI controllers are designed to allow maximum power tracking and control the 1925 Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ application of the UPQC. Simulation results of voltages, currents, active and reactive power prove the fast recovery, lower transients, and improvement of system power quality when applying UPQC. A comparison between the system performance for LVRT when using STATCOM and DVR is given to prove the superiority of UPQC over other FACTS devices. II. SYSTEM DESCRIPTION The DFIG system is presented in Fig. 1. The system consists of a wound rotor induction generator whose Rotor circuit is connected via the slip rings and a back-to-back converter to the grid. The stator is directly connected to the grid through a three-winding transformer. The rotor side converter (RSC) is utilized to control the electromagnetic torque and the excitation of the generator, while the generator side converter (GSC) controls the dc-link voltage. Since only the slip power is handled by the converter, the power rating of the converter can be only a fraction of The rated power of the rotor converters is typically in the range of 10% as proved by the authors of this paper in a previously published research paper [14]. d ds e qs dt d qs v qs R s i qs e ds dt d v dr R r i dr dr (e r ) qr dt d qr v qr R r i qr (e r ) dr dt v ds R s i ds (1) Where vds and vqs are the d &q stator voltages, vdr and vqr are the d &q rotor voltages, ids and iqs are the d &q stator currents, idr and iqr are the d &q rotor currents, ωe is the supply angular frequency, ωr is the rotor angular frequency, λds and λqs are the d &q stator flux linkage, and λdr and λqr are the d &q rotor flux linkages: ds L s i ds L m i dr qs L s i qs L m i qr dr L m i ds L r i dr (2) qr L m i qs L r i qr Where Rs and Rr are the stator and rotor resistance, Lls and Llr are the stator and rotor leakage inductance, Lm is the magnetizing inductance, and Ls = Lls+Lm, Lr = Llr+Lm. Under stator flux-oriented control, adjustment of the rotor q-axis current controls the generator torque or the stator active power of the DFIG as Ps 3 3 Lm ( v qs i qs v ds i ds ) v qs i qr 2 2 Ls (3) On the other hand, regulating the rotor d-axis current component controls the stator reactive power as: Fig. 1 Schematic diagram of the DFIG-based wind energy generation system. The equations for the fluxes, currents, and voltages can be expressed as: Qs 3 3 Lm ( v qs i ds v ds i qs ) v qs (i mc i dr ) (4) 2 2 Ls Where ims is magnetizing current. 1926 Eskander et. al., Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ III. OUPQC MODEL The conventional UPFC, shown in Fig. 2 is the combination of two voltage source converters (VSC); one converter connected to the power system through a shunt transformer, while the second converter is inserted into the transmission line via a series transformer. The converters are connected by a common DC link. For the OUPFC proposed in this paper the common DC link is replaced by separate DC source in each converter, which allows shutting down any of two converters if not needed. This scheme also helps in reducing maintenance cost. It also allows individual dealing with each customer. Figure 3 shows the stator active and reactive power variation due to the ground fault. The small deviation from the P and Q original values, as well as the fast response is clear. It is noticed that the active power decreases slowly at the beginning of the fault, and its value reaches zero for shorter time than the ground fault duration. This is due to the series inductance of the transformer connecting the UPQC series converter to the WECS. The low value of the reactive power proves the high power factor achieved by WECS due to the presence of UPQC. 1800 1600 1400 Ps Stator P & Q 1200 1000 800 600 400 200 Qs 0 -200 0 Fig. 2 Conventional UPQC scheme. The main objective of the series converter is to produce an ac voltage of controllable magnitude and phase angle, and inject this voltage at fundamental frequency into the transmission line, exchanging real and reactive power at its ac terminals through the series connected transformer. The shunt converter provides the required real power at the dc terminals. The two converters and associated transformers are simulated with Matlab/Simulink. PI controllers are designed for each converter, and the proposed system is tested under 3-phase ground fault. IV. SIMULATION RESULTS The WECS employing the DFIG with the UPQC is modeled with Matlab/Simulink. The model incorporates two PI controllers for adjusting the amplitude and phase of the rotor injected voltage via the two converters; RSC and GSC. The injected voltage is adjusted to force the generator speed to follow the turbine rotational speed to allow maximum extraction of wind power. Another two PI controllers are tuned to control the series and parallel VSC of the UPQC. Three phase line to ground fault is applied to the proposed system from t=0.3sec for 100msec. The LVRT of the WECS-UPQC is tested at sub-synchronous speed (slip=0.045, and applied rotor voltage Vr=0.2Vs). 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Fig. 3 Stator P and Q of UPQC-WECS during fault. To verify the validity of UPQC for LVRT, the response of stator active and reactive power due to 3-phase ground fault for a WECS employing STATCOM is shown in Fig. 4. The slower LVRT and higher harmonic contents of the STATCOM-WECS is apparent. It is also noted that the reactive power magnitude is comparable to the active power magnitude, which means that the STATCOM-WECS suffers from low power factor. To verify the superiority of UPQC over DVR for LVRT, the response of stator active and reactive power due to 3-phase ground fault for a WECS employing DVR is shown in Fig. 5. The slower LVRT and higher harmonic contents of the DVR-WECS is clear. However, the reactive power is compensated due to the series coil of the DVR device. Figure 6 shows the rotor active and reactive power variation due to the ground fault. The fast recovery to the rotor applied power is clear. 1927 Eskander et. al., Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ Figure 7 shows the electric torque response of UPQC-WECS during fault. The low peak, and fast recovery from the ground fault is clear. Similar to active power response, the electric torque decreases slowly at the beginning of the fault, and its value reaches zero for shorter time than the ground fault duration. This is due to the series inductance of the transformer connecting the UPQC series converter to the WECS. 6000 2000 0 -2000 6 -4000 5 -6000 4 -8000 0 0.1 0.2 0.3 0.4 0.5 0.6 Electric Torque Stator active & reactive power 4000 0.7 Time Fig. 4 P and Q of STATCOM-WECS during fault. 3 2 4 4 x 10 1 3 0 2 -1 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Stator P &Q Time 1 Fig. 7 Torque of UPQC-WECS during fault. 0 -1 -2 -3 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time The stator current, shown in Fig.(8), reveals the fast recovery after the fault. It is noticed that the current recovery is not associated with transient peaks, which proves the benefits of using the UPQC. It is also noted that the stator current did not reach zero during ground fault, as expected. This is due to the inductance of the series transformer connected to the series converter of the UPQC. This performance allows protection to the generator windings. Fig. 5 P and Q of DVR-WECS during fault. 10 180 8 160 6 140 Pr 4 Sttaor Current Rotor P & Q 120 100 80 Qr 2 0 -2 60 -4 40 -6 20 -8 0 -20 -10 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Fig. 6 Rotor P and Q of UPQC-WECS during fault. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Fig. 8 Stator current of UPQC-WECS during fault. 1928 Eskander et. al., Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ Figure (9) shows the rotor currents for the studied system. Since stator current did not decrease during fault, consequently the rotor current is not highly affected by fault. Also the transient value is limited. Figure 11 shows the dc link current due to the 3-phase ground fault. A negative peak is noticed at the beginning of the fault. However, the magnitude of the dc current peak is 20% of the steady state dc current value. This percentage is within safety limits and hence the rotor converters could not be damaged. 10 8 1.2 6 1 4 DC-Link Current Rotor Current 0.8 2 0 -2 -4 0.6 0.4 0.2 -6 0 -8 -10 0 0.1 0.2 0.3 0.4 0.5 0.6 -0.2 0.7 Time -0.4 Fig. 9 Rotor current of UPQC-WECS during fault 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time The effect of fault on the rotor speed is shown in Fig. (10). The limited increase in the rotor speed due to the 3-phase ground fault is minimal, showing that the system is protected from overspeed. Fast recovery to the rotor speed value before the fault is clear. The speed is set by the applied rotor voltage magnitude and phase calculated to allow maximum power extraction from the wind. Fig. 11 DC link current of UPQC-WECS. Figure (12) shows the Ac line voltage due to the 3-phase ground fault. A negative peak is noticed at the edge of the fault. However, the fast recovery of the voltage peak is obvious, hence the stator coils could not be damaged. 400 200 300 180 200 Phase A Line Voltage 160 Rotor Speed 140 120 100 80 0 -100 -200 -300 60 -400 40 -500 20 0 100 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Fig. (12) AC line voltage of UPQC-WECS 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Time Fig. 10 Effect of fault on rotor speed. 1929 Eskander et. al., Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller International Electrical Engineering Journal (IEEJ) Vol. 6 (2015) No.6, pp. 1925-1930 ISSN 2078-2365 http://www.ieejournal.com/ V. CONCLUSIONS In this paper a unified power quality controller (UPQC) is applied to a wind energy conversion system employing a doubly fed induction generator to enhance the low voltage ride through of the system during 3-phase ground fault. PI controllers are used to allow variable speed operation of the DFIG for maximum wind power extraction. Other PI controllers are tuned to control the VSC of the UPQC. The proposed system is modeled using Matlab/Simulink and simulation results are presented. The results revealed the fast recovery of stator, rotor, and dc link currents to their steady state values after fault removal. The electric torque, the active and reactive stator power, and the active and reactive rotor power also reached their values prior to fault without high transients. The fast recovery of line voltage peak due to the ground fault proved the validity of UPQC. The system power factor is high, and the increase in the rotor speed due to the ground fault is limited, hence the generation system is not endangered. The stator active and reactive power during 3-phase fault for a WECS using a STATCOM is compared with the results obtained in WECS using UPQC. Results ensured the superior performance of WECS employing the UPQC. Also, the stator active and reactive power during 3-phase fault for a WECS using a DVR is compared with the results obtained in WECS using UPQC. Results ensured the superior performance of WECS employing the UPQC with respect to higher harmonics and longer recovery time. However, the consumed reactive power is lower due to the series-connected coil of the DVR device. REFERENCES [1] J. Matevosyan, T. Ackermann, S. Bolik, and L. SdeR, “Comparison of international regulations for connection of wind turbines to the network,” Proc. NWPC, Gothenburg, Sweden, pp. 1–7, March 2004. [2] S. Seman, J. Niiranen, and A. Arkkio, “Ride-through analysis of doubly fed induction wind-power generator under unsymmetrical network disturbance,” IEEE Trans. Power Syst., vol. 21, no. 4, pp. 1782–1789, November 2006. [3] J. Morren and S. W. H. de Haan, “Ride through of wind turbines with doubly-fed induction generator during a voltage dip,” IEEE Trans. Energy Conversion., vol. 20, no. 2, pp. 435–441, Jun. 2005. [4] J. Yang, J. E. Fletcher, and J. O’Reilly, “A series-dynamic-resistor-based converter protection scheme for doubly-fed induction generator during various fault conditions,” IEEE Trans. Energy Conversion, vol. 25, no. 2, pp. 422–432, Jun. 2010. [5] L. G.Meegahapola, T. Littler, and D. Flynn, “Decoupled-DFIG fault ride through strategy for enhanced stability performance during grid faults,” IEEE Trans. Sustainable Energy, vol. 1, no. 3, pp. 152–162, Oct. 2010. [6] J. G. Nielsen and F. Blaabjerg, “A detailed comparison of system topologies for dynamic voltage restorers,” IEEE Trans. Ind. Appl., vol. 41, no. 5, pp. 1272–1280, Sep./Oct. 2005. [7] Christian Wessels, Fabian Gebhardt and Friedrich W. Fuchs, "Dynamic voltage restorer to allow LVRT for a DFIG wind turbine", IEEE International Symposium on Industrial Electronics (ISIE), 2010 [8] N. Hasegawa, and T. Kumano, "Low voltage ride-through capability improvement of wind power generation using dynamic voltage restorer", Proceedings of the 5th IASME/WSEAS international conference on Energy & environment, USA, 2010, pp166-171. [9] S. K. Meeravali, and K. Chandrasekhar, "Power Quality Enhancement Using Multi-Level Cascaded H-Bridge Based D-STATCOM with IRP Theory" International Electrical Engineering Journal (IEEJ), March 2015. [10] K. Wang and M. L. Crow, “Power system voltage regulation via STATCOM internal nonlinear control,” IEEE Trans. Power Syst., vol. 26, no. 3, pp. 1252–1262, Aug. 2011. [11] V. Spitsa, A. Alexandrovitz, and E. Zeheb, “Design of a robust state feedback controller for a STATCOM using a zero set concept,” IEEE Trans. Power Del., vol. 25, no. 1, pp. 456–467, Jan. 2010. [12] A. Luo, C. Tang, Z. Shuai, J. Tang, X. Y. Xu, and D. Chen, “Fuzzy-PI based direct-output-voltage control strategy for the STATCOM used in utility distribution systems,” IEEE Trans. Ind. Electron., vol. 56, no. 1, pp. 2401–2411, Jul. 2009. [13] C. H. Liu and Y. Y. Hsu, “Design of a self-tuning PI controller for a STATCOM using particle swarm optimization,” IEEE Trans. Ind. Electron., vol. 57, no. 2, pp. 702–715, Feb. 2010. [14] Mahmoud A. Saleh and Mona N. Eskander, "Sizing of converters interfacing the rotor of wind driven DFIG to the power grid", Smart grid and Renewable Energy Journal, pp.1-5, August 2011. 1930 Eskander et. al., Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller