Multipurpose Brake Installation & Operating Manual 7/02 MN802 Table of Contents Section 1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Multipurpose Brake Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selection of Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 2 Receiving & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Receiving, Inspection and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Quick Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Master Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pre-Stop Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 3 Startup and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Initial Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Board Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Cell Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 5 Specifications and Product Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 16A-80A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 135A - 600A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Torque and Wire Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions / Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 16A to 30A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 55A and 80A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 135A and 250A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 420A and 600A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MN802 1-1 1-1 1-2 1-2 1-4 1-5 2-1 2-1 2-1 2-2 2-2 2-2 2-3 2-4 2-4 2-6 2-8 3-1 3-1 3-1 3-1 3-1 4-1 4-1 4-2 4-3 5-1 5-1 5-2 5-4 5-4 5-5 5-6 5-6 5-7 5-7 5-8 5-9 5-10 Table of Contents i ii Table of Contents MN802 Section 1 General Information Multipurpose Brake Operation The Baldor Multipurpose brake provides smooth frictionless braking to standard three phase AC induction motors. The brake can be used with a standard magnetic starter or with a solid state reduced voltage starter and contactor. Braking is accomplished by applying an adjustable DC current to the motor windings. This current sets up a stationary magnetic field in the motor. The magnetic field causes the motor to come to a smooth frictionless stop. The brake electronically senses when the motor has stopped and removes the DC current (disengages the brake). (See Figure 1-1). AC motors, when turned off, have residual magnetism that causes voltage to be present inside the motor. Large surge currents could occur if DC is applied to the motor before the voltage in the motor reaches a safe level. The traditional method of a fixed time delay does not allow for the variations of motors or changes in a motor under different load conditions. Baldor’s dynamic brake monitors the voltage in the motor and waits for the motor voltage to drop to a safe level before applying DC braking. The Multipurpose Brake verifies that the DC contactor has opened before allowing the AC contactor (starter) to close. Zero speed sensing will quickly shut off the DC brake when the motor stops. This prevents excess motor heating. The multipurpose Brake, with its three operating modes and zero speed sensing, makes it flexible for many applications. Sensing motor voltage and checking for the DC contactor opening eliminates the most common failures of solid state brakes caused by high surge currents resulting in blown AC starter fuses and welded contacts of the AC contactor. Figure 1-1 Typical Operation Motor Voltage Motor Voltage VACRMS Motor Speed Motor Speed DC Voltage Legend ABCDE- Motor AC contactor opens. Motor voltage decreases and motor begins to slow down. DC braking begins after a safe motor voltage level is reached. The control senses the motor has stopped. DC braking is turned off. Motor Voltage Safe Level A B C MN802 DE t General Information 1-1 Section 1 General Information Additional Information Stopping Time Depending on the load, the Baldor dynamic brake can stop the motor faster than the motor will start (at 460VAC). However, this can cause damage to the motor or the driven machinery. Motor Sizing Each stop (with the dynamic brake) should be treated as a start for calculating duty cycle and for sizing the motor. The brake does not have a duty cycle limit. Holding Brake A solid state brake is not a substitute for a mechanical holding brake. Brake Sizing Use the motor FLA and operating voltage to size the brake. All Baldor Multipurpose Brakes can be used on high inertia loads. Selection of Operating Mode Three operating modes are available in the Multipurpose Dynamic Brake control. These operating modes define sequence of braking cycle, connections of control and power devices, setting and adjustments. Selection of Operating Mode is done by setting Dip switch (S1) on the Brake Control Board. Available operating modes include: Basic Mode Master Mode Pre-stop Mode Basic Mode Basic Mode features automatic sensing of motor terminal line voltage. Brake activates automatically when voltage on the motor terminal decreases to a save level. Separate motor starter controls govern start and stop cycle. Brake release function provides immediate means of opening the brake contactor. This feature adds operational flexibility and a safety factor as well. Figure 1-2 Functional Diagram – Basic Mode Optional Emergency Stop Push Button and Brake Release Switch Full Voltage Non-Reversing Controller Start/Stop Push Buttons Brake Motor 1-2 General Information MN802 Section 1 General Information Master Mode In Master mode, the Brake controls the motor starter operation through the Motor Interlock. Motor Start and Stop pushbuttons are wired to the Brake Control Board. Master Mode initiates the brake cycle when the Stop or Emergency Stop push buttons are pressed. Extended brake times allows the motor to come to a controlled full stop before the brake shuts off, thus avoiding uncontrolled coasting. Also, Master Mode allows the Jog function. Jog allows conventional jogging push button control of the motor starter contactor with motor coasting with brake action disabled. Brake release function provides immediate means of opening the brake contactor. This feature adds operational flexibility and a safety factor as well. Figure 1-3 Functional Diagram – Master Mode Emergency Stop Push Button and Brake Release Switch Start/Stop/Jog Push Buttons Full Voltage Non-Reversing Controller Brake Motor Pre-stop Mode In Pre-stop mode, the Brake controls the motor starter operation through the Motor Interlock. Motor Start and Stop pushbuttons are wired to the Brake Control Board. Pre-stop Mode initiates the brake cycle when the Start push button is pressed. The Brake cycle includes opening of a motor starter contactor, sensing the safe voltage level, closing the brake contactor, injecting DC current into motor winding (brake action), then sensing zero speed and opening the brake contactor. The sequence ensures that the motor is first stopped before starting the motor. Stop push button open the motor starter contactor and motor coast to stop. Zero speed sensing followed by brake shut off eliminates unnecessary heat in the motor winding. Figure 1-4 Functional Diagram – Pre-stop Mode Emergency Stop Push Button and Brake Release Switch Start/Stop Push Buttons Full Voltage Non-Reversing Controller Brake Motor MN802 General Information 1-3 Safety Notice This equipment contains voltages that may be as high as 600 volts! Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the start-up procedure or troubleshoot this equipment. This equipment may be connected to other machines that have rotating parts or parts that are driven by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start-up procedure or troubleshoot this equipment. PRECAUTIONS WARNING: A solid state Multipurpose brake is not suitable for use as a mechanical holding brake. Because the solid state Multipurpose brake requires AC power for braking, if power is interrupted no braking is provided. This can be hazardous to personnel or equipment. WARNING: Do not touch any circuit board, power device or electrical connection before you first ensure that power has been disconnected and there is no high voltage present from this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury. WARNING: Be sure that you are completely familiar with the safe operation of this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start-up procedure or troubleshoot this equipment. WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you ensure that all grounding instructions have been followed. Electrical shock can cause serious or fatal injury. 1-4 General Information Caution: To prevent equipment damage, be certain that the electrical service is not capable of delivering more than the maximum line short circuit current amperes listed for the control rating. Caution: Do not “Megger” test the motor while it is connected to the brake. Failure to disconnect motor will result in extensive damage to the brake. The brake is tested at the factory for high voltage / leakage resistance as part of Underwriter Laboratory requirements. Caution: Do not connect power factor correction capacitors to motor terminals or brake output terminals. MN802 Limited Warranty For a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. This warranty is in lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), inconvenience, or consequential damage, including injury to any person or property caused by items of our manufacture or sale. (Some states do not allow exclusion or limitation of incidental or consequential damages, so the above exclusion may not apply.) In any event, BALDOR’s total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements must be referred to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the problem encountered. No liability is assumed for expendable items such as fuses. Goods may be returned only with written notification including a BALDOR Return Authorization Number and any return shipments must be prepaid. MN802 General Information 1-5 1-6 General Information MN802 Section 2 Receiving & Installation Receiving, Inspection and Storage When you receive your control, there are several things you should do immediately. 1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control. 2. Verify that the part number of the control you received is the same as the part number listed on your purchase order. 3. If the control is to be stored for several weeks before use, be sure that it is stored in a location that is clean, dry and free from corrosives and contaminants. Storage temperatures must not exceed 140°F (60°C). Quick Reference Chart LED Indicators: Switch (S1): S1-1 S1-2 Brake Timer Range OFF OFF ON ON OFF ON OFF ON 1 to 17 seconds 15 to 32 seconds 30 to 47 seconds 45 to 62 seconds S1-3 S1-4 Brake Operating Mode OFF ON ON ON OFF ON Master Brake Mode Pre-Stop Brake Mode Basic Brake Mode Zero Speed Sensor Disable OFF ON Brake zero speed sensor ON Brake zero speed sensor OFF S1-6 Brake Status and Reset OFF ON Brake is operational Brake is disabled and reset MN802 PWR RDY RUN BRK 12 345 6 S1 MAG1 MAG2 TIME J6 J7 J4 BALDOR ELECTRIC TB1 1 2 3 4 5 6 7 8 9 10 P1 P3 P2 Adjustments: MAG1 (P1) CCW 0 S1-5 J3 ON indicates brake contactor (BC) is closed. J8 BRK J2 On indicates M contactor is closed or enabled (TB1 terminals 7 and 8 closed). Brake ON RUN J5 On indicates Brake ready. Flashing indicates error detected. 2 flashes- Improper line voltage 3 flashes- Motor contactor (M) failed to open 4 flashes- Brake contactor (BC) failed to open 5 flashes- Improper line frequency Motor Run RDY Brake Ready On indicates 115VAC input is present Brake Logic Power ON PWR J1 Brake Control Board (BRDT-B2) MAG2 (P3) CCW 0 Time (P2) CCW 0 CW 100 CW 100 CW 100 Brake Magnitude Adjustment (0-100%) Adjustment for brake torque with a motor stop push button. See operation chart (in Section 1) for more information. Emergency Brake Magnitude (0-100%) Adjustment for brake torque for emergency stop push button. See operation chart (in Section 1) for more information. Brake Timer Adjustment (0-100%) Adjusts the maximum amount of Brake Time. When zero speed sensing is ON, timer must be set to the longest stopping time. Receiving & Installation 2-1 Installation Considerations Installation, troubleshooting and repair of this equipment should only be performed by qualified personnel familiar with the safe operation of this device. It should be installed in an area that is protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. Exposure to these elements can reduce the operating life and degrade performance of the control. When installing a Multipurpose Brake, several factors should be considered: Checklist 1. Verify horsepower, line voltage, and current rating of control and motor match the ratings of the brake panel. 2. Verify environmental conditions are compatible with the brake panel. 3. Examine the associated motor combination controller and verify that controller rating and type is compatible with DC single winding injection braking for a three phase induction motor. 4. Verify that the power source has good line voltage regulation and that DC injection braking will not reduce the line-to-line voltage to less than 75% of nominal value. Line voltages less than 75% of nominal may cause brake contactor chatter which may also result in SCR or diode damage. 5. Determine which operating mode will be used (Basic, Master or Pre-Stop). Refer to the Control Wiring Diagrams on the following pages to determine which mode is right for your configuration. The existing motor control wiring and the additional connections required for the brake panel are shown in Figures 2-5, 2-6 and 2-7. Table 2-1 Branch-Circuit Short-Circuit and Ground-Fault Protective Device Ratings Brake Size (Amperes) 16A 25 30 55 80 135 160 250 420 600 2-2 Receiving & Installation Fuse Size (Amperes) 60A 100A 110A 175A 175A 400A 400A 400A 800A 800A Class J J J J J J RK1 or RK5 RK1 or RK5 J or L J or L Instantaneous Trip Breaker Size (Amperes) 20A 20A 50A 100A 100A 300A 300A 300A MN802 Procedure 1. Mount the panel in vertical position. Refer to Section 5 for mounting dimensions. 2. Verify that associated combination controller is a full voltage nonreversing type with control coil operation at 115V, 50/60Hz. Connect the line and load terminals with proper size wire to line and load side terminals of associated controller. Refer to schematic and torque and wire specifications in Section 5. Do not change phase rotation. See Figure 2-5, 2-6 or 2-7. 3. Verify that the maximum rating or setting of the motor Branch-Circuit Short-Circuit and Ground-Fault protective devices meets the ratings shown in Table 2-1. Note: The M contactor must have a surge suppressor installed across its coil. 4. Refer to Operating Chart choose the operating mode and wire remote control switches or pushbuttons as shown on wiring diagrams (Figures 2-5, 2-6 and 2-7) for each selected specific operating mode. Route control wiring separate from power wiring. 5. Verify line voltage and adjust jumper on control power transformer (CPT) primary taps. 6. Verify correct phasing of all power connections. 7. Apply power with motor leads disconnected and verify that motor starter contactor and brake contactor do not close at the same time and confirm that there is no phase to phase short circuit condition. 8. Refer to Operation Chart; confirm chosen operating mode is set, select and set brake time range. 9. Set brake magnitude MAG1 adjustment potentiometer P1 to 0% (full CCW). 10. If Emergency braking is required and emergency Stop Push Button is wired, set emergency brake magnitude MAG2 adjustment potentiometer P2 to 0% (full CCW). 11. Set brake time potentiometer P3 to 100% (full CW). 12. Energize the motor without load and confirm that brake operates properly. 13. Energize motor at full load and stop with brake. Observe deceleration and adjust brake magnitude and stopping time to the required sequence. MN802 Receiving & Installation 2-3 Control Wiring Diagrams Basic Mode Basic Mode features automatic sensing of motor terminal line voltage. Brake activates automatically when voltage on the motor terminal decreases to a save level. Separate motor starter controls govern start and stop cycle. Brake release function provides immediate means of opening the brake contactor. This feature adds operational flexibility and a safety factor as well. Figure 2-5 shows the Basic mode connections into an existing motor combination controller and motor. Use MAG1 potentiometer P1 to adjust braking magnitude for stop. Description of Control Board Connections (Refer to Figure 2-5) Terminal Description TB1-4 OPEN initiates emergency stop braking with magnitude MAG2(P3). (Open M contactor, close brake contactor, apply DC to motor (T1, T2) with MAG2(P3), and open brake contactor at zero speed or end of brake timer). CLOSED allows normal operation. TB1-6 OPEN Brake enabled (closes brake contactor). CLOSED releases Brake (opens brake contactor). TB1-7 & 8 Motor interlock is rated 5A at 125VAC. Motor Interlock is energized when 115VAC is applied to Brake Control Board. Note: For brake panels that have a higher current rating, relay R2 is installed to provide a 10 Amp rating for the M contactor. The relay is shown but is not installed in all brake panels. If R2 is installed, connect the Start switch and M contactor outputs to R2 terminals 1 and 3 (10 Amp, 240VAC rating). If R2 is not installed, connect the Start switch and M contactor outputs to TB1 terminals 7 and 8 (10 Amp, 125VAC rating). Switch (S1): Adjustments MAG1 (P1) Brake Magnitude Adjustment (0-100%) Adjusts brake torque for normal motor stop. CCW 0 MAG2 (P3) Emergency Brake Magnitude (0-100%) Adjusts brake torque for emergency motor stop. CCW 0 Time (P2) CW 100 CCW 0 CW 100 CW 100 Brake Timer Adjustment (0-100%) Adjusts the maximum amount of Brake Time. When zero speed sensing is ON, timer must be set to the longest stopping time. 2-4 Receiving & Installation S1-1 S1-2 Brake Timer Range OFF OFF ON ON OFF ON OFF ON 1 to 17 seconds 15 to 32 seconds 30 to 47 seconds 45 to 62 seconds S1-3 S1-4 Brake Operating Mode ON ON Basic Mode S1-5 Zero Speed Sensor OFF ON Brake zero speed sensor ON Brake zero speed sensor OFF S1-6 Brake Status OFF ON Brake is operational Brake is disabled and reset MN802 Control Wiring Diagrams Continued Figure 2-5 Basic Mode Diagram Refer to the operation chart for the use of inputs and switches. All switches and contacts wired to TB1 terminals 1 - 6 must be dry isolated contact type. All control wiring must be installed in a separate conduit and routed away from the line voltage and motor lead conduits for noise reduction. In Basic mode, braking is activated when the voltage at the motor terminals decreases to a safe level (80% of nominal Line voltage). P1 adjusts brake magnitude. Braking time is controlled by timer or zero speed sensing. If the emergency stop switch is not used, place jumper wire from TB1-4 to TB1-1. Phase A L2 Phase B Phase C Circuit Breakers or Fused Inputs L2 OL T1 M OL T2 M OL Motor T3 Brake Assembly 2 3 4 Emergency Stop 5 6 Brake Release 7 Motor Interlock 8 T1 T2 T3 F2 Control Board BC 208V 230V L1 Existing Site Wiring M P1 P3 P2 TB1 1 Common Brake Connection Diagram – Basic Mode L1 Brake Control Board (BRDT-B2) S1 MAG1 MAG2 TIME 12 345 6 Notes: J5 Notes: 460V F1 TB1 CPT 1 7 4 R2 8 6 3 1 4 6 8 5 Fuse Stop Start OL M M Noise Suppressor Relay R2 is only installed on large brake assemblies to provide 10A contact for connection to M contactor. If Relay R2 is installed, connections should be made to R2 pins 1 and 3. If Relay R2 is not installed, connections should be made to Control Board pins 7 and 8. Add surge suppressor if not included in contactor coil. Operating Modes Basic Mode Emergency Stop (TB1Ć4) 1. Open motor contactor 2. Close brake contactor 3. Apply DC to motor (T1, T2) (using Magnitude 2 Ć P3) 4. Open brake contactor at zero speed or at end of brake timer Brake Release 1. Open brake contactor Zero Speed Sense Braking will stop when the motor (S1Ć5) stops rotating Magnitude 1 (P1) Adjustment for brake magnitude with standard stop switch Magnitude 2 (P3) Adjustment for brake magnitude with emergency stop switch Time (P2) Adjustment for time brake is applied if zero speed sense is enabled (S1Ć5) Operation MN802 Receiving & Installation 2-5 Section 1 General Information Control Wiring Diagrams Continued Master Mode Master Mode initiates the brake cycle when the Stop or Emergency Stop push buttons are pressed. Extended brake times allows the motor to come to a controlled full stop before the brake shuts off, thus avoiding uncontrolled coasting. Also, Master Mode allows the Jog function. Jog allows conventional jogging push button control of the motor starter contactor with motor coasting with brake action disabled. Brake release function provides immediate means of opening the brake contactor. This feature adds operational flexibility and a safety factor as well. Figure 2-6 shows the Master mode connections into an existing motor combination controller and motor. Description of Control Board Connections (Refer to Figure 2-6) Terminal Description TB1-2 OPEN allows normal operation. CLOSED starts motor (closes M contactor). TB1-3 Momentary OPEN stops motor (open the M contactor, closes brake contactor, apply DC to motor (T1, T2) with MAG1 (P1), and open brake contactor at zero speed or end of brake timer). TB1-4 OPEN initiates emergency stop braking with magnitude MAG2(P3). (Open M contactor, close brake contactor, apply DC to motor (T1, T2) with MAG2(P3), and open brake contactor at zero speed or end of brake timer). CLOSED allows normal operation. TB1-5 Momentary CLOSED starts motor (closes M contactor) while switch is closed. When switch is released, M contactor opens without braking (motor coasts to stop). TB1-6 OPEN Brake enabled (closes brake contactor). CLOSED releases Brake (opens brake contactor). TB1-7 & 8 Motor interlock is rated 5A at 125VAC. Motor Interlock is energized when 115VAC is applied to Brake Control Board. Note: For brake panels that have a higher current rating, relay R2 is installed to provide a 10 Amp rating for the M contactor. The relay is shown but is not installed in all brake panels. If R2 is installed, connect the Start switch and M contactor outputs to R2 terminals 1 and 3 (10 Amp rating). If R2 is not installed, connect the Start switch and M contactor outputs to TB1 terminals 7 and 8 (5 Amp rating). Switch (S1): Adjustments MAG1 (P1) Brake Magnitude Adjustment (0-100%) Adjusts brake torque for normal motor stop. CCW 0 MAG2 (P3) Emergency Brake Magnitude (0-100%) Adjusts brake torque for emergency motor stop. CCW 0 Time (P2) CW 100 CCW 0 CW 100 CW 100 Brake Timer Adjustment (0-100%) Adjusts the maximum amount of Brake Time. When zero speed sensing is ON, timer must be set to the longest stopping time. 2-6 Receiving & Installation S1-1 S1-2 Brake Timer Range OFF OFF ON ON OFF ON OFF ON 1 to 17 seconds 15 to 32 seconds 30 to 47 seconds 45 to 62 seconds S1-3 S1-4 Brake Operating Mode OFF ON Master Mode S1-5 Zero Speed Sensor OFF ON Brake zero speed sensor ON Brake zero speed sensor OFF S1-6 Brake Status OFF ON Brake is operational Brake is disabled and reset MN802 Section 1 General Information Control Wiring Diagrams Continued Figure 2-6 Master Mode Diagram Refer to the operation chart for the use of inputs and switches. All switches and contacts wired to TB1 terminals 1 - 6 must be dry isolated contact type. All control wiring must be installed in a separate conduit and routed away from the line voltage and motor lead conduits. This will reduce the electromagnetic noise induction that will cause erratic operation. If non-momentary 2 wire control is used, place jumper wire from TB1-3 to TB1-2. If the emergency stop switch is not used, place jumper wire from TB1-4 to TB1-1. Phase A L2 Phase B Phase C L2 Fuse T1 OL T2 M OL Motor T3 Brake Assembly T1 T2 T3 Control Board 2 3 4 5 6 7 8 Start Stop Emergency Stop Jog Brake Release Motor Interlock 208V 230V L1 Existing Site Wiring OL M F2 BC Circuit Breakers or Fused Inputs M P1 P3 P2 TB1 1 Common Brake Connection Diagram – Master Mode L1 Brake Control Board (BRDT-B2) S1 MAG1 MAG2 TIME 12 345 6 Notes: J5 460V F1 CPT 1 TB1 2 3 4 Start Stop Emergency Stop Jog Brake Release 5 6 7 R2 8 3 1 4 6 Notes: 8 5 OL M Noise Suppressor Relay R2 is only installed on large brake assemblies to provide 10A contact for connection to M contactor. If Relay R2 is installed, connections should be made to R2 pins 1 and 3. If Relay R2 is not installed, connections should be made to Control Board pins 7 and 8. Add surge suppressor if not included in contactor coil. Operation Start (TB1Ć2) Stop (TB1Ć3) Master Mode 1. Close motor contactor 1. Open motor contactor 2. Close brake contactor 3. Apply DC to motor (T1, T2) (using Magnitude 1 Ć P1) 4. Open brake contactor at zero speed or at end of brake timer Emergency Stop (TB1Ć4) 1. Open motor contactor 2. Close brake contactor 3. Apply DC to motor (T1, T2) (using Magnitude 2 Ć P3) 4. Open brake contactor at zero speed or at end of brake timer JOG (TB1Ć5) 1. Close motor contactor while switch is closed 2. M contactor opens without braking, motor coasts to stop Brake Release 1. Open brake contactor Zero Speed Sense Braking will stop when the motor (S1Ć5) stops rotating Magnitude 1 (P1) Adjustment for brake magnitude with standard stop switch Magnitude 2 (P3) Adjustment for brake magnitude with emergency stop switch Time (P2) Adjustment for time brake is applied if zero speed sense is enabled (S1Ć5) MN802 Receiving & Installation 2-7 Control Wiring Diagrams Continued Pre-Stop Mode Pre-stop Mode initiates the brake cycle when the Start push button is pressed. The Brake cycle includes opening of a motor starter contactor, sensing the safe voltage level, closing the brake contactor, injecting DC current into motor winding (brake action), then sensing zero speed and opening the brake contactor. The sequence ensures that the motor is first stopped before starting the motor. Stop push button open the motor starter contactor and motor coast to stop. Zero speed sensing followed by brake shut off eliminates unnecessary heat in the motor winding. Figure 2-7 shows the Pre-Stop mode connections into an existing motor combination controller and motor. Description of Control Board Connections (Refer to Figure 2-7) Terminal Description TB1-2 OPEN allows normal operation. CLOSED starts motor (close brake contactor, apply DC to motor (T1, T2), open brake contactor and closes M contactor). TB1-3 Momentary OPEN stops motor (open the M contactor, motor coasts to stop). TB1-4 OPEN initiates emergency stop braking with magnitude MAG2(P3). (Open M contactor, close brake contactor, apply DC to motor (T1, T2) with MAG2(P3), and open brake contactor at zero speed or end of brake timer). CLOSED allows normal operation. TB1-6 OPEN Brake enabled (closes brake contactor). CLOSED releases Brake (opens brake contactor). TB1-7 & 8 Motor interlock is rated 5A at 125VAC. Motor Interlock is energized when 115VAC is applied to Brake Control Board. TB1-9 & 10 115VAC input is factory wired from control power transformer. Note: For brake panels that have a higher current rating, relay R2 is installed to provide a 10 Amp rating for the M contactor. The relay is shown but is not installed in all brake panels. If R2 is installed, connect the Start switch and M contactor outputs to R2 terminals 1 and 3 (10 Amp rating). If R2 is not installed, connect the Start switch and M contactor outputs to TB1 terminals 7 and 8 (5 Amp rating). Switch (S1): Adjustments MAG1 (P1) Brake Magnitude Adjustment (0-100%) Adjusts brake torque for normal motor stop. CCW 0 MAG2 (P3) Emergency Brake Magnitude (0-100%) Adjusts brake torque for emergency motor stop. CCW 0 Time (P2) CW 100 CCW 0 CW 100 CW 100 Brake Timer Adjustment (0-100%) Adjusts the maximum amount of Brake Time. When zero speed sensing is ON, timer must be set to the longest stopping time. 2-8 Receiving & Installation S1-1 S1-2 Brake Timer Range OFF OFF ON ON OFF ON OFF ON 1 to 17 seconds 15 to 32 seconds 30 to 47 seconds 45 to 62 seconds S1-3 S1-4 Brake Operating Mode ON OFF Pre-Stop Mode S1-5 Zero Speed Sensor OFF ON Brake zero speed sensor ON Brake zero speed sensor OFF S1-6 Brake Status OFF ON Brake is operational Brake is disabled and reset MN802 Control Wiring Diagrams Continued Figure 2-7 Pre-Stop Mode Diagram Refer to the operation chart for the use of inputs and switches. All switches and contacts wired to TB1 terminals 1 - 6 must be dry isolated contact type. All control wiring must be installed in a separate conduit and routed away from the line voltage and motor lead conduits. This will reduce the electromagnetic noise induction that will cause erratic operation. If the emergency stop switch is not used, place jumper wire from TB1-4 to TB1-1. L2 Phase B Phase C L2 T1 OL T2 M OL T3 Brake Assembly Start Stop Emergency Stop Brake Release Motor Interlock T1 T2 T3 208V 230V J5 460V F1 CPT 1 TB1 2 3 4 Start Stop Emergency Stop Fuse Motor 2 3 4 5 6 7 8 Control Board L1 Existing Site Wiring OL M F2 BC Circuit Breakers or Fused Inputs M P1 P3 P2 TB1 1 Common Brake Connection Diagram – Pre-Stop Mode L1 Phase A Brake Control Board (BRDT-B2) S1 MAG1 MAG2 TIME 12 345 6 Notes: 5 6 7 R2 8 3 1 4 6 Notes: 8 5 Brake Release OL M Noise Suppressor Relay R2 is only installed on large brake assemblies to provide 10A contact for connection to M contactor. If Relay R2 is installed, connections should be made to R2 pins 1 and 3. If Relay R2 is not installed, connections should be made to Control Board pins 7 and 8. Add surge suppressor if not included in contactor coil. Operation Start (TB1Ć2) Pre-Stop Mode 1. Close brake contactor 2. Apply DC to motor (T1, T2) 3. Open brake contactor 4. Close motor contactor Stop (TB1Ć3) 1. Open motor contactor (motor coasts to stop) Emergency Stop (TB1Ć4) 1. Open motor contactor 2. Close brake contactor 3. Apply DC to motor (T1, T2) (using Magnitude 2 Ć P3) 4. Open brake contactor at zero speed or at end of brake timer Brake Release 1. Open brake contactor Zero Speed Sense Braking will stop when the motor (S1Ć5) stops rotating Magnitude 1 (P1) Adjustment for brake magnitude with standard stop switch Magnitude 2 (P3) Adjustment for brake magnitude with emergency stop switch Time (P2) Adjustment for time brake is applied if zero speed sense is enabled (S1Ć5) MN802 Receiving & Installation 2-9 2-10 Receiving & Installation MN802 Section 3 Startup and Maintenance Overview Before the Multipurpose Brake is placed into service, adjustment of its operating characteristics is required. None of the adjustments are preset at the factory. Be careful not to damage the potentiometers during adjustment. They have a maximum rotation span of 270 degrees. Use the adjustment wand provided and do not force the adjustments beyond the stops. Two tools are needed for these adjustments. Initial Adjustments Operation Checks Maintenance Volt ohm meter (VOM) - at least 20kW per volt. Adjustment wand provided with the Multipurpose Brake. Use this procedure as a guideline to match the braking characteristics to the motor load. 1. Confirm operating mode, time range switch settings and external pushbutton and selector switch connections. 2. Set MAG1 potentiometer P1 to 0 (full CCW). 3. Set brake TIME potentiometer P2 to 100% (full CW). 4. Adjust MAG1 and TIME as needed to obtain correct stop sequence. After the initial adjustments are complete, these operation checks should be performed to ensure optimum operation of the control. 1. Measure the line voltage at the control L1 and L2 terminals during acceleration. The line voltage should never be less than the minimum operating voltage. 2. Measure the voltage at TB1-9 and TB1-10 of the Brake Control Board. It should be 120VAC (±10%). The control should be checked at regular intervals. Disconnect all input power before any maintenance checks are performed. MN802 Check all connections for tightness and signs of overheating. Check for cracked or damaged insulators and terminal blocks. Inspect heat sinks for cleanliness. Be sure to remove dust or dirt buildup and to maintain proper ventilation. Remove dust and dirt by vacuuming. Do not wash or use solvents. Startup and Maintenance 3-1 Section 1 General Information 3-2 Startup and Maintenance MN802 Section 4 Troubleshooting Preliminary Checks In the event of trouble disconnect all input power to the control and perform these preliminary checks. Check all electrical connections to verify they are proper for the operating mode selected. (Refer to Installation Section 2 and Control Wiring Diagrams in Sections 2 and 5 of this manual.) Verify that DIP switches are correctly set for the operating mode selected. (Refer to Installation Section 2 of this manual.) Verify that the Motor Interlock (TB1-7 and TB1-8) are properly connected in series with the Motor Contractor coil. Verify TIME (P2) is fully CCW, 0% braking time. Verify MAG1 (P1) is fully CCW, 0% braking magnitude. Verify MAG2 (P3) is fully CW, 100% braking. Check all connections for tightness and signs of overheating. Check for cracked or damaged insulators and terminal blocks. Check all motor connections from the control to the motor. Verify transformer primary line connections are proper for line voltage. (See transformer nameplate). LED Indicators (Brake Control Board) RDY- Ready LED should be continuously on. If the RDY LED is flashing, it is signaling an error condition. The number of flashes indicates one of the following: 2 flashes Improper line voltage. 3 flashes Motor contactor (M) failed to open. 4 flashes Brake contactor (BC) failed to open. 5 flashes Improper line frequency. Resistance checks: Be sure that all power to the control is still disconnected. Use a VOM (at least 20kW per volt) and check the resistance at the following terminals. The measured resistance should be greater than 10kW for each measurement on the power cell. KS to AA (SCR cathode to common anode) AA to KD (common anode to diode cathode) If the measured resistance is less than 10kW for any measurement, a power cell (SCR and Diode pair) is defective. If a shorted SCR is found, be sure to check for shorted connections, system grounds, or any other condition that may cause the short. Replacement of an SCR without determining the cause of failure may result in repeat failures. MN802 Troubleshooting 4-1 Control Board Checks Several steps need to be performed before testing the control board. 1. Disconnect all input power. 2. Disconnect all motor leads. 3. Disconnect wires to the control board terminals TB1-7 and TB1-10. Figure 4-1 Control Board (BRDT-B2) Resistance Measurements Circuit Rating Rating 016-080 135-250 Resistance Gate to Anode (SCR) J8 - J4 J8 - AA Greater than 10 K ohms Cathode to Anode (SCR) J3 - J4 J3 - AA Greater than 10 K ohms Anode to Cathode (SCR) J4 - J3 AA - J3 Greater than 10 K ohms Anode to Cathode (Diode) J4 - J2 AA - J2 Greater than 10 K ohms Cathode to Anode (Diode) J2 - J4 J2 - AA Greater than 10 K ohms BRDT-B2 to KD J2 - KD J2 - KD Less than 5 ohms BRDT-B2 to KS J3 - KS J3 - KS Less than 5 ohms BRDT-B2 to AA J4 - AA NA Less than 5 ohms BRDT-B2 to GK J8 - GK J8 - GK Less than 5 ohms Motor Interlock TB1-7 to TB1-8 Greater than 10 K ohms Power Supply XFMR TB1-9 to TB1-10 350 to 450 ohms Brake Power Cell (BPC) CS AA RS AA 5 to 30 ohms KS KS J8 - J3 KD J8 - J3 SCR Gate to Cathode (SCR) SCR Measurement GK Brake Control Board (BRDT-B2) Diode J6 J7 J4 J3 J8 J2 J5 J1 KD BALDOR ELECTRIC PWR RDY RUN BRK 12 345 678 MAG1 4-2 Troubleshooting MAG2 TIME TB1 1 2 3 4 5 6 7 8 9 10 MN802 Power Cell Checks Several steps need to be performed before testing the power cell. 1. Disconnect all input power. 2. Disconnect all motor leads. 3. Inspect all connections for tightness and indications of overheating. 4. Snubber capacitors should be replaced if there is any sign of leakage. Brakes size 16A to 80A have snubber capacitors on the control board. Larger brakes have capacitors installed on power cells. 5. SCR clamps should be inspected for cracks and tightened evenly using a clamp gauge. A clamp gauge is available from Baldor or shipped with the replacement SCR/Diode kit. 6. Heat sinks and insulated surfaces must be clean and free of debris. Air flow must not be obstructed. Figure 4-2 Power Cell (BPC) -SCR Resistance Measurements BPC Resistance Gate to Anode (SCR) GK - AA Greater than 10 K ohms Cathode to Anode (SCR) KS - AA Greater than 10 K ohms Anode to Cathode (SCR) AA - KS Greater than 10 K ohms Anode to Cathode (Diode) AA - KD Greater than 10 K ohms Cathode to Anode (Diode) KD - AA Greater than 10 K ohms CS AA KS AA 5 to 30 ohms KS GK - KS RS KD Gate to Cathode (SCR) SCR Circuit SCR Measurement GK Diode KD MN802 Troubleshooting 4-3 Section 1 General Information 4-4 Troubleshooting MN802 Section 5 Specifications and Product Data Identification B Q 7 – 030 – C B –*** Control Type B- Dynamic Brake Custom Product Part Number Brake Type Q- 3 Operating Modes Input Voltage Code 7208/230/460VAC (50/60Hz) 8220/230/460/575VAC (50/60Hz) 9380/415VAC (50/60Hz) Enclosure BNEMA1 CNEMA12 PPanel / Open DNEMA4 Ampere Rating 01616 Amp 03030 Amp 05555 Amp 08080 Amp 135135 Amp 160160 Amp 250250 Amp 420420 Amp 600600 Amp Configuration CIncludes control power transformer The brake must have a separate 115VAC input. The inpur voltage code is the range of voltages over which the brake will operate. For example, voltage code “7” will operate between 208 - 460VAC. Use rated motor full load current (FLA) to select the proper size brake. Stocked multi-purpose dynamic brakes are shipped with control power transformer included. Be sure to set the primary voltage tap jumper to match the applied line voltage. MN802 Specifications and Product Data 5-1 General Specifications Output Ratings Output Horsepower and Current by Model Number Input Voltage VAC BQXĆ016ĆCY Q BQXĆ030ĆCY Q BQXĆ055ĆCY Q BQXĆ080ĆCY Q BQXĆ135ĆCY Q BQXĆ160ĆCY Q BQXĆ250ĆCY Q BQXĆ420ĆCY Q BQXĆ600ĆCY Q BQXĆ016ĆCY HP A BQXĆ030ĆCY HP A BQXĆ055ĆCY HP A BQXĆ080ĆCY HP A BQXĆ135ĆCY HP A BQXĆ160ĆCY HP A BQXĆ250ĆCY HP A BQXĆ420ĆCY HP A BQXĆ600ĆCY HP A 4 5 10 10 10 10 20 25 20 20 40 50 25 30 60 75 40 50 100 125 50 60 125 150 75 100 200 250 150 150 350 400 200 250 500 600 208 230 460 575 16 16 16 16 30 30 30 30 55 55 55 55 80 80 80 80 135 135 135 135 160 160 160 160 250 250 250 250 420 420 420 420 600 600 600 600 Input Ratings Input Frequency 50/60 HZ ± 5% Input Voltage ± 10% of Input Voltage Rating (208, 230, 460 or 575 VAC) Input Current 16, 30, 55, 80,135, 160, 250, 420 or 600 Amperes (see Output Ratings table) Note: Use rated motor full load current (FLA) to select the proper Multi-Purpose Brake model number for your application. Phase Three (3) Phase Service Factor 1.0 Duty Continuous Operating Conditions Ambient Operating Temperature: 30-113°F (0 to +45 °C) enclosed 30-122°F (0 to +50 °C) open panel Derate Output 1.5% per 1°C over maximum ambient Rated Storage Temperature: – 30 °C to +65 °C Humidity: 90% RH Non-Condensing Altitude: Sea level to 3300 Feet (1000 Meters) Derate 1% per 330 Feet (100 Meters) above 3300 Feet Enclosure: Open Panel NEMA 1 NEMA 12 NEMA 4 Heat Loss 1 Watt per running ampere of input current while braking. 5-2 Specifications and Product Data (Indoor) (Industrial indoor, general purpose) (Industrial indoor, dust proof) (Outdoor) MN802 Control Specifications Control Method Common Anode SCR and Diode to achieve DC Peak Inverse Voltage 1200V - for 460VAC controls; 1600V - for 575VAC controls Brake Magnitude Two (2) adjustable brake magnitudes Brake Timer Ranges 1-17 seconds; 15-32 seconds; 30-47 seconds; 45-62 seconds Zero Speed Sensor Selectable (Brake disengages when motor stops rotating) Motor Interlock Contact Rating 10 Amperes at 125VAC Status LED’s Power, Ready, Run and Braking Error Indications Improper line voltage; Improper line frequency; Motor contact failed to open; Brake contactor failed to open; Listings UL and cUL MN802 Specifications and Product Data 5-3 Control Wiring Diagrams Size 16A-80A Multipurpose Brake Line Input L1 12 345 6 MAG1 MAG2 TIME 1 2 3 4 5 6 7 8 9 10 J7 Brake P1 Control P3 Board P2 TB1 Common Start Stop Emergency Stop Jog Brake Release CS RS L3 CB J6 S1 L2 L2 L1 BC BC J2 J1 J4 SCR J3 J8 3 1 KS GK CS MOV AA M M RS OL OL MOV Motor Interlock KD 115VAC Input F3 X2 115VAC CPT J5 H1-460V H2-230V F1 TB2 T1 T2 T3 Motor H3-208V F2 X1 Note: F1 is connected to H1 for 460VAC operation. For 230VAC remove the wire from H1 and connect it to H2. For 208VAC operation remove the wire from H1 and connect it to H3. LEGEND AAAnode (Diode & SCR) BCBrake Contactor BCBBrake Control Board CBCMotor Circuit Breaker CPTControl Power Transformer CSSnubber Capacitor F1,2Transformer Primary Fuses F3Transformer Secondary Fuse KDDiode (Cathode) KSSCR (Cathode) MMotor Contactor MOVMetal Oxide Varistor OLMotor Overload P1, P2, P3- Potentiometer RSSnubber Resistor S1Switch SCRBrake SCR/Diode Assembly TB1Brake Control Terminals TB2Brake Output Terminals 5-4 Specifications and Product Data Caution: Do not connect power factor correction capacitors to the brake output terminals. Note: Refer to Section 2 of this manual for TB1 wiring and motor contactor coil connection information. Power wiring between motor controller and motor conduit box. Refer to local codes and NEC for required wire sizing and wire practice. Power wiring between brake and motor controller or between brake and motor conduit box. Refer to the Torque and Wire Specifications table in this manual for load wire sizing. Zero Speed sensing and low voltage sensing input conductor. When motor is located more than 50 feet from brake and zero speed sensing is used to stop braking action, use #14 AWG or larger wire for this connection. If it does not violate local electrical code, run this control wire in a separate conduit from T1 and T2 DC Brake power wires. MN802 Control Wiring Diagrams Continued Size 135A - 600A Multipurpose Brake 3 2 R2 R1 Line Input 7 L2 L1 1 J6 12 345 6 R2 4 MAG1 MAG2 TIME 6 R2 8 1 R2 5 Relay R2 Terminals 2 R2 7 2 3 4 5 6 7 8 9 10 J7 BC 1 L2 L3 CB BC S1 Brake P1 Control P3 Board P2 TB1 Common Start Stop Emergency Stop Jog Brake Release CS J2 J1 J4 KS BPC RS J3 J8 3 1 MOV GK CS CS SCR M M RS RS OL OL AA MOV Diode Motor Interlock KD 115VAC Input J5 TB2 R1 L1 F3 X2 3 115VAC CPT H1-460V H2-230V T2 T3 Motor F1 H3-208V X1 T1 F2 Note: Connect F1 to H1 for 460VAC operation or remove the wire from H1 and connect it to H2 for 230VAC or to H3 for 208VAC operation. LEGEND AAAnode (Diode & SCR) BCBrake Contactor Caution: Do not connect power factor correction BCBBrake Control Board BCPBrake Power Cell capacitors to the brake output terminals. CBMotor Circuit Breaker CPTControl Power Transformer Note: Refer to Section 2 of this manual for TB1 wiring and CSSnubber Capacitor motor contactor coil connection information. F1,2Transformer Primary Fuses F3Transformer Secondary Fuse GKGate (SCR) KDDiode Cathode Power wiring between motor controller and motor conduit box. KSSCR Cathode Refer to local codes and NEC for required wire sizing and wire practice. L1,2AC Power Input MMotor Contactor Power wiring between brake and motor controller or between brake and MOVMetal Oxide Varistor motor conduit box. Refer to the Torque and Wire Specifications table in OLMotor Overload this manual for load wire sizing. P1, P2, P3- Potentiometer Zero Speed sensing and low voltage sensing input conductor. When motor R1Brake Contactor Relay is located more than 50 feet from brake and zero speed sensing is used to R2Motor Interlock Relay RSSnubber Resistor stop braking action, use #14 AWG or larger wire for this connection. If it S1Switch does not violate local electrical code, run this control wire in a separate SCRBrake SCR/Diode Assembly conduit from T1 and T2 DC Brake power wires. T1,2,3- Motor Leads TB1Brake Control Terminals TB2Brake Output Terminals MN802 Specifications and Product Data 5-5 Torque and Wire Specifications Ampere Rating 16 30 55 80 135 160 250 420 600 TB1 Torque Lb-in Nm 9 1 9 1 9 1 9 1 9 1 9 1 9 1 9 1 9 1 Line Wire Size AWG mm2 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 12-22 3.31-0.326 Torque Lb-in Nm Refer to tightening torque specified on terminal label. Load Wire Size AWG mm2 10 5.26 6 13.3 4 21.3 3 26.7 3/0 85.0 3/0 85.0 350MCM 177 (2) 300MCM (2) 152 (2) 300MCM (2) 152 Torque Lb-in Nm Refer to tightening torque specified on terminal label. Wire Size AWG mm2 10 5.26 6 13.3 4 21.3 3 26.7 3/0 85.0 3/0 85.0 350MCM 177 (2) 300MCM (2) 152 (2) 300MCM (2) 152 Mounting Dimensions Ampere Rating 16 30 55 80 135 160 250 420 600 H 14.75 14.75 14.75 14.75 21.0 21.0 21.0 33.0 33.0 Panel / Open D a 5.0 14.25 5.0 14.25 6.0 14.25 6.0 14.25 8.0 19.24 8.0 19.24 8.0 19.24 9.75 31.24 9.75 31.24 W 12.88 12.88 12.88 12.88 21.0 21.0 21.0 33.0 33.0 b 12.26 12.26 12.26 12.26 19.24 19.24 19.24 31.24 31.24 dia. 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.50 0.50 H 16.0 16.0 16.0 16.0 24.0 24.0 24.0 36.0 36.0 W 14.0 14.0 14.0 14.0 24.0 24.0 24.0 36.0 36.0 Panel / Open D b 12.0 12.0 12.0 12.0 18.0 18.0 18.0 30.0 30.0 dia. 0.31 .031 0.31 0.31 0.44 0.44 0.44 0.44 0.44 NEMA 12 Enclosure b H NEMA 12 D a 6.3 16.75 6.3 16.75 6.3 16.75 6.3 16.75 10.0 25.24 10.0 25.24 10.0 25.24 12.0 37.24 12.0 37.24 D a b H a dia. dia. W 5-6 Specifications and Product Data W MN802 Dimensions / Panel Layout Size 16A to 30A 12.88 12.26 Depth = 5″ CPT L1 F1 0.25″ Holes L2 F2 BC 14.75 F3 J1 BCB J2 SCR J8 J3 GK BALDOR ELECTRIC 14.25 J5 KD KS AA TB2 J4 J7 J6 T1 T2 T3 GND Legend: AA BC BCB BPC CPT F1,2,3 GK GND KD KS L1,2 R1 R2 SCR T1,2,3 TB2 MN802 Anode (Diode & SCR) Brake Contactor Brake Control Board Brake Power Cell Control Power Transformer Fuses F1, F2 F3 Gate (SCR) Earth (Ground) Cathode (Diode) Cathode (SCR) AC Power lines Brake Contactor Relay Motor Interlock Relay Silicon Controlled Rectifier Motor Leads Terminal Strip for motor leads Specifications and Product Data 5-7 Dimensions / Panel Layout Continued Size 55A and 80A 12.88 12.26 Depth = 6″ GND 0.25″ Holes TB2 CPT T1 T2 T3 L1 L2 F1 F2 14.75 BC 14.25 F3 SCR GK KD KS AA J4 J7 J6 J8 J3 J2 J5 J1 BCB BALDOR ELECTRIC Legend: AA BC BCB BPC CPT F1,2,3 GK GND KD KS L1,2 R1 R2 SCR T1,2,3 TB2 Anode (Diode & SCR) Brake Contactor Brake Control Board Brake Power Cell Control Power Transformer Fuses F1, F2 F3 Gate (SCR) Earth (Ground) Cathode (Diode) Cathode (SCR) AC Power lines Brake Contactor Relay Motor Interlock Relay Silicon Controlled Rectifier Motor Leads Terminal Strip for motor leads 5-8 Specifications and Product Data MN802 Dimensions / Panel Layout Continued Size 135A and 250A 21 19.24 BPC KS 0.25″ Holes Depth =8″ G GND CS L1 T1 RS T2 L2 T3 KS SCR AA TB2 21 BC Diode 19.24 KD BALDOR J4 J7 J6 J8 J3 CPT J2 J5 J1 BCB R1 BALDOR ELECTRIC R2 F1 F2 F3 Legend: AA BC BCB BPC CPT F1,2,3 G GK GND KD KS L1,2 R1 R2 RS SCR T1,2,3 TB2 MN802 Anode (Diode & SCR) Brake Contactor Brake Control Board Brake Power Cell Control Power Transformer Fuses F1, F2 F3 Gate (SCR) Earth (Ground) Cathode (Diode) Cathode (SCR) AC Power lines Brake Contactor Relay Motor Interlock Relay Snubber Resistor Silicon Controlled Rectifier Motor Leads Terminal Strip for motor leads Specifications and Product Data 5-9 Dimensions / Panel Layout Continued Size 420A and 600A 33.00 31.24 GND Depth =9.75″ 0.50″ Holes BPC A B L1 T2 L2 T3 SCR T1 TB2 33.00 S BC SCR 31.24 T GT SA SB GL L CS RS R1 R2 CPT BALDOR ELECTRIC J4 J7 J6 J8 J3 J2 J5 J1 BCB F1 F2 F3 Legend: AA BC BCB BPC CPT F1,2,3 G GK GND KD KS L1,2 R1 R2 RS SCR T1,2,3 TB2 Anode (Diode & SCR) Brake Contactor Brake Control Board Brake Power Cell Control Power Transformer Fuses F1, F2 F3 Gate (SCR) Earth (Ground) Cathode (Diode) Cathode (SCR) AC Power lines Brake Contactor Relay Motor Interlock Relay Snubber Resistor Silicon Controlled Rectifier Motor Leads Terminal Strip for motor leads 5-10 Specifications and Product Data MN802 BALDOR ELECTRIC COMPANY P.O. Box 2400 Ft. Smith, AR 72902–2400 (479) 646–4711 Fax (479) 648–5792 Baldor Electric Company MN802 Printed in USA 7/02 C&J 1000